Depending on the format type, different record fields are used for output and input. The variable x stands for the written or read value.

DOUBLE format (e.g. %f):
Output: x=(VAL-AOFF)/ASLO
Input: VAL=(x*ASLO+AOFF)*(1.0-SMOO)+VAL*SMOO
In both cases, if ASLO==0.0, it is treated as 1.0. Default values are ASLO=1.0, AOFF=0.0, SMOO=0.0.
If input is successful, UDF is cleared.
LONG format (e.g. %i):
Output: x=RVAL
Input: RVAL=x
Note that the record calculates VAL=(((RVAL+ROFF)*ASLO+AOFF)*ESLO+EOFF)*(1.0-SMOO)+VAL*SMOO if LINR=="LINEAR". ESLO and EOFF might be set in the record definition. StreamDevice does not set it. For example, EOFF=-10 and ESLO=0.000305180437934 (=20.0/0xFFFF) maps 0x0000 to -10.0, 0x7FFF to 0.0 and 0xFFFF to 10.0. Using unsigned formats with values ≥ 0x800000 gives different results on 64 bit machines.
ENUM format (e.g. %{):
Not allowed.
STRING format (e.g. %s):
Not allowed.

Initialization

During initialization, the @init handler is executed, if present. In contrast to normal operation, in DOUBLE input SMOO is ignored (treated as 0.0).


aai aao ao bi bo mbbi mbbo mbbiDirect mbboDirect longin longout stringin stringout waveform calcout scalcout