# SIS38XX.template
# Mark Rivers
# April 29, 2011

record(bi,"$(P)SNL_Connected") {
  field(ZNAM, "Not connected")
  field(ZSV,  "MAJOR")
  field(ONAM, "Connected")
  field(OSV,  "NO_ALARM")
}

record(bo,"$(P)EraseAll") {
  field(DTYP, "asynInt32")
  field(OUT,  "@asyn($(PORT),0)MCA_ERASE")
  field(ZNAM, "Done")
  field(ONAM, "Erase")
  field(VAL,  "1")
  field(FLNK, "$(P)ReadAllOnce")
}

record(bo,"$(P)EraseStart") {
  field(DTYP, "asynInt32")
  field(OUT,  "@asyn($(PORT),0)MCA_ERASE")
  field(ZNAM, "Done")
  field(ONAM, "Erase")
  field(VAL,  "1")
  field(FLNK, "$(P)StartAll.PROC")
}

record(bo,"$(P)StartAll") {
  field(DTYP, "asynInt32")
  field(OUT,  "@asyn($(PORT),0)MCA_START_ACQUIRE")
  field(ZNAM, "Done")
  field(ONAM, "Start")
  field(VAL,  "1")
  field(FLNK, "$(P)SetAcquiring.PROC")
}

record(bo,"$(P)SetAcquiring") {
  field(OUT,  "$(P)Acquiring PP MS")
  field(ZNAM, "Done")
  field(ONAM, "Set")
  field(VAL,  "1")
  field(FLNK, "$(P)SetClientWait.PROC")
}

record(busy,"$(P)Acquiring") {
  field(ZNAM, "Done")
  field(ONAM, "Acquiring")
}

record(bo,"$(P)StopAll") {
  field(DTYP, "asynInt32")
  field(OUT,  "@asyn($(PORT),0)MCA_STOP_ACQUIRE")
  field(ZNAM, "Done")
  field(ONAM, "Stop")
  field(VAL,  "1")
}

record(ao,"$(P)PresetReal") {
  field(PINI, "YES")
  field(DTYP, "asynFloat64")
  field(OUT,  "@asyn($(PORT),0)MCA_PRESET_REAL")
  field(VAL,  "0.0")
  field(PREC, "2")
}

record(bi,"$(P)HardwareAcquiring") {
  field(DTYP, "asynInt32")
  field(INP,  "@asyn($(PORT),0)MCA_ACQUIRING")
  field(ZNAM, "Done")
  field(ONAM, "Acquiring")
  field(SCAN, "I/O Intr")
}

record(ai,"$(P)ElapsedReal") {
  field(DTYP, "asynFloat64")
  field(INP,  "@asyn($(PORT),0)MCA_ELAPSED_REAL")
  field(PREC, "2")
  field(SCAN, "I/O Intr")
}

record(bo,"$(P)ReadAll") {
  field(SCAN, "1 second")
  field(DISV, "0")
  field(SDIS, "$(P)Acquiring NPP NMS")
  field(ZNAM, "Done")
  field(ONAM, "Read")
  field(FLNK, "$(P)ReadAllOnce")
}

record(bo,"$(P)ReadAllOnce") {
  field(VAL,  "1")
  field(OUT,  "$(P)DoReadAll.VAL PP MS")
}

record(bo,"$(P)DoReadAll") {
  field(ZNAM, "Done")
  field(ONAM, "Read")
}

record(longout,"$(P)NuseAll") {
  field(PINI, "YES")
  field(DTYP, "asynInt32")
  field(OUT,  "@asyn($(PORT),0)MCA_NUM_CHANNELS")
}

record(longin,"$(P)CurrentChannel") {
  field(DTYP, "asynInt32")
  field(INP,  "@asyn($(PORT),0)SIS38XX_CURRENT_CHANNEL")
  field(SCAN, "I/O Intr")
}

record(ao,"$(P)Dwell") {
  field(PINI, "YES")
  field(DTYP, "asynFloat64")
  field(OUT,  "@asyn($(PORT),0)MCA_DWELL_TIME")
  field(VAL,  "0.1")
  field(PREC, "3")
}

record(ao,"$(P)PresetReal") {
  field(PINI, "YES")
  field(DTYP, "asynFloat64")
  field(OUT,  "@asyn($(PORT),0)MCA_PRESET_REAL")
  field(VAL,  "0")
  field(PREC, "3")
}

record(bo,"$(P)ChannelAdvance") {
  field(PINI, "YES")
  field(DTYP, "asynInt32")
  field(OUT,  "@asyn($(PORT),0)MCA_CH_ADV_SOURCE")
  field(ZNAM, "Internal")
  field(ONAM, "External")
}

record(bo,"$(P)InitialChannelAdvance") {
  field(PINI, "YES")
  field(DTYP, "asynInt32")
  field(OUT,  "@asyn($(PORT),0)SIS38XX_INITIAL_CHANNEL_ADVANCE")
  field(ZNAM, "No")
  field(ONAM, "Yes")
}

record(bo,"$(P)SoftwareChannelAdvance") {
  field(DTYP, "asynInt32")
  field(OUT,  "@asyn($(PORT),0)SIS38XX_SOFTWARE_CHANNEL_ADVANCE")
  field(ZNAM, "No")
  field(ONAM, "Yes")
  field(VAL,  "1")
}

# Binary record to enable switching input 1
# between internal 25 MHz (SIS3801) or 50MHz (SIS3820) reference clock and
# and external source 
record(bo, "$(P)Channel1Source") {
  field(PINI, "YES")
  field(DTYP, "asynInt32")
  field(OUT,  "@asyn($(PORT) 0)SIS38XX_CHANNEL1_SOURCE")
  field(ZNAM, "Int. clock")
  field(ONAM, "External")
}

record(longout,"$(P)Prescale") {
  field(PINI, "YES")
  field(DTYP, "asynInt32")
  field(OUT,  "@asyn($(PORT),0)MCA_PRESCALE")
  field(VAL,  "1")
}

record(bo,"$(P)EnableClientWait") {
  field(PINI, "YES")
  field(ZNAM, "Disable")
  field(ONAM, "Enable")
}

record(bo,"$(P)SetClientWait") {
  field(DISV, "0")
  field(SDIS, "$(P)EnableClientWait NPP NMS")
  field(OMSL, "closed_loop")
  field(DOL,  "1")
  field(OUT,  "$(P)ClientWait PP MS")
  field(ONAM, "SetClientWait")
  field(ZNAM, "Done")
}

record(busy,"$(P)ClientWait") {
}

#
# This record reflect the current mode of the
# driver.
# Can be either MCA or SCALER (or UNDEFINED).
# Use it to disable the autocount feature of the 
# scaler record when in MCA mode.
record(mbbi, "$(P)AcquireMode") {
  field(DESC, "SIS38XX acquire mode")
  field(DTYP, "asynInt32")
  field(INP,  "@asyn($(PORT) 0)SIS38XX_ACQUIRE_MODE")
  field(ZRVL, "0")
  field(ONVL, "1")
  field(ZRST, "MCS")
  field(ONST, "Scaler")
  field(SCAN, "I/O Intr")
  field(FLNK, "$(P)DisableAutoCount.PROC CA MS")
}

record(calcout, "$(P)DisableAutoCount") {
  field(CALC, "A==1?0:1")
  field(INPA, "$(P)Mode")
  field(OUT,  "$(SCALER).CONT")
  field(OOPT, "Transition To Zero")
}

# MUXOUT analogue record to enable switching
# of the multiplexed output on output 7.
record(ao, "$(P)MUXOutput") {
  field(DTYP, "asynInt32")
  field(OUT,  "@asyn($(PORT) 0)SIS38XX_MUX_OUT")
  field(HOPR, "32")
  field(LOPR, "0")
  field(VAL,  "3")
  field(DESC, "Route to output 7")
}


# Toggle the USER LED which also toggles the
# control output signal 8.
record(bo, "$(P)UserLED") {
  field(DESC, "Flash user LED")
  field(DTYP, "asynInt32")
  field(SCAN, "Passive")
  field(OUT,  "@asyn($(PORT) 0)SIS38XX_LED")
  field(ZNAM, "Low/Off")
  field(ONAM, "High/On")
}

record(mbbo, "$(P)InputMode") {
  field(PINI, "YES")
  field(DESC, "SIS38XX input mode")
  field(DTYP, "asynInt32")
  field(OUT,  "@asyn($(PORT) 0)SIS38XX_INPUT_MODE")
  field(ZRVL, "0")
  field(ONVL, "1")
  field(TWVL, "2")
  field(THVL, "3")
  field(FRVL, "4")
  field(FVVL, "5")
  field(SXVL, "6")
  field(ZRST, "Mode 0")
  field(ONST, "Mode 1")
  field(TWST, "Mode 2")
  field(THST, "Mode 3")
  field(FRST, "Mode 4")
  field(FVST, "Mode 5")
  field(SXST, "Mode 6")
  field(VAL,  "3")
}

record(mbbo, "$(P)OutputMode") {
  field(PINI, "YES")
  field(DESC, "SIS38XX output mode")
  field(DTYP, "asynInt32")
  field(OUT,  "@asyn($(PORT) 0)SIS38XX_OUTPUT_MODE")
  field(ZRVL, "0")
  field(ONVL, "1")
  field(TWVL, "2")
  field(THVL, "3")
  field(ZRST, "Mode 0")
  field(ONST, "Mode 1")
  field(TWST, "Mode 2")
  field(THST, "Mode 3")
  field(VAL,  "3")
}

record(bo, "$(P)OutputPolarity") {
  field(PINI, "YES")
  field(DESC, "SIS38XX output polarity")
  field(DTYP, "asynInt32")
  field(OUT,  "@asyn($(PORT) 0)SIS38XX_OUTPUT_POLARITY")
  field(ZNAM, "Normal")
  field(ONAM, "Inverted")
}

record(mbbi, "$(P)Model") {
  field(PINI, "YES")
  field(DESC, "SIS38XX model")
  field(DTYP, "asynInt32")
  field(INP,  "@asyn($(PORT) 0)SIS38XX_MODEL")
  field(ZRVL, "0")
  field(ONVL, "1")
  field(ZRST, "SIS3801")
  field(ONST, "SIS3820")
}

record(longin,"$(P)Firmware") {
  field(PINI, "YES")
  field(DTYP, "asynInt32")
  field(INP,  "@asyn($(PORT),0)SIS38XX_FIRMWARE")
}

record(longin,"$(P)MaxChannels") {
  field(PINI, "YES")
  field(DTYP, "asynInt32")
  field(INP,  "@asyn($(PORT),0)SIS38XX_MAX_CHANNELS")
}



# asyn record for debugging
record(asyn, "$(P)Asyn") {
  field(PORT, "$(PORT)")
}