#! Generated by VisualDCT v2.6 #! DBDSTART #! DBDEND # # vitaraFreqSearch.template # # Required macros: #DEV - PV prefix for all vitara PV's #FREQ_MOTOR- Motor PV name #FREQ- Freq counter PV name # These first records provide a local PV with a common # prefix to make it easier to share screens and db templates record(ao, "$(DEV):FREQ_CUR") { field(DESC, "Current Vitara Freq") field(DOL, "$(FREQ) CP MS") field(OMSL, "closed_loop") field(EGU, "Hz") field(PREC, "0") field(FLNK, "$(DEV):FREQ_ERR") info(autosaveFields, "DESC EGU HHSV HIGH HIHI HSV LLSV LOLO LOW LSV PREC") } record(ai, "$(DEV):FREQ_MOTOR_POS") { field(DESC, "Cur Freq motor pos") field(INP, "$(FREQ_MOTOR).RBV CP MS") field(EGU, "mm") field(PREC, "6") info(autosaveFields, "DESC EGU HHSV HIGH HIHI HSV LLSV LOLO LOW LSV PREC") } # Frequence target set point record(ao, "$(DEV):FREQ_SP") { field(DESC, "Freq target set point") field(VAL, "67999964") field(EGU, "Hz") field(PREC, "0") field(PINI, "YES") info(autosaveFields, "VAL HHSV HIGH HIHI HSV LLSV LOLO LOW LSV PREC") } record(calc, "$(DEV):FREQ_ERR") { field(DESC, "Freq Err in Hz") field(CALC, "A-B") field(INPA, "$(DEV):FREQ_CUR NPP NMS") field(INPB, "$(DEV):FREQ_SP CP") field(EGU, "Hz") field(PREC, "3") field(FLNK, "$(DEV):FREQ_ERR_SMOOTHED PP MS") info(autosaveFields, "DESC EGU HHSV HIGH HIHI HSV LLSV LOLO LOW LSV PREC") } # # Keep FREQ_ERR Limits consistent w/ search and lock criteria # # Propagate FREQ_ERR.HIHI # to FREQ_ERR_RMS.HIHI, FREQ_ERR.LOLO, and FREQ_ERR_RMS.LOLO record( dfanout, "$(DEV):FREQ_ERR_UPDATE_HIHI" ) { field( OMSL, "closed_loop" ) field( DOL, "$(DEV):FREQ_ERR.HIHI CPP NMS" ) field( OUTA, "$(DEV):FREQ_ERR_RMS.HIHI NPP NMS" ) field( FLNK, "$(DEV):FREQ_ERR_CALC_LOLO" ) } record( calc, "$(DEV):FREQ_ERR_CALC_LOLO" ) { field( INPA, "$(DEV):FREQ_ERR.HIHI NPP NMS" ) field( CALC, "-A" ) field( FLNK, "$(DEV):FREQ_ERR_UPDATE_LOLO" ) info(autosaveFields, "DESC EGU HHSV HIGH HIHI HSV LLSV LOLO LOW LSV PREC") } record( dfanout, "$(DEV):FREQ_ERR_UPDATE_LOLO" ) { field( OMSL, "closed_loop" ) field( DOL, "$(DEV):FREQ_ERR_CALC_LOLO" ) field( OUTA, "$(DEV):FREQ_ERR.LOLO NPP NMS" ) field( OUTB, "$(DEV):FREQ_ERR_RMS.LOLO NPP NMS" ) } # Propagate FREQ_TOLERANCE # to FREQ_ERR.HIGH, FREQ_ERR_RMS.HIGH, FREQ_ERR.LOW, and FREQ_ERR_RMS.LOW record( dfanout, "$(DEV):FREQ_ERR_UPDATE_HIGH" ) { field( OMSL, "closed_loop" ) field( DOL, "$(DEV):FREQ_TOLERANCE CPP NMS" ) field( OUTA, "$(DEV):FREQ_ERR.HIGH NPP NMS" ) field( OUTB, "$(DEV):FREQ_ERR_RMS.HIGH NPP NMS" ) } record( calc, "$(DEV):FREQ_ERR_CALC_LOW" ) { field( INPA, "$(DEV):FREQ_TOLERANCE CPP NMS" ) field( CALC, "-A" ) field( FLNK, "$(DEV):FREQ_ERR_UPDATE_LOW" ) info(autosaveFields, "DESC EGU HHSV HIGH HIHI HSV LLSV LOLO LOW LSV PREC") } record( dfanout, "$(DEV):FREQ_ERR_UPDATE_LOW" ) { field( OMSL, "closed_loop" ) field( DOL, "$(DEV):FREQ_ERR_CALC_LOW" ) field( OUTA, "$(DEV):FREQ_ERR.LOW NPP NMS" ) field( OUTB, "$(DEV):FREQ_ERR_RMS.LOW NPP NMS" ) field( FLNK, "$(DEV):FREQ_ERR_UPDATE_HIGH" ) } # SMOO field updated by $(DEV):FREQ_ERR_SMOOTH record(ai, "$(DEV):FREQ_ERR_SMOOTHED") { field(DESC, "Freq Err in Hz") field(SMOO, "0.5") field(INP, "$(DEV):FREQ_ERR") field(EGU, "Hz") field(PREC, "3") field(FLNK, "$(DEV):FREQ_MOTOR_TGT PP NMS") info(autosaveFields, "DESC EGU HHSV HIGH HIHI HSV LLSV LOLO LOW LSV PREC") } record(ao, "$(DEV):FREQ_ERR_SMOOTH") { field(DESC, "IIR filter smooth factor") field(VAL, "0.5") field(OUT, "$(DEV):FREQ_ERR_SMOOTHED.SMOO") field(PINI, "YES") field(PREC, "4") info(autosaveFields, "VAL HHSV HIGH HIHI HSV LLSV LOLO LOW LSV PREC") } # Calibrate for each system,do not merge or copy VAL. record(ao, "$(DEV):FREQ_ERR_CORRECTION") { field(DESC, "Freq err corr factor") field(VAL, "149800") field(PINI, "YES") field(PREC, "0") info(autosaveFields, "VAL HHSV HIGH HIHI HSV LLSV LOLO LOW LSV PREC") } record(calcout, "$(DEV):FREQ_MOTOR_TGT") { field(DESC, "Calc chamber motor target") field(CALC, "C - A/B") field(INPA, "$(DEV):FREQ_ERR_SMOOTHED NPP NMS") field(INPB, "$(DEV):FREQ_ERR_CORRECTION NPP NMS") field(INPC, "$(DEV):FREQ_MOTOR_POS CA MS") field(EGU, "mm") field(PREC, "5") info(autosaveFields, "HHSV HIGH HIHI HSV LLSV LOLO LOW LSV PREC") } # Only process this PV when you want to move the motor # to $(DEV):FREQ_MOTOR_TGT record(ao, "$(DEV):FREQ_MOTOR_POS_GOTO") { field(DESC, "Go to calc motor pos") field(OMSL, "closed_loop") field(DOL, "$(DEV):FREQ_MOTOR_TGT NPP MS") field(OUT, "$(FREQ_MOTOR).VAL PP") field(EGU, "mm") field(FLNK, "$(DEV):FREQ_RETRY_COUNTER PP NMS") info(autosaveFields, "VAL HHSV HIGH HIHI HSV LLSV LOLO LOW LSV PREC") } record(bo, "$(DEV):FREQ_SEARCH_IN_TOL") { field(DESC, "Freq search in tol") field(ZNAM, "Not OK") field(ZSV, "MINOR") field(ONAM, "OK") field(OSV, "NO_ALARM") # info(autosaveFields, "intentionally blank") } record( mbbo, "$(DEV):FREQ_SEARCH_STATE" ) { field( DESC, "Freq search state" ) field( VAL, "1" ) field( ZRVL, "0" ) field( ZRST, "Searching" ) field( ZRSV, "MINOR") field( ONVL, "1" ) field( ONST, "Idle" ) field( TWVL, "2" ) field( TWST, "Found" ) field( THVL, "3" ) field( THST, "Failed" ) field( THSV, "MAJOR" ) field( PINI, "YES" ) field( FLNK, "$(DEV):FREQ_SEARCH_ACTIVE" ) # info(autosaveFields, "intentionally blank") } record( calc, "$(DEV):FREQ_SEARCH_ACTIVE" ) { field(DESC, "Freq search in progress") field( INPA, "$(DEV):FREQ_SEARCH_STATE NPP MS" ) field( CALC, "0=A" ) # info(autosaveFields, "intentionally blank") } record( seq, "$(DEV):FREQ_SEARCH_START" ) { field(DESC, "Start frequency search") field(DOL1, "0") field(LNK1, "$(DEV):FREQ_RETRY_COUNTER PP") field(DLY2, "0.5") field( DOL2, "0" ) field( LNK2, "$(DEV):FREQ_SEARCH_STATE PP" ) # field( DOL2, "1" ) # field( LNK2, "$(DEV):FREQ_SEARCH_ACTIVE PP" ) } record( seq, "$(DEV):FREQ_SEARCH_STOP" ) { field( DESC, "Stop frequency search" ) field( DOL1, "1" ) field( LNK1, "$(DEV):FREQ_SEARCH_STATE PP" ) field( DOL2, "0" ) field( LNK2, "$(DEV):FREQ_RETRY_COUNTER PP" ) } record( calcout, "$(DEV):FREQ_DO_RETRY" ) { field(DESC, "Retry if not at freq") # If motor is done moving, initiate another retry field(INPA, "$(FREQ_MOTOR).DMOV CA") field(CALC, "A==1") field( SCAN, "5 second" ) field(OOPT, "When Non-zero") field(DOPT, "Use OCAL") field(OCAL, "1") field(ODLY, "2.5") field(OUT, "$(DEV):FREQ_MOTOR_POS_GOTO.PROC") # Disabled when FREQ_SEARCH_ACTIVE is 0 field(DISV, "0") field(SDIS, "$(DEV):FREQ_SEARCH_ACTIVE") # info(autosaveFields, "intentionally blank") } # Is the frequency search within tolerance? record(calcout, "$(DEV):FREQ_SEARCH_IN_TOL_CALC") { field(DESC, "Frequency tolerance calc") field(VAL, "0") field(INPA, "$(DEV):FREQ_ERR_SMOOTHED CP MS") field(INPB, "$(DEV):FREQ_TOLERANCE NPP") field(CALC, "abs(A) <= B") field(OUT, "$(DEV):FREQ_SEARCH_IN_TOL PP") field(FLNK, "$(DEV):FREQ_SEARCH_MONITOR PP NMS") # info(autosaveFields, "intentionally blank") } # Monitor the frequency search and shut it down when done record(calcout, "$(DEV):FREQ_SEARCH_MONITOR") { field(DESC, "Monitor frequency search") field( INPA, "$(DEV):FREQ_SEARCH_IN_TOL NPP NMS" ) field( INPC, "$(FREQ_MOTOR).DMOV NPP NMS" ) field( INPD, "$(DEV):FREQ_RETRY_COUNTER NPP NMS" ) field( INPE, "$(DEV):FREQ_RETRY_COUNTER.HIHI NPP NMS" ) field( INPF, "$(DEV):FREQ_ERR_LAST_N_STD NPP NMS" ) field( INPG, "$(DEV):FREQ_ERR_LAST_N_STD.HIHI NPP NMS" ) field( INPH, "$(DEV):FREQ_MOTOR_TGT NPP NMS" ) field( INPI, "$(FREQ_MOTOR).HLM NPP NMS" ) field( INPJ, "$(FREQ_MOTOR).LLM NPP NMS" ) field( CALC, "(A && C) || ((D>=E)||(F>G)||(H>I)||(H=E)||(F>G)||(H>I)||(H