Configuration for the ES3602 2 channel 24-bit ADC module The filter settings of the unit can be configured using the SDO register 0x8000:0x15. The information below was extracted from Beckhoffs .chm file Read filter setting (upload SDO parameter) ========================================== /dls_sw/work/common/rt/ethercat/bin/ethercat -m 0 upload -p 1 --type uint16 0x8000 0x15 Write filter setting (download SDO parameter) ============================================= /dls_sw/work/common/rt/ethercat/bin/ethercat -m 0 download -p 1 --type uing16 0x8000 0x15 the possible settings are 0 ..... 50 Hz 1 ..... 60 Hz 2 ..... 100 Hz 3 ..... 500 Hz 4 ..... 1000 Hz 5 ..... 2000 Hz 6 ..... 3750 Hz 7 ..... 7500 Hz 8 ..... 15000 Hz 9 ..... 30000 Hz 10 .....5 Hz 11 .....10 Hz For example, to set the filter to 5 Hz /dls_sw/work/common/rt/ethercat/bin/ethercat -m 0 download -p 1 --type uing16 0x8000 0x15 0x0a