#LyX 1.5.6 created this file. For more info see http://www.lyx.org/
\lyxformat 276
\begin_document
\begin_header
\textclass article
\begin_preamble
\usepackage{moreverb}
\usepackage{url}

\textwidth=6.5in
\topmargin=0pt
\headheight=0pt
\textheight=8.6truein
\oddsidemargin=0in
\evensidemargin=0in
\footskip=40pt

\parindent=0pt
\parskip=0.5ex
\usepackage{hyperref}
%HEVEA \def{\textbackslash}{$\backslash$} % No \textbackslash in hevea.
\end_preamble
\language english
\inputencoding auto
\font_roman times
\font_sans default
\font_typewriter default
\font_default_family default
\font_sc false
\font_osf false
\font_sf_scale 100
\font_tt_scale 100
\graphics default
\paperfontsize default
\spacing single
\papersize default
\use_geometry false
\use_amsmath 1
\use_esint 0
\cite_engine basic
\use_bibtopic false
\paperorientation portrait
\secnumdepth 3
\tocdepth 2
\paragraph_separation indent
\defskip medskip
\quotes_language english
\papercolumns 1
\papersides 2
\paperpagestyle default
\tracking_changes false
\output_changes false
\author "" 
\author "" 
\end_header

\begin_body

\begin_layout Title
How to create EPICS device support for a simple serial or GPIB device
\end_layout

\begin_layout Author
W.
 Eric Norum
\newline

\begin_inset LatexCommand url
name "norume.aps.anl.gov"
target "mailto:norume@aps.anl.gov"

\end_inset


\end_layout

\begin_layout Section
Introduction
\end_layout

\begin_layout Standard
This tutorial provides step-by-step instructions on how to create EPICS
 support for a simple serial or GPIB (IEEE-488) device.
 The steps are presented in a way that should make it possible to apply
 them in cookbook fashion to create support for other devices.
 For comprehensive description of all the details of the I/O system used
 here, refer to the 
\begin_inset LatexCommand htmlurl
name "asynDriver"
target "../asynDriver.html"

\end_inset

 and 
\begin_inset LatexCommand htmlurl
name "devGpib"
target "../devGpib.html"

\end_inset

 documentation.
\end_layout

\begin_layout Standard
This document isn't for the absolute newcomer though.
 You must have EPICS installed on a system somewhere and know how to build
 and run the example application.
 In particular you must have the following installed: 
\end_layout

\begin_layout Itemize
EPICS R3.14.6 or higher.
\end_layout

\begin_layout Itemize
EPICS modules/soft/asyn version 4.0 or higher.
\end_layout

\begin_layout Standard
Serial and GPIB devices can now be treated in much the same way.
 The EPICS 'asyn' driver devGpib module can use the low-level drivers which
 communicate with serial devices connected to ports on the IOC or to Ethernet/Se
rial converters or with GPIB devices connected to local I/O cards or to
 Ethernet/GPIB converters.
\end_layout

\begin_layout Standard
I based this tutorial on the device support I wrote for a CVI Laser Corporation
 AB300 filter wheel.
 You're almost certainly interested in controlling some other device so
 you won't be able to use the information directly.
 I chose the AB300 as the basis for this tutorial since the AB300 has a
 very limited command set, which keeps this document small, and yet has
 commands which raise many of the issues that you'll have to consider when
 writing support for other devices.
 If you'd like to print this tutorial you can download 
\begin_inset LatexCommand url
name "PDF version"
target "tutorial.pdf"

\end_inset

.
\end_layout

\begin_layout Section
Determine the required I/O operations
\end_layout

\begin_layout Standard
The first order of business is to determine the set of operations the device
 will have to perform.
 A look at the AB300 documentation reveals that there are four commands
 that must be supported.
 Each command will be associated with an EPICS process variable (PV) whose
 type must be appropriate to the data transferred by the command.
 The AB300 commands and process variable record types I choose to associate
 with them are shown in table\InsetSpace ~

\begin_inset LatexCommand ref
reference "commandList"

\end_inset

.
\end_layout

\begin_layout Standard
\begin_inset Float table
wide false
sideways false
status open

\begin_layout Standard
\begin_inset Caption

\begin_layout Standard
AB300 filter wheel commands
\begin_inset LatexCommand label
name "commandList"

\end_inset


\end_layout

\end_inset


\end_layout

\begin_layout Standard
\align center
\begin_inset Tabular
<lyxtabular version="3" rows="6" columns="2">
<features>
<column alignment="left" valignment="top" leftline="true" rightline="true" width="0pt">
<column alignment="left" valignment="top" rightline="true" width="0pt">
<row topline="true" bottomline="true">
<cell multicolumn="1" alignment="left" valignment="top" topline="true" bottomline="true" leftline="true" rightline="true" usebox="none">
\begin_inset Text

\begin_layout Standard
CVI Laser Corporation AB300 filter wheel
\end_layout

\end_inset
</cell>
<cell multicolumn="2" alignment="left" valignment="top" topline="true" bottomline="true" rightline="true" usebox="none">
\begin_inset Text

\begin_layout Standard

\end_layout

\end_inset
</cell>
</row>
<row bottomline="true">
<cell multicolumn="1" alignment="left" valignment="top" bottomline="true" leftline="true" rightline="true" usebox="none">
\begin_inset Text

\begin_layout Standard
Command
\end_layout

\end_inset
</cell>
<cell multicolumn="1" alignment="left" valignment="top" bottomline="true" rightline="true" usebox="none">
\begin_inset Text

\begin_layout Standard
EPICS record type
\end_layout

\end_inset
</cell>
</row>
<row>
<cell alignment="left" valignment="top" leftline="true" rightline="true" usebox="none">
\begin_inset Text

\begin_layout Standard
Reset 
\end_layout

\end_inset
</cell>
<cell alignment="left" valignment="top" rightline="true" usebox="none">
\begin_inset Text

\begin_layout Standard
longout 
\end_layout

\end_inset
</cell>
</row>
<row>
<cell alignment="left" valignment="top" leftline="true" rightline="true" usebox="none">
\begin_inset Text

\begin_layout Standard
Go to new position 
\end_layout

\end_inset
</cell>
<cell alignment="left" valignment="top" rightline="true" usebox="none">
\begin_inset Text

\begin_layout Standard
longout 
\end_layout

\end_inset
</cell>
</row>
<row>
<cell alignment="left" valignment="top" leftline="true" rightline="true" usebox="none">
\begin_inset Text

\begin_layout Standard
Query position 
\end_layout

\end_inset
</cell>
<cell alignment="left" valignment="top" rightline="true" usebox="none">
\begin_inset Text

\begin_layout Standard
longin 
\end_layout

\end_inset
</cell>
</row>
<row bottomline="true">
<cell alignment="left" valignment="top" bottomline="true" leftline="true" rightline="true" usebox="none">
\begin_inset Text

\begin_layout Standard
Query status 
\end_layout

\end_inset
</cell>
<cell alignment="left" valignment="top" bottomline="true" rightline="true" usebox="none">
\begin_inset Text

\begin_layout Standard
longin  
\end_layout

\end_inset
</cell>
</row>
</lyxtabular>

\end_inset


\end_layout

\end_inset


\end_layout

\begin_layout Standard
There are lots of other ways that the AB300 could be handled.
 It might be useful, for example, to treat the filter position as multi-bit
 binary records instead.
\end_layout

\begin_layout Section
Create a new device support module
\end_layout

\begin_layout Standard
Now that the device operations and EPICS process variable types have been
 chosen it's time to create a new EPICS application to provide a place to
 perform subsequent software development.
 The easiest way to do this is with the makeSupport.pl script supplied with
 the EPICS ASYN package.
\end_layout

\begin_layout Standard
Here are the commands I ran.
 You'll have to change the 
\family typewriter
/home/EPICS/modules/soft/asyn
\family default
 to the path where your EPICS ASYN driver is installed.
\end_layout

\begin_layout LyX-Code
norume> 
\family roman
\series bold
mkdir ab300
\family default
\series default

\newline
norume> 
\family roman
\series bold
cd ab300
\family default
\series default

\newline
norume> 
\family roman
\series bold
/home/EPICS/modules/soft/asyn/bin/linux-x86/makeSupport.pl -t devGpib AB300
\end_layout

\begin_layout Subsection
Make some changes to the files in configure/
\end_layout

\begin_layout Standard
Edit the 
\family typewriter
configure/RELEASE
\family default
 file which makeSupport.pl created and confirm that the entries describing
 the paths to your EPICS base and ASYN support are correct.
 For example these might be:
\end_layout

\begin_layout LyX-Code
ASYN=/home/EPICS/modules/soft/asyn
\end_layout

\begin_layout LyX-Code
EPICS_BASE=/home/EPICS/base
\end_layout

\begin_layout Standard
Edit the 
\family typewriter
configure/CONFIG
\family default
 file which makeSupport.pl created and specify the IOC architectures on which
 the application is to run.
 I wanted the application to run as a soft IOC, so I uncommented the 
\family typewriter
CROSS_COMPILER_TARGET_ARCHS
\family default
 definition and set the definition to be empty: 
\end_layout

\begin_layout LyX-Code
CROSS_COMPILER_TARGET_ARCHS =
\end_layout

\begin_layout Subsection
Create the device support file
\end_layout

\begin_layout Standard
The contents of the device support file provide all the details of the communica
tion between the device and EPICS.
 The makeSupport.pl command created a skeleton device support file in 
\family typewriter
AB300Sup/devAB300.c
\family default
.
 Of course, device support for a device similar to the one you're working
 with provides an even easier starting point.
\end_layout

\begin_layout Standard
The remainder this section describes the changes that I made to the skeleton
 file in order to support the AB300 filter wheel.
 You'll have to modify the steps as appropriate for your device.
\end_layout

\begin_layout Subsubsection
Declare the DSET tables provided by the device support
\end_layout

\begin_layout Standard
Since the AB300 provides only longin and longout records most of the 
\family typewriter
DSET_
\family default
\shape italic
xxx
\shape default
 define statements can be removed.
 Because of the way that the device initialization is performed you must
 define an analog-in DSET even if the device provides no analog-in records
 (as is the case for the AB300).
\end_layout

\begin_layout LyX-Code
#define DSET_AI    devAiAB300
\newline
#define DSET_LI    devLiAB300
\newline
#define DSET_LO
    devLoAB300
\end_layout

\begin_layout Subsubsection
Select timeout values
\end_layout

\begin_layout Standard
The default value of 
\family typewriter
TIMEWINDOW
\family default
 (2 seconds) is reasonable for the AB300, but I increased the value of 
\family typewriter
TIMEOUT
\family default
 to 5\InsetSpace ~
seconds since the filter wheel can be slow in responding.
\end_layout

\begin_layout LyX-Code
#define TIMEOUT     5.0    /* I/O must complete within this time */
\newline
#define
 TIMEWINDOW  2.0    /* Wait this long after device timeout */
\end_layout

\begin_layout Subsubsection
Clean up some unused values
\end_layout

\begin_layout Standard
The skeleton file provides a number of example character string arrays.
 None are needed for the AB300 so I just removed them.
 Not much space would be wasted by just leaving them in place however.
\end_layout

\begin_layout Subsubsection
Declare the command array
\end_layout

\begin_layout Standard
This is the hardest part of the job.
 Here's where you have to figure how to produce the command strings required
 to control the device and how to convert the device responses into EPICS
 process variable values.
\end_layout

\begin_layout Standard
Each command array entry describes the details of a single I/O operation
 type.
 The application database uses the index of the entry in the command array
 to provide the link between the process variable and the I/O operation
 to read or write that value.
\end_layout

\begin_layout Standard
The command array entries I created for the AB300 are shown below.
 The elements of each entry are described using the names from the 
\begin_inset LatexCommand url
name "GPIB documentation"
target "../devGpib.html"

\end_inset

.
 
\end_layout

\begin_layout Paragraph
Command array index 0 -- Device Reset
\end_layout

\begin_layout LyX-Code
{&DSET_LO, GPIBWRITE, IB_Q_LOW, NULL, "
\backslash
377
\backslash
377
\backslash
033", 10, 10,
\newline
       NULL, 0, 0, NULL, NULL, "
\backslash
033"},
\end_layout

\begin_layout Description
dset This command is associated with an longout record.
 
\end_layout

\begin_layout Description
type A WRITE operation is to be performed.
 
\end_layout

\begin_layout Description
pri This operation will be placed on the low-priority queue of I/O requests.
 
\end_layout

\begin_layout Description
cmd Because this is a GPIBWRITE operation this element is unused.
 
\end_layout

\begin_layout Description
format The format string to generate the command to be sent to the device.
 The first two bytes are the RESET command, the third byte is the ECHO command.
 The AB300 sends no response to a reset command so I send the 'ECHO' to
 verify that the device is responding.
 The AB300 resets itself fast enough that it can see an echo command immediately
 following the reset command.
\end_layout

\begin_deeper
\begin_layout Standard
Note that the process variable value is not used (there's no printf 
\family typewriter
%
\family default
 format character in the command string).
 The AB300 is reset whenever the EPICS record is processed.
 
\end_layout

\end_deeper
\begin_layout Description
rspLen The size of the readback buffer.
 Although only one readback byte is expected I allow for a few extra bytes
 just in case.
 
\end_layout

\begin_layout Description
msgLen The size of the buffer into which the command string is placed.
 I allowed a little extra space in case a longer command is used some day.
 
\end_layout

\begin_layout Description
convert No special conversion function is needed.
 
\end_layout

\begin_layout Description
P1,P2,P3 There's no special conversion function so no arguments are needed.
 
\end_layout

\begin_layout Description
pdevGpibNames There's no name table.
 
\end_layout

\begin_layout Description
eos The end-of-string value used to mark the end of the readback operation.
 GPIB devices can usually leave this entry NULL since they use the End-Or-Identi
fy (EOI) line to delimit messages.Serial devices which have the same end-of-strin
g value for all commands couldalso leave these entries NULL and set the
 end-of-string value with theiocsh asynOctetSetInputEos command.
\end_layout

\begin_layout Paragraph
Command array index 1 -- Go to new filter position
\end_layout

\begin_layout LyX-Code
{&DSET_LO, GPIBWRITE, IB_Q_LOW, NULL, "
\backslash
017%c", 10, 10,
\newline
        NULL, 0, 0, NULL, NULL, "
\backslash
030"},
\end_layout

\begin_layout Description
dset This command is associated with an longout record.
 
\end_layout

\begin_layout Description
type A WRITE operation is to be performed.
 
\end_layout

\begin_layout Description
pri This operation will be placed on the low-priority queue of I/O requests.
 
\end_layout

\begin_layout Description
cmd Because this is a GPIBWRITE operation this element is unused.
 
\end_layout

\begin_layout Description
format The format string to generate the command to be sent to the device.
 The filter position (1-6) can be converted to the required command byte
 with the printf 
\family typewriter
%c
\family default
 format.
 
\end_layout

\begin_layout Description
rspLen The size of the readback buffer.
 Although only two readback bytes are expected I allow for a few extra bytes
 just in case.
 
\end_layout

\begin_layout Description
msgLen The size of the buffer into which the command string is placed.
 I allowed a little extra space in case a longer command is used some day.
 
\end_layout

\begin_layout Description
convert No special conversion function is needed.
 
\end_layout

\begin_layout Description
P1,P2,P3 There's no special conversion function so no arguments are needed.
 
\end_layout

\begin_layout Description
pdevGpibNames There's no name table.
 
\end_layout

\begin_layout Description
eos The end-of-string value used to mark the end of the readback operation.
 
\end_layout

\begin_layout Paragraph
Command array index 2 -- Query filter position
\end_layout

\begin_layout LyX-Code
{&DSET_LI, GPIBREAD, IB_Q_LOW, "
\backslash
035", NULL, 0, 10,
\newline
        convertPositionReply, 0, 0, NULL, NULL, "
\backslash
030"},
\end_layout

\begin_layout Description
dset This command is associated with an longin record.
 
\end_layout

\begin_layout Description
type A READ operation is to be performed.
 
\end_layout

\begin_layout Description
pri This operation will be placed on the low-priority queue of I/O requests.
 
\end_layout

\begin_layout Description
cmd The command string to be sent to the device.
 The AB300 responds to this command by sending back three bytes: the current
 position, the controller status, and a terminating 
\family typewriter
'
\backslash
030'
\family default
.
 
\end_layout

\begin_layout Description
format Because this operation has its own conversion function this element
 is unused.
 
\end_layout

\begin_layout Description
rspLen There is no command echo to be read.
 
\end_layout

\begin_layout Description
msgLen The size of the buffer into which the reply string is placed.
 Although only three reply bytes are expected I allow for a few extra bytes
 just in case.
\end_layout

\begin_layout Description
convert There's no sscanf format that can convert the reply from the AB300
 so a special conversion function must be provided.
 
\end_layout

\begin_layout Description
P1,P2,P3 The special conversion function requires no arguments.
 
\end_layout

\begin_layout Description
pdevGpibNames There's no name table.
 
\end_layout

\begin_layout Description
eos The end-of-string value used to mark the end of the read operation.
 
\end_layout

\begin_layout Paragraph
Command array index 3 -- Query controller status
\end_layout

\begin_layout Standard
This command array entry is almost identical to the previous entry.
 The only change is that a different custom conversion function is used.
 
\end_layout

\begin_layout LyX-Code
{&DSET_LI, GPIBREAD, IB_Q_LOW, "
\backslash
035", NULL, 0, 10,
\newline
        convertStatusReply, 0, 0, NULL, NULL, "
\backslash
030"},
\end_layout

\begin_layout Subsubsection
Write the special conversion functions
\end_layout

\begin_layout Standard
As mentioned above, special conversion functions are need to convert reply
 messages from the AB300 into EPICS PV values.
 The easiest place to put these functions is just before the 
\family typewriter
gpibCmds
\family default
 table.
 The conversion functions are passed a pointer to the 
\family typewriter
gpibDpvt
\family default
 structure and three values from the command table entry.
 The 
\family typewriter
gpibDpvt
\family default
 structure contains a pointer to the EPICS record.
 The custom conversion function uses this pointer to set the record's value
 field.
\end_layout

\begin_layout Standard
Here are the custom conversion functions I wrote for the AB300.
\end_layout

\begin_layout LyX-Code
/*
\newline
 * Custom conversion routines
\newline
 */
\newline
static int
\newline
convertPositionReply(struct
 gpibDpvt *pdpvt, int P1, int P2, char **P3)
\newline
{
\newline
    struct longinRecord *pli
 = ((struct longinRecord *)(pdpvt->precord));
\newline

\newline
    if (pdpvt->msgInputLen
 != 3) {
\newline
        epicsSnprintf(pdpvt->pasynUser->errorMessage,
\newline
          
            pdpvt->pasynUser->errorMessageSize,
\newline
                      "Invalid
 reply");
\newline
        return -1;
\newline
    }
\newline
    pli->val = pdpvt->msg[0];
\newline
    return
 0;
\newline
}
\newline
static int
\newline
convertStatusReply(struct gpibDpvt *pdpvt, int P1, int P2,
 char **P3)
\newline
{
\newline
    struct longinRecord *pli = ((struct longinRecord *)(pdpvt->preco
rd));
\newline

\newline
    if (pdpvt->msgInputLen != 3) {
\newline
        epicsSnprintf(pdpvt->pasynUser->e
rrorMessage,
\newline
                      pdpvt->pasynUser->errorMessageSize,
\newline
  
                    "Invalid reply");
\newline
        return -1;
\newline
    }
\newline
    pli->val
 = pdpvt->msg[1];
\newline
    return 0;
\newline
}
\end_layout

\begin_layout Standard
Some points of interest: 
\end_layout

\begin_layout Enumerate
Custom conversion functions indicate an error by returning -1.
\end_layout

\begin_layout Enumerate
If an error status is returned an explanation should be left in the 
\family typewriter
errorMessage
\family default
 buffer.
 
\end_layout

\begin_layout Enumerate
I put in a sanity check to ensure that the end-of-string character is where
 it should be.
 
\end_layout

\begin_layout Subsubsection
Provide the device support initialization
\end_layout

\begin_layout Standard
Because of way code is stored in object libraries on different systems the
 device support parameter table must be initialized at run-time.
 The analog-in initializer is used to perform this operation.
 This is why all device support files must declare an analog-in DSET.
\end_layout

\begin_layout Standard
Here's the initialization for the AB300 device support.
 The AB300 immediately echos the command characters sent to it so the respond2Wr
ites value must be set to 0.
 All the other values are left as created by the makeSupport.pl script:
\end_layout

\begin_layout LyX-Code
static long init_ai(int pass)
\newline
{
\newline
    if(pass==0) {
\newline
        devSupParms.name =
 "devAB300";
\newline
        devSupParms.gpibCmds = gpibCmds;
\newline
        devSupParms.numparams
 = NUMPARAMS;
\newline
        devSupParms.timeout = TIMEOUT;
\newline
        devSupParms.timeWindow
 = TIMEWINDOW;
\newline
        devSupParms.respond2Writes = 0;
\newline
    }
\newline
    return(0);
\newline
}
\end_layout

\begin_layout LyX-Code

\end_layout

\begin_layout Subsection
Modify the device support database definition file
\end_layout

\begin_layout Standard
This file specifies the link between the DSET names defined in the device
 support file and the DTYP fields in the application database.
 The makeSupport.pl command created an example file in 
\family typewriter
AB300Sup/devAB300.dbd
\family default
.
 If you removed any of the 
\family typewriter
DSET_
\family default
\shape italic
xxx
\shape default
 definitions from the device support file you must remove the corresponding
 lines from this file.
 You must define an analog-in DSET even if the device provides no analog-in
 records (as is the case for the AB300).
\end_layout

\begin_layout Standard
\begin_inset ERT
status open

\begin_layout Standard


\backslash
verbatiminput{AB300/AB300Sup/devAB300.dbd}
\end_layout

\end_inset


\end_layout

\begin_layout Subsection
Create the device support database file
\end_layout

\begin_layout Standard
This is the database describing the actual EPICS process variables associated
 with the filter wheel.
\end_layout

\begin_layout Standard
I modified the file 
\family typewriter
AB300Sup/devAB300.db
\family default
 to have the following contents:
\end_layout

\begin_layout Standard
\begin_inset ERT
status open

\begin_layout Standard


\backslash
verbatiminput{AB300/AB300Sup/devAB300.db}
\end_layout

\end_inset


\end_layout

\begin_layout Standard
Notes: 
\end_layout

\begin_layout Enumerate
The numbers following the 
\family typewriter
L
\family default
 in the INP and OUT fields are the number of the `link' used to communicate
 with the filter wheel.
 This link is set up at run time by commands in the application startup
 script.
 
\end_layout

\begin_layout Enumerate
The numbers following the 
\family typewriter
A
\family default
 in the INP and OUT fields are unused by serial devices but must be a valid
 GPIB address (0-30) since the GPIB address conversion routines check the
 value and the diagnostic display routines require a matching value.
 
\end_layout

\begin_layout Enumerate
The numbers following the 
\family typewriter
@
\family default
 in the INP and OUT fields are the indices into the GPIB command array.
 
\end_layout

\begin_layout Enumerate
The DTYP fields must match the names specified in the devAB300.dbd database
 definition.
 
\end_layout

\begin_layout Enumerate
The device support database follows the ASYN convention that the macros
 $(P), $(R), $(L) and $(A) are used to specify the record name prefixes,
 link number and GPIB address, respectively.
\end_layout

\begin_layout Subsection
Build the device support
\end_layout

\begin_layout Standard
Change directories to the top-level directory of your device support and:
\end_layout

\begin_layout LyX-Code
norume> 
\family roman
\series bold
make
\end_layout

\begin_layout Standard
(
\series bold
gnumake
\series default
 on Solaris).
\end_layout

\begin_layout Standard
If all goes well you'll be left with a device support library in lib/
\shape italic
<EPICS_HOST_ARCH>
\shape default
/, a device support database definition in dbd/ and a device support database
 in db/.
\end_layout

\begin_layout Section
Create a test application
\end_layout

\begin_layout Standard
Now that the device support has been completed it's time to create a new
 EPICS application to confirm that the device support is operating correctly.
 The easiest way to do this is with the makeBaseApp.pl script supplied with
 EPICS.
\end_layout

\begin_layout Standard
Here are the commands I ran.
 You'll have to change the 
\family typewriter
/home/EPICS/base
\family default
 to the path to where your EPICS base is installed.
 If you're not running on Linux you'll also have to change all the 
\family typewriter
linux-x86
\family default
 to reflect the architecture you're using (
\family typewriter
solaris-sparc
\family default
, 
\family typewriter
darwin-ppc
\family default
, etc.).
 I built the test application in the same <top> as the device support, but
 the application could be built anywhere.
 As well, I built the application as a 'soft' IOC running on the host machine,
 but the serial/GPIB driver also works on RTEMS and vxWorks.
\end_layout

\begin_layout LyX-Code
norume> 
\family roman
\series bold
cd ab300
\family default
\series default

\newline
norume> 
\family roman
\series bold
/home/EPICS/base/bin/linux-x86/makeBaseApp.pl -t ioc AB300
\family default
\series default

\newline
norume> 
\family roman
\series bold
/home/EPICS/base/bin/linux-x86/makeBaseApp.pl -i -t ioc AB300
\family default
\series default

\newline
The following target architectures are available in base:
\newline
    RTEMS-pc386
\newline

    linux-x86
\newline
    solaris-sparc
\newline
    win32-x86-cygwin
\newline
    vxWorks-ppc603
\newline
What
 architecture do you want to use? 
\family roman
\series bold
linux-x86
\end_layout

\begin_layout Section
Using the device support in an application
\end_layout

\begin_layout Standard
Several files need minor modifications to use the device support in the
 test, or any other, application.
\end_layout

\begin_layout Subsection
Make some changes to configure/RELEASE
\end_layout

\begin_layout Standard
Edit the 
\family typewriter
configure/RELEASE
\family default
 file which makeBaseApp.pl created and confirm that the EPICS_BASE path is
 correct.
 Add entries for your ASYN and device support.
 For example these might be:
\end_layout

\begin_layout LyX-Code
AB300=/home/EPICS/modules/instrument/ab300/1-2
\end_layout

\begin_layout LyX-Code
ASYN=/home/EPICS/modules/soft/asyn/3-2
\end_layout

\begin_layout LyX-Code
EPICS_BASE=/home/EPICS/base
\end_layout

\begin_layout Subsection
Modify the application database definition file
\end_layout

\begin_layout Standard
Your application database definition file must include the database definition
 files for your instrument and for the ASYN drivers.
 There are two ways that this can be done:
\end_layout

\begin_layout Enumerate
If you are building your application database definition from an 
\shape italic
xxx
\family typewriter
\shape default
Include.dbd
\family default
 file you include the additional database definitions in that file.
 For example, to add support for the AB300 instrument and local and remote
 serial line drivers:
\newline

\begin_inset ERT
status open

\begin_layout Standard


\backslash
verbatiminput{AB300/AB300App/src/AB300Include.dbd}
\end_layout

\end_inset


\end_layout

\begin_layout Enumerate
If you are building your application database definition from the application
 Makefile you specify the additional database definitions there:
\newline
 .
\newline
.
\newline

\shape italic
xxx
\shape default
_DBD += base.dbd
\newline

\shape italic
xxx
\shape default
_DBD += devAB300.dbd
\newline

\shape italic
xxx
\shape default
_DBD += drvAsynIPPort.dbd
\newline

\shape italic
xxx
\shape default
_DBD += drvAsynSerialPort.dbd
\newline
.
\newline
.
\newline
This is the preferred method.
\end_layout

\begin_layout Subsection
Add the device support libraries to the application
\end_layout

\begin_layout Standard
You must link your device support library and the ASYN support library with
 the application.
 Add the following lines 
\end_layout

\begin_layout LyX-Code

\family roman
\shape italic
xxx
\family default
\shape default
_LIBS += devAB300
\end_layout

\begin_layout LyX-Code

\family roman
\shape italic
xxx
\family default
\shape default
_LIBS += asyn
\end_layout

\begin_layout Standard
before the
\end_layout

\begin_layout LyX-Code

\family roman
\shape italic
xxx
\family default
\shape default
_LIBS += $(EPICS_BASE_IOC_LIBS)
\end_layout

\begin_layout Standard
line in the application 
\family typewriter
Makefile
\family default
.
\end_layout

\begin_layout Subsection
Modify the application startup script
\end_layout

\begin_layout Standard
The 
\family typewriter
st.cmd
\family default
 application startup script created by the makeBaseApp.pl script needs a
 few changes to get the application working properly.
\end_layout

\begin_layout Enumerate
Load the device support database records:
\end_layout

\begin_deeper
\begin_layout LyX-Code
cd $(AB300)          
\family roman
(
\family default
cd AB300 
\family roman
if using the vxWorks shell)
\end_layout

\begin_layout LyX-Code
dbLoadRecords("db/devAB300.db","P=AB300:,R=,L=0,A=0")
\end_layout

\end_deeper
\begin_layout Enumerate
Set up the 'port' between the IOC and the filter wheel.
 
\end_layout

\begin_deeper
\begin_layout Itemize
If you're using an Ethernet/RS-232 converter or a device which communicates
 over a telnet-style socket connection you need to specify the Internet
 host and port number like:
\end_layout

\begin_deeper
\begin_layout LyX-Code
drvAsynIPPortConfigure("L0","164.54.9.91:4002",0,0,0)
\end_layout

\end_deeper
\begin_layout Itemize
If you're using a serial line directly attached to the IOC you need something
 like:
\end_layout

\begin_deeper
\begin_layout LyX-Code
drvAsynSerialPortConfigure("L0","/dev/ttyS0",0,0,0)
\newline
asynSetOption("L0", -1,
 "baud", "9600")
\newline
asynSetOption("L0", -1, "bits", "8")
\newline
asynSetOption("L0",
 -1, "parity", "none")
\newline
asynSetOption("L0", -1, "stop", "1")
\newline
asynSetOption("L0",
 -1, "clocal", "Y")
\newline
asynSetOption("L0", -1, "crtscts", "N")
\end_layout

\end_deeper
\begin_layout Itemize
If you're using a serial line directly attached to a vxWorks IOC you must
 first configure the serial port interface hardware.
 The following example shows the commands to configure a port on a GreenSprings
 UART Industry-Pack module.
\end_layout

\begin_deeper
\begin_layout LyX-Code
ipacAddVIPC616_01("0x6000,B0000000")
\newline
tyGSOctalDrv(1)
\newline
tyGSOctalModuleInit("RS232",
 0x80, 0, 0)
\newline
tyGSOctalDevCreate("/tyGS/0/0",0,0,1000,1000)
\newline
drvAsynSerialPortConfig
ure("L0","/tyGS/0/0",0,0,0)
\newline
asynSetOption("L0",-1,"baud","9600")
\end_layout

\end_deeper
\begin_layout Standard
In all of the above examples the first argument of the configure and set
 port option commands is the link identifier and must match the 
\family typewriter
L
\family default
 value in the EPICS database record INP and OUT fields.
 The second argument of the configure command identifies the port to which
 the connection is to be made.
 The third argument sets the priority of the worker thread which performs
 the I/O operations.
  A value of zero directs the command to choose a reasonable default value.
 The fourth argument is zero to direct the device support layer to automatically
 connect to the serial port on startup and whenever the serial port becomes
 disconnected.
 The final argument is zero to direct the device support layer to use standard
 end-of-string processing on input messages.
\end_layout

\end_deeper
\begin_layout Enumerate
(Optional) Add lines to control the debugging level of the serial/GPIB driver.
 The following enables error messages and a description of every I/O operation.
\end_layout

\begin_deeper
\begin_layout LyX-Code
asynSetTraceMask("L0",-1,0x9)
\newline
asynSetTraceIOMask("L0",-1,0x2)
\end_layout

\begin_layout Standard
A better way to control the amount and type of diagnostic output is to add
 an 
\begin_inset LatexCommand url
name "asynRecord"
target "../asynRecord.html"

\end_inset

 to your application.
\end_layout

\end_deeper
\begin_layout Subsection
Build the application
\end_layout

\begin_layout Standard
Change directories to the top-level directory of your application and:
\end_layout

\begin_layout LyX-Code
norume> 
\family roman
\series bold
make
\end_layout

\begin_layout Standard
(
\series bold
gnumake
\series default
 on Solaris).
\end_layout

\begin_layout Standard
If all goes well you'll be left with an executable program in bin/linux-x86/AB30
0.
\end_layout

\begin_layout Subsection
Run the application
\end_layout

\begin_layout Standard
Change directories to where makeBaseApp.pl put the application startup script
 and run the application:
\end_layout

\begin_layout LyX-Code
norume> 
\family roman
\series bold
cd iocBoot/iocAB300
\family default
\series default

\newline
norume> 
\family roman
\series bold
../../bin/linux-x86/AB300 st.cmd
\family default
\series default

\newline
dbLoadDatabase("../../dbd/AB300.dbd",0,0)
\newline
AB300_registerRecordDeviceDriver(pdbbase)
\newline
cd
 ${AB300}
\end_layout

\begin_layout LyX-Code
dbLoadRecords("db/devAB300.db","P=AB300:,R=,L=0,A=0")
\newline
drvAsynIPPortConfigure("L0",
"164.54.3.137:4001",0,0,0)
\newline
asynSetTraceMask("L0",-1,0x9)
\newline
asynSetTraceIOMask("L0",-1,0
x2)
\newline
iocInit()
\newline
####################################################################
########
\newline
###  EPICS IOC CORE built on Apr 23 2004
\newline
###  EPICS R3.14.6  2008/03/25
 18:06:21
\newline
#######################################################################
#####
\newline
Starting iocInit
\newline
iocInit: All initialization complete
\end_layout

\begin_layout Standard
Check the process variable names:
\end_layout

\begin_layout LyX-Code
epics> 
\family roman
\series bold
dbl
\family default
\series default

\newline
AB300:FilterWheel:fbk
\newline
AB300:FilterWheel:status
\newline
AB300:FilterWheel
\newline
AB300:FilterWheel:
reset
\end_layout

\begin_layout Standard
Reset the filter wheel.
 The values sent between the IOC and the filter wheel are shown:
\end_layout

\begin_layout LyX-Code
epics> 
\family roman
\series bold
dbpf AB300:FilterWheel:reset 0
\family default
\series default

\newline
DBR_LONG:           0         0x0
\newline
2004/04/21 12:05:14.386 164.54.3.137:4001 write
 3 
\backslash
377
\backslash
377
\backslash
033
\newline
2004/04/21 12:05:16.174 164.54.3.137:4001 read 1 
\backslash
033
\end_layout

\begin_layout Standard
Read back the filter wheel position.
 The dbtr command prints the record before the I/O has a chance to occur:
\end_layout

\begin_layout LyX-Code
epics> 
\family roman
\series bold
dbtr AB300:FilterWheel:fbk
\family default
\series default

\newline
ACKS: NO_ALARM      ACKT: YES           ADEL: 0             ALST: 0
\newline
ASG:
                BKPT: 0x00          DESC: Filter Wheel Position
\newline
DISA: 0 
            DISP: 0             DISS: NO_ALARM      DISV: 1
\newline
DTYP: AB300Gpib
     EGU:                EVNT: 0             FLNK:CONSTANT 0
\newline
HHSV: NO_ALARM
      HIGH: 0             HIHI: 0             HOPR: 6
\newline
HSV: NO_ALARM     
  HYST: 0             INP:GPIB_IO #L0 A0 @2
\newline
LALM: 0             LCNT: 0 
            LLSV: NO_ALARM      LOLO: 0
\newline
LOPR: 1             LOW: 0      
        LSV: NO_ALARM       MDEL: 0
\newline
MLST: 0             NAME: AB300:FilterWheel:f
bk             NSEV: NO_ALARM
\newline
NSTA: NO_ALARM      PACT: 1             PHAS:
 0             PINI: NO
\newline
PRIO: LOW           PROC: 0             PUTF: 0 
            RPRO: 0
\newline
SCAN: Passive       SDIS:CONSTANT       SEVR: INVALID
       SIML:CONSTANT
\newline
SIMM: NO            SIMS: NO_ALARM      SIOL:CONSTANT
       STAT: UDF
\newline
SVAL: 0             TPRO: 0             TSE: 0         
     TSEL:CONSTANT
\newline
UDF: 1              VAL: 0
\newline
2004/04/21 12:08:01.971 164.54.3.137:400
1 write 1 
\backslash
035
\newline
2004/04/21 12:08:01.994 164.54.3.137:4001 read 3 
\backslash
001
\backslash
020
\backslash
030
\end_layout

\begin_layout Standard
Now the process variable should have that value:
\end_layout

\begin_layout LyX-Code
epics> 
\family roman
\series bold
dbpr AB300:FilterWheel:fbk
\family default
\series default

\newline
ASG:                DESC: Filter Wheel Position             DISA: 0
\newline
DISP:
 0             DISV: 1             NAME: AB300:FilterWheel:fbk
\newline
SEVR: NO_ALARM
      STAT: NO_ALARM      SVAL: 0             TPRO: 0
\newline
VAL: 1
\end_layout

\begin_layout Standard
Move the wheel to position 4:
\end_layout

\begin_layout LyX-Code
epics> 
\family roman
\series bold
dbpf AB300:FilterWheel 4
\family default
\series default

\newline
DBR_LONG:           4         0x4 
\newline
2004/04/21 12:10:51.542 164.54.3.137:4001
 write 2 
\backslash
017
\backslash
004
\newline
2004/04/21 12:10:51.562 164.54.3.137:4001 read 1 
\backslash
020
\newline
2004/04/21 12:10:52.902 164.54.3.137:4001 read 1 
\backslash
030
\end_layout

\begin_layout Standard
Read back the position:
\end_layout

\begin_layout LyX-Code
epics> 
\family roman
\series bold
dbtr AB300:FilterWheel:fbk
\family default
\series default

\newline
ACKS: NO_ALARM      ACKT: YES           ADEL: 0             ALST: 1
\newline
ASG:
                BKPT: 0x00          DESC: Filter Wheel Position 
\newline
DISA: 0
             DISP: 0             DISS: NO_ALARM      DISV: 1
\newline
DTYP: AB300Gpib
     EGU:                EVNT: 0             FLNK:CONSTANT 0
\newline
HHSV: NO_ALARM
      HIGH: 0             HIHI: 0             HOPR: 6
\newline
HSV: NO_ALARM     
  HYST: 0             INP:GPIB_IO #L0 A0 @2
\newline
LALM: 1             LCNT: 0 
            LLSV: NO_ALARM      LOLO: 0
\newline
LOPR: 1             LOW: 0      
        LSV: NO_ALARM       MDEL: 0
\newline
MLST: 1             NAME: AB300:FilterWheel:f
bk             NSEV: NO_ALARM
\newline
NSTA: NO_ALARM      PACT: 1             PHAS:
 0             PINI: NO
\newline
PRIO: LOW           PROC: 0             PUTF: 0 
            RPRO: 0
\newline
SCAN: Passive       SDIS:CONSTANT       SEVR: NO_ALARM
      SIML:CONSTANT
\newline
SIMM: NO            SIMS: NO_ALARM      SIOL:CONSTANT
       STAT: NO_ALARM
\newline
SVAL: 0             TPRO: 0             TSE: 0    
          TSEL:CONSTANT
\newline
UDF: 0              VAL: 1
\newline
2004/04/21 12:11:43.372
 164.54.3.137:4001 write 1 
\backslash
035
\newline
2004/04/21 12:11:43.391 164.54.3.137:4001 read 3 
\backslash
004
\backslash
020
\backslash
030
\end_layout

\begin_layout Standard
And it really is 4:
\end_layout

\begin_layout LyX-Code
epics> 
\family roman
\series bold
dbpr AB300:FilterWheel:fbk
\family default
\series default

\newline
ASG:                DESC: Filter Wheel Position             DISA: 0
\newline
DISP:
 0             DISV: 1             NAME: AB300:FilterWheel:fbk
\newline
SEVR: NO_ALARM
      STAT: NO_ALARM      SVAL: 0             TPRO: 0
\newline
VAL: 4
\end_layout

\begin_layout Section
Device Support File
\end_layout

\begin_layout Standard
Here is the complete device support file for the AB300 filter wheel (
\family typewriter
AB300Sup/devAB300.c
\family default
):
\end_layout

\begin_layout Standard
\begin_inset ERT
status open

\begin_layout Standard


\backslash
verbatiminput{AB300/AB300Sup/devAB300.c}
\end_layout

\end_inset


\end_layout

\begin_layout Section
asynRecord support
\end_layout

\begin_layout Standard
The asynRecord provides a convenient mechanism for controlling the diagnostic
 messages produced by asyn drivers.
 To use an asynRecord in your application: 
\end_layout

\begin_layout Enumerate
Add the line
\newline

\newline

\family typewriter
DB_INSTALLS += $(ASYN)/db/asynRecord.db
\family default
 
\newline

\newline
to an application 
\family typewriter
Makefile
\family default
.
\end_layout

\begin_layout Enumerate
Create the diagnostic record by adding a line like
\newline

\newline
cd $(ASYN)          
\family roman
(
\family default
cd ASYN 
\family roman
if using the vxWorks shell)
\family typewriter
\size small

\newline
dbLoadRecords("db/asynRecord.db","P=AB300,R=Test,PORT=L0,ADDR=0,IMAX=0,OMAX=0")
\family default
\size default

\newline

\newline
to the application startup (
\family typewriter
st.cmd
\family default
) script.
 The 
\family typewriter
PORT
\family default
 value must match the the value in the corresponding 
\family typewriter
drvAsynIPPortConfigure
\family default
 or 
\family typewriter
drvAsynSerialPortConfigure
\family default
 command.
 The 
\family typewriter
addr
\family default
 value should be that of the instrument whose I/O you wish to monitor.
 The 
\family typewriter
P
\family default
 and 
\family typewriter
R
\family default
 values are arbitrary and are concatenated together to form the record name.
 Choose values which are  unique among all IOCs on your network.
 
\end_layout

\begin_layout Standard
To run the asynRecord screen, add 
\shape italic
<asynTop
\family typewriter
\shape default
>/medm
\family default
 to your 
\family typewriter
EPICS_DISPLAY_PATH
\family default
 environment variable and start medm with 
\family typewriter
P
\family default
, 
\family typewriter
R
\family default
, 
\family typewriter
PORT
\family default
 and 
\family typewriter
ADDR
\family default
 values matching those given in the 
\family typewriter
dbLoadRecords
\family default
 command:
\end_layout

\begin_layout LyX-Code
medm -x -macro "P=AB300,R=Test" asynRecord.adl
\end_layout

\begin_layout Section
Support for devices with common 'end-of-string' characters
\end_layout

\begin_layout Standard
Devices which use the same character, or characters, to mark the end of
 each command or response message need not specify these characters in the
 GPIB command table entries.
 They can, instead, specify the terminator sequences as part of the driver
 port configuration commands.
 This makes it possible for a single command table to provide support for
 devices which provide a serial or Ethernet interface (and require command/respo
nse terminators) and also provide a GPIB interface (which does not require
 command/response terminators).
\end_layout

\begin_layout Standard
For example, the configuration commands for a TDS3000 digital oscilloscope
 connected through an Ethernet serial port adapter might look like:
\end_layout

\begin_layout LyX-Code
drvAsynIPPortConfigure("L0", "192.168.9.90:4003", 0, 0, 0)
\newline
asynOctetSetInputEos("L0"
,0,"
\backslash
n")
\newline
asynOctetSetOutputEos("L0",0,"
\backslash
n")
\end_layout

\begin_layout Standard
The configuration command for the same oscilloscope connected to an Ethernet
 GPIB adapter would be:
\end_layout

\begin_layout LyX-Code
vxi11Configure("L0", "192.168.8.129", 0, "0.0", "gpib0", 0)
\end_layout

\begin_layout Standard
An example command table entry for this device is shown below.
 Notice that there is no 
\family typewriter

\backslash
n
\family default
 at the end of the command and that the table 'eos' field is 
\family typewriter
NULL
\family default
:
\end_layout

\begin_layout LyX-Code
/* 2 : read delay : AI */
\newline
  {&DSET_AI, GPIBREAD, IB_Q_LOW, "HOR:DEL:TIM?",
 "%lf", 0, 20,
\newline
                                 NULL, 0, 0, NULL, NULL, NULL},
\end_layout

\end_body
\end_document