#! Generated by VisualDCT v2.6 #! DBDSTART #! DBDEND record(calc, "$(device):PLOG") { field(DESC, "log Pressure") field(EGU, "log") field(CALC, "LOG(A)") field(INPA, "$(device):PMON CP MS") field(HOPR, "-2") field(LOPR, "-11") } record(calc, "$(device):P") { field(DESC, "Pressure") field(EGU, "Torr") field(CALC, "(A)") field(INPA, "$(device):PMON CP MS") field(HOPR, "-2") field(LOPR, "-11") field(PREC, "14") } record(calcout, "$(device):PADEL") { field(DESC, "deadband") field(CALC, "A/B") field(OUT, "$(device):PMON.ADEL") field(INPA, "$(device):PMON.VAL") field(INPB, "20") field(SCAN, "10 second") } #Only works when signal is less than 5% of full scale record(bo, "$(device):ZEROCM") { field(DESC, "Exec ZeroCM") field(DTYP, "stream") field(OUT, "@mks937b.proto.db setZeroCM($(channel),$(addr)) $(port) 0") field(ZNAM, "ZeroCM") field(ONAM, "ZeroCM") field(ASG, "MCC") } # Setpoints and Relays ######################################## record(mbbo, "$(device):PSTATENADES_1") { field(DESC, "Setpt Enable DES Relay $(setpointA)") field(DTYP, "stream") field(OUT, "@mks937b.proto.db setRlyEn($(setpointA),$(addr)) $(port) 0") # 0: clear(Disbale); 1: set(FORCE); 2: enable; field(ZRST, "Disabled") field(ONST, "ForceSET") field(TWST, "Enabled") field(ZRSV, "MINOR") field(ONSV, "MINOR") field(TWSV, "NO_ALARM") } record(mbbo, "$(device):PSTATENADES_2") { field(DESC, "Setpt Enable DES Relay $(setpointB)") field(DTYP, "stream") field(OUT, "@mks937b.proto.db setRlyEn($(setpointB),$(addr)) $(port) 0") # 0: clear(Disbale); 1: set(FORCE); 2: enable; field(ZRST, "Disabled") field(ONST, "ForceSET") field(TWST, "Enabled") field(ZRSV, "MINOR") field(ONSV, "MINOR") field(TWSV, "NO_ALARM") } record(bo, "$(device):PSTATDIRDES_1") { field(DESC, "Setpt Dir DES Relay $(setpointA)") field(DTYP, "stream") field(OUT, "@mks937b.proto.db setSpDir($(setpointA),$(addr)) $(port) 0") field(ZNAM, "BELOW") field(ONAM, "ABOVE") } record(bo, "$(device):PSTATDIRDES_2") { field(DESC, "Setpt Dir DES Relay $(setpointB)") field(DTYP, "stream") field(OUT, "@mks937b.proto.db setSpDir($(setpointB),$(addr)) $(port) 0") field(ZNAM, "BELOW") field(ONAM, "ABOVE") } record(mbbi, "$(device):PSTATENABLE_1") { field(DESC, "Setpt Enable RBCK Relay $(setpointA)") field(DTYP, "stream") field(INP, "@mks937b.proto.db getRlyEn($(setpointA),$(addr)) $(port) 0") field(SCAN, "2 second") # 0: clear(Disbale); 1: set(FORCE); 2: enable; field(ZRST, "Disabled") field(ONST, "SET") field(TWST, "Enabled") field(ZRSV, "MINOR") field(ONSV, "MINOR") field(TWSV, "NO_ALARM") } record(mbbi, "$(device):PSTATENABLE_2") { field(DESC, "Setpt Enable RBCK Relay $(setpointB)") field(DTYP, "stream") field(INP, "@mks937b.proto.db getRlyEn($(setpointB),$(addr)) $(port) 0") field(SCAN, "2 second") field(ZRST, "Disabled") field(ONST, "SET") field(TWST, "Enabled") field(ZRSV, "MINOR") field(ONSV, "MINOR") field(TWSV, "NO_ALARM") } record(ai, "$(device):PSTATSPRBCK_1") { field(DESC, "Setpt RBCK Relay $(setpointA)") field(DTYP, "stream") field(INP, "@mks937b.proto.db getsp($(setpointA),$(addr)) $(port) 0") field(SCAN, "2 second") field(EGU, "Torr") field(PREC, "1") } record(ao, "$(device):PSTATSPDES_1") { field(DESC, "Setpt DES Relay $(setpointA)") field(DTYP, "stream") field(OUT, "@mks937b.proto.db setsp($(setpointA),$(addr)) $(port) 0") field(EGU, "Torr") field(PREC, "2") field(HOPR, "1000") field(LOPR, "0") field(DRVH, "1000") field(DRVL, "0") field(DOL, "1.0e2") field(ASG, "MCC") } record(ai, "$(device):HYSTSPRBCK_1") { field(DESC, "Setpt RBCK HYST $(setpointA)") field(DTYP, "stream") field(INP, "@mks937b.proto.db getHysp($(setpointA),$(addr)) $(port) 0") field(SCAN, "2 second") field(EGU, "Torr") field(PREC, "1") } record(ao, "$(device):HYSTSPDES_1") { field(DESC, "Setpt DES HYST $(setpointA)") field(DTYP, "stream") field(OMSL, "supervisory") field(OUT, "@mks937b.proto.db setHysp($(setpointA),$(addr)) $(port) 0") field(EGU, "Torr") field(PREC, "2") field(HOPR, "1000") field(LOPR, "0") field(DRVH, "1000") field(DRVL, "0") field(DOL, "1.0e2") field(ASG, "MCC") } record(ai, "$(device):PSTATSPRBCK_2") { field(DESC, "Setpt RBCK Relay $(setpointB)") field(DTYP, "stream") field(INP, "@mks937b.proto.db getsp($(setpointB),$(addr)) $(port) 0") field(SCAN, "2 second") field(EGU, "Torr") field(PREC, "1") } record(ao, "$(device):PSTATSPDES_2") { field(DESC, "Setpt DES Relay $(setpointB)") field(DTYP, "stream") field(OMSL, "supervisory") field(OUT, "@mks937b.proto.db setsp($(setpointB),$(addr)) $(port) 0") field(EGU, "Torr") field(PREC, "2") field(HOPR, "1000") field(LOPR, "0") field(DRVH, "1000") field(DRVL, "0") field(DOL, "1.0e2") field(ASG, "MCC") } record(ai, "$(device):HYSTSPRBCK_2") { field(DESC, "Setpt RBCK HYST $(setpointB)") field(DTYP, "stream") field(INP, "@mks937b.proto.db getHysp($(setpointB),$(addr)) $(port) 0") field(SCAN, "2 second") field(EGU, "Torr") field(PREC, "1") } record(ao, "$(device):HYSTSPDES_2") { field(DESC, "Setpt DES HYST $(setpointB)") field(DTYP, "stream") field(OMSL, "supervisory") field(OUT, "@mks937b.proto.db setHysp($(setpointB),$(addr)) $(port) 0") field(EGU, "Torr") field(PREC, "2") field(HOPR, "1000") field(LOPR, "0") field(DRVH, "1000") field(DRVL, "0") field(DOL, "1.0e2") field(ASG, "MCC") } #Direction record(bi, "$(device):PSTATSPDIR_1") { field(DESC, "Setpt DIR RBCK Relay $(setpointA)") field(DTYP, "stream") field(INP, "@mks937b.proto.db getSpDir($(setpointA),$(addr)) $(port) 0") field(SCAN, "2 second") field(ZNAM, "BELOW") field(ONAM, "ABOVE") } record(bi, "$(device):PSTATSPDIR_2") { field(DESC, "Setpt DIR RBCK Relay $(setpointB)") field(DTYP, "stream") field(INP, "@mks937b.proto.db getSpDir($(setpointB),$(addr)) $(port) 0") field(SCAN, "2 second") field(ZNAM, "BELOW") field(ONAM, "ABOVE") } ################################################################################ # PSTAT - # record(mbbiDirect, "$(device):PSTATALL") { field(DTYP, "stream") field(DESC, "ALL 12 Relay Status in CTRL") field(SCAN, "2 second") field(INP, "@mks937b.proto.db getspALL($(channel),$(addr)) $(port) 0") field(FLNK, "$(device):PSTATENALL PP NMS") } # Does not quite work with normal mks973b proto file due to CM gauges only having 2 relays record(mbbiDirect, "$(device):PSTATENALL") { field(DTYP, "stream") field(DESC, "ALL 12 Relay Status in CTRL") field(INP, "@mks937b.proto.db getRlyENA($(channel),$(addr)) $(port) 0") field(FLNK, "$(device):SEL_PSTAT1 PP NMS") } record(calc, "$(device):SEL_CALC_PSTAT1") { field(DESC, "Calc PSTAT BIT") field(CALC, "A-1") field(INPA, "$(setpointA)") field(PINI, "1") } record(calc, "$(device):SEL_CALC_PSTAT2") { field(DESC, "Calc PSTAT BIT") field(CALC, "A-1") field(INPA, "$(setpointB)") field(PINI, "1") } record(sel, "$(device):SEL_PSTAT1") { field(DESC, "SEL PSTAT from PSTATALL") field(NVL, "$(device):SEL_CALC_PSTAT1") field(SELM, "Specified") field(INPA, "$(device):PSTATALL.B0") field(INPB, "$(device):PSTATALL.B1") field(INPC, "$(device):PSTATALL.B2") field(INPD, "$(device):PSTATALL.B3") field(INPE, "$(device):PSTATALL.B4") field(INPF, "$(device):PSTATALL.B5") field(INPG, "$(device):PSTATALL.B6") field(INPH, "$(device):PSTATALL.B7") field(INPI, "$(device):PSTATALL.B8") field(INPJ, "$(device):PSTATALL.B9") field(INPK, "$(device):PSTATALL.BA") field(INPL, "$(device):PSTATALL.BB") field(FLNK, "$(device):PSTAT_1 PP NMS") } record(bi, "$(device):PSTAT_1") { field(DESC, "PSTAT 1 (Relay $(setpointA))") field(INP, "$(device):SEL_PSTAT1") field(ZNAM, "Faulted") field(ONAM, "OK") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") field(FLNK, "$(device):SEL_PSTAT2") } record(sel, "$(device):SEL_PSTAT2") { field(DESC, "SEL PSTAT from PSTATALL") field(NVL, "$(device):SEL_CALC_PSTAT2") field(SELM, "Specified") field(INPA, "$(device):PSTATALL.B0") field(INPB, "$(device):PSTATALL.B1") field(INPC, "$(device):PSTATALL.B2") field(INPD, "$(device):PSTATALL.B3") field(INPE, "$(device):PSTATALL.B4") field(INPF, "$(device):PSTATALL.B5") field(INPG, "$(device):PSTATALL.B6") field(INPH, "$(device):PSTATALL.B7") field(INPI, "$(device):PSTATALL.B8") field(INPJ, "$(device):PSTATALL.B9") field(INPK, "$(device):PSTATALL.BA") field(INPL, "$(device):PSTATALL.BB") field(FLNK, "$(device):PSTAT_2") } record(bi, "$(device):PSTAT_2") { field(DESC, "PSTAT 2 (Relay $(setpointB))") field(INP, "$(device):SEL_PSTAT2") field(ZNAM, "Faulted") field(ONAM, "OK") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } #CM gauges only have two Pressure Releys record(calc, "$(device):PSTAT_CALC") { field(CALC, "A& B") field(INPA, "$(device):PSTAT_1.VAL MS CP") field(INPB, "$(device):PSTAT_2.VAL MS CP") field(FLNK, "$(device):PSTAT_SUM") } record(bi, "$(device):PSTAT_SUM") { field(DESC, "PSTAT Summary") field(INP, "$(device):PSTAT_CALC") field(ZNAM, "Faulted") field(ONAM, "OK") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") } ################################################################################ # Status # #% controldesk Pressure smon record(mbbi, "$(device):STATE") { field(DTYP, "stream") field(INP, "@mks937b.proto.db stateCM($(channel),$(addr)) $(port) 0") field(DESC, "Status") field(SCAN, "1 second") field(FLNK, "$(device):STATUSCALC2") field(ZRST, "OK") field(ONST, "OK") field(TWST, "Below Range") field(THST, "Above Range") field(FRST, "At Atmosphere") field(FVST, "HV Off") field(SXST, "RP_OFF") field(SVST, "Wait") field(EIST, "LowEmis") field(NIST, "CNTRL_Off") field(TEST, "Protected State") field(ELST, "MISCONN") field(TVST, "Protected State") field(TTST, "NoGauge") field(FTST, "Not Connected") field(FFST, "Wrong Gauge") # field(UNSV, "Bad Command") field(ZRSV, "NO_ALARM") field(ONSV, "NO_ALARM") field(TWSV, "NO_ALARM") field(THSV, "NO_ALARM") field(FRSV, "MINOR") field(FVSV, "MAJOR") field(SXSV, "MAJOR") field(SVSV, "MINOR") field(EISV, "MINOR") field(NISV, "MAJOR") field(TESV, "MAJOR") field(ELSV, "MAJOR") field(TVSV, "MINOR") field(TTSV, "MAJOR") field(FTSV, "MAJOR") field(FFSV, "MAJOR") } record(sel, "$(device):PMON") { field(SELM, "Specified") field(NVL, "$(device):STATUSCALC") field(INPA, "$(device):PMONRAW PP MS") field(INPB, "$(device):PMONRAW PP MS") field(DESC, "Pressure") field(FLNK, "$(device):PLOG") field(PREC, "11") field(EGU, "Torr") field(HOPR, ".01") field(LOPR, "0") } record(calc, "$(device):STATUSCALC") { field(FLNK, "$(device):PMON") field(CALC, "A<=1?0:1") field(INPA, "$(device):PMONRAW.VAL") } record(ai, "$(device):PMONRAW") { field(SCAN, "1 second") field(DESC, "Pressure") field(DTYP, "stream") field(INP, "@mks937b.proto.db pressure($(channel),$(addr),$(device):STATUS) $(port) 0") field(EGU, "Torr") field(PREC, "11") field(HOPR, "1000") field(LOPR, "0") field(FLNK, "$(device):STATUSCALC") } record(stringin, "$(device):STATUS") { field(DESC, "Channel Status") field(PINI, "YES") field(VAL, "Ok") } # Clean up Combo Pressure Status if there is no error record(calcout, "$(device):STATUS_RS_CALC1") { field(INPA, "$(device):PMONRAW.SEVR CP") field(CALC, "A#2") field(OOPT, "When Non-zero") field(OUT, "$(device):STATUS_RS_CALC2.PROC") } record(stringout, "$(device):STATUS_RS_CALC2") { field(VAL, "OK") field(OUT, "$(device):STATUS PP") } record(stringout, "$(device):STATUSOUT") { field(DESC, "Chan Status Update when OK") field(PINI, "YES") field(VAL, "Ok") field(DOL, "$(device):STATUS") } record(calcout, "$(device):STATUSCALC2") { field(CALC, "A#2") field(OOPT, "When Non-zero") field(OUT, "$(device):STATUSOUT.PROC") field(INPA, "$(device):STATUSMON.SEVR CP") } record(mbbi, "$(device):STATUSMON") { field(DTYP, "stream") field(INP, "@mks937b.proto.db statusCM($(channel),$(addr)) $(port) 0") field(DESC, "Status") field(SCAN, "1 second") field(FLNK, "$(device):STATUSCALC2") field(ZRST, "OK") field(ONST, "OK") field(TWST, "Below Range") field(THST, "Above Range") field(FRST, "At Atmosphere") field(FVST, "HV Off") field(SXST, "RP_OFF") field(SVST, "Wait") field(EIST, "LowEmis") field(NIST, "CNTRL_Off") field(TEST, "Protected State") field(ELST, "MISCONN") field(TVST, "Protected State") field(TTST, "NoGauge") field(FTST, "Not Connected") field(FFST, "Wrong Gauge") # field(UNSV, "Bad Command") field(ZRSV, "NO_ALARM") field(ONSV, "NO_ALARM") field(TWSV, "NO_ALARM") field(THSV, "NO_ALARM") field(FRSV, "MINOR") field(FVSV, "MAJOR") field(SXSV, "MAJOR") field(SVSV, "MINOR") field(EISV, "MINOR") field(NISV, "MAJOR") field(TESV, "MAJOR") field(ELSV, "MAJOR") field(TVSV, "MINOR") field(TTSV, "MAJOR") field(FTSV, "MAJOR") field(FFSV, "MAJOR") } ################################################################################ # Controler Status # # record(stringin, "$(device):UNITRAW") { field(DESC, "Pressure Unit") field(DTYP, "stream") field(SCAN, "2 second") field(INP, "@mks937b.proto.db unit($(channel),$(addr)) $(port) 0") field(PINI, "YES") } record(stringin, "$(device):UNIT") { field(DESC, "Pressure Units") field(INP, "$(device):UNITRAW CP") field(PINI, "YES") } record(stringin, "$(device):VERSIONRAW") { field(DESC, "Controller S/N") field(DTYP, "stream") field(SCAN, "2 second") field(INP, "@mks937b.proto.db version($(channel),$(addr)) $(port) 0") field(PINI, "YES") } record(ai, "$(device):VERSION") { field(DESC, "Controller Unit") field(INP, "$(device):VERSIONRAW CP") field(PINI, "YES") } record(mbbi, "$(device):SENSOR_A") { field(DTYP, "stream") field(INP, "@mks937b.proto.db getSenrA($(channel),$(addr)) $(port) 0") field(DESC, "Sensor SLOT A Type") field(SCAN, "10 second") field(ZRST, "CC") field(ONST, "PR") field(TWST, "CP") field(THST, "CM") field(FRST, "MB") field(FVST, "GB") field(SXST, "LN") field(SVST, "24") field(EIST, "NC") field(NIST, "HC") field(FLNK, "$(device):SENSOR_B") } record(mbbi, "$(device):SENSOR_B") { field(DTYP, "stream") field(INP, "@mks937b.proto.db getSenrB($(channel),$(addr)) $(port) 0") field(DESC, "Sensor SLOT B Type") field(ZRST, "CC") field(ONST, "PR") field(TWST, "CP") field(THST, "CM") field(FRST, "MB") field(FVST, "GB") field(SXST, "LN") field(SVST, "24") field(EIST, "NC") field(NIST, "HC") field(FLNK, "$(device):SENSOR_C") } record(mbbi, "$(device):SENSOR_C") { field(DTYP, "stream") field(INP, "@mks937b.proto.db getSenrC($(channel),$(addr)) $(port) 0") field(DESC, "Sensor SLOT C Type") field(ZRST, "CC") field(ONST, "PR") field(TWST, "CP") field(THST, "CM") field(FRST, "MB") field(FVST, "GB") field(SXST, "LN") field(SVST, "24") field(EIST, "NC") field(NIST, "HC") field(FLNK, "$(device):MODTYPE_A") } record(mbbi, "$(device):MODTYPE_A") { field(DTYP, "stream") field(INP, "@mks937b.proto.db getModT1($(channel),$(addr)) $(port) 0") field(DESC, "Sensor SLOT A Type") field(ZRST, "CC") field(ONST, "HC") field(TWST, "CM") field(THST, "PR") field(FRST, "FC") field(FVST, "NC") field(SXST, "NA") field(FLNK, "$(device):MODTYPE_B") } record(mbbi, "$(device):MODTYPE_B") { field(DTYP, "stream") field(INP, "@mks937b.proto.db getModT2($(channel),$(addr)) $(port) 0") field(DESC, "Sensor SLOT B Type") field(ZRST, "CC") field(ONST, "HC") field(TWST, "CM") field(THST, "PR") field(FRST, "FC") field(FVST, "NC") field(SXST, "NA") field(FLNK, "$(device):MODTYPE_C") } record(mbbi, "$(device):MODTYPE_C") { field(DTYP, "stream") field(INP, "@mks937b.proto.db getModT3($(channel),$(addr)) $(port) 0") field(DESC, "Sensor SLOT C Type") field(ZRST, "CC") field(ONST, "HC") field(TWST, "CM") field(THST, "PR") field(FRST, "FC") field(FVST, "NC") field(SXST, "NA") } #! Further lines contain data used by VisualDCT #! View(257,0,0.8) #! Record("$(device):PLOG",1360,185,0,0,"$(device):PLOG") #! Field("$(device):PLOG.INPA",16777215,0,"$(device):PLOG.INPA") #! Link("$(device):PLOG.INPA","$(device):PLOG/INPA") #! Connector("$(device):PLOG/INPA","$(device):PMON.VAL",1240,410,16777215,"",0) #! Record("$(device):P",20,10,0,0,"$(device):P") #! Field("$(device):P.INPA",16777215,1,"$(device):P.INPA") #! Link("$(device):P.INPA","$(device):PMON.VAL") #! Record("$(device):PADEL",1360,439,0,1,"$(device):PADEL") #! Field("$(device):PADEL.INPA",16777215,0,"$(device):PADEL.INPA") #! Link("$(device):PADEL.INPA","$(device):PADEL/INPA") #! Field("$(device):PADEL.OUT",16777215,0,"$(device):PADEL.OUT") #! Link("$(device):PADEL.OUT","$(device):PMON.ADEL") #! Connector("$(device):PADEL/INPA","$(device):PMON.VAL",1240,530,16777215,"",0) #! Record("$(device):PSTATENABLE_1",260,23,0,0,"$(device):PSTATENABLE_1") #! Record("$(device):PSTATENABLE_2",500,23,0,0,"$(device):PSTATENABLE_2") #! Record("$(device):PSTATSPRBCK_1",740,19,0,0,"$(device):PSTATSPRBCK_1") #! Record("$(device):HYSTSPRBCK_1",980,19,0,0,"$(device):HYSTSPRBCK_1") #! Record("$(device):PSTATSPRBCK_2",1220,19,0,0,"$(device):PSTATSPRBCK_2") #! Record("$(device):HYSTSPRBCK_2",1460,19,0,0,"$(device):HYSTSPRBCK_2") #! Record("$(device):PSTATSPDIR_1",1700,19,0,0,"$(device):PSTATSPDIR_1") #! Record("$(device):PSTATSPDIR_2",1940,19,0,0,"$(device):PSTATSPDIR_2") #! Record("$(device):PSTAT_1",2180,17,0,0,"$(device):PSTAT_1") #! Field("$(device):PSTAT_1.FLNK",16777215,1,"$(device):PSTAT_1.FLNK") #! Link("$(device):PSTAT_1.FLNK","$(device):PSTAT_2") #! Field("$(device):PSTAT_1.VAL",16777215,1,"$(device):PSTAT_1.VAL") #! Record("$(device):PSTAT_2",2420,25,0,1,"$(device):PSTAT_2") #! Field("$(device):PSTAT_2.VAL",16777215,0,"$(device):PSTAT_2.VAL") #! Record("$(device):PSTAT_CALC",2660,27,0,0,"$(device):PSTAT_CALC") #! Field("$(device):PSTAT_CALC.INPA",16777215,0,"$(device):PSTAT_CALC.INPA") #! Link("$(device):PSTAT_CALC.INPA","$(device):PSTAT_1.VAL") #! Field("$(device):PSTAT_CALC.INPB",16777215,0,"$(device):PSTAT_CALC.INPB") #! Link("$(device):PSTAT_CALC.INPB","$(device):PSTAT_2.VAL") #! Field("$(device):PSTAT_CALC.FLNK",16777215,1,"$(device):PSTAT_CALC.FLNK") #! Link("$(device):PSTAT_CALC.FLNK","$(device):PSTAT_SUM") #! Field("$(device):PSTAT_CALC.VAL",16777215,0,"$(device):PSTAT_CALC.VAL") #! Record("$(device):PSTAT_SUM",2900,19,0,1,"$(device):PSTAT_SUM") #! Field("$(device):PSTAT_SUM.INP",16777215,0,"$(device):PSTAT_SUM.INP") #! Link("$(device):PSTAT_SUM.INP","$(device):PSTAT_CALC.VAL") #! Record("$(device):STATE",340,3,0,0,"$(device):STATE") #! Field("$(device):STATE.FLNK",16777215,1,"$(device):STATE.FLNK") #! Link("$(device):STATE.FLNK","$(device):STATUS/FLNK") #! Connector("$(device):STATUS/FLNK","$(device):STATUSCALC",560,400,16777215,"",0) #! Record("$(device):PMON",960,203,0,0,"$(device):PMON") #! Field("$(device):PMON.NVL",16777215,0,"$(device):PMON.NVL") #! Link("$(device):PMON.NVL","$(device):STATUSCALC.VAL") #! Field("$(device):PMON.INPA",16777215,0,"$(device):PMON.INPA") #! Link("$(device):PMON.INPA","$(device):PMONRAW.VAL") #! Field("$(device):PMON.FLNK",16777215,1,"$(device):PMON.FLNK") #! Link("$(device):PMON.FLNK","$(device):P/FLNK") #! Field("$(device):PMON.VAL",16777215,1,"$(device):PMON.VAL") #! Field("$(device):PMON.ADEL",16777215,1,"$(device):PMON.ADEL") #! Connector("$(device):P/FLNK","$(device):PLOG",1180,356,16777215,"",0) #! Field("$(device):PMON.INPB",16777215,0,"$(device):PMON.INPB") #! Link("$(device):PMON.INPB","$(device):PMONRAW.VAL") #! Record("$(device):STATUSCALC",640,162,0,0,"$(device):STATUSCALC") #! Field("$(device):STATUSCALC.INPA",16777215,0,"$(device):STATUSCALC.INPA") #! Link("$(device):STATUSCALC.INPA","$(device):STATUSCALC/INPA") #! Field("$(device):STATUSCALC.FLNK",16777215,1,"$(device):STATUSCALC.FLNK") #! Link("$(device):STATUSCALC.FLNK","$(device):PMON") #! Field("$(device):STATUSCALC.VAL",16777215,1,"$(device):STATUSCALC.VAL") #! Connector("$(device):STATUSCALC/INPA","$(device):PMONRAW.VAL",580,450,16777215,"",0) #! Record("$(device):PMONRAW",640,437,0,1,"$(device):PMONRAW") #! Field("$(device):PMONRAW.VAL",16777215,1,"$(device):PMONRAW.VAL") #! Field("$(device):PMONRAW.FLNK",16777215,0,"$(device):PMONRAW.FLNK") #! Link("$(device):PMONRAW.FLNK","$(device):STATUSCALC") #! Record("$(device):STATUS",3140,15,0,0,"$(device):STATUS") #! Field("$(device):STATUS.VAL",16777215,0,"$(device):STATUS.VAL") #! Record("$(device):STATUSOUT",3380,27,0,0,"$(device):STATUSOUT") #! Field("$(device):STATUSOUT.DOL",16777215,0,"$(device):STATUSOUT.DOL") #! Link("$(device):STATUSOUT.DOL","$(device):STATUS.VAL") #! Field("$(device):STATUSOUT.PROC",16777215,0,"$(device):STATUSOUT.PROC") #! Record("$(device):STATUSCALC2",3620,13,0,0,"$(device):STATUSCALC2") #! Field("$(device):STATUSCALC2.OUT",16777215,0,"$(device):STATUSCALC2.OUT") #! Link("$(device):STATUSCALC2.OUT","$(device):STATUSOUT.PROC") #! Field("$(device):STATUSCALC2.INPA",16777215,0,"$(device):STATUSCALC2.INPA") #! Link("$(device):STATUSCALC2.INPA","$(device):STATUSMON.VAL") #! Record("$(device):STATUSMON",340,663,0,1,"$(device):STATUSMON") #! Field("$(device):STATUSMON.FLNK",16777215,1,"$(device):STATUSMON.FLNK") #! Link("$(device):STATUSMON.FLNK","$(device):STATUSCALC2") #! Field("$(device):STATUSMON.VAL",16777215,1,"$(device):STATUSMON.VAL") #! Record("$(device):PSTATALL",3860,13,0,0,"$(device):PSTATALL") #! Field("$(device):PSTATALL.FLNK",16777215,1,"$(device):PSTATALL.FLNK") #! Link("$(device):PSTATALL.FLNK","$(device):PSTATENALL") #! Record("$(device):PSTATENALL",4100,22,0,1,"$(device):PSTATENALL") #! Record("$(device):UNITRAW",4340,27,0,0,"$(device):UNITRAW") #! Field("$(device):UNITRAW.VAL",16777215,0,"$(device):UNITRAW.VAL") #! Record("$(device):UNIT",4580,22,0,0,"$(device):UNIT") #! Field("$(device):UNIT.INP",16777215,0,"$(device):UNIT.INP") #! Link("$(device):UNIT.INP","$(device):UNITRAW.VAL") #! Record("$(device):VERSIONRAW",20,387,0,0,"$(device):VERSIONRAW") #! Field("$(device):VERSIONRAW.VAL",16777215,0,"$(device):VERSIONRAW.VAL") #! Record("$(device):VERSION",260,382,0,0,"$(device):VERSION") #! Field("$(device):VERSION.INP",16777215,0,"$(device):VERSION.INP") #! Link("$(device):VERSION.INP","$(device):VERSIONRAW.VAL") #! Record("$(device):SENSOR_A",500,380,0,0,"$(device):SENSOR_A") #! Record("$(device):SENSOR_B",740,380,0,0,"$(device):SENSOR_B") #! Record("$(device):SENSOR_C",980,380,0,0,"$(device):SENSOR_C") #! Record("$(device):MODTYPE_A",1220,383,0,0,"$(device):MODTYPE_A") #! Record("$(device):MODTYPE_B",1460,383,0,0,"$(device):MODTYPE_B") #! Record("$(device):MODTYPE_C",1700,383,0,0,"$(device):MODTYPE_C")