#! Generated by VisualDCT v2.5 #! DBDSTART #! DBDEND # #% archiver 1 Monitor # record(calc, "$(device):PLOG") { field(DESC, "log Pressure") field(EGU, "log") field(CALC, "LOG(A)") field(INPA, "$(device):PMON.VAL") field(HOPR, "3") field(LOPR, "-3") field(ADEL, "0.025") field(FLNK, "$(device):PSTATMON") } record(calc, "$(device):STATUSCALC") { field(CALC, "A<=1?0:1") field(INPA, "$(device):STATE.VAL") field(FLNK, "$(device):PMON") } # % archiver 10 Monitor record(mbbo, "$(device):PSTATEN") { field(DESC, "Enable Relay Setpoint") field(FLNK, "$(device):PSTATENSEQ") field(ZRST, "Force On I/L") field(ONST, "I/L Operating") field(ZRVL, "1") field(ONVL, "2") field(ZRSV, "MAJOR") field(ONSV, "NO_ALARM") field(DOL, "1") field(ASG, "MCC") } ################################################################################ # Relay - Ion Pump Interlock # #% archiver 10 Monitor # record(ao, "$(device):PSTATSPDES") { field(DESC, "Ion Pump I/L") field(FLNK, "$(device):PSTATSPSEQ") field(EGU, "mbar") field(PREC, "1") field(HOPR, "1.2e2") field(LOPR, "2.7e-3") field(DRVH, "1.2e2") field(DRVL, "2.7e-3") field(DOL, "1.0e-2") field(ASG, "MCC") } record(seq, "$(device):PSTATENSEQ") { field(DESC, "Sequence Relay Setpoint") field(SELM, "Specified") field(SELL, "$(device):PSTATEN.RVAL") field(DOL1, "0") field(LNK1, "$(device):PSTATENOUT.VAL PP") field(DOL2, "$(device):PSTATSPDES.VAL") field(LNK2, "$(device):PSTATSPOUT.VAL PP") } record(bo, "$(device):PSTATENOUT") { field(DESC, "Disable Relay Setpoint") field(DTYP, "stream") field(OUT, "@mks937a.proto.db dissp($(channel),RLY) $(port) 0") } record(ao, "$(device):PSTATSPOUT") { field(DESC, "Output Relay Setpoint") field(DTYP, "stream") field(OUT, "@mks937a.proto.db setsp($(channel),RLY) $(port) 0") } # #% archiver 10 Monitor #% controldesk Ion Pump Interlock readback # record(ai, "$(device):PSTATSPRBCK") { field(DESC, "Ion Pump I/L") field(DTYP, "stream") field(INP, "@mks937a.proto.db getsp($(channel),RLY) $(port) 0") field(SCAN, "1 second") field(EGU, "mbar") field(PREC, "1") field(HOPR, "1.2e2") field(LOPR, "2.7e-3") field(HIHI, "1.0e3") field(LOLO, "2.6e-3") field(HIGH, "1.1e-2") field(LOW, "9.0e-3") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(FLNK, "$(device):PSTATENCALC2") } record(seq, "$(device):PSTATSPSEQ") { field(DESC, "Sequence Relay Setpoint") field(SELM, "Specified") field(SELL, "$(device):PSTATENRBCK") field(DOL1, "$(device):PSTATSPDES") field(LNK1, "$(device):PSTATSPOUT PP") } record(calc, "$(device):PSTATENCALC2") { field(FLNK, "$(device):PSTATENRBCK") field(CALC, "A=0.0E-5?0:A>0.0E-5?1:2") field(INPA, "$(device):PSTATSPRBCK") } record(bi, "$(device):PSTATENRBCK") { field(INP, "$(device):PSTATENCALC2") field(ZNAM, "Disabled") field(ONAM, "Enabled") } record(calcout, "$(device):PADEL") { field(DESC, "deadband") field(CALC, "A/B") field(OUT, "$(device):PMON.ADEL") field(INPA, "$(device):PMON.VAL") field(INPB, "20") field(SCAN, "10 second") } record(bi, "$(device):PSTATMON") { field(DTYP, "stream") field(INP, "@mks937a.proto.db relaystat$(channel) $(port) 0") field(ZNAM, "Faulted") field(ONAM, "OK") } # mks937aPirg.db # Template database for a pirani guage connected to # one channel of an MKS937A Multi-Sensor System # Pete Owens - 29/8/03 # # This file is the same as mks937a-peng.db without the # record for enabling a cold cathode # # substitutions: # device - device name # port - serial port (steam device code ie /ty/0/1 => ty_0_1) # channel - MKS 937A channel number (1-4) # ############################################################################## # Status # # % archiver 10 Monitor # % controldesk Pressure smon record(mbbi, "$(device):STATE") { field(DTYP, "stream") field(INP, "@mks937a.proto.db state($(channel)) $(port) 0") field(DESC, "Status") field(SCAN, "1 second") field(FLNK, "$(device):STATUSCALC") field(ZRST, "OK") field(ONST, "OK") field(TWST, "Above Range") field(THST, "At Atmosphere") field(FRST, "Low Emission") field(FVST, "Filament Off") field(SXST, "HV Off") field(SVST, "Startup Delay") field(EIST, "Below Range") field(NIST, "Controlled") field(TEST, "Protected State") field(ELST, "No Gauge") field(TVST, "Not Connected") field(TTST, "Wrong Gauge") field(FTST, "Bad Command") field(FFST, "Locked Out") field(UNSV, "MAJOR") field(ZRSV, "NO_ALARM") field(ONSV, "NO_ALARM") field(TWSV, "MINOR") field(THSV, "MINOR") field(FRSV, "MAJOR") field(FVSV, "MAJOR") field(SXSV, "MAJOR") field(SVSV, "MINOR") field(EISV, "NO_ALARM") field(NISV, "MINOR") field(TESV, "MINOR") field(ELSV, "MAJOR") field(TVSV, "MAJOR") field(TTSV, "MAJOR") field(FTSV, "MAJOR") field(FFSV, "MAJOR") } record(sel, "$(device):PMON") { field(SELM, "Specified") field(NVL, "$(device):STATUSCALC") field(INPA, "$(device):PMONRAW.VAL PP") field(INPB, "0") field(DESC, "Pressure") field(FLNK, "$(device):PLOG") field(PREC, "11") field(EGU, "Torr") field(HOPR, "1000") field(LOPR, "0") } ################################################################################ # Pressure # #% archiver 1 Monitor #% controldesk Pressure readback # record(ai, "$(device):PMONRAW") { field(DESC, "Pressure") field(DTYP, "stream") field(INP, "@mks937a.proto.db pressure($(channel)) $(port) 0") field(EGU, "mbar") field(PREC, "3") field(HOPR, "1000") field(LOPR, "0") } record(mbbi, "$(device):STATUSMON") { field(DTYP, "stream") field(INP, "@mks937a.proto.db status($(channel)) $(port) 0") field(DESC, "Status") field(SCAN, "1 second") field(ZRST, "OK") field(ONST, "OK") field(TWST, "Above Range") field(THST, "At Atmosphere") field(FRST, "Low Emission") field(FVST, "Filament Off") field(SXST, "HV Off") field(SVST, "Startup Delay") field(EIST, "Below Range") field(NIST, "Controlled") field(TEST, "Protected State") field(ELST, "No Gauge") field(TVST, "Not Connected") field(TTST, "Wrong Gauge") field(FTST, "Bad Command") field(FFST, "Locked Out") field(UNSV, "MAJOR") field(ZRSV, "NO_ALARM") field(ONSV, "NO_ALARM") field(TWSV, "MINOR") field(THSV, "MINOR") field(FRSV, "MAJOR") field(FVSV, "MAJOR") field(SXSV, "MAJOR") field(SVSV, "MINOR") field(EISV, "NO_ALARM") field(NISV, "MINOR") field(TESV, "MINOR") field(ELSV, "MAJOR") field(TVSV, "MAJOR") field(TTSV, "MAJOR") field(FTSV, "MAJOR") field(FFSV, "MAJOR") } #! Further lines contain data used by VisualDCT #! View(1723,113,0.9) #! Record("$(device):PLOG",1400,630,0,0,"$(device):PLOG") #! Field("$(device):PLOG.INPA",16777215,0,"$(device):PLOG.INPA") #! Link("$(device):PLOG.INPA","$(device):PLOG/INPA") #! Field("$(device):PLOG.FLNK",16777215,1,"$(device):PLOG.FLNK") #! Link("$(device):PLOG.FLNK","$(device):PSTATMON") #! Connector("$(device):PLOG/INPA","$(device):PMON.VAL",1320,940,16777215,"",0) #! Record("$(device):STATUSCALC",340,862,0,0,"$(device):STATUSCALC") #! Field("$(device):STATUSCALC.FLNK",16777215,1,"$(device):STATUSCALC.FLNK") #! Link("$(device):STATUSCALC.FLNK","$(device):PMON") #! Field("$(device):STATUSCALC.INPA",16777215,0,"$(device):STATUSCALC.INPA") #! Link("$(device):STATUSCALC.INPA","$(device):STATE.VAL") #! Field("$(device):STATUSCALC.VAL",16777215,1,"$(device):STATUSCALC.VAL") #! Record("$(device):PSTATEN",2520,143,0,0,"$(device):PSTATEN") #! Field("$(device):PSTATEN.FLNK",16777215,1,"$(device):PSTATEN.FLNK") #! Link("$(device):PSTATEN.FLNK","$(device):PSTATEN/FLNK") #! Field("$(device):PSTATEN.RVAL",16777215,1,"$(device):PSTATEN.RVAL") #! Connector("$(device):PSTATEN/FLNK","$(device):PSTATENSEQ",2800,316,16777215,"",0) #! Record("$(device):PSTATSPDES",2520,423,0,0,"$(device):PSTATSPDES") #! Field("$(device):PSTATSPDES.VAL",16777215,1,"$(device):PSTATSPDES.VAL") #! Field("$(device):PSTATSPDES.FLNK",16777215,1,"$(device):PSTATSPDES.FLNK") #! Link("$(device):PSTATSPDES.FLNK","$(device):PSTATSPSEQ") #! Record("$(device):PSTATENSEQ",2900,205,0,0,"$(device):PSTATENSEQ") #! Field("$(device):PSTATENSEQ.SELL",16777215,0,"$(device):PSTATENSEQ.SELL") #! Link("$(device):PSTATENSEQ.SELL","$(device):PSTATEN.RVAL") #! Field("$(device):PSTATENSEQ.LNK1",16777215,1,"$(device):PSTATENSEQ.LNK1") #! Link("$(device):PSTATENSEQ.LNK1","$(device):PSTATENOUT.VAL") #! Field("$(device):PSTATENSEQ.DOL2",16777215,0,"$(device):PSTATENSEQ.DOL2") #! Link("$(device):PSTATENSEQ.DOL2","$(device):RLY:SEQ/DOL2") #! Field("$(device):PSTATENSEQ.LNK2",16777215,1,"$(device):PSTATENSEQ.LNK2") #! Link("$(device):PSTATENSEQ.LNK2","$(device):PSTATSPOUT.VAL") #! Connector("$(device):RLY:SEQ/DOL2","$(device):PSTATSPDES.VAL",2800,520,16777215,"",0) #! Record("$(device):PSTATENOUT",3200,282,0,0,"$(device):PSTATENOUT") #! Field("$(device):PSTATENOUT.VAL",16777215,0,"$(device):PSTATENOUT.VAL") #! Record("$(device):PSTATSPOUT",3200,482,0,0,"$(device):PSTATSPOUT") #! Field("$(device):PSTATSPOUT.VAL",16777215,0,"$(device):PSTATSPOUT.VAL") #! Record("$(device):PSTATSPRBCK",1960,504,0,0,"$(device):PSTATSPRBCK") #! Field("$(device):PSTATSPRBCK.FLNK",16777215,1,"$(device):PSTATSPRBCK.FLNK") #! Link("$(device):PSTATSPRBCK.FLNK","$(device):PSTATENCALC2") #! Field("$(device):PSTATSPRBCK.VAL",16777215,1,"$(device):PSTATSPRBCK.VAL") #! Record("$(device):PSTATSPSEQ",2900,594,0,0,"$(device):PSTATSPSEQ") #! Field("$(device):PSTATSPSEQ.DOL1",16777215,0,"$(device):PSTATSPSEQ.DOL1") #! Link("$(device):PSTATSPSEQ.DOL1","$(device):PSTATSPSEQ/DOL1") #! Field("$(device):PSTATSPSEQ.LNK1",16777215,1,"$(device):PSTATSPSEQ.LNK1") #! Link("$(device):PSTATSPSEQ.LNK1","$(device):PSTATSPOUT.VAL") #! Field("$(device):PSTATSPSEQ.SELL",16777215,0,"$(device):PSTATSPSEQ.SELL") #! Link("$(device):PSTATSPSEQ.SELL","$(device):PSTATSPSEQ/SELL") #! Connector("$(device):PSTATSPSEQ/DOL1","$(device):PSTATSPDES.VAL",2800,680,16777215,"",0) #! Connector("$(device):PSTATSPSEQ/SELL","$(device):PSTATENRBCK.VAL",2800,850,16777215,"",0) #! Record("$(device):PSTATENCALC2",2240,762,0,0,"$(device):PSTATENCALC2") #! Field("$(device):PSTATENCALC2.FLNK",16777215,1,"$(device):PSTATENCALC2.FLNK") #! Link("$(device):PSTATENCALC2.FLNK","$(device):PSTATENRBCK") #! Field("$(device):PSTATENCALC2.INPA",16777215,0,"$(device):PSTATENCALC2.INPA") #! Link("$(device):PSTATENCALC2.INPA","$(device):PSTATSPRBCK.VAL") #! Field("$(device):PSTATENCALC2.VAL",16777215,1,"$(device):PSTATENCALC2.VAL") #! Record("$(device):PSTATENRBCK",2520,802,0,0,"$(device):PSTATENRBCK") #! Field("$(device):PSTATENRBCK.INP",16777215,0,"$(device):PSTATENRBCK.INP") #! Link("$(device):PSTATENRBCK.INP","$(device):PSTATENCALC2.VAL") #! Field("$(device):PSTATENRBCK.VAL",16777215,1,"$(device):PSTATENRBCK.VAL") #! Record("$(device):PADEL",1400,899,0,0,"$(device):PADEL") #! Field("$(device):PADEL.INPA",16777215,0,"$(device):PADEL.INPA") #! Link("$(device):PADEL.INPA","$(device):PMON.VAL") #! Field("$(device):PADEL.OUT",16777215,0,"$(device):PADEL.OUT") #! Link("$(device):PADEL.OUT","$(device):PMON.ADEL") #! Record("$(device):PSTATMON",1660,767,0,0,"$(device):PSTATMON") #! Record("$(device):STATE",20,366,0,0,"$(device):STATE") #! Field("$(device):STATE.FLNK",16777215,1,"$(device):STATE.FLNK") #! Link("$(device):STATE.FLNK","$(device):STATUSCALC") #! Field("$(device):STATE.VAL",16777215,1,"$(device):STATE.VAL") #! Record("$(device):PMON",1000,803,0,0,"$(device):PMON") #! Field("$(device):PMON.NVL",16777215,0,"$(device):PMON.NVL") #! Link("$(device):PMON.NVL","$(device):STATUSCALC.VAL") #! Field("$(device):PMON.INPA",16777215,0,"$(device):PMON.INPA") #! Link("$(device):PMON.INPA","$(device):PMONRAW.VAL") #! Field("$(device):PMON.FLNK",16777215,1,"$(device):PMON.FLNK") #! Link("$(device):PMON.FLNK","$(device):P2/FLNK") #! Field("$(device):PMON.VAL",16777215,1,"$(device):PMON.VAL") #! Field("$(device):PMON.ADEL",16777215,1,"$(device):PMON.ADEL") #! Connector("$(device):P2/FLNK","$(device):PLOG",1220,882,16777215,"",0) #! Record("$(device):PMONRAW",600,1025,0,0,"$(device):PMONRAW") #! Field("$(device):PMONRAW.VAL",16777215,1,"$(device):PMONRAW.VAL") #! Record("$(device):STATUSMON",40,1180,0,1,"$(device):STATUSMON")