#! Generated by VisualDCT v2.6 #! DBDSTART #! DBD("../../dbd/vac.dbd") #! DBDEND record(mbbi, "$(PUMP):OP_MODE") { field(DESC, "Pump Online/Offline/Maint. Mode") field(SCAN, "Passive") field(PINI, "1") field(VAL, "0") field(ZRST, "Online") field(ONST, "Offline") field(TWST, "Maintenance") field(ZRSV, "NO_ALARM") field(ONSV, "MINOR") field(TWSV, "MINOR") info(autosaveFields_pass0, "VAL") } record(calc, "$(PUMP):OP_MODE_CALC") { field(DESC, "CALC: DISA for Other Recs") field(CALC, "A>0?1:A") field(INPA, "$(PUMP):OP_MODE CP") } record(bi, "$(PUMP):IS_RUNNING") { field(DESC, "Back Pump (DP) state") field(SCAN, "2 second") field(DTYP, "stream") field(INP, "@kashiyama-pc80.proto.db isRunning $(port)") field(ZNAM, "Stopped") field(ONAM, "Running") field(OSV, "NO_ALARM") field(ZSV, "MAJOR") field(DISV, "1") field(SDIS, "$(PUMP):OP_MODE_CALC") field(DISS, "NO_ALARM") } record(mbbi, "$(PUMP):COM_ERROR") { field(DESC, "Protocol errors from pump") field(SCAN, "I/O Intr") field(DTYP, "stream") field(INP, "@kashiyama-pc80.proto.db endCode $(port)") field(ZRST, "Normal") field(ONST, "FCS Error") field(TWST, "Format Error") field(THST, "Entry out of range") field(FRST, "Frame Length Error") field(FVST, "FCS Error 2") field(SXST, "Frame Length Error 2") field(ZRSV, "NO_ALARM") field(ONSV, "INVALID") field(TWSV, "INVALID") field(THSV, "INVALID") field(FRSV, "INVALID") field(FVSV, "INVALID") field(SXSV, "INVALID") field(DISV, "1") field(SDIS, "$(PUMP):OP_MODE_CALC") field(DISS, "NO_ALARM") } record(bi, "$(PUMP):IS_WARNING") { field(DESC, "Warning state") field(SCAN, "1 second") field(DTYP, "stream") field(INP, "@kashiyama-pc80.proto.db isWarning $(port)") field(ZNAM, "Normal") field(ONAM, "Warning") field(FLNK, "$(PUMP):STATUS_CODE PP MS") field(OSV, "MINOR") field(DISV, "1") field(SDIS, "$(PUMP):OP_MODE_CALC") field(DISS, "NO_ALARM") } record(bi, "$(PUMP):IS_ALARM") { field(DESC, "Alarm state") field(SCAN, "1 second") field(DTYP, "stream") field(INP, "@kashiyama-pc80.proto.db isAlarm $(port)") field(ZNAM, "Normal") field(ONAM, "Alarm") field(FLNK, "$(PUMP):STATUS_CODE PP MS") field(OSV, "MAJOR") field(DISV, "1") field(SDIS, "$(PUMP):OP_MODE_CALC") field(DISS, "NO_ALARM") } record(bi, "$(PUMP):FORE_IS_RUNNING") { field(DESC, "Fore pump (MBP) state") field(SCAN, "1 second") field(DTYP, "stream") field(INP, "@kashiyama-pc80.proto.db isForeRunning $(port)") field(ZNAM, "Stopped") field(ONAM, "Running") field(OSV, "NO_ALARM") field(ZSV, "MAJOR") field(DISV, "1") field(SDIS, "$(PUMP):OP_MODE_CALC") field(DISS, "NO_ALARM") } record(bi, "$(PUMP):IS_REMOTE") { field(DESC, "Remote/Local control") field(SCAN, "2 second") field(DTYP, "stream") field(INP, "@kashiyama-pc80.proto.db isRemote $(port)") field(ZNAM, "Local") field(ONAM, "Remote") field(DISV, "1") field(SDIS, "$(PUMP):OP_MODE_CALC") field(DISS, "NO_ALARM") } record(bi, "$(PUMP):IS_EMO") { field(DESC, "Look this up") field(SCAN, "Passive") field(DTYP, "stream") field(INP, "@kashiyama-pc80.proto.db isEMO $(port)") field(ZNAM, "Normal") field(ONAM, "EMO") field(DISV, "1") field(SDIS, "$(PUMP):OP_MODE_CALC") field(DISS, "NO_ALARM") } record(calcout, "$(PUMP):STATUS_CODE") { field(DESC, "See table to decode") field(SCAN, "1 second") field(DTYP, "stream") field(INPA, "$(PUMP):IS_ALARM MS") field(INPB, "$(PUMP):IS_WARNING MS") field(OUT, "@kashiyama-pc80.proto.db statusCode $(port)") field(DISV, "1") field(SDIS, "$(PUMP):OP_MODE_CALC") field(DISS, "NO_ALARM") } record(ai, "$(PUMP):BACK_CURRENT") { field(DESC, "Back Pump (DP) current") field(SCAN, ".5 second") field(DTYP, "stream") field(INP, "@kashiyama-pc80.proto.db backCurrent $(port)") field(LINR, "LINEAR") field(ASLO, "0.1") field(EGUL, "0") field(EGU, "A") field(HIHI, "11.6") field(HHSV, "MAJOR") field(PREC, "1") field(HOPR, "15.0") field(LOPR, "0.0") field(MDEL, "0.1") field(DISV, "1") field(SDIS, "$(PUMP):OP_MODE_CALC") field(DISS, "NO_ALARM") } record(ai, "$(PUMP):BACK_TEMP") { field(DESC, "Back Pump (DP) temperature") field(SCAN, "5 second") field(DTYP, "stream") field(INP, "@kashiyama-pc80.proto.db backTemp $(port)") field(EGU, "C") field(HOPR, "500.0") field(LOPR, "0.0") field(DISV, "1") field(SDIS, "$(PUMP):OP_MODE_CALC") field(DISS, "NO_ALARM") } record(ai, "$(PUMP):BACK_WATER") { field(DESC, "Back Pump (DP) cooling water") field(SCAN, "5 second") field(DTYP, "stream") field(INP, "@kashiyama-pc80.proto.db backWater $(port)") field(LINR, "LINEAR") field(ASLO, "0.1") field(EGUL, "0") field(EGU, "L/min") field(LOLO, "2") field(LLSV, "MAJOR") field(PREC, "1") field(HOPR, "23.1") field(LOPR, "0.5") field(DISV, "1") field(SDIS, "$(PUMP):OP_MODE_CALC") field(DISS, "NO_ALARM") } record(ai, "$(PUMP):BACK_PRESSURE_KPA") { field(DESC, "Back Pump (DP) back pressure") field(SCAN, "10 second") field(DTYP, "stream") field(INP, "@kashiyama-pc80.proto.db backPressure $(port)") field(EGU, "kPa") field(HOPR, "200.0") field(LOPR, "4.0") field(DISV, "1") field(SDIS, "$(PUMP):OP_MODE_CALC") field(DISS, "NO_ALARM") } record(calc, "$(PUMP):BACK_PRESSURE") { field(DESC, "kPa to torr") field(EGU, "torr") field(CALC, "A*7.5") field(INPA, "$(PUMP):BACK_PRESSURE_KPA CP MS") field(PREC, "1") field(HOPR, "1500.0") field(LOPR, "30.0") field(DISV, "1") field(SDIS, "$(PUMP):OP_MODE_CALC") field(DISS, "NO_ALARM") } record(ai, "$(PUMP):BACK_N2") { field(DESC, "Back Pump (DP) N2 purge flow") field(SCAN, "10 second") field(DTYP, "stream") field(INP, "@kashiyama-pc80.proto.db backN2 $(port)") field(LINR, "LINEAR") field(ASLO, "0.1") field(EGUL, "0") field(EGU, "SLM") field(PREC, "1") field(HOPR, "20.0") field(LOPR, "0.3") field(DISV, "1") field(SDIS, "$(PUMP):OP_MODE_CALC") field(DISS, "NO_ALARM") } record(ai, "$(PUMP):FORE_CURRENT") { field(DESC, "Fore Pump (MBP) current") field(SCAN, ".5 second") field(DTYP, "stream") field(INP, "@kashiyama-pc80.proto.db foreCurrent $(port)") field(LINR, "LINEAR") field(ASLO, "0.1") field(EGUL, "0") field(EGU, "A") field(HIHI, "11.6") field(HHSV, "MAJOR") field(PREC, "1") field(HOPR, "15.0") field(LOPR, "0.0") field(MDEL, "0.1") field(DISV, "1") field(SDIS, "$(PUMP):OP_MODE_CALC") field(DISS, "NO_ALARM") } record(ai, "$(PUMP):BACK_SPEED") { field(DESC, "Back Pump (DP) speed") field(SCAN, ".5 second") field(DTYP, "stream") field(INP, "@kashiyama-pc80.proto.db backSpeed $(port)") field(EGU, "rpm") field(HOPR, "7000.0") field(LOPR, "0.0") field(HIHI, "7100") field(HHSV, "MAJOR") field(HIGH, "7000") field(HSV, "MINOR") field(LOW, "1000") field(LSV, "MINOR") field(LOLO, "100") field(LLSV, "MAJOR") field(MDEL, "1.0") field(DISV, "1") field(SDIS, "$(PUMP):OP_MODE_CALC") field(DISS, "NO_ALARM") } record(ai, "$(PUMP):FORE_SPEED") { field(DESC, "Fore Pump (MBP) speed ") field(SCAN, ".5 second") field(DTYP, "stream") field(INP, "@kashiyama-pc80.proto.db foreSpeed $(port)") field(EGU, "rpm") field(HOPR, "7000.0") field(LOPR, "0.0") field(HIHI, "7100") field(HHSV, "MAJOR") field(HIGH, "7000") field(HSV, "MINOR") field(LOW, "1000") field(LSV, "MINOR") field(LOLO, "100") field(LLSV, "MAJOR") field(MDEL, "1.0") field(DISV, "1") field(SDIS, "$(PUMP):OP_MODE_CALC") field(DISS, "NO_ALARM") } record(ai, "$(PUMP):RUN_TIME_HIGH") { field(DESC, "High byte, x1000 Hrs") field(SCAN, "10 second") field(DTYP, "stream") field(INP, "@kashiyama-pc80.proto.db runTimeHigh $(port)") field(EGU, "Hrs") field(MDEL, "1.0") field(DISV, "1") field(SDIS, "$(PUMP):OP_MODE_CALC") field(DISS, "NO_ALARM") } record(ai, "$(PUMP):RUN_TIME_LOW") { field(DESC, "Low byte, x0.1 Hrs") field(SCAN, "10 second") field(DTYP, "stream") field(INP, "@kashiyama-pc80.proto.db runtimeLow $(port)") field(EGU, "Hrs") field(MDEL, "1.0") field(DISV, "1") field(SDIS, "$(PUMP):OP_MODE_CALC") field(DISS, "NO_ALARM") } record(calc, "$(PUMP):RUN_TIME") { field(DESC, "Pump running time") field(EGU, "Hrs") field(CALC, "A*1000 + B*0.1") field(INPA, "$(PUMP):RUN_TIME_HIGH CP MS") field(INPB, "$(PUMP):RUN_TIME_LOW CP MS") field(PREC, "1") field(DISV, "1") field(SDIS, "$(PUMP):OP_MODE_CALC") field(DISS, "NO_ALARM") } #! Further lines contain data used by VisualDCT #! View(0,0,0.8) #! Record("$(PUMP):IS_RUNNING",300,479,0,1,"$(PUMP):IS_RUNNING") #! Record("$(PUMP):COM_ERROR",100,410,0,1,"$(PUMP):COM_ERROR") #! Record("$(PUMP):IS_WARNING",60,10,0,1,"$(PUMP):IS_WARNING") #! Field("$(PUMP):IS_WARNING.FLNK",16777215,0,"$(PUMP):IS_WARNING.FLNK") #! Link("$(PUMP):IS_WARNING.FLNK","$(PUMP):STATUS_CODE") #! Field("$(PUMP):IS_WARNING.VAL",16777215,0,"$(PUMP):IS_WARNING.VAL") #! Record("$(PUMP):IS_ALARM",300,30,0,1,"$(PUMP):IS_ALARM") #! Field("$(PUMP):IS_ALARM.FLNK",16777215,0,"$(PUMP):IS_ALARM.FLNK") #! Link("$(PUMP):IS_ALARM.FLNK","$(PUMP):STATUS_CODE") #! Field("$(PUMP):IS_ALARM.VAL",16777215,1,"$(PUMP):IS_ALARM.VAL") #! Record("$(PUMP):FORE_IS_RUNNING",300,279,0,1,"$(PUMP):FORE_IS_RUNNING") #! Record("$(PUMP):IS_REMOTE",120,759,0,1,"$(PUMP):IS_REMOTE") #! Record("$(PUMP):IS_EMO",300,679,0,1,"$(PUMP):IS_EMO") #! Record("$(PUMP):STATUS_CODE",60,219,0,1,"$(PUMP):STATUS_CODE") #! Field("$(PUMP):STATUS_CODE.INPA",16777215,1,"$(PUMP):STATUS_CODE.INPA") #! Link("$(PUMP):STATUS_CODE.INPA","$(PUMP):IS_ALARM.VAL") #! Field("$(PUMP):STATUS_CODE.INPB",16777215,0,"$(PUMP):STATUS_CODE.INPB") #! Link("$(PUMP):STATUS_CODE.INPB","$(PUMP):IS_WARNING.VAL") #! Record("$(PUMP):BACK_CURRENT",500,487,0,1,"$(PUMP):BACK_CURRENT") #! Record("$(PUMP):BACK_TEMP",500,65,0,1,"$(PUMP):BACK_TEMP") #! Record("$(PUMP):BACK_WATER",500,240,0,1,"$(PUMP):BACK_WATER") #! Record("$(PUMP):BACK_PRESSURE_kPa",720,45,0,0,"$(PUMP):BACK_PRESSURE_kPa") #! Field("$(PUMP):BACK_PRESSURE_kPa.VAL",16777215,0,"$(PUMP):BACK_PRESSURE_kPa.VAL") #! Record("$(PUMP):BACK_PRESSURE_torr",960,45,0,0,"$(PUMP):BACK_PRESSURE_torr") #! Field("$(PUMP):BACK_PRESSURE_torr.INPA",16777215,0,"$(PUMP):BACK_PRESSURE_torr.INPA") #! Link("$(PUMP):BACK_PRESSURE_torr.INPA","$(PUMP):BACK_PRESSURE_kPa.VAL") #! Record("$(PUMP):BACK_N2",700,249,0,1,"$(PUMP):BACK_N2") #! Record("$(PUMP):FORE_CURRENT",700,487,0,1,"$(PUMP):FORE_CURRENT") #! Record("$(PUMP):BACK_SPEED",500,770,0,1,"$(PUMP):BACK_SPEED") #! Record("$(PUMP):FORE_SPEED",700,770,0,1,"$(PUMP):FORE_SPEED") #! Record("$(PUMP):RUN_TIME_HIGH",920,279,0,1,"$(PUMP):RUN_TIME_HIGH") #! Field("$(PUMP):RUN_TIME_HIGH.VAL",16777215,0,"$(PUMP):RUN_TIME_HIGH.VAL") #! Record("$(PUMP):RUN_TIME_LOW",920,679,0,1,"$(PUMP):RUN_TIME_LOW") #! Field("$(PUMP):RUN_TIME_LOW.VAL",16777215,0,"$(PUMP):RUN_TIME_LOW.VAL") #! Record("$(PUMP):RUN_TIME",980,459,0,1,"$(PUMP):RUN_TIME") #! Field("$(PUMP):RUN_TIME.INPA",16777215,0,"$(PUMP):RUN_TIME.INPA") #! Link("$(PUMP):RUN_TIME.INPA","$(PUMP):RUN_TIME_HIGH.VAL") #! Field("$(PUMP):RUN_TIME.INPB",16777215,0,"$(PUMP):RUN_TIME.INPB") #! Link("$(PUMP):RUN_TIME.INPB","$(PUMP):RUN_TIME_LOW.VAL")