#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(ai, "$(GAUGE):PRAW") {
  field(DESC, "Gauge Pressure in Volts")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC) $(PRAW)")
  field(FLNK, "$(GAUGE):P")
  field(EGU, "V")
}

record(calc, "$(GAUGE):P") {
  field(CALC, "10^(B - 4)")
  field(INPB, "$(GAUGE):PRAW.VAL PP")
  field(EGU, "TORR")
  field(PREC, "2")
}


record(bi, "$(GAUGE):PSTAT") {
  field(DESC, "Process set point 1")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@$(PLC) $(PSTAT)")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("$(GAUGE):PRAW",20,19,0,1,"$(GAUGE):PRAW")
#! Field("$(GAUGE):PRAW.FLNK",16777215,1,"$(GAUGE):PRAW.FLNK")
#! Link("$(GAUGE):PRAW.FLNK","$(GAUGE):P")
#! Field("$(GAUGE):PRAW.VAL",16777215,1,"$(GAUGE):PRAW.VAL")
#! Record("$(GAUGE):P",340,87,0,0,"$(GAUGE):P")
#! Field("$(GAUGE):P.INPB",16777215,0,"$(GAUGE):P.INPB")
#! Link("$(GAUGE):P.INPB","$(GAUGE):PRAW.VAL")
#! Record("$(GAUGE):PSTAT",20,271,0,1,"$(GAUGE):PSTAT")