## Database for MKS Microvision RGA ## Substitutions: ## Pri - Primary system ## Sec - Secondary system ## PORT - IP or Serial port name # Get sensor information record(mbbi, "$(PRI):$(SEC):$(POS):SENSOR_STS") { field(DESC, "Sensor Status") field(DTYP, "stream") field(INP, "@mks_rga_common.proto.db sensors($(PRI),$(SEC),$(POS)) $(PORT)") field(PINI, "1") field(ZRST, "InUse") field(ONST, "Ready") field(TWST, "Config") field(THST, "ERROR") } record(stringin, "$(PRI):$(SEC):$(POS):SENSOR_SRLNO_I") { field(DESC, "Serial Number") } record(stringin, "$(PRI):$(SEC):$(POS):SENSOR_NAME_I") { field(DESC, "Sensor Name") } #USE FOR MANUALLY ENTERING SERIAL NUMBER record(stringout, "$(PRI):$(SEC):$(POS):SELECTSENSOR") { field(DESC, "Slct Snsr by SN") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db sensorsSelect($(PRI),$(SEC),$(POS),$(SERIALNUM)) $(PORT)") } # Select Sensor record(mbbi, "$(PRI):$(SEC):$(POS):SENSOR_SELECT") { field(DESC, "Sensor Name") field(PINI, "1") field(DTYP, "stream") field(INP, "@mks_rga_common.proto.db sensorsSelect($(PRI),$(SEC),$(POS),$(SERIALNUM)) $(PORT)") field(ZRST, "InUse") field(ONST, "Ready") field(TWST, "Config") field(THST, "ERROR") } # Selected Sensor record(stringin, "$(PRI):$(SEC):$(POS):SELECTED_SRLNO_I") { field(DESC, "Serial Number Selected") } # Selected SensorState, also inits the waveform to a low number to avoid zeroes #this record is disabled during active scans at mass > 95 record(mbbi, "$(PRI):$(SEC):$(POS):SENSOR_STATE") { field(DESC, "Sensor User IP") field(SCAN, "5 second") field(PINI, "1") field(DTYP, "stream") field(INP, "@mks_rga_common.proto.db sensorsState($(PRI),$(SEC),$(POS),:Message) $(PORT)") field(VAL, "3") field(ZRST, "InUse") field(ONST, "Ready") field(TWST, "Config") field(THST, "ERROR") field(DISV, "1") field(SDIS, "$(PRI):$(SEC):$(POS):STOPSTATUS") # field(FLNK, "$(PRI):$(SEC):$(POS):killZeroes") } record(stringin, "$(PRI):$(SEC):$(POS):SENSOR_IP") { field(DESC, "Sensor User IP") } record(stringin, "$(PRI):$(SEC):$(POS):SENSOR_APP") { field(DESC, "Sensor App Name") } record(stringin, "$(PRI):$(SEC):$(POS):SENSOR_APP_VER") { field(DESC, "Sensor App Version") } record(stringin, "$(PRI):$(SEC):$(POS):SENSOR_INFO") { field(DESC, "Sensor App Name") } record (stringin, "$(PRI):$(SEC):$(POS):SENSOR_MESSAGE") { } # Get the sensor available electonic gain factors record(longin, "$(PRI):$(SEC):$(POS):EGAIN_I") { field(DESC, "Electronic Gain") field(DTYP, "stream") field(INP, "@mks_rga_common.proto.db egains() $(PORT)") field(PINI, "1") } #Get RFINFO record(mbbi, "$(PRI):$(SEC):$(POS):RFINFO") { field(DESC, "Sensor User IP") field(SCAN, "5 second") field(PINI, "1") field(DTYP, "stream") field(INP, "@mks_rga_common.proto.db rfInfo($(PRI),$(SEC),$(POS),:Message) $(PORT)") field(ZRST, "OK") field(ONST, "ERROR") } # R Trip information record(bi, "$(PRI):$(SEC):$(POS):RFCONFIG_STS") { field(DESC, "RF Trip Enabled") # field(INP, "@mks_rga_common.proto.db rfInfo($(PRI),$(SEC),$(POS)) $(PORT)") field(PINI, "1") field(ZNAM, "No") field(ONAM, "Yes") } record(bi, "$(PRI):$(SEC):$(POS):RFTRIP_STS") { field(DESC, "RF Trip Status") field(ZNAM, "No") field(ONAM, "Yes") field(PINI, "1") } record(bi, "$(PRI):$(SEC):$(POS):RFTRIP_STATE") { field(DESC, "RF Trip State") field(DTYP, "stream") field(INP, "@mks_rga_meas.proto.db getRFTripStatus() $(PORT)") field(SCAN, "I/O Intr") field(ZNAM, "Tripped") field(ONAM, "OK") field(VAL, "1") } # Retrieve the current configuration and state of the filaments #this record is disabled during active scans at mass >95 record(mbbi, "$(PRI):$(SEC):$(POS):FIL_STS") { field(DESC, "Filament Status") field(DTYP, "stream") field(INP, "@mks_rga_common.proto.db filamentInfo($(PRI),$(SEC),$(POS)) $(PORT)") field(PINI, "1") field(SCAN, "5 second") field(ZRST, "OFF") field(ONST, "WARM-UP") field(TWST, "ON") field(THST, "COOL-DOWN") field(FRST, "BAD-EMISSION") field(ZRSV, "MAJOR") field(ONSV, "MINOR") field(TWSV, "NO_ALARM") field(THSV, "MINOR") field(FRSV, "MAJOR") field(DISV, "1") field(SDIS, "$(PRI):$(SEC):$(POS):STOPSTATUS") } record(longin, "$(PRI):$(SEC):$(POS):ATVFIL_I") { field(DESC, "Active Filament") } record(bi, "$(PRI):$(SEC):$(POS):EXTTRIPENA_STS") { field(DESC, "Extrn Trip Enabled") field(ZNAM, "No") field(ONAM, "Yes") } # External trip mode status record(bi, "$(PRI):$(SEC):$(POS):EXTTRIPMODE_STS") { field(DESC, "Extrn Trip Mode") field(PINI, "1") field(ZNAM, "Trip") field(ONAM, "Control") } record(bi, "$(PRI):$(SEC):$(POS):EMITRIPENA_STS") { field(DESC, "Emisison Trip Enable") field(ZNAM, "No") field(ONAM, "Yes") } record(longin, "$(PRI):$(SEC):$(POS):MAXONK_I") { field(DESC, "Max On K") } record(longin, "$(PRI):$(SEC):$(POS):ONREMAINK_I") { field(DESC, "On Remain K") } record(mbbi, "$(PRI):$(SEC):$(POS):FILTRIP_STS") { field(DESC, "Filament Trip Status") field(ZRST, "None") field(ONST, "Emission") field(TWST, "External") field(THST, "RVC") field(FRST, "GaugeFail") field(SXST, "TotalPressure") } record(bi, "$(PRI):$(SEC):$(POS):FILPS_STS") { field(DESC, "Filament PS Status") field(ZNAM, "Off") field(ONAM, "On") } record(bi, "$(PRI):$(SEC):$(POS):EMITRIP_STS") { field(DESC, "Emisison Trip Status") field(ZNAM, "Fail") field(ONAM, "OK") } record(bi, "$(PRI):$(SEC):$(POS):EXTTRIP_STS") { field(DESC, "External Trip Status") field(ZNAM, "Fail") field(ONAM, "OK") } record(bi, "$(PRI):$(SEC):$(POS):RVCTRIP_STS") { field(DESC, "RVC Trip Status") field(ZNAM, "Fail") field(ONAM, "OK") } record(bi, "$(PRI):$(SEC):$(POS):GAUGETRIP_STS") { field(DESC, "Gauge Trip Status") field(ZNAM, "Fail") field(ONAM, "OK") } # Return information about all the analog inputs record(bi, "$(PRI):$(SEC):$(POS):ENA_AI1_STS") { field(DESC, "AI1 Enable Status") field(DTYP, "stream") field(INP, "@mks_rga_common.proto.db aiInfo($(PRI),$(SEC),$(POS)) $(PORT)") field(PINI, "1") field(ZNAM, "No") field(ONAM, "Yes") } # AI1 min voltage record(ai, "$(PRI):$(SEC):$(POS):MINVOLT_AI1_I") { field(DESC, "AI1 Min Volt") } # AI1 max voltage record(ai, "$(PRI):$(SEC):$(POS):MAXVOLT_AI1_I") { field(DESC, "AI1 Max Volt") } # AI1 resolution record(longin, "$(PRI):$(SEC):$(POS):RES_AI1_I") { field(DESC, "AI1 Resolution") } # AI1 interval record(longin, "$(PRI):$(SEC):$(POS):INTV_AI1_I") { field(DESC, "AI1 Interval") } # AI1 average count record(longin, "$(PRI):$(SEC):$(POS):AVGCNT_AI1_I") { field(DESC, "AI1 Avg Count") } # AI1 resolution record(longin, "$(PRI):$(SEC):$(POS):AI1_I") { field(DESC, "AI1 Value") } # AI2 enabled status record(bi, "$(PRI):$(SEC):$(POS):ENA_AI2_STS") { field(DESC, "AI2 Enable Status") field(ZNAM, "No") field(ONAM, "Yes") } # AI2 min voltage record(ai, "$(PRI):$(SEC):$(POS):MINVOLT_AI2_I") { field(DESC, "AI2 Min Volt") } # AI2 max voltage record(ai, "$(PRI):$(SEC):$(POS):MAXVOLT_AI2_I") { field(DESC, "AI2 Max Volt") } # AI2 resolution record(longin, "$(PRI):$(SEC):$(POS):RES_AI2_I") { field(DESC, "AI2 Resolution") } # AI2 interval record(longin, "$(PRI):$(SEC):$(POS):INTV_AI2_I") { field(DESC, "AI2 Interval") } # AI2 average count record(longin, "$(PRI):$(SEC):$(POS):AVGCNT_AI2_I") { field(DESC, "AI2 Avg Count") } # AI2 resolution record(longin, "$(PRI):$(SEC):$(POS):AI2_I") { field(DESC, "AI2 Value") } # AI3 enabled status record(bi, "$(PRI):$(SEC):$(POS):ENA_AI3_STS") { field(DESC, "AI3 Enable Status") field(ZNAM, "No") field(ONAM, "Yes") } # AI3 min voltage record(ai, "$(PRI):$(SEC):$(POS):MINVOLT_AI3_I") { field(DESC, "AI3 Min Volt") } # AI3 max voltage record(ai, "$(PRI):$(SEC):$(POS):MAXVOLT_AI3_I") { field(DESC, "AI3 Max Volt") } # AI3 resolution record(longin, "$(PRI):$(SEC):$(POS):RES_AI3_I") { field(DESC, "AI3 Resolution") } # AI3 interval record(longin, "$(PRI):$(SEC):$(POS):INTV_AI3_I") { field(DESC, "AI3 Interval") } # AI3 average count record(longin, "$(PRI):$(SEC):$(POS):AVGCNT_AI3_I") { field(DESC, "AI3 Avg Count") } # AI3 resolution record(longin, "$(PRI):$(SEC):$(POS):AI3_I") { field(DESC, "AI3 Value") } # AI4 enabled status record(bi, "$(PRI):$(SEC):$(POS):ENA_AI4_STS") { field(DESC, "AI4 Enable Status") field(ZNAM, "No") field(ONAM, "Yes") } # AI4 min voltage record(ai, "$(PRI):$(SEC):$(POS):MINVOLT_AI4_I") { field(DESC, "AI4 Min Volt") } # AI4 max voltage record(ai, "$(PRI):$(SEC):$(POS):MAXVOLT_AI4_I") { field(DESC, "AI4 Max Volt") } # AI4 resolution record(longin, "$(PRI):$(SEC):$(POS):RES_AI4_I") { field(DESC, "AI4 Resolution") } # AI4 interval record(longin, "$(PRI):$(SEC):$(POS):INTV_AI4_I") { field(DESC, "AI4 Interval") } # AI4 average count record(longin, "$(PRI):$(SEC):$(POS):AVGCNT_AI4_I") { field(DESC, "AI4 Avg Count") } # AI4 resolution record(longin, "$(PRI):$(SEC):$(POS):AI4_I") { field(DESC, "AI4 Value") } # Return information about all the analog outputs # AO1 min voltage record(ai, "$(PRI):$(SEC):$(POS):MINVOLT_AO1_I") { field(DESC, "AI1 Min Volt") field(DTYP, "stream") field(INP, "@mks_rga_common.proto.db aoInfo($(PRI),$(SEC),$(POS)) $(PORT)") field(PINI, "1") } # AO1 max voltage record(ai, "$(PRI):$(SEC):$(POS):MAXVOLT_AO1_I") { field(DESC, "AO1 Max Volt") } # AI1 resolution record(longin, "$(PRI):$(SEC):$(POS):RES_AO1_I") { field(DESC, "AO1 Resolution") } # AO1 resolution record(longin, "$(PRI):$(SEC):$(POS):AO1_I") { field(DESC, "AO1 Value") } # AO2 min voltage record(ai, "$(PRI):$(SEC):$(POS):MINVOLT_AO2_I") { field(DESC, "AI1 Min Volt") } # AO2 max voltage record(ai, "$(PRI):$(SEC):$(POS):MAXVOLT_AO2_I") { field(DESC, "AO2 Max Volt") } # AI1 resolution record(longin, "$(PRI):$(SEC):$(POS):RES_AO2_I") { field(DESC, "AO2 Resolution") } # AO2 resolution record(longin, "$(PRI):$(SEC):$(POS):AO2_I") { field(DESC, "AO2 Value") } # Information about the fitted digital input ports. # Deglitching logic enable status record(bi, "$(PRI):$(SEC):$(POS):DEGLITCH_STS") { field(DESC, "Deglitch Status") field(DTYP, "stream") field(INP, "@mks_rga_common.proto.db digitalInfo($(PRI),$(SEC),$(POS)) $(PORT)") field(PINI, "1") field(ZNAM, "No") field(ONAM, "Yes") } # Deglitch time record(longin, "$(PRI):$(SEC):$(POS):DEGLITCHT_I") { field(DESC, "Deglitch Time") } # Max Port Bit 6&7 on time record(longin, "$(PRI):$(SEC):$(POS):MAXPB67ONT_I") { field(DESC, "Max PB67 On Time") } # Port A connected mask record(longin, "$(PRI):$(SEC):$(POS):CONNMASK_A_I") { field(DESC, "PA Conn Mask") } # Port A output mask record(longin, "$(PRI):$(SEC):$(POS):OUTMASK_A_I") { field(DESC, "PA Out Mask") } # Port A value record(longin, "$(PRI):$(SEC):$(POS):DIG_A_I") { field(DESC, "PA Value") } # Port B connected mask record(longin, "$(PRI):$(SEC):$(POS):CONNMASK_B_I") { field(DESC, "PB Conn Mask") } # Port B output mask record(longin, "$(PRI):$(SEC):$(POS):OUTMASK_B_I") { field(DESC, "PB Out Mask") } # Port B value record(longin, "$(PRI):$(SEC):$(POS):DIG_B_I") { field(DESC, "PB Value") } # Information about the mass program DAC and resolution DAC # Mass DAC bits record(longin, "$(PRI):$(SEC):$(POS):MASSDACBITS_I") { field(DESC, "Mass DAC Bits") field(DTYP, "stream") field(INP, "@mks_rga_common.proto.db sourceTuneInfo($(PRI),$(SEC),$(POS)) $(PORT)") field(PINI, "1") } # Information about the mass program DAC and the resolution DAC # Mass DAC upper limit M record(ai, "$(PRI):$(SEC):$(POS):MASSDACHIM_I") { field(DESC, "Mass DAC Hi M") } # Mass DAC upper limit C record(ai, "$(PRI):$(SEC):$(POS):MASSDACHIC_I") { field(DESC, "Mass DAC Hi C") } # Mass DAC lower limit M record(ai, "$(PRI):$(SEC):$(POS):MASSDACLOM_I") { field(DESC, "Mass DAC Hi M") } # Mass DAC lower limit C record(ai, "$(PRI):$(SEC):$(POS):MASSDACLOC_I") { field(DESC, "Mass DAC Lo C") } # Resolution DAC bits record(longin, "$(PRI):$(SEC):$(POS):RESDACBITS_I") { field(DESC, "Resolution DAC Bits") } ## Information about the available diagnostic input channel ## +3.3V diagnostic enable status record(bi, "$(PRI):$(SEC):$(POS):DIAG_3V_STS") { field(DESC, "+3.3V Diag Ena Stat") field(DTYP, "stream") field(INP, "@mks_rga_common.proto.db diaginInfo($(PRI),$(SEC),$(POS),$(POS):) $(PORT)") field(PINI, "1") field(ZNAM, "No") field(ONAM, "Yes") # field(SCAN, "5 second") field(FLNK, "$(PRI):$(SEC):$(POS):DIAG_1_FOUT") } # +3.3V interval record(longin, "$(PRI):$(SEC):$(POS):INTER_3V_I") { field(DESC, "+3.3V Interval") } # +3.3V average count record(longin, "$(PRI):$(SEC):$(POS):AVGCNT_3V_I") { field(DESC, "+3.3V Avg Cnt") } # +3.3V value record(ai, "$(PRI):$(SEC):$(POS):Diag3V_I") { field(DESC, "+3.3V Interval") field(EGU, "Volts") } # Forward link record(fanout, "$(PRI):$(SEC):$(POS):DIAG_1_FOUT") { field(DESC, "Diagnostic Fanout1") field(LNK1, "$(PRI):$(SEC):$(POS):DIAG_RFIDENT_I") field(LNK2, "$(PRI):$(SEC):$(POS):DIAG_EXTMON_I") field(LNK3, "$(PRI):$(SEC):$(POS):DIAG_NEG_15V_I") field(LNK4, "$(PRI):$(SEC):$(POS):DIAG_RFK_I") field(LNK5, "$(PRI):$(SEC):$(POS):DIAG_RFTUNEE_I") field(LNK6, "$(PRI):$(SEC):$(POS):DIAG_2_FOUT") } record(fanout, "$(PRI):$(SEC):$(POS):DIAG_2_FOUT") { field(DESC, "Diagnostic Fanout2") field(LNK1, "$(PRI):$(SEC):$(POS):Diag24V_I") field(LNK2, "$(PRI):$(SEC):$(POS):DIAG_NEG_130V_I") field(LNK3, "$(PRI):$(SEC):$(POS):DIAG_IONNRG_I") field(LNK4, "$(PRI):$(SEC):$(POS):DIAG_SEMMON_I") field(LNK5, "$(PRI):$(SEC):$(POS):DIAG_SRCIMON_I") field(LNK6, "$(PRI):$(SEC):$(POS):DIAG_2_FOUT") } record(fanout, "$(PRI):$(SEC):$(POS):DIAG_3_FOUT") { field(DESC, "Diagnostic Fanout3") field(LNK1, "$(PRI):$(SEC):$(POS):DIAG_MASSDAC_I") field(LNK2, "$(PRI):$(SEC):$(POS):DIAG_FILI_I") field(LNK3, "$(PRI):$(SEC):$(POS):DIAG_ENRG_I") field(LNK4, "$(PRI):$(SEC):$(POS):DIAG_RES_I") field(LNK5, "$(PRI):$(SEC):$(POS):DIAG_POLEBIAS_I") field(LNK6, "$(PRI):$(SEC):$(POS):DIAG_3_FOUT") } record(fanout, "$(PRI):$(SEC):$(POS):DIAG_4_FOUT") { field(DESC, "Diagnostic Fanout4") field(LNK1, "$(PRI):$(SEC):$(POS):Diag15V_I") field(LNK2, "$(PRI):$(SEC):$(POS):DIAG_INTK_I") } # RF Ident diagnostic enable status record(bi, "$(PRI):$(SEC):$(POS):DIAG_RFIDENT_STS") { field(DESC, "RF Id Diag Ena Stat") field(ZNAM, "No") field(ONAM, "Yes") } # RF Ident interval record(longin, "$(PRI):$(SEC):$(POS):INTER_RFIDENT_I") { field(DESC, "RF Ident Interval") field(PINI, "1") } # RF Ident average count record(longin, "$(PRI):$(SEC):$(POS):AVGCNT_RFIDENT_I") { field(DESC, "RF Ident Avg Cnt") field(PINI, "1") } # RF Ident value record(ai, "$(PRI):$(SEC):$(POS):DIAG_RFIDENT_I") { field(DESC, "RF Ident Interval") field(PINI, "1") field(EGU, "Volts") } # Extraction Monitor diagnostic enable status record(bi, "$(PRI):$(SEC):$(POS):DIAG_EXTMON_STS") { field(DESC, "Extract Mon Diag Ena") field(PINI, "1") field(ZNAM, "No") field(ONAM, "Yes") } # Extraction Monitor interval record(longin, "$(PRI):$(SEC):$(POS):INTER_EXTMON_I") { field(DESC, "Extract Mon Intrvl") field(PINI, "1") } # Extraction Monitor average count record(longin, "$(PRI):$(SEC):$(POS):AVGCNT_EXTMON_I") { field(DESC, "Extraction Monitor Avg Cnt") field(PINI, "1") } # Extraction Monitor value record(ai, "$(PRI):$(SEC):$(POS):DIAG_EXTMON_I") { field(DESC, "Extraction Monitor Interval") field(PINI, "1") field(EGU, "Volts") } # -15V diagnostic enable status record(bi, "$(PRI):$(SEC):$(POS):DIAG_NEG_15V_STS") { field(DESC, "-15V Diagn Enable Stat") field(PINI, "1") field(ZNAM, "No") field(ONAM, "Yes") } # -15V interval record(longin, "$(PRI):$(SEC):$(POS):INTER_NEG_15V_I") { field(DESC, "-15V Interval") field(PINI, "1") } # -15V average count record(longin, "$(PRI):$(SEC):$(POS):AVGCNT_NEG_15V_I") { field(DESC, "-15V Avg Cnt") field(PINI, "1") } # -15V value record(ai, "$(PRI):$(SEC):$(POS):DIAG_NEG_15V_I") { field(DESC, "-15V Interval") field(PINI, "1") field(EGU, "Volts") } # RF temperature diagnostic enable status record(bi, "$(PRI):$(SEC):$(POS):DIAG_RFK_STS") { field(DESC, "RFK Diag Ena Stat") field(PINI, "1") field(ZNAM, "No") field(ONAM, "Yes") } # RF temperature interval record(longin, "$(PRI):$(SEC):$(POS):INTER_RFK_I") { field(DESC, "RFK Intrvl") field(PINI, "1") } # RF temperature average count record(longin, "$(PRI):$(SEC):$(POS):AVGCNT_RFK_I") { field(DESC, "RFK Avg Cnt") field(PINI, "1") } # RF temperature value record(ai, "$(PRI):$(SEC):$(POS):DIAG_RFK_I") { field(DESC, "RFK Intrvl") field(PINI, "1") field(EGU, "Degress C") } # RF tune voltage diagnostic enable status record(bi, "$(PRI):$(SEC):$(POS):DIAG_RFTUNEE_STS") { field(DESC, "RFTuneE Diag Ena Stat") field(PINI, "1") field(ZNAM, "No") field(ONAM, "Yes") } # RF tune voltage interval record(longin, "$(PRI):$(SEC):$(POS):INTER_RFTUNEE_I") { field(DESC, "RFTuneE Interval") field(PINI, "1") } # RF tune voltage average count record(longin, "$(PRI):$(SEC):$(POS):AVGCNT_RFTUNEE_I") { field(DESC, "RFTuneE Avg Cnt") field(PINI, "1") } # RF tune voltage value record(ai, "$(PRI):$(SEC):$(POS):DIAG_RFTUNEE_I") { field(DESC, "RFTuneE Interval") field(PINI, "1") field(EGU, "Volts") } # +24V diagnostic enable status record(bi, "$(PRI):$(SEC):$(POS):DIAG_24V_STS") { field(DESC, "+24V Diag Ena Stat") field(PINI, "1") field(ZNAM, "No") field(ONAM, "Yes") } # +24V interval record(longin, "$(PRI):$(SEC):$(POS):INTER_24V_I") { field(DESC, "+24V Interval") field(PINI, "1") } # +24V average count record(longin, "$(PRI):$(SEC):$(POS):AVGCNT_24V_I") { field(DESC, "+24V Avg Cnt") field(PINI, "1") } # +24V value record(ai, "$(PRI):$(SEC):$(POS):Diag24V_I") { field(DESC, "+24V Interval") field(PINI, "1") field(EGU, "Volts") } # -130V diagnostic enable status record(bi, "$(PRI):$(SEC):$(POS):DIAG_NEG_130V_STS") { field(DESC, "-130V Diag Ena Stat") field(PINI, "1") field(ZNAM, "No") field(ONAM, "Yes") } # -130V interval record(longin, "$(PRI):$(SEC):$(POS):INTER_NEG_130V_I") { field(DESC, "-130V Interval") field(PINI, "1") } # -130V average count record(longin, "$(PRI):$(SEC):$(POS):AVGCNTNEG_130V_I") { field(DESC, "-130V Avg Cnt") field(PINI, "1") } # -130V value record(ai, "$(PRI):$(SEC):$(POS):DIAG_NEG_130V_I") { field(DESC, "-130V Interval") field(PINI, "1") field(EGU, "Volts") } # Ion energy diagnostic enable status record(bi, "$(PRI):$(SEC):$(POS):DIAG_IONNRG_STS") { field(DESC, "IonNrg Diag Ena Stat") field(PINI, "1") field(ZNAM, "No") field(ONAM, "Yes") } # Ion energy interval record(longin, "$(PRI):$(SEC):$(POS):INTER_IONNRG_I") { field(DESC, "IonNrg Interval") field(PINI, "1") } # Ion energy average count record(longin, "$(PRI):$(SEC):$(POS):AVGCNT_IONNRG_I") { field(DESC, "IonNrg Avg Cnt") field(PINI, "1") } # Ion energy value record(ai, "$(PRI):$(SEC):$(POS):DIAG_IONNRG_I") { field(DESC, "IonNrg Interval") field(PINI, "1") field(EGU, "Volts") } # SEM monitor diagnostic enable status record(bi, "$(PRI):$(SEC):$(POS):DIAG_SEMMON_STS") { field(DESC, "SEMMon Diag Ena Stat") field(PINI, "1") field(ZNAM, "No") field(ONAM, "Yes") } # SEM monitor interval record(longin, "$(PRI):$(SEC):$(POS):INTER_SEMMON_I") { field(DESC, "SEMMonitor Interval") field(PINI, "1") } # SEM monitor average count record(longin, "$(PRI):$(SEC):$(POS):AVGCNT_SEMMON_I") { field(DESC, "SEMMonitor Avg Cnt") field(PINI, "1") } # SEM monitor value record(ai, "$(PRI):$(SEC):$(POS):DIAG_SEMMON_I") { field(DESC, "SEMMonitor Interval") field(PINI, "1") field(EGU, "Volts") } # Source current monitor diagnostic enable status record(bi, "$(PRI):$(SEC):$(POS):DIAG_SRCIMON_STS") { field(DESC, "SourceIMon Diag Ena Stat") field(PINI, "1") field(ZNAM, "No") field(ONAM, "Yes") } # Source current monitor interval record(longin, "$(PRI):$(SEC):$(POS):INTER_SRCIMON_I") { field(DESC, "SourceIMonitor Interval") field(PINI, "1") } # Source current monitor average count record(longin, "$(PRI):$(SEC):$(POS):AVGCNT_SRCIMON_I") { field(DESC, "SourceIMonitor Avg Cnt") field(PINI, "1") } # Source current monitor value record(ai, "$(PRI):$(SEC):$(POS):DIAG_SRCIMON_I") { field(DESC, "SourceIMonitor Interval") field(PINI, "1") field(EGU, "mA") } # Mass DAC diagnostic enable status record(bi, "$(PRI):$(SEC):$(POS):DIAG_MASSDAC_STS") { field(DESC, "MassDAC Diag Ena Stat") field(PINI, "1") field(ZNAM, "No") field(ONAM, "Yes") } # Mass DAC interval record(longin, "$(PRI):$(SEC):$(POS):INTER_MASSDAC_I") { field(DESC, "MassDAC Interval") field(PINI, "1") } # Mass DAC average count record(longin, "$(PRI):$(SEC):$(POS):AVGCNT_MASSDAC_I") { field(DESC, "MassDAC Avg Cnt") field(PINI, "1") } # Mass DAC value record(ai, "$(PRI):$(SEC):$(POS):DIAG_MASSDAC_I") { field(DESC, "MassDAC Interval") field(PINI, "1") field(EGU, "Volts") } # Filament current diagnostic enable status record(bi, "$(PRI):$(SEC):$(POS):DIAG_FILI_STS") { field(DESC, "FilI Diag Ena Stat") field(PINI, "1") field(ZNAM, "No") field(ONAM, "Yes") } # Filament current interval record(longin, "$(PRI):$(SEC):$(POS):INTER_FILI_I") { field(DESC, "FilI Interval") field(PINI, "1") } # Filament current average count record(longin, "$(PRI):$(SEC):$(POS):AVGCNT_FILI_I") { field(DESC, "FilI Avg Cnt") field(PINI, "1") } # Filament current value record(ai, "$(PRI):$(SEC):$(POS):DIAG_FILI_I") { field(DESC, "FilI Interval") field(PINI, "1") field(EGU, "Amps") } # Electron energy diagnostic enable status record(bi, "$(PRI):$(SEC):$(POS):DIAG_ENRG_STS") { field(DESC, "eNrg Diag Ena Stat") field(PINI, "1") field(ZNAM, "No") field(ONAM, "Yes") } # Electron energy interval record(longin, "$(PRI):$(SEC):$(POS):INTER_ENRG_I") { field(DESC, "eNrg Interval") field(PINI, "1") } # Electron energy average count record(longin, "$(PRI):$(SEC):$(POS):AVGCNT_ENRG_I") { field(DESC, "eNrg Avg Cnt") field(PINI, "1") } # Electron energy value record(ai, "$(PRI):$(SEC):$(POS):DIAG_ENRG_I") { field(DESC, "eNrg Intrvl") field(PINI, "1") field(EGU, "Volts") } # Resolution diagnostic enable status record(bi, "$(PRI):$(SEC):$(POS):DIAG_RES_STS") { field(DESC, "Res Diag Ena Stat") field(PINI, "1") field(ZNAM, "No") field(ONAM, "Yes") } # Resolution interval record(longin, "$(PRI):$(SEC):$(POS):INTER_RES_I") { field(DESC, "Res Interval") field(PINI, "1") } # Resolution average count record(longin, "$(PRI):$(SEC):$(POS):AVGCNT_RES_I") { field(DESC, "Res Avg Cnt") field(PINI, "1") } # Resolution value record(ai, "$(PRI):$(SEC):$(POS):DIAG_RES_I") { field(DESC, "Res Interval") field(PINI, "1") field(EGU, "Volts") } # Pole bias diagnostic enable status record(bi, "$(PRI):$(SEC):$(POS):DIAG_POLEBIAS_STS") { field(DESC, "PoleBias Diagn Ena Stat") field(PINI, "1") field(ZNAM, "No") field(ONAM, "Yes") } # Pole bias interval record(longin, "$(PRI):$(SEC):$(POS):INTER_POLEBIAS_I") { field(DESC, "PoleBias Interval") field(PINI, "1") } # Pole bias average count record(longin, "$(PRI):$(SEC):$(POS):AVGCNT_POLEBIAS_I") { field(DESC, "PoleBias Avg Cnt") field(PINI, "1") } # Pole bias value record(ai, "$(PRI):$(SEC):$(POS):DIAG_POLEBIAS_I") { field(DESC, "PoleBias Interval") field(PINI, "1") field(EGU, "Volts") } # Electrometer temperature diagnostic enable status record(bi, "$(PRI):$(SEC):$(POS):DIAG_EMETERK_STS") { field(DESC, "EmeterK Diag Ena Stat") field(PINI, "1") field(ZNAM, "No") field(ONAM, "Yes") } # Electrometer temperature interval record(longin, "$(PRI):$(SEC):$(POS):INTER_EMETERK_I") { field(DESC, "EmeterK Interval") field(PINI, "1") } # Electrometer temperature average count record(longin, "$(PRI):$(SEC):$(POS):AVGCNT_EMETERK_I") { field(DESC, "EmeterK Avg Cnt") field(PINI, "1") } # Electrometer temperature value record(ai, "$(PRI):$(SEC):$(POS):DIAG_EMETERK_I") { field(DESC, "EmeterK Interval") field(PINI, "1") field(EGU, "Degrees C") } # +15V diagnostic enable status record(bi, "$(PRI):$(SEC):$(POS):DIAG_15V_STS") { field(DESC, "+15V Diag Ena Stat") field(PINI, "1") field(ZNAM, "No") field(ONAM, "Yes") } # +15V interval record(longin, "$(PRI):$(SEC):$(POS):INTER_15V_I") { field(DESC, "+15V Interval") field(PINI, "1") } # +15V average count record(longin, "$(PRI):$(SEC):$(POS):AVGCNT_15V_I") { field(DESC, "+15V Avg Cnt") field(PINI, "1") } # +15V value record(ai, "$(PRI):$(SEC):$(POS):Diag15V_I") { field(DESC, "+15V Interval") field(PINI, "1") field(EGU, "Volts") } # Internal temperature diagnostic enable status record(bi, "$(PRI):$(SEC):$(POS):DIAG_INTK_STS") { field(DESC, "IntK Diag Ena Stat") field(PINI, "1") field(ZNAM, "No") field(ONAM, "Yes") } # Internal temperature interval record(longin, "$(PRI):$(SEC):$(POS):INTER_INTK_I") { field(DESC, "IntK Interval") field(PINI, "1") } # Internal temperature average count record(longin, "$(PRI):$(SEC):$(POS):AVGCNT_INTK_I") { field(DESC, "IntK Avg Cnt") field(PINI, "1") } # Internal temperature value record(ai, "$(PRI):$(SEC):$(POS):DIAG_INTK_I") { field(DESC, "IntK Interval") field(PINI, "1") field(EGU, "Degrees C") } #used to gain control and setup graphs in one button click record(dfanout, "$(PRI):$(SEC):$(POS):SETUP_CMD") { field(DESC, "Setup Sensor and Graphs") field(OUTA, "$(PRI):$(SEC):$(POS):CTL_CMD.PROC") field(OUTB, "$(PRI):$(SEC):$(POS):GRAPH_DFOUT PP") } ## Gain control of a sensor record(bo, "$(PRI):$(SEC):$(POS):CTL_CMD") { field(DESC, "Control Sensor") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db control($(PRI),$(SEC),$(POS),$(SERIALNUM),$(DRV_VER)) $(PORT)") field(ZNAM, "OK") field(ONAM, "ERROR") } ## Release control of a sensor record(bo, "$(PRI):$(SEC):$(POS):RELEASE_CMD") { field(DESC, "Release Sensor Control") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db release() $(PORT)") field(ZNAM, "OK") field(ONAM, "ERROR") } ## Sensor control # Turn the currently selected filament On or Off record(bo, "$(PRI):$(SEC):$(POS):FILCTL_CMD") { field(DESC, "Filament Control") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db filamentControl() $(PORT)") field(ZNAM, "Off") field(ONAM, "On") } # Select a particular filament record(bo, "$(PRI):$(SEC):$(POS):FILSEL_CMD") { field(DESC, "Filament Select") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db filamentSelect() $(PORT)") field(ZNAM, "1") field(ONAM, "2") } # Set filaments on time before filaments automatically go off record(longout, "$(PRI):$(SEC):$(POS):FILONT_SP") { field(DESC, "Set Filament On Time") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db filamentOnT() $(PORT)") field(LOPR, "60") field(HOPR, "43200") field(EGU, "s") } ##Used to Add Analog or Bar Chart NOT NEEDED CURRENTLY -Pelham 2/28/11 record(bo, "$(PRI):$(SEC):$(POS):GRAPH_SEL") { field(DESC, "Select Analog or Bar Chart") field(ZNAM, "Analog") field(ONAM, "Bar") field(OUT, "$(PRI):$(SEC):$(POS):GRAPH_DFOUT PP") } record(dfanout, "$(PRI):$(SEC):$(POS):GRAPH_DFOUT") { field(DESC, "Scan Fanout") field(OUTA, "$(PRI):$(SEC):$(POS):ADDANL_CMD PP") field(OUTB, "$(PRI):$(SEC):$(POS):ADDBAR_CMD PP") } ## Add a new analog measurement to the sensor record(bo, "$(PRI):$(SEC):$(POS):ADDANL_CMD") { field(DESC, "Set Analog Mode") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db addAnalog($(PRI),$(SEC),$(POS)) $(PORT)") } record(longout, "$(PRI):$(SEC):$(POS):ADDANL_STRTMASS_SP") { field(DESC, "Set Start Mass") field(LOPR, "1") field(HOPR, "100") field(VAL, "1") field(PINI, "1") } record(longout, "$(PRI):$(SEC):$(POS):ADDANL_ENDMASS_SP") { field(DESC, "Set End Mass") field(LOPR, "1") field(HOPR, "100") field(VAL, "100") field(PINI, "1") } record(mbbo, "$(PRI):$(SEC):$(POS):ADDANL_POINTS_PK_SEL") { field(DESC, "Set PointsPerPeak") field(ZRST, "1") field(ONST, "2") field(TWST, "4") field(THST, "8") field(FRST, "16") field(FVST, "32") field(VAL, "2") } record(mbbo, "$(PRI):$(SEC):$(POS):AddAnalog:ACCURACY_SEL") { field(DESC, "Analog Accuracy") field(ZRST, "Accuracy 0") field(ONST, "Accuracy 1") field(TWST, "Accuracy 2") field(THST, "Accuracy 3") field(FRST, "Accuracy 4") field(FVST, "Accuracy 5") field(SXST, "Accuracy 6") field(SVST, "Accuracy 7") field(EIST, "Accuracy 8") field(VAL, "6") } record(mbbo, "$(PRI):$(SEC):$(POS):ADDANL_EGAIN_INDX_SEL") { field(DESC, "Set EGain Index") field(ZRST, "Index 0") field(ONST, "Index 1") } record(mbbo, "$(PRI):$(SEC):$(POS):ADDANL_SRCINDX_SEL") { field(DESC, "Set Source Index") field(ZRST, "Source Index 0") field(ONST, "Source Index 1") field(TWST, "Source Index 2") field(THST, "Source Index 3") field(FRST, "Source Index 4") field(FVST, "Source Index 5") field(SXST, "Source Index 6") } record(mbbo, "$(PRI):$(SEC):$(POS):ADDANL_DETCINDX_SEL") { field(DESC, "Set Detector Index") field(ZRST, "Faraday") field(ONST, "Multiplier 1") field(TWST, "Multiplier 2") field(THST, "Multiplier 3") } ## Add a new barchart measurement to the sensor record(bo, "$(PRI):$(SEC):$(POS):ADDBAR_CMD") { field(DESC, "Set Bar Mode") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db addBarchart($(PRI),$(SEC),$(POS)) $(PORT)") } record(longout, "$(PRI):$(SEC):$(POS):ADDBAR_STRTMASS_SP") { field(DESC, "Set Start Mass") field(LOPR, "1") field(HOPR, "100") field(VAL, "1") } record(longout, "$(PRI):$(SEC):$(POS):ADDBAR_ENDMASS_SP") { field(DESC, "Set End Mass") field(LOPR, "1") field(HOPR, "100") field(VAL, "100") } record(mbbo, "$(PRI):$(SEC):$(POS):ADDBAR_FILTERMODE_SEL") { field(DESC, "Set Bar Filter Mode") field(ZRST, "PeakCenter") field(ONST, "PeakMax") field(TWST, "PeakAverage") } record(mbbo, "$(PRI):$(SEC):$(POS):AddBar:ACCURACY_SEL") { field(DESC, "Set Bar Accuracy") field(ZRST, "Accuracy 0") field(ONST, "Accuracy 1") field(TWST, "Accuracy 2") field(THST, "Accuracy 3") field(FRST, "Accuracy 4") field(FVST, "Accuracy 5") field(SXST, "Accuracy 6") field(SVST, "Accuracy 7") field(EIST, "Accuracy 8") field(VAL, "6") } record(mbbo, "$(PRI):$(SEC):$(POS):ADDBAR_EGAININDX_SEL") { field(DESC, "Set EGain Index") field(ZRST, "Index 0") field(ONST, "Index 1") } record(mbbo, "$(PRI):$(SEC):$(POS):ADDBAR_SRCINDX_SEL") { field(DESC, "Set Source Index") field(ZRST, "Source Index 0") field(ONST, "Source Index 1") field(TWST, "Source Index 2") field(THST, "Source Index 3") field(FRST, "Source Index 4") field(FVST, "Source Index 5") field(SXST, "Source Index 6") } record(mbbo, "$(PRI):$(SEC):$(POS):ADDBAR_DETCINDX_SEL") { field(DESC, "Set Detector Index") field(ZRST, "Faraday") field(ONST, "Multiplier 1") field(TWST, "Multiplier 2") field(THST, "Multiplier 3") } ## Add a new peak jump measurement to the sensor # Set peak jump measurement name record(stringout, "$(PRI):$(SEC):$(POS):ADDPKJUMP_NAME_SP") { field(DESC, "Set PeakJump Measuremtn Name") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db addPeakjump($(PRI),$(SEC),$(POS)) $(PORT)") field(VAL, "PeakJump1") } record(mbbo, "$(PRI):$(SEC):$(POS):ADDPKJUMP_FLTRMODE") { field(DESC, "Set Filter Mode") field(ZRST, "PeakCenter") field(ONST, "PeakMax") field(TWST, "PeakAverage") } record(mbbo, "$(PRI):$(SEC):$(POS):AddPeakJump:ACCURACY_SEL") { field(DESC, "Set Accuracy") field(ZRST, "Accuracy 0") field(ONST, "Accuracy 1") field(TWST, "Accuracy 2") field(THST, "Accuracy 3") field(FRST, "Accuracy 4") field(FVST, "Accuracy 5") field(SXST, "Accuracy 6") field(SVST, "Accuracy 7") field(EIST, "Accuracy 8") field(VAL, "5") } record(mbbo, "$(PRI):$(SEC):$(POS):ADDPKJUMP_EGAININDX") { field(DESC, "Set EGain Index") field(ZRST, "Index 0") field(ONST, "Index 1") } record(mbbo, "$(PRI):$(SEC):$(POS):ADDPKJUMP_SRCINDX_SEL") { field(DESC, "Set Source Index") field(ZRST, "Source Index 0") field(ONST, "Source Index 1") field(TWST, "Source Index 2") field(THST, "Source Index 3") field(FRST, "Source Index 4") field(FVST, "Source Index 5") field(SXST, "Source Index 6") } record(mbbo, "$(PRI):$(SEC):$(POS):ADDPKJUMP_DETCINDX_SEL") { field(DESC, "Set Detector Index") field(ZRST, "Faraday") field(ONST, "Multiplier 1") field(TWST, "Multiplier 2") field(THST, "Multiplier 3") } ## Add a new single peak measurement to the sensor # Set single peak measurement name record(stringout, "$(PRI):$(SEC):$(POS):ADDSINGLEPK_NAME_SP") { field(DESC, "Set SglePk Meas Name") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db addSinglepeak($(PRI),$(SEC),$(POS)) $(PORT)") field(VAL, "SinglePeak1") } record(longout, "$(PRI):$(SEC):$(POS):ADDSINGLEPK_MASS_SP") { field(DESC, "Set Mass") field(LOPR, "1") field(HOPR, "100") field(VAL, "20") } record(mbbo, "$(PRI):$(SEC):$(POS):AddSinglePeak:ACCURACY_SEL") { field(DESC, "Set Accuracy") field(ZRST, "Accuracy 0") field(ONST, "Accuracy 1") field(TWST, "Accuracy 2") field(THST, "Accuracy 3") field(FRST, "Accuracy 4") field(FVST, "Accuracy 5") field(SXST, "Accuracy 6") field(SVST, "Accuracy 7") field(EIST, "Accuracy 8") field(VAL, "5") } record(mbbo, "$(PRI):$(SEC):$(POS):ADDSING_PK_EGAININDX") { field(DESC, "Set EGain Index") field(ZRST, "Index 0") field(ONST, "Index 1") } record(mbbo, "$(PRI):$(SEC):$(POS):ADDSINGLEPK_SRCINDX") { field(DESC, "Set Source Index") field(ZRST, "Source Index 0") field(ONST, "Source Index 1") field(TWST, "Source Index 2") field(THST, "Source Index 3") field(FRST, "Source Index 4") field(FVST, "Source Index 5") field(SXST, "Source Index 6") } record(mbbo, "$(PRI):$(SEC):$(POS):ADDSINGLEPK_DETCINDX") { field(DESC, "Set Detector Index") field(ZRST, "Faraday") field(ONST, "Multiplier 1") field(TWST, "Multiplier 2") field(THST, "Multiplier 3") } # Change accuracy code of the currently selected measurement record(mbbo, "$(PRI):$(SEC):$(POS):ACCURACY_SEL") { field(DESC, "Set Accuracy") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db measAccuracy() $(PORT)") field(ZRST, "Accuracy 0") field(ONST, "Accuracy 1") field(TWST, "Accuracy 2") field(THST, "Accuracy 3") field(FRST, "Accuracy 4") field(FVST, "Accuracy 5") field(SXST, "Accuracy 6") field(SVST, "Accuracy 7") field(EIST, "Accuracy 8") } # Add a mass to a peak jump measurement record(longout, "$(PRI):$(SEC):$(POS):MEASADDMASS_SP") { field(DESC, "Add Mass") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db measAddMass() $(PORT)") field(LOPR, "1") field(HOPR, "100") } # Changes a mass on a peak jump measurement record(longout, "$(PRI):$(SEC):$(POS):MEASCHMASS_MASS_SP") { field(DESC, "Specify Mass Index") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db measChangeMass($(PRI),$(SEC),$(POS)) $(PORT)") field(LOPR, "1") field(HOPR, "100") } record(longout, "$(PRI):$(SEC):$(POS):MEASCHMASS_INDX_SP") { field(DESC, "Set New Mass") field(LOPR, "1") field(HOPR, "100") } # Changes the selected measurements detector index record(mbbo, "$(PRI):$(SEC):$(POS):MEASDETCINDX_SEL") { field(DESC, "Change Detector Index") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db measDetectorIndex() $(PORT)") field(ZRST, "Faraday") field(ONST, "Multiplier 1") field(TWST, "Multiplier 2") field(THST, "Multiplier 3") } # Changes the selected measurements electronic gain index record(mbbo, "$(PRI):$(SEC):$(POS):MEASEGAININDX_SEL") { field(DESC, "Change EGain Index") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db measEGainIndex() $(PORT)") field(ZRST, "Index 0") # field(ONST, "Index 1") } # Select the mass filter mode to be used for Barchart and Peak Jump measurements record(mbbo, "$(PRI):$(SEC):$(POS):MEASFILTERMODE_SEL") { field(DESC, "Select Filter Mode") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db measFilterMode() $(PORT)") field(ZRST, "PeakCenter") field(ONST, "PeakMas") field(TWST, "PeakAverage") } # Changes the mass used for the selected single peak measurement record(ao, "$(PRI):$(SEC):$(POS):MEASMASS_SP") { field(DESC, "Change Meas Mass") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db measMass() $(PORT)") field(LOPR, "1.0") field(HOPR, "100.0") } # Sets the selected analog measurements number of points to measure per peak record(mbbo, "$(PRI):$(SEC):$(POS):MEASPOINTSPERPK_SEL") { field(DESC, "Set PointsPerPeak") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db measPointsPerPeak() $(PORT)") field(ZRST, "1") field(ONST, "2") field(TWST, "4") field(THST, "8") field(FRST, "16") field(FVST, "32") field(VAL, "4") } # Remvoe a mass peak from the selected peak jump measurement record(longout, "$(PRI):$(SEC):$(POS):MEASREMOVEMASS_INDX_SP") { field(DESC, "Remove Mass Index") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db measRemoveMass() $(PORT)") field(LOPR, "1") field(HOPR, "100") } # Change the selected measurements source parameter record(mbbo, "$(PRI):$(SEC):$(POS):SRCINDX_SEL") { field(DESC, "Set Source Index") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db measSourceIndex() $(PORT)") field(ZRST, "Source Index 0") field(ONST, "Source Index 1") field(TWST, "Source Index 2") field(THST, "Source Index 3") field(FRST, "Source Index 4") field(FVST, "Source Index 5") field(SXST, "Source Index 6") } # Control whether the ion beam should be on or off during a measurements zero readings record(bo, "$(PRI):$(SEC):$(POS):MEASZEROBEAMOFF_SEL") { field(DESC, "Set Zero Beam") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db measZeroBeamOff() $(PORT)") field(ZNAM, "False") field(ONAM, "True") } # Sets the selected measurements zero buffer depth record(mbbo, "$(PRI):$(SEC):$(POS):MEASZEROBUFDEPTH_SEL") { field(DESC, "Set Buffer Depth") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db measZeroBufferDepth() $(PORT)") field(ZRST, "1") field(ONST, "2") field(TWST, "4") field(THST, "8") field(FRST, "16") field(FVST, "32") field(VAL, "4") } # Sets the selected measurements zero buffer mode record(mbbo, "$(PRI):$(SEC):$(POS):MEASZEROBUFMODE_SEL") { field(DESC, "Set Buffer Mode") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db measZeroBufferMode() $(PORT)") field(ZRST, "SingleScanAvg") field(ONST, "MultScanAvg") field(TWST, "MultScanStart") field(THST, "SingleShot") } ## Re-trigger the selected measurements zero buffer if its mode is SingleShot record(bo, "$(PRI):$(SEC):$(POS):MEASZERORETRIG_CMD") { field(DESC, "Zero Retrigger") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db measZeroRetrigger() $(PORT)") } ## Set the mass position where the selected measurement should take its zero reading from. ## The default position is mass 5.5 record(ao, "$(PRI):$(SEC):$(POS):MEASZEROMASS_SP") { field(DESC, "Set Zero Mass") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db measZeroMass() $(PORT)") field(VAL, "5.5") } ## Control whether the multiplier is allowed to come on or not record(bo, "$(PRI):$(SEC):$(POS):MULTIPLIERPRO_CMD") { field(DESC, "Multiplier Protect") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db multiplierProtect() $(PORT)") field(ZNAM, "False") field(ONAM, "True") } ## Get sensors diagnostics measurements information # 3.3V value record(ai, "$(PRI):$(SEC):$(POS):3V_I") { field(DESC, "3.3V Val") field(DTYP, "stream") field(INP, "@mks_rga_common.proto.db runDiagnostics($(PRI),$(SEC),$(POS),$(POS):) $(PORT)") } # 3.3V result record(mbbi, "$(PRI):$(SEC):$(POS):RESULT_3V_STS") { field(DESC, "3.3V Result") field(ZRST, "N/A") field(ONST, "Fail") field(TWST, "Pass") } # +15V value record(ai, "$(PRI):$(SEC):$(POS):15V_I") { field(DESC, "+15 Val") } # +15V result record(mbbi, "$(PRI):$(SEC):$(POS):RESULT_15V_STS") { field(DESC, "+15V Result") field(ZRST, "N/A") field(ONST, "Fail") field(TWST, "Pass") } # -15V value record(ai, "$(PRI):$(SEC):$(POS):NEG_15V_I") { field(DESC, "-15 Val") } # -15V result record(mbbi, "$(PRI):$(SEC):$(POS):RESULT_NEG_15V_STS") { field(DESC, "-15V Result") field(ZRST, "N/A") field(ONST, "Fail") field(TWST, "Pass") } # +24V value record(ai, "$(PRI):$(SEC):$(POS):24V_I") { field(DESC, "+15 Val") } # +24V result record(mbbi, "$(PRI):$(SEC):$(POS):RESULT_24V_STS") { field(DESC, "+15V Result") field(ZRST, "N/A") field(ONST, "Fail") field(TWST, "Pass") } # -130V value record(ai, "$(PRI):$(SEC):$(POS):NEG_130V_I") { field(DESC, "-130 Val") } # -15V result record(mbbi, "$(PRI):$(SEC):$(POS):RESULT_NEG_130V_STS") { field(DESC, "-130V Result") field(ZRST, "N/A") field(ONST, "Fail") field(TWST, "Pass") } ## Set total pressure record(ao, "$(PRI):$(SEC):$(POS):TOTALP_SP") { field(DESC, "Set Total P") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db setTotalP() $(PORT)") } ## Set calibration options # Set inlet calibration factor record(mbbo, "$(PRI):$(SEC):$(POS):CALOPT_INLET_SEL") { field(DESC, "Set Inlet Cal Factor") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db calibrationOpt($(PRI),$(SEC),$(POS)) $(PORT)") field(ZRST, "Off") field(ONST, "Default") field(TWST, "Current") } # Set detector calibration factor record(mbbo, "$(PRI):$(SEC):$(POS):CALOPT_DETC_SEL") { field(DESC, "Set Detector Cal Factor") field(ZRST, "Off") field(ONST, "Default") field(TWST, "Current") } ## Set calibration factor for a given set of source parameters and detector parameters # Specify source index record(mbbo, "$(PRI):$(SEC):$(POS):DETCFACTOR_SRCINDX_SEL") { field(DESC, "Set Source Index") field(ZRST, "Source Index 0") field(ONST, "Source Index 1") field(TWST, "Source Index 2") field(THST, "Source Index 3") field(FRST, "Source Index 4") field(FVST, "Source Index 5") field(SXST, "Source Index 6") } # Specify detector index record(mbbo, "$(PRI):$(SEC):$(POS):DETCFACTOR_DETCINDX") { field(DESC, "Set Detector Index") field(ZRST, "Faraday") field(ONST, "Multiplier 1") field(TWST, "Multiplier 2") field(THST, "Multiplier 3") } # Select a particular filament record(bo, "$(PRI):$(SEC):$(POS):DETCFACTOR_FIL_SEL") { field(DESC, "Filament Select") field(ZNAM, "1") field(ONAM, "2") } # Set a new calibration factor record(ao, "$(PRI):$(SEC):$(POS):DETCFACTOR_SP") { field(DESC, "Set Detector Factor") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db detectorFactor($(PRI),$(SEC),$(POS)) $(PORT)") } ## Set a calibration date for a given set of source parameters and detector parameters record(stringout, "$(PRI):$(SEC):$(POS):DETCCALDATE_SP") { field(DESC, "Set Cal Date") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db detectorCalDate($(PRI),$(SEC),$(POS)) $(PORT)") } ## Set the multiplier voltage for a given set of source parameters and detector parameters record(ao, "$(PRI):$(SEC):$(POS):DETCE_SP") { field(DESC, "Set Multiplier E") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db detectorVoltage($(PRI),$(SEC),$(POS)) $(PORT)") } ## Add a measurement to the scans list of measurement record(mbbo, "$(PRI):$(SEC):$(POS):SCANADD_SEL") { field(DESC, "Select Scan Type") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db scanAdd() $(PORT)") field(ZRST, "Analog1") field(ONST, "Bar1") field(FLNK, "$(PRI):$(SEC):$(POS):KILLTRACKERB") } ## Start a scan running and will re-trigger the scan automatically the number of times specified by number record(bo, "$(PRI):$(SEC):$(POS):SCAN_CMD") { field(DESC, "Start/Stop Scan") field(ZNAM, "Stop") field(ONAM, "Start") field(OUT, "$(PRI):$(SEC):$(POS):SCAN_DFOUT PP") } record(dfanout, "$(PRI):$(SEC):$(POS):SCAN_DFOUT") { field(DESC, "Scan Fanout") field(OUTA, "$(PRI):$(SEC):$(POS):SCANSTRT_CMD PP") field(OUTB, "$(PRI):$(SEC):$(POS):SCANSTOP-Cmd PP") field(OUTC, "$(PRI):$(SEC):$(POS):Scan-State.DISA") } record(bo, "$(PRI):$(SEC):$(POS):SCANSTRT_CMD") { field(DESC, "Scan Start") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db scanStart($(PRI),$(SEC),$(POS)) $(PORT)") field(SDIS, "$(PRI):$(SEC):$(POS):SCAN_CMD") field(DISV, "0") field(FLNK, "$(PRI):$(SEC):$(POS):STRTTIME_I") } record(stringin, "$(PRI):$(SEC):$(POS):STRTTIME_I") { field(DESC, "Start Time") field(DTYP, "Soft Timestamp") field(INP, "@%b %d, %Y %H:%M:%S.%09f") } record(longout, "$(PRI):$(SEC):$(POS):SCANNUM_SP") { field(DESC, "Scan Start") field(PINI, "1") field(VAL, "32000") } ## Mass pressure record(ai, "$(PRI):$(SEC):$(POS):PR_MASS10_I") { field(DESC, "Mass10 Pr") field(PREC, "14") } record(ai, "$(PRI):$(SEC):$(POS):PR_MASS11_I") { field(DESC, "Mass10 Pr") field(PREC, "14") } record(ai, "$(PRI):$(SEC):$(POS):PR_MASS12_I") { field(DESC, "Mass10 Pr") field(PREC, "14") } record(ai, "$(PRI):$(SEC):$(POS):PR_MASS13_I") { field(DESC, "Mass10 Pr") field(PREC, "14") } record(ai, "$(PRI):$(SEC):$(POS):PR_MASS14_I") { field(DESC, "Mass10 Pr") field(PREC, "14") } record(ai, "$(PRI):$(SEC):$(POS):PR_MASS15_I") { field(DESC, "Mass10 Pr") field(PREC, "14") } record(ai, "$(PRI):$(SEC):$(POS):PR_MASS16_I") { field(DESC, "Mass10 Pr") field(PREC, "14") } record(ai, "$(PRI):$(SEC):$(POS):PR_MASS17_I") { field(DESC, "Mass10 Pr") field(PREC, "14") } record(ai, "$(PRI):$(SEC):$(POS):PR_MASS18_I") { field(DESC, "Mass10 Pr") field(PREC, "14") } record(ai, "$(PRI):$(SEC):$(POS):PR_MASS19_I") { field(DESC, "Mass10 Pr") field(PREC, "14") } record(ai, "$(PRI):$(SEC):$(POS):PR_MASS20_I") { field(DESC, "Mass10 Pr") field(PREC, "14") } ## Stop a scan running and remove all measurements from the scan list record(bo, "$(PRI):$(SEC):$(POS):SCANSTOP-Cmd") { field(DESC, "Scan Stop") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db scanStop() $(PORT)") field(SDIS, "$(PRI):$(SEC):$(POS):SCAN_CMD") field(DISV, "1") } ## Re-trigger the scan specified by number record(bo, "$(PRI):$(SEC):$(POS):SCANRESUME_CMD") { field(DESC, "Scan Resume") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db scanResume($(PRI),$(SEC),$(POS)) $(PORT)") field(SDIS, "$(PRI):$(SEC):$(POS):SCANSTRT_CMD") field(DISV, "0") field(FLNK, "$(PRI):$(SEC):$(POS):STRTTIME_I") } ## Restart the current scan from the beginning record(bo, "$(PRI):$(SEC):$(POS):SCANRESTRT_CMD") { field(DESC, "Scan Restart") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db scanRestart() $(PORT)") field(SDIS, "$(PRI):$(SEC):$(POS):SCANSTRT_CMD") field(DISV, "0") } ## Select a measurement to act upon record(stringout, "$(PRI):$(SEC):$(POS):MEASADD_SEL") { field(DESC, "Measurement Sel") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db measSelect() $(PORT)") } # Set new start mass for the analog or barchart measurement record(longout, "$(PRI):$(SEC):$(POS):MEASSTRTMASS_SP") { field(DESC, "Set Start Mass") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db measStartMass() $(PORT)") field(LOPR, "1") field(HOPR, "100") field(PINI, "1") } # Set new end mass for the analog or barchart measurement record(longout, "$(PRI):$(SEC):$(POS):MEASENDMASS_SP") { field(DESC, "Set End Mass") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db measEndMass() $(PORT)") field(LOPR, "1") field(HOPR, "100") field(PINI, "1") } # Set number of scans of consecutive full scale readings before skipping mass. 0 to disable record(longout, "$(PRI):$(SEC):$(POS):MEASMULTSKIPAUTOPRO_SP") { field(DESC, "Set Auto Skip Protect") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db measMultSkipAutoPro() $(PORT)") } # Add a mass to the list of masses to be skipped by the selected measurement when multiplier is being used record(longout, "$(PRI):$(SEC):$(POS):MEASMULTSKIPMASSADD_SP") { field(DESC, "Add Skip Mass") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db measMultSkipMassAdd() $(PORT)") field(LOPR, "1") field(HOPR, "100") } # Remove a mass from the multiplier skip list so that it will be scanned again with the multiplier detector record(longout, "$(PRI):$(SEC):$(POS):MEASMULT_SKPMASS_RM_SP") { field(DESC, "Remove Skip Mass") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db measMultSkipMassRemove() $(PORT)") field(LOPR, "1") field(HOPR, "100") } # Remove all masses from the multiplier skip list so that they will again be scanned with the multiplier detector record(bo, "$(PRI):$(SEC):$(POS):MEASSKIPMASSRM_ALL_CMD") { field(DESC, "Remove All Skip Mass") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db measMultSkipMassRemoveAll() $(PORT)") } # Remove all measurements from the sensor record(bo, "$(PRI):$(SEC):$(POS):MEASREMOVEALL_CMD") { field(DESC, "Remove All Meas") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db measRemoveAll() $(PORT)") } ## Remove specified measurement from the sensor record(mbbo, "$(PRI):$(SEC):$(POS):MEASREMOVE_CMD") { field(DESC, "Measurement Remove") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db measRemove() $(PORT)") field(ZRST, "Analog1") field(ONST, "Bar1") } ## Set a source settings parameters ion energy setting record(ao, "$(PRI):$(SEC):$(POS):SRCIONNRG_SP") { field(DESC, "Set Ion Energy") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db sourceIonEnergy($(PRI),$(SEC),$(POS)) $(PORT)") field(LOPR, "0") field(HOPR, "10") field(EGU, "eV") } ## Set a source settings parameters emission setting record(ao, "$(PRI):$(SEC):$(POS):SRCEMISSION_SP") { field(DESC, "Set Emission") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db sourceEmission($(PRI),$(SEC),$(POS)) $(PORT)") field(LOPR, "0") field(HOPR, "5") field(EGU, "mA") } ## Set a source settings parameters extract setting record(ao, "$(PRI):$(SEC):$(POS):SRCEXTRACT_SP") { field(DESC, "Set Extract") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db sourceExtract($(PRI),$(SEC),$(POS)) $(PORT)") field(LOPR, "-130") field(HOPR, "0") field(EGU, "V") } ## Set a source settings parameters electron energy setting record(ao, "$(PRI):$(SEC):$(POS):SRCENRG_SP") { field(DESC, "Set e Energy") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db sourceENrg($(PRI),$(SEC),$(POS)) $(PORT)") field(LOPR, "0") field(HOPR, "100") field(EGU, "eV") } ## Set the number of readings that should be taken and averaged before results are sent back record(longout, "$(PRI):$(SEC):$(POS):INDX_AI_SP") { field(DESC, "Set AI Index") } record(longout, "$(PRI):$(SEC):$(POS):AIAVGCNT_SP") { field(DESC, "Set Avg Cnt") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db aiAvgCnt($(PRI),$(SEC),$(POS)) $(PORT)") } ## Enable or disable analog input readings from being sent when in control of the sensor record(bo, "$(PRI):$(SEC):$(POS):AIENA_SEL") { field(DESC, "Enable/Disable AI") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db aiEnable($(PRI),$(SEC),$(POS)) $(PORT)") field(ZNAM, "False") field(ONAM, "True") } # Set the interval between analog input readings in the sensor record(longout, "$(PRI):$(SEC):$(POS):AIINTER_SP") { field(DESC, "Set AI Interval") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db aiInterval($(PRI),$(SEC),$(POS)) $(PORT)") } ## Set a given analog output channel to the specified voltage record(longout, "$(PRI):$(SEC):$(POS):INDX_AO_SP") { field(DESC, "Set AO Index") } record(ao, "$(PRI):$(SEC):$(POS):AO_SP") { field(DESC, "Set AO Voltage") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db aoVal($(PRI),$(SEC),$(POS)) $(PORT)") } ## Set audio frequency record(longout, "$(PRI):$(SEC):$(POS):AUDIOFRQ_SP") { field(DESC, "Set Audio Frq") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db audioFrequency() $(PORT)") } ## Set audio mode record(mbbo, "$(PRI):$(SEC):$(POS):AUDIOMODE_SEL") { field(DESC, "Set Audio Mode") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db audioMode() $(PORT)") field(ZRST, "Off") field(ONST, "Automatic") field(TWST, "Manual") } ## Set the time that either pin 6 or 7 will remain set for after they're initially set record(longout, "$(PRI):$(SEC):$(POS):DIGIMAXPB67ONT_SP") { field(DESC, "Set Digi Max PB67 OnT") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db digitalMaxPB67OnT() $(PORT)") field(EGU, "s") } ## Set digital outputs according to the value specified record(longout, "$(PRI):$(SEC):$(POS):DIGIOUT_PA_SP") { field(DESC, "Set PA Digi Out") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db digitalOut(A) $(PORT)") field(LOPR, "0") field(HOPR, "255") } record(longout, "$(PRI):$(SEC):$(POS):DIGIOUT_PB_SP") { field(DESC, "Set PB Digi Out") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db digitalOut(B) $(PORT)") field(LOPR, "0") field(HOPR, "255") } ## Save changes record(bo, "$(PRI):$(SEC):$(POS):SAVECHANGE_CMD") { field(DESC, "Save Changes") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db saveChanges() $(PORT)") } ## Run a degas operation record(bo, "$(PRI):$(SEC):$(POS):STRTDEGAS_CMD") { field(DESC, "Start Degas") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db startDegas($(PRI),$(SEC),$(POS)) $(PORT)") } record(longout, "$(PRI):$(SEC):$(POS):STRTDEGAS_STRTPWR_SP") { field(DESC, "Degas Start Pwr") field(LOPR, "0") field(HOPR, "100") field(VAL, "10") field(EGU, "%") } record(longout, "$(PRI):$(SEC):$(POS):STRTDEGAS_ENDPWR_SP") { field(DESC, "Degas End Pwr") field(LOPR, "0") field(HOPR, "100") field(VAL, "85") field(EGU, "%") } record(longout, "$(PRI):$(SEC):$(POS):STRTDEGAS_RAMP_PRD_SP") { field(DESC, "Degas Ramp Period") field(VAL, "90") field(EGU, "s") } record(longout, "$(PRI):$(SEC):$(POS):STRTDEGAS_MAXPWR_PRD_SP") { field(DESC, "Degas Max Pwr Period") field(VAL, "240") field(EGU, "s") } record(longout, "$(PRI):$(SEC):$(POS):STRT_DEGAS_SETTLE_PRD_SP") { field(DESC, "Degas Resettle Period") field(VAL, "30") field(EGU, "s") } ## End a degas operation record(bo, "$(PRI):$(SEC):$(POS):STOPDEGAS_CMD") { field(DESC, "Stop Degas") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db stopDegas() $(PORT)") } ## Copy the specified source tables alignement data to all other source tables record(bo, "$(PRI):$(SEC):$(POS):SRCALIGNCPTOALL_CMD") { field(DESC, "Copy Alignment To All") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db sourceAlignCopyToAll($(PRI),$(SEC),$(POS)) $(PORT)") } record(mbbo, "$(PRI):$(SEC):$(POS):SRCALIGN_SRCINDX_SEL") { field(DESC, "Copy Alignment To All") field(ZRST, "Source Index 0") field(ONST, "Source Index 1") field(TWST, "Source Index 2") field(THST, "Source Index 3") field(FRST, "Source Index 4") field(FVST, "Source Index 5") field(SXST, "Source Index 6") } ## Remove a specified mass from mass alignement table for the specified source table record(longout, "$(PRI):$(SEC):$(POS):SRCALIGNREMOVE_MASS_SP") { field(DESC, "Mass to Remove") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db sourceAlignRemove($(PRI),$(SEC),$(POS)) $(PORT)") field(LOPR, "0") field(HOPR, "100") } ## Copy the specified source tables resolution data to all other source tables record(bo, "$(PRI):$(SEC):$(POS):SRCRESCOPYTOALL_CMD") { field(DESC, "Copy Resolution To All") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db sourceResCopyToAll($(PRI),$(SEC),$(POS)) $(PORT)") } record(mbbo, "$(PRI):$(SEC):$(POS):SourceRes:SRCINDX_SEL") { field(DESC, "Copy Resolution To All") field(ZRST, "Source Index 0") field(ONST, "Source Index 1") field(TWST, "Source Index 2") field(THST, "Source Index 3") field(FRST, "Source Index 4") field(FVST, "Source Index 5") field(SXST, "Source Index 6") } ## Remove a specified mass from mass resolution table for the specified source table record(longout, "$(PRI):$(SEC):$(POS):SRCRESREMOVE_MASS_SP") { field(DESC, "Mass to Remove") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db sourceResRemove($(PRI),$(SEC),$(POS)) $(PORT)") field(LOPR, "0") field(HOPR, "100") } # Set pole bias settings to a specified source table entry record(mbbo, "$(PRI):$(SEC):$(POS):SourcePoleBias:SRCINDX_SEL") { field(DESC, "Source Index Sel") field(ZRST, "Source Index 0") field(ONST, "Source Index 1") field(TWST, "Source Index 2") field(THST, "Source Index 3") field(FRST, "Source Index 4") field(FVST, "Source Index 5") field(SXST, "Source Index 6") } record(ao, "$(PRI):$(SEC):$(POS):SRCPOLEBIAS_SP") { field(DESC, "Set Pole Bias") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db sourcePoleBias($(PRI),$(SEC),$(POS)) $(PORT)") field(LOPR, "-10") field(HOPR, "10") } ## Set the number of readings that should be taken and averaged before results are sent back record(longout, "$(PRI):$(SEC):$(POS):AIINDX_SP") { field(DESC, "AI Index Set") } record(longout, "$(PRI):$(SEC):$(POS):DIAGINAVGCNT_SP") { field(DESC, "Set DiagIn AvgCnt") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db diagInAvgCnt($(PRI),$(SEC),$(POS)) $(PORT)") } ## Enable or disable diagnostic input readings from being sent when in control of the sensor record(bo, "$(PRI):$(SEC):$(POS):DIAG_ENA_CMD") { field(DESC, "Enable/Disable DianIn") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db diagInEnable($(PRI),$(SEC),$(POS)) $(PORT)") field(ZNAM, "False") field(ONAM, "True") } # Set the interval between diagnostic input readings in the sensor record(longout, "$(PRI):$(SEC):$(POS):DIAGININTER_SP") { field(DESC, "Set DiagIn Interval") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db diagInInterval($(PRI),$(SEC),$(POS)) $(PORT)") } ## Get measurement time, zero mass, zero mass value, and RF trip status record(longin, "$(PRI):$(SEC):$(POS):MEAS_T_I") { field(DESC, "Measurement Time") field(DTYP, "stream") field(INP, "@mks_rga_meas.proto.db getMeasT() $(PORT)") field(SCAN, "I/O Intr") # field(FLNK, "$(PRI):$(SEC):$(POS):Trig1-Evt_") } #record (event, "$(PRI):$(SEC):$(POS):Trig1-Evt_") #{ # field (VAL, "1") #} record(ai, "$(PRI):$(SEC):$(POS):ZERO_I") { field(DESC, "Zero Reading Value") field(DTYP, "stream") field(INP, "@mks_rga_meas.proto.db getMeasZero($(PRI),$(SEC),$(POS)) $(PORT)") field(SCAN, "I/O Intr") field(PREC, "14") } record(ai, "$(PRI):$(SEC):$(POS):ZERO_MASS_I") { field(DESC, "Analog Measurement") field(PREC, "1") field(FLNK, "$(PRI):$(SEC):$(POS):TRIG2_EVT") } record (event, "$(PRI):$(SEC):$(POS):TRIG2_EVT") { field (VAL, "$(EVENT)") } ## Get current measurement mass and value record(ai, "$(PRI):$(SEC):$(POS):CUR_I") { field(DESC, "Current Measurement") field(DTYP, "stream") field(INP, "@mks_rga_meas.proto.db getMeasVal($(PRI),$(SEC),$(POS)) $(PORT)") field(SCAN, "I/O Intr") field(PREC, "14") field(FLNK, "$(PRI):$(SEC):$(POS):CUR_CALC") field(FLNK, "$(PRI):$(SEC):$(POS):STOPTIME_I") } record(stringin, "$(PRI):$(SEC):$(POS):STOPTIME_I") { field(DESC, "Stop Time") field(DTYP, "Soft Timestamp") field(INP, "@%b %d, %Y %H:%M:%S.%09f") field(FLNK, "$(PRI):$(SEC):$(POS):CUR_CALC") } #make 0 results at noise level and convert to torr from pascal (raw input is pascal) record(calc, "$(PRI):$(SEC):$(POS):CUR_CALC") { field(DESC, "Current Measurement") field(INPA, "$(PRI):$(SEC):$(POS):CUR_I") field(INPB, "1E-15") field(INPC, "133.322368") field(EGU, "TORR") field(CALC, "(A<=0)?B:(A/C)") } record(ai, "$(PRI):$(SEC):$(POS):CURMASS_I") { field(DESC, "Current Mass") field(PREC, "5") field(VAL, "0") field(EGU, "AMU") field(FLNK, "$(PRI):$(SEC):$(POS):STOPSTATUS") } #Prevent Sensor updates from messing up repeat scan record(calc, "$(PRI):$(SEC):$(POS):STOPSTATUS") { field(DESC, "Stop Sensor/Fila State") field(INPA, "$(PRI):$(SEC):$(POS):CURMASS_I") field(CALC, "A>=99?1:0") } #releases and regains control of the RGA in order to commit graph changes record(dfanout, "$(PRI):$(SEC):$(POS):GRAPH_CHANGE") { field(DESC, "Releases and Regain Control") field(OUTA, "$(PRI):$(SEC):$(POS):RELEASE_CMD.PROC") field(OUTB, "$(PRI):$(SEC):$(POS):CTL_CMD.PROC") field(OUTC, "$(PRI):$(SEC):$(POS):GRAPH_DFOUT PP") } ####### #Gets current scan number record(ai, "$(PRI):$(SEC):$(POS):CURSCAN_I") { field(DESC, "Get Current Scan Number") field(DTYP, "stream") field(INP, "@mks_rga_meas.proto.db getScanNum($(PRI),$(SEC),$(POS)) $(PORT)") field(SCAN, "I/O Intr") field(PREC, "0") field(FLNK, "$(PRI):$(SEC):$(POS):CURSCAN_CALC") } #######Code used for telling the RGA to continuously scan##### #INPC comes from the toggle button on the edm screen and is used as an on/off #switch for continuous scanning record(calcout, "$(PRI):$(SEC):$(POS):CURSCAN_CALC") { field(DESC, "Continual Scanning") field(INPA, "$(PRI):$(SEC):$(POS):CURSCAN_I") field(INPB, "$(PRI):$(SEC):$(POS):SCANNUM_SP") field(OOPT, "When Non-zero") field(CALC, "(A==B)&&(C==1)?1:0") field(OUT, "$(PRI):$(SEC):$(POS):REPEAT_SCANSTOP PP") } #In order to properly continuously scan certain commands must be sent to the RGA #in order. #Order: Stop the current Scan, check what current graph is (bar or analog), #add a new scan, start the new Scan #Stop the current scan record(bo, "$(PRI):$(SEC):$(POS):REPEAT_SCANSTOP") { field(DESC, "Stop scan to repeat") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db scanStop() $(PORT)") field(FLNK, "$(PRI):$(SEC):$(POS):REPEAT_SCANCHECK") } #Check which graph is running (analog or bar) Note: if !Bar then it must be an analog record(scalcout, "$(PRI):$(SEC):$(POS):REPEAT_SCANCHECK") { field(DESC, "Check Type of Graph") field(INAA, "$(PRI):$(SEC):$(POS):SCANADD_SEL") field(BB, "Bar1") field(CC, "Analog1") field(CALC, "(AA==BB)?BB:CC") field(OUT, "$(PRI):$(SEC):$(POS):REPEAT_SCANADD PP") } #Add a new bar scan if a bar graph is the correct output record(mbbo, "$(PRI):$(SEC):$(POS):REPEAT_SCANADD") { field(DESC, "Scan Out") field(DTYP, "stream") field(ZRST, "Analog1") field(ONST, "Bar1") field(OUT, "@mks_rga_common.proto.db scanAdd() $(PORT)") field(FLNK, "$(PRI):$(SEC):$(POS):REPEAT_SCANSTRT") } #Start the scan again record(bo, "$(PRI):$(SEC):$(POS):REPEAT_SCANSTRT") { field(DESC, "Start the scan again") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db scanStart($(PRI),$(SEC),$(POS)) $(PORT)") } ##### SUBROUTINE RECORD(S) ####### record(sub, "$(PRI):$(SEC):$(POS):PRESS_ARRAY"){ field(DESC, "Subroutine Record") field(INAM, "mksRGA_InitArrayOut") field(SNAM, "mksRGA_ArrayOut") field(INPA, "$(PRI):$(SEC):$(POS):CURMASS_I CP") field(INPB, "$(PRI):$(SEC):$(POS):CUR_CALC CP") field(INPC, "$(PRI):$(SEC):$(POS):PRESS_BUF") field(INPD, "$(PRI):$(SEC):$(POS):TOTAL_PRESS.VAL PP") field(INPE, "$(PRI):$(SEC):$(POS):HYDR_PRESS.VAL PP") field(FLNK, "$(PRI):$(SEC):$(POS):PRESS_BUF") } record(waveform, "$(PRI):$(SEC):$(POS):PRESS_BUF") { field(DTYP, "Soft Channel") field(NELM, "101") field(FTVL, "DOUBLE") field(PREC, "14") field(DISA, "1") } ##auto stop on last scan## record(calcout, "$(PRI):$(SEC):$(POS):SCANSTOP_CALC") { field(DESC, "Stop Scan at End") field(INPA, "$(PRI):$(SEC):$(POS):CURSCAN_I CP") field(INPB, "$(PRI):$(SEC):$(POS):SCANNUM_SP") field(INPC, "$(PRI):$(SEC):$(POS):CURMASS_I") field(INPD, "$(PRI):$(SEC):$(POS):CURSCAN_CALC.C") field(CALC, "((A==B)&&(C==100))&&!D?1:0") field(OOPT, "When Non-zero") field(OUT, "$(PRI):$(SEC):$(POS):SCANSTOP.PROC") } record(bo, "$(PRI):$(SEC):$(POS):SCANSTOP") { field(DESC, "Stop scan to repeat") field(DTYP, "stream") field(OUT, "@mks_rga_common.proto.db scanStop() $(PORT)") field(FLNK, "$(PRI):$(SEC):$(POS):SCANSTOP_CALC") } ##Sum of partial pressures## record(ai, "$(PRI):$(SEC):$(POS):TOTAL_PRESS") { field(DESC, "Sum of Partial Pressures") field(PINI, "1") field(PREC, "3") } ##Sum of AMU 45 and up## record(ai, "$(PRI):$(SEC):$(POS):HYDR_PRESS") { field(DESC, "Sum of AMU 45+ Pressures") field(PINI, "1") field(PREC, "3") } #Used to disable analog graph when bar is running record(scalcout, "$(PRI):$(SEC):$(POS):KILLTRACKERB") { field(DESC, "Check Type of Graph") field(INAA, "$(PRI):$(SEC):$(POS):SCANADD_SEL") field(BB, "Bar1") field(CALC, "(AA==BB)?0:1") field(OUT, "$(PRI):$(SEC):$(POS):KILLGRAPHOUT.VAL") field(FLNK, "$(PRI):$(SEC):$(POS):KILLGRAPHOUT") } record(dfanout, "$(PRI):$(SEC):$(POS):KILLGRAPHOUT") { field(DESC, "Fanout Graph Kill") field(OUTA, "$(PRI):$(SEC):$(POS):A_BUF.DISV") field(OUTB, "$(PRI):$(SEC):$(POS):PRESS_BUF.DISV") }