# File: wirescanner_status.db # # Description: # This database is used to get the status PV on EDM # Homes and encoder # It uses the motor record to get PV`s used used by HLA # # Macros: # P - Controller prefix # M - motor record(bi, "$(P)MOTR_ENABLED_STS") { field(DESC, "Enabled status") field(ZNAM, "Not Ready for WireScan") field(ONAM, "Ready for wirescan") } record(calcout, "$(P)CALC_ENABLED_STS") { field(DESC, "Check if enabled") field(CALC, "A&&B&&C") field(INPA, "$(P)MOTR_INIT_STS CP") field(INPB, "$(P)MOTR_ON_STS CP") field(INPC, "$(P)MOTR_HOMED_STS CP") field(OUT, "$(P)MOTR_ENABLED_STS PP") } record(bi, "$(P)MOTR_INIT_STS") { field(DESC, "Init status") field(ZNAM, "Not Initialized") field(ONAM, "Initialized") } record(bi, "$(P)MOTR_ON_STS") { field(DESC, "Torque status") field(INP, "$(P)AXIS_STATUS_S1.B0 CP") field(ZNAM, "Torque OFF") field(ONAM, "Torque ON") } record(bi, "$(P)MOTR_HOMED_STS") { field(DESC, "Homed") field(INP, "$(P)AXIS_STATUS_S1.B1 CP") field(ZNAM, "Not Homed") field(ONAM, "Homed") } record(bi, "$(P)MOTR_MOTION_ACT_STS") { field(DESC, "Motion Active") field(INP, "$(P)AXIS_STATUS_S1.B3 CP") field(ZNAM, "Not Moving") field(ONAM, "Moving") } record(bi, "$(P)MOTR_ERROR_STS") { field(DESC, "Error Status") field(INP, "$(P)AXIS_ERROR_CALC CP") field(ZNAM, "No Error") field(ONAM, "ERROR") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") } record(calcout, "$(P)AXIS_ERROR_CALC") { field(DESC, "Check if Axis at fault") field(CALC, "(A>0)?1:0") field(INPA, "$(P)AXIS_FAULT CP") field(OUT, "$(P)MOTR_ERROR_STS PP") field(ASG, "Internal") }