# Record example for a SequenceCommand register.
# It is a bo record with type asynUInt32Digital.
# The OUT field has the form @asynMask(PORT,ADDR,MASK)PARAM where:
#  - PORT  : The asyn port name. It must match the port name given
#            when calling "YCPSWASYNConfig" on st.cmd
#  - PARAM : The asyn parameter name. It must be defined in the
#            dictionary file and assigned to a register
#  - MASK  : It is always 1 (we only have 1-bit commands)
#  - ADDR  : Address based on the type of register interface.
#            For SequenceCommand is 4
#==================================================================

record(bo,      "$(P):$(R)") {
    field(DTYP, "asynUInt32Digital")
    field(DESC, "$(DESC)")
    field(PINI, "$(PINI)")
    field(SCAN, "$(SCAN)")
    field(OUT,  "@asynMask($(PORT),4,1)$(PARAM)")
    field(ZNAM, "Run")
    field(ONAM, "Stop")
}