########################################################## # ID Limit Switches - Only Minimum limit switches # maximum limit switches are tied to E-Stop circuit ########################################################## record(bi,"$(U):DSWMinLimit") { field(DESC,"DS Wall Min Limit Status") field(SCAN,".1 second") field(DTYP,"asynUInt32Digital") field(INP,"@asynMask($(PORT) 0x800000 0x1)") field(OSV,"MAJOR") field(ZNAM,"Limit OK") field(ONAM,"Limit Hit") } record(bi,"$(U):USWMinLimit") { field(DESC,"US Wall Min Limit Switch") field(SCAN,".1 second") field(DTYP,"asynUInt32Digital") field(INP,"@asynMask($(PORT) 0x800000 0x2)") field(OSV,"MAJOR") field(ZNAM,"Limit OK") field(ONAM,"Limit Hit") } record(bi,"$(U):DSAMinLimit") { field(DESC,"DS Aisle Min Limit Status") field(SCAN,".1 second") field(DTYP,"asynUInt32Digital") field(INP,"@asynMask($(PORT) 0x800000 0x4)") field(OSV,"MAJOR") field(ZNAM,"Limit OK") field(ONAM,"Limit Hit") } record(bi,"$(U):USAMinLimit") { field(DESC,"US Aisle Min Limit Switch") field(SCAN,".1 second") field(DTYP,"asynUInt32Digital") field(INP,"@asynMask($(PORT) 0x800000 0x8)") field(OSV,"MAJOR") field(ZNAM,"Limit OK") field(ONAM,"Limit Hit") } record(calc,"$(U):LimitStatus") { field(DESC,"LimitsStatus") field(CALC,"A||B||C||D") field(INPA,"$(U):USWMinLimit.VAL CP MS") field(INPB,"$(U):USAMinLimit.VAL CP MS") field(INPC,"$(U):DSWMinLimit.VAL CP MS") field(INPD,"$(U):DSAMinLimit.VAL CP MS") } ########################################################## # Phase Shifter Limits ########################################################## record(bi,"$(U):PSWMinLimit") { field(DESC,"PS Wall Min Limit Status") field(SCAN,"1 second") field(DTYP,"asynUInt32Digital") field(INP,"@asynMask($(PORT) 0x800000 0x10)") field(OSV,"MAJOR") field(ZNAM,"Limit OK") field(ONAM,"Limit Hit") } record(bi,"$(U):PSAMinLimit") { field(DESC,"PS Aisle Min Limit Status") field(SCAN,"1 second") field(DTYP,"asynUInt32Digital") field(INP,"@asynMask($(PORT) 0x800000 0x20)") field(OSV,"MAJOR") field(ZNAM,"Limit OK") field(ONAM,"Limit Hit") } ########################################################## record(bo,"$(U):LimitLockout") { field(DESC,"Max Limit Lockout") # field(PINI,"YES") field(ASG,"SYSTEM") field(DTYP,"asynUInt32Digital") field(OMSL,"supervisory") field(DOL,"0") field(OUT,"@asynMask($(PORT1) 0x800030 0x1)") field(ZNAM,"Normal Limit Logic") field(ONAM,"Allow Motor Open") field(OSV,"MINOR") } record(bi,"$(U):LimitLockWallRdbk") { field(DESC,"Limit Lockout Readback") field(DTYP,"asynUInt32Digital") field(SCAN,"1 second") field(INP,"@asynMask($(PORT1) 0x800030 0x1)") field(OSV,"MINOR") field(ZNAM,"Normal Limit Logic") field(ONAM,"Allow Motor Open") } record(bi,"$(U):LimitLockAisleRdbk") { field(DESC,"Limit Lockout Readback") field(DTYP,"asynUInt32Digital") field(SCAN,"1 second") field(INP,"@asynMask($(PORT1) 0x800030 0x2)") field(OSV,"MINOR") field(ZNAM,"Normal Limit Logic") field(ONAM,"Allow Motor Open") } ########################################################## record(bi,"$(U):DSANegMotorLimit") { field(DESC,"DSA Neg Motor Limit") field(SCAN,"1 second") field(DTYP,"asynUInt32Digital") field(INP,"@asynMask($(PORT) 0x800000 0x400)") field(OSV,"MAJOR") field(ZNAM,"Limit OK") field(ONAM,"DSA Neg Limit") } record(bi,"$(U):DSAPosMotorLimit") { field(DESC,"DSA Pos Motor Limit") field(SCAN,"1 second") field(DTYP,"asynUInt32Digital") field(INP,"@asynMask($(PORT) 0x800000 0x4000)") field(OSV,"MAJOR") field(ZNAM,"Limit OK") field(ONAM,"DSA Pos Limit") } record(bi,"$(U):DSWNegMotorLimit") { field(DESC,"DSW Neg Motor Limit") field(SCAN,"1 second") field(DTYP,"asynUInt32Digital") field(INP,"@asynMask($(PORT) 0x800000 0x100)") field(OSV,"MAJOR") field(ZNAM,"Limit OK") field(ONAM,"DSW Neg Limit") } record(bi,"$(U):DSWPosMotorLimit") { field(DESC,"DSW Pos Motor Limit") field(SCAN,"1 second") field(DTYP,"asynUInt32Digital") field(INP,"@asynMask($(PORT) 0x800000 0x1000)") field(OSV,"MAJOR") field(ZNAM,"Limit OK") field(ONAM,"DSW Pos Limit") } record(bi,"$(U):USANegMotorLimit") { field(DESC,"USA Neg Motor Limit") field(SCAN,"1 second") field(DTYP,"asynUInt32Digital") field(INP,"@asynMask($(PORT) 0x800000 0x800)") field(OSV,"MAJOR") field(ZNAM,"Limit OK") field(ONAM,"USA Neg Limit") } record(bi,"$(U):USAPosMotorLimit") { field(DESC,"USA Pos Motor Limit") field(SCAN,"1 second") field(DTYP,"asynUInt32Digital") field(INP,"@asynMask($(PORT) 0x800000 0x8000)") field(OSV,"MAJOR") field(ZNAM,"Limit OK") field(ONAM,"USA Pos Limit") } record(bi,"$(U):USWNegMotorLimit") { field(DESC,"USW Neg Motor Limit") field(SCAN,"1 second") field(DTYP,"asynUInt32Digital") field(INP,"@asynMask($(PORT) 0x800000 0x200)") field(OSV,"MAJOR") field(ZNAM,"Limit OK") field(ONAM,"USW Neg Limit") } record(bi,"$(U):USWPosMotorLimit") { field(DESC,"USW Pos Motor Limit") field(SCAN,"1 second") field(DTYP,"asynUInt32Digital") field(INP,"@asynMask($(PORT) 0x800000 0x2000)") field(OSV,"MAJOR") field(ZNAM,"Limit OK") field(ONAM,"USW Pos Limit") } ##########################################################