# Flow Meter.gc PV status
record(bi, "${ALIAS}ALARM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@$(PLC) PEPSB5[$(INDEX)] B $(CHAN)")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Flow Meter.gc Bypass reset It is a push button
record(bo, "${ALIAS}RESET") {
  field(DESC, "Bypass Reset request")
  field(DTYP, "EtherIP")
  field(OUT , "@$(PLC) EEPSB5[$(INDEX)] B $(CHAN)")
  field(ZNAM, "RESET")
  field(ONAM, "RESET")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(HIGH, "2")
}

# Flow Meter.gc Alarm Bypass 
record(bo, "${ALIAS}BYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(OUT , "@$(PLC) EEPSB3[$(INDEX)] B $(CHAN)")
  info(autosaveFields,"VAL")
}

record(bi, "${ALIAS}BYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@$(PLC) PEPSB3[$(INDEX)] B $(CHAN)")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

# Flow high limit
record(ao, "${ALIAS}HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC) ${PLCTAG}.HLimit")
  field(EGU, "GPM")
  field(FLNK,"${ALIAS}HLIMCALC")
  field(PREC,2)
  info(autosaveFields,"VAL")
}

record(calcout, "${ALIAS}HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(OUT, "${ALIAS}.HIGH PP")
  field(INPA, "${ALIAS}HLIMDES PP")
  field(CALC, "A")
  field(FLNK,"${ALIAS}HLIMCALC2")
}

record(calcout, "${ALIAS}HLIMCALC2"){
  field(DESC, "Desired hihi limit") 
  field(OUT, "${ALIAS}.HIHI PP")
  field(INPA, "${ALIAS}HLIMDES PP")
  field(CALC, "A+1")
  info(autosaveFields,"CALC")
}

# Flow low limit
record(ao, "${ALIAS}LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(OUT, "@$(PLC) ${PLCTAG}.LLimit")
  field(EGU, "GPM")
  field(FLNK,"${ALIAS}LLIMCALC")
  field(PREC,2)
  info(autosaveFields,"VAL")
}
record(calcout, "${ALIAS}LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(OUT, "${ALIAS}.LOW PP")
  field(INPA, "${ALIAS}LLIMDES PP")
  field(CALC, "A")
  field(FLNK,"${ALIAS}LLIMCALC2")
}

record(calcout, "${ALIAS}LLIMCALC2"){
  field(DESC, "Desired lolo  limit") 
  field(OUT, "${ALIAS}.LOLO PP")
  field(INPA, "${ALIAS}LLIMDES PP")
  field(CALC, "A-1")
  info(autosaveFields,"CALC")
}