# # This template is used to control MPS outputs # # # Macros: # CHAN I/O channel on the I/O module # PLC Name of the ether_ip connection to PLC as defined in st.cmd # ALIAS EPICS name for the PV # MAD MAD name for the PV #============================================================================== #Alarm Bypass record(bo, "${ALIAS}MPSBYP") { field(DESC, "${MAD} MPS Byp Req") field(ZNAM, "NO BYPASS") field(ONAM, "BYPASS") field(ZSV, "NO_ALARM") field(OSV, "MINOR") field(DTYP, "EtherIP") field(OUT , "@$(PLC) MPSBypReq[INDEX] B $(CHAN)") info(autosaveFields,"VAL") } # Temperature PV Alarm status # Alarm channels are the PV bit record(bi, "${ALIAS}MPSALARM"){ field(DESC, "${MAD} MPS Alarm Sts") field(SCAN, "I/O Intr") field(DTYP, "EtherIP") field(INP , "@$(PLC) MPSAlarm[INDEX] B $(CHAN)") field(ONAM, "OK") field(ZNAM, "FAULT") field(OSV, "NO_ALARM") field(ZSV, "MAJOR") } # Temperature PV Alarm status # Alarm channels are the PV bit record(bi, "${ALIAS}ALARM"){ field(DESC, "${MAD} MPS Alarm Sts") field(SCAN, "I/O Intr") field(DTYP, "EtherIP") field(INP , "@$(PLC) IntlkAlarmStat[INDEX] B $(CHAN)") field(ONAM, "OK") field(ZNAM, "FAULT") field(OSV, "NO_ALARM") field(ZSV, "MAJOR") }