#============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "LASR:LR10:1:OSCILATOR") { field(DESC,"Primary Oscillator") field(SCAN, "1 second") field(INP, "LASR:LR10:1:OSCILATOR_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "75") field(LOLO, "64") field(HIGH, "72") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "LASR:LR10:1:OSCILATOR_AVG") { field(DESC, "Avg sig samples") field(INP, "LASR:LR10:1:OSCILATOR_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "LASR:LR10:1:OSCILATOR_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:LR10:TM01:M1_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:LR10:TM01:M1_CH1_TEMP") { field(DESC, "Primary Oscillator") field(FLNK, "LASR:LR10:1:OSCILATOR") field(CALC, "A*1.8+32") field(INPA, "BKHF:LR10:TM01:M1_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "75") field(LOLO, "64") field(HIGH, "72") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "LASR:LR10:1:OSCILATOR_DATA") field(ASG, "") } record(ai, "BKHF:LR10:TM01:M1_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-lr10-tm01:1:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:LR10:TM01:M1_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "LASR:LR10:1:REGEN") { field(DESC,"Primary Regen") field(SCAN, "1 second") field(INP, "LASR:LR10:1:REGEN_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "64") field(HIGH, "77") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "LASR:LR10:1:REGEN_AVG") { field(DESC, "Avg sig samples") field(INP, "LASR:LR10:1:REGEN_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "LASR:LR10:1:REGEN_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:LR10:TM01:M1_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:LR10:TM01:M1_CH2_TEMP") { field(DESC, "Primary Regen") field(FLNK, "LASR:LR10:1:REGEN") field(CALC, "A*1.8+32") field(INPA, "BKHF:LR10:TM01:M1_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "64") field(HIGH, "77") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "LASR:LR10:1:REGEN_DATA") field(ASG, "") } record(ai, "BKHF:LR10:TM01:M1_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-lr10-tm01:1:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:LR10:TM01:M1_CH2_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "LASR:LR10:1:MPA") { field(DESC,"Primary MPA") field(SCAN, "1 second") field(INP, "LASR:LR10:1:MPA_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "64") field(HIGH, "77") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "LASR:LR10:1:MPA_AVG") { field(DESC, "Avg sig samples") field(INP, "LASR:LR10:1:MPA_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "LASR:LR10:1:MPA_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:LR10:TM01:M2_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:LR10:TM01:M2_CH1_TEMP") { field(DESC, "Primary MPA") field(FLNK, "LASR:LR10:1:MPA") field(CALC, "A*1.8+32") field(INPA, "BKHF:LR10:TM01:M2_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "64") field(HIGH, "77") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "LASR:LR10:1:MPA_DATA") field(ASG, "") } record(ai, "BKHF:LR10:TM01:M2_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-lr10-tm01:2:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:LR10:TM01:M2_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "LASR:LR10:1:TRIPLER") { field(DESC,"Primary Tripler") field(SCAN, "1 second") field(INP, "LASR:LR10:1:TRIPLER_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "64") field(HIGH, "77") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "LASR:LR10:1:TRIPLER_AVG") { field(DESC, "Avg sig samples") field(INP, "LASR:LR10:1:TRIPLER_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "LASR:LR10:1:TRIPLER_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:LR10:TM01:M2_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:LR10:TM01:M2_CH2_TEMP") { field(DESC, "Primary Tripler") field(FLNK, "LASR:LR10:1:TRIPLER") field(CALC, "A*1.8+32") field(INPA, "BKHF:LR10:TM01:M2_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "64") field(HIGH, "77") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "LASR:LR10:1:TRIPLER_DATA") field(ASG, "") } record(ai, "BKHF:LR10:TM01:M2_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-lr10-tm01:2:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:LR10:TM01:M2_CH2_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "LASR:LR10:1:OSC_OUTLET") { field(DESC,"Primary Laser Chiller") field(SCAN, "1 second") field(INP, "LASR:LR10:1:OSC_OUTLET_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "77") field(LOLO, "64") field(HIGH, "74") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "LASR:LR10:1:OSC_OUTLET_AVG") { field(DESC, "Avg sig samples") field(INP, "LASR:LR10:1:OSC_OUTLET_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "LASR:LR10:1:OSC_OUTLET_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:LR10:TM01:M3_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:LR10:TM01:M3_CH1_TEMP") { field(DESC, "Primary Laser Chiller") field(FLNK, "LASR:LR10:1:OSC_OUTLET") field(CALC, "A*1.8+32") field(INPA, "BKHF:LR10:TM01:M3_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "77") field(LOLO, "64") field(HIGH, "74") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "LASR:LR10:1:OSC_OUTLET_DATA") field(ASG, "") } record(ai, "BKHF:LR10:TM01:M3_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-lr10-tm01:3:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:LR10:TM01:M3_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "LASR:LR10:1:REGENVO") { field(DESC,"Regen EVO") field(SCAN, "1 second") field(INP, "LASR:LR10:1:REGENVO_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "64") field(HIGH, "77") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "LASR:LR10:1:REGENVO_AVG") { field(DESC, "Avg sig samples") field(INP, "LASR:LR10:1:REGENVO_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "LASR:LR10:1:REGENVO_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:LR10:TM01:M6_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:LR10:TM01:M6_CH1_TEMP") { field(DESC, "Regen EVO") field(FLNK, "LASR:LR10:1:REGENVO") field(CALC, "A*1.8+32") field(INPA, "BKHF:LR10:TM01:M6_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "64") field(HIGH, "77") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "LASR:LR10:1:REGENVO_DATA") field(ASG, "") } record(ai, "BKHF:LR10:TM01:M6_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-lr10-tm01:6:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:LR10:TM01:M6_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "LASR:LR10:1:MPA1EVO") { field(DESC,"MPA EVO") field(SCAN, "1 second") field(INP, "LASR:LR10:1:MPA1EVO_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "64") field(HIGH, "77") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "LASR:LR10:1:MPA1EVO_AVG") { field(DESC, "Avg sig samples") field(INP, "LASR:LR10:1:MPA1EVO_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "LASR:LR10:1:MPA1EVO_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:LR10:TM01:M7_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:LR10:TM01:M7_CH1_TEMP") { field(DESC, "MPA EVO") field(FLNK, "LASR:LR10:1:MPA1EVO") field(CALC, "A*1.8+32") field(INPA, "BKHF:LR10:TM01:M7_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "64") field(HIGH, "77") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "LASR:LR10:1:MPA1EVO_DATA") field(ASG, "") } record(ai, "BKHF:LR10:TM01:M7_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-lr10-tm01:7:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:LR10:TM01:M7_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "LASR:LR10:1:MPA2EVO") { field(DESC,"MPA EVO") field(SCAN, "1 second") field(INP, "LASR:LR10:1:MPA2EVO_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "64") field(HIGH, "77") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "LASR:LR10:1:MPA2EVO_AVG") { field(DESC, "Avg sig samples") field(INP, "LASR:LR10:1:MPA2EVO_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "LASR:LR10:1:MPA2EVO_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:LR10:TM01:M7_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:LR10:TM01:M7_CH2_TEMP") { field(DESC, "MPA EVO") field(FLNK, "LASR:LR10:1:MPA2EVO") field(CALC, "A*1.8+32") field(INPA, "BKHF:LR10:TM01:M7_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "64") field(HIGH, "77") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "LASR:LR10:1:MPA2EVO_DATA") field(ASG, "") } record(ai, "BKHF:LR10:TM01:M7_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-lr10-tm01:7:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:LR10:TM01:M7_CH2_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "LASR:LR10:1:UVBEAM") { field(DESC,"UVBeam") field(SCAN, "1 second") field(INP, "LASR:LR10:1:UVBEAM_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "64") field(HIGH, "77") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "LASR:LR10:1:UVBEAM_AVG") { field(DESC, "Avg sig samples") field(INP, "LASR:LR10:1:UVBEAM_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "LASR:LR10:1:UVBEAM_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:LR10:TM01:M9_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:LR10:TM01:M9_CH1_TEMP") { field(DESC, "UVBeam") field(FLNK, "LASR:LR10:1:UVBEAM") field(CALC, "A*1.8+32") field(INPA, "BKHF:LR10:TM01:M9_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "64") field(HIGH, "77") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "LASR:LR10:1:UVBEAM_DATA") field(ASG, "") } record(ai, "BKHF:LR10:TM01:M9_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-lr10-tm01:9:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:LR10:TM01:M9_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "LASR:LR10:1:CLIPPING_IRIS") { field(DESC,"Clipping Iris") field(SCAN, "1 second") field(INP, "LASR:LR10:1:CLIPPING_IRIS_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "64") field(HIGH, "77") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "LASR:LR10:1:CLIPPING_IRIS_AVG") { field(DESC, "Avg sig samples") field(INP, "LASR:LR10:1:CLIPPING_IRIS_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "LASR:LR10:1:CLIPPING_IRIS_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:LR10:TM01:M9_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:LR10:TM01:M9_CH2_TEMP") { field(DESC, "Clipping Iris") field(FLNK, "LASR:LR10:1:CLIPPING_IRIS") field(CALC, "A*1.8+32") field(INPA, "BKHF:LR10:TM01:M9_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "64") field(HIGH, "77") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "LASR:LR10:1:CLIPPING_IRIS_DATA") field(ASG, "") } record(ai, "BKHF:LR10:TM01:M9_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-lr10-tm01:9:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:LR10:TM01:M9_CH2_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "LASR:LR10:1:UVTELESCOPE_LENS") { field(DESC,"UV Telescope Lens") field(SCAN, "1 second") field(INP, "LASR:LR10:1:UVTELESCOPE_LENS_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "64") field(HIGH, "77") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "LASR:LR10:1:UVTELESCOPE_LENS_AVG") { field(DESC, "Avg sig samples") field(INP, "LASR:LR10:1:UVTELESCOPE_LENS_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "LASR:LR10:1:UVTELESCOPE_LENS_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:LR10:TM01:M10_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:LR10:TM01:M10_CH1_TEMP") { field(DESC, "UV Telescope Lens") field(FLNK, "LASR:LR10:1:UVTELESCOPE_LENS") field(CALC, "A*1.8+32") field(INPA, "BKHF:LR10:TM01:M10_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "64") field(HIGH, "77") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "LASR:LR10:1:UVTELESCOPE_LENS_DATA") field(ASG, "") } record(ai, "BKHF:LR10:TM01:M10_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-lr10-tm01:10:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:LR10:TM01:M10_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "LASR:LR10:1:LCS_SUPPLY") { field(DESC,"Water Supply") field(SCAN, "1 second") field(INP, "LASR:LR10:1:LCS_SUPPLY_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "67") field(LOLO, "52") field(HIGH, "64") field(LOW, "55") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "LASR:LR10:1:LCS_SUPPLY_AVG") { field(DESC, "Avg sig samples") field(INP, "LASR:LR10:1:LCS_SUPPLY_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "LASR:LR10:1:LCS_SUPPLY_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:LR10:TM01:M11_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:LR10:TM01:M11_CH1_TEMP") { field(DESC, "Water Supply") field(FLNK, "LASR:LR10:1:LCS_SUPPLY") field(CALC, "A*1.8+32") field(INPA, "BKHF:LR10:TM01:M11_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "67") field(LOLO, "52") field(HIGH, "64") field(LOW, "55") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "LASR:LR10:1:LCS_SUPPLY_DATA") field(ASG, "") } record(ai, "BKHF:LR10:TM01:M11_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-lr10-tm01:11:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:LR10:TM01:M11_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "LASR:LR10:1:LCS_RETURN") { field(DESC,"Water Return") field(SCAN, "1 second") field(INP, "LASR:LR10:1:LCS_RETURN_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "69") field(LOLO, "54") field(HIGH, "66") field(LOW, "57") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "LASR:LR10:1:LCS_RETURN_AVG") { field(DESC, "Avg sig samples") field(INP, "LASR:LR10:1:LCS_RETURN_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "LASR:LR10:1:LCS_RETURN_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:LR10:TM01:M11_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:LR10:TM01:M11_CH2_TEMP") { field(DESC, "Water Return") field(FLNK, "LASR:LR10:1:LCS_RETURN") field(CALC, "A*1.8+32") field(INPA, "BKHF:LR10:TM01:M11_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "69") field(LOLO, "54") field(HIGH, "66") field(LOW, "57") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "LASR:LR10:1:LCS_RETURN_DATA") field(ASG, "") } record(ai, "BKHF:LR10:TM01:M11_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-lr10-tm01:11:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:LR10:TM01:M11_CH2_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "ROOM:LR10:1:AIRTEMP1") { field(DESC,"Air Temperature") field(SCAN, "1 second") field(INP, "ROOM:LR10:1:AIRTEMP1_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "60") field(HIGH, "78") field(LOW, "66") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "ROOM:LR10:1:AIRTEMP1_AVG") { field(DESC, "Avg sig samples") field(INP, "ROOM:LR10:1:AIRTEMP1_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "ROOM:LR10:1:AIRTEMP1_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:LR10:TM01:M13_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:LR10:TM01:M13_CH1_TEMP") { field(DESC, "Air Temperature") field(FLNK, "ROOM:LR10:1:AIRTEMP1") field(CALC, "A*1.8+32") field(INPA, "BKHF:LR10:TM01:M13_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "60") field(HIGH, "78") field(LOW, "66") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "ROOM:LR10:1:AIRTEMP1_DATA") field(ASG, "") } record(ai, "BKHF:LR10:TM01:M13_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-lr10-tm01:13:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:LR10:TM01:M13_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "ROOM:LR10:1:AIRTEMP2") { field(DESC,"Air Temperature") field(SCAN, "1 second") field(INP, "ROOM:LR10:1:AIRTEMP2_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "60") field(HIGH, "78") field(LOW, "66") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "ROOM:LR10:1:AIRTEMP2_AVG") { field(DESC, "Avg sig samples") field(INP, "ROOM:LR10:1:AIRTEMP2_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "ROOM:LR10:1:AIRTEMP2_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:LR10:TM01:M13_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:LR10:TM01:M13_CH2_TEMP") { field(DESC, "Air Temperature") field(FLNK, "ROOM:LR10:1:AIRTEMP2") field(CALC, "A*1.8+32") field(INPA, "BKHF:LR10:TM01:M13_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "60") field(HIGH, "78") field(LOW, "66") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "ROOM:LR10:1:AIRTEMP2_DATA") field(ASG, "") } record(ai, "BKHF:LR10:TM01:M13_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-lr10-tm01:13:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:LR10:TM01:M13_CH2_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "ROOM:LR10:1:AIRTEMP3") { field(DESC,"Air Temperature") field(SCAN, "1 second") field(INP, "ROOM:LR10:1:AIRTEMP3_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "60") field(HIGH, "78") field(LOW, "66") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "ROOM:LR10:1:AIRTEMP3_AVG") { field(DESC, "Avg sig samples") field(INP, "ROOM:LR10:1:AIRTEMP3_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "ROOM:LR10:1:AIRTEMP3_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:LR10:TM01:M14_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:LR10:TM01:M14_CH1_TEMP") { field(DESC, "Air Temperature") field(FLNK, "ROOM:LR10:1:AIRTEMP3") field(CALC, "A*1.8+32") field(INPA, "BKHF:LR10:TM01:M14_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "60") field(HIGH, "78") field(LOW, "66") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "ROOM:LR10:1:AIRTEMP3_DATA") field(ASG, "") } record(ai, "BKHF:LR10:TM01:M14_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-lr10-tm01:14:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:LR10:TM01:M14_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "LASR:LR10:1:TABLETEMP1") { field(DESC,"Table Temperature") field(SCAN, "1 second") field(INP, "LASR:LR10:1:TABLETEMP1_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "60") field(HIGH, "76") field(LOW, "66") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "LASR:LR10:1:TABLETEMP1_AVG") { field(DESC, "Avg sig samples") field(INP, "LASR:LR10:1:TABLETEMP1_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "LASR:LR10:1:TABLETEMP1_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:LR10:TM01:M14_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:LR10:TM01:M14_CH2_TEMP") { field(DESC, "Table Temperature") field(FLNK, "LASR:LR10:1:TABLETEMP1") field(CALC, "A*1.8+32") field(INPA, "BKHF:LR10:TM01:M14_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "60") field(HIGH, "76") field(LOW, "66") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "LASR:LR10:1:TABLETEMP1_DATA") field(ASG, "") } record(ai, "BKHF:LR10:TM01:M14_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-lr10-tm01:14:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:LR10:TM01:M14_CH2_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "LASR:LR10:1:TABLETEMP2") { field(DESC,"Table Temperature") field(SCAN, "1 second") field(INP, "LASR:LR10:1:TABLETEMP2_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "60") field(HIGH, "76") field(LOW, "66") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "LASR:LR10:1:TABLETEMP2_AVG") { field(DESC, "Avg sig samples") field(INP, "LASR:LR10:1:TABLETEMP2_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "LASR:LR10:1:TABLETEMP2_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:LR10:TM01:M15_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:LR10:TM01:M15_CH1_TEMP") { field(DESC, "Table Temperature") field(FLNK, "LASR:LR10:1:TABLETEMP2") field(CALC, "A*1.8+32") field(INPA, "BKHF:LR10:TM01:M15_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "60") field(HIGH, "76") field(LOW, "66") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "LASR:LR10:1:TABLETEMP2_DATA") field(ASG, "") } record(ai, "BKHF:LR10:TM01:M15_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-lr10-tm01:15:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:LR10:TM01:M15_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "LASR:LR10:1:TABLETEMP3") { field(DESC,"Table Temperature") field(SCAN, "1 second") field(INP, "LASR:LR10:1:TABLETEMP3_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "60") field(HIGH, "76") field(LOW, "66") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "LASR:LR10:1:TABLETEMP3_AVG") { field(DESC, "Avg sig samples") field(INP, "LASR:LR10:1:TABLETEMP3_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "LASR:LR10:1:TABLETEMP3_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:LR10:TM01:M15_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:LR10:TM01:M15_CH2_TEMP") { field(DESC, "Table Temperature") field(FLNK, "LASR:LR10:1:TABLETEMP3") field(CALC, "A*1.8+32") field(INPA, "BKHF:LR10:TM01:M15_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "60") field(HIGH, "76") field(LOW, "66") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "LASR:LR10:1:TABLETEMP3_DATA") field(ASG, "") } record(ai, "BKHF:LR10:TM01:M15_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-lr10-tm01:15:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:LR10:TM01:M15_CH2_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "LASR:LR10:1:TABLETEMP4") { field(DESC,"Table Temperature") field(SCAN, "1 second") field(INP, "LASR:LR10:1:TABLETEMP4_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "60") field(HIGH, "76") field(LOW, "66") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "LASR:LR10:1:TABLETEMP4_AVG") { field(DESC, "Avg sig samples") field(INP, "LASR:LR10:1:TABLETEMP4_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "LASR:LR10:1:TABLETEMP4_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:LR10:TM01:M16_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:LR10:TM01:M16_CH1_TEMP") { field(DESC, "Table Temperature") field(FLNK, "LASR:LR10:1:TABLETEMP4") field(CALC, "A*1.8+32") field(INPA, "BKHF:LR10:TM01:M16_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "60") field(HIGH, "76") field(LOW, "66") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "LASR:LR10:1:TABLETEMP4_DATA") field(ASG, "") } record(ai, "BKHF:LR10:TM01:M16_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-lr10-tm01:16:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:LR10:TM01:M16_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "LASR:LR10:1:TABLETEMP5") { field(DESC,"Table Temperature") field(SCAN, "1 second") field(INP, "LASR:LR10:1:TABLETEMP5_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "60") field(HIGH, "76") field(LOW, "66") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "LASR:LR10:1:TABLETEMP5_AVG") { field(DESC, "Avg sig samples") field(INP, "LASR:LR10:1:TABLETEMP5_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "LASR:LR10:1:TABLETEMP5_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:LR10:TM01:M16_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:LR10:TM01:M16_CH2_TEMP") { field(DESC, "Table Temperature") field(FLNK, "LASR:LR10:1:TABLETEMP5") field(CALC, "A*1.8+32") field(INPA, "BKHF:LR10:TM01:M16_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80") field(LOLO, "60") field(HIGH, "76") field(LOW, "66") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "LASR:LR10:1:TABLETEMP5_DATA") field(ASG, "") } record(ai, "BKHF:LR10:TM01:M16_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-lr10-tm01:16:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:LR10:TM01:M16_CH2_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "LASR:LR10:1:OSC_BASEPLATE1") { field(DESC,"Osciliator Baseplate") field(SCAN, "1 second") field(INP, "LASR:LR10:1:OSC_BASEPLATE1_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "75") field(LOLO, "64") field(HIGH, "72") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "LASR:LR10:1:OSC_BASEPLATE1_AVG") { field(DESC, "Avg sig samples") field(INP, "LASR:LR10:1:OSC_BASEPLATE1_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "LASR:LR10:1:OSC_BASEPLATE1_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:LR10:TM01:M17_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:LR10:TM01:M17_CH1_TEMP") { field(DESC, "Osciliator Baseplate") field(FLNK, "LASR:LR10:1:OSC_BASEPLATE1") field(CALC, "A*1.8+32") field(INPA, "BKHF:LR10:TM01:M17_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "75") field(LOLO, "64") field(HIGH, "72") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "LASR:LR10:1:OSC_BASEPLATE1_DATA") field(ASG, "") } record(ai, "BKHF:LR10:TM01:M17_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-lr10-tm01:17:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:LR10:TM01:M17_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "LASR:LR10:1:OSC_BASEPLATE2") { field(DESC,"Osciliator Baseplate") field(SCAN, "1 second") field(INP, "LASR:LR10:1:OSC_BASEPLATE2_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "75") field(LOLO, "64") field(HIGH, "72") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "LASR:LR10:1:OSC_BASEPLATE2_AVG") { field(DESC, "Avg sig samples") field(INP, "LASR:LR10:1:OSC_BASEPLATE2_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "LASR:LR10:1:OSC_BASEPLATE2_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:LR10:TM01:M17_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:LR10:TM01:M17_CH2_TEMP") { field(DESC, "Osciliator Baseplate") field(FLNK, "LASR:LR10:1:OSC_BASEPLATE2") field(CALC, "A*1.8+32") field(INPA, "BKHF:LR10:TM01:M17_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "75") field(LOLO, "64") field(HIGH, "72") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "LASR:LR10:1:OSC_BASEPLATE2_DATA") field(ASG, "") } record(ai, "BKHF:LR10:TM01:M17_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-lr10-tm01:17:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:LR10:TM01:M17_CH2_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "LASR:LR10:1:REGEN_MOUNT1") { field(DESC,"Regen TiSa Mount") field(SCAN, "1 second") field(INP, "LASR:LR10:1:REGEN_MOUNT1_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "75") field(LOLO, "64") field(HIGH, "72") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "LASR:LR10:1:REGEN_MOUNT1_AVG") { field(DESC, "Avg sig samples") field(INP, "LASR:LR10:1:REGEN_MOUNT1_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "LASR:LR10:1:REGEN_MOUNT1_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:LR10:TM01:M18_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:LR10:TM01:M18_CH1_TEMP") { field(DESC, "Regen TiSa Mount") field(FLNK, "LASR:LR10:1:REGEN_MOUNT1") field(CALC, "A*1.8+32") field(INPA, "BKHF:LR10:TM01:M18_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "75") field(LOLO, "64") field(HIGH, "72") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "LASR:LR10:1:REGEN_MOUNT1_DATA") field(ASG, "") } record(ai, "BKHF:LR10:TM01:M18_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-lr10-tm01:18:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:LR10:TM01:M18_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "LASR:LR10:1:REGEN_MOUNT2") { field(DESC,"Regen TiSa Mount") field(SCAN, "1 second") field(INP, "LASR:LR10:1:REGEN_MOUNT2_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "75") field(LOLO, "64") field(HIGH, "72") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "LASR:LR10:1:REGEN_MOUNT2_AVG") { field(DESC, "Avg sig samples") field(INP, "LASR:LR10:1:REGEN_MOUNT2_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "LASR:LR10:1:REGEN_MOUNT2_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:LR10:TM01:M18_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:LR10:TM01:M18_CH2_TEMP") { field(DESC, "Regen TiSa Mount") field(FLNK, "LASR:LR10:1:REGEN_MOUNT2") field(CALC, "A*1.8+32") field(INPA, "BKHF:LR10:TM01:M18_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "75") field(LOLO, "64") field(HIGH, "72") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "LASR:LR10:1:REGEN_MOUNT2_DATA") field(ASG, "") } record(ai, "BKHF:LR10:TM01:M18_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-lr10-tm01:18:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:LR10:TM01:M18_CH2_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "LASR:LR10:1:MPA_MOUNT1") { field(DESC,"MPA TiSa Mount") field(SCAN, "1 second") field(INP, "LASR:LR10:1:MPA_MOUNT1_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "75") field(LOLO, "64") field(HIGH, "72") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "LASR:LR10:1:MPA_MOUNT1_AVG") { field(DESC, "Avg sig samples") field(INP, "LASR:LR10:1:MPA_MOUNT1_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "LASR:LR10:1:MPA_MOUNT1_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:LR10:TM01:M19_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:LR10:TM01:M19_CH1_TEMP") { field(DESC, "MPA TiSa Mount") field(FLNK, "LASR:LR10:1:MPA_MOUNT1") field(CALC, "A*1.8+32") field(INPA, "BKHF:LR10:TM01:M19_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "75") field(LOLO, "64") field(HIGH, "72") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "LASR:LR10:1:MPA_MOUNT1_DATA") field(ASG, "") } record(ai, "BKHF:LR10:TM01:M19_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-lr10-tm01:19:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:LR10:TM01:M19_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "LASR:LR10:1:MPA_MOUNT2") { field(DESC,"MPA TiSa Mount") field(SCAN, "1 second") field(INP, "LASR:LR10:1:MPA_MOUNT2_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "75") field(LOLO, "64") field(HIGH, "72") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "LASR:LR10:1:MPA_MOUNT2_AVG") { field(DESC, "Avg sig samples") field(INP, "LASR:LR10:1:MPA_MOUNT2_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "LASR:LR10:1:MPA_MOUNT2_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:LR10:TM01:M19_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:LR10:TM01:M19_CH2_TEMP") { field(DESC, "MPA TiSa Mount") field(FLNK, "LASR:LR10:1:MPA_MOUNT2") field(CALC, "A*1.8+32") field(INPA, "BKHF:LR10:TM01:M19_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "75") field(LOLO, "64") field(HIGH, "72") field(LOW, "67") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "LASR:LR10:1:MPA_MOUNT2_DATA") field(ASG, "") } record(ai, "BKHF:LR10:TM01:M19_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-lr10-tm01:19:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:LR10:TM01:M19_CH2_TEMP") field(ASG, "") }