#============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "CATH:IN10:111:TEMP1") { field(DESC,"Photo Cathode") field(SCAN, "1 second") field(INP, "CATH:IN10:111:TEMP1_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "89") field(LOLO, "77.1") field(HIGH, "85.8") field(LOW, "80.3") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "CATH:IN10:111:TEMP1_AVG") { field(DESC, "Avg sig samples") field(INP, "CATH:IN10:111:TEMP1_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "CATH:IN10:111:TEMP1_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M1_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M1_CH1_TEMP") { field(DESC, "Photo Cathode") field(FLNK, "CATH:IN10:111:TEMP1") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M1_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "89") field(LOLO, "77.1") field(HIGH, "85.8") field(LOW, "80.3") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "CATH:IN10:111:TEMP1_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M1_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:1:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M1_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "CATH:IN10:111:TEMP2") { field(DESC,"Photo Cathode") field(SCAN, "1 second") field(INP, "CATH:IN10:111:TEMP2_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "88.8") field(LOLO, "76.9") field(HIGH, "85.6") field(LOW, "80.1") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "CATH:IN10:111:TEMP2_AVG") { field(DESC, "Avg sig samples") field(INP, "CATH:IN10:111:TEMP2_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "CATH:IN10:111:TEMP2_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M1_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M1_CH2_TEMP") { field(DESC, "Photo Cathode") field(FLNK, "CATH:IN10:111:TEMP2") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M1_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "88.8") field(LOLO, "76.9") field(HIGH, "85.6") field(LOW, "80.1") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "CATH:IN10:111:TEMP2_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M1_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:1:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M1_CH2_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "SOLN:IN10:111:SUPPORT_TEMP1") { field(DESC,"Solenoid Support") field(SCAN, "1 second") field(INP, "SOLN:IN10:111:SUPPORT_TEMP1_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "90.2") field(LOLO, "79.9") field(HIGH, "87.4") field(LOW, "82.7") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "SOLN:IN10:111:SUPPORT_TEMP1_AVG") { field(DESC, "Avg sig samples") field(INP, "SOLN:IN10:111:SUPPORT_TEMP1_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "SOLN:IN10:111:SUPPORT_TEMP1_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M2_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M2_CH1_TEMP") { field(DESC, "Solenoid Support") field(FLNK, "SOLN:IN10:111:SUPPORT_TEMP1") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M2_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "90.2") field(LOLO, "79.9") field(HIGH, "87.4") field(LOW, "82.7") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "SOLN:IN10:111:SUPPORT_TEMP1_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M2_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:2:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M2_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "SOLN:IN10:111:SUPPORT_TEMP2") { field(DESC,"Solenoid Support") field(SCAN, "1 second") field(INP, "SOLN:IN10:111:SUPPORT_TEMP2_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "89.3") field(LOLO, "80.3") field(HIGH, "86.9") field(LOW, "82.7") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "SOLN:IN10:111:SUPPORT_TEMP2_AVG") { field(DESC, "Avg sig samples") field(INP, "SOLN:IN10:111:SUPPORT_TEMP2_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "SOLN:IN10:111:SUPPORT_TEMP2_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M2_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M2_CH2_TEMP") { field(DESC, "Solenoid Support") field(FLNK, "SOLN:IN10:111:SUPPORT_TEMP2") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M2_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "89.3") field(LOLO, "80.3") field(HIGH, "86.9") field(LOW, "82.7") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "SOLN:IN10:111:SUPPORT_TEMP2_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M2_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:2:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M2_CH2_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "SOLN:IN10:111:SUPPORT_TEMP3") { field(DESC,"Solenoid Support") field(SCAN, "1 second") field(INP, "SOLN:IN10:111:SUPPORT_TEMP3_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "89.8") field(LOLO, "80.8") field(HIGH, "87.4") field(LOW, "83.2") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "SOLN:IN10:111:SUPPORT_TEMP3_AVG") { field(DESC, "Avg sig samples") field(INP, "SOLN:IN10:111:SUPPORT_TEMP3_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "SOLN:IN10:111:SUPPORT_TEMP3_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M3_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M3_CH1_TEMP") { field(DESC, "Solenoid Support") field(FLNK, "SOLN:IN10:111:SUPPORT_TEMP3") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M3_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "89.8") field(LOLO, "80.8") field(HIGH, "87.4") field(LOW, "83.2") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "SOLN:IN10:111:SUPPORT_TEMP3_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M3_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:3:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M3_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "SOLN:IN10:111:SUPPORT_TEMP4") { field(DESC,"Solenoid Support") field(SCAN, "1 second") field(INP, "SOLN:IN10:111:SUPPORT_TEMP4_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "89.5") field(LOLO, "80.5") field(HIGH, "87.1") field(LOW, "82.9") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "SOLN:IN10:111:SUPPORT_TEMP4_AVG") { field(DESC, "Avg sig samples") field(INP, "SOLN:IN10:111:SUPPORT_TEMP4_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "SOLN:IN10:111:SUPPORT_TEMP4_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M3_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M3_CH2_TEMP") { field(DESC, "Solenoid Support") field(FLNK, "SOLN:IN10:111:SUPPORT_TEMP4") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M3_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "89.5") field(LOLO, "80.5") field(HIGH, "87.1") field(LOW, "82.9") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "SOLN:IN10:111:SUPPORT_TEMP4_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M3_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:3:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M3_CH2_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "SOLN:IN10:111:INLETTEMP") { field(DESC,"Solenoid Water Temps") field(SCAN, "1 second") field(INP, "SOLN:IN10:111:INLETTEMP_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "83.8") field(LOLO, "75") field(HIGH, "81.4") field(LOW, "77.4") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "SOLN:IN10:111:INLETTEMP_AVG") { field(DESC, "Avg sig samples") field(INP, "SOLN:IN10:111:INLETTEMP_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "SOLN:IN10:111:INLETTEMP_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M4_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M4_CH1_TEMP") { field(DESC, "Solenoid Water Temps") field(FLNK, "SOLN:IN10:111:INLETTEMP") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M4_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "83.8") field(LOLO, "75") field(HIGH, "81.4") field(LOW, "77.4") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "SOLN:IN10:111:INLETTEMP_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M4_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:4:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M4_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "SOLN:IN10:111:OUTLETTEMP") { field(DESC,"Solenoid Water Temps") field(SCAN, "1 second") field(INP, "SOLN:IN10:111:OUTLETTEMP_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "86.3") field(LOLO, "77.4") field(HIGH, "83.9") field(LOW, "79.8") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "SOLN:IN10:111:OUTLETTEMP_AVG") { field(DESC, "Avg sig samples") field(INP, "SOLN:IN10:111:OUTLETTEMP_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "SOLN:IN10:111:OUTLETTEMP_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M4_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M4_CH2_TEMP") { field(DESC, "Solenoid Water Temps") field(FLNK, "SOLN:IN10:111:OUTLETTEMP") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M4_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "86.3") field(LOLO, "77.4") field(HIGH, "83.9") field(LOW, "79.8") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "SOLN:IN10:111:OUTLETTEMP_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M4_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:4:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M4_CH2_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "SOLN:IN10:111:STRONG_BACK1") { field(DESC,"Strong Back Temps") field(SCAN, "1 second") field(INP, "SOLN:IN10:111:STRONG_BACK1_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "86") field(LOLO, "78.7") field(HIGH, "84") field(LOW, "80.7") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "SOLN:IN10:111:STRONG_BACK1_AVG") { field(DESC, "Avg sig samples") field(INP, "SOLN:IN10:111:STRONG_BACK1_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "SOLN:IN10:111:STRONG_BACK1_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M5_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M5_CH1_TEMP") { field(DESC, "Strong Back Temps") field(FLNK, "SOLN:IN10:111:STRONG_BACK1") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M5_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "86") field(LOLO, "78.7") field(HIGH, "84") field(LOW, "80.7") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "SOLN:IN10:111:STRONG_BACK1_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M5_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:5:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M5_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "SOLN:IN10:111:STRONG_BACK2") { field(DESC,"Strong Back Temps") field(SCAN, "1 second") field(INP, "SOLN:IN10:111:STRONG_BACK2_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "87.6") field(LOLO, "78.8") field(HIGH, "85.2") field(LOW, "81.2") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "SOLN:IN10:111:STRONG_BACK2_AVG") { field(DESC, "Avg sig samples") field(INP, "SOLN:IN10:111:STRONG_BACK2_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "SOLN:IN10:111:STRONG_BACK2_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M5_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M5_CH2_TEMP") { field(DESC, "Strong Back Temps") field(FLNK, "SOLN:IN10:111:STRONG_BACK2") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M5_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "87.6") field(LOLO, "78.8") field(HIGH, "85.2") field(LOW, "81.2") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "SOLN:IN10:111:STRONG_BACK2_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M5_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:5:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M5_CH2_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "SOLN:IN10:111:STRONG_BACK3") { field(DESC,"Strong Back Temps") field(SCAN, "1 second") field(INP, "SOLN:IN10:111:STRONG_BACK3_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "85.6") field(LOLO, "79.6") field(HIGH, "84") field(LOW, "81.2") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "SOLN:IN10:111:STRONG_BACK3_AVG") { field(DESC, "Avg sig samples") field(INP, "SOLN:IN10:111:STRONG_BACK3_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "SOLN:IN10:111:STRONG_BACK3_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M6_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M6_CH1_TEMP") { field(DESC, "Strong Back Temps") field(FLNK, "SOLN:IN10:111:STRONG_BACK3") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M6_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "85.6") field(LOLO, "79.6") field(HIGH, "84") field(LOW, "81.2") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "SOLN:IN10:111:STRONG_BACK3_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M6_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:6:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M6_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "SOLN:IN10:111:STRONG_BACK4") { field(DESC,"Strong Back Temps") field(SCAN, "1 second") field(INP, "SOLN:IN10:111:STRONG_BACK4_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "85.6") field(LOLO, "78.3") field(HIGH, "83.6") field(LOW, "80.3") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "SOLN:IN10:111:STRONG_BACK4_AVG") { field(DESC, "Avg sig samples") field(INP, "SOLN:IN10:111:STRONG_BACK4_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "SOLN:IN10:111:STRONG_BACK4_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M6_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M6_CH2_TEMP") { field(DESC, "Strong Back Temps") field(FLNK, "SOLN:IN10:111:STRONG_BACK4") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M6_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "85.6") field(LOLO, "78.3") field(HIGH, "83.6") field(LOW, "80.3") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "SOLN:IN10:111:STRONG_BACK4_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M6_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:6:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M6_CH2_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "QUAD:IN10:121:TEMP") { field(DESC,"Quadropole Magnet") field(SCAN, "1 second") field(INP, "QUAD:IN10:121:TEMP_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "84.9") field(LOLO, "80") field(HIGH, "84.4") field(LOW, "80.4") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "QUAD:IN10:121:TEMP_AVG") { field(DESC, "Avg sig samples") field(INP, "QUAD:IN10:121:TEMP_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "QUAD:IN10:121:TEMP_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M7_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M7_CH1_TEMP") { field(DESC, "Quadropole Magnet") field(FLNK, "QUAD:IN10:121:TEMP") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M7_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "84.9") field(LOLO, "80") field(HIGH, "84.4") field(LOW, "80.4") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "QUAD:IN10:121:TEMP_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M7_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:7:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M7_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "QUAD:IN10:122:TEMP") { field(DESC,"Quadropole Magnet") field(SCAN, "1 second") field(INP, "QUAD:IN10:122:TEMP_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "84.9") field(LOLO, "80") field(HIGH, "84.4") field(LOW, "80.4") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "QUAD:IN10:122:TEMP_AVG") { field(DESC, "Avg sig samples") field(INP, "QUAD:IN10:122:TEMP_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "QUAD:IN10:122:TEMP_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M7_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M7_CH2_TEMP") { field(DESC, "Quadropole Magnet") field(FLNK, "QUAD:IN10:122:TEMP") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M7_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "84.9") field(LOLO, "80") field(HIGH, "84.4") field(LOW, "80.4") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "QUAD:IN10:122:TEMP_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M7_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:7:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M7_CH2_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "MIRR:IN10:181:LASER_VAC_TEMP1") { field(DESC,"Laser Vacuum Mirror") field(SCAN, "1 second") field(INP, "MIRR:IN10:181:LASER_VAC_TEMP1_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "86.9") field(LOLO, "84") field(HIGH, "86.4") field(LOW, "84.4") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "MIRR:IN10:181:LASER_VAC_TEMP1_AVG") { field(DESC, "Avg sig samples") field(INP, "MIRR:IN10:181:LASER_VAC_TEMP1_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "MIRR:IN10:181:LASER_VAC_TEMP1_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M8_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M8_CH1_TEMP") { field(DESC, "Laser Vacuum Mirror") field(FLNK, "MIRR:IN10:181:LASER_VAC_TEMP1") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M8_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "86.9") field(LOLO, "84") field(HIGH, "86.4") field(LOW, "84.4") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "MIRR:IN10:181:LASER_VAC_TEMP1_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M8_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:8:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M8_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "MIRR:IN10:181:LASER_VAC_TEMP2") { field(DESC,"Laser Vacuum Mirror") field(SCAN, "1 second") field(INP, "MIRR:IN10:181:LASER_VAC_TEMP2_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "86.9") field(LOLO, "84") field(HIGH, "86.4") field(LOW, "84.4") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "MIRR:IN10:181:LASER_VAC_TEMP2_AVG") { field(DESC, "Avg sig samples") field(INP, "MIRR:IN10:181:LASER_VAC_TEMP2_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "MIRR:IN10:181:LASER_VAC_TEMP2_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M8_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M8_CH2_TEMP") { field(DESC, "Laser Vacuum Mirror") field(FLNK, "MIRR:IN10:181:LASER_VAC_TEMP2") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M8_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "86.9") field(LOLO, "84") field(HIGH, "86.4") field(LOW, "84.4") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "MIRR:IN10:181:LASER_VAC_TEMP2_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M8_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:8:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M8_CH2_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "GUN:IN10:111:UPPERWINDTEMP") { field(DESC,"Gun Waveguide Window Temps") field(SCAN, "1 second") field(INP, "GUN:IN10:111:UPPERWINDTEMP_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "95.6") field(LOLO, "92.5") field(HIGH, "94.8") field(LOW, "93.3") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "GUN:IN10:111:UPPERWINDTEMP_AVG") { field(DESC, "Avg sig samples") field(INP, "GUN:IN10:111:UPPERWINDTEMP_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "GUN:IN10:111:UPPERWINDTEMP_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M9_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M9_CH1_TEMP") { field(DESC, "Gun Waveguide Window Temps") field(FLNK, "GUN:IN10:111:UPPERWINDTEMP") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M9_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "95.6") field(LOLO, "92.5") field(HIGH, "94.8") field(LOW, "93.3") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "GUN:IN10:111:UPPERWINDTEMP_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M9_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:9:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M9_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "GUN:IN10:111:LOWERWINDTEMP") { field(DESC,"Gun Waveguide Window Temps") field(SCAN, "1 second") field(INP, "GUN:IN10:111:LOWERWINDTEMP_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "95.8") field(LOLO, "92.8") field(HIGH, "95") field(LOW, "93.6") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "GUN:IN10:111:LOWERWINDTEMP_AVG") { field(DESC, "Avg sig samples") field(INP, "GUN:IN10:111:LOWERWINDTEMP_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "GUN:IN10:111:LOWERWINDTEMP_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M9_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M9_CH2_TEMP") { field(DESC, "Gun Waveguide Window Temps") field(FLNK, "GUN:IN10:111:LOWERWINDTEMP") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M9_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "95.8") field(LOLO, "92.8") field(HIGH, "95") field(LOW, "93.6") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "GUN:IN10:111:LOWERWINDTEMP_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M9_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:9:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M9_CH2_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "GUN:IN10:111:WGBDYTEMP1") { field(DESC,"Gun Waveguide Body Temps") field(SCAN, "1 second") field(INP, "GUN:IN10:111:WGBDYTEMP1_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "94.9") field(LOLO, "91.8") field(HIGH, "94.1") field(LOW, "92.6") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "GUN:IN10:111:WGBDYTEMP1_AVG") { field(DESC, "Avg sig samples") field(INP, "GUN:IN10:111:WGBDYTEMP1_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "GUN:IN10:111:WGBDYTEMP1_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M10_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M10_CH1_TEMP") { field(DESC, "Gun Waveguide Body Temps") field(FLNK, "GUN:IN10:111:WGBDYTEMP1") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M10_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "94.9") field(LOLO, "91.8") field(HIGH, "94.1") field(LOW, "92.6") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "GUN:IN10:111:WGBDYTEMP1_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M10_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:10:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M10_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "GUN:IN10:111:WGBDYTEMP2") { field(DESC,"Gun Waveguide Body Temps") field(SCAN, "1 second") field(INP, "GUN:IN10:111:WGBDYTEMP2_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "94.9") field(LOLO, "91.8") field(HIGH, "94.1") field(LOW, "92.6") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "GUN:IN10:111:WGBDYTEMP2_AVG") { field(DESC, "Avg sig samples") field(INP, "GUN:IN10:111:WGBDYTEMP2_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "GUN:IN10:111:WGBDYTEMP2_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M10_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M10_CH2_TEMP") { field(DESC, "Gun Waveguide Body Temps") field(FLNK, "GUN:IN10:111:WGBDYTEMP2") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M10_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "94.9") field(LOLO, "91.8") field(HIGH, "94.1") field(LOW, "92.6") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "GUN:IN10:111:WGBDYTEMP2_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M10_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:10:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M10_CH2_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "GUN:IN10:111:FLOOR_SUPPORT_TEMP1") { field(DESC,"Gun Floor Supports Temps") field(SCAN, "1 second") field(INP, "GUN:IN10:111:FLOOR_SUPPORT_TEMP1_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "89.9") field(LOLO, "79.5") field(HIGH, "87.1") field(LOW, "82.3") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "GUN:IN10:111:FLOOR_SUPPORT_TEMP1_AVG") { field(DESC, "Avg sig samples") field(INP, "GUN:IN10:111:FLOOR_SUPPORT_TEMP1_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "GUN:IN10:111:FLOOR_SUPPORT_TEMP1_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M11_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M11_CH1_TEMP") { field(DESC, "Gun Floor Supports Temps") field(FLNK, "GUN:IN10:111:FLOOR_SUPPORT_TEMP1") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M11_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "89.9") field(LOLO, "79.5") field(HIGH, "87.1") field(LOW, "82.3") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "GUN:IN10:111:FLOOR_SUPPORT_TEMP1_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M11_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:11:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M11_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "GUN:IN10:111:FLOOR_SUPPORT_TEMP2") { field(DESC,"Gun Floor Supports Temps") field(SCAN, "1 second") field(INP, "GUN:IN10:111:FLOOR_SUPPORT_TEMP2_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "89.8") field(LOLO, "79.5") field(HIGH, "87") field(LOW, "82.3") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "GUN:IN10:111:FLOOR_SUPPORT_TEMP2_AVG") { field(DESC, "Avg sig samples") field(INP, "GUN:IN10:111:FLOOR_SUPPORT_TEMP2_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "GUN:IN10:111:FLOOR_SUPPORT_TEMP2_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M11_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M11_CH2_TEMP") { field(DESC, "Gun Floor Supports Temps") field(FLNK, "GUN:IN10:111:FLOOR_SUPPORT_TEMP2") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M11_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "89.8") field(LOLO, "79.5") field(HIGH, "87") field(LOW, "82.3") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "GUN:IN10:111:FLOOR_SUPPORT_TEMP2_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M11_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:11:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M11_CH2_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "GUN:IN10:111:WGOUTLETTEMP") { field(DESC,"Gun Waveguide Water Temps") field(SCAN, "1 second") field(INP, "GUN:IN10:111:WGOUTLETTEMP_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "96.2") field(LOLO, "93.2") field(HIGH, "95.4") field(LOW, "94") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "GUN:IN10:111:WGOUTLETTEMP_AVG") { field(DESC, "Avg sig samples") field(INP, "GUN:IN10:111:WGOUTLETTEMP_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "GUN:IN10:111:WGOUTLETTEMP_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M12_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M12_CH1_TEMP") { field(DESC, "Gun Waveguide Water Temps") field(FLNK, "GUN:IN10:111:WGOUTLETTEMP") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M12_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "96.2") field(LOLO, "93.2") field(HIGH, "95.4") field(LOW, "94") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "GUN:IN10:111:WGOUTLETTEMP_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M12_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:12:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M12_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "GUN:IN10:111:WGINLETTEMP") { field(DESC,"Gun Waveguide Water Temps") field(SCAN, "1 second") field(INP, "GUN:IN10:111:WGINLETTEMP_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "96.1") field(LOLO, "93.1") field(HIGH, "95.3") field(LOW, "93.9") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "GUN:IN10:111:WGINLETTEMP_AVG") { field(DESC, "Avg sig samples") field(INP, "GUN:IN10:111:WGINLETTEMP_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "GUN:IN10:111:WGINLETTEMP_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M12_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M12_CH2_TEMP") { field(DESC, "Gun Waveguide Water Temps") field(FLNK, "GUN:IN10:111:WGINLETTEMP") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M12_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "96.1") field(LOLO, "93.1") field(HIGH, "95.3") field(LOW, "93.9") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "GUN:IN10:111:WGINLETTEMP_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M12_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:12:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M12_CH2_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "PCAV:IN10:365:WGTEMP2") { field(DESC,"Phase Cavity") field(SCAN, "1 second") field(INP, "PCAV:IN10:365:WGTEMP2_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "81.2") field(LOLO, "78.6") field(HIGH, "80.9") field(LOW, "78.9") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "PCAV:IN10:365:WGTEMP2_AVG") { field(DESC, "Avg sig samples") field(INP, "PCAV:IN10:365:WGTEMP2_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "PCAV:IN10:365:WGTEMP2_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M13_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M13_CH1_TEMP") { field(DESC, "Phase Cavity") field(FLNK, "PCAV:IN10:365:WGTEMP2") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M13_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "81.2") field(LOLO, "78.6") field(HIGH, "80.9") field(LOW, "78.9") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "PCAV:IN10:365:WGTEMP2_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M13_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:13:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M13_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "QUAD:IN10:371:TEMP") { field(DESC,"Quadropole Magnet") field(SCAN, "1 second") field(INP, "QUAD:IN10:371:TEMP_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "87.9") field(LOLO, "85") field(HIGH, "87.4") field(LOW, "85.4") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "QUAD:IN10:371:TEMP_AVG") { field(DESC, "Avg sig samples") field(INP, "QUAD:IN10:371:TEMP_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "QUAD:IN10:371:TEMP_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M13_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M13_CH2_TEMP") { field(DESC, "Quadropole Magnet") field(FLNK, "QUAD:IN10:371:TEMP") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M13_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "87.9") field(LOLO, "85") field(HIGH, "87.4") field(LOW, "85.4") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "QUAD:IN10:371:TEMP_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M13_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:13:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M13_CH2_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "ACCL:IN10:300:WGTEMP1") { field(DESC,"L0A Accelerator Structure") field(SCAN, "1 second") field(INP, "ACCL:IN10:300:WGTEMP1_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "112.3") field(LOLO, "107.1") field(HIGH, "111.4") field(LOW, "108") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "ACCL:IN10:300:WGTEMP1_AVG") { field(DESC, "Avg sig samples") field(INP, "ACCL:IN10:300:WGTEMP1_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "ACCL:IN10:300:WGTEMP1_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M15_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M15_CH1_TEMP") { field(DESC, "L0A Accelerator Structure") field(FLNK, "ACCL:IN10:300:WGTEMP1") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M15_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "112.3") field(LOLO, "107.1") field(HIGH, "111.4") field(LOW, "108") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "ACCL:IN10:300:WGTEMP1_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M15_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:15:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M15_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "ACCL:IN10:300:WGTEMP2") { field(DESC,"L0A Accelerator Structure") field(SCAN, "1 second") field(INP, "ACCL:IN10:300:WGTEMP2_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "111") field(LOLO, "106.8") field(HIGH, "110.3") field(LOW, "107.5") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "ACCL:IN10:300:WGTEMP2_AVG") { field(DESC, "Avg sig samples") field(INP, "ACCL:IN10:300:WGTEMP2_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "ACCL:IN10:300:WGTEMP2_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M15_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M15_CH2_TEMP") { field(DESC, "L0A Accelerator Structure") field(FLNK, "ACCL:IN10:300:WGTEMP2") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M15_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "111") field(LOLO, "106.8") field(HIGH, "110.3") field(LOW, "107.5") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "ACCL:IN10:300:WGTEMP2_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M15_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:15:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M15_CH2_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "QUAD:IN10:361:TEMP") { field(DESC,"Quadropole Magnet") field(SCAN, "1 second") field(INP, "QUAD:IN10:361:TEMP_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "87.3") field(LOLO, "84.3") field(HIGH, "86.9") field(LOW, "84.8") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "QUAD:IN10:361:TEMP_AVG") { field(DESC, "Avg sig samples") field(INP, "QUAD:IN10:361:TEMP_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "QUAD:IN10:361:TEMP_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M16_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M16_CH1_TEMP") { field(DESC, "Quadropole Magnet") field(FLNK, "QUAD:IN10:361:TEMP") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M16_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "87.3") field(LOLO, "84.3") field(HIGH, "86.9") field(LOW, "84.8") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "QUAD:IN10:361:TEMP_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M16_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:16:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M16_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "PCAV:IN10:365:WGTEMP1") { field(DESC,"Phase Cavity") field(SCAN, "1 second") field(INP, "PCAV:IN10:365:WGTEMP1_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80.8") field(LOLO, "78.3") field(HIGH, "80.5") field(LOW, "78.6") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "PCAV:IN10:365:WGTEMP1_AVG") { field(DESC, "Avg sig samples") field(INP, "PCAV:IN10:365:WGTEMP1_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "PCAV:IN10:365:WGTEMP1_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M16_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M16_CH2_TEMP") { field(DESC, "Phase Cavity") field(FLNK, "PCAV:IN10:365:WGTEMP1") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M16_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "80.8") field(LOLO, "78.3") field(HIGH, "80.5") field(LOW, "78.6") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "PCAV:IN10:365:WGTEMP1_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M16_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:16:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M16_CH2_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "ACCL:IN10:400:WGTEMP1") { field(DESC,"L0B Accelerator Structure") field(SCAN, "1 second") field(INP, "ACCL:IN10:400:WGTEMP1_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "110.4") field(LOLO, "106.6") field(HIGH, "109.8") field(LOW, "107.3") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "ACCL:IN10:400:WGTEMP1_AVG") { field(DESC, "Avg sig samples") field(INP, "ACCL:IN10:400:WGTEMP1_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "ACCL:IN10:400:WGTEMP1_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M18_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M18_CH1_TEMP") { field(DESC, "L0B Accelerator Structure") field(FLNK, "ACCL:IN10:400:WGTEMP1") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M18_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "110.4") field(LOLO, "106.6") field(HIGH, "109.8") field(LOW, "107.3") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "ACCL:IN10:400:WGTEMP1_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M18_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:18:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M18_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "ACCL:IN10:400:WGTEMP2") { field(DESC,"L0B Accelerator Structure") field(SCAN, "1 second") field(INP, "ACCL:IN10:400:WGTEMP2_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "111.1") field(LOLO, "107.4") field(HIGH, "110.5") field(LOW, "107.9") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "ACCL:IN10:400:WGTEMP2_AVG") { field(DESC, "Avg sig samples") field(INP, "ACCL:IN10:400:WGTEMP2_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "ACCL:IN10:400:WGTEMP2_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M18_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M18_CH2_TEMP") { field(DESC, "L0B Accelerator Structure") field(FLNK, "ACCL:IN10:400:WGTEMP2") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M18_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "111.1") field(LOLO, "107.4") field(HIGH, "110.5") field(LOW, "107.9") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "ACCL:IN10:400:WGTEMP2_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M18_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:18:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M18_CH2_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "TCAV:IN10:490:WGTEMP1") { field(DESC,"TCAV") field(SCAN, "1 second") field(INP, "TCAV:IN10:490:WGTEMP1_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "103.2") field(LOLO, "101.1") field(HIGH, "102.9") field(LOW, "101.4") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "TCAV:IN10:490:WGTEMP1_AVG") { field(DESC, "Avg sig samples") field(INP, "TCAV:IN10:490:WGTEMP1_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "TCAV:IN10:490:WGTEMP1_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M19_CH1_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M19_CH1_TEMP") { field(DESC, "TCAV") field(FLNK, "TCAV:IN10:490:WGTEMP1") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M19_CH1_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "103.2") field(LOLO, "101.1") field(HIGH, "102.9") field(LOW, "101.4") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "TCAV:IN10:490:WGTEMP1_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M19_CH1_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:19:R_ANA_IN_1") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M19_CH1_TEMP") field(ASG, "") } #============================================================================== # # Abs: RTD module KL3222 template, customized for LCLS conventions # # Name: KL3222-lcls.template # # Macros: # # APC (All Purpose Controller) # First three fields of APC device name, for example: APC:LTU0:1 # (Numbering convention: Each set of I/O modules that share a single # controller is one unit. All PVs associated with this set of modules # should share this APC device name.) # # COUPLER Node name of coupler, for example: bkhf-ltu0-tm01 # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # D Type of device (string), for example: "RTD" # or device description, for example "50B1" # # SLOT Slot number of I/O module. Slot numbers increment from left to right. # The first module to the right of the coupler is in slot 1. # # CH Channel number, from 1 to 4 # # ALIAS Device name, for example: QUAD:LTU0:110:TEMP # # SCAN Data acquisition rate in EPICS record SCAN format. If you are not using data # averaging, set this to "1 second". Otherwise, set it to your desired # data acquisition rate. It will set the scan rate for the low-level PVs. # The high-level PVs (ALIAS) still scan at "1 second". # # NSAM Number of samples to average in _AVG compress record. # Set to "1" if no averaging desired. # # ASG Access Security Group (used by RTDs for MPS) # #============================================================================== record(ai, "TCAV:IN10:490:WGTEMP2") { field(DESC,"TCAV") field(SCAN, "1 second") field(INP, "TCAV:IN10:490:WGTEMP2_AVG PP MSI") field(PREC, "1") field(EGU, "DegF") field(HOPR, "150") field(LOPR, "50") field(HIHI, "103.4") field(LOLO, "100.8") field(HIGH, "103.1") field(LOW, "101.1") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(ASG, "") } # Optional averaging # If no averaging desired, # set 10 to "1" and 1 second to "1 second" #--------------------------------------- record(compress, "TCAV:IN10:490:WGTEMP2_AVG") { field(DESC, "Avg sig samples") field(INP, "TCAV:IN10:490:WGTEMP2_DATA NPP MSI") field(ALG, "N to 1 Average") field(N, "10") field(NSAM, "1") field(PREC, "1") field(ASG, "") } record(compress, "TCAV:IN10:490:WGTEMP2_DATA") { field(DESC, "Samples to avg") field(INP, "BKHF:IN10:TM01:M19_CH2_TEMP NPP MSI") field(ALG, "Circular Buffer") field(NSAM, "10") field(PREC, "1") field(ASG, "") } #----------------------------------------- # Convert degC to degF # .VAL and .A used by generic KL3314 diagnostic display record(calc, "BKHF:IN10:TM01:M19_CH2_TEMP") { field(DESC, "TCAV") field(FLNK, "TCAV:IN10:490:WGTEMP2") field(CALC, "A*1.8+32") field(INPA, "BKHF:IN10:TM01:M19_CH2_SIG NPP MS") field(EGU, "DegF") field(PREC, "1") field(HOPR, "150") field(LOPR, "50") field(HIHI, "103.4") field(LOLO, "100.8") field(HIGH, "103.1") field(LOW, "101.1") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MINOR") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(FLNK, "TCAV:IN10:490:WGTEMP2_DATA") field(ASG, "") } record(ai, "BKHF:IN10:TM01:M19_CH2_SIG") { field(DESC, "RTD Readback") field(SCAN, "1 second") field(DTYP, "Bk9000_KL3222") field(INP, "@bkhf-li10-tm01:19:R_ANA_IN_2") field(PREC, "1") field(HOPR, "500") field(HIHI, "500") field(HIGH, "500") field(LOW, "-100") field(LOLO, "-100") field(LOPR, "-100") field(HYST, ".1") field(ADEL, "0.001") field(MDEL, "0.001") field(EGU, "DegC") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(FLNK, "BKHF:IN10:TM01:M19_CH2_TEMP") field(ASG, "") }