#PV status
record(bi, "${ALIAS}"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@$(PLC) $(PLC_TAG) B $(CHAN)")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

#Alarm Bypass 
record(bo, "${ALIAS}BYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(OUT , "@$(PLC) EEPSB6[$(INDEX)] B $(CHAN)")
  info(autosaveFields,"VAL")
}

record(bi, "${ALIAS}BYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@$(PLC) PEPSB6[$(INDEX)] B $(CHAN)")
  field(ONAM, "BYPASSED")
  field(ZNAM, "NOT BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}