#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(ai, "PLC:HTR:TM01:STATUSRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[5]")
  field(FLNK, "PLC:HTR:TM01:DEVICESTATUSRAW")
}

record(ai, "PLC:HTR:TM01:MODELRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[6]")
  field(FLNK, "PLC:HTR:TM01:MODELCALC")
}

record(ai, "PLC:HTR:TM01:UPTIMESEC") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[17]")
  field(FLNK, "PLC:HTR:TM01:UPTIMEHOURS PP MS")
}

record(calc, "PLC:HTR:TM01:UPTIMEHOURS") {
  field(FLNK, "PLC:HTR:TM01:UPTIMEMINUTES PP MS")
  field(CALC, "FLOOR(A/3600)")
  field(INPA, "PLC:HTR:TM01:UPTIMESEC")
  field(EGU, "Hours")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC NPP MS")
}

record(calc, "PLC:HTR:TM01:UPTIMEMINUTES") {
  field(FLNK, "PLC:HTR:TM01:UPTIMESECONDS PP MS")
  field(CALC, "FLOOR((A%3600)/60)")
  field(INPA, "PLC:HTR:TM01:UPTIMESEC")
  field(EGU, "Minutes")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:HTR:TM01:UPTIMESECONDS") {
  field(CALC, "A%60")
  field(INPA, "PLC:HTR:TM01:UPTIMESEC")
  field(EGU, "Seconds")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(bi, "PLC:HTR:TM01:HEARTBEATRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[19] B 0")
  field(ZNAM, "ZERO")
  field(ONAM, "ONE")
  field(FLNK, "PLC:HTR:TM01:COMMLINK")
}

record(mbbi, "PLC:HTR:TM01:MODEL") {
  field(INP, "PLC:HTR:TM01:MODELCALC NPP MS")
  field(ZRST, "UNKNOWN")
  field(ONST, "CTL_LGX_L61")
  field(TWST, "CTL_LGX_5555")
  field(THST, "CTL_LTX_5550")
  field(FRST, "CMP_LGX_L32")
}

record(ai, "PLC:HTR:TM01:FWVERSIONRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[7]")
  field(FLNK, "PLC:HTR:TM01:FWVERSIONMAJ")
}

record(calc, "PLC:HTR:TM01:FWVERSIONMAJ") {
  field(FLNK, "PLC:HTR:TM01:FWVERSIONMIN")
  field(CALC, "A%16")
  field(INPA, "PLC:HTR:TM01:FWVERSIONRAW NPP MS")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:HTR:TM01:FWVERSIONMIN") {
  field(CALC, "(A/256)%16")
  field(INPA, "PLC:HTR:TM01:FWVERSIONRAW NPP MS")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:HTR:TM01:MODELCALC") {
  field(FLNK, "PLC:HTR:TM01:MODEL")
  field(CALC, "A=54?1:A=51?2:A=3?3:A=77?4:0")
  field(INPA, "PLC:HTR:TM01:MODELRAW NPP MS")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:HTR:TM01:DEVICESTATUSCALC") {
  field(FLNK, "PLC:HTR:TM01:DEVICESTATUS")
  field(CALC, "A=B?1:A=C?2:A=D?3:A=E?4:A=F?5:A=G?6:0")
  field(INPA, "PLC:HTR:TM01:DEVICESTATUSRAW NPP MS")
  field(INPB, "0x7")
  field(INPC, "0x6")
  field(INPD, "0x5")
  field(INPE, "0x4")
  field(INPF, "0x1")
}

record(calc, "PLC:HTR:TM01:DEVICESTATUSRAW") {
  field(FLNK, "PLC:HTR:TM01:DEVICESTATUSCALC")
  field(CALC, "A>>4&B")
  field(INPA, "PLC:HTR:TM01:STATUSRAW")
  field(INPB, "0xF")
  field(INPC, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(mbbi, "PLC:HTR:TM01:DEVICESTATUS") {
  field(FLNK, "PLC:HTR:TM01:FAULTSTATUSRAW")
  field(INP, "PLC:HTR:TM01:DEVICESTATUSCALC NPP MS")
  field(ZRST, "UNKNOWN")
  field(ONST, "PROGRAM")
  field(TWST, "RUN")
  field(THST, "FAULTED")
  field(FRST, "FLASH_ERROR")
  field(FVST, "FLASHING")
  field(ZRSV, "MAJOR")
  field(ONSV, "MAJOR")
  field(TWSV, "NO_ALARM")
  field(THSV, "MAJOR")
  field(FRSV, "MAJOR")
  field(FVSV, "MAJOR")
}

record(calc, "PLC:HTR:TM01:FAULTSTATUSRAW") {
  field(FLNK, "PLC:HTR:TM01:FAULTSTATUSCALC")
  field(CALC, "A>>8&B")
  field(INPA, "PLC:HTR:TM01:STATUSRAW")
  field(INPB, "0xF")
  field(INPC, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:HTR:TM01:FAULTSTATUSCALC") {
  field(FLNK, "PLC:HTR:TM01:FAULTSTATUS")
  field(CALC, "A=B?1:A=C?2:A=D?3:A=E?4:0")
  field(INPA, "PLC:HTR:TM01:FAULTSTATUSRAW NPP MS")
  field(INPB, "0x0004")
  field(INPC, "0x0003")
  field(INPD, "0x0002")
  field(INPE, "0x0001")
}

record(mbbi, "PLC:HTR:TM01:FAULTSTATUS") {
  field(FLNK, "PLC:HTR:TM01:KEYSTATUSRAW")
  field(INP, "PLC:HTR:TM01:FAULTSTATUSCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MAJOR_UNRECOVBL")
  field(TWST, "MAJOR_RECOVBL")
  field(THST, "MINOR_UNRECOVBL")
  field(FRST, "MINOR_RECOVBL")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "MAJOR")
  field(THSV, "MINOR")
  field(FRSV, "NO_ALARM")
}

record(calc, "PLC:HTR:TM01:KEYSTATUSRAW") {
  field(FLNK, "PLC:HTR:TM01:KEYSTATUSCALC")
  field(CALC, "A>>12&B")
  field(INPA, "PLC:HTR:TM01:STATUSRAW")
  field(INPB, "0x3")
  field(INPC, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:HTR:TM01:KEYSTATUSCALC") {
  field(FLNK, "PLC:HTR:TM01:KEYSTATUS")
  field(CALC, "A=B?1:A=C?2:A=D?3:0")
  field(INPA, "PLC:HTR:TM01:KEYSTATUSRAW NPP MS")
  field(INPB, "0x3")
  field(INPC, "0x2")
  field(INPD, "0x1")
}

record(mbbi, "PLC:HTR:TM01:KEYSTATUS") {
  field(INP, "PLC:HTR:TM01:KEYSTATUSCALC NPP MS")
  field(ZRST, "UNKNOWN")
  field(ONST, "REMOTE")
  field(TWST, "PROGRAM")
  field(THST, "RUN")
  field(ZRSV, "MAJOR")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "NO_ALARM")
}

record(ai, "PLC:HTR:TM01:MAJORFAULTRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[8]")
  field(FLNK, "PLC:HTR:TM01:FAULTPOWERCALC")
}

record(ai, "PLC:HTR:TM01:MINORFAULTRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[9]")
}

record(calc, "PLC:HTR:TM01:FAULTPOWERCALC") {
  field(FLNK, "PLC:HTR:TM01:FAULTPOWER")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:HTR:TM01:MAJORFAULTRAW")
  field(INPB, "PLC:HTR:TM01:MINORFAULTRAW")
  field(INPC, "0x2")
  field(INPD, "PLC:HTR:TM01:HEARTBEATCLC NPP MS")
}

record(mbbi, "PLC:HTR:TM01:FAULTPOWER") {
  field(FLNK, "PLC:HTR:TM01:FAULTIOCALC")
  field(INP, "PLC:HTR:TM01:FAULTPOWERCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
}

record(calc, "PLC:HTR:TM01:FAULTIOCALC") {
  field(FLNK, "PLC:HTR:TM01:FAULTIO")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:HTR:TM01:MAJORFAULTRAW")
  field(INPB, "PLC:HTR:TM01:MINORFAULTRAW")
  field(INPC, "0x8")
  field(INPD, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(mbbi, "PLC:HTR:TM01:FAULTIO") {
  field(FLNK, "PLC:HTR:TM01:FAULTPROGRAMCALC")
  field(INP, "PLC:HTR:TM01:FAULTIOCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
}

record(calc, "PLC:HTR:TM01:FAULTPROGRAMCALC") {
  field(FLNK, "PLC:HTR:TM01:FAULTPROGRAM")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:HTR:TM01:MAJORFAULTRAW")
  field(INPB, "PLC:HTR:TM01:MINORFAULTRAW")
  field(INPC, "0x10")
  field(INPD, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(mbbi, "PLC:HTR:TM01:FAULTPROGRAM") {
  field(FLNK, "PLC:HTR:TM01:FAULTFLTHNDLCALC")
  field(INP, "PLC:HTR:TM01:FAULTPROGRAMCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
}

record(mbbi, "PLC:HTR:TM01:FAULTFLTHNDL") {
  field(FLNK, "PLC:HTR:TM01:FAULTWTCHDOGCALC")
  field(INP, "PLC:HTR:TM01:FAULTFLTHNDLCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
}

record(calc, "PLC:HTR:TM01:FAULTFLTHNDLCALC") {
  field(FLNK, "PLC:HTR:TM01:FAULTFLTHNDL")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:HTR:TM01:MAJORFAULTRAW")
  field(INPB, "PLC:HTR:TM01:MINORFAULTRAW")
  field(INPC, "0x20")
  field(INPD, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:HTR:TM01:FAULTWTCHDOGCALC") {
  field(FLNK, "PLC:HTR:TM01:FAULTWTCHDOG")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:HTR:TM01:MAJORFAULTRAW")
  field(INPB, "PLC:HTR:TM01:MINORFAULTRAW")
  field(INPC, "0x40")
  field(INPD, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(mbbi, "PLC:HTR:TM01:FAULTWTCHDOG") {
  field(FLNK, "PLC:HTR:TM01:FAULTSTACKCALC")
  field(INP, "PLC:HTR:TM01:FAULTWTCHDOGCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
}

record(calc, "PLC:HTR:TM01:FAULTSTACKCALC") {
  field(FLNK, "PLC:HTR:TM01:FAULTSTACK")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:HTR:TM01:MAJORFAULTRAW")
  field(INPB, "PLC:HTR:TM01:MINORFAULTRAW")
  field(INPC, "0x80")
  field(INPD, "PLC:HTR:TM01:HEARTBEATCLC MS")
}


record(mbbi, "PLC:HTR:TM01:FAULTSTACK") {
  field(FLNK, "PLC:HTR:TM01:FAULTMODECHGCALC")
  field(INP, "PLC:HTR:TM01:FAULTSTACKCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "NO_ALARM")
  field(TWSV, "MAJOR")
}

record(calc, "PLC:HTR:TM01:FAULTMODECHGCALC") {
  field(FLNK, "PLC:HTR:TM01:FAULTMODECHG")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:HTR:TM01:MAJORFAULTRAW")
  field(INPB, "PLC:HTR:TM01:MINORFAULTRAW")
  field(INPC, "0x100")
  field(INPD, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(mbbi, "PLC:HTR:TM01:FAULTMODECHG") {
  field(FLNK, "PLC:HTR:TM01:FAULTSERIALCALC")
  field(INP, "PLC:HTR:TM01:FAULTMODECHGCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
}

record(calc, "PLC:HTR:TM01:FAULTSERIALCALC") {
  field(FLNK, "PLC:HTR:TM01:FAULTSERIAL")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:HTR:TM01:MAJORFAULTRAW")
  field(INPB, "PLC:HTR:TM01:MINORFAULTRAW")
  field(INPC, "0x200")
  field(INPD, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(mbbi, "PLC:HTR:TM01:FAULTSERIAL") {
  field(FLNK, "PLC:HTR:TM01:FAULTBATTERYCALC")
  field(INP, "PLC:HTR:TM01:FAULTSERIALCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
}

record(mbbi, "PLC:HTR:TM01:FAULTBATTERY") {
  field(FLNK, "PLC:HTR:TM01:FAULTMOTIONCALC")
  field(INP, "PLC:HTR:TM01:FAULTBATTERYCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
}

record(calc, "PLC:HTR:TM01:FAULTBATTERYCALC") {
  field(FLNK, "PLC:HTR:TM01:FAULTBATTERY")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:HTR:TM01:MAJORFAULTRAW")
  field(INPB, "PLC:HTR:TM01:MINORFAULTRAW")
  field(INPC, "0x400")
  field(INPD, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:HTR:TM01:FAULTMOTIONCALC") {
  field(FLNK, "PLC:HTR:TM01:FAULTMOTION")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:HTR:TM01:MAJORFAULTRAW")
  field(INPB, "PLC:HTR:TM01:MINORFAULTRAW")
  field(INPC, "0x800")
  field(INPD, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(mbbi, "PLC:HTR:TM01:FAULTMOTION") {
  field(INP, "PLC:HTR:TM01:FAULTMOTIONCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
}

record(ai, "PLC:HTR:TM01:VERSIONMAJORDES") {
  field(PINI, "YES")
  field(FLNK, "PLC:HTR:TM01:VERSIONMAJORCALCHI")
  field(VAL, "1")
  field(PREC, "0")
}

record(calcout, "PLC:HTR:TM01:VERSIONMAJORCALCHI") {
  field(FLNK, "PLC:HTR:TM01:VERSIONMAJORCALCLO")
  field(CALC, "A+1")
  field(INPA, "PLC:HTR:TM01:VERSIONMAJORDES")
  field(OUT, "PLC:HTR:TM01:VERSIONMAJOR.HIGH")
}

record(calcout, "PLC:HTR:TM01:VERSIONMAJORCALCLO") {
  field(CALC, "A-1")
  field(INPA, "PLC:HTR:TM01:VERSIONMAJORDES")
  field(OUT, "PLC:HTR:TM01:VERSIONMAJOR.LOW")
}

record(ai, "PLC:HTR:TM01:VERSIONMINORDES") {
  field(PINI, "YES")
  field(FLNK, "PLC:HTR:TM01:VERSIONMINORCALCHI")
  field(VAL, "1")
  field(PREC, "0")
}

record(calcout, "PLC:HTR:TM01:VERSIONMINORCALCLO") {
  field(CALC, "A-1")
  field(INPA, "PLC:HTR:TM01:VERSIONMINORDES.VAL")
  field(OUT, "PLC:HTR:TM01:VERSIONMINOR.LOW")
}

record(calcout, "PLC:HTR:TM01:VERSIONMINORCALCHI") {
  field(FLNK, "PLC:HTR:TM01:VERSIONMINORCALCLO")
  field(CALC, "A+1")
  field(INPA, "PLC:HTR:TM01:VERSIONMINORDES.VAL")
  field(OUT, "PLC:HTR:TM01:VERSIONMINOR.HIGH")
}

record(ai, "PLC:HTR:TM01:VERSIONREVDES") {
  field(PINI, "YES")
  field(FLNK, "PLC:HTR:TM01:VERSIONREVCALCHI")
  field(VAL, "1")
  field(PREC, "0")
}

record(calcout, "PLC:HTR:TM01:VERSIONREVCALCHI") {
  field(FLNK, "PLC:HTR:TM01:VERSIONREVCALCLO")
  field(CALC, "A+1")
  field(INPA, "PLC:HTR:TM01:VERSIONREVDES.VAL")
  field(OUT, "PLC:HTR:TM01:VERSIONREV.HIGH")
}

record(calcout, "PLC:HTR:TM01:VERSIONREVCALCLO") {
  field(CALC, "A-1")
  field(INPA, "PLC:HTR:TM01:VERSIONREVDES.VAL")
  field(OUT, "PLC:HTR:TM01:VERSIONREV.LOW")
}

record(calc, "PLC:HTR:TM01:HEARTBEATCALC") {
  field(FLNK, "PLC:HTR:TM01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:HEARTBEATRAW")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCALC")
}

record(bi, "PLC:HTR:TM01:HEARTBEATOK") {
  field(FLNK, "PLC:HTR:TM01:HEARTBEATE01")
  field(INP, "PLC:HTR:TM01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "PLC:HTR:TM01:HEARTBEATERR") {
  field(FLNK, "PLC:HTR:TM01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "PLC:HTR:TM01:HEARTBEATCALC.A")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCALC.B")
}

record(calc, "PLC:HTR:TM01:HEARTBEATECT") {
  field(FLNK, "PLC:HTR:TM01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "PLC:HTR:TM01:HEARTBEATE01")
  field(INPB, "PLC:HTR:TM01:HEARTBEATE02")
  field(INPC, "PLC:HTR:TM01:HEARTBEATE03")
  field(INPD, "PLC:HTR:TM01:HEARTBEATE04")
  field(INPE, "PLC:HTR:TM01:HEARTBEATE05")
  field(INPF, "PLC:HTR:TM01:HEARTBEATE06")
  field(INPG, "PLC:HTR:TM01:HEARTBEATE07")
  field(INPH, "PLC:HTR:TM01:HEARTBEATE08")
  field(INPI, "PLC:HTR:TM01:HEARTBEATE09")
  field(INPJ, "PLC:HTR:TM01:HEARTBEATE10")
  field(HIHI, "7")
  field(LOLO, "-1")
  field(HIGH, "5")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "PLC:HTR:TM01:HEARTBEATE09") {
  field(FLNK, "PLC:HTR:TM01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:HEARTBEATE08.B")
  field(INPB, "PLC:HTR:TM01:HEARTBEATE09.VAL")
}

record(calc, "PLC:HTR:TM01:HEARTBEATE08") {
  field(FLNK, "PLC:HTR:TM01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:HEARTBEATE07.B")
  field(INPB, "PLC:HTR:TM01:HEARTBEATE08.VAL")
}

record(calc, "PLC:HTR:TM01:HEARTBEATE07") {
  field(FLNK, "PLC:HTR:TM01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:HEARTBEATE06.B")
  field(INPB, "PLC:HTR:TM01:HEARTBEATE07.VAL")
}

record(calc, "PLC:HTR:TM01:HEARTBEATE06") {
  field(FLNK, "PLC:HTR:TM01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:HEARTBEATE05.B")
  field(INPB, "PLC:HTR:TM01:HEARTBEATE06.VAL")
}

record(calc, "PLC:HTR:TM01:HEARTBEATE05") {
  field(FLNK, "PLC:HTR:TM01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:HEARTBEATE04.B")
  field(INPB, "PLC:HTR:TM01:HEARTBEATE05.VAL")
}

record(calc, "PLC:HTR:TM01:HEARTBEATE04") {
  field(FLNK, "PLC:HTR:TM01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:HEARTBEATE03.B")
  field(INPB, "PLC:HTR:TM01:HEARTBEATE04.VAL")
}

record(calc, "PLC:HTR:TM01:HEARTBEATE03") {
  field(FLNK, "PLC:HTR:TM01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:HEARTBEATE02.B")
  field(INPB, "PLC:HTR:TM01:HEARTBEATE03.VAL")
}

record(calc, "PLC:HTR:TM01:HEARTBEATE02") {
  field(FLNK, "PLC:HTR:TM01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:HEARTBEATE01.B")
  field(INPB, "PLC:HTR:TM01:HEARTBEATE02.VAL")
}

record(calc, "PLC:HTR:TM01:HEARTBEATE01") {
  field(FLNK, "PLC:HTR:TM01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:HEARTBEATERR")
  field(INPB, "PLC:HTR:TM01:HEARTBEATE01.VAL")
}

record(calc, "PLC:HTR:TM01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "PLC:HTR:TM01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "PLC:HTR:TM01:HEARTBEATSUM") {
  field(FLNK, "PLC:HTR:TM01:HEARTBEATCLC")
  field(INP, "PLC:HTR:TM01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(ai, "PLC:HTR:TM01:UPTIMEDAYRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[18]")
  field(FLNK, "PLC:HTR:TM01:UPTIMEDAY")
}

record(calc, "PLC:HTR:TM01:UPTIMEDAY") {
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:UPTIMEDAYRAW")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(ai, "PLC:HTR:TM01:TODYEARRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[10]")
  field(FLNK, "PLC:HTR:TM01:TODYEAR")
}

record(ai, "PLC:HTR:TM01:TODDAYRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[12]")
  field(SCAN, "1 second")
  field(FLNK, "PLC:HTR:TM01:TODDAY")
}

record(ai, "PLC:HTR:TM01:TODMONTHRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[11]")
  field(FLNK, "PLC:HTR:TM01:TODMONTH")
  field(SCAN, "1 second")
}

record(ai, "PLC:HTR:TM01:TODHOURRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[13]")
  field(FLNK, "PLC:HTR:TM01:TODHOUR")
}

record(ai, "PLC:HTR:TM01:TODMINUTERAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[14]")
  field(FLNK, "PLC:HTR:TM01:TODMINUTE")
  field(SCAN, "1 second")
}

record(ai, "PLC:HTR:TM01:TODSECONDRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[15]")
  field(SCAN, "1 second")
  field(FLNK, "PLC:HTR:TM01:TODSECOND")
}

record(calc, "PLC:HTR:TM01:TODYEAR") {
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:TODYEARRAW NPP MS")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:HTR:TM01:TODMONTH") {
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:TODMONTHRAW NPP MS")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:HTR:TM01:TODDAY") {
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:TODDAYRAW NPP MS")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:HTR:TM01:TODHOUR") {
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:TODHOURRAW NPP MS")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:HTR:TM01:TODMINUTE") {
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:TODMINUTERAW NPP MS")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:HTR:TM01:TODSECOND") {
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:TODSECONDRAW NPP MS")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(ai, "PLC:HTR:TM01:VERSIONMAJORRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[36]")
  field(HYST, "1")
  field(FLNK, "PLC:HTR:TM01:VERSIONMAJOR")
}

record(ai, "PLC:HTR:TM01:VERSIONMINORRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[37]")
  field(FLNK, "PLC:HTR:TM01:VERSIONMINOR")
}

record(calc, "PLC:HTR:TM01:VERSIONMAJOR") {
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:VERSIONMAJORRAW NPP MS")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
  field(HSV, "MAJOR")
  field(LSV, "MAJOR")
}

record(calc, "PLC:HTR:TM01:VERSIONMINOR") {
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:VERSIONMINORRAW NPP MS")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
  field(HSV, "MAJOR")
  field(LSV, "MAJOR")
}

record(ai, "PLC:HTR:TM01:VERSIONREVRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[38]")
  field(FLNK, "PLC:HTR:TM01:VERSIONREV")
}

record(calc, "PLC:HTR:TM01:VERSIONREV") {
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:VERSIONREVRAW NPP MS")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
  field(HSV, "MAJOR")
  field(LSV, "MAJOR")
}

record(ai, "PLC:HTR:TM01:SERIALNUMBERRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[4]")
  field(FLNK, "PLC:HTR:TM01:SERIALNUMBER")
}

record(calc, "PLC:HTR:TM01:SERIALNUMBER") {
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:SERIALNUMBERRAW NPP MS")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(mbbi, "PLC:HTR:TM01:COMMLINK") {
  field(FLNK, "PLC:HTR:TM01:HEARTBEATCALC")
  field(INP, "PLC:HTR:TM01:HEARTBEATRAW.SEVR")
  field(ZRST, "OK")
  field(ONST, "OK")
  field(TWST, "OK")
  field(THST, "FAULT")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "NO_ALARM")
  field(TWSV, "NO_ALARM")
  field(THSV, "MAJOR")
}

record(calc, "PLC:HTR:TM01:HEARTBEATE10") {
  field(FLNK, "PLC:HTR:TM01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:HEARTBEATE09.B")
  field(INPB, "PLC:HTR:TM01:HEARTBEATE10.VAL")
}

record(ai, "PLC:HTR:TM01:DOCPREFIXRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:HTR:TM01:DOCPREFIXCALC")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[31]")
}

record(calc, "PLC:HTR:TM01:DOCPREFIXCALC") {
  field(FLNK, "PLC:HTR:TM01:DOCPREFIX")
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:DOCPREFIXRAW")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(mbbi, "PLC:HTR:TM01:DOCPREFIX") {
  field(INP, "PLC:HTR:TM01:DOCPREFIXCALC NPP MS")
  field(ZRVL, "0")
  field(ONVL, "1")
  field(ZRST, "NONE")
  field(ONST, "SD")
  field(TWVL, "2")
  field(THVL, "3")
  field(FRVL, "4")
  field(FVVL, "5")
  field(SXVL, "6")
  field(SVVL, "7")
  field(EIVL, "8")
  field(NIVL, "9")
  field(TEVL, "10")
  field(ELVL, "11")
  field(TWST, "BD")
  field(THST, "DL")
  field(FRST, "EI")
  field(FVST, "FC")
  field(SXST, "FS")
  field(SVST, "IM")
  field(EIST, "LD")
  field(NIST, "OM")
  field(TEST, "QT")
  field(ELST, "WD")
}

record(ai, "PLC:HTR:TM01:DOCSERIESRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:HTR:TM01:DOCSERIES")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[32]")
}

record(calc, "PLC:HTR:TM01:DOCSERIES") {
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:DOCSERIESRAW.VAL")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(ai, "PLC:HTR:TM01:DOCBASERAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:HTR:TM01:DOCBASE")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[33]")
}

record(calc, "PLC:HTR:TM01:DOCBASE") {
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:DOCBASERAW.VAL")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(ai, "PLC:HTR:TM01:DOCSUFFIXRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:HTR:TM01:DOCSUFFIX")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[34]")
}

record(calc, "PLC:HTR:TM01:DOCSUFFIX") {
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:DOCSUFFIXRAW")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(ai, "PLC:HTR:TM01:DOCREVRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:HTR:TM01:DOCREV")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[35]")
}

record(calc, "PLC:HTR:TM01:DOCREV") {
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:DOCREVRAW")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(stringin, "PLC:HTR:TM01:SUBSYSTEM") {
  field(PINI, "YES")
  field(VAL, "TEMPERATURE")
}

record(ai, "PLC:HTR:TM01:PLCADMINVMAJRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[0]")
  field(SCAN, "1 second")
  field(FLNK, "PLC:HTR:TM01:PLCADMINVMAJ")
}

record(calc, "PLC:HTR:TM01:PLCADMINVMAJ") {
  field(INPA, "PLC:HTR:TM01:PLCADMINVMAJRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
  field(PREC, "0")
  field(HIHI, "2")
  field(LOLO, "0")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
}

record(ai, "PLC:HTR:TM01:PLCADMINVMINRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[1]")
  field(SCAN, "1 second")
  field(FLNK, "PLC:HTR:TM01:PLCADMINVMIN")
}

record(calc, "PLC:HTR:TM01:PLCADMINVMIN") {
  field(INPA, "PLC:HTR:TM01:PLCADMINVMINRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
  field(PREC, "0")
  field(HIHI, "1")
  field(LOLO, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
}

record(ai, "PLC:HTR:TM01:PLCADMINVREVRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[2]")
  field(SCAN, "1 second")
  field(FLNK, "PLC:HTR:TM01:PLCADMINVREV")
}

record(calc, "PLC:HTR:TM01:PLCADMINVREV") {
  field(INPA, "PLC:HTR:TM01:PLCADMINVREVRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
  field(PREC, "0")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
}

record(ai, "PLC:HTR:TM01:PROGPLCATMAXRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[23]")
  field(SCAN, "1 second")
  field(FLNK, "PLC:HTR:TM01:PROGPLCATMAX")
}

record(ai, "PLC:HTR:TM01:PROGPLCATLSTRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[22]")
  field(FLNK, "PLC:HTR:TM01:PROGPLCATLST")
}

record(calc, "PLC:HTR:TM01:PROGPLCATLST") {
  field(INPA, "PLC:HTR:TM01:PROGPLCATLSTRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:HTR:TM01:PROGPLCATMAX") {
  field(INPA, "PLC:HTR:TM01:PROGPLCATMAXRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(stringin, "PLC:HTR:TM01:PLCADMINTAG") {
  field(PINI, "YES")
  field(VAL, "PLCADMIN_PLC_HTR_TM01")
}

record(ai, "PLC:HTR:TM01:TASKMAINTLSTRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[20]")
  field(FLNK, "PLC:HTR:TM01:TASKMAINTLST")
}

record(calc, "PLC:HTR:TM01:TASKMAINTLST") {
  field(INPA, "PLC:HTR:TM01:TASKMAINTLSTRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(ai, "PLC:HTR:TM01:TASKMAINTMAXRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[21]")
  field(FLNK, "PLC:HTR:TM01:TASKMAINTMAX")
  field(SCAN, "1 second")
}

record(calc, "PLC:HTR:TM01:TASKMAINTMAX") {
  field(INPA, "PLC:HTR:TM01:TASKMAINTMAXRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(ai, "PLC:HTR:TM01:PROG1TLSTRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[24]")
  field(FLNK, "PLC:HTR:TM01:PROG1TLST")
}

record(ai, "PLC:HTR:TM01:PROG1TMAXRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[25]")
  field(SCAN, "1 second")
  field(FLNK, "PLC:HTR:TM01:PROG1TMAX")
}

record(calc, "PLC:HTR:TM01:PROG1TLST") {
  field(INPA, "PLC:HTR:TM01:PROG1TLSTRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:HTR:TM01:PROG1TMAX") {
  field(INPA, "PLC:HTR:TM01:PROG1TMAXRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(ai, "PLC:HTR:TM01:PROG2TLSTRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[26]")
  field(FLNK, "PLC:HTR:TM01:PROG2TLST")
}

record(ai, "PLC:HTR:TM01:PROG2TMAXRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[27]")
  field(SCAN, "1 second")
  field(FLNK, "PLC:HTR:TM01:PROG2TMAX")
}

record(calc, "PLC:HTR:TM01:PROG2TLST") {
  field(INPA, "PLC:HTR:TM01:PROG2TLSTRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:HTR:TM01:PROG2TMAX") {
  field(INPA, "PLC:HTR:TM01:PROG2TMAXRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(ai, "PLC:HTR:TM01:PROG3TLSTRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[28]")
  field(FLNK, "PLC:HTR:TM01:PROG3TLST")
}

record(ai, "PLC:HTR:TM01:PROG3TMAXRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01[29]")
  field(SCAN, "1 second")
  field(FLNK, "PLC:HTR:TM01:PROG3TMAX")
}

record(calc, "PLC:HTR:TM01:PROG3TMAX") {
  field(INPA, "PLC:HTR:TM01:PROG3TMAXRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:HTR:TM01:PROG3TLST") {
  field(INPA, "PLC:HTR:TM01:PROG3TLSTRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:HTR:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:HTR:TM01:STATSUMY") {
  field(SCAN, "1 second")
  field(CALC, "A")
  field(INPA, "PLC:HTR:TM01:STATSUMY.SEVR")
  field(INPB, "PLC:HTR:TM01:HEARTBEATSUM MS")
  field(INPC, "PLC:HTR:TM01:FAULTSTATUS MS")
  field(INPD, "PLC:HTR:TM01:KEYSTATUS MS")
  field(INPE, "PLC:HTR:TM01:DEVICESTATUS MS")
  field(INPF, "PLC:HTR:TM01:VERSIONMAJOR MS")
  field(INPG, "PLC:HTR:TM01:VERSIONMINOR MS")
  field(INPH, "PLC:HTR:TM01:VERSIONREV MS")
}

#! Further lines contain data used by VisualDCT
#! View(935,906,0.9)
#! Record("PLC:HTR:TM01:STATUSRAW",2160,3987,0,1,"PLC:HTR:TM01:STATUSRAW")
#! Field("PLC:HTR:TM01:STATUSRAW.FLNK",16777215,1,"PLC:HTR:TM01:STATUSRAW.FLNK")
#! Link("PLC:HTR:TM01:STATUSRAW.FLNK","PLC:HTR:TM01:DEVICESTATUSRAW")
#! Field("PLC:HTR:TM01:STATUSRAW.VAL",16777215,1,"PLC:HTR:TM01:STATUSRAW.VAL")
#! Record("PLC:HTR:TM01:MODELRAW",4120,7,0,0,"PLC:HTR:TM01:MODELRAW")
#! Field("PLC:HTR:TM01:MODELRAW.FLNK",16777215,1,"PLC:HTR:TM01:MODELRAW.FLNK")
#! Link("PLC:HTR:TM01:MODELRAW.FLNK","PLC:HTR:TM01:MODELCALC")
#! Field("PLC:HTR:TM01:MODELRAW.VAL",16777215,0,"PLC:HTR:TM01:MODELRAW.VAL")
#! Record("PLC:HTR:TM01:UPTIMESEC",4280,1787,0,0,"PLC:HTR:TM01:UPTIMESEC")
#! Field("PLC:HTR:TM01:UPTIMESEC.FLNK",16777215,1,"PLC:HTR:TM01:UPTIMESEC.FLNK")
#! Link("PLC:HTR:TM01:UPTIMESEC.FLNK","PLC:HTR:TM01:UPTIMEHOURS")
#! Field("PLC:HTR:TM01:UPTIMESEC.VAL",16777215,1,"PLC:HTR:TM01:UPTIMESEC.VAL")
#! Record("PLC:HTR:TM01:UPTIMEHOURS",4540,1794,0,0,"PLC:HTR:TM01:UPTIMEHOURS")
#! Field("PLC:HTR:TM01:UPTIMEHOURS.INPA",16777215,0,"PLC:HTR:TM01:UPTIMEHOURS.INPA")
#! Link("PLC:HTR:TM01:UPTIMEHOURS.INPA","PLC:HTR:TM01:UPTIMESEC.VAL")
#! Field("PLC:HTR:TM01:UPTIMEHOURS.FLNK",16777215,1,"PLC:HTR:TM01:UPTIMEHOURS.FLNK")
#! Link("PLC:HTR:TM01:UPTIMEHOURS.FLNK","PLC:HTR:TM01:UPTIMEMINUTES")
#! Field("PLC:HTR:TM01:UPTIMEHOURS.INPB",16777215,0,"PLC:HTR:TM01:UPTIMEHOURS.INPB")
#! Link("PLC:HTR:TM01:UPTIMEHOURS.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:UPTIMEMINUTES",4580,2014,0,1,"PLC:HTR:TM01:UPTIMEMINUTES")
#! Field("PLC:HTR:TM01:UPTIMEMINUTES.INPA",16777215,0,"PLC:HTR:TM01:UPTIMEMINUTES.INPA")
#! Link("PLC:HTR:TM01:UPTIMEMINUTES.INPA","PLC:HTR:TM01:UPTIMESEC.VAL")
#! Field("PLC:HTR:TM01:UPTIMEMINUTES.FLNK",16777215,1,"PLC:HTR:TM01:UPTIMEMINUTES.FLNK")
#! Link("PLC:HTR:TM01:UPTIMEMINUTES.FLNK","PLC:HTR:TM01:UPTIMESECONDS")
#! Field("PLC:HTR:TM01:UPTIMEMINUTES.INPB",16777215,0,"PLC:HTR:TM01:UPTIMEMINUTES.INPB")
#! Link("PLC:HTR:TM01:UPTIMEMINUTES.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:UPTIMESECONDS",4620,2227,0,1,"PLC:HTR:TM01:UPTIMESECONDS")
#! Field("PLC:HTR:TM01:UPTIMESECONDS.INPA",16777215,0,"PLC:HTR:TM01:UPTIMESECONDS.INPA")
#! Link("PLC:HTR:TM01:UPTIMESECONDS.INPA","PLC:HTR:TM01:UPTIMESEC.VAL")
#! Field("PLC:HTR:TM01:UPTIMESECONDS.INPB",16777215,0,"PLC:HTR:TM01:UPTIMESECONDS.INPB")
#! Link("PLC:HTR:TM01:UPTIMESECONDS.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:HEARTBEATRAW",60,79,0,1,"PLC:HTR:TM01:HEARTBEATRAW")
#! Field("PLC:HTR:TM01:HEARTBEATRAW.FLNK",16777215,1,"PLC:HTR:TM01:HEARTBEATRAW.FLNK")
#! Link("PLC:HTR:TM01:HEARTBEATRAW.FLNK","PLC:HTR:TM01:COMMLINK")
#! Field("PLC:HTR:TM01:HEARTBEATRAW.SEVR",16777215,1,"PLC:HTR:TM01:HEARTBEATRAW.SEVR")
#! Field("PLC:HTR:TM01:HEARTBEATRAW.VAL",16777215,1,"PLC:HTR:TM01:HEARTBEATRAW.VAL")
#! Record("PLC:HTR:TM01:MODEL",4640,54,0,0,"PLC:HTR:TM01:MODEL")
#! Field("PLC:HTR:TM01:MODEL.INP",16777215,0,"PLC:HTR:TM01:MODEL.INP")
#! Link("PLC:HTR:TM01:MODEL.INP","PLC:HTR:TM01:MODELCALC.VAL")
#! Record("PLC:HTR:TM01:FWVERSIONRAW",4180,227,0,0,"PLC:HTR:TM01:FWVERSIONRAW")
#! Field("PLC:HTR:TM01:FWVERSIONRAW.FLNK",16777215,1,"PLC:HTR:TM01:FWVERSIONRAW.FLNK")
#! Link("PLC:HTR:TM01:FWVERSIONRAW.FLNK","PLC:HTR:TM01:FWVERSIONMAJ")
#! Field("PLC:HTR:TM01:FWVERSIONRAW.VAL",16777215,1,"PLC:HTR:TM01:FWVERSIONRAW.VAL")
#! Record("PLC:HTR:TM01:FWVERSIONMAJ",4460,247,0,0,"PLC:HTR:TM01:FWVERSIONMAJ")
#! Field("PLC:HTR:TM01:FWVERSIONMAJ.FLNK",16777215,1,"PLC:HTR:TM01:FWVERSIONMAJ.FLNK")
#! Link("PLC:HTR:TM01:FWVERSIONMAJ.FLNK","PLC:HTR:TM01:FWVERSIONMIN")
#! Field("PLC:HTR:TM01:FWVERSIONMAJ.INPA",16777215,0,"PLC:HTR:TM01:FWVERSIONMAJ.INPA")
#! Link("PLC:HTR:TM01:FWVERSIONMAJ.INPA","PLC:HTR:TM01:FWVERSIONRAW.VAL")
#! Field("PLC:HTR:TM01:FWVERSIONMAJ.INPB",16777215,0,"PLC:HTR:TM01:FWVERSIONMAJ.INPB")
#! Link("PLC:HTR:TM01:FWVERSIONMAJ.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:FWVERSIONMIN",4720,322,0,0,"PLC:HTR:TM01:FWVERSIONMIN")
#! Field("PLC:HTR:TM01:FWVERSIONMIN.INPA",16777215,0,"PLC:HTR:TM01:FWVERSIONMIN.INPA")
#! Link("PLC:HTR:TM01:FWVERSIONMIN.INPA","PLC:HTR:TM01:FWVERSIONRAW.VAL")
#! Field("PLC:HTR:TM01:FWVERSIONMIN.INPB",16777215,0,"PLC:HTR:TM01:FWVERSIONMIN.INPB")
#! Link("PLC:HTR:TM01:FWVERSIONMIN.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:MODELCALC",4380,27,0,0,"PLC:HTR:TM01:MODELCALC")
#! Field("PLC:HTR:TM01:MODELCALC.INPA",16777215,0,"PLC:HTR:TM01:MODELCALC.INPA")
#! Link("PLC:HTR:TM01:MODELCALC.INPA","PLC:HTR:TM01:MODELRAW.VAL")
#! Field("PLC:HTR:TM01:MODELCALC.FLNK",16777215,1,"PLC:HTR:TM01:MODELCALC.FLNK")
#! Link("PLC:HTR:TM01:MODELCALC.FLNK","PLC:HTR:TM01:MODEL")
#! Field("PLC:HTR:TM01:MODELCALC.VAL",16777215,0,"PLC:HTR:TM01:MODELCALC.VAL")
#! Field("PLC:HTR:TM01:MODELCALC.INPB",16777215,0,"PLC:HTR:TM01:MODELCALC.INPB")
#! Link("PLC:HTR:TM01:MODELCALC.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:DEVICESTATUSCALC",2760,3930,0,0,"PLC:HTR:TM01:DEVICESTATUSCALC")
#! Field("PLC:HTR:TM01:DEVICESTATUSCALC.FLNK",16777215,1,"PLC:HTR:TM01:DEVICESTATUSCALC.FLNK")
#! Link("PLC:HTR:TM01:DEVICESTATUSCALC.FLNK","PLC:HTR:TM01:DEVICESTATUS")
#! Field("PLC:HTR:TM01:DEVICESTATUSCALC.INPA",16777215,0,"PLC:HTR:TM01:DEVICESTATUSCALC.INPA")
#! Link("PLC:HTR:TM01:DEVICESTATUSCALC.INPA","PLC:HTR:TM01:DEVICESTATUSRAW.VAL")
#! Field("PLC:HTR:TM01:DEVICESTATUSCALC.VAL",16777215,1,"PLC:HTR:TM01:DEVICESTATUSCALC.VAL")
#! Record("PLC:HTR:TM01:DEVICESTATUSRAW",2480,3974,0,0,"PLC:HTR:TM01:DEVICESTATUSRAW")
#! Field("PLC:HTR:TM01:DEVICESTATUSRAW.FLNK",16777215,1,"PLC:HTR:TM01:DEVICESTATUSRAW.FLNK")
#! Link("PLC:HTR:TM01:DEVICESTATUSRAW.FLNK","PLC:HTR:TM01:DEVICESTATUSCALC")
#! Field("PLC:HTR:TM01:DEVICESTATUSRAW.INPA",16777215,0,"PLC:HTR:TM01:DEVICESTATUSRAW.INPA")
#! Link("PLC:HTR:TM01:DEVICESTATUSRAW.INPA","PLC:HTR:TM01:STATUSRAW.VAL")
#! Field("PLC:HTR:TM01:DEVICESTATUSRAW.VAL",16777215,1,"PLC:HTR:TM01:DEVICESTATUSRAW.VAL")
#! Field("PLC:HTR:TM01:DEVICESTATUSRAW.INPC",16777215,1,"PLC:HTR:TM01:DEVICESTATUSRAW.INPC")
#! Link("PLC:HTR:TM01:DEVICESTATUSRAW.INPC","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:DEVICESTATUS",3040,3926,0,0,"PLC:HTR:TM01:DEVICESTATUS")
#! Field("PLC:HTR:TM01:DEVICESTATUS.INP",16777215,0,"PLC:HTR:TM01:DEVICESTATUS.INP")
#! Link("PLC:HTR:TM01:DEVICESTATUS.INP","PLC:HTR:TM01:DEVICESTATUSCALC.VAL")
#! Field("PLC:HTR:TM01:DEVICESTATUS.FLNK",16777215,0,"PLC:HTR:TM01:DEVICESTATUS.FLNK")
#! Link("PLC:HTR:TM01:DEVICESTATUS.FLNK","PLC:HTR:TM01:FAULTSTATUSRAW")
#! Field("PLC:HTR:TM01:DEVICESTATUS.VAL",16777215,0,"PLC:HTR:TM01:DEVICESTATUS.VAL")
#! Record("PLC:HTR:TM01:FAULTSTATUSRAW",2480,4274,0,1,"PLC:HTR:TM01:FAULTSTATUSRAW")
#! Field("PLC:HTR:TM01:FAULTSTATUSRAW.FLNK",16777215,1,"PLC:HTR:TM01:FAULTSTATUSRAW.FLNK")
#! Link("PLC:HTR:TM01:FAULTSTATUSRAW.FLNK","PLC:HTR:TM01:FAULTSTATUSCALC")
#! Field("PLC:HTR:TM01:FAULTSTATUSRAW.INPA",16777215,0,"PLC:HTR:TM01:FAULTSTATUSRAW.INPA")
#! Link("PLC:HTR:TM01:FAULTSTATUSRAW.INPA","PLC:HTR:TM01:STATUSRAW.VAL")
#! Field("PLC:HTR:TM01:FAULTSTATUSRAW.VAL",16777215,1,"PLC:HTR:TM01:FAULTSTATUSRAW.VAL")
#! Field("PLC:HTR:TM01:FAULTSTATUSRAW.INPC",16777215,1,"PLC:HTR:TM01:FAULTSTATUSRAW.INPC")
#! Link("PLC:HTR:TM01:FAULTSTATUSRAW.INPC","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:FAULTSTATUSCALC",2760,4225,0,0,"PLC:HTR:TM01:FAULTSTATUSCALC")
#! Field("PLC:HTR:TM01:FAULTSTATUSCALC.FLNK",16777215,1,"PLC:HTR:TM01:FAULTSTATUSCALC.FLNK")
#! Link("PLC:HTR:TM01:FAULTSTATUSCALC.FLNK","PLC:HTR:TM01:FAULTSTATUS")
#! Field("PLC:HTR:TM01:FAULTSTATUSCALC.INPA",16777215,0,"PLC:HTR:TM01:FAULTSTATUSCALC.INPA")
#! Link("PLC:HTR:TM01:FAULTSTATUSCALC.INPA","PLC:HTR:TM01:FAULTSTATUSRAW.VAL")
#! Field("PLC:HTR:TM01:FAULTSTATUSCALC.VAL",16777215,1,"PLC:HTR:TM01:FAULTSTATUSCALC.VAL")
#! Record("PLC:HTR:TM01:FAULTSTATUS",3040,4254,0,0,"PLC:HTR:TM01:FAULTSTATUS")
#! Field("PLC:HTR:TM01:FAULTSTATUS.INP",16777215,0,"PLC:HTR:TM01:FAULTSTATUS.INP")
#! Link("PLC:HTR:TM01:FAULTSTATUS.INP","PLC:HTR:TM01:FAULTSTATUSCALC.VAL")
#! Field("PLC:HTR:TM01:FAULTSTATUS.FLNK",16777215,0,"PLC:HTR:TM01:FAULTSTATUS.FLNK")
#! Link("PLC:HTR:TM01:FAULTSTATUS.FLNK","PLC:HTR:TM01:KEYSTATUSRAW")
#! Field("PLC:HTR:TM01:FAULTSTATUS.VAL",16777215,0,"PLC:HTR:TM01:FAULTSTATUS.VAL")
#! Record("PLC:HTR:TM01:KEYSTATUSRAW",2480,4594,0,1,"PLC:HTR:TM01:KEYSTATUSRAW")
#! Field("PLC:HTR:TM01:KEYSTATUSRAW.FLNK",16777215,1,"PLC:HTR:TM01:KEYSTATUSRAW.FLNK")
#! Link("PLC:HTR:TM01:KEYSTATUSRAW.FLNK","PLC:HTR:TM01:KEYSTATUSCALC")
#! Field("PLC:HTR:TM01:KEYSTATUSRAW.INPA",16777215,0,"PLC:HTR:TM01:KEYSTATUSRAW.INPA")
#! Link("PLC:HTR:TM01:KEYSTATUSRAW.INPA","PLC:HTR:TM01:STATUSRAW.VAL")
#! Field("PLC:HTR:TM01:KEYSTATUSRAW.VAL",16777215,1,"PLC:HTR:TM01:KEYSTATUSRAW.VAL")
#! Field("PLC:HTR:TM01:KEYSTATUSRAW.INPC",16777215,1,"PLC:HTR:TM01:KEYSTATUSRAW.INPC")
#! Link("PLC:HTR:TM01:KEYSTATUSRAW.INPC","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:KEYSTATUSCALC",2760,4579,0,0,"PLC:HTR:TM01:KEYSTATUSCALC")
#! Field("PLC:HTR:TM01:KEYSTATUSCALC.FLNK",16777215,1,"PLC:HTR:TM01:KEYSTATUSCALC.FLNK")
#! Link("PLC:HTR:TM01:KEYSTATUSCALC.FLNK","PLC:HTR:TM01:KEYSTATUS")
#! Field("PLC:HTR:TM01:KEYSTATUSCALC.INPA",16777215,0,"PLC:HTR:TM01:KEYSTATUSCALC.INPA")
#! Link("PLC:HTR:TM01:KEYSTATUSCALC.INPA","PLC:HTR:TM01:KEYSTATUSRAW.VAL")
#! Field("PLC:HTR:TM01:KEYSTATUSCALC.VAL",16777215,1,"PLC:HTR:TM01:KEYSTATUSCALC.VAL")
#! Record("PLC:HTR:TM01:KEYSTATUS",3040,4577,0,0,"PLC:HTR:TM01:KEYSTATUS")
#! Field("PLC:HTR:TM01:KEYSTATUS.INP",16777215,0,"PLC:HTR:TM01:KEYSTATUS.INP")
#! Link("PLC:HTR:TM01:KEYSTATUS.INP","PLC:HTR:TM01:KEYSTATUSCALC.VAL")
#! Field("PLC:HTR:TM01:KEYSTATUS.VAL",16777215,0,"PLC:HTR:TM01:KEYSTATUS.VAL")
#! Record("PLC:HTR:TM01:MAJORFAULTRAW",4020,2427,0,0,"PLC:HTR:TM01:MAJORFAULTRAW")
#! Field("PLC:HTR:TM01:MAJORFAULTRAW.FLNK",16777215,1,"PLC:HTR:TM01:MAJORFAULTRAW.FLNK")
#! Link("PLC:HTR:TM01:MAJORFAULTRAW.FLNK","PLC:HTR:TM01:FAULTPOWERCALC")
#! Field("PLC:HTR:TM01:MAJORFAULTRAW.VAL",16777215,1,"PLC:HTR:TM01:MAJORFAULTRAW.VAL")
#! Record("PLC:HTR:TM01:MINORFAULTRAW",4000,2622,0,0,"PLC:HTR:TM01:MINORFAULTRAW")
#! Field("PLC:HTR:TM01:MINORFAULTRAW.VAL",16777215,1,"PLC:HTR:TM01:MINORFAULTRAW.VAL")
#! Record("PLC:HTR:TM01:FAULTPOWERCALC",4360,2559,0,0,"PLC:HTR:TM01:FAULTPOWERCALC")
#! Field("PLC:HTR:TM01:FAULTPOWERCALC.INPA",16777215,0,"PLC:HTR:TM01:FAULTPOWERCALC.INPA")
#! Link("PLC:HTR:TM01:FAULTPOWERCALC.INPA","PLC:HTR:TM01:MAJORFAULTRAW.VAL")
#! Field("PLC:HTR:TM01:FAULTPOWERCALC.INPB",16777215,0,"PLC:HTR:TM01:FAULTPOWERCALC.INPB")
#! Link("PLC:HTR:TM01:FAULTPOWERCALC.INPB","PLC:HTR:TM01:MINORFAULTRAW.VAL")
#! Field("PLC:HTR:TM01:FAULTPOWERCALC.FLNK",16777215,1,"PLC:HTR:TM01:FAULTPOWERCALC.FLNK")
#! Link("PLC:HTR:TM01:FAULTPOWERCALC.FLNK","PLC:HTR:TM01:FAULTPOWER")
#! Field("PLC:HTR:TM01:FAULTPOWERCALC.VAL",16777215,1,"PLC:HTR:TM01:FAULTPOWERCALC.VAL")
#! Field("PLC:HTR:TM01:FAULTPOWERCALC.INPD",16777215,0,"PLC:HTR:TM01:FAULTPOWERCALC.INPD")
#! Link("PLC:HTR:TM01:FAULTPOWERCALC.INPD","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:FAULTPOWER",4640,2590,0,0,"PLC:HTR:TM01:FAULTPOWER")
#! Field("PLC:HTR:TM01:FAULTPOWER.INP",16777215,0,"PLC:HTR:TM01:FAULTPOWER.INP")
#! Link("PLC:HTR:TM01:FAULTPOWER.INP","PLC:HTR:TM01:FAULTPOWERCALC.VAL")
#! Field("PLC:HTR:TM01:FAULTPOWER.FLNK",16777215,0,"PLC:HTR:TM01:FAULTPOWER.FLNK")
#! Link("PLC:HTR:TM01:FAULTPOWER.FLNK","PLC:HTR:TM01:FAULTIOCALC")
#! Record("PLC:HTR:TM01:FAULTIOCALC",4360,2799,0,1,"PLC:HTR:TM01:FAULTIOCALC")
#! Field("PLC:HTR:TM01:FAULTIOCALC.FLNK",16777215,1,"PLC:HTR:TM01:FAULTIOCALC.FLNK")
#! Link("PLC:HTR:TM01:FAULTIOCALC.FLNK","PLC:HTR:TM01:FAULTIO")
#! Field("PLC:HTR:TM01:FAULTIOCALC.INPA",16777215,0,"PLC:HTR:TM01:FAULTIOCALC.INPA")
#! Link("PLC:HTR:TM01:FAULTIOCALC.INPA","PLC:HTR:TM01:MAJORFAULTRAW.VAL")
#! Field("PLC:HTR:TM01:FAULTIOCALC.INPB",16777215,0,"PLC:HTR:TM01:FAULTIOCALC.INPB")
#! Link("PLC:HTR:TM01:FAULTIOCALC.INPB","PLC:HTR:TM01:MINORFAULTRAW.VAL")
#! Field("PLC:HTR:TM01:FAULTIOCALC.VAL",16777215,1,"PLC:HTR:TM01:FAULTIOCALC.VAL")
#! Field("PLC:HTR:TM01:FAULTIOCALC.INPD",16777215,0,"PLC:HTR:TM01:FAULTIOCALC.INPD")
#! Link("PLC:HTR:TM01:FAULTIOCALC.INPD","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:FAULTIO",4640,2830,0,0,"PLC:HTR:TM01:FAULTIO")
#! Field("PLC:HTR:TM01:FAULTIO.INP",16777215,0,"PLC:HTR:TM01:FAULTIO.INP")
#! Link("PLC:HTR:TM01:FAULTIO.INP","PLC:HTR:TM01:FAULTIOCALC.VAL")
#! Field("PLC:HTR:TM01:FAULTIO.FLNK",16777215,0,"PLC:HTR:TM01:FAULTIO.FLNK")
#! Link("PLC:HTR:TM01:FAULTIO.FLNK","PLC:HTR:TM01:FAULTPROGRAMCALC")
#! Record("PLC:HTR:TM01:FAULTPROGRAMCALC",4360,3039,0,1,"PLC:HTR:TM01:FAULTPROGRAMCALC")
#! Field("PLC:HTR:TM01:FAULTPROGRAMCALC.FLNK",16777215,1,"PLC:HTR:TM01:FAULTPROGRAMCALC.FLNK")
#! Link("PLC:HTR:TM01:FAULTPROGRAMCALC.FLNK","PLC:HTR:TM01:FAULTPROGRAM")
#! Field("PLC:HTR:TM01:FAULTPROGRAMCALC.INPA",16777215,0,"PLC:HTR:TM01:FAULTPROGRAMCALC.INPA")
#! Link("PLC:HTR:TM01:FAULTPROGRAMCALC.INPA","PLC:HTR:TM01:MAJORFAULTRAW.VAL")
#! Field("PLC:HTR:TM01:FAULTPROGRAMCALC.INPB",16777215,0,"PLC:HTR:TM01:FAULTPROGRAMCALC.INPB")
#! Link("PLC:HTR:TM01:FAULTPROGRAMCALC.INPB","PLC:HTR:TM01:MINORFAULTRAW.VAL")
#! Field("PLC:HTR:TM01:FAULTPROGRAMCALC.VAL",16777215,1,"PLC:HTR:TM01:FAULTPROGRAMCALC.VAL")
#! Field("PLC:HTR:TM01:FAULTPROGRAMCALC.INPD",16777215,0,"PLC:HTR:TM01:FAULTPROGRAMCALC.INPD")
#! Link("PLC:HTR:TM01:FAULTPROGRAMCALC.INPD","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:FAULTPROGRAM",4640,3070,0,0,"PLC:HTR:TM01:FAULTPROGRAM")
#! Field("PLC:HTR:TM01:FAULTPROGRAM.INP",16777215,0,"PLC:HTR:TM01:FAULTPROGRAM.INP")
#! Link("PLC:HTR:TM01:FAULTPROGRAM.INP","PLC:HTR:TM01:FAULTPROGRAMCALC.VAL")
#! Field("PLC:HTR:TM01:FAULTPROGRAM.FLNK",16777215,0,"PLC:HTR:TM01:FAULTPROGRAM.FLNK")
#! Link("PLC:HTR:TM01:FAULTPROGRAM.FLNK","PLC:HTR:TM01:FAULTFLTHNDLCALC")
#! Record("PLC:HTR:TM01:FAULTFLTHNDL",4640,3310,0,0,"PLC:HTR:TM01:FAULTFLTHNDL")
#! Field("PLC:HTR:TM01:FAULTFLTHNDL.INP",16777215,0,"PLC:HTR:TM01:FAULTFLTHNDL.INP")
#! Link("PLC:HTR:TM01:FAULTFLTHNDL.INP","PLC:HTR:TM01:FAULTFLTHNDLCALC.VAL")
#! Field("PLC:HTR:TM01:FAULTFLTHNDL.FLNK",16777215,0,"PLC:HTR:TM01:FAULTFLTHNDL.FLNK")
#! Link("PLC:HTR:TM01:FAULTFLTHNDL.FLNK","PLC:HTR:TM01:FAULTWTCHDOGCALC")
#! Record("PLC:HTR:TM01:FAULTFLTHNDLCALC",4360,3279,0,1,"PLC:HTR:TM01:FAULTFLTHNDLCALC")
#! Field("PLC:HTR:TM01:FAULTFLTHNDLCALC.FLNK",16777215,1,"PLC:HTR:TM01:FAULTFLTHNDLCALC.FLNK")
#! Link("PLC:HTR:TM01:FAULTFLTHNDLCALC.FLNK","PLC:HTR:TM01:FAULTFLTHNDL")
#! Field("PLC:HTR:TM01:FAULTFLTHNDLCALC.INPA",16777215,0,"PLC:HTR:TM01:FAULTFLTHNDLCALC.INPA")
#! Link("PLC:HTR:TM01:FAULTFLTHNDLCALC.INPA","PLC:HTR:TM01:MAJORFAULTRAW.VAL")
#! Field("PLC:HTR:TM01:FAULTFLTHNDLCALC.INPB",16777215,0,"PLC:HTR:TM01:FAULTFLTHNDLCALC.INPB")
#! Link("PLC:HTR:TM01:FAULTFLTHNDLCALC.INPB","PLC:HTR:TM01:MINORFAULTRAW.VAL")
#! Field("PLC:HTR:TM01:FAULTFLTHNDLCALC.VAL",16777215,1,"PLC:HTR:TM01:FAULTFLTHNDLCALC.VAL")
#! Field("PLC:HTR:TM01:FAULTFLTHNDLCALC.INPD",16777215,0,"PLC:HTR:TM01:FAULTFLTHNDLCALC.INPD")
#! Link("PLC:HTR:TM01:FAULTFLTHNDLCALC.INPD","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:FAULTWTCHDOGCALC",4360,3499,0,1,"PLC:HTR:TM01:FAULTWTCHDOGCALC")
#! Field("PLC:HTR:TM01:FAULTWTCHDOGCALC.FLNK",16777215,1,"PLC:HTR:TM01:FAULTWTCHDOGCALC.FLNK")
#! Link("PLC:HTR:TM01:FAULTWTCHDOGCALC.FLNK","PLC:HTR:TM01:FAULTWTCHDOG")
#! Field("PLC:HTR:TM01:FAULTWTCHDOGCALC.INPA",16777215,0,"PLC:HTR:TM01:FAULTWTCHDOGCALC.INPA")
#! Link("PLC:HTR:TM01:FAULTWTCHDOGCALC.INPA","PLC:HTR:TM01:MAJORFAULTRAW.VAL")
#! Field("PLC:HTR:TM01:FAULTWTCHDOGCALC.INPB",16777215,0,"PLC:HTR:TM01:FAULTWTCHDOGCALC.INPB")
#! Link("PLC:HTR:TM01:FAULTWTCHDOGCALC.INPB","PLC:HTR:TM01:MINORFAULTRAW.VAL")
#! Field("PLC:HTR:TM01:FAULTWTCHDOGCALC.VAL",16777215,1,"PLC:HTR:TM01:FAULTWTCHDOGCALC.VAL")
#! Field("PLC:HTR:TM01:FAULTWTCHDOGCALC.INPD",16777215,0,"PLC:HTR:TM01:FAULTWTCHDOGCALC.INPD")
#! Link("PLC:HTR:TM01:FAULTWTCHDOGCALC.INPD","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:FAULTWTCHDOG",4640,3530,0,0,"PLC:HTR:TM01:FAULTWTCHDOG")
#! Field("PLC:HTR:TM01:FAULTWTCHDOG.INP",16777215,0,"PLC:HTR:TM01:FAULTWTCHDOG.INP")
#! Link("PLC:HTR:TM01:FAULTWTCHDOG.INP","PLC:HTR:TM01:FAULTWTCHDOGCALC.VAL")
#! Field("PLC:HTR:TM01:FAULTWTCHDOG.FLNK",16777215,0,"PLC:HTR:TM01:FAULTWTCHDOG.FLNK")
#! Link("PLC:HTR:TM01:FAULTWTCHDOG.FLNK","PLC:HTR:TM01:FAULTSTACKCALC")
#! Record("PLC:HTR:TM01:FAULTSTACKCALC",4360,3719,0,1,"PLC:HTR:TM01:FAULTSTACKCALC")
#! Field("PLC:HTR:TM01:FAULTSTACKCALC.FLNK",16777215,1,"PLC:HTR:TM01:FAULTSTACKCALC.FLNK")
#! Link("PLC:HTR:TM01:FAULTSTACKCALC.FLNK","PLC:HTR:TM01:FAULTSTACK")
#! Field("PLC:HTR:TM01:FAULTSTACKCALC.INPA",16777215,0,"PLC:HTR:TM01:FAULTSTACKCALC.INPA")
#! Link("PLC:HTR:TM01:FAULTSTACKCALC.INPA","PLC:HTR:TM01:MAJORFAULTRAW.VAL")
#! Field("PLC:HTR:TM01:FAULTSTACKCALC.INPB",16777215,0,"PLC:HTR:TM01:FAULTSTACKCALC.INPB")
#! Link("PLC:HTR:TM01:FAULTSTACKCALC.INPB","PLC:HTR:TM01:MINORFAULTRAW.VAL")
#! Field("PLC:HTR:TM01:FAULTSTACKCALC.VAL",16777215,1,"PLC:HTR:TM01:FAULTSTACKCALC.VAL")
#! Field("PLC:HTR:TM01:FAULTSTACKCALC.INPD",16777215,0,"PLC:HTR:TM01:FAULTSTACKCALC.INPD")
#! Link("PLC:HTR:TM01:FAULTSTACKCALC.INPD","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:FAULTSTACK",4640,3750,0,0,"PLC:HTR:TM01:FAULTSTACK")
#! Field("PLC:HTR:TM01:FAULTSTACK.INP",16777215,0,"PLC:HTR:TM01:FAULTSTACK.INP")
#! Link("PLC:HTR:TM01:FAULTSTACK.INP","PLC:HTR:TM01:FAULTSTACKCALC.VAL")
#! Field("PLC:HTR:TM01:FAULTSTACK.FLNK",16777215,0,"PLC:HTR:TM01:FAULTSTACK.FLNK")
#! Link("PLC:HTR:TM01:FAULTSTACK.FLNK","PLC:HTR:TM01:FAULTMODECHGCALC")
#! Record("PLC:HTR:TM01:FAULTMODECHGCALC",4360,3939,0,1,"PLC:HTR:TM01:FAULTMODECHGCALC")
#! Field("PLC:HTR:TM01:FAULTMODECHGCALC.FLNK",16777215,1,"PLC:HTR:TM01:FAULTMODECHGCALC.FLNK")
#! Link("PLC:HTR:TM01:FAULTMODECHGCALC.FLNK","PLC:HTR:TM01:FAULTMODECHG")
#! Field("PLC:HTR:TM01:FAULTMODECHGCALC.INPA",16777215,0,"PLC:HTR:TM01:FAULTMODECHGCALC.INPA")
#! Link("PLC:HTR:TM01:FAULTMODECHGCALC.INPA","PLC:HTR:TM01:MAJORFAULTRAW.VAL")
#! Field("PLC:HTR:TM01:FAULTMODECHGCALC.INPB",16777215,0,"PLC:HTR:TM01:FAULTMODECHGCALC.INPB")
#! Link("PLC:HTR:TM01:FAULTMODECHGCALC.INPB","PLC:HTR:TM01:MINORFAULTRAW.VAL")
#! Field("PLC:HTR:TM01:FAULTMODECHGCALC.VAL",16777215,1,"PLC:HTR:TM01:FAULTMODECHGCALC.VAL")
#! Field("PLC:HTR:TM01:FAULTMODECHGCALC.INPD",16777215,0,"PLC:HTR:TM01:FAULTMODECHGCALC.INPD")
#! Link("PLC:HTR:TM01:FAULTMODECHGCALC.INPD","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:FAULTMODECHG",4640,3970,0,0,"PLC:HTR:TM01:FAULTMODECHG")
#! Field("PLC:HTR:TM01:FAULTMODECHG.INP",16777215,0,"PLC:HTR:TM01:FAULTMODECHG.INP")
#! Link("PLC:HTR:TM01:FAULTMODECHG.INP","PLC:HTR:TM01:FAULTMODECHGCALC.VAL")
#! Field("PLC:HTR:TM01:FAULTMODECHG.FLNK",16777215,0,"PLC:HTR:TM01:FAULTMODECHG.FLNK")
#! Link("PLC:HTR:TM01:FAULTMODECHG.FLNK","PLC:HTR:TM01:FAULTSERIALCALC")
#! Record("PLC:HTR:TM01:FAULTSERIALCALC",4360,4159,0,1,"PLC:HTR:TM01:FAULTSERIALCALC")
#! Field("PLC:HTR:TM01:FAULTSERIALCALC.FLNK",16777215,1,"PLC:HTR:TM01:FAULTSERIALCALC.FLNK")
#! Link("PLC:HTR:TM01:FAULTSERIALCALC.FLNK","PLC:HTR:TM01:FAULTSERIAL")
#! Field("PLC:HTR:TM01:FAULTSERIALCALC.INPA",16777215,0,"PLC:HTR:TM01:FAULTSERIALCALC.INPA")
#! Link("PLC:HTR:TM01:FAULTSERIALCALC.INPA","PLC:HTR:TM01:MAJORFAULTRAW.VAL")
#! Field("PLC:HTR:TM01:FAULTSERIALCALC.INPB",16777215,0,"PLC:HTR:TM01:FAULTSERIALCALC.INPB")
#! Link("PLC:HTR:TM01:FAULTSERIALCALC.INPB","PLC:HTR:TM01:MINORFAULTRAW.VAL")
#! Field("PLC:HTR:TM01:FAULTSERIALCALC.VAL",16777215,1,"PLC:HTR:TM01:FAULTSERIALCALC.VAL")
#! Field("PLC:HTR:TM01:FAULTSERIALCALC.INPD",16777215,0,"PLC:HTR:TM01:FAULTSERIALCALC.INPD")
#! Link("PLC:HTR:TM01:FAULTSERIALCALC.INPD","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:FAULTSERIAL",4640,4190,0,0,"PLC:HTR:TM01:FAULTSERIAL")
#! Field("PLC:HTR:TM01:FAULTSERIAL.INP",16777215,0,"PLC:HTR:TM01:FAULTSERIAL.INP")
#! Link("PLC:HTR:TM01:FAULTSERIAL.INP","PLC:HTR:TM01:FAULTSERIALCALC.VAL")
#! Field("PLC:HTR:TM01:FAULTSERIAL.FLNK",16777215,0,"PLC:HTR:TM01:FAULTSERIAL.FLNK")
#! Link("PLC:HTR:TM01:FAULTSERIAL.FLNK","PLC:HTR:TM01:FAULTBATTERYCALC")
#! Record("PLC:HTR:TM01:FAULTBATTERY",4640,4410,0,0,"PLC:HTR:TM01:FAULTBATTERY")
#! Field("PLC:HTR:TM01:FAULTBATTERY.INP",16777215,0,"PLC:HTR:TM01:FAULTBATTERY.INP")
#! Link("PLC:HTR:TM01:FAULTBATTERY.INP","PLC:HTR:TM01:FAULTBATTERYCALC.VAL")
#! Field("PLC:HTR:TM01:FAULTBATTERY.FLNK",16777215,0,"PLC:HTR:TM01:FAULTBATTERY.FLNK")
#! Link("PLC:HTR:TM01:FAULTBATTERY.FLNK","PLC:HTR:TM01:FAULTMOTIONCALC")
#! Record("PLC:HTR:TM01:FAULTBATTERYCALC",4360,4379,0,1,"PLC:HTR:TM01:FAULTBATTERYCALC")
#! Field("PLC:HTR:TM01:FAULTBATTERYCALC.FLNK",16777215,1,"PLC:HTR:TM01:FAULTBATTERYCALC.FLNK")
#! Link("PLC:HTR:TM01:FAULTBATTERYCALC.FLNK","PLC:HTR:TM01:FAULTBATTERY")
#! Field("PLC:HTR:TM01:FAULTBATTERYCALC.INPA",16777215,0,"PLC:HTR:TM01:FAULTBATTERYCALC.INPA")
#! Link("PLC:HTR:TM01:FAULTBATTERYCALC.INPA","PLC:HTR:TM01:MAJORFAULTRAW.VAL")
#! Field("PLC:HTR:TM01:FAULTBATTERYCALC.INPB",16777215,0,"PLC:HTR:TM01:FAULTBATTERYCALC.INPB")
#! Link("PLC:HTR:TM01:FAULTBATTERYCALC.INPB","PLC:HTR:TM01:MINORFAULTRAW.VAL")
#! Field("PLC:HTR:TM01:FAULTBATTERYCALC.VAL",16777215,1,"PLC:HTR:TM01:FAULTBATTERYCALC.VAL")
#! Field("PLC:HTR:TM01:FAULTBATTERYCALC.INPD",16777215,0,"PLC:HTR:TM01:FAULTBATTERYCALC.INPD")
#! Link("PLC:HTR:TM01:FAULTBATTERYCALC.INPD","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:FAULTMOTIONCALC",4360,4599,0,1,"PLC:HTR:TM01:FAULTMOTIONCALC")
#! Field("PLC:HTR:TM01:FAULTMOTIONCALC.FLNK",16777215,1,"PLC:HTR:TM01:FAULTMOTIONCALC.FLNK")
#! Link("PLC:HTR:TM01:FAULTMOTIONCALC.FLNK","PLC:HTR:TM01:FAULTMOTION")
#! Field("PLC:HTR:TM01:FAULTMOTIONCALC.INPA",16777215,0,"PLC:HTR:TM01:FAULTMOTIONCALC.INPA")
#! Link("PLC:HTR:TM01:FAULTMOTIONCALC.INPA","PLC:HTR:TM01:MAJORFAULTRAW.VAL")
#! Field("PLC:HTR:TM01:FAULTMOTIONCALC.INPB",16777215,0,"PLC:HTR:TM01:FAULTMOTIONCALC.INPB")
#! Link("PLC:HTR:TM01:FAULTMOTIONCALC.INPB","PLC:HTR:TM01:MINORFAULTRAW.VAL")
#! Field("PLC:HTR:TM01:FAULTMOTIONCALC.VAL",16777215,1,"PLC:HTR:TM01:FAULTMOTIONCALC.VAL")
#! Field("PLC:HTR:TM01:FAULTMOTIONCALC.INPD",16777215,0,"PLC:HTR:TM01:FAULTMOTIONCALC.INPD")
#! Link("PLC:HTR:TM01:FAULTMOTIONCALC.INPD","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:FAULTMOTION",4640,4645,0,0,"PLC:HTR:TM01:FAULTMOTION")
#! Field("PLC:HTR:TM01:FAULTMOTION.INP",16777215,0,"PLC:HTR:TM01:FAULTMOTION.INP")
#! Link("PLC:HTR:TM01:FAULTMOTION.INP","PLC:HTR:TM01:FAULTMOTIONCALC.VAL")
#! Record("PLC:HTR:TM01:VERSIONMAJORDES",2160,2867,0,1,"PLC:HTR:TM01:VERSIONMAJORDES")
#! Field("PLC:HTR:TM01:VERSIONMAJORDES.FLNK",16777215,1,"PLC:HTR:TM01:VERSIONMAJORDES.FLNK")
#! Link("PLC:HTR:TM01:VERSIONMAJORDES.FLNK","PLC:HTR:TM01:VERSIONMAJORCALCHI")
#! Field("PLC:HTR:TM01:VERSIONMAJORDES.VAL",16777215,1,"PLC:HTR:TM01:VERSIONMAJORDES.VAL")
#! Record("PLC:HTR:TM01:VERSIONMAJORCALCHI",2420,2687,0,0,"PLC:HTR:TM01:VERSIONMAJORCALCHI")
#! Field("PLC:HTR:TM01:VERSIONMAJORCALCHI.INPA",16777215,0,"PLC:HTR:TM01:VERSIONMAJORCALCHI.INPA")
#! Link("PLC:HTR:TM01:VERSIONMAJORCALCHI.INPA","PLC:HTR:TM01:VERSIONMAJORDES.VAL")
#! Field("PLC:HTR:TM01:VERSIONMAJORCALCHI.OUT",16777215,1,"PLC:HTR:TM01:VERSIONMAJORCALCHI.OUT")
#! Link("PLC:HTR:TM01:VERSIONMAJORCALCHI.OUT","PLC:HTR:TM01:VERSIONMAJOR.HIGH")
#! Field("PLC:HTR:TM01:VERSIONMAJORCALCHI.FLNK",16777215,1,"PLC:HTR:TM01:VERSIONMAJORCALCHI.FLNK")
#! Link("PLC:HTR:TM01:VERSIONMAJORCALCHI.FLNK","PLC:HTR:TM01:VERSIONMAJORCALCLO")
#! Record("PLC:HTR:TM01:VERSIONMAJORCALCLO",2460,2922,0,1,"PLC:HTR:TM01:VERSIONMAJORCALCLO")
#! Field("PLC:HTR:TM01:VERSIONMAJORCALCLO.INPA",16777215,0,"PLC:HTR:TM01:VERSIONMAJORCALCLO.INPA")
#! Link("PLC:HTR:TM01:VERSIONMAJORCALCLO.INPA","PLC:HTR:TM01:VERSIONMAJORDES.VAL")
#! Field("PLC:HTR:TM01:VERSIONMAJORCALCLO.OUT",16777215,1,"PLC:HTR:TM01:VERSIONMAJORCALCLO.OUT")
#! Link("PLC:HTR:TM01:VERSIONMAJORCALCLO.OUT","PLC:HTR:TM01:VERSIONMAJOR.LOW")
#! Record("PLC:HTR:TM01:VERSIONMINORDES",2160,3147,0,1,"PLC:HTR:TM01:VERSIONMINORDES")
#! Field("PLC:HTR:TM01:VERSIONMINORDES.FLNK",16777215,1,"PLC:HTR:TM01:VERSIONMINORDES.FLNK")
#! Link("PLC:HTR:TM01:VERSIONMINORDES.FLNK","PLC:HTR:TM01:VERSIONMINORCALCHI")
#! Field("PLC:HTR:TM01:VERSIONMINORDES.VAL",16777215,1,"PLC:HTR:TM01:VERSIONMINORDES.VAL")
#! Record("PLC:HTR:TM01:VERSIONMINORCALCLO",2480,3322,0,1,"PLC:HTR:TM01:VERSIONMINORCALCLO")
#! Field("PLC:HTR:TM01:VERSIONMINORCALCLO.INPA",16777215,0,"PLC:HTR:TM01:VERSIONMINORCALCLO.INPA")
#! Link("PLC:HTR:TM01:VERSIONMINORCALCLO.INPA","PLC:HTR:TM01:VERSIONMINORDES.VAL")
#! Field("PLC:HTR:TM01:VERSIONMINORCALCLO.OUT",16777215,1,"PLC:HTR:TM01:VERSIONMINORCALCLO.OUT")
#! Link("PLC:HTR:TM01:VERSIONMINORCALCLO.OUT","PLC:HTR:TM01:VERSIONMINOR.LOW")
#! Record("PLC:HTR:TM01:VERSIONMINORCALCHI",2440,3087,0,0,"PLC:HTR:TM01:VERSIONMINORCALCHI")
#! Field("PLC:HTR:TM01:VERSIONMINORCALCHI.FLNK",16777215,1,"PLC:HTR:TM01:VERSIONMINORCALCHI.FLNK")
#! Link("PLC:HTR:TM01:VERSIONMINORCALCHI.FLNK","PLC:HTR:TM01:VERSIONMINORCALCLO")
#! Field("PLC:HTR:TM01:VERSIONMINORCALCHI.INPA",16777215,0,"PLC:HTR:TM01:VERSIONMINORCALCHI.INPA")
#! Link("PLC:HTR:TM01:VERSIONMINORCALCHI.INPA","PLC:HTR:TM01:VERSIONMINORDES.VAL")
#! Field("PLC:HTR:TM01:VERSIONMINORCALCHI.OUT",16777215,1,"PLC:HTR:TM01:VERSIONMINORCALCHI.OUT")
#! Link("PLC:HTR:TM01:VERSIONMINORCALCHI.OUT","PLC:HTR:TM01:VERSIONMINOR.HIGH")
#! Record("PLC:HTR:TM01:VERSIONREVDES",2180,3547,0,1,"PLC:HTR:TM01:VERSIONREVDES")
#! Field("PLC:HTR:TM01:VERSIONREVDES.FLNK",16777215,1,"PLC:HTR:TM01:VERSIONREVDES.FLNK")
#! Link("PLC:HTR:TM01:VERSIONREVDES.FLNK","PLC:HTR:TM01:VERSIONREVCALCHI")
#! Field("PLC:HTR:TM01:VERSIONREVDES.VAL",16777215,1,"PLC:HTR:TM01:VERSIONREVDES.VAL")
#! Record("PLC:HTR:TM01:VERSIONREVCALCHI",2460,3487,0,0,"PLC:HTR:TM01:VERSIONREVCALCHI")
#! Field("PLC:HTR:TM01:VERSIONREVCALCHI.FLNK",16777215,1,"PLC:HTR:TM01:VERSIONREVCALCHI.FLNK")
#! Link("PLC:HTR:TM01:VERSIONREVCALCHI.FLNK","PLC:HTR:TM01:VERSIONREVCALCLO")
#! Field("PLC:HTR:TM01:VERSIONREVCALCHI.INPA",16777215,0,"PLC:HTR:TM01:VERSIONREVCALCHI.INPA")
#! Link("PLC:HTR:TM01:VERSIONREVCALCHI.INPA","PLC:HTR:TM01:VERSIONREVDES.VAL")
#! Field("PLC:HTR:TM01:VERSIONREVCALCHI.OUT",16777215,1,"PLC:HTR:TM01:VERSIONREVCALCHI.OUT")
#! Link("PLC:HTR:TM01:VERSIONREVCALCHI.OUT","PLC:HTR:TM01:VERSIONREV.HIGH")
#! Record("PLC:HTR:TM01:VERSIONREVCALCLO",2500,3722,0,1,"PLC:HTR:TM01:VERSIONREVCALCLO")
#! Field("PLC:HTR:TM01:VERSIONREVCALCLO.INPA",16777215,0,"PLC:HTR:TM01:VERSIONREVCALCLO.INPA")
#! Link("PLC:HTR:TM01:VERSIONREVCALCLO.INPA","PLC:HTR:TM01:VERSIONREVDES.VAL")
#! Field("PLC:HTR:TM01:VERSIONREVCALCLO.OUT",16777215,1,"PLC:HTR:TM01:VERSIONREVCALCLO.OUT")
#! Link("PLC:HTR:TM01:VERSIONREVCALCLO.OUT","PLC:HTR:TM01:VERSIONREV.LOW")
#! Record("PLC:HTR:TM01:HEARTBEATCALC",600,187,0,0,"PLC:HTR:TM01:HEARTBEATCALC")
#! Field("PLC:HTR:TM01:HEARTBEATCALC.INPA",16777215,0,"PLC:HTR:TM01:HEARTBEATCALC.INPA")
#! Link("PLC:HTR:TM01:HEARTBEATCALC.INPA","PLC:HTR:TM01:HEARTBEATRAW.VAL")
#! Field("PLC:HTR:TM01:HEARTBEATCALC.VAL",16777215,0,"PLC:HTR:TM01:HEARTBEATCALC.VAL")
#! Field("PLC:HTR:TM01:HEARTBEATCALC.INPB",16777215,0,"PLC:HTR:TM01:HEARTBEATCALC.INPB")
#! Link("PLC:HTR:TM01:HEARTBEATCALC.INPB","PLC:HTR:TM01:HEARTBEATCALC.VAL")
#! Field("PLC:HTR:TM01:HEARTBEATCALC.FLNK",16777215,1,"PLC:HTR:TM01:HEARTBEATCALC.FLNK")
#! Link("PLC:HTR:TM01:HEARTBEATCALC.FLNK","PLC:HTR:TM01:HEARTBEATERR")
#! Field("PLC:HTR:TM01:HEARTBEATCALC.A",16777215,1,"PLC:HTR:TM01:HEARTBEATCALC.A")
#! Field("PLC:HTR:TM01:HEARTBEATCALC.B",16777215,1,"PLC:HTR:TM01:HEARTBEATCALC.B")
#! Record("PLC:HTR:TM01:HEARTBEATOK",1600,299,0,0,"PLC:HTR:TM01:HEARTBEATOK")
#! Field("PLC:HTR:TM01:HEARTBEATOK.INP",16777215,0,"PLC:HTR:TM01:HEARTBEATOK.INP")
#! Link("PLC:HTR:TM01:HEARTBEATOK.INP","PLC:HTR:TM01:HEARTBEATERR.VAL")
#! Field("PLC:HTR:TM01:HEARTBEATOK.FLNK",16777215,0,"PLC:HTR:TM01:HEARTBEATOK.FLNK")
#! Link("PLC:HTR:TM01:HEARTBEATOK.FLNK","PLC:HTR:TM01:HEARTBEATE01")
#! Record("PLC:HTR:TM01:HEARTBEATERR",900,267,0,0,"PLC:HTR:TM01:HEARTBEATERR")
#! Field("PLC:HTR:TM01:HEARTBEATERR.INPA",16777215,0,"PLC:HTR:TM01:HEARTBEATERR.INPA")
#! Link("PLC:HTR:TM01:HEARTBEATERR.INPA","PLC:HTR:TM01:HEARTBEATCALC.A")
#! Field("PLC:HTR:TM01:HEARTBEATERR.INPB",16777215,0,"PLC:HTR:TM01:HEARTBEATERR.INPB")
#! Link("PLC:HTR:TM01:HEARTBEATERR.INPB","PLC:HTR:TM01:HEARTBEATCALC.B")
#! Field("PLC:HTR:TM01:HEARTBEATERR.FLNK",16777215,1,"PLC:HTR:TM01:HEARTBEATERR.FLNK")
#! Link("PLC:HTR:TM01:HEARTBEATERR.FLNK","PLC:HTR:TM01:HEARTBEATOK")
#! Field("PLC:HTR:TM01:HEARTBEATERR.VAL",16777215,1,"PLC:HTR:TM01:HEARTBEATERR.VAL")
#! Record("PLC:HTR:TM01:HEARTBEATECT",1740,1160,0,0,"PLC:HTR:TM01:HEARTBEATECT")
#! Field("PLC:HTR:TM01:HEARTBEATECT.INPA",16777215,0,"PLC:HTR:TM01:HEARTBEATECT.INPA")
#! Link("PLC:HTR:TM01:HEARTBEATECT.INPA","PLC:HTR:TM01:HEARTBEATECT/INPA")
#! Field("PLC:HTR:TM01:HEARTBEATECT.INPB",16777215,0,"PLC:HTR:TM01:HEARTBEATECT.INPB")
#! Link("PLC:HTR:TM01:HEARTBEATECT.INPB","PLC:HTR:TM01:HEARTBEATECT/INPB")
#! Field("PLC:HTR:TM01:HEARTBEATECT.INPC",16777215,0,"PLC:HTR:TM01:HEARTBEATECT.INPC")
#! Link("PLC:HTR:TM01:HEARTBEATECT.INPC","PLC:HTR:TM01:HEARTBEATECT/INPC")
#! Field("PLC:HTR:TM01:HEARTBEATECT.INPD",16777215,0,"PLC:HTR:TM01:HEARTBEATECT.INPD")
#! Link("PLC:HTR:TM01:HEARTBEATECT.INPD","PLC:HTR:TM01:HEARTBEATECT/INPD")
#! Field("PLC:HTR:TM01:HEARTBEATECT.INPE",16777215,0,"PLC:HTR:TM01:HEARTBEATECT.INPE")
#! Link("PLC:HTR:TM01:HEARTBEATECT.INPE","PLC:HTR:TM01:HEARTBEATECT/INPE")
#! Field("PLC:HTR:TM01:HEARTBEATECT.INPF",16777215,0,"PLC:HTR:TM01:HEARTBEATECT.INPF")
#! Link("PLC:HTR:TM01:HEARTBEATECT.INPF","PLC:HTR:TM01:HEARTBEATECT/INPF")
#! Field("PLC:HTR:TM01:HEARTBEATECT.INPG",16777215,0,"PLC:HTR:TM01:HEARTBEATECT.INPG")
#! Link("PLC:HTR:TM01:HEARTBEATECT.INPG","PLC:HTR:TM01:HEARTBEATECT/INPG")
#! Field("PLC:HTR:TM01:HEARTBEATECT.INPH",16777215,0,"PLC:HTR:TM01:HEARTBEATECT.INPH")
#! Link("PLC:HTR:TM01:HEARTBEATECT.INPH","PLC:HTR:TM01:HEARTBEATECT/INPH")
#! Field("PLC:HTR:TM01:HEARTBEATECT.INPI",16777215,0,"PLC:HTR:TM01:HEARTBEATECT.INPI")
#! Link("PLC:HTR:TM01:HEARTBEATECT.INPI","PLC:HTR:TM01:HEARTBEATECT/INPI")
#! Field("PLC:HTR:TM01:HEARTBEATECT.INPJ",16777215,0,"PLC:HTR:TM01:HEARTBEATECT.INPJ")
#! Link("PLC:HTR:TM01:HEARTBEATECT.INPJ","PLC:HTR:TM01:HEARTBEATECT/INPJ")
#! Field("PLC:HTR:TM01:HEARTBEATECT.FLNK",16777215,1,"PLC:HTR:TM01:HEARTBEATECT.FLNK")
#! Link("PLC:HTR:TM01:HEARTBEATECT.FLNK","PLC:HTR:TM01:HEARTBEATSUM")
#! Field("PLC:HTR:TM01:HEARTBEATECT.SEVR",16777215,1,"PLC:HTR:TM01:HEARTBEATECT.SEVR")
#! Connector("PLC:HTR:TM01:HEARTBEATECT/INPJ","PLC:HTR:TM01:HEARTBEATE10.VAL",1600,2130,16777215,"",0)
#! Connector("PLC:HTR:TM01:HEARTBEATECT/INPI","PLC:HTR:TM01:HEARTBEATE09.VAL",1560,2020,16777215,"",0)
#! Connector("PLC:HTR:TM01:HEARTBEATECT/INPH","PLC:HTR:TM01:HEARTBEATE08.VAL",1520,1910,16777215,"",0)
#! Connector("PLC:HTR:TM01:HEARTBEATECT/INPG","PLC:HTR:TM01:HEARTBEATE07.VAL",1480,1790,16777215,"",0)
#! Connector("PLC:HTR:TM01:HEARTBEATECT/INPF","PLC:HTR:TM01:HEARTBEATE06.VAL",1280,1670,16777215,"",0)
#! Connector("PLC:HTR:TM01:HEARTBEATECT/INPE","PLC:HTR:TM01:HEARTBEATE05.VAL",1320,1550,16777215,"",0)
#! Connector("PLC:HTR:TM01:HEARTBEATECT/INPD","PLC:HTR:TM01:HEARTBEATE04.VAL",1360,1430,16777215,"",0)
#! Connector("PLC:HTR:TM01:HEARTBEATECT/INPC","PLC:HTR:TM01:HEARTBEATE03.VAL",1400,1310,16777215,"",0)
#! Connector("PLC:HTR:TM01:HEARTBEATECT/INPB","PLC:HTR:TM01:HEARTBEATE02.VAL",1440,1190,16777215,"",0)
#! Connector("PLC:HTR:TM01:HEARTBEATECT/INPA","PLC:HTR:TM01:HEARTBEATE01.VAL",1480,1070,16777215,"",0)
#! Record("PLC:HTR:TM01:HEARTBEATE09",1060,2227,0,1,"PLC:HTR:TM01:HEARTBEATE09")
#! Field("PLC:HTR:TM01:HEARTBEATE09.INPA",16777215,0,"PLC:HTR:TM01:HEARTBEATE09.INPA")
#! Link("PLC:HTR:TM01:HEARTBEATE09.INPA","PLC:HTR:TM01:HEARTBEATE08.B")
#! Field("PLC:HTR:TM01:HEARTBEATE09.VAL",16777215,1,"PLC:HTR:TM01:HEARTBEATE09.VAL")
#! Field("PLC:HTR:TM01:HEARTBEATE09.FLNK",16777215,1,"PLC:HTR:TM01:HEARTBEATE09.FLNK")
#! Link("PLC:HTR:TM01:HEARTBEATE09.FLNK","PLC:HTR:TM01:HEARTBEATE10")
#! Field("PLC:HTR:TM01:HEARTBEATE09.INPB",16777215,0,"PLC:HTR:TM01:HEARTBEATE09.INPB")
#! Link("PLC:HTR:TM01:HEARTBEATE09.INPB","PLC:HTR:TM01:HEARTBEATE09.VAL")
#! Field("PLC:HTR:TM01:HEARTBEATE09.B",16777215,0,"PLC:HTR:TM01:HEARTBEATE09.B")
#! Record("PLC:HTR:TM01:HEARTBEATE08",1040,2007,0,1,"PLC:HTR:TM01:HEARTBEATE08")
#! Field("PLC:HTR:TM01:HEARTBEATE08.FLNK",16777215,1,"PLC:HTR:TM01:HEARTBEATE08.FLNK")
#! Link("PLC:HTR:TM01:HEARTBEATE08.FLNK","PLC:HTR:TM01:HEARTBEATE09")
#! Field("PLC:HTR:TM01:HEARTBEATE08.INPA",16777215,0,"PLC:HTR:TM01:HEARTBEATE08.INPA")
#! Link("PLC:HTR:TM01:HEARTBEATE08.INPA","PLC:HTR:TM01:HEARTBEATE07.B")
#! Field("PLC:HTR:TM01:HEARTBEATE08.VAL",16777215,1,"PLC:HTR:TM01:HEARTBEATE08.VAL")
#! Field("PLC:HTR:TM01:HEARTBEATE08.INPB",16777215,0,"PLC:HTR:TM01:HEARTBEATE08.INPB")
#! Link("PLC:HTR:TM01:HEARTBEATE08.INPB","PLC:HTR:TM01:HEARTBEATE08.VAL")
#! Field("PLC:HTR:TM01:HEARTBEATE08.B",16777215,0,"PLC:HTR:TM01:HEARTBEATE08.B")
#! Record("PLC:HTR:TM01:HEARTBEATE07",1020,1787,0,1,"PLC:HTR:TM01:HEARTBEATE07")
#! Field("PLC:HTR:TM01:HEARTBEATE07.FLNK",16777215,1,"PLC:HTR:TM01:HEARTBEATE07.FLNK")
#! Link("PLC:HTR:TM01:HEARTBEATE07.FLNK","PLC:HTR:TM01:HEARTBEATE08")
#! Field("PLC:HTR:TM01:HEARTBEATE07.INPA",16777215,0,"PLC:HTR:TM01:HEARTBEATE07.INPA")
#! Link("PLC:HTR:TM01:HEARTBEATE07.INPA","PLC:HTR:TM01:HEARTBEATE06.B")
#! Field("PLC:HTR:TM01:HEARTBEATE07.VAL",16777215,1,"PLC:HTR:TM01:HEARTBEATE07.VAL")
#! Field("PLC:HTR:TM01:HEARTBEATE07.INPB",16777215,0,"PLC:HTR:TM01:HEARTBEATE07.INPB")
#! Link("PLC:HTR:TM01:HEARTBEATE07.INPB","PLC:HTR:TM01:HEARTBEATE07.VAL")
#! Field("PLC:HTR:TM01:HEARTBEATE07.B",16777215,0,"PLC:HTR:TM01:HEARTBEATE07.B")
#! Record("PLC:HTR:TM01:HEARTBEATE06",1020,1567,0,1,"PLC:HTR:TM01:HEARTBEATE06")
#! Field("PLC:HTR:TM01:HEARTBEATE06.FLNK",16777215,1,"PLC:HTR:TM01:HEARTBEATE06.FLNK")
#! Link("PLC:HTR:TM01:HEARTBEATE06.FLNK","PLC:HTR:TM01:HEARTBEATE05/FLNK")
#! Field("PLC:HTR:TM01:HEARTBEATE06.INPA",16777215,0,"PLC:HTR:TM01:HEARTBEATE06.INPA")
#! Link("PLC:HTR:TM01:HEARTBEATE06.INPA","PLC:HTR:TM01:HEARTBEATE05.B")
#! Field("PLC:HTR:TM01:HEARTBEATE06.VAL",16777215,1,"PLC:HTR:TM01:HEARTBEATE06.VAL")
#! Field("PLC:HTR:TM01:HEARTBEATE06.INPB",16777215,0,"PLC:HTR:TM01:HEARTBEATE06.INPB")
#! Link("PLC:HTR:TM01:HEARTBEATE06.INPB","PLC:HTR:TM01:HEARTBEATE06.VAL")
#! Field("PLC:HTR:TM01:HEARTBEATE06.B",16777215,0,"PLC:HTR:TM01:HEARTBEATE06.B")
#! Connector("PLC:HTR:TM01:HEARTBEATE05/FLNK","PLC:HTR:TM01:HEARTBEATE07",1260,1766,16777215,"",0)
#! Record("PLC:HTR:TM01:HEARTBEATE05",1000,1347,0,1,"PLC:HTR:TM01:HEARTBEATE05")
#! Field("PLC:HTR:TM01:HEARTBEATE05.FLNK",16777215,1,"PLC:HTR:TM01:HEARTBEATE05.FLNK")
#! Link("PLC:HTR:TM01:HEARTBEATE05.FLNK","PLC:HTR:TM01:HEARTBEATE06")
#! Field("PLC:HTR:TM01:HEARTBEATE05.INPA",16777215,0,"PLC:HTR:TM01:HEARTBEATE05.INPA")
#! Link("PLC:HTR:TM01:HEARTBEATE05.INPA","PLC:HTR:TM01:HEARTBEATE04.B")
#! Field("PLC:HTR:TM01:HEARTBEATE05.VAL",16777215,1,"PLC:HTR:TM01:HEARTBEATE05.VAL")
#! Field("PLC:HTR:TM01:HEARTBEATE05.INPB",16777215,0,"PLC:HTR:TM01:HEARTBEATE05.INPB")
#! Link("PLC:HTR:TM01:HEARTBEATE05.INPB","PLC:HTR:TM01:HEARTBEATE05.VAL")
#! Field("PLC:HTR:TM01:HEARTBEATE05.B",16777215,0,"PLC:HTR:TM01:HEARTBEATE05.B")
#! Record("PLC:HTR:TM01:HEARTBEATE04",980,1127,0,1,"PLC:HTR:TM01:HEARTBEATE04")
#! Field("PLC:HTR:TM01:HEARTBEATE04.FLNK",16777215,1,"PLC:HTR:TM01:HEARTBEATE04.FLNK")
#! Link("PLC:HTR:TM01:HEARTBEATE04.FLNK","PLC:HTR:TM01:HEARTBEATE05")
#! Field("PLC:HTR:TM01:HEARTBEATE04.INPA",16777215,0,"PLC:HTR:TM01:HEARTBEATE04.INPA")
#! Link("PLC:HTR:TM01:HEARTBEATE04.INPA","PLC:HTR:TM01:HEARTBEATE03.B")
#! Field("PLC:HTR:TM01:HEARTBEATE04.VAL",16777215,1,"PLC:HTR:TM01:HEARTBEATE04.VAL")
#! Field("PLC:HTR:TM01:HEARTBEATE04.INPB",16777215,0,"PLC:HTR:TM01:HEARTBEATE04.INPB")
#! Link("PLC:HTR:TM01:HEARTBEATE04.INPB","PLC:HTR:TM01:HEARTBEATE04.VAL")
#! Field("PLC:HTR:TM01:HEARTBEATE04.B",16777215,0,"PLC:HTR:TM01:HEARTBEATE04.B")
#! Record("PLC:HTR:TM01:HEARTBEATE03",960,907,0,1,"PLC:HTR:TM01:HEARTBEATE03")
#! Field("PLC:HTR:TM01:HEARTBEATE03.FLNK",16777215,1,"PLC:HTR:TM01:HEARTBEATE03.FLNK")
#! Link("PLC:HTR:TM01:HEARTBEATE03.FLNK","PLC:HTR:TM01:HEARTBEATE04")
#! Field("PLC:HTR:TM01:HEARTBEATE03.INPA",16777215,0,"PLC:HTR:TM01:HEARTBEATE03.INPA")
#! Link("PLC:HTR:TM01:HEARTBEATE03.INPA","PLC:HTR:TM01:HEARTBEATE02.B")
#! Field("PLC:HTR:TM01:HEARTBEATE03.VAL",16777215,1,"PLC:HTR:TM01:HEARTBEATE03.VAL")
#! Field("PLC:HTR:TM01:HEARTBEATE03.INPB",16777215,0,"PLC:HTR:TM01:HEARTBEATE03.INPB")
#! Link("PLC:HTR:TM01:HEARTBEATE03.INPB","PLC:HTR:TM01:HEARTBEATE03.VAL")
#! Field("PLC:HTR:TM01:HEARTBEATE03.B",16777215,0,"PLC:HTR:TM01:HEARTBEATE03.B")
#! Record("PLC:HTR:TM01:HEARTBEATE02",940,687,0,1,"PLC:HTR:TM01:HEARTBEATE02")
#! Field("PLC:HTR:TM01:HEARTBEATE02.FLNK",16777215,1,"PLC:HTR:TM01:HEARTBEATE02.FLNK")
#! Link("PLC:HTR:TM01:HEARTBEATE02.FLNK","PLC:HTR:TM01:HEARTBEATE03")
#! Field("PLC:HTR:TM01:HEARTBEATE02.INPA",16777215,0,"PLC:HTR:TM01:HEARTBEATE02.INPA")
#! Link("PLC:HTR:TM01:HEARTBEATE02.INPA","PLC:HTR:TM01:HEARTBEATE01.B")
#! Field("PLC:HTR:TM01:HEARTBEATE02.VAL",16777215,1,"PLC:HTR:TM01:HEARTBEATE02.VAL")
#! Field("PLC:HTR:TM01:HEARTBEATE02.INPB",16777215,0,"PLC:HTR:TM01:HEARTBEATE02.INPB")
#! Link("PLC:HTR:TM01:HEARTBEATE02.INPB","PLC:HTR:TM01:HEARTBEATE02.VAL")
#! Field("PLC:HTR:TM01:HEARTBEATE02.B",16777215,0,"PLC:HTR:TM01:HEARTBEATE02.B")
#! Record("PLC:HTR:TM01:HEARTBEATE01",900,467,0,1,"PLC:HTR:TM01:HEARTBEATE01")
#! Field("PLC:HTR:TM01:HEARTBEATE01.INPA",16777215,0,"PLC:HTR:TM01:HEARTBEATE01.INPA")
#! Link("PLC:HTR:TM01:HEARTBEATE01.INPA","PLC:HTR:TM01:HEARTBEATERR.VAL")
#! Field("PLC:HTR:TM01:HEARTBEATE01.FLNK",16777215,1,"PLC:HTR:TM01:HEARTBEATE01.FLNK")
#! Link("PLC:HTR:TM01:HEARTBEATE01.FLNK","PLC:HTR:TM01:HEARTBEATE02")
#! Field("PLC:HTR:TM01:HEARTBEATE01.VAL",16777215,1,"PLC:HTR:TM01:HEARTBEATE01.VAL")
#! Field("PLC:HTR:TM01:HEARTBEATE01.INPB",16777215,0,"PLC:HTR:TM01:HEARTBEATE01.INPB")
#! Link("PLC:HTR:TM01:HEARTBEATE01.INPB","PLC:HTR:TM01:HEARTBEATE01.VAL")
#! Field("PLC:HTR:TM01:HEARTBEATE01.B",16777215,0,"PLC:HTR:TM01:HEARTBEATE01.B")
#! Record("PLC:HTR:TM01:HEARTBEATCLC",3300,1847,0,0,"PLC:HTR:TM01:HEARTBEATCLC")
#! Field("PLC:HTR:TM01:HEARTBEATCLC.INPA",16777215,0,"PLC:HTR:TM01:HEARTBEATCLC.INPA")
#! Link("PLC:HTR:TM01:HEARTBEATCLC.INPA","PLC:HTR:TM01:HEARTBEATECT.SEVR")
#! Field("PLC:HTR:TM01:HEARTBEATCLC.VAL",16777215,1,"PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:HEARTBEATSUM",2080,1690,0,0,"PLC:HTR:TM01:HEARTBEATSUM")
#! Field("PLC:HTR:TM01:HEARTBEATSUM.INP",16777215,0,"PLC:HTR:TM01:HEARTBEATSUM.INP")
#! Link("PLC:HTR:TM01:HEARTBEATSUM.INP","PLC:HTR:TM01:HEARTBEATECT.SEVR")
#! Field("PLC:HTR:TM01:HEARTBEATSUM.FLNK",16777215,1,"PLC:HTR:TM01:HEARTBEATSUM.FLNK")
#! Link("PLC:HTR:TM01:HEARTBEATSUM.FLNK","PLC:HTR:TM01:HEARTBEATCLC")
#! Field("PLC:HTR:TM01:HEARTBEATSUM.VAL",16777215,0,"PLC:HTR:TM01:HEARTBEATSUM.VAL")
#! Record("PLC:HTR:TM01:UPTIMEDAYRAW",4280,1587,0,0,"PLC:HTR:TM01:UPTIMEDAYRAW")
#! Field("PLC:HTR:TM01:UPTIMEDAYRAW.FLNK",16777215,1,"PLC:HTR:TM01:UPTIMEDAYRAW.FLNK")
#! Link("PLC:HTR:TM01:UPTIMEDAYRAW.FLNK","PLC:HTR:TM01:UPTIMEDAY")
#! Field("PLC:HTR:TM01:UPTIMEDAYRAW.VAL",16777215,1,"PLC:HTR:TM01:UPTIMEDAYRAW.VAL")
#! Record("PLC:HTR:TM01:UPTIMEDAY",4560,1622,0,0,"PLC:HTR:TM01:UPTIMEDAY")
#! Field("PLC:HTR:TM01:UPTIMEDAY.INPA",16777215,0,"PLC:HTR:TM01:UPTIMEDAY.INPA")
#! Link("PLC:HTR:TM01:UPTIMEDAY.INPA","PLC:HTR:TM01:UPTIMEDAYRAW.VAL")
#! Field("PLC:HTR:TM01:UPTIMEDAY.INPB",16777215,0,"PLC:HTR:TM01:UPTIMEDAY.INPB")
#! Link("PLC:HTR:TM01:UPTIMEDAY.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:TODYEARRAW",4220,487,0,0,"PLC:HTR:TM01:TODYEARRAW")
#! Field("PLC:HTR:TM01:TODYEARRAW.FLNK",16777215,1,"PLC:HTR:TM01:TODYEARRAW.FLNK")
#! Link("PLC:HTR:TM01:TODYEARRAW.FLNK","PLC:HTR:TM01:TODYEAR")
#! Field("PLC:HTR:TM01:TODYEARRAW.VAL",16777215,1,"PLC:HTR:TM01:TODYEARRAW.VAL")
#! Record("PLC:HTR:TM01:TODDAYRAW",4220,847,0,0,"PLC:HTR:TM01:TODDAYRAW")
#! Field("PLC:HTR:TM01:TODDAYRAW.FLNK",16777215,1,"PLC:HTR:TM01:TODDAYRAW.FLNK")
#! Link("PLC:HTR:TM01:TODDAYRAW.FLNK","PLC:HTR:TM01:TODDAY")
#! Field("PLC:HTR:TM01:TODDAYRAW.VAL",16777215,1,"PLC:HTR:TM01:TODDAYRAW.VAL")
#! Record("PLC:HTR:TM01:TODMONTHRAW",4220,667,0,0,"PLC:HTR:TM01:TODMONTHRAW")
#! Field("PLC:HTR:TM01:TODMONTHRAW.FLNK",16777215,1,"PLC:HTR:TM01:TODMONTHRAW.FLNK")
#! Link("PLC:HTR:TM01:TODMONTHRAW.FLNK","PLC:HTR:TM01:TODMONTH")
#! Field("PLC:HTR:TM01:TODMONTHRAW.VAL",16777215,1,"PLC:HTR:TM01:TODMONTHRAW.VAL")
#! Record("PLC:HTR:TM01:TODHOURRAW",4220,1027,0,0,"PLC:HTR:TM01:TODHOURRAW")
#! Field("PLC:HTR:TM01:TODHOURRAW.FLNK",16777215,1,"PLC:HTR:TM01:TODHOURRAW.FLNK")
#! Link("PLC:HTR:TM01:TODHOURRAW.FLNK","PLC:HTR:TM01:TODHOUR")
#! Field("PLC:HTR:TM01:TODHOURRAW.VAL",16777215,1,"PLC:HTR:TM01:TODHOURRAW.VAL")
#! Record("PLC:HTR:TM01:TODMINUTERAW",4220,1207,0,0,"PLC:HTR:TM01:TODMINUTERAW")
#! Field("PLC:HTR:TM01:TODMINUTERAW.FLNK",16777215,1,"PLC:HTR:TM01:TODMINUTERAW.FLNK")
#! Link("PLC:HTR:TM01:TODMINUTERAW.FLNK","PLC:HTR:TM01:TODMINUTE")
#! Field("PLC:HTR:TM01:TODMINUTERAW.VAL",16777215,1,"PLC:HTR:TM01:TODMINUTERAW.VAL")
#! Record("PLC:HTR:TM01:TODSECONDRAW",4220,1374,0,0,"PLC:HTR:TM01:TODSECONDRAW")
#! Field("PLC:HTR:TM01:TODSECONDRAW.FLNK",16777215,1,"PLC:HTR:TM01:TODSECONDRAW.FLNK")
#! Link("PLC:HTR:TM01:TODSECONDRAW.FLNK","PLC:HTR:TM01:TODSECOND")
#! Field("PLC:HTR:TM01:TODSECONDRAW.VAL",16777215,1,"PLC:HTR:TM01:TODSECONDRAW.VAL")
#! Record("PLC:HTR:TM01:TODYEAR",4520,522,0,0,"PLC:HTR:TM01:TODYEAR")
#! Field("PLC:HTR:TM01:TODYEAR.INPA",16777215,0,"PLC:HTR:TM01:TODYEAR.INPA")
#! Link("PLC:HTR:TM01:TODYEAR.INPA","PLC:HTR:TM01:TODYEARRAW.VAL")
#! Field("PLC:HTR:TM01:TODYEAR.INPB",16777215,0,"PLC:HTR:TM01:TODYEAR.INPB")
#! Link("PLC:HTR:TM01:TODYEAR.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:TODMONTH",4520,702,0,0,"PLC:HTR:TM01:TODMONTH")
#! Field("PLC:HTR:TM01:TODMONTH.INPA",16777215,0,"PLC:HTR:TM01:TODMONTH.INPA")
#! Link("PLC:HTR:TM01:TODMONTH.INPA","PLC:HTR:TM01:TODMONTHRAW.VAL")
#! Field("PLC:HTR:TM01:TODMONTH.INPB",16777215,0,"PLC:HTR:TM01:TODMONTH.INPB")
#! Link("PLC:HTR:TM01:TODMONTH.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:TODDAY",4520,882,0,0,"PLC:HTR:TM01:TODDAY")
#! Field("PLC:HTR:TM01:TODDAY.INPA",16777215,0,"PLC:HTR:TM01:TODDAY.INPA")
#! Link("PLC:HTR:TM01:TODDAY.INPA","PLC:HTR:TM01:TODDAYRAW.VAL")
#! Field("PLC:HTR:TM01:TODDAY.INPB",16777215,0,"PLC:HTR:TM01:TODDAY.INPB")
#! Link("PLC:HTR:TM01:TODDAY.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:TODHOUR",4520,1062,0,0,"PLC:HTR:TM01:TODHOUR")
#! Field("PLC:HTR:TM01:TODHOUR.INPA",16777215,0,"PLC:HTR:TM01:TODHOUR.INPA")
#! Link("PLC:HTR:TM01:TODHOUR.INPA","PLC:HTR:TM01:TODHOURRAW.VAL")
#! Field("PLC:HTR:TM01:TODHOUR.INPB",16777215,0,"PLC:HTR:TM01:TODHOUR.INPB")
#! Link("PLC:HTR:TM01:TODHOUR.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:TODMINUTE",4520,1242,0,0,"PLC:HTR:TM01:TODMINUTE")
#! Field("PLC:HTR:TM01:TODMINUTE.INPA",16777215,0,"PLC:HTR:TM01:TODMINUTE.INPA")
#! Link("PLC:HTR:TM01:TODMINUTE.INPA","PLC:HTR:TM01:TODMINUTERAW.VAL")
#! Field("PLC:HTR:TM01:TODMINUTE.INPB",16777215,0,"PLC:HTR:TM01:TODMINUTE.INPB")
#! Link("PLC:HTR:TM01:TODMINUTE.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:TODSECOND",4520,1422,0,0,"PLC:HTR:TM01:TODSECOND")
#! Field("PLC:HTR:TM01:TODSECOND.INPA",16777215,0,"PLC:HTR:TM01:TODSECOND.INPA")
#! Link("PLC:HTR:TM01:TODSECOND.INPA","PLC:HTR:TM01:TODSECONDRAW.VAL")
#! Field("PLC:HTR:TM01:TODSECOND.INPB",16777215,0,"PLC:HTR:TM01:TODSECOND.INPB")
#! Link("PLC:HTR:TM01:TODSECOND.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:VERSIONMAJORRAW",2740,2874,0,1,"PLC:HTR:TM01:VERSIONMAJORRAW")
#! Field("PLC:HTR:TM01:VERSIONMAJORRAW.VAL",16777215,1,"PLC:HTR:TM01:VERSIONMAJORRAW.VAL")
#! Field("PLC:HTR:TM01:VERSIONMAJORRAW.FLNK",16777215,1,"PLC:HTR:TM01:VERSIONMAJORRAW.FLNK")
#! Link("PLC:HTR:TM01:VERSIONMAJORRAW.FLNK","PLC:HTR:TM01:VERSIONMAJOR")
#! Record("PLC:HTR:TM01:VERSIONMINORRAW",2760,3287,0,1,"PLC:HTR:TM01:VERSIONMINORRAW")
#! Field("PLC:HTR:TM01:VERSIONMINORRAW.VAL",16777215,1,"PLC:HTR:TM01:VERSIONMINORRAW.VAL")
#! Field("PLC:HTR:TM01:VERSIONMINORRAW.FLNK",16777215,1,"PLC:HTR:TM01:VERSIONMINORRAW.FLNK")
#! Link("PLC:HTR:TM01:VERSIONMINORRAW.FLNK","PLC:HTR:TM01:VERSIONMINOR")
#! Record("PLC:HTR:TM01:VERSIONMAJOR",3040,2834,0,0,"PLC:HTR:TM01:VERSIONMAJOR")
#! Field("PLC:HTR:TM01:VERSIONMAJOR.INPA",16777215,0,"PLC:HTR:TM01:VERSIONMAJOR.INPA")
#! Link("PLC:HTR:TM01:VERSIONMAJOR.INPA","PLC:HTR:TM01:VERSIONMAJORRAW.VAL")
#! Field("PLC:HTR:TM01:VERSIONMAJOR.HIGH",16777215,0,"PLC:HTR:TM01:VERSIONMAJOR.HIGH")
#! Field("PLC:HTR:TM01:VERSIONMAJOR.LOW",16777215,0,"PLC:HTR:TM01:VERSIONMAJOR.LOW")
#! Field("PLC:HTR:TM01:VERSIONMAJOR.INPB",16777215,1,"PLC:HTR:TM01:VERSIONMAJOR.INPB")
#! Link("PLC:HTR:TM01:VERSIONMAJOR.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Field("PLC:HTR:TM01:VERSIONMAJOR.VAL",16777215,0,"PLC:HTR:TM01:VERSIONMAJOR.VAL")
#! Record("PLC:HTR:TM01:VERSIONMINOR",3060,3194,0,0,"PLC:HTR:TM01:VERSIONMINOR")
#! Field("PLC:HTR:TM01:VERSIONMINOR.HIGH",16777215,0,"PLC:HTR:TM01:VERSIONMINOR.HIGH")
#! Field("PLC:HTR:TM01:VERSIONMINOR.INPA",16777215,0,"PLC:HTR:TM01:VERSIONMINOR.INPA")
#! Link("PLC:HTR:TM01:VERSIONMINOR.INPA","PLC:HTR:TM01:VERSIONMINORRAW.VAL")
#! Field("PLC:HTR:TM01:VERSIONMINOR.LOW",16777215,0,"PLC:HTR:TM01:VERSIONMINOR.LOW")
#! Field("PLC:HTR:TM01:VERSIONMINOR.INPB",16777215,1,"PLC:HTR:TM01:VERSIONMINOR.INPB")
#! Link("PLC:HTR:TM01:VERSIONMINOR.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Field("PLC:HTR:TM01:VERSIONMINOR.VAL",16777215,0,"PLC:HTR:TM01:VERSIONMINOR.VAL")
#! Record("PLC:HTR:TM01:VERSIONREVRAW",2780,3687,0,1,"PLC:HTR:TM01:VERSIONREVRAW")
#! Field("PLC:HTR:TM01:VERSIONREVRAW.FLNK",16777215,1,"PLC:HTR:TM01:VERSIONREVRAW.FLNK")
#! Link("PLC:HTR:TM01:VERSIONREVRAW.FLNK","PLC:HTR:TM01:VERSIONREV")
#! Field("PLC:HTR:TM01:VERSIONREVRAW.VAL",16777215,1,"PLC:HTR:TM01:VERSIONREVRAW.VAL")
#! Record("PLC:HTR:TM01:VERSIONREV",3060,3594,0,0,"PLC:HTR:TM01:VERSIONREV")
#! Field("PLC:HTR:TM01:VERSIONREV.HIGH",16777215,0,"PLC:HTR:TM01:VERSIONREV.HIGH")
#! Field("PLC:HTR:TM01:VERSIONREV.LOW",16777215,0,"PLC:HTR:TM01:VERSIONREV.LOW")
#! Field("PLC:HTR:TM01:VERSIONREV.INPA",16777215,0,"PLC:HTR:TM01:VERSIONREV.INPA")
#! Link("PLC:HTR:TM01:VERSIONREV.INPA","PLC:HTR:TM01:VERSIONREVRAW.VAL")
#! Field("PLC:HTR:TM01:VERSIONREV.INPB",16777215,1,"PLC:HTR:TM01:VERSIONREV.INPB")
#! Link("PLC:HTR:TM01:VERSIONREV.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Field("PLC:HTR:TM01:VERSIONREV.VAL",16777215,0,"PLC:HTR:TM01:VERSIONREV.VAL")
#! Record("PLC:HTR:TM01:SERIALNUMBERRAW",1960,3787,0,1,"PLC:HTR:TM01:SERIALNUMBERRAW")
#! Field("PLC:HTR:TM01:SERIALNUMBERRAW.FLNK",16777215,1,"PLC:HTR:TM01:SERIALNUMBERRAW.FLNK")
#! Link("PLC:HTR:TM01:SERIALNUMBERRAW.FLNK","PLC:HTR:TM01:SERIALNUMBER")
#! Field("PLC:HTR:TM01:SERIALNUMBERRAW.VAL",16777215,0,"PLC:HTR:TM01:SERIALNUMBERRAW.VAL")
#! Record("PLC:HTR:TM01:SERIALNUMBER",2220,3822,0,0,"PLC:HTR:TM01:SERIALNUMBER")
#! Field("PLC:HTR:TM01:SERIALNUMBER.INPA",16777215,0,"PLC:HTR:TM01:SERIALNUMBER.INPA")
#! Link("PLC:HTR:TM01:SERIALNUMBER.INPA","PLC:HTR:TM01:SERIALNUMBERRAW.VAL")
#! Field("PLC:HTR:TM01:SERIALNUMBER.INPB",16777215,1,"PLC:HTR:TM01:SERIALNUMBER.INPB")
#! Link("PLC:HTR:TM01:SERIALNUMBER.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:COMMLINK",340,43,0,0,"PLC:HTR:TM01:COMMLINK")
#! Field("PLC:HTR:TM01:COMMLINK.INP",16777215,0,"PLC:HTR:TM01:COMMLINK.INP")
#! Link("PLC:HTR:TM01:COMMLINK.INP","PLC:HTR:TM01:HEARTBEATRAW.SEVR")
#! Field("PLC:HTR:TM01:COMMLINK.FLNK",16777215,1,"PLC:HTR:TM01:COMMLINK.FLNK")
#! Link("PLC:HTR:TM01:COMMLINK.FLNK","PLC:HTR:TM01:HEARTBEATCALC")
#! Record("PLC:HTR:TM01:HEARTBEATE10",1100,2447,0,1,"PLC:HTR:TM01:HEARTBEATE10")
#! Field("PLC:HTR:TM01:HEARTBEATE10.VAL",16777215,1,"PLC:HTR:TM01:HEARTBEATE10.VAL")
#! Field("PLC:HTR:TM01:HEARTBEATE10.INPB",16777215,0,"PLC:HTR:TM01:HEARTBEATE10.INPB")
#! Link("PLC:HTR:TM01:HEARTBEATE10.INPB","PLC:HTR:TM01:HEARTBEATE10.VAL")
#! Field("PLC:HTR:TM01:HEARTBEATE10.FLNK",16777215,1,"PLC:HTR:TM01:HEARTBEATE10.FLNK")
#! Link("PLC:HTR:TM01:HEARTBEATE10.FLNK","PLC:HTR:TM01:HEARTBEATECT")
#! Field("PLC:HTR:TM01:HEARTBEATE10.INPA",16777215,0,"PLC:HTR:TM01:HEARTBEATE10.INPA")
#! Link("PLC:HTR:TM01:HEARTBEATE10.INPA","PLC:HTR:TM01:HEARTBEATE09.B")
#! Record("PLC:HTR:TM01:DOCPREFIXRAW",880,2867,0,1,"PLC:HTR:TM01:DOCPREFIXRAW")
#! Field("PLC:HTR:TM01:DOCPREFIXRAW.FLNK",16777215,1,"PLC:HTR:TM01:DOCPREFIXRAW.FLNK")
#! Link("PLC:HTR:TM01:DOCPREFIXRAW.FLNK","PLC:HTR:TM01:DOCPREFIXCALC")
#! Field("PLC:HTR:TM01:DOCPREFIXRAW.VAL",16777215,1,"PLC:HTR:TM01:DOCPREFIXRAW.VAL")
#! Record("PLC:HTR:TM01:DOCPREFIXCALC",1160,2887,0,0,"PLC:HTR:TM01:DOCPREFIXCALC")
#! Field("PLC:HTR:TM01:DOCPREFIXCALC.INPA",16777215,0,"PLC:HTR:TM01:DOCPREFIXCALC.INPA")
#! Link("PLC:HTR:TM01:DOCPREFIXCALC.INPA","PLC:HTR:TM01:DOCPREFIXRAW.VAL")
#! Field("PLC:HTR:TM01:DOCPREFIXCALC.FLNK",16777215,1,"PLC:HTR:TM01:DOCPREFIXCALC.FLNK")
#! Link("PLC:HTR:TM01:DOCPREFIXCALC.FLNK","PLC:HTR:TM01:DOCPREFIX")
#! Field("PLC:HTR:TM01:DOCPREFIXCALC.VAL",16777215,1,"PLC:HTR:TM01:DOCPREFIXCALC.VAL")
#! Field("PLC:HTR:TM01:DOCPREFIXCALC.INPB",16777215,1,"PLC:HTR:TM01:DOCPREFIXCALC.INPB")
#! Link("PLC:HTR:TM01:DOCPREFIXCALC.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:DOCPREFIX",1460,2630,0,0,"PLC:HTR:TM01:DOCPREFIX")
#! Field("PLC:HTR:TM01:DOCPREFIX.INP",16777215,0,"PLC:HTR:TM01:DOCPREFIX.INP")
#! Link("PLC:HTR:TM01:DOCPREFIX.INP","PLC:HTR:TM01:DOCPREFIXCALC.VAL")
#! Record("PLC:HTR:TM01:DOCSERIESRAW",880,3087,0,1,"PLC:HTR:TM01:DOCSERIESRAW")
#! Field("PLC:HTR:TM01:DOCSERIESRAW.FLNK",16777215,1,"PLC:HTR:TM01:DOCSERIESRAW.FLNK")
#! Link("PLC:HTR:TM01:DOCSERIESRAW.FLNK","PLC:HTR:TM01:DOCSERIES")
#! Field("PLC:HTR:TM01:DOCSERIESRAW.VAL",16777215,1,"PLC:HTR:TM01:DOCSERIESRAW.VAL")
#! Record("PLC:HTR:TM01:DOCSERIES",1160,3122,0,0,"PLC:HTR:TM01:DOCSERIES")
#! Field("PLC:HTR:TM01:DOCSERIES.INPA",16777215,0,"PLC:HTR:TM01:DOCSERIES.INPA")
#! Link("PLC:HTR:TM01:DOCSERIES.INPA","PLC:HTR:TM01:DOCSERIESRAW.VAL")
#! Field("PLC:HTR:TM01:DOCSERIES.INPB",16777215,1,"PLC:HTR:TM01:DOCSERIES.INPB")
#! Link("PLC:HTR:TM01:DOCSERIES.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:DOCBASERAW",878,3307,0,1,"PLC:HTR:TM01:DOCBASERAW")
#! Field("PLC:HTR:TM01:DOCBASERAW.FLNK",16777215,1,"PLC:HTR:TM01:DOCBASERAW.FLNK")
#! Link("PLC:HTR:TM01:DOCBASERAW.FLNK","PLC:HTR:TM01:DOCBASE")
#! Field("PLC:HTR:TM01:DOCBASERAW.VAL",16777215,1,"PLC:HTR:TM01:DOCBASERAW.VAL")
#! Record("PLC:HTR:TM01:DOCBASE",1160,3342,0,0,"PLC:HTR:TM01:DOCBASE")
#! Field("PLC:HTR:TM01:DOCBASE.INPA",16777215,0,"PLC:HTR:TM01:DOCBASE.INPA")
#! Link("PLC:HTR:TM01:DOCBASE.INPA","PLC:HTR:TM01:DOCBASERAW.VAL")
#! Field("PLC:HTR:TM01:DOCBASE.INPB",16777215,1,"PLC:HTR:TM01:DOCBASE.INPB")
#! Link("PLC:HTR:TM01:DOCBASE.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:DOCSUFFIXRAW",878,3567,0,1,"PLC:HTR:TM01:DOCSUFFIXRAW")
#! Field("PLC:HTR:TM01:DOCSUFFIXRAW.FLNK",16777215,1,"PLC:HTR:TM01:DOCSUFFIXRAW.FLNK")
#! Link("PLC:HTR:TM01:DOCSUFFIXRAW.FLNK","PLC:HTR:TM01:DOCSUFFIX")
#! Field("PLC:HTR:TM01:DOCSUFFIXRAW.VAL",16777215,1,"PLC:HTR:TM01:DOCSUFFIXRAW.VAL")
#! Record("PLC:HTR:TM01:DOCSUFFIX",1160,3602,0,0,"PLC:HTR:TM01:DOCSUFFIX")
#! Field("PLC:HTR:TM01:DOCSUFFIX.INPA",16777215,0,"PLC:HTR:TM01:DOCSUFFIX.INPA")
#! Link("PLC:HTR:TM01:DOCSUFFIX.INPA","PLC:HTR:TM01:DOCSUFFIXRAW.VAL")
#! Field("PLC:HTR:TM01:DOCSUFFIX.INPB",16777215,1,"PLC:HTR:TM01:DOCSUFFIX.INPB")
#! Link("PLC:HTR:TM01:DOCSUFFIX.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:DOCREVRAW",874,3787,0,1,"PLC:HTR:TM01:DOCREVRAW")
#! Field("PLC:HTR:TM01:DOCREVRAW.FLNK",16777215,1,"PLC:HTR:TM01:DOCREVRAW.FLNK")
#! Link("PLC:HTR:TM01:DOCREVRAW.FLNK","PLC:HTR:TM01:DOCREV")
#! Field("PLC:HTR:TM01:DOCREVRAW.VAL",16777215,1,"PLC:HTR:TM01:DOCREVRAW.VAL")
#! Record("PLC:HTR:TM01:DOCREV",1154,3822,0,0,"PLC:HTR:TM01:DOCREV")
#! Field("PLC:HTR:TM01:DOCREV.INPA",16777215,0,"PLC:HTR:TM01:DOCREV.INPA")
#! Link("PLC:HTR:TM01:DOCREV.INPA","PLC:HTR:TM01:DOCREVRAW.VAL")
#! Field("PLC:HTR:TM01:DOCREV.INPB",16777215,1,"PLC:HTR:TM01:DOCREV.INPB")
#! Link("PLC:HTR:TM01:DOCREV.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:SUBSYSTEM",3320,2816,0,1,"PLC:HTR:TM01:SUBSYSTEM")
#! Record("PLC:HTR:TM01:PLCADMINVMAJRAW",2720,2087,0,1,"PLC:HTR:TM01:PLCADMINVMAJRAW")
#! Field("PLC:HTR:TM01:PLCADMINVMAJRAW.FLNK",16777215,1,"PLC:HTR:TM01:PLCADMINVMAJRAW.FLNK")
#! Link("PLC:HTR:TM01:PLCADMINVMAJRAW.FLNK","PLC:HTR:TM01:PLCADMINVMAJ")
#! Field("PLC:HTR:TM01:PLCADMINVMAJRAW.VAL",16777215,1,"PLC:HTR:TM01:PLCADMINVMAJRAW.VAL")
#! Record("PLC:HTR:TM01:PLCADMINVMAJ",3020,2050,0,0,"PLC:HTR:TM01:PLCADMINVMAJ")
#! Field("PLC:HTR:TM01:PLCADMINVMAJ.INPA",16777215,0,"PLC:HTR:TM01:PLCADMINVMAJ.INPA")
#! Link("PLC:HTR:TM01:PLCADMINVMAJ.INPA","PLC:HTR:TM01:PLCADMINVMAJRAW.VAL")
#! Field("PLC:HTR:TM01:PLCADMINVMAJ.INPB",16777215,1,"PLC:HTR:TM01:PLCADMINVMAJ.INPB")
#! Link("PLC:HTR:TM01:PLCADMINVMAJ.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:PLCADMINVMINRAW",2720,2327,0,1,"PLC:HTR:TM01:PLCADMINVMINRAW")
#! Field("PLC:HTR:TM01:PLCADMINVMINRAW.FLNK",16777215,1,"PLC:HTR:TM01:PLCADMINVMINRAW.FLNK")
#! Link("PLC:HTR:TM01:PLCADMINVMINRAW.FLNK","PLC:HTR:TM01:PLCADMINVMIN")
#! Field("PLC:HTR:TM01:PLCADMINVMINRAW.VAL",16777215,1,"PLC:HTR:TM01:PLCADMINVMINRAW.VAL")
#! Record("PLC:HTR:TM01:PLCADMINVMIN",3020,2290,0,0,"PLC:HTR:TM01:PLCADMINVMIN")
#! Field("PLC:HTR:TM01:PLCADMINVMIN.INPA",16777215,0,"PLC:HTR:TM01:PLCADMINVMIN.INPA")
#! Link("PLC:HTR:TM01:PLCADMINVMIN.INPA","PLC:HTR:TM01:PLCADMINVMINRAW.VAL")
#! Field("PLC:HTR:TM01:PLCADMINVMIN.INPB",16777215,1,"PLC:HTR:TM01:PLCADMINVMIN.INPB")
#! Link("PLC:HTR:TM01:PLCADMINVMIN.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:PLCADMINVREVRAW",2720,2567,0,1,"PLC:HTR:TM01:PLCADMINVREVRAW")
#! Field("PLC:HTR:TM01:PLCADMINVREVRAW.FLNK",16777215,1,"PLC:HTR:TM01:PLCADMINVREVRAW.FLNK")
#! Link("PLC:HTR:TM01:PLCADMINVREVRAW.FLNK","PLC:HTR:TM01:PLCADMINVREV")
#! Field("PLC:HTR:TM01:PLCADMINVREVRAW.VAL",16777215,1,"PLC:HTR:TM01:PLCADMINVREVRAW.VAL")
#! Record("PLC:HTR:TM01:PLCADMINVREV",3020,2530,0,0,"PLC:HTR:TM01:PLCADMINVREV")
#! Field("PLC:HTR:TM01:PLCADMINVREV.INPA",16777215,0,"PLC:HTR:TM01:PLCADMINVREV.INPA")
#! Link("PLC:HTR:TM01:PLCADMINVREV.INPA","PLC:HTR:TM01:PLCADMINVREVRAW.VAL")
#! Field("PLC:HTR:TM01:PLCADMINVREV.INPB",16777215,1,"PLC:HTR:TM01:PLCADMINVREV.INPB")
#! Link("PLC:HTR:TM01:PLCADMINVREV.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:PROGPLCATMAXRAW",2700,727,0,0,"PLC:HTR:TM01:PROGPLCATMAXRAW")
#! Field("PLC:HTR:TM01:PROGPLCATMAXRAW.FLNK",16777215,1,"PLC:HTR:TM01:PROGPLCATMAXRAW.FLNK")
#! Link("PLC:HTR:TM01:PROGPLCATMAXRAW.FLNK","PLC:HTR:TM01:PROGPLCATMAX")
#! Field("PLC:HTR:TM01:PROGPLCATMAXRAW.VAL",16777215,1,"PLC:HTR:TM01:PROGPLCATMAXRAW.VAL")
#! Record("PLC:HTR:TM01:PROGPLCATLSTRAW",2700,567,0,0,"PLC:HTR:TM01:PROGPLCATLSTRAW")
#! Field("PLC:HTR:TM01:PROGPLCATLSTRAW.FLNK",16777215,1,"PLC:HTR:TM01:PROGPLCATLSTRAW.FLNK")
#! Link("PLC:HTR:TM01:PROGPLCATLSTRAW.FLNK","PLC:HTR:TM01:PROGPLCATLST")
#! Field("PLC:HTR:TM01:PROGPLCATLSTRAW.VAL",16777215,1,"PLC:HTR:TM01:PROGPLCATLSTRAW.VAL")
#! Record("PLC:HTR:TM01:PROGPLCATLST",3000,602,0,0,"PLC:HTR:TM01:PROGPLCATLST")
#! Field("PLC:HTR:TM01:PROGPLCATLST.INPA",16777215,0,"PLC:HTR:TM01:PROGPLCATLST.INPA")
#! Link("PLC:HTR:TM01:PROGPLCATLST.INPA","PLC:HTR:TM01:PROGPLCATLSTRAW.VAL")
#! Field("PLC:HTR:TM01:PROGPLCATLST.INPB",16777215,1,"PLC:HTR:TM01:PROGPLCATLST.INPB")
#! Link("PLC:HTR:TM01:PROGPLCATLST.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:PROGPLCATMAX",3000,762,0,0,"PLC:HTR:TM01:PROGPLCATMAX")
#! Field("PLC:HTR:TM01:PROGPLCATMAX.INPA",16777215,0,"PLC:HTR:TM01:PROGPLCATMAX.INPA")
#! Link("PLC:HTR:TM01:PROGPLCATMAX.INPA","PLC:HTR:TM01:PROGPLCATMAXRAW.VAL")
#! Field("PLC:HTR:TM01:PROGPLCATMAX.INPB",16777215,1,"PLC:HTR:TM01:PROGPLCATMAX.INPB")
#! Link("PLC:HTR:TM01:PROGPLCATMAX.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:PLCADMINTAG",2120,876,0,1,"PLC:HTR:TM01:PLCADMINTAG")
#! Record("PLC:HTR:TM01:TASKMAINTLSTRAW",2700,247,0,0,"PLC:HTR:TM01:TASKMAINTLSTRAW")
#! Field("PLC:HTR:TM01:TASKMAINTLSTRAW.FLNK",16777215,1,"PLC:HTR:TM01:TASKMAINTLSTRAW.FLNK")
#! Link("PLC:HTR:TM01:TASKMAINTLSTRAW.FLNK","PLC:HTR:TM01:TASKMAINTLST")
#! Field("PLC:HTR:TM01:TASKMAINTLSTRAW.VAL",16777215,1,"PLC:HTR:TM01:TASKMAINTLSTRAW.VAL")
#! Record("PLC:HTR:TM01:TASKMAINTLST",3000,282,0,0,"PLC:HTR:TM01:TASKMAINTLST")
#! Field("PLC:HTR:TM01:TASKMAINTLST.INPA",16777215,0,"PLC:HTR:TM01:TASKMAINTLST.INPA")
#! Link("PLC:HTR:TM01:TASKMAINTLST.INPA","PLC:HTR:TM01:TASKMAINTLSTRAW.VAL")
#! Field("PLC:HTR:TM01:TASKMAINTLST.INPB",16777215,1,"PLC:HTR:TM01:TASKMAINTLST.INPB")
#! Link("PLC:HTR:TM01:TASKMAINTLST.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:TASKMAINTMAXRAW",2700,407,0,0,"PLC:HTR:TM01:TASKMAINTMAXRAW")
#! Field("PLC:HTR:TM01:TASKMAINTMAXRAW.FLNK",16777215,1,"PLC:HTR:TM01:TASKMAINTMAXRAW.FLNK")
#! Link("PLC:HTR:TM01:TASKMAINTMAXRAW.FLNK","PLC:HTR:TM01:TASKMAINTMAX")
#! Field("PLC:HTR:TM01:TASKMAINTMAXRAW.VAL",16777215,1,"PLC:HTR:TM01:TASKMAINTMAXRAW.VAL")
#! Record("PLC:HTR:TM01:TASKMAINTMAX",3000,442,0,0,"PLC:HTR:TM01:TASKMAINTMAX")
#! Field("PLC:HTR:TM01:TASKMAINTMAX.INPA",16777215,0,"PLC:HTR:TM01:TASKMAINTMAX.INPA")
#! Link("PLC:HTR:TM01:TASKMAINTMAX.INPA","PLC:HTR:TM01:TASKMAINTMAXRAW.VAL")
#! Field("PLC:HTR:TM01:TASKMAINTMAX.INPB",16777215,1,"PLC:HTR:TM01:TASKMAINTMAX.INPB")
#! Link("PLC:HTR:TM01:TASKMAINTMAX.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:PROG1TLSTRAW",2700,887,0,0,"PLC:HTR:TM01:PROG1TLSTRAW")
#! Field("PLC:HTR:TM01:PROG1TLSTRAW.FLNK",16777215,1,"PLC:HTR:TM01:PROG1TLSTRAW.FLNK")
#! Link("PLC:HTR:TM01:PROG1TLSTRAW.FLNK","PLC:HTR:TM01:PROG1TLST")
#! Field("PLC:HTR:TM01:PROG1TLSTRAW.VAL",16777215,1,"PLC:HTR:TM01:PROG1TLSTRAW.VAL")
#! Record("PLC:HTR:TM01:PROG1TMAXRAW",2700,1047,0,0,"PLC:HTR:TM01:PROG1TMAXRAW")
#! Field("PLC:HTR:TM01:PROG1TMAXRAW.FLNK",16777215,1,"PLC:HTR:TM01:PROG1TMAXRAW.FLNK")
#! Link("PLC:HTR:TM01:PROG1TMAXRAW.FLNK","PLC:HTR:TM01:PROG1TMAX")
#! Field("PLC:HTR:TM01:PROG1TMAXRAW.VAL",16777215,1,"PLC:HTR:TM01:PROG1TMAXRAW.VAL")
#! Record("PLC:HTR:TM01:PROG1TLST",3000,922,0,0,"PLC:HTR:TM01:PROG1TLST")
#! Field("PLC:HTR:TM01:PROG1TLST.INPA",16777215,0,"PLC:HTR:TM01:PROG1TLST.INPA")
#! Link("PLC:HTR:TM01:PROG1TLST.INPA","PLC:HTR:TM01:PROG1TLSTRAW.VAL")
#! Field("PLC:HTR:TM01:PROG1TLST.INPB",16777215,1,"PLC:HTR:TM01:PROG1TLST.INPB")
#! Link("PLC:HTR:TM01:PROG1TLST.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:PROG1TMAX",3000,1082,0,0,"PLC:HTR:TM01:PROG1TMAX")
#! Field("PLC:HTR:TM01:PROG1TMAX.INPA",16777215,0,"PLC:HTR:TM01:PROG1TMAX.INPA")
#! Link("PLC:HTR:TM01:PROG1TMAX.INPA","PLC:HTR:TM01:PROG1TMAXRAW.VAL")
#! Field("PLC:HTR:TM01:PROG1TMAX.INPB",16777215,1,"PLC:HTR:TM01:PROG1TMAX.INPB")
#! Link("PLC:HTR:TM01:PROG1TMAX.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:PROG2TLSTRAW",2700,1207,0,0,"PLC:HTR:TM01:PROG2TLSTRAW")
#! Field("PLC:HTR:TM01:PROG2TLSTRAW.FLNK",16777215,1,"PLC:HTR:TM01:PROG2TLSTRAW.FLNK")
#! Link("PLC:HTR:TM01:PROG2TLSTRAW.FLNK","PLC:HTR:TM01:PROG2TLST")
#! Field("PLC:HTR:TM01:PROG2TLSTRAW.VAL",16777215,1,"PLC:HTR:TM01:PROG2TLSTRAW.VAL")
#! Record("PLC:HTR:TM01:PROG2TMAXRAW",2700,1367,0,0,"PLC:HTR:TM01:PROG2TMAXRAW")
#! Field("PLC:HTR:TM01:PROG2TMAXRAW.FLNK",16777215,1,"PLC:HTR:TM01:PROG2TMAXRAW.FLNK")
#! Link("PLC:HTR:TM01:PROG2TMAXRAW.FLNK","PLC:HTR:TM01:PROG2TMAX")
#! Field("PLC:HTR:TM01:PROG2TMAXRAW.VAL",16777215,1,"PLC:HTR:TM01:PROG2TMAXRAW.VAL")
#! Record("PLC:HTR:TM01:PROG2TLST",3000,1242,0,0,"PLC:HTR:TM01:PROG2TLST")
#! Field("PLC:HTR:TM01:PROG2TLST.INPA",16777215,0,"PLC:HTR:TM01:PROG2TLST.INPA")
#! Link("PLC:HTR:TM01:PROG2TLST.INPA","PLC:HTR:TM01:PROG2TLSTRAW.VAL")
#! Field("PLC:HTR:TM01:PROG2TLST.INPB",16777215,1,"PLC:HTR:TM01:PROG2TLST.INPB")
#! Link("PLC:HTR:TM01:PROG2TLST.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:PROG2TMAX",3000,1402,0,0,"PLC:HTR:TM01:PROG2TMAX")
#! Field("PLC:HTR:TM01:PROG2TMAX.INPA",16777215,0,"PLC:HTR:TM01:PROG2TMAX.INPA")
#! Link("PLC:HTR:TM01:PROG2TMAX.INPA","PLC:HTR:TM01:PROG2TMAXRAW.VAL")
#! Field("PLC:HTR:TM01:PROG2TMAX.INPB",16777215,1,"PLC:HTR:TM01:PROG2TMAX.INPB")
#! Link("PLC:HTR:TM01:PROG2TMAX.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:PROG3TLSTRAW",2700,1527,0,0,"PLC:HTR:TM01:PROG3TLSTRAW")
#! Field("PLC:HTR:TM01:PROG3TLSTRAW.FLNK",16777215,1,"PLC:HTR:TM01:PROG3TLSTRAW.FLNK")
#! Link("PLC:HTR:TM01:PROG3TLSTRAW.FLNK","PLC:HTR:TM01:PROG3TLST")
#! Field("PLC:HTR:TM01:PROG3TLSTRAW.VAL",16777215,1,"PLC:HTR:TM01:PROG3TLSTRAW.VAL")
#! Record("PLC:HTR:TM01:PROG3TMAXRAW",2700,1687,0,0,"PLC:HTR:TM01:PROG3TMAXRAW")
#! Field("PLC:HTR:TM01:PROG3TMAXRAW.FLNK",16777215,1,"PLC:HTR:TM01:PROG3TMAXRAW.FLNK")
#! Link("PLC:HTR:TM01:PROG3TMAXRAW.FLNK","PLC:HTR:TM01:PROG3TMAX")
#! Field("PLC:HTR:TM01:PROG3TMAXRAW.VAL",16777215,1,"PLC:HTR:TM01:PROG3TMAXRAW.VAL")
#! Record("PLC:HTR:TM01:PROG3TMAX",3000,1722,0,0,"PLC:HTR:TM01:PROG3TMAX")
#! Field("PLC:HTR:TM01:PROG3TMAX.INPA",16777215,0,"PLC:HTR:TM01:PROG3TMAX.INPA")
#! Link("PLC:HTR:TM01:PROG3TMAX.INPA","PLC:HTR:TM01:PROG3TMAXRAW.VAL")
#! Field("PLC:HTR:TM01:PROG3TMAX.INPB",16777215,1,"PLC:HTR:TM01:PROG3TMAX.INPB")
#! Link("PLC:HTR:TM01:PROG3TMAX.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:PROG3TLST",3000,1562,0,0,"PLC:HTR:TM01:PROG3TLST")
#! Field("PLC:HTR:TM01:PROG3TLST.INPA",16777215,0,"PLC:HTR:TM01:PROG3TLST.INPA")
#! Link("PLC:HTR:TM01:PROG3TLST.INPA","PLC:HTR:TM01:PROG3TLSTRAW.VAL")
#! Field("PLC:HTR:TM01:PROG3TLST.INPB",16777215,1,"PLC:HTR:TM01:PROG3TLST.INPB")
#! Link("PLC:HTR:TM01:PROG3TLST.INPB","PLC:HTR:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:HTR:TM01:STATSUMY",1600,4643,0,1,"PLC:HTR:TM01:STATSUMY")
#! Field("PLC:HTR:TM01:STATSUMY.INPB",16777215,1,"PLC:HTR:TM01:STATSUMY.INPB")
#! Link("PLC:HTR:TM01:STATSUMY.INPB","PLC:HTR:TM01:HEARTBEATSUM.VAL")
#! Field("PLC:HTR:TM01:STATSUMY.INPC",16777215,1,"PLC:HTR:TM01:STATSUMY.INPC")
#! Link("PLC:HTR:TM01:STATSUMY.INPC","PLC:HTR:TM01:FAULTSTATUS.VAL")
#! Field("PLC:HTR:TM01:STATSUMY.INPD",16777215,1,"PLC:HTR:TM01:STATSUMY.INPD")
#! Link("PLC:HTR:TM01:STATSUMY.INPD","PLC:HTR:TM01:KEYSTATUS.VAL")
#! Field("PLC:HTR:TM01:STATSUMY.INPE",16777215,1,"PLC:HTR:TM01:STATSUMY.INPE")
#! Link("PLC:HTR:TM01:STATSUMY.INPE","PLC:HTR:TM01:DEVICESTATUS.VAL")
#! Field("PLC:HTR:TM01:STATSUMY.INPF",16777215,1,"PLC:HTR:TM01:STATSUMY.INPF")
#! Link("PLC:HTR:TM01:STATSUMY.INPF","PLC:HTR:TM01:VERSIONMAJOR.VAL")
#! Field("PLC:HTR:TM01:STATSUMY.INPG",16777215,1,"PLC:HTR:TM01:STATSUMY.INPG")
#! Link("PLC:HTR:TM01:STATSUMY.INPG","PLC:HTR:TM01:VERSIONMINOR.VAL")
#! Field("PLC:HTR:TM01:STATSUMY.INPH",16777215,1,"PLC:HTR:TM01:STATSUMY.INPH")
#! Link("PLC:HTR:TM01:STATSUMY.INPH","PLC:HTR:TM01:VERSIONREV.VAL")
#! Field("PLC:HTR:TM01:STATSUMY.SEVR",16777215,0,"PLC:HTR:TM01:STATSUMY.SEVR")
#! Field("PLC:HTR:TM01:STATSUMY.INPA",16777215,0,"PLC:HTR:TM01:STATSUMY.INPA")
#! Link("PLC:HTR:TM01:STATSUMY.INPA","PLC:HTR:TM01:STATSUMY.SEVR")
# -*- shell-script -*-
# AI records that read statistical information from EtherIP
# driver/device
#
# IOC:  prefix to records
# PLC:  PLC to use
# TAG:  queried tag (leads to PLC's ScanList)

record(ai, "PLC:HTR:TM01:PLC_ERRORS")
{
	field(SCAN, ".5 second")
	field(DTYP, "EtherIP")
	field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01 PLC_ERRORS")
	field(EGUF, "5")
	field(EGU, "Errors")
	field(HOPR, "5")
	field(LOPR, "0")
}


record(ai, "PLC:HTR:TM01:PLC_TASK_SLOW")
{
	field(SCAN, ".5 second")
	field(DTYP, "EtherIP")
	field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01 PLC_TASK_SLOW")
	field(EGUF, "5")
	field(EGU, "Holdups")
	field(HOPR, "5")
	field(LOPR, "0")
}

record(ai, "PLC:HTR:TM01:LIST_TICKS")
{
	field(SCAN, ".5 second")
	field(DTYP, "EtherIP")
	field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01 LIST_TICKS")
	field(EGUF, "5")
	field(EGU, "vx ticks")
	field(HOPR, "5")
	field(LOPR, "0")
}

record(ai, "PLC:HTR:TM01:LIST_SCAN_TIME")
{
	field(SCAN, ".5 second")
	field(DTYP, "EtherIP")
	field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01 LIST_SCAN_TIME")
	field(EGUF, "1")
	field(EGU, "s")
	field(HOPR, "1")
	field(LOPR, "0")
	field(PREC, "5")
}

record(ai, "PLC:HTR:TM01:LIST_MIN_SCAN_TIME")
{
	field(SCAN, ".5 second")
	field(DTYP, "EtherIP")
	field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01 LIST_MIN_SCAN_TIME")
	field(EGUF, "1")
	field(EGU, "s")
	field(HOPR, "1")
	field(LOPR, "0")
	field(PREC, "5")
}

record(ai, "PLC:HTR:TM01:LIST_MAX_SCAN_TIME")
{
	field(SCAN, ".5 second")
	field(DTYP, "EtherIP")
	field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01 LIST_MAX_SCAN_TIME")
	field(EGUF, "1")
	field(EGU, "s")
	field(HOPR, "1")
	field(LOPR, "0")
	field(PREC, "5")
}

record(ai, "PLC:HTR:TM01:TAG_TRANSFER_TIME")
{
	field(SCAN, ".5 second")
	field(DTYP, "EtherIP")
	field(INP, "@PLC_HTR_TM01 PLCADMIN_PLC_HTR_TM01 TAG_TRANSFER_TIME")
	field(EGUF, "1000000000")
	field(EGU, "s")
	field(HOPR, "1")
	field(LOPR, "0")
	field(PREC, "5")
}






#==============================================================================
#
# Abs:  Database template for plcinfo.
#
# Name: ab-plc-info-lcls2.template
#
# Macros:
#       CR          Panel or crate number
#       NUM_CHANS   Total number of channels
#       UNIT        Unit number of the PLC   
#       LOCA        Location of the PLC
#       LOCATION    Location of the panel
#==============================================================================
record(stringin, "PLC:HTR:TM01:CR1_LOC") {
    field(VAL, "L2KA01-0528")
}

record(longout, "PLC:HTR:TM01:CR1_NUM_CHANS") {
    field(VAL, "40")
}

record(bo, "PLC:HTR:TM01:INITIALIZE") {
    field(DTYP, "EtherIP")
    field(OUT, "@PLC_HTR_TM01 INITIALIZE") 
    field(DESC, "Init")

}
#==============================================================================
#
# Abs:  Database template for plcinfo.
#
# Name: ab-plc-info-lcls2.template
#
# Macros:
#       CR          Panel or crate number
#       NUM_CHANS   Total number of channels
#       UNIT        Unit number of the PLC   
#       LOCA        Location of the PLC
#       LOCATION    Location of the panel
#==============================================================================
record(stringin, "PLC:HTR:TM01:CR2_LOC") {
    field(VAL, "L2KA01-0520")
}

record(longout, "PLC:HTR:TM01:CR2_NUM_CHANS") {
    field(VAL, "40")
}

record(bo, "PLC:HTR:TM01:INITIALIZE") {
    field(DTYP, "EtherIP")
    field(OUT, "@PLC_HTR_TM01 INITIALIZE") 
    field(DESC, "Init")

}
#
# This template is used to control MPS outputs
#
#
# Macros:
#        TYPE  Type of MPS Permit signal- eg: TEMP, FLOW etc.
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS EPICS name for the PV
#        MAD   MAD name for the PV
#==============================================================================
# Temperature PV Alarm status
# Alarm channels are the PV  bit
record(bi, "COLL:HTR:615:TEMP_PERMIT"){
  field(DESC, "CEHTR TEMP Permit Alarm Sts")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 MPSAlarm[0] B 0")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Bypass reset
# Alarm channels are the PV  bit
# Eg: SigResetReq[0].0
# Uses Reset_Index 0 , Uses Channel 0
record(bo, "COLL:HTR:615:TEMP_RESET") {
  field(DESC, "Reset Request")
  field(DTYP, "EtherIP")
  #field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigResetReq[0] B 0")
  field(ZNAM, "RESET")
  field(ONAM, "RESET")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(HIGH, "2")
  field(ASG, "MCC")
}

#
# This template is used to control MPS outputs
#
#
# Macros:
#        TYPE  Type of MPS Permit signal- eg: TEMP, FLOW etc.
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS EPICS name for the PV
#        MAD   MAD name for the PV
#==============================================================================
# Temperature PV Alarm status
# Alarm channels are the PV  bit
record(bi, "COLL:COL0:390:TEMP_PERMIT"){
  field(DESC, "CYC01 TEMP Permit Alarm Sts")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 MPSAlarm[0] B 1")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Bypass reset
# Alarm channels are the PV  bit
# Eg: SigResetReq[0].0
# Uses Reset_Index 0 , Uses Channel 0
record(bo, "COLL:COL0:390:TEMP_RESET") {
  field(DESC, "Reset Request")
  field(DTYP, "EtherIP")
  #field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigResetReq[0] B 1")
  field(ZNAM, "RESET")
  field(ONAM, "RESET")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(HIGH, "2")
  field(ASG, "MCC")
}

#
# This template is used to control MPS outputs
#
#
# Macros:
#        TYPE  Type of MPS Permit signal- eg: TEMP, FLOW etc.
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS EPICS name for the PV
#        MAD   MAD name for the PV
#==============================================================================
# Temperature PV Alarm status
# Alarm channels are the PV  bit
record(bi, "COLL:COL0:470:TEMP_PERMIT"){
  field(DESC, "CXC01 TEMP Permit Alarm Sts")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 MPSAlarm[0] B 2")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Bypass reset
# Alarm channels are the PV  bit
# Eg: SigResetReq[0].0
# Uses Reset_Index 0 , Uses Channel 0
record(bo, "COLL:COL0:470:TEMP_RESET") {
  field(DESC, "Reset Request")
  field(DTYP, "EtherIP")
  #field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigResetReq[0] B 2")
  field(ZNAM, "RESET")
  field(ONAM, "RESET")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(HIGH, "2")
  field(ASG, "MCC")
}

#
# This template is used to control MPS outputs
#
#
# Macros:
#        TYPE  Type of MPS Permit signal- eg: TEMP, FLOW etc.
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS EPICS name for the PV
#        MAD   MAD name for the PV
#==============================================================================
# Temperature PV Alarm status
# Alarm channels are the PV  bit
record(bi, "COLL:COL0:710:TEMP_PERMIT"){
  field(DESC, "CYC03 TEMP Permit Alarm Sts")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 MPSAlarm[0] B 3")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Bypass reset
# Alarm channels are the PV  bit
# Eg: SigResetReq[0].0
# Uses Reset_Index 0 , Uses Channel 0
record(bo, "COLL:COL0:710:TEMP_RESET") {
  field(DESC, "Reset Request")
  field(DTYP, "EtherIP")
  #field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigResetReq[0] B 3")
  field(ZNAM, "RESET")
  field(ONAM, "RESET")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(HIGH, "2")
  field(ASG, "MCC")
}

#
# This template is used to control MPS outputs
#
#
# Macros:
#        TYPE  Type of MPS Permit signal- eg: TEMP, FLOW etc.
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS EPICS name for the PV
#        MAD   MAD name for the PV
#==============================================================================
# Temperature PV Alarm status
# Alarm channels are the PV  bit
record(bi, "COLL:COL0:790:TEMP_PERMIT"){
  field(DESC, "CXC03 TEMP Permit Alarm Sts")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 MPSAlarm[0] B 4")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Bypass reset
# Alarm channels are the PV  bit
# Eg: SigResetReq[0].0
# Uses Reset_Index 0 , Uses Channel 0
record(bo, "COLL:COL0:790:TEMP_RESET") {
  field(DESC, "Reset Request")
  field(DTYP, "EtherIP")
  #field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigResetReq[0] B 4")
  field(ZNAM, "RESET")
  field(ONAM, "RESET")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(HIGH, "2")
  field(ASG, "MCC")
}

#
# This template is used to control MPS outputs
#
#
# Macros:
#        TYPE  Type of MPS Permit signal- eg: TEMP, FLOW etc.
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS EPICS name for the PV
#        MAD   MAD name for the PV
#==============================================================================
# Temperature PV Alarm status
# Alarm channels are the PV  bit
record(bi, "BLEN:HTR:350:TEMP_PERMIT"){
  field(DESC, "BLEN TEMP Permit Alarm Sts")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 MPSAlarm[0] B 5")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Bypass reset
# Alarm channels are the PV  bit
# Eg: SigResetReq[0].0
# Uses Reset_Index 0 , Uses Channel 0
record(bo, "BLEN:HTR:350:TEMP_RESET") {
  field(DESC, "Reset Request")
  field(DTYP, "EtherIP")
  #field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigResetReq[0] B 5")
  field(ZNAM, "RESET")
  field(ONAM, "RESET")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(HIGH, "2")
  field(ASG, "MCC")
}

#
# This template is used to control MPS outputs
#
#
# Macros:
#        TYPE  Type of MPS Permit signal- eg: TEMP, FLOW etc.
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS EPICS name for the PV
#        MAD   MAD name for the PV
#==============================================================================
# Temperature PV Alarm status
# Alarm channels are the PV  bit
record(bi, "COLL:HTR:103:TEMP_PERMIT"){
  field(DESC, "PC0H00 TEMP Permit Alarm Sts")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 MPSAlarm[0] B 6")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Bypass reset
# Alarm channels are the PV  bit
# Eg: SigResetReq[0].0
# Uses Reset_Index 0 , Uses Channel 0
record(bo, "COLL:HTR:103:TEMP_RESET") {
  field(DESC, "Reset Request")
  field(DTYP, "EtherIP")
  #field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigResetReq[0] B 6")
  field(ZNAM, "RESET")
  field(ONAM, "RESET")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(HIGH, "2")
  field(ASG, "MCC")
}

#
# This template is used to control MPS outputs
#
#
# Macros:
#        TYPE  Type of MPS Permit signal- eg: TEMP, FLOW etc.
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS EPICS name for the PV
#        MAD   MAD name for the PV
#==============================================================================
# Temperature PV Alarm status
# Alarm channels are the PV  bit
record(bi, "FARC:DIAG0:530:TEMP_PERMIT"){
  field(DESC, "FCDG0DU TEMP Permit Alarm Sts")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 MPSAlarm[0] B 7")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Bypass reset
# Alarm channels are the PV  bit
# Eg: SigResetReq[0].0
# Uses Reset_Index 0 , Uses Channel 0
record(bo, "FARC:DIAG0:530:TEMP_RESET") {
  field(DESC, "Reset Request")
  field(DTYP, "EtherIP")
  #field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigResetReq[0] B 7")
  field(ZNAM, "RESET")
  field(ONAM, "RESET")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(HIGH, "2")
  field(ASG, "MCC")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:HTR:615:POSX:SUPPLYTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[0] B 0")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:HTR:615:POSX:SUPPLYTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[0] B 0")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:HTR:615:POSX:SUPPLYTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[0] B 0")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:HTR:615:POSX:SUPPLYTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[0] B 0")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:HTR:615:POSX:RETURNTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[0] B 1")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:HTR:615:POSX:RETURNTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[0] B 1")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:HTR:615:POSX:RETURNTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[0] B 1")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:HTR:615:POSX:RETURNTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[0] B 1")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:HTR:615:NEGX:SUPPLYTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[0] B 2")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:HTR:615:NEGX:SUPPLYTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[0] B 2")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:HTR:615:NEGX:SUPPLYTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[0] B 2")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:HTR:615:NEGX:SUPPLYTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[0] B 2")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:HTR:615:NEGX:RETURNTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[0] B 3")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:HTR:615:NEGX:RETURNTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[0] B 3")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:HTR:615:NEGX:RETURNTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[0] B 3")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:HTR:615:NEGX:RETURNTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[0] B 3")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:COL0:390:POSY:SUPPLYTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[0] B 4")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:COL0:390:POSY:SUPPLYTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[0] B 4")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:COL0:390:POSY:SUPPLYTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[0] B 4")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:COL0:390:POSY:SUPPLYTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[0] B 4")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:COL0:390:POSY:RETURNTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[0] B 5")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:COL0:390:POSY:RETURNTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[0] B 5")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:COL0:390:POSY:RETURNTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[0] B 5")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:COL0:390:POSY:RETURNTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[0] B 5")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:COL0:390:NEGY:SUPPLYTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[0] B 6")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:COL0:390:NEGY:SUPPLYTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[0] B 6")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:COL0:390:NEGY:SUPPLYTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[0] B 6")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:COL0:390:NEGY:SUPPLYTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[0] B 6")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:COL0:390:NEGY:RETURNTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[0] B 7")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:COL0:390:NEGY:RETURNTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[0] B 7")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:COL0:390:NEGY:RETURNTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[0] B 7")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:COL0:390:NEGY:RETURNTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[0] B 7")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:COL0:470:POSX:SUPPLYTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[0] B 8")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:COL0:470:POSX:SUPPLYTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[0] B 8")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:COL0:470:POSX:SUPPLYTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[0] B 8")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:COL0:470:POSX:SUPPLYTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[0] B 8")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:COL0:470:POSX:RETURNTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[0] B 9")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:COL0:470:POSX:RETURNTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[0] B 9")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:COL0:470:POSX:RETURNTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[0] B 9")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:COL0:470:POSX:RETURNTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[0] B 9")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:COL0:470:NEGX:SUPPLYTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[0] B 10")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:COL0:470:NEGX:SUPPLYTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[0] B 10")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:COL0:470:NEGX:SUPPLYTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[0] B 10")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:COL0:470:NEGX:SUPPLYTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[0] B 10")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:COL0:470:NEGX:RETURNTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[0] B 11")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:COL0:470:NEGX:RETURNTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[0] B 11")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:COL0:470:NEGX:RETURNTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[0] B 11")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:COL0:470:NEGX:RETURNTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[0] B 11")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:COL0:710:POSY:SUPPLYTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[0] B 12")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:COL0:710:POSY:SUPPLYTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[0] B 12")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:COL0:710:POSY:SUPPLYTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[0] B 12")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:COL0:710:POSY:SUPPLYTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[0] B 12")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:COL0:710:POSY:RETURNTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[0] B 13")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:COL0:710:POSY:RETURNTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[0] B 13")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:COL0:710:POSY:RETURNTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[0] B 13")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:COL0:710:POSY:RETURNTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[0] B 13")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:COL0:710:NEGY:SUPPLYTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[0] B 14")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:COL0:710:NEGY:SUPPLYTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[0] B 14")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:COL0:710:NEGY:SUPPLYTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[0] B 14")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:COL0:710:NEGY:SUPPLYTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[0] B 14")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:COL0:710:NEGY:RETURNTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[0] B 15")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:COL0:710:NEGY:RETURNTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[0] B 15")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:COL0:710:NEGY:RETURNTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[0] B 15")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:COL0:710:NEGY:RETURNTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[0] B 15")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:COL0:790:POSX:SUPPLYTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[1] B 0")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:COL0:790:POSX:SUPPLYTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[1] B 0")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:COL0:790:POSX:SUPPLYTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[1] B 0")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:COL0:790:POSX:SUPPLYTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[1] B 0")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:COL0:790:POSX:RETURNTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[1] B 1")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:COL0:790:POSX:RETURNTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[1] B 1")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:COL0:790:POSX:RETURNTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[1] B 1")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:COL0:790:POSX:RETURNTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[1] B 1")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:COL0:790:NEGX:SUPPLYTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[1] B 2")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:COL0:790:NEGX:SUPPLYTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[1] B 2")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:COL0:790:NEGX:SUPPLYTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[1] B 2")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:COL0:790:NEGX:SUPPLYTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[1] B 2")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:COL0:790:NEGX:RETURNTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[1] B 3")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:COL0:790:NEGX:RETURNTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[1] B 3")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:COL0:790:NEGX:RETURNTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[1] B 3")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:COL0:790:NEGX:RETURNTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[1] B 3")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "BLEN:HTR:350:1:TEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[1] B 4")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "BLEN:HTR:350:1:TEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[1] B 4")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "BLEN:HTR:350:1:TEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[1] B 4")
  info(autosaveFields,"VAL")
}

record(bi, "BLEN:HTR:350:1:TEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[1] B 4")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "BLEN:HTR:350:2:TEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[1] B 5")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "BLEN:HTR:350:2:TEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[1] B 5")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "BLEN:HTR:350:2:TEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[1] B 5")
  info(autosaveFields,"VAL")
}

record(bi, "BLEN:HTR:350:2:TEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[1] B 5")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "BLEN:HTR:350:3:TEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[1] B 6")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "BLEN:HTR:350:3:TEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[1] B 6")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "BLEN:HTR:350:3:TEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[1] B 6")
  info(autosaveFields,"VAL")
}

record(bi, "BLEN:HTR:350:3:TEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[1] B 6")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "BLEN:HTR:350:4:TEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[1] B 7")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "BLEN:HTR:350:4:TEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[1] B 7")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "BLEN:HTR:350:4:TEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[1] B 7")
  info(autosaveFields,"VAL")
}

record(bi, "BLEN:HTR:350:4:TEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[1] B 7")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "BLEN:HTR:350:5:TEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[1] B 8")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "BLEN:HTR:350:5:TEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[1] B 8")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "BLEN:HTR:350:5:TEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[1] B 8")
  info(autosaveFields,"VAL")
}

record(bi, "BLEN:HTR:350:5:TEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[1] B 8")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:HTR:103:TEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[1] B 9")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:HTR:103:TEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[1] B 9")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:HTR:103:TEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[1] B 9")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:HTR:103:TEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[1] B 9")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:HTR:103:RETURNTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[1] B 10")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:HTR:103:RETURNTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[1] B 10")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:HTR:103:RETURNTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[1] B 10")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:HTR:103:RETURNTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[1] B 10")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:HTR:103:FLOWALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[1] B 11")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:HTR:103:FLOWALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[1] B 11")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:HTR:103:FLOWBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[1] B 11")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:HTR:103:FLOWBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[1] B 11")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:HTR:103:2:TEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[1] B 12")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:HTR:103:2:TEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[1] B 12")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:HTR:103:2:TEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[1] B 12")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:HTR:103:2:TEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[1] B 12")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:HTR:103:SUPPLYTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[1] B 13")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:HTR:103:SUPPLYTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[1] B 13")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:HTR:103:SUPPLYTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[1] B 13")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:HTR:103:SUPPLYTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[1] B 13")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "FARC:DIAG0:530:TEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmLatch[1] B 14")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "FARC:DIAG0:530:TEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigAlarmReal[1] B 14")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "FARC:DIAG0:530:TEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_HTR_TM01 SigBypReq[1] B 14")
  info(autosaveFields,"VAL")
}

record(bi, "FARC:DIAG0:530:TEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 SigBypStat[1] B 14")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M1_CH00_TEMP") {
  field(DESC, "BCXH1 Temp 1")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BEND:HTR:480:TEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[0]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M1_CH00_ALIAS") {
    field(VAL,"BEND:HTR:480:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BEND:HTR:480:TEMP") {
  field(DESC, "BCXH1 Temp 1")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M1_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BEND:HTR:480:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[0]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:HTR:480:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BEND:HTR:480:TEMP.HIHI CP")
  field(OUT, "BEND:HTR:480:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:HTR:480:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "BEND:HTR:480:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[0]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:HTR:480:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BEND:HTR:480:TEMP.LOLO CP")
  field(OUT, "BEND:HTR:480:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:HTR:480:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M1_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[1] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M1_CH01_TEMP") {
  field(DESC, "PRL S1 1 Z 7m")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "LLRF:HTR:1:PRLTEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[1]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M1_CH01_ALIAS") {
    field(VAL,"LLRF:HTR:1:PRLTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "LLRF:HTR:1:PRLTEMP") {
  field(DESC, "PRL S1 1 Z 7m")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M1_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "LLRF:HTR:1:PRLTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[1]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:HTR:1:PRLTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "LLRF:HTR:1:PRLTEMP.HIHI CP")
  field(OUT, "LLRF:HTR:1:PRLTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:HTR:1:PRLTEMPHLIMDES")
}

# Temperature low limit
record(ao, "LLRF:HTR:1:PRLTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[1]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:HTR:1:PRLTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "LLRF:HTR:1:PRLTEMP.LOLO CP")
  field(OUT, "LLRF:HTR:1:PRLTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:HTR:1:PRLTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M1_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[1] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M1_CH02_TEMP") {
  field(DESC, "PC0H00 Flange Temp 1")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:HTR:103:TEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[2]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M1_CH02_ALIAS") {
    field(VAL,"COLL:HTR:103:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:HTR:103:TEMP") {
  field(DESC, "PC0H00 Flange Temp 1")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M1_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "40")
  field(LOLO, "20")
  field(HIGH, "38")
  field(LOW, "25")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:HTR:103:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[2]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:HTR:103:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:HTR:103:TEMP.HIHI CP")
  field(OUT, "COLL:HTR:103:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:HTR:103:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:HTR:103:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[2]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:HTR:103:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:HTR:103:TEMP.LOLO CP")
  field(OUT, "COLL:HTR:103:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:HTR:103:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M1_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[1] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M1_CH03_TEMP") {
  field(DESC, "Laser Table Temp")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "LASR:LHTR:600:TABLETEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[3]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M1_CH03_ALIAS") {
    field(VAL,"LASR:LHTR:600:TABLETEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "LASR:LHTR:600:TABLETEMP") {
  field(DESC, "Laser Table Temp")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M1_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "LASR:LHTR:600:TABLETEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[3]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LASR:LHTR:600:TABLETEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "LASR:LHTR:600:TABLETEMP.HIHI CP")
  field(OUT, "LASR:LHTR:600:TABLETEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"LASR:LHTR:600:TABLETEMPHLIMDES")
}

# Temperature low limit
record(ao, "LASR:LHTR:600:TABLETEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[3]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LASR:LHTR:600:TABLETEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "LASR:LHTR:600:TABLETEMP.LOLO CP")
  field(OUT, "LASR:LHTR:600:TABLETEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"LASR:LHTR:600:TABLETEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M1_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[1] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M2_CH00_TEMP") {
  field(DESC, "BLEN 1 -x,-y")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BLEN:HTR:350:1:TEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[4]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M2_CH00_ALIAS") {
    field(VAL,"BLEN:HTR:350:1:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BLEN:HTR:350:1:TEMP") {
  field(DESC, "BLEN 1 -x,-y")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M2_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "35")
  field(LOLO, "0")
  field(HIGH, "30")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BLEN:HTR:350:1:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[4]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BLEN:HTR:350:1:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BLEN:HTR:350:1:TEMP.HIHI CP")
  field(OUT, "BLEN:HTR:350:1:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BLEN:HTR:350:1:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "BLEN:HTR:350:1:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[4]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BLEN:HTR:350:1:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BLEN:HTR:350:1:TEMP.LOLO CP")
  field(OUT, "BLEN:HTR:350:1:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BLEN:HTR:350:1:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M2_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[2] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M2_CH01_TEMP") {
  field(DESC, "BLEN 2 -x,+y")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BLEN:HTR:350:2:TEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[5]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M2_CH01_ALIAS") {
    field(VAL,"BLEN:HTR:350:2:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BLEN:HTR:350:2:TEMP") {
  field(DESC, "BLEN 2 -x,+y")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M2_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "35")
  field(LOLO, "0")
  field(HIGH, "30")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BLEN:HTR:350:2:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[5]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BLEN:HTR:350:2:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BLEN:HTR:350:2:TEMP.HIHI CP")
  field(OUT, "BLEN:HTR:350:2:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BLEN:HTR:350:2:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "BLEN:HTR:350:2:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[5]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BLEN:HTR:350:2:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BLEN:HTR:350:2:TEMP.LOLO CP")
  field(OUT, "BLEN:HTR:350:2:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BLEN:HTR:350:2:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M2_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[2] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M2_CH02_TEMP") {
  field(DESC, "BLEN 3 +x,-y")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BLEN:HTR:350:3:TEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[6]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M2_CH02_ALIAS") {
    field(VAL,"BLEN:HTR:350:3:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BLEN:HTR:350:3:TEMP") {
  field(DESC, "BLEN 3 +x,-y")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M2_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "35")
  field(LOLO, "0")
  field(HIGH, "30")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BLEN:HTR:350:3:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[6]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BLEN:HTR:350:3:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BLEN:HTR:350:3:TEMP.HIHI CP")
  field(OUT, "BLEN:HTR:350:3:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BLEN:HTR:350:3:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "BLEN:HTR:350:3:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[6]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BLEN:HTR:350:3:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BLEN:HTR:350:3:TEMP.LOLO CP")
  field(OUT, "BLEN:HTR:350:3:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BLEN:HTR:350:3:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M2_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[2] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M2_CH03_TEMP") {
  field(DESC, "BLEN 4 +x,+y")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BLEN:HTR:350:4:TEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[7]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M2_CH03_ALIAS") {
    field(VAL,"BLEN:HTR:350:4:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BLEN:HTR:350:4:TEMP") {
  field(DESC, "BLEN 4 +x,+y")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M2_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "35")
  field(LOLO, "0")
  field(HIGH, "30")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BLEN:HTR:350:4:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[7]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BLEN:HTR:350:4:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BLEN:HTR:350:4:TEMP.HIHI CP")
  field(OUT, "BLEN:HTR:350:4:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BLEN:HTR:350:4:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "BLEN:HTR:350:4:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[7]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BLEN:HTR:350:4:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BLEN:HTR:350:4:TEMP.LOLO CP")
  field(OUT, "BLEN:HTR:350:4:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BLEN:HTR:350:4:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M2_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[2] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M3_CH00_TEMP") {
  field(DESC, "BLEN 5 center")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BLEN:HTR:350:5:TEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[8]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M3_CH00_ALIAS") {
    field(VAL,"BLEN:HTR:350:5:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BLEN:HTR:350:5:TEMP") {
  field(DESC, "BLEN 5 center")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M3_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "35")
  field(LOLO, "0")
  field(HIGH, "30")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BLEN:HTR:350:5:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[8]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BLEN:HTR:350:5:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BLEN:HTR:350:5:TEMP.HIHI CP")
  field(OUT, "BLEN:HTR:350:5:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BLEN:HTR:350:5:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "BLEN:HTR:350:5:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[8]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BLEN:HTR:350:5:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BLEN:HTR:350:5:TEMP.LOLO CP")
  field(OUT, "BLEN:HTR:350:5:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BLEN:HTR:350:5:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M3_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[3] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M3_CH01_TEMP") {
  field(DESC, "CEHTR Temp 1")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:HTR:615:POSX:SUPPLYTEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[9]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M3_CH01_ALIAS") {
    field(VAL,"COLL:HTR:615:POSX:SUPPLYTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:HTR:615:POSX:SUPPLYTEMP") {
  field(DESC, "CEHTR Temp 1")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M3_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:HTR:615:POSX:SUPPLYTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[9]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:HTR:615:POSX:SUPPLYTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:HTR:615:POSX:SUPPLYTEMP.HIHI CP")
  field(OUT, "COLL:HTR:615:POSX:SUPPLYTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:HTR:615:POSX:SUPPLYTEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:HTR:615:POSX:SUPPLYTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[9]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:HTR:615:POSX:SUPPLYTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:HTR:615:POSX:SUPPLYTEMP.LOLO CP")
  field(OUT, "COLL:HTR:615:POSX:SUPPLYTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:HTR:615:POSX:SUPPLYTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M3_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[3] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M3_CH02_TEMP") {
  field(DESC, "CEHTR Temp 2")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:HTR:615:POSX:RETURNTEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[10]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M3_CH02_ALIAS") {
    field(VAL,"COLL:HTR:615:POSX:RETURNTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:HTR:615:POSX:RETURNTEMP") {
  field(DESC, "CEHTR Temp 2")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M3_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:HTR:615:POSX:RETURNTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[10]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:HTR:615:POSX:RETURNTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:HTR:615:POSX:RETURNTEMP.HIHI CP")
  field(OUT, "COLL:HTR:615:POSX:RETURNTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:HTR:615:POSX:RETURNTEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:HTR:615:POSX:RETURNTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[10]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:HTR:615:POSX:RETURNTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:HTR:615:POSX:RETURNTEMP.LOLO CP")
  field(OUT, "COLL:HTR:615:POSX:RETURNTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:HTR:615:POSX:RETURNTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M3_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[3] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M3_CH03_TEMP") {
  field(DESC, "CEHTR Temp 3")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:HTR:615:NEGX:SUPPLYTEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[11]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M3_CH03_ALIAS") {
    field(VAL,"COLL:HTR:615:NEGX:SUPPLYTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:HTR:615:NEGX:SUPPLYTEMP") {
  field(DESC, "CEHTR Temp 3")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M3_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:HTR:615:NEGX:SUPPLYTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[11]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:HTR:615:NEGX:SUPPLYTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:HTR:615:NEGX:SUPPLYTEMP.HIHI CP")
  field(OUT, "COLL:HTR:615:NEGX:SUPPLYTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:HTR:615:NEGX:SUPPLYTEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:HTR:615:NEGX:SUPPLYTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[11]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:HTR:615:NEGX:SUPPLYTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:HTR:615:NEGX:SUPPLYTEMP.LOLO CP")
  field(OUT, "COLL:HTR:615:NEGX:SUPPLYTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:HTR:615:NEGX:SUPPLYTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M3_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[3] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M4_CH00_TEMP") {
  field(DESC, "CEHTR Temp 4")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:HTR:615:NEGX:RETURNTEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[12]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M4_CH00_ALIAS") {
    field(VAL,"COLL:HTR:615:NEGX:RETURNTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:HTR:615:NEGX:RETURNTEMP") {
  field(DESC, "CEHTR Temp 4")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M4_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:HTR:615:NEGX:RETURNTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[12]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:HTR:615:NEGX:RETURNTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:HTR:615:NEGX:RETURNTEMP.HIHI CP")
  field(OUT, "COLL:HTR:615:NEGX:RETURNTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:HTR:615:NEGX:RETURNTEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:HTR:615:NEGX:RETURNTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[12]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:HTR:615:NEGX:RETURNTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:HTR:615:NEGX:RETURNTEMP.LOLO CP")
  field(OUT, "COLL:HTR:615:NEGX:RETURNTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:HTR:615:NEGX:RETURNTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M4_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[4] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M4_CH01_TEMP") {
  field(DESC, "BCXH2")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BEND:HTR:600:TEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[13]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M4_CH01_ALIAS") {
    field(VAL,"BEND:HTR:600:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BEND:HTR:600:TEMP") {
  field(DESC, "BCXH2")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M4_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BEND:HTR:600:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[13]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:HTR:600:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BEND:HTR:600:TEMP.HIHI CP")
  field(OUT, "BEND:HTR:600:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:HTR:600:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "BEND:HTR:600:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[13]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:HTR:600:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BEND:HTR:600:TEMP.LOLO CP")
  field(OUT, "BEND:HTR:600:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:HTR:600:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M4_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[4] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M4_CH02_TEMP") {
  field(DESC, "BCXH3")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BEND:HTR:700:TEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[14]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M4_CH02_ALIAS") {
    field(VAL,"BEND:HTR:700:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BEND:HTR:700:TEMP") {
  field(DESC, "BCXH3")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M4_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BEND:HTR:700:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[14]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:HTR:700:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BEND:HTR:700:TEMP.HIHI CP")
  field(OUT, "BEND:HTR:700:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:HTR:700:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "BEND:HTR:700:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[14]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:HTR:700:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BEND:HTR:700:TEMP.LOLO CP")
  field(OUT, "BEND:HTR:700:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:HTR:700:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M4_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[4] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M4_CH03_TEMP") {
  field(DESC, "BCXH4 Temp 1")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BEND:HTR:820:TEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[15]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M4_CH03_ALIAS") {
    field(VAL,"BEND:HTR:820:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BEND:HTR:820:TEMP") {
  field(DESC, "BCXH4 Temp 1")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M4_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BEND:HTR:820:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[15]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:HTR:820:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BEND:HTR:820:TEMP.HIHI CP")
  field(OUT, "BEND:HTR:820:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:HTR:820:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "BEND:HTR:820:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[15]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:HTR:820:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BEND:HTR:820:TEMP.LOLO CP")
  field(OUT, "BEND:HTR:820:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:HTR:820:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M4_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[4] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M5_CH00_TEMP") {
  field(DESC, "BXDG0")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BEND:DIAG0:260:TEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[16]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M5_CH00_ALIAS") {
    field(VAL,"BEND:DIAG0:260:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BEND:DIAG0:260:TEMP") {
  field(DESC, "BXDG0")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M5_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BEND:DIAG0:260:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[16]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:DIAG0:260:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BEND:DIAG0:260:TEMP.HIHI CP")
  field(OUT, "BEND:DIAG0:260:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:DIAG0:260:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "BEND:DIAG0:260:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[16]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:DIAG0:260:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BEND:DIAG0:260:TEMP.LOLO CP")
  field(OUT, "BEND:DIAG0:260:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:DIAG0:260:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M5_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[5] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M5_CH01_TEMP") {
  field(DESC, "CYC01 Temp 1")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:COL0:390:POSY:SUPPLYTEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[17]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M5_CH01_ALIAS") {
    field(VAL,"COLL:COL0:390:POSY:SUPPLYTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:COL0:390:POSY:SUPPLYTEMP") {
  field(DESC, "CYC01 Temp 1")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M5_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:COL0:390:POSY:SUPPLYTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[17]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:390:POSY:SUPPLYTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:COL0:390:POSY:SUPPLYTEMP.HIHI CP")
  field(OUT, "COLL:COL0:390:POSY:SUPPLYTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:390:POSY:SUPPLYTEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:COL0:390:POSY:SUPPLYTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[17]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:390:POSY:SUPPLYTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:COL0:390:POSY:SUPPLYTEMP.LOLO CP")
  field(OUT, "COLL:COL0:390:POSY:SUPPLYTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:390:POSY:SUPPLYTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M5_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[5] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M5_CH02_TEMP") {
  field(DESC, "CYC01 Temp 2")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:COL0:390:POSY:RETURNTEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[18]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M5_CH02_ALIAS") {
    field(VAL,"COLL:COL0:390:POSY:RETURNTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:COL0:390:POSY:RETURNTEMP") {
  field(DESC, "CYC01 Temp 2")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M5_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:COL0:390:POSY:RETURNTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[18]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:390:POSY:RETURNTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:COL0:390:POSY:RETURNTEMP.HIHI CP")
  field(OUT, "COLL:COL0:390:POSY:RETURNTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:390:POSY:RETURNTEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:COL0:390:POSY:RETURNTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[18]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:390:POSY:RETURNTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:COL0:390:POSY:RETURNTEMP.LOLO CP")
  field(OUT, "COLL:COL0:390:POSY:RETURNTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:390:POSY:RETURNTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M5_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[5] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M5_CH03_TEMP") {
  field(DESC, "CYC01 Temp 3")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:COL0:390:NEGY:SUPPLYTEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[19]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M5_CH03_ALIAS") {
    field(VAL,"COLL:COL0:390:NEGY:SUPPLYTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:COL0:390:NEGY:SUPPLYTEMP") {
  field(DESC, "CYC01 Temp 3")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M5_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:COL0:390:NEGY:SUPPLYTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[19]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:390:NEGY:SUPPLYTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:COL0:390:NEGY:SUPPLYTEMP.HIHI CP")
  field(OUT, "COLL:COL0:390:NEGY:SUPPLYTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:390:NEGY:SUPPLYTEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:COL0:390:NEGY:SUPPLYTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[19]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:390:NEGY:SUPPLYTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:COL0:390:NEGY:SUPPLYTEMP.LOLO CP")
  field(OUT, "COLL:COL0:390:NEGY:SUPPLYTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:390:NEGY:SUPPLYTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M5_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[5] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M6_CH00_TEMP") {
  field(DESC, "CYC01 Temp 4")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:COL0:390:NEGY:RETURNTEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[20]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M6_CH00_ALIAS") {
    field(VAL,"COLL:COL0:390:NEGY:RETURNTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:COL0:390:NEGY:RETURNTEMP") {
  field(DESC, "CYC01 Temp 4")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M6_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:COL0:390:NEGY:RETURNTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[20]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:390:NEGY:RETURNTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:COL0:390:NEGY:RETURNTEMP.HIHI CP")
  field(OUT, "COLL:COL0:390:NEGY:RETURNTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:390:NEGY:RETURNTEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:COL0:390:NEGY:RETURNTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[20]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:390:NEGY:RETURNTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:COL0:390:NEGY:RETURNTEMP.LOLO CP")
  field(OUT, "COLL:COL0:390:NEGY:RETURNTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:390:NEGY:RETURNTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M6_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[6] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M6_CH01_TEMP") {
  field(DESC, "CXC01 Temp 1")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:COL0:470:POSX:SUPPLYTEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[21]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M6_CH01_ALIAS") {
    field(VAL,"COLL:COL0:470:POSX:SUPPLYTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:COL0:470:POSX:SUPPLYTEMP") {
  field(DESC, "CXC01 Temp 1")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M6_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:COL0:470:POSX:SUPPLYTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[21]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:470:POSX:SUPPLYTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:COL0:470:POSX:SUPPLYTEMP.HIHI CP")
  field(OUT, "COLL:COL0:470:POSX:SUPPLYTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:470:POSX:SUPPLYTEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:COL0:470:POSX:SUPPLYTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[21]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:470:POSX:SUPPLYTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:COL0:470:POSX:SUPPLYTEMP.LOLO CP")
  field(OUT, "COLL:COL0:470:POSX:SUPPLYTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:470:POSX:SUPPLYTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M6_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[6] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M6_CH02_TEMP") {
  field(DESC, "CXC01 Temp 2")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:COL0:470:POSX:RETURNTEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[22]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M6_CH02_ALIAS") {
    field(VAL,"COLL:COL0:470:POSX:RETURNTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:COL0:470:POSX:RETURNTEMP") {
  field(DESC, "CXC01 Temp 2")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M6_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:COL0:470:POSX:RETURNTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[22]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:470:POSX:RETURNTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:COL0:470:POSX:RETURNTEMP.HIHI CP")
  field(OUT, "COLL:COL0:470:POSX:RETURNTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:470:POSX:RETURNTEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:COL0:470:POSX:RETURNTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[22]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:470:POSX:RETURNTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:COL0:470:POSX:RETURNTEMP.LOLO CP")
  field(OUT, "COLL:COL0:470:POSX:RETURNTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:470:POSX:RETURNTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M6_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[6] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M6_CH03_TEMP") {
  field(DESC, "CXC01 Temp 3")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:COL0:470:NEGX:SUPPLYTEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[23]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M6_CH03_ALIAS") {
    field(VAL,"COLL:COL0:470:NEGX:SUPPLYTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:COL0:470:NEGX:SUPPLYTEMP") {
  field(DESC, "CXC01 Temp 3")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M6_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:COL0:470:NEGX:SUPPLYTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[23]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:470:NEGX:SUPPLYTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:COL0:470:NEGX:SUPPLYTEMP.HIHI CP")
  field(OUT, "COLL:COL0:470:NEGX:SUPPLYTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:470:NEGX:SUPPLYTEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:COL0:470:NEGX:SUPPLYTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[23]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:470:NEGX:SUPPLYTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:COL0:470:NEGX:SUPPLYTEMP.LOLO CP")
  field(OUT, "COLL:COL0:470:NEGX:SUPPLYTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:470:NEGX:SUPPLYTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M6_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[6] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M7_CH00_TEMP") {
  field(DESC, "CXC01 Temp 4")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:COL0:470:NEGX:RETURNTEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[24]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M7_CH00_ALIAS") {
    field(VAL,"COLL:COL0:470:NEGX:RETURNTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:COL0:470:NEGX:RETURNTEMP") {
  field(DESC, "CXC01 Temp 4")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M7_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:COL0:470:NEGX:RETURNTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[24]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:470:NEGX:RETURNTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:COL0:470:NEGX:RETURNTEMP.HIHI CP")
  field(OUT, "COLL:COL0:470:NEGX:RETURNTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:470:NEGX:RETURNTEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:COL0:470:NEGX:RETURNTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[24]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:470:NEGX:RETURNTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:COL0:470:NEGX:RETURNTEMP.LOLO CP")
  field(OUT, "COLL:COL0:470:NEGX:RETURNTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:470:NEGX:RETURNTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M7_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[7] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M7_CH01_TEMP") {
  field(DESC, "Air S1 1 Z 36m")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ROOM:LI01:1:KT:TEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[25]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M7_CH01_ALIAS") {
    field(VAL,"ROOM:LI01:1:KT:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ROOM:LI01:1:KT:TEMP") {
  field(DESC, "Air S1 1 Z 36m")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M7_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ROOM:LI01:1:KT:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[25]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI01:1:KT:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ROOM:LI01:1:KT:TEMP.HIHI CP")
  field(OUT, "ROOM:LI01:1:KT:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI01:1:KT:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "ROOM:LI01:1:KT:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[25]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI01:1:KT:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ROOM:LI01:1:KT:TEMP.LOLO CP")
  field(OUT, "ROOM:LI01:1:KT:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI01:1:KT:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M7_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[7] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M7_CH02_TEMP") {
  field(DESC, "PRL S1 2 Z 33m")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "LLRF:HTR:2:PRLTEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[26]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M7_CH02_ALIAS") {
    field(VAL,"LLRF:HTR:2:PRLTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "LLRF:HTR:2:PRLTEMP") {
  field(DESC, "PRL S1 2 Z 33m")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M7_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "LLRF:HTR:2:PRLTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[26]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:HTR:2:PRLTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "LLRF:HTR:2:PRLTEMP.HIHI CP")
  field(OUT, "LLRF:HTR:2:PRLTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:HTR:2:PRLTEMPHLIMDES")
}

# Temperature low limit
record(ao, "LLRF:HTR:2:PRLTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[26]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:HTR:2:PRLTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "LLRF:HTR:2:PRLTEMP.LOLO CP")
  field(OUT, "LLRF:HTR:2:PRLTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:HTR:2:PRLTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M7_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[7] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M7_CH03_TEMP") {
  field(DESC, "CYC03 Temp 1")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:COL0:710:POSY:SUPPLYTEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[27]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M7_CH03_ALIAS") {
    field(VAL,"COLL:COL0:710:POSY:SUPPLYTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:COL0:710:POSY:SUPPLYTEMP") {
  field(DESC, "CYC03 Temp 1")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M7_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:COL0:710:POSY:SUPPLYTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[27]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:710:POSY:SUPPLYTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:COL0:710:POSY:SUPPLYTEMP.HIHI CP")
  field(OUT, "COLL:COL0:710:POSY:SUPPLYTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:710:POSY:SUPPLYTEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:COL0:710:POSY:SUPPLYTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[27]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:710:POSY:SUPPLYTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:COL0:710:POSY:SUPPLYTEMP.LOLO CP")
  field(OUT, "COLL:COL0:710:POSY:SUPPLYTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:710:POSY:SUPPLYTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M7_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[7] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M8_CH00_TEMP") {
  field(DESC, "CYC03 Temp 2")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:COL0:710:POSY:RETURNTEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[28]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M8_CH00_ALIAS") {
    field(VAL,"COLL:COL0:710:POSY:RETURNTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:COL0:710:POSY:RETURNTEMP") {
  field(DESC, "CYC03 Temp 2")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M8_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:COL0:710:POSY:RETURNTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[28]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:710:POSY:RETURNTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:COL0:710:POSY:RETURNTEMP.HIHI CP")
  field(OUT, "COLL:COL0:710:POSY:RETURNTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:710:POSY:RETURNTEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:COL0:710:POSY:RETURNTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[28]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:710:POSY:RETURNTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:COL0:710:POSY:RETURNTEMP.LOLO CP")
  field(OUT, "COLL:COL0:710:POSY:RETURNTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:710:POSY:RETURNTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M8_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[8] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M8_CH01_TEMP") {
  field(DESC, "CYC03 Temp 3")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:COL0:710:NEGY:SUPPLYTEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[29]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M8_CH01_ALIAS") {
    field(VAL,"COLL:COL0:710:NEGY:SUPPLYTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:COL0:710:NEGY:SUPPLYTEMP") {
  field(DESC, "CYC03 Temp 3")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M8_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:COL0:710:NEGY:SUPPLYTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[29]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:710:NEGY:SUPPLYTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:COL0:710:NEGY:SUPPLYTEMP.HIHI CP")
  field(OUT, "COLL:COL0:710:NEGY:SUPPLYTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:710:NEGY:SUPPLYTEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:COL0:710:NEGY:SUPPLYTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[29]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:710:NEGY:SUPPLYTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:COL0:710:NEGY:SUPPLYTEMP.LOLO CP")
  field(OUT, "COLL:COL0:710:NEGY:SUPPLYTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:710:NEGY:SUPPLYTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M8_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[8] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M8_CH02_TEMP") {
  field(DESC, "CYC03 Temp 4")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:COL0:710:NEGY:RETURNTEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[30]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M8_CH02_ALIAS") {
    field(VAL,"COLL:COL0:710:NEGY:RETURNTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:COL0:710:NEGY:RETURNTEMP") {
  field(DESC, "CYC03 Temp 4")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M8_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:COL0:710:NEGY:RETURNTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[30]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:710:NEGY:RETURNTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:COL0:710:NEGY:RETURNTEMP.HIHI CP")
  field(OUT, "COLL:COL0:710:NEGY:RETURNTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:710:NEGY:RETURNTEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:COL0:710:NEGY:RETURNTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[30]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:710:NEGY:RETURNTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:COL0:710:NEGY:RETURNTEMP.LOLO CP")
  field(OUT, "COLL:COL0:710:NEGY:RETURNTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:710:NEGY:RETURNTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M8_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[8] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M8_CH03_TEMP") {
  field(DESC, "CXC03 Temp 1")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:COL0:790:POSX:SUPPLYTEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[31]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M8_CH03_ALIAS") {
    field(VAL,"COLL:COL0:790:POSX:SUPPLYTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:COL0:790:POSX:SUPPLYTEMP") {
  field(DESC, "CXC03 Temp 1")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M8_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:COL0:790:POSX:SUPPLYTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[31]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:790:POSX:SUPPLYTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:COL0:790:POSX:SUPPLYTEMP.HIHI CP")
  field(OUT, "COLL:COL0:790:POSX:SUPPLYTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:790:POSX:SUPPLYTEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:COL0:790:POSX:SUPPLYTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[31]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:790:POSX:SUPPLYTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:COL0:790:POSX:SUPPLYTEMP.LOLO CP")
  field(OUT, "COLL:COL0:790:POSX:SUPPLYTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:790:POSX:SUPPLYTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M8_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[8] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M9_CH00_TEMP") {
  field(DESC, "CXC03 Temp 2")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:COL0:790:POSX:RETURNTEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[32]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M9_CH00_ALIAS") {
    field(VAL,"COLL:COL0:790:POSX:RETURNTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:COL0:790:POSX:RETURNTEMP") {
  field(DESC, "CXC03 Temp 2")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M9_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:COL0:790:POSX:RETURNTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[32]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:790:POSX:RETURNTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:COL0:790:POSX:RETURNTEMP.HIHI CP")
  field(OUT, "COLL:COL0:790:POSX:RETURNTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:790:POSX:RETURNTEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:COL0:790:POSX:RETURNTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[32]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:790:POSX:RETURNTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:COL0:790:POSX:RETURNTEMP.LOLO CP")
  field(OUT, "COLL:COL0:790:POSX:RETURNTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:790:POSX:RETURNTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M9_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[9] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M9_CH01_TEMP") {
  field(DESC, "CXC03 Temp 3")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:COL0:790:NEGX:SUPPLYTEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[33]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M9_CH01_ALIAS") {
    field(VAL,"COLL:COL0:790:NEGX:SUPPLYTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:COL0:790:NEGX:SUPPLYTEMP") {
  field(DESC, "CXC03 Temp 3")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M9_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:COL0:790:NEGX:SUPPLYTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[33]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:790:NEGX:SUPPLYTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:COL0:790:NEGX:SUPPLYTEMP.HIHI CP")
  field(OUT, "COLL:COL0:790:NEGX:SUPPLYTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:790:NEGX:SUPPLYTEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:COL0:790:NEGX:SUPPLYTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[33]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:790:NEGX:SUPPLYTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:COL0:790:NEGX:SUPPLYTEMP.LOLO CP")
  field(OUT, "COLL:COL0:790:NEGX:SUPPLYTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:790:NEGX:SUPPLYTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M9_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[9] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M9_CH02_TEMP") {
  field(DESC, "CXC03 Temp 4")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:COL0:790:NEGX:RETURNTEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[34]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M9_CH02_ALIAS") {
    field(VAL,"COLL:COL0:790:NEGX:RETURNTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:COL0:790:NEGX:RETURNTEMP") {
  field(DESC, "CXC03 Temp 4")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M9_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:COL0:790:NEGX:RETURNTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[34]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:790:NEGX:RETURNTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:COL0:790:NEGX:RETURNTEMP.HIHI CP")
  field(OUT, "COLL:COL0:790:NEGX:RETURNTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:790:NEGX:RETURNTEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:COL0:790:NEGX:RETURNTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[34]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:COL0:790:NEGX:RETURNTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:COL0:790:NEGX:RETURNTEMP.LOLO CP")
  field(OUT, "COLL:COL0:790:NEGX:RETURNTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:COL0:790:NEGX:RETURNTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M9_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[9] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M9_CH03_TEMP") {
  field(DESC, "Air S1 2 Z 77m")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ROOM:LI01:2:KT:TEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[35]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M9_CH03_ALIAS") {
    field(VAL,"ROOM:LI01:2:KT:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ROOM:LI01:2:KT:TEMP") {
  field(DESC, "Air S1 2 Z 77m")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M9_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ROOM:LI01:2:KT:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[35]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI01:2:KT:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ROOM:LI01:2:KT:TEMP.HIHI CP")
  field(OUT, "ROOM:LI01:2:KT:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI01:2:KT:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "ROOM:LI01:2:KT:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[35]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI01:2:KT:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ROOM:LI01:2:KT:TEMP.LOLO CP")
  field(OUT, "ROOM:LI01:2:KT:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI01:2:KT:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M9_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[9] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M10_CH00_TEMP") {
  field(DESC, "PRL S1 3 Z 57m")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "LLRF:COL0:1:PRLTEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[36]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M10_CH00_ALIAS") {
    field(VAL,"LLRF:COL0:1:PRLTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "LLRF:COL0:1:PRLTEMP") {
  field(DESC, "PRL S1 3 Z 57m")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M10_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "LLRF:COL0:1:PRLTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[36]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:COL0:1:PRLTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "LLRF:COL0:1:PRLTEMP.HIHI CP")
  field(OUT, "LLRF:COL0:1:PRLTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:COL0:1:PRLTEMPHLIMDES")
}

# Temperature low limit
record(ao, "LLRF:COL0:1:PRLTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[36]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:COL0:1:PRLTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "LLRF:COL0:1:PRLTEMP.LOLO CP")
  field(OUT, "LLRF:COL0:1:PRLTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:COL0:1:PRLTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M10_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[10] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M10_CH01_TEMP") {
  field(DESC, "PRL S1 4 Z 81m")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "LLRF:L1B:1:PRLTEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[37]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M10_CH01_ALIAS") {
    field(VAL,"LLRF:L1B:1:PRLTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "LLRF:L1B:1:PRLTEMP") {
  field(DESC, "PRL S1 4 Z 81m")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M10_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "LLRF:L1B:1:PRLTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[37]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:L1B:1:PRLTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "LLRF:L1B:1:PRLTEMP.HIHI CP")
  field(OUT, "LLRF:L1B:1:PRLTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:L1B:1:PRLTEMPHLIMDES")
}

# Temperature low limit
record(ao, "LLRF:L1B:1:PRLTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[37]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:L1B:1:PRLTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "LLRF:L1B:1:PRLTEMP.LOLO CP")
  field(OUT, "LLRF:L1B:1:PRLTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:L1B:1:PRLTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M10_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[10] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M10_CH02_TEMP") {
  field(DESC, "PC0H00 Water Temp Return")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:HTR:103:RETURNTEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[38]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M10_CH02_ALIAS") {
    field(VAL,"COLL:HTR:103:RETURNTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:HTR:103:RETURNTEMP") {
  field(DESC, "PC0H00 Water Temp Return")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M10_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "31")
  field(LOLO, "20")
  field(HIGH, "30")
  field(LOW, "25")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:HTR:103:RETURNTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[38]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:HTR:103:RETURNTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:HTR:103:RETURNTEMP.HIHI CP")
  field(OUT, "COLL:HTR:103:RETURNTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:HTR:103:RETURNTEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:HTR:103:RETURNTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[38]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:HTR:103:RETURNTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:HTR:103:RETURNTEMP.LOLO CP")
  field(OUT, "COLL:HTR:103:RETURNTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:HTR:103:RETURNTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M10_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[10] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR01_M10_CH03_TEMP") {
  field(DESC, "WS0H04 RTD")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "WIRE:HTR:340:TEMP")
  field(INP , "@PLC_HTR_TM01 CR01_Temp[39]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR01_M10_CH03_ALIAS") {
    field(VAL,"WIRE:HTR:340:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "WIRE:HTR:340:TEMP") {
  field(DESC, "WS0H04 RTD")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR01_M10_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "WIRE:HTR:340:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_HiTemp[39]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "WIRE:HTR:340:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "WIRE:HTR:340:TEMP.HIHI CP")
  field(OUT, "WIRE:HTR:340:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"WIRE:HTR:340:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "WIRE:HTR:340:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR01_LoTemp[39]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "WIRE:HTR:340:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "WIRE:HTR:340:TEMP.LOLO CP")
  field(OUT, "WIRE:HTR:340:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"WIRE:HTR:340:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR01_M10_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR01_Ch_Faults[10] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M1_CH00_TEMP") {
  field(DESC, "PEN 1-1 Temp 1")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L0B:0150:P0101:Temp1")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[0]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M1_CH00_ALIAS") {
    field(VAL,"ACCL:L0B:0150:P0101:Temp1")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L0B:0150:P0101:Temp1") {
  field(DESC, "PEN 1-1 Temp 1")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M1_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L0B:0150:P0101:Temp1HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[0]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L0B:0150:P0101:Temp1HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L0B:0150:P0101:Temp1.HIHI CP")
  field(OUT, "ACCL:L0B:0150:P0101:Temp1HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L0B:0150:P0101:Temp1HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L0B:0150:P0101:Temp1LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[0]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L0B:0150:P0101:Temp1LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L0B:0150:P0101:Temp1.LOLO CP")
  field(OUT, "ACCL:L0B:0150:P0101:Temp1LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L0B:0150:P0101:Temp1LLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M1_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[1] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M1_CH01_TEMP") {
  field(DESC, "PEN 1-1 Temp 2")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L0B:0150:P0101:Temp2")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[1]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M1_CH01_ALIAS") {
    field(VAL,"ACCL:L0B:0150:P0101:Temp2")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L0B:0150:P0101:Temp2") {
  field(DESC, "PEN 1-1 Temp 2")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M1_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L0B:0150:P0101:Temp2HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[1]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L0B:0150:P0101:Temp2HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L0B:0150:P0101:Temp2.HIHI CP")
  field(OUT, "ACCL:L0B:0150:P0101:Temp2HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L0B:0150:P0101:Temp2HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L0B:0150:P0101:Temp2LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[1]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L0B:0150:P0101:Temp2LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L0B:0150:P0101:Temp2.LOLO CP")
  field(OUT, "ACCL:L0B:0150:P0101:Temp2LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L0B:0150:P0101:Temp2LLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M1_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[1] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M1_CH02_TEMP") {
  field(DESC, "PEN 1-1 Temp 3")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L0B:0150:P0101:Temp3")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[2]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M1_CH02_ALIAS") {
    field(VAL,"ACCL:L0B:0150:P0101:Temp3")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L0B:0150:P0101:Temp3") {
  field(DESC, "PEN 1-1 Temp 3")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M1_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L0B:0150:P0101:Temp3HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[2]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L0B:0150:P0101:Temp3HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L0B:0150:P0101:Temp3.HIHI CP")
  field(OUT, "ACCL:L0B:0150:P0101:Temp3HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L0B:0150:P0101:Temp3HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L0B:0150:P0101:Temp3LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[2]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L0B:0150:P0101:Temp3LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L0B:0150:P0101:Temp3.LOLO CP")
  field(OUT, "ACCL:L0B:0150:P0101:Temp3LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L0B:0150:P0101:Temp3LLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M1_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[1] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M1_CH03_TEMP") {
  field(DESC, "Gallery S0 Air ")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ROOM:LI00:1:KG:TEMP")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[3]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M1_CH03_ALIAS") {
    field(VAL,"ROOM:LI00:1:KG:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ROOM:LI00:1:KG:TEMP") {
  field(DESC, "Gallery S0 Air ")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M1_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ROOM:LI00:1:KG:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[3]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI00:1:KG:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ROOM:LI00:1:KG:TEMP.HIHI CP")
  field(OUT, "ROOM:LI00:1:KG:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI00:1:KG:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "ROOM:LI00:1:KG:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[3]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI00:1:KG:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ROOM:LI00:1:KG:TEMP.LOLO CP")
  field(OUT, "ROOM:LI00:1:KG:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI00:1:KG:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M1_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[1] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M2_CH00_TEMP") {
  field(DESC, "PEN 1-14 Temp 1")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L1B:0210:P0114:Temp1")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[4]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M2_CH00_ALIAS") {
    field(VAL,"ACCL:L1B:0210:P0114:Temp1")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L1B:0210:P0114:Temp1") {
  field(DESC, "PEN 1-14 Temp 1")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M2_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L1B:0210:P0114:Temp1HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[4]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L1B:0210:P0114:Temp1HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L1B:0210:P0114:Temp1.HIHI CP")
  field(OUT, "ACCL:L1B:0210:P0114:Temp1HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L1B:0210:P0114:Temp1HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L1B:0210:P0114:Temp1LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[4]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L1B:0210:P0114:Temp1LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L1B:0210:P0114:Temp1.LOLO CP")
  field(OUT, "ACCL:L1B:0210:P0114:Temp1LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L1B:0210:P0114:Temp1LLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M2_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[2] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M2_CH01_TEMP") {
  field(DESC, "PEN 1-14 Temp 2")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L1B:0210:P0114:Temp2")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[5]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M2_CH01_ALIAS") {
    field(VAL,"ACCL:L1B:0210:P0114:Temp2")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L1B:0210:P0114:Temp2") {
  field(DESC, "PEN 1-14 Temp 2")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M2_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L1B:0210:P0114:Temp2HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[5]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L1B:0210:P0114:Temp2HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L1B:0210:P0114:Temp2.HIHI CP")
  field(OUT, "ACCL:L1B:0210:P0114:Temp2HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L1B:0210:P0114:Temp2HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L1B:0210:P0114:Temp2LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[5]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L1B:0210:P0114:Temp2LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L1B:0210:P0114:Temp2.LOLO CP")
  field(OUT, "ACCL:L1B:0210:P0114:Temp2LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L1B:0210:P0114:Temp2LLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M2_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[2] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M2_CH02_TEMP") {
  field(DESC, "PEN 1-14 Temp 3")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L1B:0210:P0114:Temp3")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[6]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M2_CH02_ALIAS") {
    field(VAL,"ACCL:L1B:0210:P0114:Temp3")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L1B:0210:P0114:Temp3") {
  field(DESC, "PEN 1-14 Temp 3")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M2_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L1B:0210:P0114:Temp3HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[6]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L1B:0210:P0114:Temp3HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L1B:0210:P0114:Temp3.HIHI CP")
  field(OUT, "ACCL:L1B:0210:P0114:Temp3HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L1B:0210:P0114:Temp3HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L1B:0210:P0114:Temp3LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[6]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L1B:0210:P0114:Temp3LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L1B:0210:P0114:Temp3.LOLO CP")
  field(OUT, "ACCL:L1B:0210:P0114:Temp3LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L1B:0210:P0114:Temp3LLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M2_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[2] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M2_CH03_TEMP") {
  field(DESC, "Spare          ")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:HTR:TM01:02:M2_CH3_SPARE")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[7]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M2_CH03_ALIAS") {
    field(VAL,"PLC:HTR:TM01:02:M2_CH3_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:HTR:TM01:02:M2_CH3_SPARE") {
  field(DESC, "Spare          ")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M2_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:HTR:TM01:02:M2_CH3_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[7]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:HTR:TM01:02:M2_CH3_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:HTR:TM01:02:M2_CH3_SPARE.HIHI CP")
  field(OUT, "PLC:HTR:TM01:02:M2_CH3_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:HTR:TM01:02:M2_CH3_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:HTR:TM01:02:M2_CH3_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[7]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:HTR:TM01:02:M2_CH3_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:HTR:TM01:02:M2_CH3_SPARE.LOLO CP")
  field(OUT, "PLC:HTR:TM01:02:M2_CH3_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:HTR:TM01:02:M2_CH3_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M2_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[2] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M3_CH00_TEMP") {
  field(DESC, "PEN 1-15 Temp 1")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L1B:0250:P0115:Temp1")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[8]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M3_CH00_ALIAS") {
    field(VAL,"ACCL:L1B:0250:P0115:Temp1")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L1B:0250:P0115:Temp1") {
  field(DESC, "PEN 1-15 Temp 1")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M3_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L1B:0250:P0115:Temp1HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[8]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L1B:0250:P0115:Temp1HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L1B:0250:P0115:Temp1.HIHI CP")
  field(OUT, "ACCL:L1B:0250:P0115:Temp1HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L1B:0250:P0115:Temp1HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L1B:0250:P0115:Temp1LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[8]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L1B:0250:P0115:Temp1LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L1B:0250:P0115:Temp1.LOLO CP")
  field(OUT, "ACCL:L1B:0250:P0115:Temp1LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L1B:0250:P0115:Temp1LLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M3_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[3] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M3_CH01_TEMP") {
  field(DESC, "PEN 1-15 Temp 2")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L1B:0250:P0115:Temp2")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[9]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M3_CH01_ALIAS") {
    field(VAL,"ACCL:L1B:0250:P0115:Temp2")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L1B:0250:P0115:Temp2") {
  field(DESC, "PEN 1-15 Temp 2")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M3_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L1B:0250:P0115:Temp2HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[9]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L1B:0250:P0115:Temp2HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L1B:0250:P0115:Temp2.HIHI CP")
  field(OUT, "ACCL:L1B:0250:P0115:Temp2HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L1B:0250:P0115:Temp2HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L1B:0250:P0115:Temp2LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[9]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L1B:0250:P0115:Temp2LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L1B:0250:P0115:Temp2.LOLO CP")
  field(OUT, "ACCL:L1B:0250:P0115:Temp2LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L1B:0250:P0115:Temp2LLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M3_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[3] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M3_CH02_TEMP") {
  field(DESC, "PEN 1-15 Temp 3")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L1B:0250:P0115:Temp3")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[10]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M3_CH02_ALIAS") {
    field(VAL,"ACCL:L1B:0250:P0115:Temp3")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L1B:0250:P0115:Temp3") {
  field(DESC, "PEN 1-15 Temp 3")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M3_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L1B:0250:P0115:Temp3HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[10]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L1B:0250:P0115:Temp3HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L1B:0250:P0115:Temp3.HIHI CP")
  field(OUT, "ACCL:L1B:0250:P0115:Temp3HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L1B:0250:P0115:Temp3HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L1B:0250:P0115:Temp3LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[10]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L1B:0250:P0115:Temp3LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L1B:0250:P0115:Temp3.LOLO CP")
  field(OUT, "ACCL:L1B:0250:P0115:Temp3LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L1B:0250:P0115:Temp3LLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M3_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[3] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M3_CH03_TEMP") {
  field(DESC, "Spare          ")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:HTR:TM01:02:M3_CH3_SPARE")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[11]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M3_CH03_ALIAS") {
    field(VAL,"PLC:HTR:TM01:02:M3_CH3_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:HTR:TM01:02:M3_CH3_SPARE") {
  field(DESC, "Spare          ")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M3_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:HTR:TM01:02:M3_CH3_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[11]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:HTR:TM01:02:M3_CH3_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:HTR:TM01:02:M3_CH3_SPARE.HIHI CP")
  field(OUT, "PLC:HTR:TM01:02:M3_CH3_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:HTR:TM01:02:M3_CH3_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:HTR:TM01:02:M3_CH3_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[11]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:HTR:TM01:02:M3_CH3_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:HTR:TM01:02:M3_CH3_SPARE.LOLO CP")
  field(OUT, "PLC:HTR:TM01:02:M3_CH3_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:HTR:TM01:02:M3_CH3_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M3_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[3] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M4_CH00_TEMP") {
  field(DESC, "PEN 1-16 Temp 1")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L1B:0310:P0116:Temp1")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[12]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M4_CH00_ALIAS") {
    field(VAL,"ACCL:L1B:0310:P0116:Temp1")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L1B:0310:P0116:Temp1") {
  field(DESC, "PEN 1-16 Temp 1")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M4_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L1B:0310:P0116:Temp1HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[12]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L1B:0310:P0116:Temp1HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L1B:0310:P0116:Temp1.HIHI CP")
  field(OUT, "ACCL:L1B:0310:P0116:Temp1HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L1B:0310:P0116:Temp1HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L1B:0310:P0116:Temp1LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[12]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L1B:0310:P0116:Temp1LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L1B:0310:P0116:Temp1.LOLO CP")
  field(OUT, "ACCL:L1B:0310:P0116:Temp1LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L1B:0310:P0116:Temp1LLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M4_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[4] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M4_CH01_TEMP") {
  field(DESC, "PEN 1-16 Temp 2")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L1B:0310:P0116:Temp2")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[13]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M4_CH01_ALIAS") {
    field(VAL,"ACCL:L1B:0310:P0116:Temp2")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L1B:0310:P0116:Temp2") {
  field(DESC, "PEN 1-16 Temp 2")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M4_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L1B:0310:P0116:Temp2HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[13]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L1B:0310:P0116:Temp2HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L1B:0310:P0116:Temp2.HIHI CP")
  field(OUT, "ACCL:L1B:0310:P0116:Temp2HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L1B:0310:P0116:Temp2HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L1B:0310:P0116:Temp2LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[13]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L1B:0310:P0116:Temp2LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L1B:0310:P0116:Temp2.LOLO CP")
  field(OUT, "ACCL:L1B:0310:P0116:Temp2LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L1B:0310:P0116:Temp2LLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M4_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[4] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M4_CH02_TEMP") {
  field(DESC, "PEN 1-16 Temp 3")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L1B:0310:P0116:Temp3")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[14]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M4_CH02_ALIAS") {
    field(VAL,"ACCL:L1B:0310:P0116:Temp3")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L1B:0310:P0116:Temp3") {
  field(DESC, "PEN 1-16 Temp 3")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M4_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L1B:0310:P0116:Temp3HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[14]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L1B:0310:P0116:Temp3HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L1B:0310:P0116:Temp3.HIHI CP")
  field(OUT, "ACCL:L1B:0310:P0116:Temp3HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L1B:0310:P0116:Temp3HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L1B:0310:P0116:Temp3LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[14]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L1B:0310:P0116:Temp3LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L1B:0310:P0116:Temp3.LOLO CP")
  field(OUT, "ACCL:L1B:0310:P0116:Temp3LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L1B:0310:P0116:Temp3LLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M4_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[4] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M4_CH03_TEMP") {
  field(DESC, "Spare          ")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:HTR:TM01:02:M4_CH4_SPARE")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[15]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M4_CH03_ALIAS") {
    field(VAL,"PLC:HTR:TM01:02:M4_CH4_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:HTR:TM01:02:M4_CH4_SPARE") {
  field(DESC, "Spare          ")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M4_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:HTR:TM01:02:M4_CH4_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[15]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:HTR:TM01:02:M4_CH4_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:HTR:TM01:02:M4_CH4_SPARE.HIHI CP")
  field(OUT, "PLC:HTR:TM01:02:M4_CH4_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:HTR:TM01:02:M4_CH4_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:HTR:TM01:02:M4_CH4_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[15]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:HTR:TM01:02:M4_CH4_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:HTR:TM01:02:M4_CH4_SPARE.LOLO CP")
  field(OUT, "PLC:HTR:TM01:02:M4_CH4_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:HTR:TM01:02:M4_CH4_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M4_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[4] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M5_CH00_TEMP") {
  field(DESC, "Water S1 1 us return z9m")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "WATR:LI01:1:KT:TEMP")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[16]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M5_CH00_ALIAS") {
    field(VAL,"WATR:LI01:1:KT:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "WATR:LI01:1:KT:TEMP") {
  field(DESC, "Water S1 1 us return z9m")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M5_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "WATR:LI01:1:KT:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[16]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "WATR:LI01:1:KT:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "WATR:LI01:1:KT:TEMP.HIHI CP")
  field(OUT, "WATR:LI01:1:KT:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"WATR:LI01:1:KT:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "WATR:LI01:1:KT:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[16]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "WATR:LI01:1:KT:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "WATR:LI01:1:KT:TEMP.LOLO CP")
  field(OUT, "WATR:LI01:1:KT:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"WATR:LI01:1:KT:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M5_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[5] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M5_CH01_TEMP") {
  field(DESC, "Water S1 2 main return z13m")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "WATR:LI01:2:KT:TEMP")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[17]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M5_CH01_ALIAS") {
    field(VAL,"WATR:LI01:2:KT:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "WATR:LI01:2:KT:TEMP") {
  field(DESC, "Water S1 2 main return z13m")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M5_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "WATR:LI01:2:KT:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[17]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "WATR:LI01:2:KT:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "WATR:LI01:2:KT:TEMP.HIHI CP")
  field(OUT, "WATR:LI01:2:KT:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"WATR:LI01:2:KT:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "WATR:LI01:2:KT:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[17]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "WATR:LI01:2:KT:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "WATR:LI01:2:KT:TEMP.LOLO CP")
  field(OUT, "WATR:LI01:2:KT:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"WATR:LI01:2:KT:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M5_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[5] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M5_CH02_TEMP") {
  field(DESC, "Water S1 3 main supply z13m")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "WATR:LI01:3:KT:TEMP")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[18]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M5_CH02_ALIAS") {
    field(VAL,"WATR:LI01:3:KT:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "WATR:LI01:3:KT:TEMP") {
  field(DESC, "Water S1 3 main supply z13m")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M5_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "WATR:LI01:3:KT:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[18]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "WATR:LI01:3:KT:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "WATR:LI01:3:KT:TEMP.HIHI CP")
  field(OUT, "WATR:LI01:3:KT:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"WATR:LI01:3:KT:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "WATR:LI01:3:KT:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[18]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "WATR:LI01:3:KT:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "WATR:LI01:3:KT:TEMP.LOLO CP")
  field(OUT, "WATR:LI01:3:KT:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"WATR:LI01:3:KT:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M5_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[5] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M5_CH03_TEMP") {
  field(DESC, "BKRDG01   ")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "KICK:DIAG0:110:TEMP")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[19]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M5_CH03_ALIAS") {
    field(VAL,"KICK:DIAG0:110:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "KICK:DIAG0:110:TEMP") {
  field(DESC, "BKRDG01   ")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M5_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "KICK:DIAG0:110:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[19]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "KICK:DIAG0:110:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "KICK:DIAG0:110:TEMP.HIHI CP")
  field(OUT, "KICK:DIAG0:110:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"KICK:DIAG0:110:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "KICK:DIAG0:110:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[19]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "KICK:DIAG0:110:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "KICK:DIAG0:110:TEMP.LOLO CP")
  field(OUT, "KICK:DIAG0:110:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"KICK:DIAG0:110:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M5_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[5] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M6_CH00_TEMP") {
  field(DESC, "BLRDG0    ")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BEND:DIAG0:155:TEMP")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[20]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M6_CH00_ALIAS") {
    field(VAL,"BEND:DIAG0:155:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BEND:DIAG0:155:TEMP") {
  field(DESC, "BLRDG0    ")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M6_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BEND:DIAG0:155:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[20]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:DIAG0:155:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BEND:DIAG0:155:TEMP.HIHI CP")
  field(OUT, "BEND:DIAG0:155:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:DIAG0:155:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "BEND:DIAG0:155:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[20]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:DIAG0:155:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BEND:DIAG0:155:TEMP.LOLO CP")
  field(OUT, "BEND:DIAG0:155:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:DIAG0:155:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M6_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[6] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M6_CH01_TEMP") {
  field(DESC, "Faraday cup")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "FARC:DIAG0:530:TEMP")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[21]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M6_CH01_ALIAS") {
    field(VAL,"FARC:DIAG0:530:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "FARC:DIAG0:530:TEMP") {
  field(DESC, "Faraday cup")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M6_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "FARC:DIAG0:530:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[21]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "FARC:DIAG0:530:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "FARC:DIAG0:530:TEMP.HIHI CP")
  field(OUT, "FARC:DIAG0:530:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"FARC:DIAG0:530:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "FARC:DIAG0:530:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[21]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "FARC:DIAG0:530:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "FARC:DIAG0:530:TEMP.LOLO CP")
  field(OUT, "FARC:DIAG0:530:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"FARC:DIAG0:530:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M6_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[6] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M6_CH02_TEMP") {
  field(DESC, "Water S1 4 ds return z68m")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "WATR:LI01:4:KT:TEMP")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[22]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M6_CH02_ALIAS") {
    field(VAL,"WATR:LI01:4:KT:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "WATR:LI01:4:KT:TEMP") {
  field(DESC, "Water S1 4 ds return z68m")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M6_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "WATR:LI01:4:KT:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[22]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "WATR:LI01:4:KT:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "WATR:LI01:4:KT:TEMP.HIHI CP")
  field(OUT, "WATR:LI01:4:KT:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"WATR:LI01:4:KT:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "WATR:LI01:4:KT:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[22]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "WATR:LI01:4:KT:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "WATR:LI01:4:KT:TEMP.LOLO CP")
  field(OUT, "WATR:LI01:4:KT:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"WATR:LI01:4:KT:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M6_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[6] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M6_CH03_TEMP") {
  field(DESC, "BYDG0     ")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BEND:DIAG0:510:TEMP")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[23]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M6_CH03_ALIAS") {
    field(VAL,"BEND:DIAG0:510:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BEND:DIAG0:510:TEMP") {
  field(DESC, "BYDG0     ")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M6_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BEND:DIAG0:510:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[23]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:DIAG0:510:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BEND:DIAG0:510:TEMP.HIHI CP")
  field(OUT, "BEND:DIAG0:510:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:DIAG0:510:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "BEND:DIAG0:510:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[23]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:DIAG0:510:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BEND:DIAG0:510:TEMP.LOLO CP")
  field(OUT, "BEND:DIAG0:510:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:DIAG0:510:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M6_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[6] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M7_CH00_TEMP") {
  field(DESC, "Alcove S1 Air")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ROOM:LI01:1:KA:TEMP")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[24]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M7_CH00_ALIAS") {
    field(VAL,"ROOM:LI01:1:KA:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ROOM:LI01:1:KA:TEMP") {
  field(DESC, "Alcove S1 Air")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M7_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ROOM:LI01:1:KA:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[24]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI01:1:KA:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ROOM:LI01:1:KA:TEMP.HIHI CP")
  field(OUT, "ROOM:LI01:1:KA:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI01:1:KA:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "ROOM:LI01:1:KA:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[24]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI01:1:KA:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ROOM:LI01:1:KA:TEMP.LOLO CP")
  field(OUT, "ROOM:LI01:1:KA:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI01:1:KA:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M7_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[7] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M7_CH01_TEMP") {
  field(DESC, "Gallery S1 Air")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ROOM:LI01:1:KG:TEMP")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[25]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M7_CH01_ALIAS") {
    field(VAL,"ROOM:LI01:1:KG:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ROOM:LI01:1:KG:TEMP") {
  field(DESC, "Gallery S1 Air")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M7_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ROOM:LI01:1:KG:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[25]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI01:1:KG:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ROOM:LI01:1:KG:TEMP.HIHI CP")
  field(OUT, "ROOM:LI01:1:KG:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI01:1:KG:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "ROOM:LI01:1:KG:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[25]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI01:1:KG:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ROOM:LI01:1:KG:TEMP.LOLO CP")
  field(OUT, "ROOM:LI01:1:KG:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI01:1:KG:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M7_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[7] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M7_CH02_TEMP") {
  field(DESC, "LLRF Rack Water Temp")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:DIAG0:340:RACK:TEMP")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[26]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M7_CH02_ALIAS") {
    field(VAL,"ACCL:DIAG0:340:RACK:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:DIAG0:340:RACK:TEMP") {
  field(DESC, "LLRF Rack Water Temp")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M7_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:DIAG0:340:RACK:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[26]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:DIAG0:340:RACK:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:DIAG0:340:RACK:TEMP.HIHI CP")
  field(OUT, "ACCL:DIAG0:340:RACK:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:DIAG0:340:RACK:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "ACCL:DIAG0:340:RACK:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[26]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:DIAG0:340:RACK:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:DIAG0:340:RACK:TEMP.LOLO CP")
  field(OUT, "ACCL:DIAG0:340:RACK:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:DIAG0:340:RACK:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M7_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[7] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M7_CH03_TEMP") {
  field(DESC, "LLRF Rack Air Temp")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:DIAG0:340:RACK:AIRTEMP")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[27]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M7_CH03_ALIAS") {
    field(VAL,"ACCL:DIAG0:340:RACK:AIRTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:DIAG0:340:RACK:AIRTEMP") {
  field(DESC, "LLRF Rack Air Temp")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M7_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:DIAG0:340:RACK:AIRTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[27]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:DIAG0:340:RACK:AIRTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:DIAG0:340:RACK:AIRTEMP.HIHI CP")
  field(OUT, "ACCL:DIAG0:340:RACK:AIRTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:DIAG0:340:RACK:AIRTEMPHLIMDES")
}

# Temperature low limit
record(ao, "ACCL:DIAG0:340:RACK:AIRTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[27]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:DIAG0:340:RACK:AIRTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:DIAG0:340:RACK:AIRTEMP.LOLO CP")
  field(OUT, "ACCL:DIAG0:340:RACK:AIRTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:DIAG0:340:RACK:AIRTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M7_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[7] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M8_CH00_TEMP") {
  field(DESC, "Tunnel Waveguide Temp ")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:DIAG0:340:WGTEMP")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[28]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M8_CH00_ALIAS") {
    field(VAL,"ACCL:DIAG0:340:WGTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:DIAG0:340:WGTEMP") {
  field(DESC, "Tunnel Waveguide Temp ")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M8_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:DIAG0:340:WGTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[28]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:DIAG0:340:WGTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:DIAG0:340:WGTEMP.HIHI CP")
  field(OUT, "ACCL:DIAG0:340:WGTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:DIAG0:340:WGTEMPHLIMDES")
}

# Temperature low limit
record(ao, "ACCL:DIAG0:340:WGTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[28]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:DIAG0:340:WGTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:DIAG0:340:WGTEMP.LOLO CP")
  field(OUT, "ACCL:DIAG0:340:WGTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:DIAG0:340:WGTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M8_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[8] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M8_CH01_TEMP") {
  field(DESC, "Tunnel RF Cavity Temp 1 ")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:DIAG0:340:1:TEMP")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[30]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M8_CH01_ALIAS") {
    field(VAL,"ACCL:DIAG0:340:1:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:DIAG0:340:1:TEMP") {
  field(DESC, "Tunnel RF Cavity Temp 1 ")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M8_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:DIAG0:340:1:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[30]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:DIAG0:340:1:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:DIAG0:340:1:TEMP.HIHI CP")
  field(OUT, "ACCL:DIAG0:340:1:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:DIAG0:340:1:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "ACCL:DIAG0:340:1:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[30]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:DIAG0:340:1:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:DIAG0:340:1:TEMP.LOLO CP")
  field(OUT, "ACCL:DIAG0:340:1:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:DIAG0:340:1:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M8_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[8] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M8_CH02_TEMP") {
  field(DESC, "Tunnel RF Cavity Temp 2 ")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:DIAG0:340:2:TEMP")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[31]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M8_CH02_ALIAS") {
    field(VAL,"ACCL:DIAG0:340:2:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:DIAG0:340:2:TEMP") {
  field(DESC, "Tunnel RF Cavity Temp 2 ")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M8_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:DIAG0:340:2:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[31]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:DIAG0:340:2:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:DIAG0:340:2:TEMP.HIHI CP")
  field(OUT, "ACCL:DIAG0:340:2:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:DIAG0:340:2:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "ACCL:DIAG0:340:2:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[31]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:DIAG0:340:2:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:DIAG0:340:2:TEMP.LOLO CP")
  field(OUT, "ACCL:DIAG0:340:2:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:DIAG0:340:2:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M8_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[8] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M8_CH03_TEMP") {
  field(DESC, "Tunnel RF Load Temp   ")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:DIAG0:340:LOADTEMP")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[29]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M8_CH03_ALIAS") {
    field(VAL,"ACCL:DIAG0:340:LOADTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:DIAG0:340:LOADTEMP") {
  field(DESC, "Tunnel RF Load Temp   ")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M8_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:DIAG0:340:LOADTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[29]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:DIAG0:340:LOADTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:DIAG0:340:LOADTEMP.HIHI CP")
  field(OUT, "ACCL:DIAG0:340:LOADTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:DIAG0:340:LOADTEMPHLIMDES")
}

# Temperature low limit
record(ao, "ACCL:DIAG0:340:LOADTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[29]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:DIAG0:340:LOADTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:DIAG0:340:LOADTEMP.LOLO CP")
  field(OUT, "ACCL:DIAG0:340:LOADTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:DIAG0:340:LOADTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M8_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[8] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M9_CH00_TEMP") {
  field(DESC, "PC0H00 Water Temp Supply")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:HTR:103:SUPPLYTEMP")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[32]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M9_CH00_ALIAS") {
    field(VAL,"COLL:HTR:103:SUPPLYTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:HTR:103:SUPPLYTEMP") {
  field(DESC, "PC0H00 Water Temp Supply")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M9_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "31")
  field(LOLO, "20")
  field(HIGH, "30")
  field(LOW, "25")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:HTR:103:SUPPLYTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[32]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:HTR:103:SUPPLYTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:HTR:103:SUPPLYTEMP.HIHI CP")
  field(OUT, "COLL:HTR:103:SUPPLYTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:HTR:103:SUPPLYTEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:HTR:103:SUPPLYTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[32]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:HTR:103:SUPPLYTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:HTR:103:SUPPLYTEMP.LOLO CP")
  field(OUT, "COLL:HTR:103:SUPPLYTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:HTR:103:SUPPLYTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M9_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[9] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M9_CH01_TEMP") {
  field(DESC, "PC0H00 Flange Temp 2")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:HTR:103:2:TEMP")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[33]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M9_CH01_ALIAS") {
    field(VAL,"COLL:HTR:103:2:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:HTR:103:2:TEMP") {
  field(DESC, "PC0H00 Flange Temp 2")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M9_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "40")
  field(LOLO, "20")
  field(HIGH, "38")
  field(LOW, "25")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:HTR:103:2:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[33]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:HTR:103:2:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:HTR:103:2:TEMP.HIHI CP")
  field(OUT, "COLL:HTR:103:2:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:HTR:103:2:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:HTR:103:2:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[33]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:HTR:103:2:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:HTR:103:2:TEMP.LOLO CP")
  field(OUT, "COLL:HTR:103:2:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:HTR:103:2:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M9_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[9] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M9_CH02_TEMP") {
  field(DESC, "BCXH1 Temp 2")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BEND:HTR:480:2:TEMP")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[34]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M9_CH02_ALIAS") {
    field(VAL,"BEND:HTR:480:2:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BEND:HTR:480:2:TEMP") {
  field(DESC, "BCXH1 Temp 2")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M9_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BEND:HTR:480:2:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[34]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:HTR:480:2:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BEND:HTR:480:2:TEMP.HIHI CP")
  field(OUT, "BEND:HTR:480:2:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:HTR:480:2:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "BEND:HTR:480:2:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[34]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:HTR:480:2:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BEND:HTR:480:2:TEMP.LOLO CP")
  field(OUT, "BEND:HTR:480:2:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:HTR:480:2:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M9_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[9] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M9_CH03_TEMP") {
  field(DESC, "BPMHD01 Temp")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BPMS:HTR:830:TEMP")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[35]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M9_CH03_ALIAS") {
    field(VAL,"BPMS:HTR:830:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BPMS:HTR:830:TEMP") {
  field(DESC, "BPMHD01 Temp")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M9_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BPMS:HTR:830:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[35]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BPMS:HTR:830:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BPMS:HTR:830:TEMP.HIHI CP")
  field(OUT, "BPMS:HTR:830:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BPMS:HTR:830:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "BPMS:HTR:830:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[35]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BPMS:HTR:830:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BPMS:HTR:830:TEMP.LOLO CP")
  field(OUT, "BPMS:HTR:830:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BPMS:HTR:830:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M9_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[9] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M10_CH00_TEMP") {
  field(DESC, "Spare          ")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:HTR:TM01:02:M10_CH0_SPARE")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[36]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M10_CH00_ALIAS") {
    field(VAL,"PLC:HTR:TM01:02:M10_CH0_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:HTR:TM01:02:M10_CH0_SPARE") {
  field(DESC, "Spare          ")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M10_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:HTR:TM01:02:M10_CH0_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[36]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:HTR:TM01:02:M10_CH0_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:HTR:TM01:02:M10_CH0_SPARE.HIHI CP")
  field(OUT, "PLC:HTR:TM01:02:M10_CH0_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:HTR:TM01:02:M10_CH0_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:HTR:TM01:02:M10_CH0_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[36]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:HTR:TM01:02:M10_CH0_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:HTR:TM01:02:M10_CH0_SPARE.LOLO CP")
  field(OUT, "PLC:HTR:TM01:02:M10_CH0_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:HTR:TM01:02:M10_CH0_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M10_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[10] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M10_CH01_TEMP") {
  field(DESC, "Spare          ")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:HTR:TM01:02:M10_CH1_SPARE")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[37]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M10_CH01_ALIAS") {
    field(VAL,"PLC:HTR:TM01:02:M10_CH1_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:HTR:TM01:02:M10_CH1_SPARE") {
  field(DESC, "Spare          ")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M10_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:HTR:TM01:02:M10_CH1_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[37]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:HTR:TM01:02:M10_CH1_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:HTR:TM01:02:M10_CH1_SPARE.HIHI CP")
  field(OUT, "PLC:HTR:TM01:02:M10_CH1_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:HTR:TM01:02:M10_CH1_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:HTR:TM01:02:M10_CH1_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[37]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:HTR:TM01:02:M10_CH1_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:HTR:TM01:02:M10_CH1_SPARE.LOLO CP")
  field(OUT, "PLC:HTR:TM01:02:M10_CH1_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:HTR:TM01:02:M10_CH1_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M10_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[10] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M10_CH02_TEMP") {
  field(DESC, "Spare          ")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:HTR:TM01:02:M10_CH2_SPARE")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[38]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M10_CH02_ALIAS") {
    field(VAL,"PLC:HTR:TM01:02:M10_CH2_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:HTR:TM01:02:M10_CH2_SPARE") {
  field(DESC, "Spare          ")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M10_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:HTR:TM01:02:M10_CH2_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[38]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:HTR:TM01:02:M10_CH2_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:HTR:TM01:02:M10_CH2_SPARE.HIHI CP")
  field(OUT, "PLC:HTR:TM01:02:M10_CH2_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:HTR:TM01:02:M10_CH2_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:HTR:TM01:02:M10_CH2_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[38]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:HTR:TM01:02:M10_CH2_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:HTR:TM01:02:M10_CH2_SPARE.LOLO CP")
  field(OUT, "PLC:HTR:TM01:02:M10_CH2_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:HTR:TM01:02:M10_CH2_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M10_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[10] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M10_CH03_TEMP") {
  field(DESC, "Spare          ")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:HTR:TM01:02:M10_CH3_SPARE")
  field(INP , "@PLC_HTR_TM01 CR02_Temp[39]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M10_CH03_ALIAS") {
    field(VAL,"PLC:HTR:TM01:02:M10_CH3_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:HTR:TM01:02:M10_CH3_SPARE") {
  field(DESC, "Spare          ")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M10_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:HTR:TM01:02:M10_CH3_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_HiTemp[39]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:HTR:TM01:02:M10_CH3_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:HTR:TM01:02:M10_CH3_SPARE.HIHI CP")
  field(OUT, "PLC:HTR:TM01:02:M10_CH3_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:HTR:TM01:02:M10_CH3_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:HTR:TM01:02:M10_CH3_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_HTR_TM01 CR02_LoTemp[39]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:HTR:TM01:02:M10_CH3_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:HTR:TM01:02:M10_CH3_SPARE.LOLO CP")
  field(OUT, "PLC:HTR:TM01:02:M10_CH3_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:HTR:TM01:02:M10_CH3_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:HTR:TM01:CR02_M10_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[10] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IF8 is a analog 8 channel input module that monitors a flow Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M11_CH0_FLOW") {
  field(DESC, "PC0H00 Flow")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:HTR:103:FLOW")
  field(INP , "@PLC_HTR_TM01 CR02_Flow[0]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-6.5")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M11_CH0_ALIAS") {
    field(VAL,"COLL:HTR:103:FLOW")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:HTR:103:FLOW") {
  field(DESC, "PC0H00 Flow")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M11_CH0_FLOW CA MS")
  field(EGU, "GPM")
  field(HOPR, "100")
  field(LOPR, "-10")
  field(HIHI, "1.1")
  field(LOLO, "0.2")
  field(HIGH, "1.0")
  field(LOW, "0.3")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Flow high limit
record(ao, "COLL:HTR:103:FLOWHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(OUT, "@PLC_HTR_TM01 CR02_HiFlow[0]")
  field(EGU, "GPM")
  field(PREC, "2")
  field(ASG, "MCC")
}

record(calcout, "COLL:HTR:103:FLOWHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:HTR:103:FLOW.HIHI CP")
  field(OUT, "COLL:HTR:103:FLOWHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:HTR:103:FLOWHLIMDES")
}

# Flow low limit
record(ao, "COLL:HTR:103:FLOWLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(OUT, "@PLC_HTR_TM01 CR02_LoFlow[0]")
  field(EGU, "GPM")
  field(PREC, "2")
  field(ASG, "MCC")
}

record(calcout, "COLL:HTR:103:FLOWLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:HTR:103:FLOW.LOLO CP")
  field(OUT, "COLL:HTR:103:FLOWLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:HTR:103:FLOWLLIMDES")
}

# Flow meter status
record(bi, "PLC:HTR:TM01:CR02_M11_CH0_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[11] B 0")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IF8 is a analog 8 channel input module that monitors a flow Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:HTR:TM01:CR02_M11_CH1_FLOW") {
  field(DESC, "LLRF Rack Flow Meter")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:DIAG0:340:RACK:FLOW")
  field(INP , "@PLC_HTR_TM01 CR02_Flow[1]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-6.5")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:HTR:TM01:CR02_M11_CH1_ALIAS") {
    field(VAL,"ACCL:DIAG0:340:RACK:FLOW")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:DIAG0:340:RACK:FLOW") {
  field(DESC, "LLRF Rack Flow Meter")
  field(PREC, "2")
  field(INP, "PLC:HTR:TM01:CR02_M11_CH1_FLOW CA MS")
  field(EGU, "GPM")
  field(HOPR, "100")
  field(LOPR, "-10")
  field(HIHI, "6.1")
  field(LOLO, "1.9")
  field(HIGH, "6.0")
  field(LOW, "2.0")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Flow high limit
record(ao, "ACCL:DIAG0:340:RACK:FLOWHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(OUT, "@PLC_HTR_TM01 CR02_HiFlow[1]")
  field(EGU, "GPM")
  field(PREC, "2")
  field(ASG, "MCC")
}

record(calcout, "ACCL:DIAG0:340:RACK:FLOWHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:DIAG0:340:RACK:FLOW.HIHI CP")
  field(OUT, "ACCL:DIAG0:340:RACK:FLOWHLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:DIAG0:340:RACK:FLOWHLIMDES")
}

# Flow low limit
record(ao, "ACCL:DIAG0:340:RACK:FLOWLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(OUT, "@PLC_HTR_TM01 CR02_LoFlow[1]")
  field(EGU, "GPM")
  field(PREC, "2")
  field(ASG, "MCC")
}

record(calcout, "ACCL:DIAG0:340:RACK:FLOWLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:DIAG0:340:RACK:FLOW.LOLO CP")
  field(OUT, "ACCL:DIAG0:340:RACK:FLOWLLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:DIAG0:340:RACK:FLOWLLIMDES")
}

# Flow meter status
record(bi, "PLC:HTR:TM01:CR02_M11_CH1_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_HTR_TM01 CR02_Ch_Faults[11] B 1")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}