#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(ai, "PLC:BC2B:TM01:STATUSRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[5]")
  field(FLNK, "PLC:BC2B:TM01:DEVICESTATUSRAW")
}

record(ai, "PLC:BC2B:TM01:MODELRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[6]")
  field(FLNK, "PLC:BC2B:TM01:MODELCALC")
}

record(ai, "PLC:BC2B:TM01:UPTIMESEC") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[17]")
  field(FLNK, "PLC:BC2B:TM01:UPTIMEHOURS PP MS")
}

record(calc, "PLC:BC2B:TM01:UPTIMEHOURS") {
  field(FLNK, "PLC:BC2B:TM01:UPTIMEMINUTES PP MS")
  field(CALC, "FLOOR(A/3600)")
  field(INPA, "PLC:BC2B:TM01:UPTIMESEC")
  field(EGU, "Hours")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC NPP MS")
}

record(calc, "PLC:BC2B:TM01:UPTIMEMINUTES") {
  field(FLNK, "PLC:BC2B:TM01:UPTIMESECONDS PP MS")
  field(CALC, "FLOOR((A%3600)/60)")
  field(INPA, "PLC:BC2B:TM01:UPTIMESEC")
  field(EGU, "Minutes")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:BC2B:TM01:UPTIMESECONDS") {
  field(CALC, "A%60")
  field(INPA, "PLC:BC2B:TM01:UPTIMESEC")
  field(EGU, "Seconds")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(bi, "PLC:BC2B:TM01:HEARTBEATRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[19] B 0")
  field(ZNAM, "ZERO")
  field(ONAM, "ONE")
  field(FLNK, "PLC:BC2B:TM01:COMMLINK")
}

record(mbbi, "PLC:BC2B:TM01:MODEL") {
  field(INP, "PLC:BC2B:TM01:MODELCALC NPP MS")
  field(ZRST, "UNKNOWN")
  field(ONST, "CTL_LGX_L61")
  field(TWST, "CTL_LGX_5555")
  field(THST, "CTL_LTX_5550")
  field(FRST, "CMP_LGX_L32")
}

record(ai, "PLC:BC2B:TM01:FWVERSIONRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[7]")
  field(FLNK, "PLC:BC2B:TM01:FWVERSIONMAJ")
}

record(calc, "PLC:BC2B:TM01:FWVERSIONMAJ") {
  field(FLNK, "PLC:BC2B:TM01:FWVERSIONMIN")
  field(CALC, "A%16")
  field(INPA, "PLC:BC2B:TM01:FWVERSIONRAW NPP MS")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:BC2B:TM01:FWVERSIONMIN") {
  field(CALC, "(A/256)%16")
  field(INPA, "PLC:BC2B:TM01:FWVERSIONRAW NPP MS")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:BC2B:TM01:MODELCALC") {
  field(FLNK, "PLC:BC2B:TM01:MODEL")
  field(CALC, "A=54?1:A=51?2:A=3?3:A=77?4:0")
  field(INPA, "PLC:BC2B:TM01:MODELRAW NPP MS")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:BC2B:TM01:DEVICESTATUSCALC") {
  field(FLNK, "PLC:BC2B:TM01:DEVICESTATUS")
  field(CALC, "A=B?1:A=C?2:A=D?3:A=E?4:A=F?5:A=G?6:0")
  field(INPA, "PLC:BC2B:TM01:DEVICESTATUSRAW NPP MS")
  field(INPB, "0x7")
  field(INPC, "0x6")
  field(INPD, "0x5")
  field(INPE, "0x4")
  field(INPF, "0x1")
}

record(calc, "PLC:BC2B:TM01:DEVICESTATUSRAW") {
  field(FLNK, "PLC:BC2B:TM01:DEVICESTATUSCALC")
  field(CALC, "A>>4&B")
  field(INPA, "PLC:BC2B:TM01:STATUSRAW")
  field(INPB, "0xF")
  field(INPC, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(mbbi, "PLC:BC2B:TM01:DEVICESTATUS") {
  field(FLNK, "PLC:BC2B:TM01:FAULTSTATUSRAW")
  field(INP, "PLC:BC2B:TM01:DEVICESTATUSCALC NPP MS")
  field(ZRST, "UNKNOWN")
  field(ONST, "PROGRAM")
  field(TWST, "RUN")
  field(THST, "FAULTED")
  field(FRST, "FLASH_ERROR")
  field(FVST, "FLASHING")
  field(ZRSV, "MAJOR")
  field(ONSV, "MAJOR")
  field(TWSV, "NO_ALARM")
  field(THSV, "MAJOR")
  field(FRSV, "MAJOR")
  field(FVSV, "MAJOR")
}

record(calc, "PLC:BC2B:TM01:FAULTSTATUSRAW") {
  field(FLNK, "PLC:BC2B:TM01:FAULTSTATUSCALC")
  field(CALC, "A>>8&B")
  field(INPA, "PLC:BC2B:TM01:STATUSRAW")
  field(INPB, "0xF")
  field(INPC, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:BC2B:TM01:FAULTSTATUSCALC") {
  field(FLNK, "PLC:BC2B:TM01:FAULTSTATUS")
  field(CALC, "A=B?1:A=C?2:A=D?3:A=E?4:0")
  field(INPA, "PLC:BC2B:TM01:FAULTSTATUSRAW NPP MS")
  field(INPB, "0x0004")
  field(INPC, "0x0003")
  field(INPD, "0x0002")
  field(INPE, "0x0001")
}

record(mbbi, "PLC:BC2B:TM01:FAULTSTATUS") {
  field(FLNK, "PLC:BC2B:TM01:KEYSTATUSRAW")
  field(INP, "PLC:BC2B:TM01:FAULTSTATUSCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MAJOR_UNRECOVBL")
  field(TWST, "MAJOR_RECOVBL")
  field(THST, "MINOR_UNRECOVBL")
  field(FRST, "MINOR_RECOVBL")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "MAJOR")
  field(THSV, "MINOR")
  field(FRSV, "NO_ALARM")
}

record(calc, "PLC:BC2B:TM01:KEYSTATUSRAW") {
  field(FLNK, "PLC:BC2B:TM01:KEYSTATUSCALC")
  field(CALC, "A>>12&B")
  field(INPA, "PLC:BC2B:TM01:STATUSRAW")
  field(INPB, "0x3")
  field(INPC, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:BC2B:TM01:KEYSTATUSCALC") {
  field(FLNK, "PLC:BC2B:TM01:KEYSTATUS")
  field(CALC, "A=B?1:A=C?2:A=D?3:0")
  field(INPA, "PLC:BC2B:TM01:KEYSTATUSRAW NPP MS")
  field(INPB, "0x3")
  field(INPC, "0x2")
  field(INPD, "0x1")
}

record(mbbi, "PLC:BC2B:TM01:KEYSTATUS") {
  field(INP, "PLC:BC2B:TM01:KEYSTATUSCALC NPP MS")
  field(ZRST, "UNKNOWN")
  field(ONST, "REMOTE")
  field(TWST, "PROGRAM")
  field(THST, "RUN")
  field(ZRSV, "MAJOR")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "NO_ALARM")
}

record(ai, "PLC:BC2B:TM01:MAJORFAULTRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[8]")
  field(FLNK, "PLC:BC2B:TM01:FAULTPOWERCALC")
}

record(ai, "PLC:BC2B:TM01:MINORFAULTRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[9]")
}

record(calc, "PLC:BC2B:TM01:FAULTPOWERCALC") {
  field(FLNK, "PLC:BC2B:TM01:FAULTPOWER")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:BC2B:TM01:MAJORFAULTRAW")
  field(INPB, "PLC:BC2B:TM01:MINORFAULTRAW")
  field(INPC, "0x2")
  field(INPD, "PLC:BC2B:TM01:HEARTBEATCLC NPP MS")
}

record(mbbi, "PLC:BC2B:TM01:FAULTPOWER") {
  field(FLNK, "PLC:BC2B:TM01:FAULTIOCALC")
  field(INP, "PLC:BC2B:TM01:FAULTPOWERCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
}

record(calc, "PLC:BC2B:TM01:FAULTIOCALC") {
  field(FLNK, "PLC:BC2B:TM01:FAULTIO")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:BC2B:TM01:MAJORFAULTRAW")
  field(INPB, "PLC:BC2B:TM01:MINORFAULTRAW")
  field(INPC, "0x8")
  field(INPD, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(mbbi, "PLC:BC2B:TM01:FAULTIO") {
  field(FLNK, "PLC:BC2B:TM01:FAULTPROGRAMCALC")
  field(INP, "PLC:BC2B:TM01:FAULTIOCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
}

record(calc, "PLC:BC2B:TM01:FAULTPROGRAMCALC") {
  field(FLNK, "PLC:BC2B:TM01:FAULTPROGRAM")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:BC2B:TM01:MAJORFAULTRAW")
  field(INPB, "PLC:BC2B:TM01:MINORFAULTRAW")
  field(INPC, "0x10")
  field(INPD, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(mbbi, "PLC:BC2B:TM01:FAULTPROGRAM") {
  field(FLNK, "PLC:BC2B:TM01:FAULTFLTHNDLCALC")
  field(INP, "PLC:BC2B:TM01:FAULTPROGRAMCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
}

record(mbbi, "PLC:BC2B:TM01:FAULTFLTHNDL") {
  field(FLNK, "PLC:BC2B:TM01:FAULTWTCHDOGCALC")
  field(INP, "PLC:BC2B:TM01:FAULTFLTHNDLCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
}

record(calc, "PLC:BC2B:TM01:FAULTFLTHNDLCALC") {
  field(FLNK, "PLC:BC2B:TM01:FAULTFLTHNDL")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:BC2B:TM01:MAJORFAULTRAW")
  field(INPB, "PLC:BC2B:TM01:MINORFAULTRAW")
  field(INPC, "0x20")
  field(INPD, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:BC2B:TM01:FAULTWTCHDOGCALC") {
  field(FLNK, "PLC:BC2B:TM01:FAULTWTCHDOG")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:BC2B:TM01:MAJORFAULTRAW")
  field(INPB, "PLC:BC2B:TM01:MINORFAULTRAW")
  field(INPC, "0x40")
  field(INPD, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(mbbi, "PLC:BC2B:TM01:FAULTWTCHDOG") {
  field(FLNK, "PLC:BC2B:TM01:FAULTSTACKCALC")
  field(INP, "PLC:BC2B:TM01:FAULTWTCHDOGCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
}

record(calc, "PLC:BC2B:TM01:FAULTSTACKCALC") {
  field(FLNK, "PLC:BC2B:TM01:FAULTSTACK")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:BC2B:TM01:MAJORFAULTRAW")
  field(INPB, "PLC:BC2B:TM01:MINORFAULTRAW")
  field(INPC, "0x80")
  field(INPD, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}


record(mbbi, "PLC:BC2B:TM01:FAULTSTACK") {
  field(FLNK, "PLC:BC2B:TM01:FAULTMODECHGCALC")
  field(INP, "PLC:BC2B:TM01:FAULTSTACKCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "NO_ALARM")
  field(TWSV, "MAJOR")
}

record(calc, "PLC:BC2B:TM01:FAULTMODECHGCALC") {
  field(FLNK, "PLC:BC2B:TM01:FAULTMODECHG")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:BC2B:TM01:MAJORFAULTRAW")
  field(INPB, "PLC:BC2B:TM01:MINORFAULTRAW")
  field(INPC, "0x100")
  field(INPD, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(mbbi, "PLC:BC2B:TM01:FAULTMODECHG") {
  field(FLNK, "PLC:BC2B:TM01:FAULTSERIALCALC")
  field(INP, "PLC:BC2B:TM01:FAULTMODECHGCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
}

record(calc, "PLC:BC2B:TM01:FAULTSERIALCALC") {
  field(FLNK, "PLC:BC2B:TM01:FAULTSERIAL")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:BC2B:TM01:MAJORFAULTRAW")
  field(INPB, "PLC:BC2B:TM01:MINORFAULTRAW")
  field(INPC, "0x200")
  field(INPD, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(mbbi, "PLC:BC2B:TM01:FAULTSERIAL") {
  field(FLNK, "PLC:BC2B:TM01:FAULTBATTERYCALC")
  field(INP, "PLC:BC2B:TM01:FAULTSERIALCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
}

record(mbbi, "PLC:BC2B:TM01:FAULTBATTERY") {
  field(FLNK, "PLC:BC2B:TM01:FAULTMOTIONCALC")
  field(INP, "PLC:BC2B:TM01:FAULTBATTERYCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
}

record(calc, "PLC:BC2B:TM01:FAULTBATTERYCALC") {
  field(FLNK, "PLC:BC2B:TM01:FAULTBATTERY")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:BC2B:TM01:MAJORFAULTRAW")
  field(INPB, "PLC:BC2B:TM01:MINORFAULTRAW")
  field(INPC, "0x400")
  field(INPD, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:BC2B:TM01:FAULTMOTIONCALC") {
  field(FLNK, "PLC:BC2B:TM01:FAULTMOTION")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:BC2B:TM01:MAJORFAULTRAW")
  field(INPB, "PLC:BC2B:TM01:MINORFAULTRAW")
  field(INPC, "0x800")
  field(INPD, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(mbbi, "PLC:BC2B:TM01:FAULTMOTION") {
  field(INP, "PLC:BC2B:TM01:FAULTMOTIONCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
}

record(ai, "PLC:BC2B:TM01:VERSIONMAJORDES") {
  field(PINI, "YES")
  field(FLNK, "PLC:BC2B:TM01:VERSIONMAJORCALCHI")
  field(VAL, "1")
  field(PREC, "0")
}

record(calcout, "PLC:BC2B:TM01:VERSIONMAJORCALCHI") {
  field(FLNK, "PLC:BC2B:TM01:VERSIONMAJORCALCLO")
  field(CALC, "A+1")
  field(INPA, "PLC:BC2B:TM01:VERSIONMAJORDES")
  field(OUT, "PLC:BC2B:TM01:VERSIONMAJOR.HIGH")
}

record(calcout, "PLC:BC2B:TM01:VERSIONMAJORCALCLO") {
  field(CALC, "A-1")
  field(INPA, "PLC:BC2B:TM01:VERSIONMAJORDES")
  field(OUT, "PLC:BC2B:TM01:VERSIONMAJOR.LOW")
}

record(ai, "PLC:BC2B:TM01:VERSIONMINORDES") {
  field(PINI, "YES")
  field(FLNK, "PLC:BC2B:TM01:VERSIONMINORCALCHI")
  field(VAL, "1")
  field(PREC, "0")
}

record(calcout, "PLC:BC2B:TM01:VERSIONMINORCALCLO") {
  field(CALC, "A-1")
  field(INPA, "PLC:BC2B:TM01:VERSIONMINORDES.VAL")
  field(OUT, "PLC:BC2B:TM01:VERSIONMINOR.LOW")
}

record(calcout, "PLC:BC2B:TM01:VERSIONMINORCALCHI") {
  field(FLNK, "PLC:BC2B:TM01:VERSIONMINORCALCLO")
  field(CALC, "A+1")
  field(INPA, "PLC:BC2B:TM01:VERSIONMINORDES.VAL")
  field(OUT, "PLC:BC2B:TM01:VERSIONMINOR.HIGH")
}

record(ai, "PLC:BC2B:TM01:VERSIONREVDES") {
  field(PINI, "YES")
  field(FLNK, "PLC:BC2B:TM01:VERSIONREVCALCHI")
  field(VAL, "1")
  field(PREC, "0")
}

record(calcout, "PLC:BC2B:TM01:VERSIONREVCALCHI") {
  field(FLNK, "PLC:BC2B:TM01:VERSIONREVCALCLO")
  field(CALC, "A+1")
  field(INPA, "PLC:BC2B:TM01:VERSIONREVDES.VAL")
  field(OUT, "PLC:BC2B:TM01:VERSIONREV.HIGH")
}

record(calcout, "PLC:BC2B:TM01:VERSIONREVCALCLO") {
  field(CALC, "A-1")
  field(INPA, "PLC:BC2B:TM01:VERSIONREVDES.VAL")
  field(OUT, "PLC:BC2B:TM01:VERSIONREV.LOW")
}

record(calc, "PLC:BC2B:TM01:HEARTBEATCALC") {
  field(FLNK, "PLC:BC2B:TM01:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:HEARTBEATRAW")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCALC")
}

record(bi, "PLC:BC2B:TM01:HEARTBEATOK") {
  field(FLNK, "PLC:BC2B:TM01:HEARTBEATE01")
  field(INP, "PLC:BC2B:TM01:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "PLC:BC2B:TM01:HEARTBEATERR") {
  field(FLNK, "PLC:BC2B:TM01:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "PLC:BC2B:TM01:HEARTBEATCALC.A")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCALC.B")
}

record(calc, "PLC:BC2B:TM01:HEARTBEATECT") {
  field(FLNK, "PLC:BC2B:TM01:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "PLC:BC2B:TM01:HEARTBEATE01")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATE02")
  field(INPC, "PLC:BC2B:TM01:HEARTBEATE03")
  field(INPD, "PLC:BC2B:TM01:HEARTBEATE04")
  field(INPE, "PLC:BC2B:TM01:HEARTBEATE05")
  field(INPF, "PLC:BC2B:TM01:HEARTBEATE06")
  field(INPG, "PLC:BC2B:TM01:HEARTBEATE07")
  field(INPH, "PLC:BC2B:TM01:HEARTBEATE08")
  field(INPI, "PLC:BC2B:TM01:HEARTBEATE09")
  field(INPJ, "PLC:BC2B:TM01:HEARTBEATE10")
  field(HIHI, "7")
  field(LOLO, "-1")
  field(HIGH, "5")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "PLC:BC2B:TM01:HEARTBEATE09") {
  field(FLNK, "PLC:BC2B:TM01:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:HEARTBEATE08.B")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATE09.VAL")
}

record(calc, "PLC:BC2B:TM01:HEARTBEATE08") {
  field(FLNK, "PLC:BC2B:TM01:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:HEARTBEATE07.B")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATE08.VAL")
}

record(calc, "PLC:BC2B:TM01:HEARTBEATE07") {
  field(FLNK, "PLC:BC2B:TM01:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:HEARTBEATE06.B")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATE07.VAL")
}

record(calc, "PLC:BC2B:TM01:HEARTBEATE06") {
  field(FLNK, "PLC:BC2B:TM01:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:HEARTBEATE05.B")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATE06.VAL")
}

record(calc, "PLC:BC2B:TM01:HEARTBEATE05") {
  field(FLNK, "PLC:BC2B:TM01:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:HEARTBEATE04.B")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATE05.VAL")
}

record(calc, "PLC:BC2B:TM01:HEARTBEATE04") {
  field(FLNK, "PLC:BC2B:TM01:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:HEARTBEATE03.B")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATE04.VAL")
}

record(calc, "PLC:BC2B:TM01:HEARTBEATE03") {
  field(FLNK, "PLC:BC2B:TM01:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:HEARTBEATE02.B")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATE03.VAL")
}

record(calc, "PLC:BC2B:TM01:HEARTBEATE02") {
  field(FLNK, "PLC:BC2B:TM01:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:HEARTBEATE01.B")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATE02.VAL")
}

record(calc, "PLC:BC2B:TM01:HEARTBEATE01") {
  field(FLNK, "PLC:BC2B:TM01:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:HEARTBEATERR")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATE01.VAL")
}

record(calc, "PLC:BC2B:TM01:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "PLC:BC2B:TM01:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "PLC:BC2B:TM01:HEARTBEATSUM") {
  field(FLNK, "PLC:BC2B:TM01:HEARTBEATCLC")
  field(INP, "PLC:BC2B:TM01:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(ai, "PLC:BC2B:TM01:UPTIMEDAYRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[18]")
  field(FLNK, "PLC:BC2B:TM01:UPTIMEDAY")
}

record(calc, "PLC:BC2B:TM01:UPTIMEDAY") {
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:UPTIMEDAYRAW")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(ai, "PLC:BC2B:TM01:TODYEARRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[10]")
  field(FLNK, "PLC:BC2B:TM01:TODYEAR")
}

record(ai, "PLC:BC2B:TM01:TODDAYRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[12]")
  field(SCAN, "1 second")
  field(FLNK, "PLC:BC2B:TM01:TODDAY")
}

record(ai, "PLC:BC2B:TM01:TODMONTHRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[11]")
  field(FLNK, "PLC:BC2B:TM01:TODMONTH")
  field(SCAN, "1 second")
}

record(ai, "PLC:BC2B:TM01:TODHOURRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[13]")
  field(FLNK, "PLC:BC2B:TM01:TODHOUR")
}

record(ai, "PLC:BC2B:TM01:TODMINUTERAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[14]")
  field(FLNK, "PLC:BC2B:TM01:TODMINUTE")
  field(SCAN, "1 second")
}

record(ai, "PLC:BC2B:TM01:TODSECONDRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[15]")
  field(SCAN, "1 second")
  field(FLNK, "PLC:BC2B:TM01:TODSECOND")
}

record(calc, "PLC:BC2B:TM01:TODYEAR") {
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:TODYEARRAW NPP MS")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:BC2B:TM01:TODMONTH") {
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:TODMONTHRAW NPP MS")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:BC2B:TM01:TODDAY") {
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:TODDAYRAW NPP MS")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:BC2B:TM01:TODHOUR") {
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:TODHOURRAW NPP MS")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:BC2B:TM01:TODMINUTE") {
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:TODMINUTERAW NPP MS")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:BC2B:TM01:TODSECOND") {
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:TODSECONDRAW NPP MS")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(ai, "PLC:BC2B:TM01:VERSIONMAJORRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[36]")
  field(HYST, "1")
  field(FLNK, "PLC:BC2B:TM01:VERSIONMAJOR")
}

record(ai, "PLC:BC2B:TM01:VERSIONMINORRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[37]")
  field(FLNK, "PLC:BC2B:TM01:VERSIONMINOR")
}

record(calc, "PLC:BC2B:TM01:VERSIONMAJOR") {
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:VERSIONMAJORRAW NPP MS")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
  field(HSV, "MAJOR")
  field(LSV, "MAJOR")
}

record(calc, "PLC:BC2B:TM01:VERSIONMINOR") {
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:VERSIONMINORRAW NPP MS")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
  field(HSV, "MAJOR")
  field(LSV, "MAJOR")
}

record(ai, "PLC:BC2B:TM01:VERSIONREVRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[38]")
  field(FLNK, "PLC:BC2B:TM01:VERSIONREV")
}

record(calc, "PLC:BC2B:TM01:VERSIONREV") {
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:VERSIONREVRAW NPP MS")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
  field(HSV, "MAJOR")
  field(LSV, "MAJOR")
}

record(ai, "PLC:BC2B:TM01:SERIALNUMBERRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[4]")
  field(FLNK, "PLC:BC2B:TM01:SERIALNUMBER")
}

record(calc, "PLC:BC2B:TM01:SERIALNUMBER") {
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:SERIALNUMBERRAW NPP MS")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(mbbi, "PLC:BC2B:TM01:COMMLINK") {
  field(FLNK, "PLC:BC2B:TM01:HEARTBEATCALC")
  field(INP, "PLC:BC2B:TM01:HEARTBEATRAW.SEVR")
  field(ZRST, "OK")
  field(ONST, "OK")
  field(TWST, "OK")
  field(THST, "FAULT")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "NO_ALARM")
  field(TWSV, "NO_ALARM")
  field(THSV, "MAJOR")
}

record(calc, "PLC:BC2B:TM01:HEARTBEATE10") {
  field(FLNK, "PLC:BC2B:TM01:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:HEARTBEATE09.B")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATE10.VAL")
}

record(ai, "PLC:BC2B:TM01:DOCPREFIXRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:DOCPREFIXCALC")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[31]")
}

record(calc, "PLC:BC2B:TM01:DOCPREFIXCALC") {
  field(FLNK, "PLC:BC2B:TM01:DOCPREFIX")
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:DOCPREFIXRAW")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(mbbi, "PLC:BC2B:TM01:DOCPREFIX") {
  field(INP, "PLC:BC2B:TM01:DOCPREFIXCALC NPP MS")
  field(ZRVL, "0")
  field(ONVL, "1")
  field(ZRST, "NONE")
  field(ONST, "SD")
  field(TWVL, "2")
  field(THVL, "3")
  field(FRVL, "4")
  field(FVVL, "5")
  field(SXVL, "6")
  field(SVVL, "7")
  field(EIVL, "8")
  field(NIVL, "9")
  field(TEVL, "10")
  field(ELVL, "11")
  field(TWST, "BD")
  field(THST, "DL")
  field(FRST, "EI")
  field(FVST, "FC")
  field(SXST, "FS")
  field(SVST, "IM")
  field(EIST, "LD")
  field(NIST, "OM")
  field(TEST, "QT")
  field(ELST, "WD")
}

record(ai, "PLC:BC2B:TM01:DOCSERIESRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:DOCSERIES")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[32]")
}

record(calc, "PLC:BC2B:TM01:DOCSERIES") {
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:DOCSERIESRAW.VAL")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(ai, "PLC:BC2B:TM01:DOCBASERAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:DOCBASE")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[33]")
}

record(calc, "PLC:BC2B:TM01:DOCBASE") {
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:DOCBASERAW.VAL")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(ai, "PLC:BC2B:TM01:DOCSUFFIXRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:DOCSUFFIX")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[34]")
}

record(calc, "PLC:BC2B:TM01:DOCSUFFIX") {
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:DOCSUFFIXRAW")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(ai, "PLC:BC2B:TM01:DOCREVRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:DOCREV")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[35]")
}

record(calc, "PLC:BC2B:TM01:DOCREV") {
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:DOCREVRAW")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(stringin, "PLC:BC2B:TM01:SUBSYSTEM") {
  field(PINI, "YES")
  field(VAL, "TEMPERATURE")
}

record(ai, "PLC:BC2B:TM01:PLCADMINVMAJRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[0]")
  field(SCAN, "1 second")
  field(FLNK, "PLC:BC2B:TM01:PLCADMINVMAJ")
}

record(calc, "PLC:BC2B:TM01:PLCADMINVMAJ") {
  field(INPA, "PLC:BC2B:TM01:PLCADMINVMAJRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
  field(PREC, "0")
  field(HIHI, "2")
  field(LOLO, "0")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
}

record(ai, "PLC:BC2B:TM01:PLCADMINVMINRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[1]")
  field(SCAN, "1 second")
  field(FLNK, "PLC:BC2B:TM01:PLCADMINVMIN")
}

record(calc, "PLC:BC2B:TM01:PLCADMINVMIN") {
  field(INPA, "PLC:BC2B:TM01:PLCADMINVMINRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
  field(PREC, "0")
  field(HIHI, "1")
  field(LOLO, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
}

record(ai, "PLC:BC2B:TM01:PLCADMINVREVRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[2]")
  field(SCAN, "1 second")
  field(FLNK, "PLC:BC2B:TM01:PLCADMINVREV")
}

record(calc, "PLC:BC2B:TM01:PLCADMINVREV") {
  field(INPA, "PLC:BC2B:TM01:PLCADMINVREVRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
  field(PREC, "0")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
}

record(ai, "PLC:BC2B:TM01:PROGPLCATMAXRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[23]")
  field(SCAN, "1 second")
  field(FLNK, "PLC:BC2B:TM01:PROGPLCATMAX")
}

record(ai, "PLC:BC2B:TM01:PROGPLCATLSTRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[22]")
  field(FLNK, "PLC:BC2B:TM01:PROGPLCATLST")
}

record(calc, "PLC:BC2B:TM01:PROGPLCATLST") {
  field(INPA, "PLC:BC2B:TM01:PROGPLCATLSTRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:BC2B:TM01:PROGPLCATMAX") {
  field(INPA, "PLC:BC2B:TM01:PROGPLCATMAXRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(stringin, "PLC:BC2B:TM01:PLCADMINTAG") {
  field(PINI, "YES")
  field(VAL, "PLCADMIN_PLC_BC2B_TM01")
}

record(ai, "PLC:BC2B:TM01:TASKMAINTLSTRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[20]")
  field(FLNK, "PLC:BC2B:TM01:TASKMAINTLST")
}

record(calc, "PLC:BC2B:TM01:TASKMAINTLST") {
  field(INPA, "PLC:BC2B:TM01:TASKMAINTLSTRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(ai, "PLC:BC2B:TM01:TASKMAINTMAXRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[21]")
  field(FLNK, "PLC:BC2B:TM01:TASKMAINTMAX")
  field(SCAN, "1 second")
}

record(calc, "PLC:BC2B:TM01:TASKMAINTMAX") {
  field(INPA, "PLC:BC2B:TM01:TASKMAINTMAXRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(ai, "PLC:BC2B:TM01:PROG1TLSTRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[24]")
  field(FLNK, "PLC:BC2B:TM01:PROG1TLST")
}

record(ai, "PLC:BC2B:TM01:PROG1TMAXRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[25]")
  field(SCAN, "1 second")
  field(FLNK, "PLC:BC2B:TM01:PROG1TMAX")
}

record(calc, "PLC:BC2B:TM01:PROG1TLST") {
  field(INPA, "PLC:BC2B:TM01:PROG1TLSTRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:BC2B:TM01:PROG1TMAX") {
  field(INPA, "PLC:BC2B:TM01:PROG1TMAXRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(ai, "PLC:BC2B:TM01:PROG2TLSTRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[26]")
  field(FLNK, "PLC:BC2B:TM01:PROG2TLST")
}

record(ai, "PLC:BC2B:TM01:PROG2TMAXRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[27]")
  field(SCAN, "1 second")
  field(FLNK, "PLC:BC2B:TM01:PROG2TMAX")
}

record(calc, "PLC:BC2B:TM01:PROG2TLST") {
  field(INPA, "PLC:BC2B:TM01:PROG2TLSTRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:BC2B:TM01:PROG2TMAX") {
  field(INPA, "PLC:BC2B:TM01:PROG2TMAXRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(ai, "PLC:BC2B:TM01:PROG3TLSTRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[28]")
  field(FLNK, "PLC:BC2B:TM01:PROG3TLST")
}

record(ai, "PLC:BC2B:TM01:PROG3TMAXRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01[29]")
  field(SCAN, "1 second")
  field(FLNK, "PLC:BC2B:TM01:PROG3TMAX")
}

record(calc, "PLC:BC2B:TM01:PROG3TMAX") {
  field(INPA, "PLC:BC2B:TM01:PROG3TMAXRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:BC2B:TM01:PROG3TLST") {
  field(INPA, "PLC:BC2B:TM01:PROG3TLSTRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATCLC MS")
}

record(calc, "PLC:BC2B:TM01:STATSUMY") {
  field(SCAN, "1 second")
  field(CALC, "A")
  field(INPA, "PLC:BC2B:TM01:STATSUMY.SEVR")
  field(INPB, "PLC:BC2B:TM01:HEARTBEATSUM MS")
  field(INPC, "PLC:BC2B:TM01:FAULTSTATUS MS")
  field(INPD, "PLC:BC2B:TM01:KEYSTATUS MS")
  field(INPE, "PLC:BC2B:TM01:DEVICESTATUS MS")
  field(INPF, "PLC:BC2B:TM01:VERSIONMAJOR MS")
  field(INPG, "PLC:BC2B:TM01:VERSIONMINOR MS")
  field(INPH, "PLC:BC2B:TM01:VERSIONREV MS")
}

#! Further lines contain data used by VisualDCT
#! View(935,906,0.9)
#! Record("PLC:BC2B:TM01:STATUSRAW",2160,3987,0,1,"PLC:BC2B:TM01:STATUSRAW")
#! Field("PLC:BC2B:TM01:STATUSRAW.FLNK",16777215,1,"PLC:BC2B:TM01:STATUSRAW.FLNK")
#! Link("PLC:BC2B:TM01:STATUSRAW.FLNK","PLC:BC2B:TM01:DEVICESTATUSRAW")
#! Field("PLC:BC2B:TM01:STATUSRAW.VAL",16777215,1,"PLC:BC2B:TM01:STATUSRAW.VAL")
#! Record("PLC:BC2B:TM01:MODELRAW",4120,7,0,0,"PLC:BC2B:TM01:MODELRAW")
#! Field("PLC:BC2B:TM01:MODELRAW.FLNK",16777215,1,"PLC:BC2B:TM01:MODELRAW.FLNK")
#! Link("PLC:BC2B:TM01:MODELRAW.FLNK","PLC:BC2B:TM01:MODELCALC")
#! Field("PLC:BC2B:TM01:MODELRAW.VAL",16777215,0,"PLC:BC2B:TM01:MODELRAW.VAL")
#! Record("PLC:BC2B:TM01:UPTIMESEC",4280,1787,0,0,"PLC:BC2B:TM01:UPTIMESEC")
#! Field("PLC:BC2B:TM01:UPTIMESEC.FLNK",16777215,1,"PLC:BC2B:TM01:UPTIMESEC.FLNK")
#! Link("PLC:BC2B:TM01:UPTIMESEC.FLNK","PLC:BC2B:TM01:UPTIMEHOURS")
#! Field("PLC:BC2B:TM01:UPTIMESEC.VAL",16777215,1,"PLC:BC2B:TM01:UPTIMESEC.VAL")
#! Record("PLC:BC2B:TM01:UPTIMEHOURS",4540,1794,0,0,"PLC:BC2B:TM01:UPTIMEHOURS")
#! Field("PLC:BC2B:TM01:UPTIMEHOURS.INPA",16777215,0,"PLC:BC2B:TM01:UPTIMEHOURS.INPA")
#! Link("PLC:BC2B:TM01:UPTIMEHOURS.INPA","PLC:BC2B:TM01:UPTIMESEC.VAL")
#! Field("PLC:BC2B:TM01:UPTIMEHOURS.FLNK",16777215,1,"PLC:BC2B:TM01:UPTIMEHOURS.FLNK")
#! Link("PLC:BC2B:TM01:UPTIMEHOURS.FLNK","PLC:BC2B:TM01:UPTIMEMINUTES")
#! Field("PLC:BC2B:TM01:UPTIMEHOURS.INPB",16777215,0,"PLC:BC2B:TM01:UPTIMEHOURS.INPB")
#! Link("PLC:BC2B:TM01:UPTIMEHOURS.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:UPTIMEMINUTES",4580,2014,0,1,"PLC:BC2B:TM01:UPTIMEMINUTES")
#! Field("PLC:BC2B:TM01:UPTIMEMINUTES.INPA",16777215,0,"PLC:BC2B:TM01:UPTIMEMINUTES.INPA")
#! Link("PLC:BC2B:TM01:UPTIMEMINUTES.INPA","PLC:BC2B:TM01:UPTIMESEC.VAL")
#! Field("PLC:BC2B:TM01:UPTIMEMINUTES.FLNK",16777215,1,"PLC:BC2B:TM01:UPTIMEMINUTES.FLNK")
#! Link("PLC:BC2B:TM01:UPTIMEMINUTES.FLNK","PLC:BC2B:TM01:UPTIMESECONDS")
#! Field("PLC:BC2B:TM01:UPTIMEMINUTES.INPB",16777215,0,"PLC:BC2B:TM01:UPTIMEMINUTES.INPB")
#! Link("PLC:BC2B:TM01:UPTIMEMINUTES.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:UPTIMESECONDS",4620,2227,0,1,"PLC:BC2B:TM01:UPTIMESECONDS")
#! Field("PLC:BC2B:TM01:UPTIMESECONDS.INPA",16777215,0,"PLC:BC2B:TM01:UPTIMESECONDS.INPA")
#! Link("PLC:BC2B:TM01:UPTIMESECONDS.INPA","PLC:BC2B:TM01:UPTIMESEC.VAL")
#! Field("PLC:BC2B:TM01:UPTIMESECONDS.INPB",16777215,0,"PLC:BC2B:TM01:UPTIMESECONDS.INPB")
#! Link("PLC:BC2B:TM01:UPTIMESECONDS.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:HEARTBEATRAW",60,79,0,1,"PLC:BC2B:TM01:HEARTBEATRAW")
#! Field("PLC:BC2B:TM01:HEARTBEATRAW.FLNK",16777215,1,"PLC:BC2B:TM01:HEARTBEATRAW.FLNK")
#! Link("PLC:BC2B:TM01:HEARTBEATRAW.FLNK","PLC:BC2B:TM01:COMMLINK")
#! Field("PLC:BC2B:TM01:HEARTBEATRAW.SEVR",16777215,1,"PLC:BC2B:TM01:HEARTBEATRAW.SEVR")
#! Field("PLC:BC2B:TM01:HEARTBEATRAW.VAL",16777215,1,"PLC:BC2B:TM01:HEARTBEATRAW.VAL")
#! Record("PLC:BC2B:TM01:MODEL",4640,54,0,0,"PLC:BC2B:TM01:MODEL")
#! Field("PLC:BC2B:TM01:MODEL.INP",16777215,0,"PLC:BC2B:TM01:MODEL.INP")
#! Link("PLC:BC2B:TM01:MODEL.INP","PLC:BC2B:TM01:MODELCALC.VAL")
#! Record("PLC:BC2B:TM01:FWVERSIONRAW",4180,227,0,0,"PLC:BC2B:TM01:FWVERSIONRAW")
#! Field("PLC:BC2B:TM01:FWVERSIONRAW.FLNK",16777215,1,"PLC:BC2B:TM01:FWVERSIONRAW.FLNK")
#! Link("PLC:BC2B:TM01:FWVERSIONRAW.FLNK","PLC:BC2B:TM01:FWVERSIONMAJ")
#! Field("PLC:BC2B:TM01:FWVERSIONRAW.VAL",16777215,1,"PLC:BC2B:TM01:FWVERSIONRAW.VAL")
#! Record("PLC:BC2B:TM01:FWVERSIONMAJ",4460,247,0,0,"PLC:BC2B:TM01:FWVERSIONMAJ")
#! Field("PLC:BC2B:TM01:FWVERSIONMAJ.FLNK",16777215,1,"PLC:BC2B:TM01:FWVERSIONMAJ.FLNK")
#! Link("PLC:BC2B:TM01:FWVERSIONMAJ.FLNK","PLC:BC2B:TM01:FWVERSIONMIN")
#! Field("PLC:BC2B:TM01:FWVERSIONMAJ.INPA",16777215,0,"PLC:BC2B:TM01:FWVERSIONMAJ.INPA")
#! Link("PLC:BC2B:TM01:FWVERSIONMAJ.INPA","PLC:BC2B:TM01:FWVERSIONRAW.VAL")
#! Field("PLC:BC2B:TM01:FWVERSIONMAJ.INPB",16777215,0,"PLC:BC2B:TM01:FWVERSIONMAJ.INPB")
#! Link("PLC:BC2B:TM01:FWVERSIONMAJ.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:FWVERSIONMIN",4720,322,0,0,"PLC:BC2B:TM01:FWVERSIONMIN")
#! Field("PLC:BC2B:TM01:FWVERSIONMIN.INPA",16777215,0,"PLC:BC2B:TM01:FWVERSIONMIN.INPA")
#! Link("PLC:BC2B:TM01:FWVERSIONMIN.INPA","PLC:BC2B:TM01:FWVERSIONRAW.VAL")
#! Field("PLC:BC2B:TM01:FWVERSIONMIN.INPB",16777215,0,"PLC:BC2B:TM01:FWVERSIONMIN.INPB")
#! Link("PLC:BC2B:TM01:FWVERSIONMIN.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:MODELCALC",4380,27,0,0,"PLC:BC2B:TM01:MODELCALC")
#! Field("PLC:BC2B:TM01:MODELCALC.INPA",16777215,0,"PLC:BC2B:TM01:MODELCALC.INPA")
#! Link("PLC:BC2B:TM01:MODELCALC.INPA","PLC:BC2B:TM01:MODELRAW.VAL")
#! Field("PLC:BC2B:TM01:MODELCALC.FLNK",16777215,1,"PLC:BC2B:TM01:MODELCALC.FLNK")
#! Link("PLC:BC2B:TM01:MODELCALC.FLNK","PLC:BC2B:TM01:MODEL")
#! Field("PLC:BC2B:TM01:MODELCALC.VAL",16777215,0,"PLC:BC2B:TM01:MODELCALC.VAL")
#! Field("PLC:BC2B:TM01:MODELCALC.INPB",16777215,0,"PLC:BC2B:TM01:MODELCALC.INPB")
#! Link("PLC:BC2B:TM01:MODELCALC.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:DEVICESTATUSCALC",2760,3930,0,0,"PLC:BC2B:TM01:DEVICESTATUSCALC")
#! Field("PLC:BC2B:TM01:DEVICESTATUSCALC.FLNK",16777215,1,"PLC:BC2B:TM01:DEVICESTATUSCALC.FLNK")
#! Link("PLC:BC2B:TM01:DEVICESTATUSCALC.FLNK","PLC:BC2B:TM01:DEVICESTATUS")
#! Field("PLC:BC2B:TM01:DEVICESTATUSCALC.INPA",16777215,0,"PLC:BC2B:TM01:DEVICESTATUSCALC.INPA")
#! Link("PLC:BC2B:TM01:DEVICESTATUSCALC.INPA","PLC:BC2B:TM01:DEVICESTATUSRAW.VAL")
#! Field("PLC:BC2B:TM01:DEVICESTATUSCALC.VAL",16777215,1,"PLC:BC2B:TM01:DEVICESTATUSCALC.VAL")
#! Record("PLC:BC2B:TM01:DEVICESTATUSRAW",2480,3974,0,0,"PLC:BC2B:TM01:DEVICESTATUSRAW")
#! Field("PLC:BC2B:TM01:DEVICESTATUSRAW.FLNK",16777215,1,"PLC:BC2B:TM01:DEVICESTATUSRAW.FLNK")
#! Link("PLC:BC2B:TM01:DEVICESTATUSRAW.FLNK","PLC:BC2B:TM01:DEVICESTATUSCALC")
#! Field("PLC:BC2B:TM01:DEVICESTATUSRAW.INPA",16777215,0,"PLC:BC2B:TM01:DEVICESTATUSRAW.INPA")
#! Link("PLC:BC2B:TM01:DEVICESTATUSRAW.INPA","PLC:BC2B:TM01:STATUSRAW.VAL")
#! Field("PLC:BC2B:TM01:DEVICESTATUSRAW.VAL",16777215,1,"PLC:BC2B:TM01:DEVICESTATUSRAW.VAL")
#! Field("PLC:BC2B:TM01:DEVICESTATUSRAW.INPC",16777215,1,"PLC:BC2B:TM01:DEVICESTATUSRAW.INPC")
#! Link("PLC:BC2B:TM01:DEVICESTATUSRAW.INPC","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:DEVICESTATUS",3040,3926,0,0,"PLC:BC2B:TM01:DEVICESTATUS")
#! Field("PLC:BC2B:TM01:DEVICESTATUS.INP",16777215,0,"PLC:BC2B:TM01:DEVICESTATUS.INP")
#! Link("PLC:BC2B:TM01:DEVICESTATUS.INP","PLC:BC2B:TM01:DEVICESTATUSCALC.VAL")
#! Field("PLC:BC2B:TM01:DEVICESTATUS.FLNK",16777215,0,"PLC:BC2B:TM01:DEVICESTATUS.FLNK")
#! Link("PLC:BC2B:TM01:DEVICESTATUS.FLNK","PLC:BC2B:TM01:FAULTSTATUSRAW")
#! Field("PLC:BC2B:TM01:DEVICESTATUS.VAL",16777215,0,"PLC:BC2B:TM01:DEVICESTATUS.VAL")
#! Record("PLC:BC2B:TM01:FAULTSTATUSRAW",2480,4274,0,1,"PLC:BC2B:TM01:FAULTSTATUSRAW")
#! Field("PLC:BC2B:TM01:FAULTSTATUSRAW.FLNK",16777215,1,"PLC:BC2B:TM01:FAULTSTATUSRAW.FLNK")
#! Link("PLC:BC2B:TM01:FAULTSTATUSRAW.FLNK","PLC:BC2B:TM01:FAULTSTATUSCALC")
#! Field("PLC:BC2B:TM01:FAULTSTATUSRAW.INPA",16777215,0,"PLC:BC2B:TM01:FAULTSTATUSRAW.INPA")
#! Link("PLC:BC2B:TM01:FAULTSTATUSRAW.INPA","PLC:BC2B:TM01:STATUSRAW.VAL")
#! Field("PLC:BC2B:TM01:FAULTSTATUSRAW.VAL",16777215,1,"PLC:BC2B:TM01:FAULTSTATUSRAW.VAL")
#! Field("PLC:BC2B:TM01:FAULTSTATUSRAW.INPC",16777215,1,"PLC:BC2B:TM01:FAULTSTATUSRAW.INPC")
#! Link("PLC:BC2B:TM01:FAULTSTATUSRAW.INPC","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:FAULTSTATUSCALC",2760,4225,0,0,"PLC:BC2B:TM01:FAULTSTATUSCALC")
#! Field("PLC:BC2B:TM01:FAULTSTATUSCALC.FLNK",16777215,1,"PLC:BC2B:TM01:FAULTSTATUSCALC.FLNK")
#! Link("PLC:BC2B:TM01:FAULTSTATUSCALC.FLNK","PLC:BC2B:TM01:FAULTSTATUS")
#! Field("PLC:BC2B:TM01:FAULTSTATUSCALC.INPA",16777215,0,"PLC:BC2B:TM01:FAULTSTATUSCALC.INPA")
#! Link("PLC:BC2B:TM01:FAULTSTATUSCALC.INPA","PLC:BC2B:TM01:FAULTSTATUSRAW.VAL")
#! Field("PLC:BC2B:TM01:FAULTSTATUSCALC.VAL",16777215,1,"PLC:BC2B:TM01:FAULTSTATUSCALC.VAL")
#! Record("PLC:BC2B:TM01:FAULTSTATUS",3040,4254,0,0,"PLC:BC2B:TM01:FAULTSTATUS")
#! Field("PLC:BC2B:TM01:FAULTSTATUS.INP",16777215,0,"PLC:BC2B:TM01:FAULTSTATUS.INP")
#! Link("PLC:BC2B:TM01:FAULTSTATUS.INP","PLC:BC2B:TM01:FAULTSTATUSCALC.VAL")
#! Field("PLC:BC2B:TM01:FAULTSTATUS.FLNK",16777215,0,"PLC:BC2B:TM01:FAULTSTATUS.FLNK")
#! Link("PLC:BC2B:TM01:FAULTSTATUS.FLNK","PLC:BC2B:TM01:KEYSTATUSRAW")
#! Field("PLC:BC2B:TM01:FAULTSTATUS.VAL",16777215,0,"PLC:BC2B:TM01:FAULTSTATUS.VAL")
#! Record("PLC:BC2B:TM01:KEYSTATUSRAW",2480,4594,0,1,"PLC:BC2B:TM01:KEYSTATUSRAW")
#! Field("PLC:BC2B:TM01:KEYSTATUSRAW.FLNK",16777215,1,"PLC:BC2B:TM01:KEYSTATUSRAW.FLNK")
#! Link("PLC:BC2B:TM01:KEYSTATUSRAW.FLNK","PLC:BC2B:TM01:KEYSTATUSCALC")
#! Field("PLC:BC2B:TM01:KEYSTATUSRAW.INPA",16777215,0,"PLC:BC2B:TM01:KEYSTATUSRAW.INPA")
#! Link("PLC:BC2B:TM01:KEYSTATUSRAW.INPA","PLC:BC2B:TM01:STATUSRAW.VAL")
#! Field("PLC:BC2B:TM01:KEYSTATUSRAW.VAL",16777215,1,"PLC:BC2B:TM01:KEYSTATUSRAW.VAL")
#! Field("PLC:BC2B:TM01:KEYSTATUSRAW.INPC",16777215,1,"PLC:BC2B:TM01:KEYSTATUSRAW.INPC")
#! Link("PLC:BC2B:TM01:KEYSTATUSRAW.INPC","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:KEYSTATUSCALC",2760,4579,0,0,"PLC:BC2B:TM01:KEYSTATUSCALC")
#! Field("PLC:BC2B:TM01:KEYSTATUSCALC.FLNK",16777215,1,"PLC:BC2B:TM01:KEYSTATUSCALC.FLNK")
#! Link("PLC:BC2B:TM01:KEYSTATUSCALC.FLNK","PLC:BC2B:TM01:KEYSTATUS")
#! Field("PLC:BC2B:TM01:KEYSTATUSCALC.INPA",16777215,0,"PLC:BC2B:TM01:KEYSTATUSCALC.INPA")
#! Link("PLC:BC2B:TM01:KEYSTATUSCALC.INPA","PLC:BC2B:TM01:KEYSTATUSRAW.VAL")
#! Field("PLC:BC2B:TM01:KEYSTATUSCALC.VAL",16777215,1,"PLC:BC2B:TM01:KEYSTATUSCALC.VAL")
#! Record("PLC:BC2B:TM01:KEYSTATUS",3040,4577,0,0,"PLC:BC2B:TM01:KEYSTATUS")
#! Field("PLC:BC2B:TM01:KEYSTATUS.INP",16777215,0,"PLC:BC2B:TM01:KEYSTATUS.INP")
#! Link("PLC:BC2B:TM01:KEYSTATUS.INP","PLC:BC2B:TM01:KEYSTATUSCALC.VAL")
#! Field("PLC:BC2B:TM01:KEYSTATUS.VAL",16777215,0,"PLC:BC2B:TM01:KEYSTATUS.VAL")
#! Record("PLC:BC2B:TM01:MAJORFAULTRAW",4020,2427,0,0,"PLC:BC2B:TM01:MAJORFAULTRAW")
#! Field("PLC:BC2B:TM01:MAJORFAULTRAW.FLNK",16777215,1,"PLC:BC2B:TM01:MAJORFAULTRAW.FLNK")
#! Link("PLC:BC2B:TM01:MAJORFAULTRAW.FLNK","PLC:BC2B:TM01:FAULTPOWERCALC")
#! Field("PLC:BC2B:TM01:MAJORFAULTRAW.VAL",16777215,1,"PLC:BC2B:TM01:MAJORFAULTRAW.VAL")
#! Record("PLC:BC2B:TM01:MINORFAULTRAW",4000,2622,0,0,"PLC:BC2B:TM01:MINORFAULTRAW")
#! Field("PLC:BC2B:TM01:MINORFAULTRAW.VAL",16777215,1,"PLC:BC2B:TM01:MINORFAULTRAW.VAL")
#! Record("PLC:BC2B:TM01:FAULTPOWERCALC",4360,2559,0,0,"PLC:BC2B:TM01:FAULTPOWERCALC")
#! Field("PLC:BC2B:TM01:FAULTPOWERCALC.INPA",16777215,0,"PLC:BC2B:TM01:FAULTPOWERCALC.INPA")
#! Link("PLC:BC2B:TM01:FAULTPOWERCALC.INPA","PLC:BC2B:TM01:MAJORFAULTRAW.VAL")
#! Field("PLC:BC2B:TM01:FAULTPOWERCALC.INPB",16777215,0,"PLC:BC2B:TM01:FAULTPOWERCALC.INPB")
#! Link("PLC:BC2B:TM01:FAULTPOWERCALC.INPB","PLC:BC2B:TM01:MINORFAULTRAW.VAL")
#! Field("PLC:BC2B:TM01:FAULTPOWERCALC.FLNK",16777215,1,"PLC:BC2B:TM01:FAULTPOWERCALC.FLNK")
#! Link("PLC:BC2B:TM01:FAULTPOWERCALC.FLNK","PLC:BC2B:TM01:FAULTPOWER")
#! Field("PLC:BC2B:TM01:FAULTPOWERCALC.VAL",16777215,1,"PLC:BC2B:TM01:FAULTPOWERCALC.VAL")
#! Field("PLC:BC2B:TM01:FAULTPOWERCALC.INPD",16777215,0,"PLC:BC2B:TM01:FAULTPOWERCALC.INPD")
#! Link("PLC:BC2B:TM01:FAULTPOWERCALC.INPD","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:FAULTPOWER",4640,2590,0,0,"PLC:BC2B:TM01:FAULTPOWER")
#! Field("PLC:BC2B:TM01:FAULTPOWER.INP",16777215,0,"PLC:BC2B:TM01:FAULTPOWER.INP")
#! Link("PLC:BC2B:TM01:FAULTPOWER.INP","PLC:BC2B:TM01:FAULTPOWERCALC.VAL")
#! Field("PLC:BC2B:TM01:FAULTPOWER.FLNK",16777215,0,"PLC:BC2B:TM01:FAULTPOWER.FLNK")
#! Link("PLC:BC2B:TM01:FAULTPOWER.FLNK","PLC:BC2B:TM01:FAULTIOCALC")
#! Record("PLC:BC2B:TM01:FAULTIOCALC",4360,2799,0,1,"PLC:BC2B:TM01:FAULTIOCALC")
#! Field("PLC:BC2B:TM01:FAULTIOCALC.FLNK",16777215,1,"PLC:BC2B:TM01:FAULTIOCALC.FLNK")
#! Link("PLC:BC2B:TM01:FAULTIOCALC.FLNK","PLC:BC2B:TM01:FAULTIO")
#! Field("PLC:BC2B:TM01:FAULTIOCALC.INPA",16777215,0,"PLC:BC2B:TM01:FAULTIOCALC.INPA")
#! Link("PLC:BC2B:TM01:FAULTIOCALC.INPA","PLC:BC2B:TM01:MAJORFAULTRAW.VAL")
#! Field("PLC:BC2B:TM01:FAULTIOCALC.INPB",16777215,0,"PLC:BC2B:TM01:FAULTIOCALC.INPB")
#! Link("PLC:BC2B:TM01:FAULTIOCALC.INPB","PLC:BC2B:TM01:MINORFAULTRAW.VAL")
#! Field("PLC:BC2B:TM01:FAULTIOCALC.VAL",16777215,1,"PLC:BC2B:TM01:FAULTIOCALC.VAL")
#! Field("PLC:BC2B:TM01:FAULTIOCALC.INPD",16777215,0,"PLC:BC2B:TM01:FAULTIOCALC.INPD")
#! Link("PLC:BC2B:TM01:FAULTIOCALC.INPD","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:FAULTIO",4640,2830,0,0,"PLC:BC2B:TM01:FAULTIO")
#! Field("PLC:BC2B:TM01:FAULTIO.INP",16777215,0,"PLC:BC2B:TM01:FAULTIO.INP")
#! Link("PLC:BC2B:TM01:FAULTIO.INP","PLC:BC2B:TM01:FAULTIOCALC.VAL")
#! Field("PLC:BC2B:TM01:FAULTIO.FLNK",16777215,0,"PLC:BC2B:TM01:FAULTIO.FLNK")
#! Link("PLC:BC2B:TM01:FAULTIO.FLNK","PLC:BC2B:TM01:FAULTPROGRAMCALC")
#! Record("PLC:BC2B:TM01:FAULTPROGRAMCALC",4360,3039,0,1,"PLC:BC2B:TM01:FAULTPROGRAMCALC")
#! Field("PLC:BC2B:TM01:FAULTPROGRAMCALC.FLNK",16777215,1,"PLC:BC2B:TM01:FAULTPROGRAMCALC.FLNK")
#! Link("PLC:BC2B:TM01:FAULTPROGRAMCALC.FLNK","PLC:BC2B:TM01:FAULTPROGRAM")
#! Field("PLC:BC2B:TM01:FAULTPROGRAMCALC.INPA",16777215,0,"PLC:BC2B:TM01:FAULTPROGRAMCALC.INPA")
#! Link("PLC:BC2B:TM01:FAULTPROGRAMCALC.INPA","PLC:BC2B:TM01:MAJORFAULTRAW.VAL")
#! Field("PLC:BC2B:TM01:FAULTPROGRAMCALC.INPB",16777215,0,"PLC:BC2B:TM01:FAULTPROGRAMCALC.INPB")
#! Link("PLC:BC2B:TM01:FAULTPROGRAMCALC.INPB","PLC:BC2B:TM01:MINORFAULTRAW.VAL")
#! Field("PLC:BC2B:TM01:FAULTPROGRAMCALC.VAL",16777215,1,"PLC:BC2B:TM01:FAULTPROGRAMCALC.VAL")
#! Field("PLC:BC2B:TM01:FAULTPROGRAMCALC.INPD",16777215,0,"PLC:BC2B:TM01:FAULTPROGRAMCALC.INPD")
#! Link("PLC:BC2B:TM01:FAULTPROGRAMCALC.INPD","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:FAULTPROGRAM",4640,3070,0,0,"PLC:BC2B:TM01:FAULTPROGRAM")
#! Field("PLC:BC2B:TM01:FAULTPROGRAM.INP",16777215,0,"PLC:BC2B:TM01:FAULTPROGRAM.INP")
#! Link("PLC:BC2B:TM01:FAULTPROGRAM.INP","PLC:BC2B:TM01:FAULTPROGRAMCALC.VAL")
#! Field("PLC:BC2B:TM01:FAULTPROGRAM.FLNK",16777215,0,"PLC:BC2B:TM01:FAULTPROGRAM.FLNK")
#! Link("PLC:BC2B:TM01:FAULTPROGRAM.FLNK","PLC:BC2B:TM01:FAULTFLTHNDLCALC")
#! Record("PLC:BC2B:TM01:FAULTFLTHNDL",4640,3310,0,0,"PLC:BC2B:TM01:FAULTFLTHNDL")
#! Field("PLC:BC2B:TM01:FAULTFLTHNDL.INP",16777215,0,"PLC:BC2B:TM01:FAULTFLTHNDL.INP")
#! Link("PLC:BC2B:TM01:FAULTFLTHNDL.INP","PLC:BC2B:TM01:FAULTFLTHNDLCALC.VAL")
#! Field("PLC:BC2B:TM01:FAULTFLTHNDL.FLNK",16777215,0,"PLC:BC2B:TM01:FAULTFLTHNDL.FLNK")
#! Link("PLC:BC2B:TM01:FAULTFLTHNDL.FLNK","PLC:BC2B:TM01:FAULTWTCHDOGCALC")
#! Record("PLC:BC2B:TM01:FAULTFLTHNDLCALC",4360,3279,0,1,"PLC:BC2B:TM01:FAULTFLTHNDLCALC")
#! Field("PLC:BC2B:TM01:FAULTFLTHNDLCALC.FLNK",16777215,1,"PLC:BC2B:TM01:FAULTFLTHNDLCALC.FLNK")
#! Link("PLC:BC2B:TM01:FAULTFLTHNDLCALC.FLNK","PLC:BC2B:TM01:FAULTFLTHNDL")
#! Field("PLC:BC2B:TM01:FAULTFLTHNDLCALC.INPA",16777215,0,"PLC:BC2B:TM01:FAULTFLTHNDLCALC.INPA")
#! Link("PLC:BC2B:TM01:FAULTFLTHNDLCALC.INPA","PLC:BC2B:TM01:MAJORFAULTRAW.VAL")
#! Field("PLC:BC2B:TM01:FAULTFLTHNDLCALC.INPB",16777215,0,"PLC:BC2B:TM01:FAULTFLTHNDLCALC.INPB")
#! Link("PLC:BC2B:TM01:FAULTFLTHNDLCALC.INPB","PLC:BC2B:TM01:MINORFAULTRAW.VAL")
#! Field("PLC:BC2B:TM01:FAULTFLTHNDLCALC.VAL",16777215,1,"PLC:BC2B:TM01:FAULTFLTHNDLCALC.VAL")
#! Field("PLC:BC2B:TM01:FAULTFLTHNDLCALC.INPD",16777215,0,"PLC:BC2B:TM01:FAULTFLTHNDLCALC.INPD")
#! Link("PLC:BC2B:TM01:FAULTFLTHNDLCALC.INPD","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:FAULTWTCHDOGCALC",4360,3499,0,1,"PLC:BC2B:TM01:FAULTWTCHDOGCALC")
#! Field("PLC:BC2B:TM01:FAULTWTCHDOGCALC.FLNK",16777215,1,"PLC:BC2B:TM01:FAULTWTCHDOGCALC.FLNK")
#! Link("PLC:BC2B:TM01:FAULTWTCHDOGCALC.FLNK","PLC:BC2B:TM01:FAULTWTCHDOG")
#! Field("PLC:BC2B:TM01:FAULTWTCHDOGCALC.INPA",16777215,0,"PLC:BC2B:TM01:FAULTWTCHDOGCALC.INPA")
#! Link("PLC:BC2B:TM01:FAULTWTCHDOGCALC.INPA","PLC:BC2B:TM01:MAJORFAULTRAW.VAL")
#! Field("PLC:BC2B:TM01:FAULTWTCHDOGCALC.INPB",16777215,0,"PLC:BC2B:TM01:FAULTWTCHDOGCALC.INPB")
#! Link("PLC:BC2B:TM01:FAULTWTCHDOGCALC.INPB","PLC:BC2B:TM01:MINORFAULTRAW.VAL")
#! Field("PLC:BC2B:TM01:FAULTWTCHDOGCALC.VAL",16777215,1,"PLC:BC2B:TM01:FAULTWTCHDOGCALC.VAL")
#! Field("PLC:BC2B:TM01:FAULTWTCHDOGCALC.INPD",16777215,0,"PLC:BC2B:TM01:FAULTWTCHDOGCALC.INPD")
#! Link("PLC:BC2B:TM01:FAULTWTCHDOGCALC.INPD","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:FAULTWTCHDOG",4640,3530,0,0,"PLC:BC2B:TM01:FAULTWTCHDOG")
#! Field("PLC:BC2B:TM01:FAULTWTCHDOG.INP",16777215,0,"PLC:BC2B:TM01:FAULTWTCHDOG.INP")
#! Link("PLC:BC2B:TM01:FAULTWTCHDOG.INP","PLC:BC2B:TM01:FAULTWTCHDOGCALC.VAL")
#! Field("PLC:BC2B:TM01:FAULTWTCHDOG.FLNK",16777215,0,"PLC:BC2B:TM01:FAULTWTCHDOG.FLNK")
#! Link("PLC:BC2B:TM01:FAULTWTCHDOG.FLNK","PLC:BC2B:TM01:FAULTSTACKCALC")
#! Record("PLC:BC2B:TM01:FAULTSTACKCALC",4360,3719,0,1,"PLC:BC2B:TM01:FAULTSTACKCALC")
#! Field("PLC:BC2B:TM01:FAULTSTACKCALC.FLNK",16777215,1,"PLC:BC2B:TM01:FAULTSTACKCALC.FLNK")
#! Link("PLC:BC2B:TM01:FAULTSTACKCALC.FLNK","PLC:BC2B:TM01:FAULTSTACK")
#! Field("PLC:BC2B:TM01:FAULTSTACKCALC.INPA",16777215,0,"PLC:BC2B:TM01:FAULTSTACKCALC.INPA")
#! Link("PLC:BC2B:TM01:FAULTSTACKCALC.INPA","PLC:BC2B:TM01:MAJORFAULTRAW.VAL")
#! Field("PLC:BC2B:TM01:FAULTSTACKCALC.INPB",16777215,0,"PLC:BC2B:TM01:FAULTSTACKCALC.INPB")
#! Link("PLC:BC2B:TM01:FAULTSTACKCALC.INPB","PLC:BC2B:TM01:MINORFAULTRAW.VAL")
#! Field("PLC:BC2B:TM01:FAULTSTACKCALC.VAL",16777215,1,"PLC:BC2B:TM01:FAULTSTACKCALC.VAL")
#! Field("PLC:BC2B:TM01:FAULTSTACKCALC.INPD",16777215,0,"PLC:BC2B:TM01:FAULTSTACKCALC.INPD")
#! Link("PLC:BC2B:TM01:FAULTSTACKCALC.INPD","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:FAULTSTACK",4640,3750,0,0,"PLC:BC2B:TM01:FAULTSTACK")
#! Field("PLC:BC2B:TM01:FAULTSTACK.INP",16777215,0,"PLC:BC2B:TM01:FAULTSTACK.INP")
#! Link("PLC:BC2B:TM01:FAULTSTACK.INP","PLC:BC2B:TM01:FAULTSTACKCALC.VAL")
#! Field("PLC:BC2B:TM01:FAULTSTACK.FLNK",16777215,0,"PLC:BC2B:TM01:FAULTSTACK.FLNK")
#! Link("PLC:BC2B:TM01:FAULTSTACK.FLNK","PLC:BC2B:TM01:FAULTMODECHGCALC")
#! Record("PLC:BC2B:TM01:FAULTMODECHGCALC",4360,3939,0,1,"PLC:BC2B:TM01:FAULTMODECHGCALC")
#! Field("PLC:BC2B:TM01:FAULTMODECHGCALC.FLNK",16777215,1,"PLC:BC2B:TM01:FAULTMODECHGCALC.FLNK")
#! Link("PLC:BC2B:TM01:FAULTMODECHGCALC.FLNK","PLC:BC2B:TM01:FAULTMODECHG")
#! Field("PLC:BC2B:TM01:FAULTMODECHGCALC.INPA",16777215,0,"PLC:BC2B:TM01:FAULTMODECHGCALC.INPA")
#! Link("PLC:BC2B:TM01:FAULTMODECHGCALC.INPA","PLC:BC2B:TM01:MAJORFAULTRAW.VAL")
#! Field("PLC:BC2B:TM01:FAULTMODECHGCALC.INPB",16777215,0,"PLC:BC2B:TM01:FAULTMODECHGCALC.INPB")
#! Link("PLC:BC2B:TM01:FAULTMODECHGCALC.INPB","PLC:BC2B:TM01:MINORFAULTRAW.VAL")
#! Field("PLC:BC2B:TM01:FAULTMODECHGCALC.VAL",16777215,1,"PLC:BC2B:TM01:FAULTMODECHGCALC.VAL")
#! Field("PLC:BC2B:TM01:FAULTMODECHGCALC.INPD",16777215,0,"PLC:BC2B:TM01:FAULTMODECHGCALC.INPD")
#! Link("PLC:BC2B:TM01:FAULTMODECHGCALC.INPD","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:FAULTMODECHG",4640,3970,0,0,"PLC:BC2B:TM01:FAULTMODECHG")
#! Field("PLC:BC2B:TM01:FAULTMODECHG.INP",16777215,0,"PLC:BC2B:TM01:FAULTMODECHG.INP")
#! Link("PLC:BC2B:TM01:FAULTMODECHG.INP","PLC:BC2B:TM01:FAULTMODECHGCALC.VAL")
#! Field("PLC:BC2B:TM01:FAULTMODECHG.FLNK",16777215,0,"PLC:BC2B:TM01:FAULTMODECHG.FLNK")
#! Link("PLC:BC2B:TM01:FAULTMODECHG.FLNK","PLC:BC2B:TM01:FAULTSERIALCALC")
#! Record("PLC:BC2B:TM01:FAULTSERIALCALC",4360,4159,0,1,"PLC:BC2B:TM01:FAULTSERIALCALC")
#! Field("PLC:BC2B:TM01:FAULTSERIALCALC.FLNK",16777215,1,"PLC:BC2B:TM01:FAULTSERIALCALC.FLNK")
#! Link("PLC:BC2B:TM01:FAULTSERIALCALC.FLNK","PLC:BC2B:TM01:FAULTSERIAL")
#! Field("PLC:BC2B:TM01:FAULTSERIALCALC.INPA",16777215,0,"PLC:BC2B:TM01:FAULTSERIALCALC.INPA")
#! Link("PLC:BC2B:TM01:FAULTSERIALCALC.INPA","PLC:BC2B:TM01:MAJORFAULTRAW.VAL")
#! Field("PLC:BC2B:TM01:FAULTSERIALCALC.INPB",16777215,0,"PLC:BC2B:TM01:FAULTSERIALCALC.INPB")
#! Link("PLC:BC2B:TM01:FAULTSERIALCALC.INPB","PLC:BC2B:TM01:MINORFAULTRAW.VAL")
#! Field("PLC:BC2B:TM01:FAULTSERIALCALC.VAL",16777215,1,"PLC:BC2B:TM01:FAULTSERIALCALC.VAL")
#! Field("PLC:BC2B:TM01:FAULTSERIALCALC.INPD",16777215,0,"PLC:BC2B:TM01:FAULTSERIALCALC.INPD")
#! Link("PLC:BC2B:TM01:FAULTSERIALCALC.INPD","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:FAULTSERIAL",4640,4190,0,0,"PLC:BC2B:TM01:FAULTSERIAL")
#! Field("PLC:BC2B:TM01:FAULTSERIAL.INP",16777215,0,"PLC:BC2B:TM01:FAULTSERIAL.INP")
#! Link("PLC:BC2B:TM01:FAULTSERIAL.INP","PLC:BC2B:TM01:FAULTSERIALCALC.VAL")
#! Field("PLC:BC2B:TM01:FAULTSERIAL.FLNK",16777215,0,"PLC:BC2B:TM01:FAULTSERIAL.FLNK")
#! Link("PLC:BC2B:TM01:FAULTSERIAL.FLNK","PLC:BC2B:TM01:FAULTBATTERYCALC")
#! Record("PLC:BC2B:TM01:FAULTBATTERY",4640,4410,0,0,"PLC:BC2B:TM01:FAULTBATTERY")
#! Field("PLC:BC2B:TM01:FAULTBATTERY.INP",16777215,0,"PLC:BC2B:TM01:FAULTBATTERY.INP")
#! Link("PLC:BC2B:TM01:FAULTBATTERY.INP","PLC:BC2B:TM01:FAULTBATTERYCALC.VAL")
#! Field("PLC:BC2B:TM01:FAULTBATTERY.FLNK",16777215,0,"PLC:BC2B:TM01:FAULTBATTERY.FLNK")
#! Link("PLC:BC2B:TM01:FAULTBATTERY.FLNK","PLC:BC2B:TM01:FAULTMOTIONCALC")
#! Record("PLC:BC2B:TM01:FAULTBATTERYCALC",4360,4379,0,1,"PLC:BC2B:TM01:FAULTBATTERYCALC")
#! Field("PLC:BC2B:TM01:FAULTBATTERYCALC.FLNK",16777215,1,"PLC:BC2B:TM01:FAULTBATTERYCALC.FLNK")
#! Link("PLC:BC2B:TM01:FAULTBATTERYCALC.FLNK","PLC:BC2B:TM01:FAULTBATTERY")
#! Field("PLC:BC2B:TM01:FAULTBATTERYCALC.INPA",16777215,0,"PLC:BC2B:TM01:FAULTBATTERYCALC.INPA")
#! Link("PLC:BC2B:TM01:FAULTBATTERYCALC.INPA","PLC:BC2B:TM01:MAJORFAULTRAW.VAL")
#! Field("PLC:BC2B:TM01:FAULTBATTERYCALC.INPB",16777215,0,"PLC:BC2B:TM01:FAULTBATTERYCALC.INPB")
#! Link("PLC:BC2B:TM01:FAULTBATTERYCALC.INPB","PLC:BC2B:TM01:MINORFAULTRAW.VAL")
#! Field("PLC:BC2B:TM01:FAULTBATTERYCALC.VAL",16777215,1,"PLC:BC2B:TM01:FAULTBATTERYCALC.VAL")
#! Field("PLC:BC2B:TM01:FAULTBATTERYCALC.INPD",16777215,0,"PLC:BC2B:TM01:FAULTBATTERYCALC.INPD")
#! Link("PLC:BC2B:TM01:FAULTBATTERYCALC.INPD","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:FAULTMOTIONCALC",4360,4599,0,1,"PLC:BC2B:TM01:FAULTMOTIONCALC")
#! Field("PLC:BC2B:TM01:FAULTMOTIONCALC.FLNK",16777215,1,"PLC:BC2B:TM01:FAULTMOTIONCALC.FLNK")
#! Link("PLC:BC2B:TM01:FAULTMOTIONCALC.FLNK","PLC:BC2B:TM01:FAULTMOTION")
#! Field("PLC:BC2B:TM01:FAULTMOTIONCALC.INPA",16777215,0,"PLC:BC2B:TM01:FAULTMOTIONCALC.INPA")
#! Link("PLC:BC2B:TM01:FAULTMOTIONCALC.INPA","PLC:BC2B:TM01:MAJORFAULTRAW.VAL")
#! Field("PLC:BC2B:TM01:FAULTMOTIONCALC.INPB",16777215,0,"PLC:BC2B:TM01:FAULTMOTIONCALC.INPB")
#! Link("PLC:BC2B:TM01:FAULTMOTIONCALC.INPB","PLC:BC2B:TM01:MINORFAULTRAW.VAL")
#! Field("PLC:BC2B:TM01:FAULTMOTIONCALC.VAL",16777215,1,"PLC:BC2B:TM01:FAULTMOTIONCALC.VAL")
#! Field("PLC:BC2B:TM01:FAULTMOTIONCALC.INPD",16777215,0,"PLC:BC2B:TM01:FAULTMOTIONCALC.INPD")
#! Link("PLC:BC2B:TM01:FAULTMOTIONCALC.INPD","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:FAULTMOTION",4640,4645,0,0,"PLC:BC2B:TM01:FAULTMOTION")
#! Field("PLC:BC2B:TM01:FAULTMOTION.INP",16777215,0,"PLC:BC2B:TM01:FAULTMOTION.INP")
#! Link("PLC:BC2B:TM01:FAULTMOTION.INP","PLC:BC2B:TM01:FAULTMOTIONCALC.VAL")
#! Record("PLC:BC2B:TM01:VERSIONMAJORDES",2160,2867,0,1,"PLC:BC2B:TM01:VERSIONMAJORDES")
#! Field("PLC:BC2B:TM01:VERSIONMAJORDES.FLNK",16777215,1,"PLC:BC2B:TM01:VERSIONMAJORDES.FLNK")
#! Link("PLC:BC2B:TM01:VERSIONMAJORDES.FLNK","PLC:BC2B:TM01:VERSIONMAJORCALCHI")
#! Field("PLC:BC2B:TM01:VERSIONMAJORDES.VAL",16777215,1,"PLC:BC2B:TM01:VERSIONMAJORDES.VAL")
#! Record("PLC:BC2B:TM01:VERSIONMAJORCALCHI",2420,2687,0,0,"PLC:BC2B:TM01:VERSIONMAJORCALCHI")
#! Field("PLC:BC2B:TM01:VERSIONMAJORCALCHI.INPA",16777215,0,"PLC:BC2B:TM01:VERSIONMAJORCALCHI.INPA")
#! Link("PLC:BC2B:TM01:VERSIONMAJORCALCHI.INPA","PLC:BC2B:TM01:VERSIONMAJORDES.VAL")
#! Field("PLC:BC2B:TM01:VERSIONMAJORCALCHI.OUT",16777215,1,"PLC:BC2B:TM01:VERSIONMAJORCALCHI.OUT")
#! Link("PLC:BC2B:TM01:VERSIONMAJORCALCHI.OUT","PLC:BC2B:TM01:VERSIONMAJOR.HIGH")
#! Field("PLC:BC2B:TM01:VERSIONMAJORCALCHI.FLNK",16777215,1,"PLC:BC2B:TM01:VERSIONMAJORCALCHI.FLNK")
#! Link("PLC:BC2B:TM01:VERSIONMAJORCALCHI.FLNK","PLC:BC2B:TM01:VERSIONMAJORCALCLO")
#! Record("PLC:BC2B:TM01:VERSIONMAJORCALCLO",2460,2922,0,1,"PLC:BC2B:TM01:VERSIONMAJORCALCLO")
#! Field("PLC:BC2B:TM01:VERSIONMAJORCALCLO.INPA",16777215,0,"PLC:BC2B:TM01:VERSIONMAJORCALCLO.INPA")
#! Link("PLC:BC2B:TM01:VERSIONMAJORCALCLO.INPA","PLC:BC2B:TM01:VERSIONMAJORDES.VAL")
#! Field("PLC:BC2B:TM01:VERSIONMAJORCALCLO.OUT",16777215,1,"PLC:BC2B:TM01:VERSIONMAJORCALCLO.OUT")
#! Link("PLC:BC2B:TM01:VERSIONMAJORCALCLO.OUT","PLC:BC2B:TM01:VERSIONMAJOR.LOW")
#! Record("PLC:BC2B:TM01:VERSIONMINORDES",2160,3147,0,1,"PLC:BC2B:TM01:VERSIONMINORDES")
#! Field("PLC:BC2B:TM01:VERSIONMINORDES.FLNK",16777215,1,"PLC:BC2B:TM01:VERSIONMINORDES.FLNK")
#! Link("PLC:BC2B:TM01:VERSIONMINORDES.FLNK","PLC:BC2B:TM01:VERSIONMINORCALCHI")
#! Field("PLC:BC2B:TM01:VERSIONMINORDES.VAL",16777215,1,"PLC:BC2B:TM01:VERSIONMINORDES.VAL")
#! Record("PLC:BC2B:TM01:VERSIONMINORCALCLO",2480,3322,0,1,"PLC:BC2B:TM01:VERSIONMINORCALCLO")
#! Field("PLC:BC2B:TM01:VERSIONMINORCALCLO.INPA",16777215,0,"PLC:BC2B:TM01:VERSIONMINORCALCLO.INPA")
#! Link("PLC:BC2B:TM01:VERSIONMINORCALCLO.INPA","PLC:BC2B:TM01:VERSIONMINORDES.VAL")
#! Field("PLC:BC2B:TM01:VERSIONMINORCALCLO.OUT",16777215,1,"PLC:BC2B:TM01:VERSIONMINORCALCLO.OUT")
#! Link("PLC:BC2B:TM01:VERSIONMINORCALCLO.OUT","PLC:BC2B:TM01:VERSIONMINOR.LOW")
#! Record("PLC:BC2B:TM01:VERSIONMINORCALCHI",2440,3087,0,0,"PLC:BC2B:TM01:VERSIONMINORCALCHI")
#! Field("PLC:BC2B:TM01:VERSIONMINORCALCHI.FLNK",16777215,1,"PLC:BC2B:TM01:VERSIONMINORCALCHI.FLNK")
#! Link("PLC:BC2B:TM01:VERSIONMINORCALCHI.FLNK","PLC:BC2B:TM01:VERSIONMINORCALCLO")
#! Field("PLC:BC2B:TM01:VERSIONMINORCALCHI.INPA",16777215,0,"PLC:BC2B:TM01:VERSIONMINORCALCHI.INPA")
#! Link("PLC:BC2B:TM01:VERSIONMINORCALCHI.INPA","PLC:BC2B:TM01:VERSIONMINORDES.VAL")
#! Field("PLC:BC2B:TM01:VERSIONMINORCALCHI.OUT",16777215,1,"PLC:BC2B:TM01:VERSIONMINORCALCHI.OUT")
#! Link("PLC:BC2B:TM01:VERSIONMINORCALCHI.OUT","PLC:BC2B:TM01:VERSIONMINOR.HIGH")
#! Record("PLC:BC2B:TM01:VERSIONREVDES",2180,3547,0,1,"PLC:BC2B:TM01:VERSIONREVDES")
#! Field("PLC:BC2B:TM01:VERSIONREVDES.FLNK",16777215,1,"PLC:BC2B:TM01:VERSIONREVDES.FLNK")
#! Link("PLC:BC2B:TM01:VERSIONREVDES.FLNK","PLC:BC2B:TM01:VERSIONREVCALCHI")
#! Field("PLC:BC2B:TM01:VERSIONREVDES.VAL",16777215,1,"PLC:BC2B:TM01:VERSIONREVDES.VAL")
#! Record("PLC:BC2B:TM01:VERSIONREVCALCHI",2460,3487,0,0,"PLC:BC2B:TM01:VERSIONREVCALCHI")
#! Field("PLC:BC2B:TM01:VERSIONREVCALCHI.FLNK",16777215,1,"PLC:BC2B:TM01:VERSIONREVCALCHI.FLNK")
#! Link("PLC:BC2B:TM01:VERSIONREVCALCHI.FLNK","PLC:BC2B:TM01:VERSIONREVCALCLO")
#! Field("PLC:BC2B:TM01:VERSIONREVCALCHI.INPA",16777215,0,"PLC:BC2B:TM01:VERSIONREVCALCHI.INPA")
#! Link("PLC:BC2B:TM01:VERSIONREVCALCHI.INPA","PLC:BC2B:TM01:VERSIONREVDES.VAL")
#! Field("PLC:BC2B:TM01:VERSIONREVCALCHI.OUT",16777215,1,"PLC:BC2B:TM01:VERSIONREVCALCHI.OUT")
#! Link("PLC:BC2B:TM01:VERSIONREVCALCHI.OUT","PLC:BC2B:TM01:VERSIONREV.HIGH")
#! Record("PLC:BC2B:TM01:VERSIONREVCALCLO",2500,3722,0,1,"PLC:BC2B:TM01:VERSIONREVCALCLO")
#! Field("PLC:BC2B:TM01:VERSIONREVCALCLO.INPA",16777215,0,"PLC:BC2B:TM01:VERSIONREVCALCLO.INPA")
#! Link("PLC:BC2B:TM01:VERSIONREVCALCLO.INPA","PLC:BC2B:TM01:VERSIONREVDES.VAL")
#! Field("PLC:BC2B:TM01:VERSIONREVCALCLO.OUT",16777215,1,"PLC:BC2B:TM01:VERSIONREVCALCLO.OUT")
#! Link("PLC:BC2B:TM01:VERSIONREVCALCLO.OUT","PLC:BC2B:TM01:VERSIONREV.LOW")
#! Record("PLC:BC2B:TM01:HEARTBEATCALC",600,187,0,0,"PLC:BC2B:TM01:HEARTBEATCALC")
#! Field("PLC:BC2B:TM01:HEARTBEATCALC.INPA",16777215,0,"PLC:BC2B:TM01:HEARTBEATCALC.INPA")
#! Link("PLC:BC2B:TM01:HEARTBEATCALC.INPA","PLC:BC2B:TM01:HEARTBEATRAW.VAL")
#! Field("PLC:BC2B:TM01:HEARTBEATCALC.VAL",16777215,0,"PLC:BC2B:TM01:HEARTBEATCALC.VAL")
#! Field("PLC:BC2B:TM01:HEARTBEATCALC.INPB",16777215,0,"PLC:BC2B:TM01:HEARTBEATCALC.INPB")
#! Link("PLC:BC2B:TM01:HEARTBEATCALC.INPB","PLC:BC2B:TM01:HEARTBEATCALC.VAL")
#! Field("PLC:BC2B:TM01:HEARTBEATCALC.FLNK",16777215,1,"PLC:BC2B:TM01:HEARTBEATCALC.FLNK")
#! Link("PLC:BC2B:TM01:HEARTBEATCALC.FLNK","PLC:BC2B:TM01:HEARTBEATERR")
#! Field("PLC:BC2B:TM01:HEARTBEATCALC.A",16777215,1,"PLC:BC2B:TM01:HEARTBEATCALC.A")
#! Field("PLC:BC2B:TM01:HEARTBEATCALC.B",16777215,1,"PLC:BC2B:TM01:HEARTBEATCALC.B")
#! Record("PLC:BC2B:TM01:HEARTBEATOK",1600,299,0,0,"PLC:BC2B:TM01:HEARTBEATOK")
#! Field("PLC:BC2B:TM01:HEARTBEATOK.INP",16777215,0,"PLC:BC2B:TM01:HEARTBEATOK.INP")
#! Link("PLC:BC2B:TM01:HEARTBEATOK.INP","PLC:BC2B:TM01:HEARTBEATERR.VAL")
#! Field("PLC:BC2B:TM01:HEARTBEATOK.FLNK",16777215,0,"PLC:BC2B:TM01:HEARTBEATOK.FLNK")
#! Link("PLC:BC2B:TM01:HEARTBEATOK.FLNK","PLC:BC2B:TM01:HEARTBEATE01")
#! Record("PLC:BC2B:TM01:HEARTBEATERR",900,267,0,0,"PLC:BC2B:TM01:HEARTBEATERR")
#! Field("PLC:BC2B:TM01:HEARTBEATERR.INPA",16777215,0,"PLC:BC2B:TM01:HEARTBEATERR.INPA")
#! Link("PLC:BC2B:TM01:HEARTBEATERR.INPA","PLC:BC2B:TM01:HEARTBEATCALC.A")
#! Field("PLC:BC2B:TM01:HEARTBEATERR.INPB",16777215,0,"PLC:BC2B:TM01:HEARTBEATERR.INPB")
#! Link("PLC:BC2B:TM01:HEARTBEATERR.INPB","PLC:BC2B:TM01:HEARTBEATCALC.B")
#! Field("PLC:BC2B:TM01:HEARTBEATERR.FLNK",16777215,1,"PLC:BC2B:TM01:HEARTBEATERR.FLNK")
#! Link("PLC:BC2B:TM01:HEARTBEATERR.FLNK","PLC:BC2B:TM01:HEARTBEATOK")
#! Field("PLC:BC2B:TM01:HEARTBEATERR.VAL",16777215,1,"PLC:BC2B:TM01:HEARTBEATERR.VAL")
#! Record("PLC:BC2B:TM01:HEARTBEATECT",1740,1160,0,0,"PLC:BC2B:TM01:HEARTBEATECT")
#! Field("PLC:BC2B:TM01:HEARTBEATECT.INPA",16777215,0,"PLC:BC2B:TM01:HEARTBEATECT.INPA")
#! Link("PLC:BC2B:TM01:HEARTBEATECT.INPA","PLC:BC2B:TM01:HEARTBEATECT/INPA")
#! Field("PLC:BC2B:TM01:HEARTBEATECT.INPB",16777215,0,"PLC:BC2B:TM01:HEARTBEATECT.INPB")
#! Link("PLC:BC2B:TM01:HEARTBEATECT.INPB","PLC:BC2B:TM01:HEARTBEATECT/INPB")
#! Field("PLC:BC2B:TM01:HEARTBEATECT.INPC",16777215,0,"PLC:BC2B:TM01:HEARTBEATECT.INPC")
#! Link("PLC:BC2B:TM01:HEARTBEATECT.INPC","PLC:BC2B:TM01:HEARTBEATECT/INPC")
#! Field("PLC:BC2B:TM01:HEARTBEATECT.INPD",16777215,0,"PLC:BC2B:TM01:HEARTBEATECT.INPD")
#! Link("PLC:BC2B:TM01:HEARTBEATECT.INPD","PLC:BC2B:TM01:HEARTBEATECT/INPD")
#! Field("PLC:BC2B:TM01:HEARTBEATECT.INPE",16777215,0,"PLC:BC2B:TM01:HEARTBEATECT.INPE")
#! Link("PLC:BC2B:TM01:HEARTBEATECT.INPE","PLC:BC2B:TM01:HEARTBEATECT/INPE")
#! Field("PLC:BC2B:TM01:HEARTBEATECT.INPF",16777215,0,"PLC:BC2B:TM01:HEARTBEATECT.INPF")
#! Link("PLC:BC2B:TM01:HEARTBEATECT.INPF","PLC:BC2B:TM01:HEARTBEATECT/INPF")
#! Field("PLC:BC2B:TM01:HEARTBEATECT.INPG",16777215,0,"PLC:BC2B:TM01:HEARTBEATECT.INPG")
#! Link("PLC:BC2B:TM01:HEARTBEATECT.INPG","PLC:BC2B:TM01:HEARTBEATECT/INPG")
#! Field("PLC:BC2B:TM01:HEARTBEATECT.INPH",16777215,0,"PLC:BC2B:TM01:HEARTBEATECT.INPH")
#! Link("PLC:BC2B:TM01:HEARTBEATECT.INPH","PLC:BC2B:TM01:HEARTBEATECT/INPH")
#! Field("PLC:BC2B:TM01:HEARTBEATECT.INPI",16777215,0,"PLC:BC2B:TM01:HEARTBEATECT.INPI")
#! Link("PLC:BC2B:TM01:HEARTBEATECT.INPI","PLC:BC2B:TM01:HEARTBEATECT/INPI")
#! Field("PLC:BC2B:TM01:HEARTBEATECT.INPJ",16777215,0,"PLC:BC2B:TM01:HEARTBEATECT.INPJ")
#! Link("PLC:BC2B:TM01:HEARTBEATECT.INPJ","PLC:BC2B:TM01:HEARTBEATECT/INPJ")
#! Field("PLC:BC2B:TM01:HEARTBEATECT.FLNK",16777215,1,"PLC:BC2B:TM01:HEARTBEATECT.FLNK")
#! Link("PLC:BC2B:TM01:HEARTBEATECT.FLNK","PLC:BC2B:TM01:HEARTBEATSUM")
#! Field("PLC:BC2B:TM01:HEARTBEATECT.SEVR",16777215,1,"PLC:BC2B:TM01:HEARTBEATECT.SEVR")
#! Connector("PLC:BC2B:TM01:HEARTBEATECT/INPJ","PLC:BC2B:TM01:HEARTBEATE10.VAL",1600,2130,16777215,"",0)
#! Connector("PLC:BC2B:TM01:HEARTBEATECT/INPI","PLC:BC2B:TM01:HEARTBEATE09.VAL",1560,2020,16777215,"",0)
#! Connector("PLC:BC2B:TM01:HEARTBEATECT/INPH","PLC:BC2B:TM01:HEARTBEATE08.VAL",1520,1910,16777215,"",0)
#! Connector("PLC:BC2B:TM01:HEARTBEATECT/INPG","PLC:BC2B:TM01:HEARTBEATE07.VAL",1480,1790,16777215,"",0)
#! Connector("PLC:BC2B:TM01:HEARTBEATECT/INPF","PLC:BC2B:TM01:HEARTBEATE06.VAL",1280,1670,16777215,"",0)
#! Connector("PLC:BC2B:TM01:HEARTBEATECT/INPE","PLC:BC2B:TM01:HEARTBEATE05.VAL",1320,1550,16777215,"",0)
#! Connector("PLC:BC2B:TM01:HEARTBEATECT/INPD","PLC:BC2B:TM01:HEARTBEATE04.VAL",1360,1430,16777215,"",0)
#! Connector("PLC:BC2B:TM01:HEARTBEATECT/INPC","PLC:BC2B:TM01:HEARTBEATE03.VAL",1400,1310,16777215,"",0)
#! Connector("PLC:BC2B:TM01:HEARTBEATECT/INPB","PLC:BC2B:TM01:HEARTBEATE02.VAL",1440,1190,16777215,"",0)
#! Connector("PLC:BC2B:TM01:HEARTBEATECT/INPA","PLC:BC2B:TM01:HEARTBEATE01.VAL",1480,1070,16777215,"",0)
#! Record("PLC:BC2B:TM01:HEARTBEATE09",1060,2227,0,1,"PLC:BC2B:TM01:HEARTBEATE09")
#! Field("PLC:BC2B:TM01:HEARTBEATE09.INPA",16777215,0,"PLC:BC2B:TM01:HEARTBEATE09.INPA")
#! Link("PLC:BC2B:TM01:HEARTBEATE09.INPA","PLC:BC2B:TM01:HEARTBEATE08.B")
#! Field("PLC:BC2B:TM01:HEARTBEATE09.VAL",16777215,1,"PLC:BC2B:TM01:HEARTBEATE09.VAL")
#! Field("PLC:BC2B:TM01:HEARTBEATE09.FLNK",16777215,1,"PLC:BC2B:TM01:HEARTBEATE09.FLNK")
#! Link("PLC:BC2B:TM01:HEARTBEATE09.FLNK","PLC:BC2B:TM01:HEARTBEATE10")
#! Field("PLC:BC2B:TM01:HEARTBEATE09.INPB",16777215,0,"PLC:BC2B:TM01:HEARTBEATE09.INPB")
#! Link("PLC:BC2B:TM01:HEARTBEATE09.INPB","PLC:BC2B:TM01:HEARTBEATE09.VAL")
#! Field("PLC:BC2B:TM01:HEARTBEATE09.B",16777215,0,"PLC:BC2B:TM01:HEARTBEATE09.B")
#! Record("PLC:BC2B:TM01:HEARTBEATE08",1040,2007,0,1,"PLC:BC2B:TM01:HEARTBEATE08")
#! Field("PLC:BC2B:TM01:HEARTBEATE08.FLNK",16777215,1,"PLC:BC2B:TM01:HEARTBEATE08.FLNK")
#! Link("PLC:BC2B:TM01:HEARTBEATE08.FLNK","PLC:BC2B:TM01:HEARTBEATE09")
#! Field("PLC:BC2B:TM01:HEARTBEATE08.INPA",16777215,0,"PLC:BC2B:TM01:HEARTBEATE08.INPA")
#! Link("PLC:BC2B:TM01:HEARTBEATE08.INPA","PLC:BC2B:TM01:HEARTBEATE07.B")
#! Field("PLC:BC2B:TM01:HEARTBEATE08.VAL",16777215,1,"PLC:BC2B:TM01:HEARTBEATE08.VAL")
#! Field("PLC:BC2B:TM01:HEARTBEATE08.INPB",16777215,0,"PLC:BC2B:TM01:HEARTBEATE08.INPB")
#! Link("PLC:BC2B:TM01:HEARTBEATE08.INPB","PLC:BC2B:TM01:HEARTBEATE08.VAL")
#! Field("PLC:BC2B:TM01:HEARTBEATE08.B",16777215,0,"PLC:BC2B:TM01:HEARTBEATE08.B")
#! Record("PLC:BC2B:TM01:HEARTBEATE07",1020,1787,0,1,"PLC:BC2B:TM01:HEARTBEATE07")
#! Field("PLC:BC2B:TM01:HEARTBEATE07.FLNK",16777215,1,"PLC:BC2B:TM01:HEARTBEATE07.FLNK")
#! Link("PLC:BC2B:TM01:HEARTBEATE07.FLNK","PLC:BC2B:TM01:HEARTBEATE08")
#! Field("PLC:BC2B:TM01:HEARTBEATE07.INPA",16777215,0,"PLC:BC2B:TM01:HEARTBEATE07.INPA")
#! Link("PLC:BC2B:TM01:HEARTBEATE07.INPA","PLC:BC2B:TM01:HEARTBEATE06.B")
#! Field("PLC:BC2B:TM01:HEARTBEATE07.VAL",16777215,1,"PLC:BC2B:TM01:HEARTBEATE07.VAL")
#! Field("PLC:BC2B:TM01:HEARTBEATE07.INPB",16777215,0,"PLC:BC2B:TM01:HEARTBEATE07.INPB")
#! Link("PLC:BC2B:TM01:HEARTBEATE07.INPB","PLC:BC2B:TM01:HEARTBEATE07.VAL")
#! Field("PLC:BC2B:TM01:HEARTBEATE07.B",16777215,0,"PLC:BC2B:TM01:HEARTBEATE07.B")
#! Record("PLC:BC2B:TM01:HEARTBEATE06",1020,1567,0,1,"PLC:BC2B:TM01:HEARTBEATE06")
#! Field("PLC:BC2B:TM01:HEARTBEATE06.FLNK",16777215,1,"PLC:BC2B:TM01:HEARTBEATE06.FLNK")
#! Link("PLC:BC2B:TM01:HEARTBEATE06.FLNK","PLC:BC2B:TM01:HEARTBEATE05/FLNK")
#! Field("PLC:BC2B:TM01:HEARTBEATE06.INPA",16777215,0,"PLC:BC2B:TM01:HEARTBEATE06.INPA")
#! Link("PLC:BC2B:TM01:HEARTBEATE06.INPA","PLC:BC2B:TM01:HEARTBEATE05.B")
#! Field("PLC:BC2B:TM01:HEARTBEATE06.VAL",16777215,1,"PLC:BC2B:TM01:HEARTBEATE06.VAL")
#! Field("PLC:BC2B:TM01:HEARTBEATE06.INPB",16777215,0,"PLC:BC2B:TM01:HEARTBEATE06.INPB")
#! Link("PLC:BC2B:TM01:HEARTBEATE06.INPB","PLC:BC2B:TM01:HEARTBEATE06.VAL")
#! Field("PLC:BC2B:TM01:HEARTBEATE06.B",16777215,0,"PLC:BC2B:TM01:HEARTBEATE06.B")
#! Connector("PLC:BC2B:TM01:HEARTBEATE05/FLNK","PLC:BC2B:TM01:HEARTBEATE07",1260,1766,16777215,"",0)
#! Record("PLC:BC2B:TM01:HEARTBEATE05",1000,1347,0,1,"PLC:BC2B:TM01:HEARTBEATE05")
#! Field("PLC:BC2B:TM01:HEARTBEATE05.FLNK",16777215,1,"PLC:BC2B:TM01:HEARTBEATE05.FLNK")
#! Link("PLC:BC2B:TM01:HEARTBEATE05.FLNK","PLC:BC2B:TM01:HEARTBEATE06")
#! Field("PLC:BC2B:TM01:HEARTBEATE05.INPA",16777215,0,"PLC:BC2B:TM01:HEARTBEATE05.INPA")
#! Link("PLC:BC2B:TM01:HEARTBEATE05.INPA","PLC:BC2B:TM01:HEARTBEATE04.B")
#! Field("PLC:BC2B:TM01:HEARTBEATE05.VAL",16777215,1,"PLC:BC2B:TM01:HEARTBEATE05.VAL")
#! Field("PLC:BC2B:TM01:HEARTBEATE05.INPB",16777215,0,"PLC:BC2B:TM01:HEARTBEATE05.INPB")
#! Link("PLC:BC2B:TM01:HEARTBEATE05.INPB","PLC:BC2B:TM01:HEARTBEATE05.VAL")
#! Field("PLC:BC2B:TM01:HEARTBEATE05.B",16777215,0,"PLC:BC2B:TM01:HEARTBEATE05.B")
#! Record("PLC:BC2B:TM01:HEARTBEATE04",980,1127,0,1,"PLC:BC2B:TM01:HEARTBEATE04")
#! Field("PLC:BC2B:TM01:HEARTBEATE04.FLNK",16777215,1,"PLC:BC2B:TM01:HEARTBEATE04.FLNK")
#! Link("PLC:BC2B:TM01:HEARTBEATE04.FLNK","PLC:BC2B:TM01:HEARTBEATE05")
#! Field("PLC:BC2B:TM01:HEARTBEATE04.INPA",16777215,0,"PLC:BC2B:TM01:HEARTBEATE04.INPA")
#! Link("PLC:BC2B:TM01:HEARTBEATE04.INPA","PLC:BC2B:TM01:HEARTBEATE03.B")
#! Field("PLC:BC2B:TM01:HEARTBEATE04.VAL",16777215,1,"PLC:BC2B:TM01:HEARTBEATE04.VAL")
#! Field("PLC:BC2B:TM01:HEARTBEATE04.INPB",16777215,0,"PLC:BC2B:TM01:HEARTBEATE04.INPB")
#! Link("PLC:BC2B:TM01:HEARTBEATE04.INPB","PLC:BC2B:TM01:HEARTBEATE04.VAL")
#! Field("PLC:BC2B:TM01:HEARTBEATE04.B",16777215,0,"PLC:BC2B:TM01:HEARTBEATE04.B")
#! Record("PLC:BC2B:TM01:HEARTBEATE03",960,907,0,1,"PLC:BC2B:TM01:HEARTBEATE03")
#! Field("PLC:BC2B:TM01:HEARTBEATE03.FLNK",16777215,1,"PLC:BC2B:TM01:HEARTBEATE03.FLNK")
#! Link("PLC:BC2B:TM01:HEARTBEATE03.FLNK","PLC:BC2B:TM01:HEARTBEATE04")
#! Field("PLC:BC2B:TM01:HEARTBEATE03.INPA",16777215,0,"PLC:BC2B:TM01:HEARTBEATE03.INPA")
#! Link("PLC:BC2B:TM01:HEARTBEATE03.INPA","PLC:BC2B:TM01:HEARTBEATE02.B")
#! Field("PLC:BC2B:TM01:HEARTBEATE03.VAL",16777215,1,"PLC:BC2B:TM01:HEARTBEATE03.VAL")
#! Field("PLC:BC2B:TM01:HEARTBEATE03.INPB",16777215,0,"PLC:BC2B:TM01:HEARTBEATE03.INPB")
#! Link("PLC:BC2B:TM01:HEARTBEATE03.INPB","PLC:BC2B:TM01:HEARTBEATE03.VAL")
#! Field("PLC:BC2B:TM01:HEARTBEATE03.B",16777215,0,"PLC:BC2B:TM01:HEARTBEATE03.B")
#! Record("PLC:BC2B:TM01:HEARTBEATE02",940,687,0,1,"PLC:BC2B:TM01:HEARTBEATE02")
#! Field("PLC:BC2B:TM01:HEARTBEATE02.FLNK",16777215,1,"PLC:BC2B:TM01:HEARTBEATE02.FLNK")
#! Link("PLC:BC2B:TM01:HEARTBEATE02.FLNK","PLC:BC2B:TM01:HEARTBEATE03")
#! Field("PLC:BC2B:TM01:HEARTBEATE02.INPA",16777215,0,"PLC:BC2B:TM01:HEARTBEATE02.INPA")
#! Link("PLC:BC2B:TM01:HEARTBEATE02.INPA","PLC:BC2B:TM01:HEARTBEATE01.B")
#! Field("PLC:BC2B:TM01:HEARTBEATE02.VAL",16777215,1,"PLC:BC2B:TM01:HEARTBEATE02.VAL")
#! Field("PLC:BC2B:TM01:HEARTBEATE02.INPB",16777215,0,"PLC:BC2B:TM01:HEARTBEATE02.INPB")
#! Link("PLC:BC2B:TM01:HEARTBEATE02.INPB","PLC:BC2B:TM01:HEARTBEATE02.VAL")
#! Field("PLC:BC2B:TM01:HEARTBEATE02.B",16777215,0,"PLC:BC2B:TM01:HEARTBEATE02.B")
#! Record("PLC:BC2B:TM01:HEARTBEATE01",900,467,0,1,"PLC:BC2B:TM01:HEARTBEATE01")
#! Field("PLC:BC2B:TM01:HEARTBEATE01.INPA",16777215,0,"PLC:BC2B:TM01:HEARTBEATE01.INPA")
#! Link("PLC:BC2B:TM01:HEARTBEATE01.INPA","PLC:BC2B:TM01:HEARTBEATERR.VAL")
#! Field("PLC:BC2B:TM01:HEARTBEATE01.FLNK",16777215,1,"PLC:BC2B:TM01:HEARTBEATE01.FLNK")
#! Link("PLC:BC2B:TM01:HEARTBEATE01.FLNK","PLC:BC2B:TM01:HEARTBEATE02")
#! Field("PLC:BC2B:TM01:HEARTBEATE01.VAL",16777215,1,"PLC:BC2B:TM01:HEARTBEATE01.VAL")
#! Field("PLC:BC2B:TM01:HEARTBEATE01.INPB",16777215,0,"PLC:BC2B:TM01:HEARTBEATE01.INPB")
#! Link("PLC:BC2B:TM01:HEARTBEATE01.INPB","PLC:BC2B:TM01:HEARTBEATE01.VAL")
#! Field("PLC:BC2B:TM01:HEARTBEATE01.B",16777215,0,"PLC:BC2B:TM01:HEARTBEATE01.B")
#! Record("PLC:BC2B:TM01:HEARTBEATCLC",3300,1847,0,0,"PLC:BC2B:TM01:HEARTBEATCLC")
#! Field("PLC:BC2B:TM01:HEARTBEATCLC.INPA",16777215,0,"PLC:BC2B:TM01:HEARTBEATCLC.INPA")
#! Link("PLC:BC2B:TM01:HEARTBEATCLC.INPA","PLC:BC2B:TM01:HEARTBEATECT.SEVR")
#! Field("PLC:BC2B:TM01:HEARTBEATCLC.VAL",16777215,1,"PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:HEARTBEATSUM",2080,1690,0,0,"PLC:BC2B:TM01:HEARTBEATSUM")
#! Field("PLC:BC2B:TM01:HEARTBEATSUM.INP",16777215,0,"PLC:BC2B:TM01:HEARTBEATSUM.INP")
#! Link("PLC:BC2B:TM01:HEARTBEATSUM.INP","PLC:BC2B:TM01:HEARTBEATECT.SEVR")
#! Field("PLC:BC2B:TM01:HEARTBEATSUM.FLNK",16777215,1,"PLC:BC2B:TM01:HEARTBEATSUM.FLNK")
#! Link("PLC:BC2B:TM01:HEARTBEATSUM.FLNK","PLC:BC2B:TM01:HEARTBEATCLC")
#! Field("PLC:BC2B:TM01:HEARTBEATSUM.VAL",16777215,0,"PLC:BC2B:TM01:HEARTBEATSUM.VAL")
#! Record("PLC:BC2B:TM01:UPTIMEDAYRAW",4280,1587,0,0,"PLC:BC2B:TM01:UPTIMEDAYRAW")
#! Field("PLC:BC2B:TM01:UPTIMEDAYRAW.FLNK",16777215,1,"PLC:BC2B:TM01:UPTIMEDAYRAW.FLNK")
#! Link("PLC:BC2B:TM01:UPTIMEDAYRAW.FLNK","PLC:BC2B:TM01:UPTIMEDAY")
#! Field("PLC:BC2B:TM01:UPTIMEDAYRAW.VAL",16777215,1,"PLC:BC2B:TM01:UPTIMEDAYRAW.VAL")
#! Record("PLC:BC2B:TM01:UPTIMEDAY",4560,1622,0,0,"PLC:BC2B:TM01:UPTIMEDAY")
#! Field("PLC:BC2B:TM01:UPTIMEDAY.INPA",16777215,0,"PLC:BC2B:TM01:UPTIMEDAY.INPA")
#! Link("PLC:BC2B:TM01:UPTIMEDAY.INPA","PLC:BC2B:TM01:UPTIMEDAYRAW.VAL")
#! Field("PLC:BC2B:TM01:UPTIMEDAY.INPB",16777215,0,"PLC:BC2B:TM01:UPTIMEDAY.INPB")
#! Link("PLC:BC2B:TM01:UPTIMEDAY.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:TODYEARRAW",4220,487,0,0,"PLC:BC2B:TM01:TODYEARRAW")
#! Field("PLC:BC2B:TM01:TODYEARRAW.FLNK",16777215,1,"PLC:BC2B:TM01:TODYEARRAW.FLNK")
#! Link("PLC:BC2B:TM01:TODYEARRAW.FLNK","PLC:BC2B:TM01:TODYEAR")
#! Field("PLC:BC2B:TM01:TODYEARRAW.VAL",16777215,1,"PLC:BC2B:TM01:TODYEARRAW.VAL")
#! Record("PLC:BC2B:TM01:TODDAYRAW",4220,847,0,0,"PLC:BC2B:TM01:TODDAYRAW")
#! Field("PLC:BC2B:TM01:TODDAYRAW.FLNK",16777215,1,"PLC:BC2B:TM01:TODDAYRAW.FLNK")
#! Link("PLC:BC2B:TM01:TODDAYRAW.FLNK","PLC:BC2B:TM01:TODDAY")
#! Field("PLC:BC2B:TM01:TODDAYRAW.VAL",16777215,1,"PLC:BC2B:TM01:TODDAYRAW.VAL")
#! Record("PLC:BC2B:TM01:TODMONTHRAW",4220,667,0,0,"PLC:BC2B:TM01:TODMONTHRAW")
#! Field("PLC:BC2B:TM01:TODMONTHRAW.FLNK",16777215,1,"PLC:BC2B:TM01:TODMONTHRAW.FLNK")
#! Link("PLC:BC2B:TM01:TODMONTHRAW.FLNK","PLC:BC2B:TM01:TODMONTH")
#! Field("PLC:BC2B:TM01:TODMONTHRAW.VAL",16777215,1,"PLC:BC2B:TM01:TODMONTHRAW.VAL")
#! Record("PLC:BC2B:TM01:TODHOURRAW",4220,1027,0,0,"PLC:BC2B:TM01:TODHOURRAW")
#! Field("PLC:BC2B:TM01:TODHOURRAW.FLNK",16777215,1,"PLC:BC2B:TM01:TODHOURRAW.FLNK")
#! Link("PLC:BC2B:TM01:TODHOURRAW.FLNK","PLC:BC2B:TM01:TODHOUR")
#! Field("PLC:BC2B:TM01:TODHOURRAW.VAL",16777215,1,"PLC:BC2B:TM01:TODHOURRAW.VAL")
#! Record("PLC:BC2B:TM01:TODMINUTERAW",4220,1207,0,0,"PLC:BC2B:TM01:TODMINUTERAW")
#! Field("PLC:BC2B:TM01:TODMINUTERAW.FLNK",16777215,1,"PLC:BC2B:TM01:TODMINUTERAW.FLNK")
#! Link("PLC:BC2B:TM01:TODMINUTERAW.FLNK","PLC:BC2B:TM01:TODMINUTE")
#! Field("PLC:BC2B:TM01:TODMINUTERAW.VAL",16777215,1,"PLC:BC2B:TM01:TODMINUTERAW.VAL")
#! Record("PLC:BC2B:TM01:TODSECONDRAW",4220,1374,0,0,"PLC:BC2B:TM01:TODSECONDRAW")
#! Field("PLC:BC2B:TM01:TODSECONDRAW.FLNK",16777215,1,"PLC:BC2B:TM01:TODSECONDRAW.FLNK")
#! Link("PLC:BC2B:TM01:TODSECONDRAW.FLNK","PLC:BC2B:TM01:TODSECOND")
#! Field("PLC:BC2B:TM01:TODSECONDRAW.VAL",16777215,1,"PLC:BC2B:TM01:TODSECONDRAW.VAL")
#! Record("PLC:BC2B:TM01:TODYEAR",4520,522,0,0,"PLC:BC2B:TM01:TODYEAR")
#! Field("PLC:BC2B:TM01:TODYEAR.INPA",16777215,0,"PLC:BC2B:TM01:TODYEAR.INPA")
#! Link("PLC:BC2B:TM01:TODYEAR.INPA","PLC:BC2B:TM01:TODYEARRAW.VAL")
#! Field("PLC:BC2B:TM01:TODYEAR.INPB",16777215,0,"PLC:BC2B:TM01:TODYEAR.INPB")
#! Link("PLC:BC2B:TM01:TODYEAR.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:TODMONTH",4520,702,0,0,"PLC:BC2B:TM01:TODMONTH")
#! Field("PLC:BC2B:TM01:TODMONTH.INPA",16777215,0,"PLC:BC2B:TM01:TODMONTH.INPA")
#! Link("PLC:BC2B:TM01:TODMONTH.INPA","PLC:BC2B:TM01:TODMONTHRAW.VAL")
#! Field("PLC:BC2B:TM01:TODMONTH.INPB",16777215,0,"PLC:BC2B:TM01:TODMONTH.INPB")
#! Link("PLC:BC2B:TM01:TODMONTH.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:TODDAY",4520,882,0,0,"PLC:BC2B:TM01:TODDAY")
#! Field("PLC:BC2B:TM01:TODDAY.INPA",16777215,0,"PLC:BC2B:TM01:TODDAY.INPA")
#! Link("PLC:BC2B:TM01:TODDAY.INPA","PLC:BC2B:TM01:TODDAYRAW.VAL")
#! Field("PLC:BC2B:TM01:TODDAY.INPB",16777215,0,"PLC:BC2B:TM01:TODDAY.INPB")
#! Link("PLC:BC2B:TM01:TODDAY.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:TODHOUR",4520,1062,0,0,"PLC:BC2B:TM01:TODHOUR")
#! Field("PLC:BC2B:TM01:TODHOUR.INPA",16777215,0,"PLC:BC2B:TM01:TODHOUR.INPA")
#! Link("PLC:BC2B:TM01:TODHOUR.INPA","PLC:BC2B:TM01:TODHOURRAW.VAL")
#! Field("PLC:BC2B:TM01:TODHOUR.INPB",16777215,0,"PLC:BC2B:TM01:TODHOUR.INPB")
#! Link("PLC:BC2B:TM01:TODHOUR.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:TODMINUTE",4520,1242,0,0,"PLC:BC2B:TM01:TODMINUTE")
#! Field("PLC:BC2B:TM01:TODMINUTE.INPA",16777215,0,"PLC:BC2B:TM01:TODMINUTE.INPA")
#! Link("PLC:BC2B:TM01:TODMINUTE.INPA","PLC:BC2B:TM01:TODMINUTERAW.VAL")
#! Field("PLC:BC2B:TM01:TODMINUTE.INPB",16777215,0,"PLC:BC2B:TM01:TODMINUTE.INPB")
#! Link("PLC:BC2B:TM01:TODMINUTE.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:TODSECOND",4520,1422,0,0,"PLC:BC2B:TM01:TODSECOND")
#! Field("PLC:BC2B:TM01:TODSECOND.INPA",16777215,0,"PLC:BC2B:TM01:TODSECOND.INPA")
#! Link("PLC:BC2B:TM01:TODSECOND.INPA","PLC:BC2B:TM01:TODSECONDRAW.VAL")
#! Field("PLC:BC2B:TM01:TODSECOND.INPB",16777215,0,"PLC:BC2B:TM01:TODSECOND.INPB")
#! Link("PLC:BC2B:TM01:TODSECOND.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:VERSIONMAJORRAW",2740,2874,0,1,"PLC:BC2B:TM01:VERSIONMAJORRAW")
#! Field("PLC:BC2B:TM01:VERSIONMAJORRAW.VAL",16777215,1,"PLC:BC2B:TM01:VERSIONMAJORRAW.VAL")
#! Field("PLC:BC2B:TM01:VERSIONMAJORRAW.FLNK",16777215,1,"PLC:BC2B:TM01:VERSIONMAJORRAW.FLNK")
#! Link("PLC:BC2B:TM01:VERSIONMAJORRAW.FLNK","PLC:BC2B:TM01:VERSIONMAJOR")
#! Record("PLC:BC2B:TM01:VERSIONMINORRAW",2760,3287,0,1,"PLC:BC2B:TM01:VERSIONMINORRAW")
#! Field("PLC:BC2B:TM01:VERSIONMINORRAW.VAL",16777215,1,"PLC:BC2B:TM01:VERSIONMINORRAW.VAL")
#! Field("PLC:BC2B:TM01:VERSIONMINORRAW.FLNK",16777215,1,"PLC:BC2B:TM01:VERSIONMINORRAW.FLNK")
#! Link("PLC:BC2B:TM01:VERSIONMINORRAW.FLNK","PLC:BC2B:TM01:VERSIONMINOR")
#! Record("PLC:BC2B:TM01:VERSIONMAJOR",3040,2834,0,0,"PLC:BC2B:TM01:VERSIONMAJOR")
#! Field("PLC:BC2B:TM01:VERSIONMAJOR.INPA",16777215,0,"PLC:BC2B:TM01:VERSIONMAJOR.INPA")
#! Link("PLC:BC2B:TM01:VERSIONMAJOR.INPA","PLC:BC2B:TM01:VERSIONMAJORRAW.VAL")
#! Field("PLC:BC2B:TM01:VERSIONMAJOR.HIGH",16777215,0,"PLC:BC2B:TM01:VERSIONMAJOR.HIGH")
#! Field("PLC:BC2B:TM01:VERSIONMAJOR.LOW",16777215,0,"PLC:BC2B:TM01:VERSIONMAJOR.LOW")
#! Field("PLC:BC2B:TM01:VERSIONMAJOR.INPB",16777215,1,"PLC:BC2B:TM01:VERSIONMAJOR.INPB")
#! Link("PLC:BC2B:TM01:VERSIONMAJOR.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Field("PLC:BC2B:TM01:VERSIONMAJOR.VAL",16777215,0,"PLC:BC2B:TM01:VERSIONMAJOR.VAL")
#! Record("PLC:BC2B:TM01:VERSIONMINOR",3060,3194,0,0,"PLC:BC2B:TM01:VERSIONMINOR")
#! Field("PLC:BC2B:TM01:VERSIONMINOR.HIGH",16777215,0,"PLC:BC2B:TM01:VERSIONMINOR.HIGH")
#! Field("PLC:BC2B:TM01:VERSIONMINOR.INPA",16777215,0,"PLC:BC2B:TM01:VERSIONMINOR.INPA")
#! Link("PLC:BC2B:TM01:VERSIONMINOR.INPA","PLC:BC2B:TM01:VERSIONMINORRAW.VAL")
#! Field("PLC:BC2B:TM01:VERSIONMINOR.LOW",16777215,0,"PLC:BC2B:TM01:VERSIONMINOR.LOW")
#! Field("PLC:BC2B:TM01:VERSIONMINOR.INPB",16777215,1,"PLC:BC2B:TM01:VERSIONMINOR.INPB")
#! Link("PLC:BC2B:TM01:VERSIONMINOR.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Field("PLC:BC2B:TM01:VERSIONMINOR.VAL",16777215,0,"PLC:BC2B:TM01:VERSIONMINOR.VAL")
#! Record("PLC:BC2B:TM01:VERSIONREVRAW",2780,3687,0,1,"PLC:BC2B:TM01:VERSIONREVRAW")
#! Field("PLC:BC2B:TM01:VERSIONREVRAW.FLNK",16777215,1,"PLC:BC2B:TM01:VERSIONREVRAW.FLNK")
#! Link("PLC:BC2B:TM01:VERSIONREVRAW.FLNK","PLC:BC2B:TM01:VERSIONREV")
#! Field("PLC:BC2B:TM01:VERSIONREVRAW.VAL",16777215,1,"PLC:BC2B:TM01:VERSIONREVRAW.VAL")
#! Record("PLC:BC2B:TM01:VERSIONREV",3060,3594,0,0,"PLC:BC2B:TM01:VERSIONREV")
#! Field("PLC:BC2B:TM01:VERSIONREV.HIGH",16777215,0,"PLC:BC2B:TM01:VERSIONREV.HIGH")
#! Field("PLC:BC2B:TM01:VERSIONREV.LOW",16777215,0,"PLC:BC2B:TM01:VERSIONREV.LOW")
#! Field("PLC:BC2B:TM01:VERSIONREV.INPA",16777215,0,"PLC:BC2B:TM01:VERSIONREV.INPA")
#! Link("PLC:BC2B:TM01:VERSIONREV.INPA","PLC:BC2B:TM01:VERSIONREVRAW.VAL")
#! Field("PLC:BC2B:TM01:VERSIONREV.INPB",16777215,1,"PLC:BC2B:TM01:VERSIONREV.INPB")
#! Link("PLC:BC2B:TM01:VERSIONREV.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Field("PLC:BC2B:TM01:VERSIONREV.VAL",16777215,0,"PLC:BC2B:TM01:VERSIONREV.VAL")
#! Record("PLC:BC2B:TM01:SERIALNUMBERRAW",1960,3787,0,1,"PLC:BC2B:TM01:SERIALNUMBERRAW")
#! Field("PLC:BC2B:TM01:SERIALNUMBERRAW.FLNK",16777215,1,"PLC:BC2B:TM01:SERIALNUMBERRAW.FLNK")
#! Link("PLC:BC2B:TM01:SERIALNUMBERRAW.FLNK","PLC:BC2B:TM01:SERIALNUMBER")
#! Field("PLC:BC2B:TM01:SERIALNUMBERRAW.VAL",16777215,0,"PLC:BC2B:TM01:SERIALNUMBERRAW.VAL")
#! Record("PLC:BC2B:TM01:SERIALNUMBER",2220,3822,0,0,"PLC:BC2B:TM01:SERIALNUMBER")
#! Field("PLC:BC2B:TM01:SERIALNUMBER.INPA",16777215,0,"PLC:BC2B:TM01:SERIALNUMBER.INPA")
#! Link("PLC:BC2B:TM01:SERIALNUMBER.INPA","PLC:BC2B:TM01:SERIALNUMBERRAW.VAL")
#! Field("PLC:BC2B:TM01:SERIALNUMBER.INPB",16777215,1,"PLC:BC2B:TM01:SERIALNUMBER.INPB")
#! Link("PLC:BC2B:TM01:SERIALNUMBER.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:COMMLINK",340,43,0,0,"PLC:BC2B:TM01:COMMLINK")
#! Field("PLC:BC2B:TM01:COMMLINK.INP",16777215,0,"PLC:BC2B:TM01:COMMLINK.INP")
#! Link("PLC:BC2B:TM01:COMMLINK.INP","PLC:BC2B:TM01:HEARTBEATRAW.SEVR")
#! Field("PLC:BC2B:TM01:COMMLINK.FLNK",16777215,1,"PLC:BC2B:TM01:COMMLINK.FLNK")
#! Link("PLC:BC2B:TM01:COMMLINK.FLNK","PLC:BC2B:TM01:HEARTBEATCALC")
#! Record("PLC:BC2B:TM01:HEARTBEATE10",1100,2447,0,1,"PLC:BC2B:TM01:HEARTBEATE10")
#! Field("PLC:BC2B:TM01:HEARTBEATE10.VAL",16777215,1,"PLC:BC2B:TM01:HEARTBEATE10.VAL")
#! Field("PLC:BC2B:TM01:HEARTBEATE10.INPB",16777215,0,"PLC:BC2B:TM01:HEARTBEATE10.INPB")
#! Link("PLC:BC2B:TM01:HEARTBEATE10.INPB","PLC:BC2B:TM01:HEARTBEATE10.VAL")
#! Field("PLC:BC2B:TM01:HEARTBEATE10.FLNK",16777215,1,"PLC:BC2B:TM01:HEARTBEATE10.FLNK")
#! Link("PLC:BC2B:TM01:HEARTBEATE10.FLNK","PLC:BC2B:TM01:HEARTBEATECT")
#! Field("PLC:BC2B:TM01:HEARTBEATE10.INPA",16777215,0,"PLC:BC2B:TM01:HEARTBEATE10.INPA")
#! Link("PLC:BC2B:TM01:HEARTBEATE10.INPA","PLC:BC2B:TM01:HEARTBEATE09.B")
#! Record("PLC:BC2B:TM01:DOCPREFIXRAW",880,2867,0,1,"PLC:BC2B:TM01:DOCPREFIXRAW")
#! Field("PLC:BC2B:TM01:DOCPREFIXRAW.FLNK",16777215,1,"PLC:BC2B:TM01:DOCPREFIXRAW.FLNK")
#! Link("PLC:BC2B:TM01:DOCPREFIXRAW.FLNK","PLC:BC2B:TM01:DOCPREFIXCALC")
#! Field("PLC:BC2B:TM01:DOCPREFIXRAW.VAL",16777215,1,"PLC:BC2B:TM01:DOCPREFIXRAW.VAL")
#! Record("PLC:BC2B:TM01:DOCPREFIXCALC",1160,2887,0,0,"PLC:BC2B:TM01:DOCPREFIXCALC")
#! Field("PLC:BC2B:TM01:DOCPREFIXCALC.INPA",16777215,0,"PLC:BC2B:TM01:DOCPREFIXCALC.INPA")
#! Link("PLC:BC2B:TM01:DOCPREFIXCALC.INPA","PLC:BC2B:TM01:DOCPREFIXRAW.VAL")
#! Field("PLC:BC2B:TM01:DOCPREFIXCALC.FLNK",16777215,1,"PLC:BC2B:TM01:DOCPREFIXCALC.FLNK")
#! Link("PLC:BC2B:TM01:DOCPREFIXCALC.FLNK","PLC:BC2B:TM01:DOCPREFIX")
#! Field("PLC:BC2B:TM01:DOCPREFIXCALC.VAL",16777215,1,"PLC:BC2B:TM01:DOCPREFIXCALC.VAL")
#! Field("PLC:BC2B:TM01:DOCPREFIXCALC.INPB",16777215,1,"PLC:BC2B:TM01:DOCPREFIXCALC.INPB")
#! Link("PLC:BC2B:TM01:DOCPREFIXCALC.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:DOCPREFIX",1460,2630,0,0,"PLC:BC2B:TM01:DOCPREFIX")
#! Field("PLC:BC2B:TM01:DOCPREFIX.INP",16777215,0,"PLC:BC2B:TM01:DOCPREFIX.INP")
#! Link("PLC:BC2B:TM01:DOCPREFIX.INP","PLC:BC2B:TM01:DOCPREFIXCALC.VAL")
#! Record("PLC:BC2B:TM01:DOCSERIESRAW",880,3087,0,1,"PLC:BC2B:TM01:DOCSERIESRAW")
#! Field("PLC:BC2B:TM01:DOCSERIESRAW.FLNK",16777215,1,"PLC:BC2B:TM01:DOCSERIESRAW.FLNK")
#! Link("PLC:BC2B:TM01:DOCSERIESRAW.FLNK","PLC:BC2B:TM01:DOCSERIES")
#! Field("PLC:BC2B:TM01:DOCSERIESRAW.VAL",16777215,1,"PLC:BC2B:TM01:DOCSERIESRAW.VAL")
#! Record("PLC:BC2B:TM01:DOCSERIES",1160,3122,0,0,"PLC:BC2B:TM01:DOCSERIES")
#! Field("PLC:BC2B:TM01:DOCSERIES.INPA",16777215,0,"PLC:BC2B:TM01:DOCSERIES.INPA")
#! Link("PLC:BC2B:TM01:DOCSERIES.INPA","PLC:BC2B:TM01:DOCSERIESRAW.VAL")
#! Field("PLC:BC2B:TM01:DOCSERIES.INPB",16777215,1,"PLC:BC2B:TM01:DOCSERIES.INPB")
#! Link("PLC:BC2B:TM01:DOCSERIES.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:DOCBASERAW",878,3307,0,1,"PLC:BC2B:TM01:DOCBASERAW")
#! Field("PLC:BC2B:TM01:DOCBASERAW.FLNK",16777215,1,"PLC:BC2B:TM01:DOCBASERAW.FLNK")
#! Link("PLC:BC2B:TM01:DOCBASERAW.FLNK","PLC:BC2B:TM01:DOCBASE")
#! Field("PLC:BC2B:TM01:DOCBASERAW.VAL",16777215,1,"PLC:BC2B:TM01:DOCBASERAW.VAL")
#! Record("PLC:BC2B:TM01:DOCBASE",1160,3342,0,0,"PLC:BC2B:TM01:DOCBASE")
#! Field("PLC:BC2B:TM01:DOCBASE.INPA",16777215,0,"PLC:BC2B:TM01:DOCBASE.INPA")
#! Link("PLC:BC2B:TM01:DOCBASE.INPA","PLC:BC2B:TM01:DOCBASERAW.VAL")
#! Field("PLC:BC2B:TM01:DOCBASE.INPB",16777215,1,"PLC:BC2B:TM01:DOCBASE.INPB")
#! Link("PLC:BC2B:TM01:DOCBASE.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:DOCSUFFIXRAW",878,3567,0,1,"PLC:BC2B:TM01:DOCSUFFIXRAW")
#! Field("PLC:BC2B:TM01:DOCSUFFIXRAW.FLNK",16777215,1,"PLC:BC2B:TM01:DOCSUFFIXRAW.FLNK")
#! Link("PLC:BC2B:TM01:DOCSUFFIXRAW.FLNK","PLC:BC2B:TM01:DOCSUFFIX")
#! Field("PLC:BC2B:TM01:DOCSUFFIXRAW.VAL",16777215,1,"PLC:BC2B:TM01:DOCSUFFIXRAW.VAL")
#! Record("PLC:BC2B:TM01:DOCSUFFIX",1160,3602,0,0,"PLC:BC2B:TM01:DOCSUFFIX")
#! Field("PLC:BC2B:TM01:DOCSUFFIX.INPA",16777215,0,"PLC:BC2B:TM01:DOCSUFFIX.INPA")
#! Link("PLC:BC2B:TM01:DOCSUFFIX.INPA","PLC:BC2B:TM01:DOCSUFFIXRAW.VAL")
#! Field("PLC:BC2B:TM01:DOCSUFFIX.INPB",16777215,1,"PLC:BC2B:TM01:DOCSUFFIX.INPB")
#! Link("PLC:BC2B:TM01:DOCSUFFIX.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:DOCREVRAW",874,3787,0,1,"PLC:BC2B:TM01:DOCREVRAW")
#! Field("PLC:BC2B:TM01:DOCREVRAW.FLNK",16777215,1,"PLC:BC2B:TM01:DOCREVRAW.FLNK")
#! Link("PLC:BC2B:TM01:DOCREVRAW.FLNK","PLC:BC2B:TM01:DOCREV")
#! Field("PLC:BC2B:TM01:DOCREVRAW.VAL",16777215,1,"PLC:BC2B:TM01:DOCREVRAW.VAL")
#! Record("PLC:BC2B:TM01:DOCREV",1154,3822,0,0,"PLC:BC2B:TM01:DOCREV")
#! Field("PLC:BC2B:TM01:DOCREV.INPA",16777215,0,"PLC:BC2B:TM01:DOCREV.INPA")
#! Link("PLC:BC2B:TM01:DOCREV.INPA","PLC:BC2B:TM01:DOCREVRAW.VAL")
#! Field("PLC:BC2B:TM01:DOCREV.INPB",16777215,1,"PLC:BC2B:TM01:DOCREV.INPB")
#! Link("PLC:BC2B:TM01:DOCREV.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:SUBSYSTEM",3320,2816,0,1,"PLC:BC2B:TM01:SUBSYSTEM")
#! Record("PLC:BC2B:TM01:PLCADMINVMAJRAW",2720,2087,0,1,"PLC:BC2B:TM01:PLCADMINVMAJRAW")
#! Field("PLC:BC2B:TM01:PLCADMINVMAJRAW.FLNK",16777215,1,"PLC:BC2B:TM01:PLCADMINVMAJRAW.FLNK")
#! Link("PLC:BC2B:TM01:PLCADMINVMAJRAW.FLNK","PLC:BC2B:TM01:PLCADMINVMAJ")
#! Field("PLC:BC2B:TM01:PLCADMINVMAJRAW.VAL",16777215,1,"PLC:BC2B:TM01:PLCADMINVMAJRAW.VAL")
#! Record("PLC:BC2B:TM01:PLCADMINVMAJ",3020,2050,0,0,"PLC:BC2B:TM01:PLCADMINVMAJ")
#! Field("PLC:BC2B:TM01:PLCADMINVMAJ.INPA",16777215,0,"PLC:BC2B:TM01:PLCADMINVMAJ.INPA")
#! Link("PLC:BC2B:TM01:PLCADMINVMAJ.INPA","PLC:BC2B:TM01:PLCADMINVMAJRAW.VAL")
#! Field("PLC:BC2B:TM01:PLCADMINVMAJ.INPB",16777215,1,"PLC:BC2B:TM01:PLCADMINVMAJ.INPB")
#! Link("PLC:BC2B:TM01:PLCADMINVMAJ.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:PLCADMINVMINRAW",2720,2327,0,1,"PLC:BC2B:TM01:PLCADMINVMINRAW")
#! Field("PLC:BC2B:TM01:PLCADMINVMINRAW.FLNK",16777215,1,"PLC:BC2B:TM01:PLCADMINVMINRAW.FLNK")
#! Link("PLC:BC2B:TM01:PLCADMINVMINRAW.FLNK","PLC:BC2B:TM01:PLCADMINVMIN")
#! Field("PLC:BC2B:TM01:PLCADMINVMINRAW.VAL",16777215,1,"PLC:BC2B:TM01:PLCADMINVMINRAW.VAL")
#! Record("PLC:BC2B:TM01:PLCADMINVMIN",3020,2290,0,0,"PLC:BC2B:TM01:PLCADMINVMIN")
#! Field("PLC:BC2B:TM01:PLCADMINVMIN.INPA",16777215,0,"PLC:BC2B:TM01:PLCADMINVMIN.INPA")
#! Link("PLC:BC2B:TM01:PLCADMINVMIN.INPA","PLC:BC2B:TM01:PLCADMINVMINRAW.VAL")
#! Field("PLC:BC2B:TM01:PLCADMINVMIN.INPB",16777215,1,"PLC:BC2B:TM01:PLCADMINVMIN.INPB")
#! Link("PLC:BC2B:TM01:PLCADMINVMIN.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:PLCADMINVREVRAW",2720,2567,0,1,"PLC:BC2B:TM01:PLCADMINVREVRAW")
#! Field("PLC:BC2B:TM01:PLCADMINVREVRAW.FLNK",16777215,1,"PLC:BC2B:TM01:PLCADMINVREVRAW.FLNK")
#! Link("PLC:BC2B:TM01:PLCADMINVREVRAW.FLNK","PLC:BC2B:TM01:PLCADMINVREV")
#! Field("PLC:BC2B:TM01:PLCADMINVREVRAW.VAL",16777215,1,"PLC:BC2B:TM01:PLCADMINVREVRAW.VAL")
#! Record("PLC:BC2B:TM01:PLCADMINVREV",3020,2530,0,0,"PLC:BC2B:TM01:PLCADMINVREV")
#! Field("PLC:BC2B:TM01:PLCADMINVREV.INPA",16777215,0,"PLC:BC2B:TM01:PLCADMINVREV.INPA")
#! Link("PLC:BC2B:TM01:PLCADMINVREV.INPA","PLC:BC2B:TM01:PLCADMINVREVRAW.VAL")
#! Field("PLC:BC2B:TM01:PLCADMINVREV.INPB",16777215,1,"PLC:BC2B:TM01:PLCADMINVREV.INPB")
#! Link("PLC:BC2B:TM01:PLCADMINVREV.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:PROGPLCATMAXRAW",2700,727,0,0,"PLC:BC2B:TM01:PROGPLCATMAXRAW")
#! Field("PLC:BC2B:TM01:PROGPLCATMAXRAW.FLNK",16777215,1,"PLC:BC2B:TM01:PROGPLCATMAXRAW.FLNK")
#! Link("PLC:BC2B:TM01:PROGPLCATMAXRAW.FLNK","PLC:BC2B:TM01:PROGPLCATMAX")
#! Field("PLC:BC2B:TM01:PROGPLCATMAXRAW.VAL",16777215,1,"PLC:BC2B:TM01:PROGPLCATMAXRAW.VAL")
#! Record("PLC:BC2B:TM01:PROGPLCATLSTRAW",2700,567,0,0,"PLC:BC2B:TM01:PROGPLCATLSTRAW")
#! Field("PLC:BC2B:TM01:PROGPLCATLSTRAW.FLNK",16777215,1,"PLC:BC2B:TM01:PROGPLCATLSTRAW.FLNK")
#! Link("PLC:BC2B:TM01:PROGPLCATLSTRAW.FLNK","PLC:BC2B:TM01:PROGPLCATLST")
#! Field("PLC:BC2B:TM01:PROGPLCATLSTRAW.VAL",16777215,1,"PLC:BC2B:TM01:PROGPLCATLSTRAW.VAL")
#! Record("PLC:BC2B:TM01:PROGPLCATLST",3000,602,0,0,"PLC:BC2B:TM01:PROGPLCATLST")
#! Field("PLC:BC2B:TM01:PROGPLCATLST.INPA",16777215,0,"PLC:BC2B:TM01:PROGPLCATLST.INPA")
#! Link("PLC:BC2B:TM01:PROGPLCATLST.INPA","PLC:BC2B:TM01:PROGPLCATLSTRAW.VAL")
#! Field("PLC:BC2B:TM01:PROGPLCATLST.INPB",16777215,1,"PLC:BC2B:TM01:PROGPLCATLST.INPB")
#! Link("PLC:BC2B:TM01:PROGPLCATLST.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:PROGPLCATMAX",3000,762,0,0,"PLC:BC2B:TM01:PROGPLCATMAX")
#! Field("PLC:BC2B:TM01:PROGPLCATMAX.INPA",16777215,0,"PLC:BC2B:TM01:PROGPLCATMAX.INPA")
#! Link("PLC:BC2B:TM01:PROGPLCATMAX.INPA","PLC:BC2B:TM01:PROGPLCATMAXRAW.VAL")
#! Field("PLC:BC2B:TM01:PROGPLCATMAX.INPB",16777215,1,"PLC:BC2B:TM01:PROGPLCATMAX.INPB")
#! Link("PLC:BC2B:TM01:PROGPLCATMAX.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:PLCADMINTAG",2120,876,0,1,"PLC:BC2B:TM01:PLCADMINTAG")
#! Record("PLC:BC2B:TM01:TASKMAINTLSTRAW",2700,247,0,0,"PLC:BC2B:TM01:TASKMAINTLSTRAW")
#! Field("PLC:BC2B:TM01:TASKMAINTLSTRAW.FLNK",16777215,1,"PLC:BC2B:TM01:TASKMAINTLSTRAW.FLNK")
#! Link("PLC:BC2B:TM01:TASKMAINTLSTRAW.FLNK","PLC:BC2B:TM01:TASKMAINTLST")
#! Field("PLC:BC2B:TM01:TASKMAINTLSTRAW.VAL",16777215,1,"PLC:BC2B:TM01:TASKMAINTLSTRAW.VAL")
#! Record("PLC:BC2B:TM01:TASKMAINTLST",3000,282,0,0,"PLC:BC2B:TM01:TASKMAINTLST")
#! Field("PLC:BC2B:TM01:TASKMAINTLST.INPA",16777215,0,"PLC:BC2B:TM01:TASKMAINTLST.INPA")
#! Link("PLC:BC2B:TM01:TASKMAINTLST.INPA","PLC:BC2B:TM01:TASKMAINTLSTRAW.VAL")
#! Field("PLC:BC2B:TM01:TASKMAINTLST.INPB",16777215,1,"PLC:BC2B:TM01:TASKMAINTLST.INPB")
#! Link("PLC:BC2B:TM01:TASKMAINTLST.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:TASKMAINTMAXRAW",2700,407,0,0,"PLC:BC2B:TM01:TASKMAINTMAXRAW")
#! Field("PLC:BC2B:TM01:TASKMAINTMAXRAW.FLNK",16777215,1,"PLC:BC2B:TM01:TASKMAINTMAXRAW.FLNK")
#! Link("PLC:BC2B:TM01:TASKMAINTMAXRAW.FLNK","PLC:BC2B:TM01:TASKMAINTMAX")
#! Field("PLC:BC2B:TM01:TASKMAINTMAXRAW.VAL",16777215,1,"PLC:BC2B:TM01:TASKMAINTMAXRAW.VAL")
#! Record("PLC:BC2B:TM01:TASKMAINTMAX",3000,442,0,0,"PLC:BC2B:TM01:TASKMAINTMAX")
#! Field("PLC:BC2B:TM01:TASKMAINTMAX.INPA",16777215,0,"PLC:BC2B:TM01:TASKMAINTMAX.INPA")
#! Link("PLC:BC2B:TM01:TASKMAINTMAX.INPA","PLC:BC2B:TM01:TASKMAINTMAXRAW.VAL")
#! Field("PLC:BC2B:TM01:TASKMAINTMAX.INPB",16777215,1,"PLC:BC2B:TM01:TASKMAINTMAX.INPB")
#! Link("PLC:BC2B:TM01:TASKMAINTMAX.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:PROG1TLSTRAW",2700,887,0,0,"PLC:BC2B:TM01:PROG1TLSTRAW")
#! Field("PLC:BC2B:TM01:PROG1TLSTRAW.FLNK",16777215,1,"PLC:BC2B:TM01:PROG1TLSTRAW.FLNK")
#! Link("PLC:BC2B:TM01:PROG1TLSTRAW.FLNK","PLC:BC2B:TM01:PROG1TLST")
#! Field("PLC:BC2B:TM01:PROG1TLSTRAW.VAL",16777215,1,"PLC:BC2B:TM01:PROG1TLSTRAW.VAL")
#! Record("PLC:BC2B:TM01:PROG1TMAXRAW",2700,1047,0,0,"PLC:BC2B:TM01:PROG1TMAXRAW")
#! Field("PLC:BC2B:TM01:PROG1TMAXRAW.FLNK",16777215,1,"PLC:BC2B:TM01:PROG1TMAXRAW.FLNK")
#! Link("PLC:BC2B:TM01:PROG1TMAXRAW.FLNK","PLC:BC2B:TM01:PROG1TMAX")
#! Field("PLC:BC2B:TM01:PROG1TMAXRAW.VAL",16777215,1,"PLC:BC2B:TM01:PROG1TMAXRAW.VAL")
#! Record("PLC:BC2B:TM01:PROG1TLST",3000,922,0,0,"PLC:BC2B:TM01:PROG1TLST")
#! Field("PLC:BC2B:TM01:PROG1TLST.INPA",16777215,0,"PLC:BC2B:TM01:PROG1TLST.INPA")
#! Link("PLC:BC2B:TM01:PROG1TLST.INPA","PLC:BC2B:TM01:PROG1TLSTRAW.VAL")
#! Field("PLC:BC2B:TM01:PROG1TLST.INPB",16777215,1,"PLC:BC2B:TM01:PROG1TLST.INPB")
#! Link("PLC:BC2B:TM01:PROG1TLST.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:PROG1TMAX",3000,1082,0,0,"PLC:BC2B:TM01:PROG1TMAX")
#! Field("PLC:BC2B:TM01:PROG1TMAX.INPA",16777215,0,"PLC:BC2B:TM01:PROG1TMAX.INPA")
#! Link("PLC:BC2B:TM01:PROG1TMAX.INPA","PLC:BC2B:TM01:PROG1TMAXRAW.VAL")
#! Field("PLC:BC2B:TM01:PROG1TMAX.INPB",16777215,1,"PLC:BC2B:TM01:PROG1TMAX.INPB")
#! Link("PLC:BC2B:TM01:PROG1TMAX.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:PROG2TLSTRAW",2700,1207,0,0,"PLC:BC2B:TM01:PROG2TLSTRAW")
#! Field("PLC:BC2B:TM01:PROG2TLSTRAW.FLNK",16777215,1,"PLC:BC2B:TM01:PROG2TLSTRAW.FLNK")
#! Link("PLC:BC2B:TM01:PROG2TLSTRAW.FLNK","PLC:BC2B:TM01:PROG2TLST")
#! Field("PLC:BC2B:TM01:PROG2TLSTRAW.VAL",16777215,1,"PLC:BC2B:TM01:PROG2TLSTRAW.VAL")
#! Record("PLC:BC2B:TM01:PROG2TMAXRAW",2700,1367,0,0,"PLC:BC2B:TM01:PROG2TMAXRAW")
#! Field("PLC:BC2B:TM01:PROG2TMAXRAW.FLNK",16777215,1,"PLC:BC2B:TM01:PROG2TMAXRAW.FLNK")
#! Link("PLC:BC2B:TM01:PROG2TMAXRAW.FLNK","PLC:BC2B:TM01:PROG2TMAX")
#! Field("PLC:BC2B:TM01:PROG2TMAXRAW.VAL",16777215,1,"PLC:BC2B:TM01:PROG2TMAXRAW.VAL")
#! Record("PLC:BC2B:TM01:PROG2TLST",3000,1242,0,0,"PLC:BC2B:TM01:PROG2TLST")
#! Field("PLC:BC2B:TM01:PROG2TLST.INPA",16777215,0,"PLC:BC2B:TM01:PROG2TLST.INPA")
#! Link("PLC:BC2B:TM01:PROG2TLST.INPA","PLC:BC2B:TM01:PROG2TLSTRAW.VAL")
#! Field("PLC:BC2B:TM01:PROG2TLST.INPB",16777215,1,"PLC:BC2B:TM01:PROG2TLST.INPB")
#! Link("PLC:BC2B:TM01:PROG2TLST.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:PROG2TMAX",3000,1402,0,0,"PLC:BC2B:TM01:PROG2TMAX")
#! Field("PLC:BC2B:TM01:PROG2TMAX.INPA",16777215,0,"PLC:BC2B:TM01:PROG2TMAX.INPA")
#! Link("PLC:BC2B:TM01:PROG2TMAX.INPA","PLC:BC2B:TM01:PROG2TMAXRAW.VAL")
#! Field("PLC:BC2B:TM01:PROG2TMAX.INPB",16777215,1,"PLC:BC2B:TM01:PROG2TMAX.INPB")
#! Link("PLC:BC2B:TM01:PROG2TMAX.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:PROG3TLSTRAW",2700,1527,0,0,"PLC:BC2B:TM01:PROG3TLSTRAW")
#! Field("PLC:BC2B:TM01:PROG3TLSTRAW.FLNK",16777215,1,"PLC:BC2B:TM01:PROG3TLSTRAW.FLNK")
#! Link("PLC:BC2B:TM01:PROG3TLSTRAW.FLNK","PLC:BC2B:TM01:PROG3TLST")
#! Field("PLC:BC2B:TM01:PROG3TLSTRAW.VAL",16777215,1,"PLC:BC2B:TM01:PROG3TLSTRAW.VAL")
#! Record("PLC:BC2B:TM01:PROG3TMAXRAW",2700,1687,0,0,"PLC:BC2B:TM01:PROG3TMAXRAW")
#! Field("PLC:BC2B:TM01:PROG3TMAXRAW.FLNK",16777215,1,"PLC:BC2B:TM01:PROG3TMAXRAW.FLNK")
#! Link("PLC:BC2B:TM01:PROG3TMAXRAW.FLNK","PLC:BC2B:TM01:PROG3TMAX")
#! Field("PLC:BC2B:TM01:PROG3TMAXRAW.VAL",16777215,1,"PLC:BC2B:TM01:PROG3TMAXRAW.VAL")
#! Record("PLC:BC2B:TM01:PROG3TMAX",3000,1722,0,0,"PLC:BC2B:TM01:PROG3TMAX")
#! Field("PLC:BC2B:TM01:PROG3TMAX.INPA",16777215,0,"PLC:BC2B:TM01:PROG3TMAX.INPA")
#! Link("PLC:BC2B:TM01:PROG3TMAX.INPA","PLC:BC2B:TM01:PROG3TMAXRAW.VAL")
#! Field("PLC:BC2B:TM01:PROG3TMAX.INPB",16777215,1,"PLC:BC2B:TM01:PROG3TMAX.INPB")
#! Link("PLC:BC2B:TM01:PROG3TMAX.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:PROG3TLST",3000,1562,0,0,"PLC:BC2B:TM01:PROG3TLST")
#! Field("PLC:BC2B:TM01:PROG3TLST.INPA",16777215,0,"PLC:BC2B:TM01:PROG3TLST.INPA")
#! Link("PLC:BC2B:TM01:PROG3TLST.INPA","PLC:BC2B:TM01:PROG3TLSTRAW.VAL")
#! Field("PLC:BC2B:TM01:PROG3TLST.INPB",16777215,1,"PLC:BC2B:TM01:PROG3TLST.INPB")
#! Link("PLC:BC2B:TM01:PROG3TLST.INPB","PLC:BC2B:TM01:HEARTBEATCLC.VAL")
#! Record("PLC:BC2B:TM01:STATSUMY",1600,4643,0,1,"PLC:BC2B:TM01:STATSUMY")
#! Field("PLC:BC2B:TM01:STATSUMY.INPB",16777215,1,"PLC:BC2B:TM01:STATSUMY.INPB")
#! Link("PLC:BC2B:TM01:STATSUMY.INPB","PLC:BC2B:TM01:HEARTBEATSUM.VAL")
#! Field("PLC:BC2B:TM01:STATSUMY.INPC",16777215,1,"PLC:BC2B:TM01:STATSUMY.INPC")
#! Link("PLC:BC2B:TM01:STATSUMY.INPC","PLC:BC2B:TM01:FAULTSTATUS.VAL")
#! Field("PLC:BC2B:TM01:STATSUMY.INPD",16777215,1,"PLC:BC2B:TM01:STATSUMY.INPD")
#! Link("PLC:BC2B:TM01:STATSUMY.INPD","PLC:BC2B:TM01:KEYSTATUS.VAL")
#! Field("PLC:BC2B:TM01:STATSUMY.INPE",16777215,1,"PLC:BC2B:TM01:STATSUMY.INPE")
#! Link("PLC:BC2B:TM01:STATSUMY.INPE","PLC:BC2B:TM01:DEVICESTATUS.VAL")
#! Field("PLC:BC2B:TM01:STATSUMY.INPF",16777215,1,"PLC:BC2B:TM01:STATSUMY.INPF")
#! Link("PLC:BC2B:TM01:STATSUMY.INPF","PLC:BC2B:TM01:VERSIONMAJOR.VAL")
#! Field("PLC:BC2B:TM01:STATSUMY.INPG",16777215,1,"PLC:BC2B:TM01:STATSUMY.INPG")
#! Link("PLC:BC2B:TM01:STATSUMY.INPG","PLC:BC2B:TM01:VERSIONMINOR.VAL")
#! Field("PLC:BC2B:TM01:STATSUMY.INPH",16777215,1,"PLC:BC2B:TM01:STATSUMY.INPH")
#! Link("PLC:BC2B:TM01:STATSUMY.INPH","PLC:BC2B:TM01:VERSIONREV.VAL")
#! Field("PLC:BC2B:TM01:STATSUMY.SEVR",16777215,0,"PLC:BC2B:TM01:STATSUMY.SEVR")
#! Field("PLC:BC2B:TM01:STATSUMY.INPA",16777215,0,"PLC:BC2B:TM01:STATSUMY.INPA")
#! Link("PLC:BC2B:TM01:STATSUMY.INPA","PLC:BC2B:TM01:STATSUMY.SEVR")
# -*- shell-script -*-
# AI records that read statistical information from EtherIP
# driver/device
#
# IOC:  prefix to records
# PLC:  PLC to use
# TAG:  queried tag (leads to PLC's ScanList)

record(ai, "PLC:BC2B:TM01:PLC_ERRORS")
{
	field(SCAN, ".5 second")
	field(DTYP, "EtherIP")
	field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01 PLC_ERRORS")
	field(EGUF, "5")
	field(EGU, "Errors")
	field(HOPR, "5")
	field(LOPR, "0")
}


record(ai, "PLC:BC2B:TM01:PLC_TASK_SLOW")
{
	field(SCAN, ".5 second")
	field(DTYP, "EtherIP")
	field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01 PLC_TASK_SLOW")
	field(EGUF, "5")
	field(EGU, "Holdups")
	field(HOPR, "5")
	field(LOPR, "0")
}

record(ai, "PLC:BC2B:TM01:LIST_TICKS")
{
	field(SCAN, ".5 second")
	field(DTYP, "EtherIP")
	field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01 LIST_TICKS")
	field(EGUF, "5")
	field(EGU, "vx ticks")
	field(HOPR, "5")
	field(LOPR, "0")
}

record(ai, "PLC:BC2B:TM01:LIST_SCAN_TIME")
{
	field(SCAN, ".5 second")
	field(DTYP, "EtherIP")
	field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01 LIST_SCAN_TIME")
	field(EGUF, "1")
	field(EGU, "s")
	field(HOPR, "1")
	field(LOPR, "0")
	field(PREC, "5")
}

record(ai, "PLC:BC2B:TM01:LIST_MIN_SCAN_TIME")
{
	field(SCAN, ".5 second")
	field(DTYP, "EtherIP")
	field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01 LIST_MIN_SCAN_TIME")
	field(EGUF, "1")
	field(EGU, "s")
	field(HOPR, "1")
	field(LOPR, "0")
	field(PREC, "5")
}

record(ai, "PLC:BC2B:TM01:LIST_MAX_SCAN_TIME")
{
	field(SCAN, ".5 second")
	field(DTYP, "EtherIP")
	field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01 LIST_MAX_SCAN_TIME")
	field(EGUF, "1")
	field(EGU, "s")
	field(HOPR, "1")
	field(LOPR, "0")
	field(PREC, "5")
}

record(ai, "PLC:BC2B:TM01:TAG_TRANSFER_TIME")
{
	field(SCAN, ".5 second")
	field(DTYP, "EtherIP")
	field(INP, "@PLC_BC2B_TM01 PLCADMIN_PLC_BC2B_TM01 TAG_TRANSFER_TIME")
	field(EGUF, "1000000000")
	field(EGU, "s")
	field(HOPR, "1")
	field(LOPR, "0")
	field(PREC, "5")
}






#==============================================================================
#
# Abs:  Database template for plcinfo.
#
# Name: ab-plc-info-lcls2.template
#
# Macros:
#       CR          Panel or crate number
#       NUM_CHANS   Total number of channels
#       UNIT        Unit number of the PLC   
#       LOCA        Location of the PLC
#       LOCATION    Location of the panel
#==============================================================================
record(stringin, "PLC:BC2B:TM01:CR1_LOC") {
    field(VAL, "L2KA04-0524")
}

record(longout, "PLC:BC2B:TM01:CR1_NUM_CHANS") {
    field(VAL, "36")
}

record(bo, "PLC:BC2B:TM01:INITIALIZE") {
    field(DTYP, "EtherIP")
    field(OUT, "@PLC_BC2B_TM01 INITIALIZE") 
    field(DESC, "Init")

}
#==============================================================================
#
# Abs:  Database template for plcinfo.
#
# Name: ab-plc-info-lcls2.template
#
# Macros:
#       CR          Panel or crate number
#       NUM_CHANS   Total number of channels
#       UNIT        Unit number of the PLC   
#       LOCA        Location of the PLC
#       LOCATION    Location of the panel
#==============================================================================
record(stringin, "PLC:BC2B:TM01:CR2_LOC") {
    field(VAL, "L2KA04-0526")
}

record(longout, "PLC:BC2B:TM01:CR2_NUM_CHANS") {
    field(VAL, "16")
}

record(bo, "PLC:BC2B:TM01:INITIALIZE") {
    field(DTYP, "EtherIP")
    field(OUT, "@PLC_BC2B_TM01 INITIALIZE") 
    field(DESC, "Init")

}
#==============================================================================
#
# Abs:  Database template for plcinfo.
#
# Name: ab-plc-info-lcls2.template
#
# Macros:
#       CR          Panel or crate number
#       NUM_CHANS   Total number of channels
#       UNIT        Unit number of the PLC   
#       LOCA        Location of the PLC
#       LOCATION    Location of the panel
#==============================================================================
record(stringin, "PLC:BC2B:TM01:CR3_LOC") {
    field(VAL, "L2KA05-0524")
}

record(longout, "PLC:BC2B:TM01:CR3_NUM_CHANS") {
    field(VAL, "28")
}

record(bo, "PLC:BC2B:TM01:INITIALIZE") {
    field(DTYP, "EtherIP")
    field(OUT, "@PLC_BC2B_TM01 INITIALIZE") 
    field(DESC, "Init")

}
#==============================================================================
#
# Abs:  Database template for plcinfo.
#
# Name: ab-plc-info-lcls2.template
#
# Macros:
#       CR          Panel or crate number
#       NUM_CHANS   Total number of channels
#       UNIT        Unit number of the PLC   
#       LOCA        Location of the PLC
#       LOCATION    Location of the panel
#==============================================================================
record(stringin, "PLC:BC2B:TM01:CR4_LOC") {
    field(VAL, "L2KA06-0424")
}

record(longout, "PLC:BC2B:TM01:CR4_NUM_CHANS") {
    field(VAL, "28")
}

record(bo, "PLC:BC2B:TM01:INITIALIZE") {
    field(DTYP, "EtherIP")
    field(OUT, "@PLC_BC2B_TM01 INITIALIZE") 
    field(DESC, "Init")

}
#
# This template is used to control MPS outputs
#
#
# Macros:
#        TYPE  Type of MPS Permit signal- eg: TEMP, FLOW etc.
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS EPICS name for the PV
#        MAD   MAD name for the PV
#==============================================================================
# Temperature PV Alarm status
# Alarm channels are the PV  bit
record(bi, "COLL:BC2B:535:TEMP_PERMIT"){
  field(DESC, "CE21B TEMP Permit Alarm Sts")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 MPSAlarm[0] B 0")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Bypass reset
# Alarm channels are the PV  bit
# Eg: SigResetReq[0].0
# Uses Reset_Index 0 , Uses Channel 0
record(bo, "COLL:BC2B:535:TEMP_RESET") {
  field(DESC, "Reset Request")
  field(DTYP, "EtherIP")
  #field(ASG, "MCC")
  field(OUT , "@PLC_BC2B_TM01 SigResetReq[0] B 0")
  field(ZNAM, "RESET")
  field(ONAM, "RESET")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(HIGH, "2")
  field(ASG, "MCC")
}

#
# This template is used to control MPS outputs
#
#
# Macros:
#        TYPE  Type of MPS Permit signal- eg: TEMP, FLOW etc.
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS EPICS name for the PV
#        MAD   MAD name for the PV
#==============================================================================
# Temperature PV Alarm status
# Alarm channels are the PV  bit
record(bi, "BLEN:BC2B:950:TEMP_PERMIT"){
  field(DESC, "BZ21B TEMP Permit Alarm Sts")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 MPSAlarm[0] B 1")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Bypass reset
# Alarm channels are the PV  bit
# Eg: SigResetReq[0].0
# Uses Reset_Index 0 , Uses Channel 0
record(bo, "BLEN:BC2B:950:TEMP_RESET") {
  field(DESC, "Reset Request")
  field(DTYP, "EtherIP")
  #field(ASG, "MCC")
  field(OUT , "@PLC_BC2B_TM01 SigResetReq[0] B 1")
  field(ZNAM, "RESET")
  field(ONAM, "RESET")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(HIGH, "2")
  field(ASG, "MCC")
}

#
# This template is used to control MPS outputs
#
#
# Macros:
#        TYPE  Type of MPS Permit signal- eg: TEMP, FLOW etc.
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS EPICS name for the PV
#        MAD   MAD name for the PV
#==============================================================================
# Temperature PV Alarm status
# Alarm channels are the PV  bit
record(bi, "BMLN:BC2B:200:TEMP_PERMIT"){
  field(DESC, "BC2B TEMP Permit Alarm Sts")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 MPSAlarm[0] B 2")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Bypass reset
# Alarm channels are the PV  bit
# Eg: SigResetReq[0].0
# Uses Reset_Index 0 , Uses Channel 0
record(bo, "BMLN:BC2B:200:TEMP_RESET") {
  field(DESC, "Reset Request")
  field(DTYP, "EtherIP")
  #field(ASG, "MCC")
  field(OUT , "@PLC_BC2B_TM01 SigResetReq[0] B 2")
  field(ZNAM, "RESET")
  field(ONAM, "RESET")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(HIGH, "2")
  field(ASG, "MCC")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:BC2B:535:POSX:SUPPLYTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmLatch[0] B 0")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:BC2B:535:POSX:SUPPLYTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmReal[0] B 0")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:BC2B:535:POSX:SUPPLYTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_BC2B_TM01 SigBypReq[0] B 0")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:BC2B:535:POSX:SUPPLYTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigBypStat[0] B 0")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:BC2B:535:POSX:RETURNTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmLatch[0] B 1")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:BC2B:535:POSX:RETURNTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmReal[0] B 1")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:BC2B:535:POSX:RETURNTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_BC2B_TM01 SigBypReq[0] B 1")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:BC2B:535:POSX:RETURNTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigBypStat[0] B 1")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:BC2B:535:NEGX:SUPPLYTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmLatch[0] B 2")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:BC2B:535:NEGX:SUPPLYTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmReal[0] B 2")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:BC2B:535:NEGX:SUPPLYTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_BC2B_TM01 SigBypReq[0] B 2")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:BC2B:535:NEGX:SUPPLYTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigBypStat[0] B 2")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "COLL:BC2B:535:NEGX:RETURNTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmLatch[0] B 3")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "COLL:BC2B:535:NEGX:RETURNTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmReal[0] B 3")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "COLL:BC2B:535:NEGX:RETURNTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_BC2B_TM01 SigBypReq[0] B 3")
  info(autosaveFields,"VAL")
}

record(bi, "COLL:BC2B:535:NEGX:RETURNTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigBypStat[0] B 3")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "BLEN:BC2B:950:1:TEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmLatch[0] B 4")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "BLEN:BC2B:950:1:TEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmReal[0] B 4")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "BLEN:BC2B:950:1:TEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_BC2B_TM01 SigBypReq[0] B 4")
  info(autosaveFields,"VAL")
}

record(bi, "BLEN:BC2B:950:1:TEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigBypStat[0] B 4")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "BLEN:BC2B:950:2:TEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmLatch[0] B 5")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "BLEN:BC2B:950:2:TEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmReal[0] B 5")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "BLEN:BC2B:950:2:TEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_BC2B_TM01 SigBypReq[0] B 5")
  info(autosaveFields,"VAL")
}

record(bi, "BLEN:BC2B:950:2:TEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigBypStat[0] B 5")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "BLEN:BC2B:950:3:TEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmLatch[0] B 6")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "BLEN:BC2B:950:3:TEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmReal[0] B 6")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "BLEN:BC2B:950:3:TEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_BC2B_TM01 SigBypReq[0] B 6")
  info(autosaveFields,"VAL")
}

record(bi, "BLEN:BC2B:950:3:TEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigBypStat[0] B 6")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "BLEN:BC2B:950:4:TEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmLatch[0] B 7")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "BLEN:BC2B:950:4:TEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmReal[0] B 7")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "BLEN:BC2B:950:4:TEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_BC2B_TM01 SigBypReq[0] B 7")
  info(autosaveFields,"VAL")
}

record(bi, "BLEN:BC2B:950:4:TEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigBypStat[0] B 7")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "BEND:BC2B:200:1:VCHMBRTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmLatch[0] B 8")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "BEND:BC2B:200:1:VCHMBRTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmReal[0] B 8")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "BEND:BC2B:200:1:VCHMBRTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_BC2B_TM01 SigBypReq[0] B 8")
  info(autosaveFields,"VAL")
}

record(bi, "BEND:BC2B:200:1:VCHMBRTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigBypStat[0] B 8")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "BEND:BC2B:200:2:VCHMBRTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmLatch[0] B 9")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "BEND:BC2B:200:2:VCHMBRTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmReal[0] B 9")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "BEND:BC2B:200:2:VCHMBRTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_BC2B_TM01 SigBypReq[0] B 9")
  info(autosaveFields,"VAL")
}

record(bi, "BEND:BC2B:200:2:VCHMBRTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigBypStat[0] B 9")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "BEND:BC2B:500:1:VCHMBRTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmLatch[0] B 10")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "BEND:BC2B:500:1:VCHMBRTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmReal[0] B 10")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "BEND:BC2B:500:1:VCHMBRTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_BC2B_TM01 SigBypReq[0] B 10")
  info(autosaveFields,"VAL")
}

record(bi, "BEND:BC2B:500:1:VCHMBRTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigBypStat[0] B 10")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "BEND:BC2B:500:2:VCHMBRTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmLatch[0] B 11")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "BEND:BC2B:500:2:VCHMBRTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmReal[0] B 11")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "BEND:BC2B:500:2:VCHMBRTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_BC2B_TM01 SigBypReq[0] B 11")
  info(autosaveFields,"VAL")
}

record(bi, "BEND:BC2B:500:2:VCHMBRTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigBypStat[0] B 11")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "BEND:BC2B:600:1:VCHMBRTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmLatch[0] B 12")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "BEND:BC2B:600:1:VCHMBRTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmReal[0] B 12")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "BEND:BC2B:600:1:VCHMBRTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_BC2B_TM01 SigBypReq[0] B 12")
  info(autosaveFields,"VAL")
}

record(bi, "BEND:BC2B:600:1:VCHMBRTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigBypStat[0] B 12")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "BEND:BC2B:600:2:VCHMBRTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmLatch[0] B 13")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "BEND:BC2B:600:2:VCHMBRTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmReal[0] B 13")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "BEND:BC2B:600:2:VCHMBRTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_BC2B_TM01 SigBypReq[0] B 13")
  info(autosaveFields,"VAL")
}

record(bi, "BEND:BC2B:600:2:VCHMBRTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigBypStat[0] B 13")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "BEND:BC2B:900:1:VCHMBRTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmLatch[0] B 14")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "BEND:BC2B:900:1:VCHMBRTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmReal[0] B 14")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "BEND:BC2B:900:1:VCHMBRTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_BC2B_TM01 SigBypReq[0] B 14")
  info(autosaveFields,"VAL")
}

record(bi, "BEND:BC2B:900:1:VCHMBRTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigBypStat[0] B 14")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "BEND:BC2B:900:2:VCHMBRTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmLatch[0] B 15")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "BEND:BC2B:900:2:VCHMBRTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmReal[0] B 15")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "BEND:BC2B:900:2:VCHMBRTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_BC2B_TM01 SigBypReq[0] B 15")
  info(autosaveFields,"VAL")
}

record(bi, "BEND:BC2B:900:2:VCHMBRTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigBypStat[0] B 15")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "BEND:BC2B:900:3:VCHMBRTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmLatch[1] B 0")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "BEND:BC2B:900:3:VCHMBRTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmReal[1] B 0")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "BEND:BC2B:900:3:VCHMBRTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_BC2B_TM01 SigBypReq[1] B 0")
  info(autosaveFields,"VAL")
}

record(bi, "BEND:BC2B:900:3:VCHMBRTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigBypStat[1] B 0")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "BEND:BC2B:900:4:VCHMBRTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmLatch[1] B 1")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "BEND:BC2B:900:4:VCHMBRTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmReal[1] B 1")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "BEND:BC2B:900:4:VCHMBRTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_BC2B_TM01 SigBypReq[1] B 1")
  info(autosaveFields,"VAL")
}

record(bi, "BEND:BC2B:900:4:VCHMBRTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigBypStat[1] B 1")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "BEND:BC2B:900:5:VCHMBRTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmLatch[1] B 2")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "BEND:BC2B:900:5:VCHMBRTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmReal[1] B 2")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "BEND:BC2B:900:5:VCHMBRTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_BC2B_TM01 SigBypReq[1] B 2")
  info(autosaveFields,"VAL")
}

record(bi, "BEND:BC2B:900:5:VCHMBRTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigBypStat[1] B 2")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "BEND:BC2B:900:6:VCHMBRTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmLatch[1] B 3")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "BEND:BC2B:900:6:VCHMBRTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmReal[1] B 3")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "BEND:BC2B:900:6:VCHMBRTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_BC2B_TM01 SigBypReq[1] B 3")
  info(autosaveFields,"VAL")
}

record(bi, "BEND:BC2B:900:6:VCHMBRTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigBypStat[1] B 3")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "BEND:BC2B:900:7:VCHMBRTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmLatch[1] B 4")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "BEND:BC2B:900:7:VCHMBRTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmReal[1] B 4")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "BEND:BC2B:900:7:VCHMBRTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_BC2B_TM01 SigBypReq[1] B 4")
  info(autosaveFields,"VAL")
}

record(bi, "BEND:BC2B:900:7:VCHMBRTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigBypStat[1] B 4")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data for MPS interlock
#
#
# Macros:
#        CHAN              I/O channel on the I/O module
#        PLC               Name of the ether_ip connection to PLC as defined in st.cmd 
#        ALIAS             EPICS name for the PV
#        INDEX     	       Array number of SigAlarmLatch, SigAlarmReal, SigBypReq, SigBypStat
#        
#==============================================================================

# Temperature PV Alarm status
# Alarm channels are the PV  bit
# Eg: SigAlarmLatch[0].0
# Uses Index 0 , Uses Channel 0
record(bi, "BEND:BC2B:900:8:VCHMBRTEMPALMLATCH"){
  field(DESC, "Latched Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmLatch[1] B 5")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

record(bi, "BEND:BC2B:900:8:VCHMBRTEMPALM"){
  field(DESC, "Alarm Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigAlarmReal[1] B 5")
  field(ONAM, "OK")
  field(ZNAM, "FAULT")
  field(OSV, "NO_ALARM")
  field(ZSV, "MAJOR")
}

# Temperature Alarm Bypass 
# Alarm channels are the PV  bit
record(bo, "BEND:BC2B:900:8:VCHMBRTEMPBYP") {
  field(DESC, "Bypass Request")
  field(ZNAM, "NO BYPASS")
  field(ONAM, "BYPASS")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT , "@PLC_BC2B_TM01 SigBypReq[1] B 5")
  info(autosaveFields,"VAL")
}

record(bi, "BEND:BC2B:900:8:VCHMBRTEMPBYPSTAT"){
  field(DESC, "Bypass Status")
  field(SCAN, "I/O Intr")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 SigBypStat[1] B 5")
  field(ZNAM, "NOT BYPASSED")
  field(ONAM, "BYPASSED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M1_CH00_TEMP") {
  field(DESC, "Water S4 1 return us Z334m")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "WATR:LI04:1:KT:TEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[0]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M1_CH00_ALIAS") {
    field(VAL,"WATR:LI04:1:KT:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "WATR:LI04:1:KT:TEMP") {
  field(DESC, "Water S4 1 return us Z334m")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M1_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "WATR:LI04:1:KT:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[0]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "WATR:LI04:1:KT:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "WATR:LI04:1:KT:TEMP.HIHI CP")
  field(OUT, "WATR:LI04:1:KT:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"WATR:LI04:1:KT:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "WATR:LI04:1:KT:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[0]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "WATR:LI04:1:KT:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "WATR:LI04:1:KT:TEMP.LOLO CP")
  field(OUT, "WATR:LI04:1:KT:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"WATR:LI04:1:KT:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M1_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[1] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M1_CH01_TEMP") {
  field(DESC, "S4 PRL 1 Z334m")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "LLRF:BC2B:1:PRLTEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[1]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M1_CH01_ALIAS") {
    field(VAL,"LLRF:BC2B:1:PRLTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "LLRF:BC2B:1:PRLTEMP") {
  field(DESC, "S4 PRL 1 Z334m")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M1_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "LLRF:BC2B:1:PRLTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[1]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:BC2B:1:PRLTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "LLRF:BC2B:1:PRLTEMP.HIHI CP")
  field(OUT, "LLRF:BC2B:1:PRLTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:BC2B:1:PRLTEMPHLIMDES")
}

# Temperature low limit
record(ao, "LLRF:BC2B:1:PRLTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[1]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:BC2B:1:PRLTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "LLRF:BC2B:1:PRLTEMP.LOLO CP")
  field(OUT, "LLRF:BC2B:1:PRLTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:BC2B:1:PRLTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M1_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[1] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M1_CH02_TEMP") {
  field(DESC, "Air S4 1 Z334m")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ROOM:LI04:1:KT:TEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[2]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M1_CH02_ALIAS") {
    field(VAL,"ROOM:LI04:1:KT:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ROOM:LI04:1:KT:TEMP") {
  field(DESC, "Air S4 1 Z334m")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M1_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ROOM:LI04:1:KT:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[2]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI04:1:KT:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ROOM:LI04:1:KT:TEMP.HIHI CP")
  field(OUT, "ROOM:LI04:1:KT:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI04:1:KT:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "ROOM:LI04:1:KT:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[2]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI04:1:KT:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ROOM:LI04:1:KT:TEMP.LOLO CP")
  field(OUT, "ROOM:LI04:1:KT:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI04:1:KT:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M1_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[1] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M1_CH03_TEMP") {
  field(DESC, "BCX21 1")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BEND:BC2B:200:1:VCHMBRTEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[3]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M1_CH03_ALIAS") {
    field(VAL,"BEND:BC2B:200:1:VCHMBRTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BEND:BC2B:200:1:VCHMBRTEMP") {
  field(DESC, "BCX21 1")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M1_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BEND:BC2B:200:1:VCHMBRTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[3]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:200:1:VCHMBRTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BEND:BC2B:200:1:VCHMBRTEMP.HIHI CP")
  field(OUT, "BEND:BC2B:200:1:VCHMBRTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:200:1:VCHMBRTEMPHLIMDES")
}

# Temperature low limit
record(ao, "BEND:BC2B:200:1:VCHMBRTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[3]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:200:1:VCHMBRTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BEND:BC2B:200:1:VCHMBRTEMP.LOLO CP")
  field(OUT, "BEND:BC2B:200:1:VCHMBRTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:200:1:VCHMBRTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M1_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[1] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M2_CH00_TEMP") {
  field(DESC, "BCX21 2")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BEND:BC2B:200:2:VCHMBRTEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[4]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M2_CH00_ALIAS") {
    field(VAL,"BEND:BC2B:200:2:VCHMBRTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BEND:BC2B:200:2:VCHMBRTEMP") {
  field(DESC, "BCX21 2")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M2_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BEND:BC2B:200:2:VCHMBRTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[4]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:200:2:VCHMBRTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BEND:BC2B:200:2:VCHMBRTEMP.HIHI CP")
  field(OUT, "BEND:BC2B:200:2:VCHMBRTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:200:2:VCHMBRTEMPHLIMDES")
}

# Temperature low limit
record(ao, "BEND:BC2B:200:2:VCHMBRTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[4]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:200:2:VCHMBRTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BEND:BC2B:200:2:VCHMBRTEMP.LOLO CP")
  field(OUT, "BEND:BC2B:200:2:VCHMBRTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:200:2:VCHMBRTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M2_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[2] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M2_CH01_TEMP") {
  field(DESC, "Water S4 2 supply us Z334m")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "WATR:LI04:2:KT:TEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[5]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M2_CH01_ALIAS") {
    field(VAL,"WATR:LI04:2:KT:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "WATR:LI04:2:KT:TEMP") {
  field(DESC, "Water S4 2 supply us Z334m")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M2_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "WATR:LI04:2:KT:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[5]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "WATR:LI04:2:KT:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "WATR:LI04:2:KT:TEMP.HIHI CP")
  field(OUT, "WATR:LI04:2:KT:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"WATR:LI04:2:KT:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "WATR:LI04:2:KT:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[5]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "WATR:LI04:2:KT:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "WATR:LI04:2:KT:TEMP.LOLO CP")
  field(OUT, "WATR:LI04:2:KT:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"WATR:LI04:2:KT:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M2_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[2] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M2_CH02_TEMP") {
  field(DESC, "S4 PRL 2 Z334z")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "LLRF:BC2B:2:PRLTEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[6]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M2_CH02_ALIAS") {
    field(VAL,"LLRF:BC2B:2:PRLTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "LLRF:BC2B:2:PRLTEMP") {
  field(DESC, "S4 PRL 2 Z334z")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M2_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "LLRF:BC2B:2:PRLTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[6]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:BC2B:2:PRLTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "LLRF:BC2B:2:PRLTEMP.HIHI CP")
  field(OUT, "LLRF:BC2B:2:PRLTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:BC2B:2:PRLTEMPHLIMDES")
}

# Temperature low limit
record(ao, "LLRF:BC2B:2:PRLTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[6]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:BC2B:2:PRLTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "LLRF:BC2B:2:PRLTEMP.LOLO CP")
  field(OUT, "LLRF:BC2B:2:PRLTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:BC2B:2:PRLTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M2_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[2] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M2_CH03_TEMP") {
  field(DESC, "BCX22 1")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BEND:BC2B:500:1:VCHMBRTEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[7]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M2_CH03_ALIAS") {
    field(VAL,"BEND:BC2B:500:1:VCHMBRTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BEND:BC2B:500:1:VCHMBRTEMP") {
  field(DESC, "BCX22 1")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M2_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BEND:BC2B:500:1:VCHMBRTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[7]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:500:1:VCHMBRTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BEND:BC2B:500:1:VCHMBRTEMP.HIHI CP")
  field(OUT, "BEND:BC2B:500:1:VCHMBRTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:500:1:VCHMBRTEMPHLIMDES")
}

# Temperature low limit
record(ao, "BEND:BC2B:500:1:VCHMBRTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[7]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:500:1:VCHMBRTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BEND:BC2B:500:1:VCHMBRTEMP.LOLO CP")
  field(OUT, "BEND:BC2B:500:1:VCHMBRTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:500:1:VCHMBRTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M2_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[2] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M3_CH00_TEMP") {
  field(DESC, "BCX22 2")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BEND:BC2B:500:2:VCHMBRTEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[8]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M3_CH00_ALIAS") {
    field(VAL,"BEND:BC2B:500:2:VCHMBRTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BEND:BC2B:500:2:VCHMBRTEMP") {
  field(DESC, "BCX22 2")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M3_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BEND:BC2B:500:2:VCHMBRTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[8]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:500:2:VCHMBRTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BEND:BC2B:500:2:VCHMBRTEMP.HIHI CP")
  field(OUT, "BEND:BC2B:500:2:VCHMBRTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:500:2:VCHMBRTEMPHLIMDES")
}

# Temperature low limit
record(ao, "BEND:BC2B:500:2:VCHMBRTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[8]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:500:2:VCHMBRTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BEND:BC2B:500:2:VCHMBRTEMP.LOLO CP")
  field(OUT, "BEND:BC2B:500:2:VCHMBRTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:500:2:VCHMBRTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M3_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[3] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M3_CH01_TEMP") {
  field(DESC, "CE21B Temp 1")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:BC2B:535:POSX:SUPPLYTEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[9]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M3_CH01_ALIAS") {
    field(VAL,"COLL:BC2B:535:POSX:SUPPLYTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:BC2B:535:POSX:SUPPLYTEMP") {
  field(DESC, "CE21B Temp 1")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M3_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:BC2B:535:POSX:SUPPLYTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[9]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:BC2B:535:POSX:SUPPLYTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:BC2B:535:POSX:SUPPLYTEMP.HIHI CP")
  field(OUT, "COLL:BC2B:535:POSX:SUPPLYTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:BC2B:535:POSX:SUPPLYTEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:BC2B:535:POSX:SUPPLYTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[9]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:BC2B:535:POSX:SUPPLYTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:BC2B:535:POSX:SUPPLYTEMP.LOLO CP")
  field(OUT, "COLL:BC2B:535:POSX:SUPPLYTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:BC2B:535:POSX:SUPPLYTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M3_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[3] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M3_CH02_TEMP") {
  field(DESC, "CE21B Temp 2")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:BC2B:535:POSX:RETURNTEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[10]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M3_CH02_ALIAS") {
    field(VAL,"COLL:BC2B:535:POSX:RETURNTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:BC2B:535:POSX:RETURNTEMP") {
  field(DESC, "CE21B Temp 2")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M3_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:BC2B:535:POSX:RETURNTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[10]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:BC2B:535:POSX:RETURNTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:BC2B:535:POSX:RETURNTEMP.HIHI CP")
  field(OUT, "COLL:BC2B:535:POSX:RETURNTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:BC2B:535:POSX:RETURNTEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:BC2B:535:POSX:RETURNTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[10]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:BC2B:535:POSX:RETURNTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:BC2B:535:POSX:RETURNTEMP.LOLO CP")
  field(OUT, "COLL:BC2B:535:POSX:RETURNTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:BC2B:535:POSX:RETURNTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M3_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[3] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M3_CH03_TEMP") {
  field(DESC, "CE21B Temp 3")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:BC2B:535:NEGX:SUPPLYTEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[11]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M3_CH03_ALIAS") {
    field(VAL,"COLL:BC2B:535:NEGX:SUPPLYTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:BC2B:535:NEGX:SUPPLYTEMP") {
  field(DESC, "CE21B Temp 3")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M3_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:BC2B:535:NEGX:SUPPLYTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[11]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:BC2B:535:NEGX:SUPPLYTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:BC2B:535:NEGX:SUPPLYTEMP.HIHI CP")
  field(OUT, "COLL:BC2B:535:NEGX:SUPPLYTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:BC2B:535:NEGX:SUPPLYTEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:BC2B:535:NEGX:SUPPLYTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[11]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:BC2B:535:NEGX:SUPPLYTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:BC2B:535:NEGX:SUPPLYTEMP.LOLO CP")
  field(OUT, "COLL:BC2B:535:NEGX:SUPPLYTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:BC2B:535:NEGX:SUPPLYTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M3_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[3] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M4_CH00_TEMP") {
  field(DESC, "CE21B Temp 4")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "COLL:BC2B:535:NEGX:RETURNTEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[12]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M4_CH00_ALIAS") {
    field(VAL,"COLL:BC2B:535:NEGX:RETURNTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "COLL:BC2B:535:NEGX:RETURNTEMP") {
  field(DESC, "CE21B Temp 4")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M4_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "COLL:BC2B:535:NEGX:RETURNTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[12]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:BC2B:535:NEGX:RETURNTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "COLL:BC2B:535:NEGX:RETURNTEMP.HIHI CP")
  field(OUT, "COLL:BC2B:535:NEGX:RETURNTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:BC2B:535:NEGX:RETURNTEMPHLIMDES")
}

# Temperature low limit
record(ao, "COLL:BC2B:535:NEGX:RETURNTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[12]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "COLL:BC2B:535:NEGX:RETURNTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "COLL:BC2B:535:NEGX:RETURNTEMP.LOLO CP")
  field(OUT, "COLL:BC2B:535:NEGX:RETURNTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"COLL:BC2B:535:NEGX:RETURNTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M4_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[4] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M4_CH01_TEMP") {
  field(DESC, "BCX23 1")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BEND:BC2B:600:1:VCHMBRTEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[13]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M4_CH01_ALIAS") {
    field(VAL,"BEND:BC2B:600:1:VCHMBRTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BEND:BC2B:600:1:VCHMBRTEMP") {
  field(DESC, "BCX23 1")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M4_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BEND:BC2B:600:1:VCHMBRTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[13]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:600:1:VCHMBRTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BEND:BC2B:600:1:VCHMBRTEMP.HIHI CP")
  field(OUT, "BEND:BC2B:600:1:VCHMBRTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:600:1:VCHMBRTEMPHLIMDES")
}

# Temperature low limit
record(ao, "BEND:BC2B:600:1:VCHMBRTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[13]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:600:1:VCHMBRTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BEND:BC2B:600:1:VCHMBRTEMP.LOLO CP")
  field(OUT, "BEND:BC2B:600:1:VCHMBRTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:600:1:VCHMBRTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M4_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[4] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M4_CH02_TEMP") {
  field(DESC, "BCX23 2")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BEND:BC2B:600:2:VCHMBRTEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[14]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M4_CH02_ALIAS") {
    field(VAL,"BEND:BC2B:600:2:VCHMBRTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BEND:BC2B:600:2:VCHMBRTEMP") {
  field(DESC, "BCX23 2")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M4_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BEND:BC2B:600:2:VCHMBRTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[14]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:600:2:VCHMBRTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BEND:BC2B:600:2:VCHMBRTEMP.HIHI CP")
  field(OUT, "BEND:BC2B:600:2:VCHMBRTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:600:2:VCHMBRTEMPHLIMDES")
}

# Temperature low limit
record(ao, "BEND:BC2B:600:2:VCHMBRTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[14]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:600:2:VCHMBRTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BEND:BC2B:600:2:VCHMBRTEMP.LOLO CP")
  field(OUT, "BEND:BC2B:600:2:VCHMBRTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:600:2:VCHMBRTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M4_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[4] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M4_CH03_TEMP") {
  field(DESC, "BZ21B 1")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BLEN:BC2B:950:1:TEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[15]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M4_CH03_ALIAS") {
    field(VAL,"BLEN:BC2B:950:1:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BLEN:BC2B:950:1:TEMP") {
  field(DESC, "BZ21B 1")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M4_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BLEN:BC2B:950:1:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[15]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BLEN:BC2B:950:1:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BLEN:BC2B:950:1:TEMP.HIHI CP")
  field(OUT, "BLEN:BC2B:950:1:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BLEN:BC2B:950:1:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "BLEN:BC2B:950:1:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[15]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BLEN:BC2B:950:1:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BLEN:BC2B:950:1:TEMP.LOLO CP")
  field(OUT, "BLEN:BC2B:950:1:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BLEN:BC2B:950:1:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M4_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[4] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M5_CH00_TEMP") {
  field(DESC, "BZ21B 2")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BLEN:BC2B:950:2:TEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[16]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M5_CH00_ALIAS") {
    field(VAL,"BLEN:BC2B:950:2:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BLEN:BC2B:950:2:TEMP") {
  field(DESC, "BZ21B 2")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M5_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BLEN:BC2B:950:2:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[16]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BLEN:BC2B:950:2:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BLEN:BC2B:950:2:TEMP.HIHI CP")
  field(OUT, "BLEN:BC2B:950:2:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BLEN:BC2B:950:2:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "BLEN:BC2B:950:2:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[16]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BLEN:BC2B:950:2:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BLEN:BC2B:950:2:TEMP.LOLO CP")
  field(OUT, "BLEN:BC2B:950:2:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BLEN:BC2B:950:2:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M5_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[5] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M5_CH01_TEMP") {
  field(DESC, "BZ21B 3")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BLEN:BC2B:950:3:TEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[17]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M5_CH01_ALIAS") {
    field(VAL,"BLEN:BC2B:950:3:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BLEN:BC2B:950:3:TEMP") {
  field(DESC, "BZ21B 3")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M5_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BLEN:BC2B:950:3:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[17]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BLEN:BC2B:950:3:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BLEN:BC2B:950:3:TEMP.HIHI CP")
  field(OUT, "BLEN:BC2B:950:3:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BLEN:BC2B:950:3:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "BLEN:BC2B:950:3:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[17]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BLEN:BC2B:950:3:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BLEN:BC2B:950:3:TEMP.LOLO CP")
  field(OUT, "BLEN:BC2B:950:3:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BLEN:BC2B:950:3:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M5_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[5] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M5_CH02_TEMP") {
  field(DESC, "BZ21B 4")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BLEN:BC2B:950:4:TEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[18]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M5_CH02_ALIAS") {
    field(VAL,"BLEN:BC2B:950:4:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BLEN:BC2B:950:4:TEMP") {
  field(DESC, "BZ21B 4")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M5_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BLEN:BC2B:950:4:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[18]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BLEN:BC2B:950:4:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BLEN:BC2B:950:4:TEMP.HIHI CP")
  field(OUT, "BLEN:BC2B:950:4:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BLEN:BC2B:950:4:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "BLEN:BC2B:950:4:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[18]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BLEN:BC2B:950:4:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BLEN:BC2B:950:4:TEMP.LOLO CP")
  field(OUT, "BLEN:BC2B:950:4:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BLEN:BC2B:950:4:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M5_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[5] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M5_CH03_TEMP") {
  field(DESC, "BCX24 1")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BEND:BC2B:900:1:VCHMBRTEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[19]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M5_CH03_ALIAS") {
    field(VAL,"BEND:BC2B:900:1:VCHMBRTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BEND:BC2B:900:1:VCHMBRTEMP") {
  field(DESC, "BCX24 1")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M5_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "35")
  field(LOLO, "0")
  field(HIGH, "30")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BEND:BC2B:900:1:VCHMBRTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[19]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:900:1:VCHMBRTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BEND:BC2B:900:1:VCHMBRTEMP.HIHI CP")
  field(OUT, "BEND:BC2B:900:1:VCHMBRTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:900:1:VCHMBRTEMPHLIMDES")
}

# Temperature low limit
record(ao, "BEND:BC2B:900:1:VCHMBRTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[19]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:900:1:VCHMBRTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BEND:BC2B:900:1:VCHMBRTEMP.LOLO CP")
  field(OUT, "BEND:BC2B:900:1:VCHMBRTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:900:1:VCHMBRTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M5_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[5] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M6_CH00_TEMP") {
  field(DESC, "BCX24 2")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BEND:BC2B:900:2:VCHMBRTEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[20]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M6_CH00_ALIAS") {
    field(VAL,"BEND:BC2B:900:2:VCHMBRTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BEND:BC2B:900:2:VCHMBRTEMP") {
  field(DESC, "BCX24 2")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M6_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "35")
  field(LOLO, "0")
  field(HIGH, "30")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BEND:BC2B:900:2:VCHMBRTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[20]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:900:2:VCHMBRTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BEND:BC2B:900:2:VCHMBRTEMP.HIHI CP")
  field(OUT, "BEND:BC2B:900:2:VCHMBRTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:900:2:VCHMBRTEMPHLIMDES")
}

# Temperature low limit
record(ao, "BEND:BC2B:900:2:VCHMBRTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[20]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:900:2:VCHMBRTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BEND:BC2B:900:2:VCHMBRTEMP.LOLO CP")
  field(OUT, "BEND:BC2B:900:2:VCHMBRTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:900:2:VCHMBRTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M6_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[6] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M6_CH01_TEMP") {
  field(DESC, "BCX24 3")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BEND:BC2B:900:3:VCHMBRTEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[21]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M6_CH01_ALIAS") {
    field(VAL,"BEND:BC2B:900:3:VCHMBRTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BEND:BC2B:900:3:VCHMBRTEMP") {
  field(DESC, "BCX24 3")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M6_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "35")
  field(LOLO, "0")
  field(HIGH, "30")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BEND:BC2B:900:3:VCHMBRTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[21]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:900:3:VCHMBRTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BEND:BC2B:900:3:VCHMBRTEMP.HIHI CP")
  field(OUT, "BEND:BC2B:900:3:VCHMBRTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:900:3:VCHMBRTEMPHLIMDES")
}

# Temperature low limit
record(ao, "BEND:BC2B:900:3:VCHMBRTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[21]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:900:3:VCHMBRTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BEND:BC2B:900:3:VCHMBRTEMP.LOLO CP")
  field(OUT, "BEND:BC2B:900:3:VCHMBRTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:900:3:VCHMBRTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M6_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[6] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M6_CH02_TEMP") {
  field(DESC, "BCX24 4")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BEND:BC2B:900:4:VCHMBRTEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[22]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M6_CH02_ALIAS") {
    field(VAL,"BEND:BC2B:900:4:VCHMBRTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BEND:BC2B:900:4:VCHMBRTEMP") {
  field(DESC, "BCX24 4")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M6_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "35")
  field(LOLO, "0")
  field(HIGH, "30")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BEND:BC2B:900:4:VCHMBRTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[22]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:900:4:VCHMBRTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BEND:BC2B:900:4:VCHMBRTEMP.HIHI CP")
  field(OUT, "BEND:BC2B:900:4:VCHMBRTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:900:4:VCHMBRTEMPHLIMDES")
}

# Temperature low limit
record(ao, "BEND:BC2B:900:4:VCHMBRTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[22]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:900:4:VCHMBRTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BEND:BC2B:900:4:VCHMBRTEMP.LOLO CP")
  field(OUT, "BEND:BC2B:900:4:VCHMBRTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:900:4:VCHMBRTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M6_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[6] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M6_CH03_TEMP") {
  field(DESC, "BCX24 5")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BEND:BC2B:900:5:VCHMBRTEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[23]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M6_CH03_ALIAS") {
    field(VAL,"BEND:BC2B:900:5:VCHMBRTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BEND:BC2B:900:5:VCHMBRTEMP") {
  field(DESC, "BCX24 5")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M6_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "35")
  field(LOLO, "0")
  field(HIGH, "30")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BEND:BC2B:900:5:VCHMBRTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[23]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:900:5:VCHMBRTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BEND:BC2B:900:5:VCHMBRTEMP.HIHI CP")
  field(OUT, "BEND:BC2B:900:5:VCHMBRTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:900:5:VCHMBRTEMPHLIMDES")
}

# Temperature low limit
record(ao, "BEND:BC2B:900:5:VCHMBRTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[23]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:900:5:VCHMBRTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BEND:BC2B:900:5:VCHMBRTEMP.LOLO CP")
  field(OUT, "BEND:BC2B:900:5:VCHMBRTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:900:5:VCHMBRTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M6_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[6] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M7_CH00_TEMP") {
  field(DESC, "BCX24 6")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BEND:BC2B:900:6:VCHMBRTEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[24]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M7_CH00_ALIAS") {
    field(VAL,"BEND:BC2B:900:6:VCHMBRTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BEND:BC2B:900:6:VCHMBRTEMP") {
  field(DESC, "BCX24 6")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M7_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "35")
  field(LOLO, "0")
  field(HIGH, "30")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BEND:BC2B:900:6:VCHMBRTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[24]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:900:6:VCHMBRTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BEND:BC2B:900:6:VCHMBRTEMP.HIHI CP")
  field(OUT, "BEND:BC2B:900:6:VCHMBRTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:900:6:VCHMBRTEMPHLIMDES")
}

# Temperature low limit
record(ao, "BEND:BC2B:900:6:VCHMBRTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[24]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:900:6:VCHMBRTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BEND:BC2B:900:6:VCHMBRTEMP.LOLO CP")
  field(OUT, "BEND:BC2B:900:6:VCHMBRTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:900:6:VCHMBRTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M7_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[7] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M7_CH01_TEMP") {
  field(DESC, "BCX24 7")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BEND:BC2B:900:7:VCHMBRTEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[25]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M7_CH01_ALIAS") {
    field(VAL,"BEND:BC2B:900:7:VCHMBRTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BEND:BC2B:900:7:VCHMBRTEMP") {
  field(DESC, "BCX24 7")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M7_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "35")
  field(LOLO, "0")
  field(HIGH, "30")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BEND:BC2B:900:7:VCHMBRTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[25]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:900:7:VCHMBRTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BEND:BC2B:900:7:VCHMBRTEMP.HIHI CP")
  field(OUT, "BEND:BC2B:900:7:VCHMBRTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:900:7:VCHMBRTEMPHLIMDES")
}

# Temperature low limit
record(ao, "BEND:BC2B:900:7:VCHMBRTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[25]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:900:7:VCHMBRTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BEND:BC2B:900:7:VCHMBRTEMP.LOLO CP")
  field(OUT, "BEND:BC2B:900:7:VCHMBRTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:900:7:VCHMBRTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M7_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[7] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M7_CH02_TEMP") {
  field(DESC, "BCX24 8")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "BEND:BC2B:900:8:VCHMBRTEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[26]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M7_CH02_ALIAS") {
    field(VAL,"BEND:BC2B:900:8:VCHMBRTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "BEND:BC2B:900:8:VCHMBRTEMP") {
  field(DESC, "BCX24 8")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M7_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "35")
  field(LOLO, "0")
  field(HIGH, "30")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "BEND:BC2B:900:8:VCHMBRTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[26]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:900:8:VCHMBRTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "BEND:BC2B:900:8:VCHMBRTEMP.HIHI CP")
  field(OUT, "BEND:BC2B:900:8:VCHMBRTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:900:8:VCHMBRTEMPHLIMDES")
}

# Temperature low limit
record(ao, "BEND:BC2B:900:8:VCHMBRTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[26]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "BEND:BC2B:900:8:VCHMBRTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "BEND:BC2B:900:8:VCHMBRTEMP.LOLO CP")
  field(OUT, "BEND:BC2B:900:8:VCHMBRTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"BEND:BC2B:900:8:VCHMBRTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M7_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[7] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M7_CH03_TEMP") {
  field(DESC, "Water S4 3 return ds Z381m")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "WATR:LI04:3:KT:TEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[27]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M7_CH03_ALIAS") {
    field(VAL,"WATR:LI04:3:KT:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "WATR:LI04:3:KT:TEMP") {
  field(DESC, "Water S4 3 return ds Z381m")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M7_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "WATR:LI04:3:KT:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[27]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "WATR:LI04:3:KT:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "WATR:LI04:3:KT:TEMP.HIHI CP")
  field(OUT, "WATR:LI04:3:KT:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"WATR:LI04:3:KT:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "WATR:LI04:3:KT:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[27]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "WATR:LI04:3:KT:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "WATR:LI04:3:KT:TEMP.LOLO CP")
  field(OUT, "WATR:LI04:3:KT:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"WATR:LI04:3:KT:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M7_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[7] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M8_CH00_TEMP") {
  field(DESC, "S4 PRL 3 Z364m")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "LLRF:EMIT2:1:PRLTEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[28]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M8_CH00_ALIAS") {
    field(VAL,"LLRF:EMIT2:1:PRLTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "LLRF:EMIT2:1:PRLTEMP") {
  field(DESC, "S4 PRL 3 Z364m")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M8_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "LLRF:EMIT2:1:PRLTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[28]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:EMIT2:1:PRLTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "LLRF:EMIT2:1:PRLTEMP.HIHI CP")
  field(OUT, "LLRF:EMIT2:1:PRLTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:EMIT2:1:PRLTEMPHLIMDES")
}

# Temperature low limit
record(ao, "LLRF:EMIT2:1:PRLTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[28]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:EMIT2:1:PRLTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "LLRF:EMIT2:1:PRLTEMP.LOLO CP")
  field(OUT, "LLRF:EMIT2:1:PRLTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:EMIT2:1:PRLTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M8_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[8] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M8_CH01_TEMP") {
  field(DESC, "WSEMIT2 RTD")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "WIRE:EMIT2:600:TEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[29]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M8_CH01_ALIAS") {
    field(VAL,"WIRE:EMIT2:600:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "WIRE:EMIT2:600:TEMP") {
  field(DESC, "WSEMIT2 RTD")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M8_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "WIRE:EMIT2:600:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[29]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "WIRE:EMIT2:600:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "WIRE:EMIT2:600:TEMP.HIHI CP")
  field(OUT, "WIRE:EMIT2:600:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"WIRE:EMIT2:600:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "WIRE:EMIT2:600:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[29]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "WIRE:EMIT2:600:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "WIRE:EMIT2:600:TEMP.LOLO CP")
  field(OUT, "WIRE:EMIT2:600:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"WIRE:EMIT2:600:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M8_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[8] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M8_CH02_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:01:M8_CH2_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[30]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M8_CH02_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:01:M8_CH2_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:01:M8_CH2_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M8_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:01:M8_CH2_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[30]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:01:M8_CH2_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:01:M8_CH2_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:01:M8_CH2_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:01:M8_CH2_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:01:M8_CH2_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[30]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:01:M8_CH2_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:01:M8_CH2_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:01:M8_CH2_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:01:M8_CH2_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M8_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[8] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M8_CH03_TEMP") {
  field(DESC, "Air S4 2 Z374m")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ROOM:LI04:2:KT:TEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[31]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M8_CH03_ALIAS") {
    field(VAL,"ROOM:LI04:2:KT:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ROOM:LI04:2:KT:TEMP") {
  field(DESC, "Air S4 2 Z374m")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M8_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ROOM:LI04:2:KT:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[31]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI04:2:KT:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ROOM:LI04:2:KT:TEMP.HIHI CP")
  field(OUT, "ROOM:LI04:2:KT:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI04:2:KT:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "ROOM:LI04:2:KT:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[31]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI04:2:KT:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ROOM:LI04:2:KT:TEMP.LOLO CP")
  field(OUT, "ROOM:LI04:2:KT:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI04:2:KT:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M8_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[8] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M9_CH00_TEMP") {
  field(DESC, "Water S4 4 supply ds Z381m")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "WATR:LI04:4:KT:TEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[32]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M9_CH00_ALIAS") {
    field(VAL,"WATR:LI04:4:KT:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "WATR:LI04:4:KT:TEMP") {
  field(DESC, "Water S4 4 supply ds Z381m")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M9_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "1.1")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "WATR:LI04:4:KT:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[32]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "WATR:LI04:4:KT:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "WATR:LI04:4:KT:TEMP.HIHI CP")
  field(OUT, "WATR:LI04:4:KT:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"WATR:LI04:4:KT:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "WATR:LI04:4:KT:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[32]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "WATR:LI04:4:KT:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "WATR:LI04:4:KT:TEMP.LOLO CP")
  field(OUT, "WATR:LI04:4:KT:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"WATR:LI04:4:KT:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M9_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[9] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M9_CH01_TEMP") {
  field(DESC, "S4 PRL 4 Z374m")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "LLRF:EMIT2:2:PRLTEMP")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[33]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M9_CH01_ALIAS") {
    field(VAL,"LLRF:EMIT2:2:PRLTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "LLRF:EMIT2:2:PRLTEMP") {
  field(DESC, "S4 PRL 4 Z374m")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M9_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "LLRF:EMIT2:2:PRLTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[33]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:EMIT2:2:PRLTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "LLRF:EMIT2:2:PRLTEMP.HIHI CP")
  field(OUT, "LLRF:EMIT2:2:PRLTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:EMIT2:2:PRLTEMPHLIMDES")
}

# Temperature low limit
record(ao, "LLRF:EMIT2:2:PRLTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[33]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:EMIT2:2:PRLTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "LLRF:EMIT2:2:PRLTEMP.LOLO CP")
  field(OUT, "LLRF:EMIT2:2:PRLTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:EMIT2:2:PRLTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M9_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[9] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M9_CH02_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:01:M9_CH2_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[34]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M9_CH02_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:01:M9_CH2_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:01:M9_CH2_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M9_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:01:M9_CH2_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[34]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:01:M9_CH2_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:01:M9_CH2_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:01:M9_CH2_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:01:M9_CH2_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:01:M9_CH2_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[34]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:01:M9_CH2_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:01:M9_CH2_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:01:M9_CH2_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:01:M9_CH2_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M9_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[9] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR01_M9_CH03_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:01:M9_CH3_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR01_Temp[35]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR01_M9_CH03_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:01:M9_CH3_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:01:M9_CH3_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR01_M9_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:01:M9_CH3_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_HiTemp[35]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:01:M9_CH3_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:01:M9_CH3_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:01:M9_CH3_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:01:M9_CH3_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:01:M9_CH3_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR01_LoTemp[35]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:01:M9_CH3_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:01:M9_CH3_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:01:M9_CH3_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:01:M9_CH3_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR01_M9_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR01_Ch_Faults[9] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR02_M1_CH00_TEMP") {
  field(DESC, "Alcove S4  Air")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ROOM:LI04:1:KA:TEMP")
  field(INP , "@PLC_BC2B_TM01 CR02_Temp[0]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR02_M1_CH00_ALIAS") {
    field(VAL,"ROOM:LI04:1:KA:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ROOM:LI04:1:KA:TEMP") {
  field(DESC, "Alcove S4  Air")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR02_M1_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ROOM:LI04:1:KA:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_HiTemp[0]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI04:1:KA:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ROOM:LI04:1:KA:TEMP.HIHI CP")
  field(OUT, "ROOM:LI04:1:KA:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI04:1:KA:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "ROOM:LI04:1:KA:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_LoTemp[0]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI04:1:KA:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ROOM:LI04:1:KA:TEMP.LOLO CP")
  field(OUT, "ROOM:LI04:1:KA:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI04:1:KA:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR02_M1_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR02_Ch_Faults[1] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR02_M1_CH01_TEMP") {
  field(DESC, "Gallery S4 Air")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ROOM:LI04:1:KG:TEMP")
  field(INP , "@PLC_BC2B_TM01 CR02_Temp[1]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR02_M1_CH01_ALIAS") {
    field(VAL,"ROOM:LI04:1:KG:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ROOM:LI04:1:KG:TEMP") {
  field(DESC, "Gallery S4 Air")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR02_M1_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ROOM:LI04:1:KG:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_HiTemp[1]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI04:1:KG:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ROOM:LI04:1:KG:TEMP.HIHI CP")
  field(OUT, "ROOM:LI04:1:KG:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI04:1:KG:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "ROOM:LI04:1:KG:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_LoTemp[1]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI04:1:KG:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ROOM:LI04:1:KG:TEMP.LOLO CP")
  field(OUT, "ROOM:LI04:1:KG:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI04:1:KG:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR02_M1_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR02_Ch_Faults[1] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR02_M1_CH02_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:02:M1_CH2_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR02_Temp[2]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR02_M1_CH02_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:02:M1_CH2_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:02:M1_CH2_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR02_M1_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:02:M1_CH2_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_HiTemp[2]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:02:M1_CH2_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:02:M1_CH2_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:02:M1_CH2_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:02:M1_CH2_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:02:M1_CH2_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_LoTemp[2]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:02:M1_CH2_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:02:M1_CH2_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:02:M1_CH2_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:02:M1_CH2_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR02_M1_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR02_Ch_Faults[1] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR02_M1_CH03_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:02:M1_CH3_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR02_Temp[3]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR02_M1_CH03_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:02:M1_CH3_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:02:M1_CH3_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR02_M1_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:02:M1_CH3_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_HiTemp[3]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:02:M1_CH3_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:02:M1_CH3_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:02:M1_CH3_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:02:M1_CH3_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:02:M1_CH3_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_LoTemp[3]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:02:M1_CH3_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:02:M1_CH3_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:02:M1_CH3_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:02:M1_CH3_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR02_M1_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR02_Ch_Faults[1] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR02_M2_CH00_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:02:M2_CH0_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR02_Temp[4]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR02_M2_CH00_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:02:M2_CH0_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:02:M2_CH0_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR02_M2_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:02:M2_CH0_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_HiTemp[4]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:02:M2_CH0_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:02:M2_CH0_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:02:M2_CH0_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:02:M2_CH0_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:02:M2_CH0_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_LoTemp[4]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:02:M2_CH0_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:02:M2_CH0_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:02:M2_CH0_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:02:M2_CH0_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR02_M2_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR02_Ch_Faults[2] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR02_M2_CH01_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:02:M2_CH1_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR02_Temp[5]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR02_M2_CH01_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:02:M2_CH1_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:02:M2_CH1_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR02_M2_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:02:M2_CH1_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_HiTemp[5]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:02:M2_CH1_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:02:M2_CH1_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:02:M2_CH1_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:02:M2_CH1_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:02:M2_CH1_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_LoTemp[5]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:02:M2_CH1_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:02:M2_CH1_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:02:M2_CH1_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:02:M2_CH1_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR02_M2_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR02_Ch_Faults[2] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR02_M2_CH02_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:02:M2_CH2_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR02_Temp[6]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR02_M2_CH02_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:02:M2_CH2_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:02:M2_CH2_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR02_M2_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:02:M2_CH2_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_HiTemp[6]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:02:M2_CH2_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:02:M2_CH2_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:02:M2_CH2_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:02:M2_CH2_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:02:M2_CH2_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_LoTemp[6]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:02:M2_CH2_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:02:M2_CH2_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:02:M2_CH2_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:02:M2_CH2_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR02_M2_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR02_Ch_Faults[2] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR02_M2_CH03_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:02:M2_CH3_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR02_Temp[7]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR02_M2_CH03_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:02:M2_CH3_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:02:M2_CH3_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR02_M2_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:02:M2_CH3_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_HiTemp[7]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:02:M2_CH3_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:02:M2_CH3_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:02:M2_CH3_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:02:M2_CH3_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:02:M2_CH3_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_LoTemp[7]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:02:M2_CH3_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:02:M2_CH3_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:02:M2_CH3_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:02:M2_CH3_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR02_M2_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR02_Ch_Faults[2] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR02_M3_CH00_TEMP") {
  field(DESC, "PEN 4-1 1")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L2B:1410:P0401:Temp1")
  field(INP , "@PLC_BC2B_TM01 CR02_Temp[8]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR02_M3_CH00_ALIAS") {
    field(VAL,"ACCL:L2B:1410:P0401:Temp1")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L2B:1410:P0401:Temp1") {
  field(DESC, "PEN 4-1 1")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR02_M3_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L2B:1410:P0401:Temp1HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_HiTemp[8]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L2B:1410:P0401:Temp1HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L2B:1410:P0401:Temp1.HIHI CP")
  field(OUT, "ACCL:L2B:1410:P0401:Temp1HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L2B:1410:P0401:Temp1HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L2B:1410:P0401:Temp1LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_LoTemp[8]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L2B:1410:P0401:Temp1LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L2B:1410:P0401:Temp1.LOLO CP")
  field(OUT, "ACCL:L2B:1410:P0401:Temp1LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L2B:1410:P0401:Temp1LLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR02_M3_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR02_Ch_Faults[3] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR02_M3_CH01_TEMP") {
  field(DESC, "PEN 4-1 2")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L2B:1410:P0401:Temp2")
  field(INP , "@PLC_BC2B_TM01 CR02_Temp[9]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR02_M3_CH01_ALIAS") {
    field(VAL,"ACCL:L2B:1410:P0401:Temp2")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L2B:1410:P0401:Temp2") {
  field(DESC, "PEN 4-1 2")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR02_M3_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L2B:1410:P0401:Temp2HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_HiTemp[9]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L2B:1410:P0401:Temp2HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L2B:1410:P0401:Temp2.HIHI CP")
  field(OUT, "ACCL:L2B:1410:P0401:Temp2HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L2B:1410:P0401:Temp2HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L2B:1410:P0401:Temp2LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_LoTemp[9]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L2B:1410:P0401:Temp2LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L2B:1410:P0401:Temp2.LOLO CP")
  field(OUT, "ACCL:L2B:1410:P0401:Temp2LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L2B:1410:P0401:Temp2LLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR02_M3_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR02_Ch_Faults[3] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR02_M3_CH02_TEMP") {
  field(DESC, "PEN 4-1 3")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L2B:1410:P0401:Temp3")
  field(INP , "@PLC_BC2B_TM01 CR02_Temp[10]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR02_M3_CH02_ALIAS") {
    field(VAL,"ACCL:L2B:1410:P0401:Temp3")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L2B:1410:P0401:Temp3") {
  field(DESC, "PEN 4-1 3")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR02_M3_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L2B:1410:P0401:Temp3HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_HiTemp[10]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L2B:1410:P0401:Temp3HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L2B:1410:P0401:Temp3.HIHI CP")
  field(OUT, "ACCL:L2B:1410:P0401:Temp3HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L2B:1410:P0401:Temp3HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L2B:1410:P0401:Temp3LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_LoTemp[10]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L2B:1410:P0401:Temp3LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L2B:1410:P0401:Temp3.LOLO CP")
  field(OUT, "ACCL:L2B:1410:P0401:Temp3LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L2B:1410:P0401:Temp3LLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR02_M3_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR02_Ch_Faults[3] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR02_M3_CH03_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:02:M3_CH3_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR02_Temp[11]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR02_M3_CH03_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:02:M3_CH3_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:02:M3_CH3_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR02_M3_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:02:M3_CH3_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_HiTemp[11]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:02:M3_CH3_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:02:M3_CH3_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:02:M3_CH3_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:02:M3_CH3_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:02:M3_CH3_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_LoTemp[11]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:02:M3_CH3_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:02:M3_CH3_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:02:M3_CH3_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:02:M3_CH3_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR02_M3_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR02_Ch_Faults[3] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR02_M4_CH00_TEMP") {
  field(DESC, "PEN 4-2 1")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L2B:1450:P0402:Temp1")
  field(INP , "@PLC_BC2B_TM01 CR02_Temp[12]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR02_M4_CH00_ALIAS") {
    field(VAL,"ACCL:L2B:1450:P0402:Temp1")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L2B:1450:P0402:Temp1") {
  field(DESC, "PEN 4-2 1")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR02_M4_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L2B:1450:P0402:Temp1HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_HiTemp[12]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L2B:1450:P0402:Temp1HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L2B:1450:P0402:Temp1.HIHI CP")
  field(OUT, "ACCL:L2B:1450:P0402:Temp1HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L2B:1450:P0402:Temp1HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L2B:1450:P0402:Temp1LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_LoTemp[12]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L2B:1450:P0402:Temp1LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L2B:1450:P0402:Temp1.LOLO CP")
  field(OUT, "ACCL:L2B:1450:P0402:Temp1LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L2B:1450:P0402:Temp1LLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR02_M4_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR02_Ch_Faults[4] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR02_M4_CH01_TEMP") {
  field(DESC, "PEN 4-2 2")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L2B:1450:P0402:Temp2")
  field(INP , "@PLC_BC2B_TM01 CR02_Temp[13]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR02_M4_CH01_ALIAS") {
    field(VAL,"ACCL:L2B:1450:P0402:Temp2")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L2B:1450:P0402:Temp2") {
  field(DESC, "PEN 4-2 2")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR02_M4_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L2B:1450:P0402:Temp2HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_HiTemp[13]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L2B:1450:P0402:Temp2HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L2B:1450:P0402:Temp2.HIHI CP")
  field(OUT, "ACCL:L2B:1450:P0402:Temp2HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L2B:1450:P0402:Temp2HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L2B:1450:P0402:Temp2LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_LoTemp[13]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L2B:1450:P0402:Temp2LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L2B:1450:P0402:Temp2.LOLO CP")
  field(OUT, "ACCL:L2B:1450:P0402:Temp2LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L2B:1450:P0402:Temp2LLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR02_M4_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR02_Ch_Faults[4] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR02_M4_CH02_TEMP") {
  field(DESC, "PEN 4-2 3")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L2B:1450:P0402:Temp3")
  field(INP , "@PLC_BC2B_TM01 CR02_Temp[14]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR02_M4_CH02_ALIAS") {
    field(VAL,"ACCL:L2B:1450:P0402:Temp3")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L2B:1450:P0402:Temp3") {
  field(DESC, "PEN 4-2 3")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR02_M4_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L2B:1450:P0402:Temp3HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_HiTemp[14]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L2B:1450:P0402:Temp3HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L2B:1450:P0402:Temp3.HIHI CP")
  field(OUT, "ACCL:L2B:1450:P0402:Temp3HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L2B:1450:P0402:Temp3HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L2B:1450:P0402:Temp3LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_LoTemp[14]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L2B:1450:P0402:Temp3LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L2B:1450:P0402:Temp3.LOLO CP")
  field(OUT, "ACCL:L2B:1450:P0402:Temp3LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L2B:1450:P0402:Temp3LLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR02_M4_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR02_Ch_Faults[4] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR02_M4_CH03_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:02:M4_CH3_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR02_Temp[15]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR02_M4_CH03_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:02:M4_CH3_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:02:M4_CH3_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR02_M4_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:02:M4_CH3_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_HiTemp[15]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:02:M4_CH3_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:02:M4_CH3_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:02:M4_CH3_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:02:M4_CH3_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:02:M4_CH3_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR02_LoTemp[15]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:02:M4_CH3_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:02:M4_CH3_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:02:M4_CH3_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:02:M4_CH3_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR02_M4_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR02_Ch_Faults[4] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M1_CH00_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:01:M1_CH0_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[0]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M1_CH00_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:01:M1_CH0_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:01:M1_CH0_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M1_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:01:M1_CH0_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[0]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:01:M1_CH0_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:01:M1_CH0_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:01:M1_CH0_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:01:M1_CH0_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:01:M1_CH0_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[0]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:01:M1_CH0_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:01:M1_CH0_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:01:M1_CH0_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:01:M1_CH0_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M1_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[1] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M1_CH01_TEMP") {
  field(DESC, "S5 PRL 1 Z413z")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "LLRF:L3B:1:PRLTEMP")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[1]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M1_CH01_ALIAS") {
    field(VAL,"LLRF:L3B:1:PRLTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "LLRF:L3B:1:PRLTEMP") {
  field(DESC, "S5 PRL 1 Z413z")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M1_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "LLRF:L3B:1:PRLTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[1]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:L3B:1:PRLTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "LLRF:L3B:1:PRLTEMP.HIHI CP")
  field(OUT, "LLRF:L3B:1:PRLTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:L3B:1:PRLTEMPHLIMDES")
}

# Temperature low limit
record(ao, "LLRF:L3B:1:PRLTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[1]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:L3B:1:PRLTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "LLRF:L3B:1:PRLTEMP.LOLO CP")
  field(OUT, "LLRF:L3B:1:PRLTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:L3B:1:PRLTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M1_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[1] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M1_CH02_TEMP") {
  field(DESC, "Air S5 1 Z432m")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ROOM:LI05:1:KT:TEMP")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[2]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M1_CH02_ALIAS") {
    field(VAL,"ROOM:LI05:1:KT:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ROOM:LI05:1:KT:TEMP") {
  field(DESC, "Air S5 1 Z432m")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M1_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ROOM:LI05:1:KT:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[2]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI05:1:KT:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ROOM:LI05:1:KT:TEMP.HIHI CP")
  field(OUT, "ROOM:LI05:1:KT:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI05:1:KT:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "ROOM:LI05:1:KT:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[2]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI05:1:KT:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ROOM:LI05:1:KT:TEMP.LOLO CP")
  field(OUT, "ROOM:LI05:1:KT:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI05:1:KT:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M1_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[1] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M1_CH03_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:01:M1_CH3_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[3]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M1_CH03_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:01:M1_CH3_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:01:M1_CH3_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M1_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:01:M1_CH3_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[3]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:01:M1_CH3_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:01:M1_CH3_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:01:M1_CH3_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:01:M1_CH3_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:01:M1_CH3_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[3]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:01:M1_CH3_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:01:M1_CH3_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:01:M1_CH3_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:01:M1_CH3_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M1_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[1] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M2_CH00_TEMP") {
  field(DESC, "S5 PRL 2 Z439z")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "LLRF:L3B:2:PRLTEMP")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[4]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M2_CH00_ALIAS") {
    field(VAL,"LLRF:L3B:2:PRLTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "LLRF:L3B:2:PRLTEMP") {
  field(DESC, "S5 PRL 2 Z439z")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M2_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "LLRF:L3B:2:PRLTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[4]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:L3B:2:PRLTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "LLRF:L3B:2:PRLTEMP.HIHI CP")
  field(OUT, "LLRF:L3B:2:PRLTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:L3B:2:PRLTEMPHLIMDES")
}

# Temperature low limit
record(ao, "LLRF:L3B:2:PRLTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[4]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:L3B:2:PRLTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "LLRF:L3B:2:PRLTEMP.LOLO CP")
  field(OUT, "LLRF:L3B:2:PRLTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:L3B:2:PRLTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M2_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[2] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M2_CH01_TEMP") {
  field(DESC, "S5 PRL 3 Z465z")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "LLRF:L3B:3:PRLTEMP")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[5]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M2_CH01_ALIAS") {
    field(VAL,"LLRF:L3B:3:PRLTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "LLRF:L3B:3:PRLTEMP") {
  field(DESC, "S5 PRL 3 Z465z")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M2_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "LLRF:L3B:3:PRLTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[5]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:L3B:3:PRLTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "LLRF:L3B:3:PRLTEMP.HIHI CP")
  field(OUT, "LLRF:L3B:3:PRLTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:L3B:3:PRLTEMPHLIMDES")
}

# Temperature low limit
record(ao, "LLRF:L3B:3:PRLTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[5]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:L3B:3:PRLTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "LLRF:L3B:3:PRLTEMP.LOLO CP")
  field(OUT, "LLRF:L3B:3:PRLTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:L3B:3:PRLTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M2_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[2] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M2_CH02_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:01:M2_CH2_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[6]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M2_CH02_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:01:M2_CH2_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:01:M2_CH2_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M2_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:01:M2_CH2_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[6]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:01:M2_CH2_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:01:M2_CH2_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:01:M2_CH2_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:01:M2_CH2_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:01:M2_CH2_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[6]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:01:M2_CH2_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:01:M2_CH2_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:01:M2_CH2_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:01:M2_CH2_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M2_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[2] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M2_CH03_TEMP") {
  field(DESC, "Air S5 2 Z481m")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ROOM:LI05:2:KT:TEMP")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[7]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M2_CH03_ALIAS") {
    field(VAL,"ROOM:LI05:2:KT:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ROOM:LI05:2:KT:TEMP") {
  field(DESC, "Air S5 2 Z481m")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M2_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ROOM:LI05:2:KT:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[7]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI05:2:KT:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ROOM:LI05:2:KT:TEMP.HIHI CP")
  field(OUT, "ROOM:LI05:2:KT:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI05:2:KT:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "ROOM:LI05:2:KT:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[7]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI05:2:KT:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ROOM:LI05:2:KT:TEMP.LOLO CP")
  field(OUT, "ROOM:LI05:2:KT:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI05:2:KT:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M2_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[2] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M3_CH00_TEMP") {
  field(DESC, "S5 PRL 4 Z488z")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "LLRF:L3B:4:PRLTEMP")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[8]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M3_CH00_ALIAS") {
    field(VAL,"LLRF:L3B:4:PRLTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "LLRF:L3B:4:PRLTEMP") {
  field(DESC, "S5 PRL 4 Z488z")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M3_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "LLRF:L3B:4:PRLTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[8]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:L3B:4:PRLTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "LLRF:L3B:4:PRLTEMP.HIHI CP")
  field(OUT, "LLRF:L3B:4:PRLTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:L3B:4:PRLTEMPHLIMDES")
}

# Temperature low limit
record(ao, "LLRF:L3B:4:PRLTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[8]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:L3B:4:PRLTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "LLRF:L3B:4:PRLTEMP.LOLO CP")
  field(OUT, "LLRF:L3B:4:PRLTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:L3B:4:PRLTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M3_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[3] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M3_CH01_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:03:M3_CH1_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[9]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M3_CH01_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:03:M3_CH1_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:03:M3_CH1_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M3_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:03:M3_CH1_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[9]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:03:M3_CH1_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:03:M3_CH1_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:03:M3_CH1_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:03:M3_CH1_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:03:M3_CH1_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[9]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:03:M3_CH1_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:03:M3_CH1_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:03:M3_CH1_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:03:M3_CH1_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M3_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[3] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M3_CH02_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:03:M3_CH2_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[10]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M3_CH02_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:03:M3_CH2_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:03:M3_CH2_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M3_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:03:M3_CH2_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[10]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:03:M3_CH2_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:03:M3_CH2_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:03:M3_CH2_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:03:M3_CH2_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:03:M3_CH2_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[10]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:03:M3_CH2_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:03:M3_CH2_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:03:M3_CH2_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:03:M3_CH2_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M3_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[3] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M3_CH03_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:03:M3_CH3_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[11]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M3_CH03_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:03:M3_CH3_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:03:M3_CH3_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M3_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:03:M3_CH3_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[11]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:03:M3_CH3_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:03:M3_CH3_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:03:M3_CH3_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:03:M3_CH3_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:03:M3_CH3_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[11]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:03:M3_CH3_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:03:M3_CH3_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:03:M3_CH3_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:03:M3_CH3_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M3_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[3] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M4_CH00_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:03:M4_CH0_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[12]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M4_CH00_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:03:M4_CH0_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:03:M4_CH0_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M4_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:03:M4_CH0_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[12]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:03:M4_CH0_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:03:M4_CH0_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:03:M4_CH0_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:03:M4_CH0_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:03:M4_CH0_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[12]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:03:M4_CH0_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:03:M4_CH0_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:03:M4_CH0_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:03:M4_CH0_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M4_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[4] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M4_CH01_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:03:M4_CH1_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[13]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M4_CH01_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:03:M4_CH1_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:03:M4_CH1_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M4_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:03:M4_CH1_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[13]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:03:M4_CH1_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:03:M4_CH1_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:03:M4_CH1_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:03:M4_CH1_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:03:M4_CH1_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[13]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:03:M4_CH1_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:03:M4_CH1_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:03:M4_CH1_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:03:M4_CH1_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M4_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[4] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M4_CH02_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:03:M4_CH2_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[14]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M4_CH02_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:03:M4_CH2_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:03:M4_CH2_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M4_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:03:M4_CH2_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[14]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:03:M4_CH2_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:03:M4_CH2_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:03:M4_CH2_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:03:M4_CH2_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:03:M4_CH2_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[14]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:03:M4_CH2_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:03:M4_CH2_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:03:M4_CH2_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:03:M4_CH2_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M4_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[4] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M4_CH03_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:03:M4_CH3_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[15]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M4_CH03_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:03:M4_CH3_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:03:M4_CH3_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M4_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:03:M4_CH3_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[15]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:03:M4_CH3_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:03:M4_CH3_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:03:M4_CH3_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:03:M4_CH3_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:03:M4_CH3_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[15]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:03:M4_CH3_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:03:M4_CH3_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:03:M4_CH3_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:03:M4_CH3_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M4_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[4] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M5_CH00_TEMP") {
  field(DESC, "PEN 5-1 1")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L3B:1710:P0501:Temp1")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[16]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M5_CH00_ALIAS") {
    field(VAL,"ACCL:L3B:1710:P0501:Temp1")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L3B:1710:P0501:Temp1") {
  field(DESC, "PEN 5-1 1")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M5_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L3B:1710:P0501:Temp1HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[16]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L3B:1710:P0501:Temp1HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L3B:1710:P0501:Temp1.HIHI CP")
  field(OUT, "ACCL:L3B:1710:P0501:Temp1HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L3B:1710:P0501:Temp1HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L3B:1710:P0501:Temp1LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[16]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L3B:1710:P0501:Temp1LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L3B:1710:P0501:Temp1.LOLO CP")
  field(OUT, "ACCL:L3B:1710:P0501:Temp1LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L3B:1710:P0501:Temp1LLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M5_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[5] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M5_CH01_TEMP") {
  field(DESC, "PEN 5-1 2")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L3B:1710:P0501:Temp2")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[17]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M5_CH01_ALIAS") {
    field(VAL,"ACCL:L3B:1710:P0501:Temp2")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L3B:1710:P0501:Temp2") {
  field(DESC, "PEN 5-1 2")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M5_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L3B:1710:P0501:Temp2HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[17]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L3B:1710:P0501:Temp2HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L3B:1710:P0501:Temp2.HIHI CP")
  field(OUT, "ACCL:L3B:1710:P0501:Temp2HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L3B:1710:P0501:Temp2HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L3B:1710:P0501:Temp2LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[17]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L3B:1710:P0501:Temp2LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L3B:1710:P0501:Temp2.LOLO CP")
  field(OUT, "ACCL:L3B:1710:P0501:Temp2LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L3B:1710:P0501:Temp2LLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M5_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[5] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M5_CH02_TEMP") {
  field(DESC, "PEN 5-1 3")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L3B:1710:P0501:Temp3")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[18]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M5_CH02_ALIAS") {
    field(VAL,"ACCL:L3B:1710:P0501:Temp3")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L3B:1710:P0501:Temp3") {
  field(DESC, "PEN 5-1 3")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M5_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L3B:1710:P0501:Temp3HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[18]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L3B:1710:P0501:Temp3HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L3B:1710:P0501:Temp3.HIHI CP")
  field(OUT, "ACCL:L3B:1710:P0501:Temp3HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L3B:1710:P0501:Temp3HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L3B:1710:P0501:Temp3LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[18]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L3B:1710:P0501:Temp3LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L3B:1710:P0501:Temp3.LOLO CP")
  field(OUT, "ACCL:L3B:1710:P0501:Temp3LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L3B:1710:P0501:Temp3LLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M5_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[5] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M5_CH03_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:03:M5_CH3_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[19]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M5_CH03_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:03:M5_CH3_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:03:M5_CH3_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M5_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:03:M5_CH3_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[19]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:03:M5_CH3_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:03:M5_CH3_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:03:M5_CH3_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:03:M5_CH3_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:03:M5_CH3_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[19]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:03:M5_CH3_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:03:M5_CH3_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:03:M5_CH3_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:03:M5_CH3_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M5_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[5] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M6_CH00_TEMP") {
  field(DESC, "PEN 5-2 1")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L3B:1750:P0502:Temp1")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[20]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M6_CH00_ALIAS") {
    field(VAL,"ACCL:L3B:1750:P0502:Temp1")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L3B:1750:P0502:Temp1") {
  field(DESC, "PEN 5-2 1")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M6_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L3B:1750:P0502:Temp1HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[20]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L3B:1750:P0502:Temp1HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L3B:1750:P0502:Temp1.HIHI CP")
  field(OUT, "ACCL:L3B:1750:P0502:Temp1HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L3B:1750:P0502:Temp1HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L3B:1750:P0502:Temp1LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[20]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L3B:1750:P0502:Temp1LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L3B:1750:P0502:Temp1.LOLO CP")
  field(OUT, "ACCL:L3B:1750:P0502:Temp1LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L3B:1750:P0502:Temp1LLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M6_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[6] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M6_CH01_TEMP") {
  field(DESC, "PEN 5-2 2")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L3B:1750:P0502:Temp2")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[21]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M6_CH01_ALIAS") {
    field(VAL,"ACCL:L3B:1750:P0502:Temp2")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L3B:1750:P0502:Temp2") {
  field(DESC, "PEN 5-2 2")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M6_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L3B:1750:P0502:Temp2HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[21]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L3B:1750:P0502:Temp2HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L3B:1750:P0502:Temp2.HIHI CP")
  field(OUT, "ACCL:L3B:1750:P0502:Temp2HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L3B:1750:P0502:Temp2HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L3B:1750:P0502:Temp2LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[21]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L3B:1750:P0502:Temp2LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L3B:1750:P0502:Temp2.LOLO CP")
  field(OUT, "ACCL:L3B:1750:P0502:Temp2LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L3B:1750:P0502:Temp2LLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M6_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[6] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M6_CH02_TEMP") {
  field(DESC, "PEN 5-2 3")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L3B:1750:P0502:Temp3")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[22]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M6_CH02_ALIAS") {
    field(VAL,"ACCL:L3B:1750:P0502:Temp3")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L3B:1750:P0502:Temp3") {
  field(DESC, "PEN 5-2 3")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M6_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L3B:1750:P0502:Temp3HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[22]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L3B:1750:P0502:Temp3HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L3B:1750:P0502:Temp3.HIHI CP")
  field(OUT, "ACCL:L3B:1750:P0502:Temp3HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L3B:1750:P0502:Temp3HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L3B:1750:P0502:Temp3LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[22]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L3B:1750:P0502:Temp3LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L3B:1750:P0502:Temp3.LOLO CP")
  field(OUT, "ACCL:L3B:1750:P0502:Temp3LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L3B:1750:P0502:Temp3LLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M6_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[6] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M6_CH03_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:03:M6_CH3_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[23]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M6_CH03_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:03:M6_CH3_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:03:M6_CH3_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M6_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:03:M6_CH3_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[23]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:03:M6_CH3_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:03:M6_CH3_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:03:M6_CH3_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:03:M6_CH3_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:03:M6_CH3_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[23]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:03:M6_CH3_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:03:M6_CH3_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:03:M6_CH3_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:03:M6_CH3_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M6_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[6] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M7_CH00_TEMP") {
  field(DESC, "Alcove S5 Air")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ROOM:LI05:1:KA:TEMP")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[24]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M7_CH00_ALIAS") {
    field(VAL,"ROOM:LI05:1:KA:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ROOM:LI05:1:KA:TEMP") {
  field(DESC, "Alcove S5 Air")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M7_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ROOM:LI05:1:KA:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[24]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI05:1:KA:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ROOM:LI05:1:KA:TEMP.HIHI CP")
  field(OUT, "ROOM:LI05:1:KA:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI05:1:KA:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "ROOM:LI05:1:KA:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[24]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI05:1:KA:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ROOM:LI05:1:KA:TEMP.LOLO CP")
  field(OUT, "ROOM:LI05:1:KA:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI05:1:KA:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M7_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[7] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M7_CH01_TEMP") {
  field(DESC, "Gallery S5 Air")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ROOM:LI05:1:KG:TEMP")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[25]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M7_CH01_ALIAS") {
    field(VAL,"ROOM:LI05:1:KG:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ROOM:LI05:1:KG:TEMP") {
  field(DESC, "Gallery S5 Air")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M7_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ROOM:LI05:1:KG:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[25]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI05:1:KG:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ROOM:LI05:1:KG:TEMP.HIHI CP")
  field(OUT, "ROOM:LI05:1:KG:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI05:1:KG:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "ROOM:LI05:1:KG:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[25]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI05:1:KG:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ROOM:LI05:1:KG:TEMP.LOLO CP")
  field(OUT, "ROOM:LI05:1:KG:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI05:1:KG:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M7_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[7] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M7_CH02_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:03:M7_CH2_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[26]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M7_CH02_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:03:M7_CH2_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:03:M7_CH2_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M7_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:03:M7_CH2_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[26]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:03:M7_CH2_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:03:M7_CH2_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:03:M7_CH2_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:03:M7_CH2_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:03:M7_CH2_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[26]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:03:M7_CH2_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:03:M7_CH2_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:03:M7_CH2_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:03:M7_CH2_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M7_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[7] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR03_M7_CH03_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:03:M7_CH3_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR03_Temp[27]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR03_M7_CH03_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:03:M7_CH3_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:03:M7_CH3_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR03_M7_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:03:M7_CH3_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_HiTemp[27]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:03:M7_CH3_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:03:M7_CH3_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:03:M7_CH3_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:03:M7_CH3_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:03:M7_CH3_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR03_LoTemp[27]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:03:M7_CH3_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:03:M7_CH3_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:03:M7_CH3_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:03:M7_CH3_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR03_M7_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR03_Ch_Faults[7] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M1_CH00_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:04:M1_CH0_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[0]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M1_CH00_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:04:M1_CH0_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:04:M1_CH0_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M1_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:04:M1_CH0_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[0]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M1_CH0_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:04:M1_CH0_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:04:M1_CH0_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M1_CH0_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:04:M1_CH0_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[0]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M1_CH0_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:04:M1_CH0_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:04:M1_CH0_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M1_CH0_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M1_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[1] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M1_CH01_TEMP") {
  field(DESC, "S6 PRL 1 Z515z")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "LLRF:L3B:5:PRLTEMP")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[1]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M1_CH01_ALIAS") {
    field(VAL,"LLRF:L3B:5:PRLTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "LLRF:L3B:5:PRLTEMP") {
  field(DESC, "S6 PRL 1 Z515z")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M1_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "LLRF:L3B:5:PRLTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[1]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:L3B:5:PRLTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "LLRF:L3B:5:PRLTEMP.HIHI CP")
  field(OUT, "LLRF:L3B:5:PRLTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:L3B:5:PRLTEMPHLIMDES")
}

# Temperature low limit
record(ao, "LLRF:L3B:5:PRLTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[1]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:L3B:5:PRLTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "LLRF:L3B:5:PRLTEMP.LOLO CP")
  field(OUT, "LLRF:L3B:5:PRLTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:L3B:5:PRLTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M1_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[1] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M1_CH02_TEMP") {
  field(DESC, "Air S6 1 Z534m")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ROOM:LI06:1:KT:TEMP")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[2]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M1_CH02_ALIAS") {
    field(VAL,"ROOM:LI06:1:KT:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ROOM:LI06:1:KT:TEMP") {
  field(DESC, "Air S6 1 Z534m")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M1_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ROOM:LI06:1:KT:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[2]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI06:1:KT:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ROOM:LI06:1:KT:TEMP.HIHI CP")
  field(OUT, "ROOM:LI06:1:KT:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI06:1:KT:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "ROOM:LI06:1:KT:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[2]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI06:1:KT:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ROOM:LI06:1:KT:TEMP.LOLO CP")
  field(OUT, "ROOM:LI06:1:KT:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI06:1:KT:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M1_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[1] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M1_CH03_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:04:M1_CH3_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[3]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M1_CH03_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:04:M1_CH3_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:04:M1_CH3_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M1_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:04:M1_CH3_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[3]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M1_CH3_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:04:M1_CH3_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:04:M1_CH3_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M1_CH3_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:04:M1_CH3_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[3]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M1_CH3_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:04:M1_CH3_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:04:M1_CH3_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M1_CH3_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M1_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[1] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M2_CH00_TEMP") {
  field(DESC, "S6 PRL 2 Z540z")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "LLRF:L3B:6:PRLTEMP")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[4]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M2_CH00_ALIAS") {
    field(VAL,"LLRF:L3B:6:PRLTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "LLRF:L3B:6:PRLTEMP") {
  field(DESC, "S6 PRL 2 Z540z")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M2_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "LLRF:L3B:6:PRLTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[4]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:L3B:6:PRLTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "LLRF:L3B:6:PRLTEMP.HIHI CP")
  field(OUT, "LLRF:L3B:6:PRLTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:L3B:6:PRLTEMPHLIMDES")
}

# Temperature low limit
record(ao, "LLRF:L3B:6:PRLTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[4]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:L3B:6:PRLTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "LLRF:L3B:6:PRLTEMP.LOLO CP")
  field(OUT, "LLRF:L3B:6:PRLTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:L3B:6:PRLTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M2_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[2] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M2_CH01_TEMP") {
  field(DESC, "S6 PRL 3 Z564z")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "LLRF:L3B:7:PRLTEMP")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[5]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M2_CH01_ALIAS") {
    field(VAL,"LLRF:L3B:7:PRLTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "LLRF:L3B:7:PRLTEMP") {
  field(DESC, "S6 PRL 3 Z564z")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M2_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "LLRF:L3B:7:PRLTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[5]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:L3B:7:PRLTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "LLRF:L3B:7:PRLTEMP.HIHI CP")
  field(OUT, "LLRF:L3B:7:PRLTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:L3B:7:PRLTEMPHLIMDES")
}

# Temperature low limit
record(ao, "LLRF:L3B:7:PRLTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[5]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:L3B:7:PRLTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "LLRF:L3B:7:PRLTEMP.LOLO CP")
  field(OUT, "LLRF:L3B:7:PRLTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:L3B:7:PRLTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M2_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[2] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M2_CH02_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:04:M2_CH2_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[6]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M2_CH02_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:04:M2_CH2_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:04:M2_CH2_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M2_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:04:M2_CH2_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[6]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M2_CH2_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:04:M2_CH2_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:04:M2_CH2_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M2_CH2_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:04:M2_CH2_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[6]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M2_CH2_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:04:M2_CH2_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:04:M2_CH2_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M2_CH2_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M2_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[2] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M2_CH03_TEMP") {
  field(DESC, "Air S6 2 Z583m")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ROOM:LI06:2:KT:TEMP")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[7]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M2_CH03_ALIAS") {
    field(VAL,"ROOM:LI06:2:KT:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ROOM:LI06:2:KT:TEMP") {
  field(DESC, "Air S6 2 Z583m")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M2_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ROOM:LI06:2:KT:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[7]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI06:2:KT:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ROOM:LI06:2:KT:TEMP.HIHI CP")
  field(OUT, "ROOM:LI06:2:KT:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI06:2:KT:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "ROOM:LI06:2:KT:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[7]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI06:2:KT:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ROOM:LI06:2:KT:TEMP.LOLO CP")
  field(OUT, "ROOM:LI06:2:KT:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI06:2:KT:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M2_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[2] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M3_CH00_TEMP") {
  field(DESC, "S6 PRL 4 Z589z")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "LLRF:L3B:8:PRLTEMP")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[8]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M3_CH00_ALIAS") {
    field(VAL,"LLRF:L3B:8:PRLTEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "LLRF:L3B:8:PRLTEMP") {
  field(DESC, "S6 PRL 4 Z589z")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M3_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "LLRF:L3B:8:PRLTEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[8]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:L3B:8:PRLTEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "LLRF:L3B:8:PRLTEMP.HIHI CP")
  field(OUT, "LLRF:L3B:8:PRLTEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:L3B:8:PRLTEMPHLIMDES")
}

# Temperature low limit
record(ao, "LLRF:L3B:8:PRLTEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[8]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "LLRF:L3B:8:PRLTEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "LLRF:L3B:8:PRLTEMP.LOLO CP")
  field(OUT, "LLRF:L3B:8:PRLTEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"LLRF:L3B:8:PRLTEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M3_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[3] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M3_CH01_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:04:M3_CH1_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[9]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M3_CH01_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:04:M3_CH1_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:04:M3_CH1_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M3_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:04:M3_CH1_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[9]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M3_CH1_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:04:M3_CH1_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:04:M3_CH1_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M3_CH1_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:04:M3_CH1_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[9]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M3_CH1_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:04:M3_CH1_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:04:M3_CH1_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M3_CH1_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M3_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[3] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M3_CH02_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:04:M3_CH2_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[10]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M3_CH02_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:04:M3_CH2_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:04:M3_CH2_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M3_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:04:M3_CH2_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[10]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M3_CH2_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:04:M3_CH2_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:04:M3_CH2_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M3_CH2_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:04:M3_CH2_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[10]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M3_CH2_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:04:M3_CH2_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:04:M3_CH2_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M3_CH2_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M3_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[3] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M3_CH03_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:04:M3_CH3_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[11]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M3_CH03_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:04:M3_CH3_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:04:M3_CH3_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M3_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:04:M3_CH3_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[11]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M3_CH3_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:04:M3_CH3_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:04:M3_CH3_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M3_CH3_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:04:M3_CH3_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[11]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M3_CH3_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:04:M3_CH3_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:04:M3_CH3_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M3_CH3_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M3_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[3] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M4_CH00_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:04:M4_CH0_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[12]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M4_CH00_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:04:M4_CH0_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:04:M4_CH0_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M4_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:04:M4_CH0_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[12]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M4_CH0_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:04:M4_CH0_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:04:M4_CH0_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M4_CH0_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:04:M4_CH0_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[12]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M4_CH0_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:04:M4_CH0_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:04:M4_CH0_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M4_CH0_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M4_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[4] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M4_CH01_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:04:M4_CH1_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[13]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M4_CH01_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:04:M4_CH1_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:04:M4_CH1_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M4_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:04:M4_CH1_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[13]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M4_CH1_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:04:M4_CH1_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:04:M4_CH1_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M4_CH1_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:04:M4_CH1_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[13]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M4_CH1_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:04:M4_CH1_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:04:M4_CH1_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M4_CH1_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M4_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[4] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M4_CH02_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:04:M4_CH2_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[14]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M4_CH02_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:04:M4_CH2_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:04:M4_CH2_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M4_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:04:M4_CH2_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[14]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M4_CH2_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:04:M4_CH2_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:04:M4_CH2_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M4_CH2_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:04:M4_CH2_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[14]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M4_CH2_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:04:M4_CH2_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:04:M4_CH2_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M4_CH2_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M4_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[4] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M4_CH03_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:04:M4_CH3_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[15]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M4_CH03_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:04:M4_CH3_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:04:M4_CH3_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M4_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:04:M4_CH3_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[15]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M4_CH3_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:04:M4_CH3_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:04:M4_CH3_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M4_CH3_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:04:M4_CH3_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[15]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M4_CH3_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:04:M4_CH3_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:04:M4_CH3_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M4_CH3_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M4_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[4] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M5_CH00_TEMP") {
  field(DESC, "PEN 6-1 1")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L3B:2510:P0601:Temp1")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[16]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M5_CH00_ALIAS") {
    field(VAL,"ACCL:L3B:2510:P0601:Temp1")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L3B:2510:P0601:Temp1") {
  field(DESC, "PEN 6-1 1")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M5_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L3B:2510:P0601:Temp1HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[16]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L3B:2510:P0601:Temp1HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L3B:2510:P0601:Temp1.HIHI CP")
  field(OUT, "ACCL:L3B:2510:P0601:Temp1HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L3B:2510:P0601:Temp1HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L3B:2510:P0601:Temp1LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[16]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L3B:2510:P0601:Temp1LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L3B:2510:P0601:Temp1.LOLO CP")
  field(OUT, "ACCL:L3B:2510:P0601:Temp1LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L3B:2510:P0601:Temp1LLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M5_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[5] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M5_CH01_TEMP") {
  field(DESC, "PEN 6-1 2")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L3B:2510:P0601:Temp2")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[17]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M5_CH01_ALIAS") {
    field(VAL,"ACCL:L3B:2510:P0601:Temp2")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L3B:2510:P0601:Temp2") {
  field(DESC, "PEN 6-1 2")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M5_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L3B:2510:P0601:Temp2HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[17]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L3B:2510:P0601:Temp2HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L3B:2510:P0601:Temp2.HIHI CP")
  field(OUT, "ACCL:L3B:2510:P0601:Temp2HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L3B:2510:P0601:Temp2HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L3B:2510:P0601:Temp2LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[17]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L3B:2510:P0601:Temp2LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L3B:2510:P0601:Temp2.LOLO CP")
  field(OUT, "ACCL:L3B:2510:P0601:Temp2LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L3B:2510:P0601:Temp2LLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M5_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[5] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M5_CH02_TEMP") {
  field(DESC, "PEN 6-1 3")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L3B:2510:P0601:Temp3")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[18]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M5_CH02_ALIAS") {
    field(VAL,"ACCL:L3B:2510:P0601:Temp3")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L3B:2510:P0601:Temp3") {
  field(DESC, "PEN 6-1 3")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M5_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L3B:2510:P0601:Temp3HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[18]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L3B:2510:P0601:Temp3HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L3B:2510:P0601:Temp3.HIHI CP")
  field(OUT, "ACCL:L3B:2510:P0601:Temp3HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L3B:2510:P0601:Temp3HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L3B:2510:P0601:Temp3LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[18]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L3B:2510:P0601:Temp3LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L3B:2510:P0601:Temp3.LOLO CP")
  field(OUT, "ACCL:L3B:2510:P0601:Temp3LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L3B:2510:P0601:Temp3LLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M5_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[5] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M5_CH03_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:04:M5_CH3_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[19]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M5_CH03_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:04:M5_CH3_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:04:M5_CH3_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M5_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:04:M5_CH3_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[19]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M5_CH3_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:04:M5_CH3_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:04:M5_CH3_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M5_CH3_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:04:M5_CH3_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[19]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M5_CH3_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:04:M5_CH3_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:04:M5_CH3_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M5_CH3_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M5_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[5] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M6_CH00_TEMP") {
  field(DESC, "PEN 6-2 1")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L3B:2550:P0602:Temp1")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[20]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M6_CH00_ALIAS") {
    field(VAL,"ACCL:L3B:2550:P0602:Temp1")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L3B:2550:P0602:Temp1") {
  field(DESC, "PEN 6-2 1")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M6_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L3B:2550:P0602:Temp1HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[20]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L3B:2550:P0602:Temp1HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L3B:2550:P0602:Temp1.HIHI CP")
  field(OUT, "ACCL:L3B:2550:P0602:Temp1HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L3B:2550:P0602:Temp1HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L3B:2550:P0602:Temp1LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[20]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L3B:2550:P0602:Temp1LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L3B:2550:P0602:Temp1.LOLO CP")
  field(OUT, "ACCL:L3B:2550:P0602:Temp1LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L3B:2550:P0602:Temp1LLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M6_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[6] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M6_CH01_TEMP") {
  field(DESC, "PEN 6-2 2")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L3B:2550:P0602:Temp2")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[21]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M6_CH01_ALIAS") {
    field(VAL,"ACCL:L3B:2550:P0602:Temp2")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L3B:2550:P0602:Temp2") {
  field(DESC, "PEN 6-2 2")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M6_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L3B:2550:P0602:Temp2HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[21]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L3B:2550:P0602:Temp2HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L3B:2550:P0602:Temp2.HIHI CP")
  field(OUT, "ACCL:L3B:2550:P0602:Temp2HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L3B:2550:P0602:Temp2HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L3B:2550:P0602:Temp2LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[21]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L3B:2550:P0602:Temp2LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L3B:2550:P0602:Temp2.LOLO CP")
  field(OUT, "ACCL:L3B:2550:P0602:Temp2LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L3B:2550:P0602:Temp2LLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M6_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[6] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M6_CH02_TEMP") {
  field(DESC, "PEN 6-2 3")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ACCL:L3B:2550:P0602:Temp3")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[22]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M6_CH02_ALIAS") {
    field(VAL,"ACCL:L3B:2550:P0602:Temp3")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ACCL:L3B:2550:P0602:Temp3") {
  field(DESC, "PEN 6-2 3")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M6_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "45")
  field(LOLO, "0")
  field(HIGH, "40")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ACCL:L3B:2550:P0602:Temp3HLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[22]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L3B:2550:P0602:Temp3HLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ACCL:L3B:2550:P0602:Temp3.HIHI CP")
  field(OUT, "ACCL:L3B:2550:P0602:Temp3HLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L3B:2550:P0602:Temp3HLIMDES")
}

# Temperature low limit
record(ao, "ACCL:L3B:2550:P0602:Temp3LLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[22]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ACCL:L3B:2550:P0602:Temp3LLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ACCL:L3B:2550:P0602:Temp3.LOLO CP")
  field(OUT, "ACCL:L3B:2550:P0602:Temp3LLIMDES")
  field(CALC, "A")
  field(FLNK,"ACCL:L3B:2550:P0602:Temp3LLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M6_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[6] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M6_CH03_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:04:M6_CH3_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[23]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M6_CH03_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:04:M6_CH3_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:04:M6_CH3_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M6_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:04:M6_CH3_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[23]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M6_CH3_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:04:M6_CH3_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:04:M6_CH3_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M6_CH3_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:04:M6_CH3_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[23]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M6_CH3_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:04:M6_CH3_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:04:M6_CH3_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M6_CH3_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M6_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[6] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M7_CH00_TEMP") {
  field(DESC, "Alcove S6 Air")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ROOM:LI06:1:KA:TEMP")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[24]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M7_CH00_ALIAS") {
    field(VAL,"ROOM:LI06:1:KA:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ROOM:LI06:1:KA:TEMP") {
  field(DESC, "Alcove S6 Air")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M7_CH00_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ROOM:LI06:1:KA:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[24]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI06:1:KA:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ROOM:LI06:1:KA:TEMP.HIHI CP")
  field(OUT, "ROOM:LI06:1:KA:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI06:1:KA:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "ROOM:LI06:1:KA:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[24]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI06:1:KA:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ROOM:LI06:1:KA:TEMP.LOLO CP")
  field(OUT, "ROOM:LI06:1:KA:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI06:1:KA:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M7_CH00_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[7] B 00")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M7_CH01_TEMP") {
  field(DESC, "Gallery S6 Air")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "ROOM:LI06:1:KG:TEMP")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[25]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M7_CH01_ALIAS") {
    field(VAL,"ROOM:LI06:1:KG:TEMP")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "ROOM:LI06:1:KG:TEMP") {
  field(DESC, "Gallery S6 Air")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M7_CH01_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "ROOM:LI06:1:KG:TEMPHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[25]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI06:1:KG:TEMPHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "ROOM:LI06:1:KG:TEMP.HIHI CP")
  field(OUT, "ROOM:LI06:1:KG:TEMPHLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI06:1:KG:TEMPHLIMDES")
}

# Temperature low limit
record(ao, "ROOM:LI06:1:KG:TEMPLLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[25]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "ROOM:LI06:1:KG:TEMPLLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "ROOM:LI06:1:KG:TEMP.LOLO CP")
  field(OUT, "ROOM:LI06:1:KG:TEMPLLIMDES")
  field(CALC, "A")
  field(FLNK,"ROOM:LI06:1:KG:TEMPLLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M7_CH01_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[7] B 01")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M7_CH02_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:04:M7_CH2_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[26]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M7_CH02_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:04:M7_CH2_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:04:M7_CH2_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M7_CH02_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:04:M7_CH2_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[26]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M7_CH2_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:04:M7_CH2_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:04:M7_CH2_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M7_CH2_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:04:M7_CH2_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[26]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M7_CH2_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:04:M7_CH2_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:04:M7_CH2_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M7_CH2_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M7_CH02_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[7] B 02")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
#
# This template is used to monitor and control data from a 
# 5069-IY4 is a analog 4 channel input module that monitors a RTD  Sensor
#
#
# Macros:
#        LOCA  The sector/area in the accelerator where the sensors are present  
#        UNIT  The PLC/ IOC instance of the subsystem    
#        CR    Crate/panel number 
#        SLOT  I/O module location on the panel
#        CHAN  I/O channel on the I/O module
#        PLC   Name of the ether_ip connection to PLC as defined in st.cmd 
#        INDEX index of the array from PLC where the the data will be read out of
#        DESC  EPICS PV description
#        ALIAS EPICS name for the PV
#        EGU   Engineering units
#        H     High operating range
#        L     Low operating range
#        HH    High alarm limit
#        LL    Low alarm limit
#        HI    High warning limit
#        LO    Low warning limit
#        HY    Alarm deadband.signal hovering at limit not generate many alarm
#        AD    Archiver deadband
#        MO    Monitor deadband
#==============================================================================

#Holds raw sensor readback
record(ai, "PLC:BC2B:TM01:CR04_M7_CH03_TEMP") {
  field(DESC, "Spare")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:BC2B:TM01:04:M7_CH3_SPARE")
  field(INP , "@PLC_BC2B_TM01 CR04_Temp[27]")
  #PLC will read -200 if sensor is physically disconnected
  field(LOW, "-200")
  field(LSV, "INVALID")
  field(PREC, "2")
}

#Holds mapping between  PLC channel,slot and alias
record(stringout, "PLC:BC2B:TM01:CR04_M7_CH03_ALIAS") {
    field(VAL,"PLC:BC2B:TM01:04:M7_CH3_SPARE")
    field(PINI,"YES")
}

#Temperature PV for user
record(ai, "PLC:BC2B:TM01:04:M7_CH3_SPARE") {
  field(DESC, "Spare")
  field(PREC, "2")
  field(INP, "PLC:BC2B:TM01:CR04_M7_CH03_TEMP CA MS")
  field(EGU, "DegC")
  field(HOPR, "300")
  field(LOPR, "-20")
  field(HIHI, "60")
  field(LOLO, "0")
  field(HIGH, "50")
  field(LOW, "5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(HYST, "0.5")
  field(ADEL, ".001")
  field(MDEL, ".001")
  field(PINI,"YES")
}

# Temperature high limit
record(ao, "PLC:BC2B:TM01:04:M7_CH3_SPAREHLIMDES"){
  field(DESC, "Desired high limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_HiTemp[27]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M7_CH3_SPAREHLIMCALC"){
  field(DESC, "Desired high limit") 
  field(INPA, "PLC:BC2B:TM01:04:M7_CH3_SPARE.HIHI CP")
  field(OUT, "PLC:BC2B:TM01:04:M7_CH3_SPAREHLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M7_CH3_SPAREHLIMDES")
}

# Temperature low limit
record(ao, "PLC:BC2B:TM01:04:M7_CH3_SPARELLIMDES"){
  field(DESC, "Desired low  limit") 
  field(DTYP, "EtherIP")
  field(ASG, "MCC")
  field(OUT, "@PLC_BC2B_TM01 CR04_LoTemp[27]")
  field(DRVH, 200)
  field(DRVL, -20)
  field(EGU, "DegC")
  field(PREC, "2")
}

record(calcout, "PLC:BC2B:TM01:04:M7_CH3_SPARELLIMCALC"){
  field(DESC, "Desired low  limit") 
  field(INPA, "PLC:BC2B:TM01:04:M7_CH3_SPARE.LOLO CP")
  field(OUT, "PLC:BC2B:TM01:04:M7_CH3_SPARELLIMDES")
  field(CALC, "A")
  field(FLNK,"PLC:BC2B:TM01:04:M7_CH3_SPARELLIMDES")
}

# RTD status
record(bi, "PLC:BC2B:TM01:CR04_M7_CH03_FAULT") {
  field(DESC, "Status")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP , "@PLC_BC2B_TM01 CR04_Ch_Faults[7] B 03")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}
