# # This template is used to control MPS outputs # # # Macros: # TYPE Type of MPS Permit signal- eg: TEMP, FLOW etc. # CHAN I/O channel on the I/O module # PLC Name of the ether_ip connection to PLC as defined in st.cmd # ALIAS EPICS name for the PV # MAD MAD name for the PV #============================================================================== # Temperature PV Alarm status # Alarm channels are the PV bit record(bi, "${ALIAS}${TYPE}_PERMIT"){ field(DESC, "${MAD} ${TYPE} Permit Alarm Sts") field(SCAN, "I/O Intr") field(DTYP, "EtherIP") field(INP , "@$(PLC) MPSAlarm[${INDEX}] B $(CHAN)") field(ONAM, "OK") field(ZNAM, "FAULT") field(OSV, "NO_ALARM") field(ZSV, "MAJOR") } # Temperature Bypass reset # Alarm channels are the PV bit # Eg: SigResetReq[0].0 # Uses Reset_Index 0 , Uses Channel 0 record(bo, "${ALIAS}${TYPE}_RESET") { field(DESC, "Reset Request") field(DTYP, "EtherIP") field(OUT , "@$(PLC) SigResetReq[${INDEX}] B $(CHAN)") field(ZNAM, "RESET") field(ONAM, "RESET") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") field(HIGH, "2") }