record(ai, "STAT:$(STATION):PMS:TIMEOUT_THRESH"){ field(DESC, "Timeout Threshold Seconds") field(VAL, 3600) } record(calc, "STAT:$(STATION):PMS:TIMEOUT_CNT") { field(DESC, "Counts number of timeouts from station") field(SCAN, "1 second") field(INPA, "RADM:SITE:$(STATION):CH01:MEAS.SEVR") field(INPB, "RADM:SITE:$(STATION):GAMMA_DOSE_RATE.SEVR") #if invalid increment count otherwise let it be field(CALC, "(A=3||B=3) ? VAL + 1 : VAL ") field(HIGH, 6) field(HIHI, 3600) field(HSV,MINOR) field(HHSV,MAJOR) field(VAL, 0) } record(calcout, "STAT:$(STATION):PMS:TIMER"){ field(DESC, "Timer for timeout counter") field(SCAN, "1 second") field(INPA, "STAT:$(STATION):PMS:TIMEOUT_THRESH") field(VAL, 0) field(CALC, "(VAL + 1) % A") field(OOPT, "Transition To Zero") field(OUT , "STAT:$(STATION):PMS:TIMEOUT_CNT") } record(calcout, "STAT:$(STATION):PMS:CALC_SUM") { field(DESC, "Calc's overall station status") field(SCAN, "1 second") field(CALC, "A || B || C") field(INPA, "RADM:SITE:$(STATION):CH01:STATUS MS") field(INPB, "RADM:SITE:$(STATION):GAMMA_FAULT_SYS.RVAL MS") #field(INPC, "PDU:$(STATION):PMS:GETSTATUS.STAT MS") field(INPC, "RADM:SITE:$(STATION):STATUS_SYS MS") field(OUT, "STAT:$(STATION):PMS:SUMMARY PP MS") field(IVOA, "Set output to IVOV") field(IVOV, "1") } record(bo, "STAT:$(STATION):PMS:SUMMARY") { field(ZNAM, "Okay") field(ONAM, "Not Okay") field(OSV, "MAJOR") }