#--- Device info ------------------------ record(stringout, "RADM:BSYH:843:LOCATION") { field(DESC, "Device location") field(VAL, "BSYH D2") field(PINI, "1") } record(mbbo, "RADM:BSYH:843:TYPE") { field(DESC, "Device type") field(ZRVL, "0") field(ZRST, "Thermo FHT") field(ONVL, "1") field(ONST, "RadFET") field(TWVL, "2") field(TWST, "Air Mon Sys") field(THVL, "3") field(THST, "Periphal Mon Sys") field(VAL, "0") field(PINI, "1") } #--- Device parameters ----------------------------------- record(stringin, "RADM:BSYH:843:DEV_SN") { field(DESC, "Serial number") field(DTYP, "asynOctetRead") field(INP, "@asyn(FHT_BSYH_843 0) SN") field(SCAN, "I/O Intr") } record(stringin, "RADM:BSYH:843:DEV_FW") { field(DESC, "Firmware") field(DTYP, "asynOctetRead") field(INP, "@asyn(FHT_BSYH_843 0) FW") field(SCAN, "I/O Intr") } record(stringin, "RADM:BSYH:843:DEV_TYPE") { field(DESC, "Device type") field(DTYP, "asynOctetRead") field(INP, "@asyn(FHT_BSYH_843 0) DEV_TYPE") field(SCAN, "I/O Intr") } record(stringin, "RADM:BSYH:843:DEV_TIME") { field(DESC, "Date and time from device") field(DTYP, "asynOctetRead") field(INP, "@asyn(FHT_BSYH_843 0) DEV_TIME") field(SCAN, "I/O Intr") field(FLNK, "RADM:BSYH:843:INT_TIME") } record(longin, "RADM:BSYH:843:INT_TIME") { field(DESC, "Integer time") field(INP, "RADM:BSYH:843:DEV_TIME") } record(longin, "RADM:BSYH:843:DEV_ADDR") { field(DESC, "Device address") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843 0) DEV_ADDR") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:DEV_POLL_INT") { field(DESC, "Data polling interval") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843 0) POLL_INT") field(EGU, "s") field(SCAN, "I/O Intr") } record(longout, "RADM:BSYH:843:DEV_POLL_I_S") { field(DESC, "Set data polling int.") field(DTYP, "asynInt32") field(OUT, "@asyn(FHT_BSYH_843 0) POLL_INT") field(EGU, "s") info(asyn:READBACK, "1") } #--- Status ----------------------------------- record(longin, "RADM:BSYH:843:STATUS_SYS") { field(DESC, "System status") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843 0) STATUS_SYS") field(SCAN, "I/O Intr") } #--- Channel ----------------------------------- record(bi, "RADM:BSYH:843:CH_MODE") { field(DESC, "Channel mode") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843 0) CHAN_MODE") field(ZNAM, "Multi-channel") field(ONAM, "Single channel") field(SCAN, "I/O Intr") } record(bo, "RADM:BSYH:843:CH_READ_ALL") { field(DESC, "Read all channels") field(DTYP, "asynInt32") field(OUT, "@asyn(FHT_BSYH_843 0) CHAN_READALL") field(ZNAM, "No") field(ONAM, "Yes") field(ZSV, "MINOR") field(PINI, "1") field(VAL, "1") info(autosaveFields, "VAL") } record(longin, "RADM:BSYH:843:CH_CHAN") { field(DESC, "Single channel mode: channel") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843 0) CHAN_CHAN") field(SCAN, "I/O Intr") } #--- Misc. ----------------------------------- record(bo, "RADM:BSYH:843:HW_RESET") { field(DESC, "Hardware reset") field(DTYP, "asynInt32") field(OUT, "@asyn(FHT_BSYH_843 0) HW_RESET") } #--- Chan. 01 -------------------------------- # This record is the Nth channel's measured value. Units depend on the particular # probe and are set in the USERUNITS record below record(ai, "RADM:BSYH:843:CH01:MEAS") { field(DESC, "Meas. value, ch. 01") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 1, 0) MEAS") field(EGU, "") field(PREC, "3") field(LOLO, "") field(LOW, "") field(HIGH, "") field(HIHI, "") field(HYST, "0.5") field(LLSV, "NO_ALARM") field(LSV, "NO_ALARM") field(HSV, "MINOR") field(HHSV, "MAJOR") field(SCAN, "I/O Intr") info(autosaveFields, "LOLO LOW HIGH HIHI HYST LLSV LSV HSV HHSV") } record(longin, "RADM:BSYH:843:CH01:STATUS") { field(DESC, "Meas. val. status, ch. 01") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 1, 0) MEAS_STATUS") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH01:STATE") { field(DESC, "Channel state, ch. 01") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 1, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") field(SCAN, "I/O Intr") } record(bo, "RADM:BSYH:843:CH01:STATE_SET") { field(DESC, "Set channel state, ch. 01") field(DTYP, "asynInt32") field(OUT, "@asyn(FHT_BSYH_843, 1, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") info(asyn:READBACK, "1") } record(mbbi, "RADM:BSYH:843:CH01:DISPUNITS") { field(DESC, "Display units, ch. 01") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 1, 0) CHAN_UNITS") field(ZRVL, "0") field(ZRST, "Invalid") field(ONVL, "1") field(ONST, "Gy") field(TWVL, "2") field(TWST, "Gy/h") field(THVL, "3") field(THST, "Sv") field(FRVL, "4") field(FRST, "Sv/h") field(FVVL, "5") field(FVST, "IPS") field(SXVL, "6") field(SXST, "Bq") field(SVVL, "7") field(SVST, "Bq/cm2") field(EIVL, "8") field(EIST, "Bq/l") field(NIVL, "9") field(NIST, "R") field(TEVL, "10") field(TEST, "R/h") field(ELVL, "11") field(ELST, "User 1") field(TVVL, "12") field(TVST, "User 2") field(TTVL, "13") field(TTST, "User 3") field(FTVL, "14") field(FTST, "User 4") field(FFVL, "15") field(FFST, "User 5") field(SCAN, "I/O Intr") } # This record sets the display units record(stringout, "RADM:BSYH:843:CH01:USERUNITS") { field(DESC, "User units, ch. 01") field(OUT, "RADM:BSYH:843:CH01:MEAS.EGU PP") field(VAL, "$(EGU)") field(PINI, "1") info(autosaveFields, "VAL") } record(ai, "RADM:BSYH:843:CH01:DISPFACTOR") { field(DESC, "Display factor, ch. 01") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 1, 0) CHAN_DISP_FACT") field(EGU, "") field(PREC, "2") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH01:PREUNIT") { field(DESC, "Pre-unit, ch. 01") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 1, 0) CHAN_PREUNIT") field(ZNAM, "None") field(ONAM, "Auto") field(SCAN, "I/O Intr") } record(mbbi, "RADM:BSYH:843:CH01:PROBETYPE") { field(DESC, "Channel type, ch. 01") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 1, 0) CHAN_TYPE") field(ZRVL, "0") field(ZRST, "Unknown") field(ONVL, "1") field(ONST, "FHT 191N") field(TWVL, "2") field(TWST, "FHT 191T") field(THVL, "3") field(THST, "FHT 641D") field(FRVL, "4") field(FRST, "FHT 641P") field(FVVL, "5") field(FVST, "FHT 671 Y") field(SXVL, "6") field(SXST, "FHT 751") field(SVVL, "7") field(SVST, "FHZ 621 G-L") field(EIVL, "8") field(EIST, "FHZ 691") field(NIVL, "9") field(NIST, "SRD 2000") field(TEVL, "10") field(TEST, "FH 40G 1") field(ELVL, "11") field(ELST, "FH 40G 2") field(TVVL, "12") field(TVST, "Analog 1") field(TTVL, "13") field(TTST, "Analog 1") field(FTVL, "14") field(FTST, "Digital 1") field(FFVL, "15") field(FFST, "Digital 2") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH01:PORT") { field(DESC, "Port, ch. 01") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 1, 0) CHAN_PORT") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH01:DECODE") { field(DESC, "Decode, ch. 01") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 1, 0) CHAN_DECODE") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH01:ADDR") { field(DESC, "Address, ch. 01") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 1, 0) CHAN_ADDR") field(SCAN, "I/O Intr") } #--- Chan. 02 -------------------------------- # This record is the Nth channel's measured value. Units depend on the particular # probe and are set in the USERUNITS record below record(ai, "RADM:BSYH:843:CH02:MEAS") { field(DESC, "Meas. value, ch. 02") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 2, 0) MEAS") field(EGU, "") field(PREC, "3") field(LOLO, "") field(LOW, "") field(HIGH, "") field(HIHI, "") field(HYST, "0.5") field(LLSV, "NO_ALARM") field(LSV, "NO_ALARM") field(HSV, "MINOR") field(HHSV, "MAJOR") field(SCAN, "I/O Intr") info(autosaveFields, "LOLO LOW HIGH HIHI HYST LLSV LSV HSV HHSV") } record(longin, "RADM:BSYH:843:CH02:STATUS") { field(DESC, "Meas. val. status, ch. 02") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 2, 0) MEAS_STATUS") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH02:STATE") { field(DESC, "Channel state, ch. 02") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 2, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") field(SCAN, "I/O Intr") } record(bo, "RADM:BSYH:843:CH02:STATE_SET") { field(DESC, "Set channel state, ch. 02") field(DTYP, "asynInt32") field(OUT, "@asyn(FHT_BSYH_843, 2, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") info(asyn:READBACK, "1") } record(mbbi, "RADM:BSYH:843:CH02:DISPUNITS") { field(DESC, "Display units, ch. 02") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 2, 0) CHAN_UNITS") field(ZRVL, "0") field(ZRST, "Invalid") field(ONVL, "1") field(ONST, "Gy") field(TWVL, "2") field(TWST, "Gy/h") field(THVL, "3") field(THST, "Sv") field(FRVL, "4") field(FRST, "Sv/h") field(FVVL, "5") field(FVST, "IPS") field(SXVL, "6") field(SXST, "Bq") field(SVVL, "7") field(SVST, "Bq/cm2") field(EIVL, "8") field(EIST, "Bq/l") field(NIVL, "9") field(NIST, "R") field(TEVL, "10") field(TEST, "R/h") field(ELVL, "11") field(ELST, "User 1") field(TVVL, "12") field(TVST, "User 2") field(TTVL, "13") field(TTST, "User 3") field(FTVL, "14") field(FTST, "User 4") field(FFVL, "15") field(FFST, "User 5") field(SCAN, "I/O Intr") } # This record sets the display units record(stringout, "RADM:BSYH:843:CH02:USERUNITS") { field(DESC, "User units, ch. 02") field(OUT, "RADM:BSYH:843:CH02:MEAS.EGU PP") field(VAL, "$(EGU)") field(PINI, "1") info(autosaveFields, "VAL") } record(ai, "RADM:BSYH:843:CH02:DISPFACTOR") { field(DESC, "Display factor, ch. 02") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 2, 0) CHAN_DISP_FACT") field(EGU, "") field(PREC, "2") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH02:PREUNIT") { field(DESC, "Pre-unit, ch. 02") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 2, 0) CHAN_PREUNIT") field(ZNAM, "None") field(ONAM, "Auto") field(SCAN, "I/O Intr") } record(mbbi, "RADM:BSYH:843:CH02:PROBETYPE") { field(DESC, "Channel type, ch. 02") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 2, 0) CHAN_TYPE") field(ZRVL, "0") field(ZRST, "Unknown") field(ONVL, "1") field(ONST, "FHT 191N") field(TWVL, "2") field(TWST, "FHT 191T") field(THVL, "3") field(THST, "FHT 641D") field(FRVL, "4") field(FRST, "FHT 641P") field(FVVL, "5") field(FVST, "FHT 671 Y") field(SXVL, "6") field(SXST, "FHT 751") field(SVVL, "7") field(SVST, "FHZ 621 G-L") field(EIVL, "8") field(EIST, "FHZ 691") field(NIVL, "9") field(NIST, "SRD 2000") field(TEVL, "10") field(TEST, "FH 40G 1") field(ELVL, "11") field(ELST, "FH 40G 2") field(TVVL, "12") field(TVST, "Analog 1") field(TTVL, "13") field(TTST, "Analog 1") field(FTVL, "14") field(FTST, "Digital 1") field(FFVL, "15") field(FFST, "Digital 2") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH02:PORT") { field(DESC, "Port, ch. 02") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 2, 0) CHAN_PORT") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH02:DECODE") { field(DESC, "Decode, ch. 02") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 2, 0) CHAN_DECODE") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH02:ADDR") { field(DESC, "Address, ch. 02") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 2, 0) CHAN_ADDR") field(SCAN, "I/O Intr") } #--- Chan. 03 -------------------------------- # This record is the Nth channel's measured value. Units depend on the particular # probe and are set in the USERUNITS record below record(ai, "RADM:BSYH:843:CH03:MEAS") { field(DESC, "Meas. value, ch. 03") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 3, 0) MEAS") field(EGU, "") field(PREC, "3") field(LOLO, "") field(LOW, "") field(HIGH, "") field(HIHI, "") field(HYST, "0.5") field(LLSV, "NO_ALARM") field(LSV, "NO_ALARM") field(HSV, "MINOR") field(HHSV, "MAJOR") field(SCAN, "I/O Intr") info(autosaveFields, "LOLO LOW HIGH HIHI HYST LLSV LSV HSV HHSV") } record(longin, "RADM:BSYH:843:CH03:STATUS") { field(DESC, "Meas. val. status, ch. 03") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 3, 0) MEAS_STATUS") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH03:STATE") { field(DESC, "Channel state, ch. 03") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 3, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") field(SCAN, "I/O Intr") } record(bo, "RADM:BSYH:843:CH03:STATE_SET") { field(DESC, "Set channel state, ch. 03") field(DTYP, "asynInt32") field(OUT, "@asyn(FHT_BSYH_843, 3, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") info(asyn:READBACK, "1") } record(mbbi, "RADM:BSYH:843:CH03:DISPUNITS") { field(DESC, "Display units, ch. 03") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 3, 0) CHAN_UNITS") field(ZRVL, "0") field(ZRST, "Invalid") field(ONVL, "1") field(ONST, "Gy") field(TWVL, "2") field(TWST, "Gy/h") field(THVL, "3") field(THST, "Sv") field(FRVL, "4") field(FRST, "Sv/h") field(FVVL, "5") field(FVST, "IPS") field(SXVL, "6") field(SXST, "Bq") field(SVVL, "7") field(SVST, "Bq/cm2") field(EIVL, "8") field(EIST, "Bq/l") field(NIVL, "9") field(NIST, "R") field(TEVL, "10") field(TEST, "R/h") field(ELVL, "11") field(ELST, "User 1") field(TVVL, "12") field(TVST, "User 2") field(TTVL, "13") field(TTST, "User 3") field(FTVL, "14") field(FTST, "User 4") field(FFVL, "15") field(FFST, "User 5") field(SCAN, "I/O Intr") } # This record sets the display units record(stringout, "RADM:BSYH:843:CH03:USERUNITS") { field(DESC, "User units, ch. 03") field(OUT, "RADM:BSYH:843:CH03:MEAS.EGU PP") field(VAL, "$(EGU)") field(PINI, "1") info(autosaveFields, "VAL") } record(ai, "RADM:BSYH:843:CH03:DISPFACTOR") { field(DESC, "Display factor, ch. 03") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 3, 0) CHAN_DISP_FACT") field(EGU, "") field(PREC, "2") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH03:PREUNIT") { field(DESC, "Pre-unit, ch. 03") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 3, 0) CHAN_PREUNIT") field(ZNAM, "None") field(ONAM, "Auto") field(SCAN, "I/O Intr") } record(mbbi, "RADM:BSYH:843:CH03:PROBETYPE") { field(DESC, "Channel type, ch. 03") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 3, 0) CHAN_TYPE") field(ZRVL, "0") field(ZRST, "Unknown") field(ONVL, "1") field(ONST, "FHT 191N") field(TWVL, "2") field(TWST, "FHT 191T") field(THVL, "3") field(THST, "FHT 641D") field(FRVL, "4") field(FRST, "FHT 641P") field(FVVL, "5") field(FVST, "FHT 671 Y") field(SXVL, "6") field(SXST, "FHT 751") field(SVVL, "7") field(SVST, "FHZ 621 G-L") field(EIVL, "8") field(EIST, "FHZ 691") field(NIVL, "9") field(NIST, "SRD 2000") field(TEVL, "10") field(TEST, "FH 40G 1") field(ELVL, "11") field(ELST, "FH 40G 2") field(TVVL, "12") field(TVST, "Analog 1") field(TTVL, "13") field(TTST, "Analog 1") field(FTVL, "14") field(FTST, "Digital 1") field(FFVL, "15") field(FFST, "Digital 2") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH03:PORT") { field(DESC, "Port, ch. 03") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 3, 0) CHAN_PORT") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH03:DECODE") { field(DESC, "Decode, ch. 03") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 3, 0) CHAN_DECODE") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH03:ADDR") { field(DESC, "Address, ch. 03") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 3, 0) CHAN_ADDR") field(SCAN, "I/O Intr") } #--- Chan. 04 -------------------------------- # This record is the Nth channel's measured value. Units depend on the particular # probe and are set in the USERUNITS record below record(ai, "RADM:BSYH:843:CH04:MEAS") { field(DESC, "Meas. value, ch. 04") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 4, 0) MEAS") field(EGU, "") field(PREC, "3") field(LOLO, "") field(LOW, "") field(HIGH, "") field(HIHI, "") field(HYST, "0.5") field(LLSV, "NO_ALARM") field(LSV, "NO_ALARM") field(HSV, "MINOR") field(HHSV, "MAJOR") field(SCAN, "I/O Intr") info(autosaveFields, "LOLO LOW HIGH HIHI HYST LLSV LSV HSV HHSV") } record(longin, "RADM:BSYH:843:CH04:STATUS") { field(DESC, "Meas. val. status, ch. 04") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 4, 0) MEAS_STATUS") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH04:STATE") { field(DESC, "Channel state, ch. 04") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 4, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") field(SCAN, "I/O Intr") } record(bo, "RADM:BSYH:843:CH04:STATE_SET") { field(DESC, "Set channel state, ch. 04") field(DTYP, "asynInt32") field(OUT, "@asyn(FHT_BSYH_843, 4, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") info(asyn:READBACK, "1") } record(mbbi, "RADM:BSYH:843:CH04:DISPUNITS") { field(DESC, "Display units, ch. 04") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 4, 0) CHAN_UNITS") field(ZRVL, "0") field(ZRST, "Invalid") field(ONVL, "1") field(ONST, "Gy") field(TWVL, "2") field(TWST, "Gy/h") field(THVL, "3") field(THST, "Sv") field(FRVL, "4") field(FRST, "Sv/h") field(FVVL, "5") field(FVST, "IPS") field(SXVL, "6") field(SXST, "Bq") field(SVVL, "7") field(SVST, "Bq/cm2") field(EIVL, "8") field(EIST, "Bq/l") field(NIVL, "9") field(NIST, "R") field(TEVL, "10") field(TEST, "R/h") field(ELVL, "11") field(ELST, "User 1") field(TVVL, "12") field(TVST, "User 2") field(TTVL, "13") field(TTST, "User 3") field(FTVL, "14") field(FTST, "User 4") field(FFVL, "15") field(FFST, "User 5") field(SCAN, "I/O Intr") } # This record sets the display units record(stringout, "RADM:BSYH:843:CH04:USERUNITS") { field(DESC, "User units, ch. 04") field(OUT, "RADM:BSYH:843:CH04:MEAS.EGU PP") field(VAL, "$(EGU)") field(PINI, "1") info(autosaveFields, "VAL") } record(ai, "RADM:BSYH:843:CH04:DISPFACTOR") { field(DESC, "Display factor, ch. 04") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 4, 0) CHAN_DISP_FACT") field(EGU, "") field(PREC, "2") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH04:PREUNIT") { field(DESC, "Pre-unit, ch. 04") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 4, 0) CHAN_PREUNIT") field(ZNAM, "None") field(ONAM, "Auto") field(SCAN, "I/O Intr") } record(mbbi, "RADM:BSYH:843:CH04:PROBETYPE") { field(DESC, "Channel type, ch. 04") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 4, 0) CHAN_TYPE") field(ZRVL, "0") field(ZRST, "Unknown") field(ONVL, "1") field(ONST, "FHT 191N") field(TWVL, "2") field(TWST, "FHT 191T") field(THVL, "3") field(THST, "FHT 641D") field(FRVL, "4") field(FRST, "FHT 641P") field(FVVL, "5") field(FVST, "FHT 671 Y") field(SXVL, "6") field(SXST, "FHT 751") field(SVVL, "7") field(SVST, "FHZ 621 G-L") field(EIVL, "8") field(EIST, "FHZ 691") field(NIVL, "9") field(NIST, "SRD 2000") field(TEVL, "10") field(TEST, "FH 40G 1") field(ELVL, "11") field(ELST, "FH 40G 2") field(TVVL, "12") field(TVST, "Analog 1") field(TTVL, "13") field(TTST, "Analog 1") field(FTVL, "14") field(FTST, "Digital 1") field(FFVL, "15") field(FFST, "Digital 2") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH04:PORT") { field(DESC, "Port, ch. 04") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 4, 0) CHAN_PORT") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH04:DECODE") { field(DESC, "Decode, ch. 04") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 4, 0) CHAN_DECODE") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH04:ADDR") { field(DESC, "Address, ch. 04") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 4, 0) CHAN_ADDR") field(SCAN, "I/O Intr") } #--- Chan. 05 -------------------------------- # This record is the Nth channel's measured value. Units depend on the particular # probe and are set in the USERUNITS record below record(ai, "RADM:BSYH:843:CH05:MEAS") { field(DESC, "Meas. value, ch. 05") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 5, 0) MEAS") field(EGU, "") field(PREC, "3") field(LOLO, "") field(LOW, "") field(HIGH, "") field(HIHI, "") field(HYST, "0.5") field(LLSV, "NO_ALARM") field(LSV, "NO_ALARM") field(HSV, "MINOR") field(HHSV, "MAJOR") field(SCAN, "I/O Intr") info(autosaveFields, "LOLO LOW HIGH HIHI HYST LLSV LSV HSV HHSV") } record(longin, "RADM:BSYH:843:CH05:STATUS") { field(DESC, "Meas. val. status, ch. 05") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 5, 0) MEAS_STATUS") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH05:STATE") { field(DESC, "Channel state, ch. 05") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 5, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") field(SCAN, "I/O Intr") } record(bo, "RADM:BSYH:843:CH05:STATE_SET") { field(DESC, "Set channel state, ch. 05") field(DTYP, "asynInt32") field(OUT, "@asyn(FHT_BSYH_843, 5, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") info(asyn:READBACK, "1") } record(mbbi, "RADM:BSYH:843:CH05:DISPUNITS") { field(DESC, "Display units, ch. 05") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 5, 0) CHAN_UNITS") field(ZRVL, "0") field(ZRST, "Invalid") field(ONVL, "1") field(ONST, "Gy") field(TWVL, "2") field(TWST, "Gy/h") field(THVL, "3") field(THST, "Sv") field(FRVL, "4") field(FRST, "Sv/h") field(FVVL, "5") field(FVST, "IPS") field(SXVL, "6") field(SXST, "Bq") field(SVVL, "7") field(SVST, "Bq/cm2") field(EIVL, "8") field(EIST, "Bq/l") field(NIVL, "9") field(NIST, "R") field(TEVL, "10") field(TEST, "R/h") field(ELVL, "11") field(ELST, "User 1") field(TVVL, "12") field(TVST, "User 2") field(TTVL, "13") field(TTST, "User 3") field(FTVL, "14") field(FTST, "User 4") field(FFVL, "15") field(FFST, "User 5") field(SCAN, "I/O Intr") } # This record sets the display units record(stringout, "RADM:BSYH:843:CH05:USERUNITS") { field(DESC, "User units, ch. 05") field(OUT, "RADM:BSYH:843:CH05:MEAS.EGU PP") field(VAL, "$(EGU)") field(PINI, "1") info(autosaveFields, "VAL") } record(ai, "RADM:BSYH:843:CH05:DISPFACTOR") { field(DESC, "Display factor, ch. 05") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 5, 0) CHAN_DISP_FACT") field(EGU, "") field(PREC, "2") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH05:PREUNIT") { field(DESC, "Pre-unit, ch. 05") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 5, 0) CHAN_PREUNIT") field(ZNAM, "None") field(ONAM, "Auto") field(SCAN, "I/O Intr") } record(mbbi, "RADM:BSYH:843:CH05:PROBETYPE") { field(DESC, "Channel type, ch. 05") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 5, 0) CHAN_TYPE") field(ZRVL, "0") field(ZRST, "Unknown") field(ONVL, "1") field(ONST, "FHT 191N") field(TWVL, "2") field(TWST, "FHT 191T") field(THVL, "3") field(THST, "FHT 641D") field(FRVL, "4") field(FRST, "FHT 641P") field(FVVL, "5") field(FVST, "FHT 671 Y") field(SXVL, "6") field(SXST, "FHT 751") field(SVVL, "7") field(SVST, "FHZ 621 G-L") field(EIVL, "8") field(EIST, "FHZ 691") field(NIVL, "9") field(NIST, "SRD 2000") field(TEVL, "10") field(TEST, "FH 40G 1") field(ELVL, "11") field(ELST, "FH 40G 2") field(TVVL, "12") field(TVST, "Analog 1") field(TTVL, "13") field(TTST, "Analog 1") field(FTVL, "14") field(FTST, "Digital 1") field(FFVL, "15") field(FFST, "Digital 2") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH05:PORT") { field(DESC, "Port, ch. 05") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 5, 0) CHAN_PORT") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH05:DECODE") { field(DESC, "Decode, ch. 05") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 5, 0) CHAN_DECODE") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH05:ADDR") { field(DESC, "Address, ch. 05") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 5, 0) CHAN_ADDR") field(SCAN, "I/O Intr") } #--- Chan. 06 -------------------------------- # This record is the Nth channel's measured value. Units depend on the particular # probe and are set in the USERUNITS record below record(ai, "RADM:BSYH:843:CH06:MEAS") { field(DESC, "Meas. value, ch. 06") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 6, 0) MEAS") field(EGU, "") field(PREC, "3") field(LOLO, "") field(LOW, "") field(HIGH, "") field(HIHI, "") field(HYST, "0.5") field(LLSV, "NO_ALARM") field(LSV, "NO_ALARM") field(HSV, "MINOR") field(HHSV, "MAJOR") field(SCAN, "I/O Intr") info(autosaveFields, "LOLO LOW HIGH HIHI HYST LLSV LSV HSV HHSV") } record(longin, "RADM:BSYH:843:CH06:STATUS") { field(DESC, "Meas. val. status, ch. 06") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 6, 0) MEAS_STATUS") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH06:STATE") { field(DESC, "Channel state, ch. 06") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 6, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") field(SCAN, "I/O Intr") } record(bo, "RADM:BSYH:843:CH06:STATE_SET") { field(DESC, "Set channel state, ch. 06") field(DTYP, "asynInt32") field(OUT, "@asyn(FHT_BSYH_843, 6, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") info(asyn:READBACK, "1") } record(mbbi, "RADM:BSYH:843:CH06:DISPUNITS") { field(DESC, "Display units, ch. 06") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 6, 0) CHAN_UNITS") field(ZRVL, "0") field(ZRST, "Invalid") field(ONVL, "1") field(ONST, "Gy") field(TWVL, "2") field(TWST, "Gy/h") field(THVL, "3") field(THST, "Sv") field(FRVL, "4") field(FRST, "Sv/h") field(FVVL, "5") field(FVST, "IPS") field(SXVL, "6") field(SXST, "Bq") field(SVVL, "7") field(SVST, "Bq/cm2") field(EIVL, "8") field(EIST, "Bq/l") field(NIVL, "9") field(NIST, "R") field(TEVL, "10") field(TEST, "R/h") field(ELVL, "11") field(ELST, "User 1") field(TVVL, "12") field(TVST, "User 2") field(TTVL, "13") field(TTST, "User 3") field(FTVL, "14") field(FTST, "User 4") field(FFVL, "15") field(FFST, "User 5") field(SCAN, "I/O Intr") } # This record sets the display units record(stringout, "RADM:BSYH:843:CH06:USERUNITS") { field(DESC, "User units, ch. 06") field(OUT, "RADM:BSYH:843:CH06:MEAS.EGU PP") field(VAL, "$(EGU)") field(PINI, "1") info(autosaveFields, "VAL") } record(ai, "RADM:BSYH:843:CH06:DISPFACTOR") { field(DESC, "Display factor, ch. 06") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 6, 0) CHAN_DISP_FACT") field(EGU, "") field(PREC, "2") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH06:PREUNIT") { field(DESC, "Pre-unit, ch. 06") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 6, 0) CHAN_PREUNIT") field(ZNAM, "None") field(ONAM, "Auto") field(SCAN, "I/O Intr") } record(mbbi, "RADM:BSYH:843:CH06:PROBETYPE") { field(DESC, "Channel type, ch. 06") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 6, 0) CHAN_TYPE") field(ZRVL, "0") field(ZRST, "Unknown") field(ONVL, "1") field(ONST, "FHT 191N") field(TWVL, "2") field(TWST, "FHT 191T") field(THVL, "3") field(THST, "FHT 641D") field(FRVL, "4") field(FRST, "FHT 641P") field(FVVL, "5") field(FVST, "FHT 671 Y") field(SXVL, "6") field(SXST, "FHT 751") field(SVVL, "7") field(SVST, "FHZ 621 G-L") field(EIVL, "8") field(EIST, "FHZ 691") field(NIVL, "9") field(NIST, "SRD 2000") field(TEVL, "10") field(TEST, "FH 40G 1") field(ELVL, "11") field(ELST, "FH 40G 2") field(TVVL, "12") field(TVST, "Analog 1") field(TTVL, "13") field(TTST, "Analog 1") field(FTVL, "14") field(FTST, "Digital 1") field(FFVL, "15") field(FFST, "Digital 2") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH06:PORT") { field(DESC, "Port, ch. 06") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 6, 0) CHAN_PORT") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH06:DECODE") { field(DESC, "Decode, ch. 06") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 6, 0) CHAN_DECODE") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH06:ADDR") { field(DESC, "Address, ch. 06") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 6, 0) CHAN_ADDR") field(SCAN, "I/O Intr") } #--- Chan. 07 -------------------------------- # This record is the Nth channel's measured value. Units depend on the particular # probe and are set in the USERUNITS record below record(ai, "RADM:BSYH:843:CH07:MEAS") { field(DESC, "Meas. value, ch. 07") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 7, 0) MEAS") field(EGU, "") field(PREC, "3") field(LOLO, "") field(LOW, "") field(HIGH, "") field(HIHI, "") field(HYST, "0.5") field(LLSV, "NO_ALARM") field(LSV, "NO_ALARM") field(HSV, "MINOR") field(HHSV, "MAJOR") field(SCAN, "I/O Intr") info(autosaveFields, "LOLO LOW HIGH HIHI HYST LLSV LSV HSV HHSV") } record(longin, "RADM:BSYH:843:CH07:STATUS") { field(DESC, "Meas. val. status, ch. 07") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 7, 0) MEAS_STATUS") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH07:STATE") { field(DESC, "Channel state, ch. 07") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 7, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") field(SCAN, "I/O Intr") } record(bo, "RADM:BSYH:843:CH07:STATE_SET") { field(DESC, "Set channel state, ch. 07") field(DTYP, "asynInt32") field(OUT, "@asyn(FHT_BSYH_843, 7, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") info(asyn:READBACK, "1") } record(mbbi, "RADM:BSYH:843:CH07:DISPUNITS") { field(DESC, "Display units, ch. 07") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 7, 0) CHAN_UNITS") field(ZRVL, "0") field(ZRST, "Invalid") field(ONVL, "1") field(ONST, "Gy") field(TWVL, "2") field(TWST, "Gy/h") field(THVL, "3") field(THST, "Sv") field(FRVL, "4") field(FRST, "Sv/h") field(FVVL, "5") field(FVST, "IPS") field(SXVL, "6") field(SXST, "Bq") field(SVVL, "7") field(SVST, "Bq/cm2") field(EIVL, "8") field(EIST, "Bq/l") field(NIVL, "9") field(NIST, "R") field(TEVL, "10") field(TEST, "R/h") field(ELVL, "11") field(ELST, "User 1") field(TVVL, "12") field(TVST, "User 2") field(TTVL, "13") field(TTST, "User 3") field(FTVL, "14") field(FTST, "User 4") field(FFVL, "15") field(FFST, "User 5") field(SCAN, "I/O Intr") } # This record sets the display units record(stringout, "RADM:BSYH:843:CH07:USERUNITS") { field(DESC, "User units, ch. 07") field(OUT, "RADM:BSYH:843:CH07:MEAS.EGU PP") field(VAL, "$(EGU)") field(PINI, "1") info(autosaveFields, "VAL") } record(ai, "RADM:BSYH:843:CH07:DISPFACTOR") { field(DESC, "Display factor, ch. 07") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 7, 0) CHAN_DISP_FACT") field(EGU, "") field(PREC, "2") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH07:PREUNIT") { field(DESC, "Pre-unit, ch. 07") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 7, 0) CHAN_PREUNIT") field(ZNAM, "None") field(ONAM, "Auto") field(SCAN, "I/O Intr") } record(mbbi, "RADM:BSYH:843:CH07:PROBETYPE") { field(DESC, "Channel type, ch. 07") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 7, 0) CHAN_TYPE") field(ZRVL, "0") field(ZRST, "Unknown") field(ONVL, "1") field(ONST, "FHT 191N") field(TWVL, "2") field(TWST, "FHT 191T") field(THVL, "3") field(THST, "FHT 641D") field(FRVL, "4") field(FRST, "FHT 641P") field(FVVL, "5") field(FVST, "FHT 671 Y") field(SXVL, "6") field(SXST, "FHT 751") field(SVVL, "7") field(SVST, "FHZ 621 G-L") field(EIVL, "8") field(EIST, "FHZ 691") field(NIVL, "9") field(NIST, "SRD 2000") field(TEVL, "10") field(TEST, "FH 40G 1") field(ELVL, "11") field(ELST, "FH 40G 2") field(TVVL, "12") field(TVST, "Analog 1") field(TTVL, "13") field(TTST, "Analog 1") field(FTVL, "14") field(FTST, "Digital 1") field(FFVL, "15") field(FFST, "Digital 2") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH07:PORT") { field(DESC, "Port, ch. 07") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 7, 0) CHAN_PORT") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH07:DECODE") { field(DESC, "Decode, ch. 07") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 7, 0) CHAN_DECODE") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH07:ADDR") { field(DESC, "Address, ch. 07") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 7, 0) CHAN_ADDR") field(SCAN, "I/O Intr") } #--- Chan. 08 -------------------------------- # This record is the Nth channel's measured value. Units depend on the particular # probe and are set in the USERUNITS record below record(ai, "RADM:BSYH:843:CH08:MEAS") { field(DESC, "Meas. value, ch. 08") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 8, 0) MEAS") field(EGU, "") field(PREC, "3") field(LOLO, "") field(LOW, "") field(HIGH, "") field(HIHI, "") field(HYST, "0.5") field(LLSV, "NO_ALARM") field(LSV, "NO_ALARM") field(HSV, "MINOR") field(HHSV, "MAJOR") field(SCAN, "I/O Intr") info(autosaveFields, "LOLO LOW HIGH HIHI HYST LLSV LSV HSV HHSV") } record(longin, "RADM:BSYH:843:CH08:STATUS") { field(DESC, "Meas. val. status, ch. 08") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 8, 0) MEAS_STATUS") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH08:STATE") { field(DESC, "Channel state, ch. 08") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 8, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") field(SCAN, "I/O Intr") } record(bo, "RADM:BSYH:843:CH08:STATE_SET") { field(DESC, "Set channel state, ch. 08") field(DTYP, "asynInt32") field(OUT, "@asyn(FHT_BSYH_843, 8, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") info(asyn:READBACK, "1") } record(mbbi, "RADM:BSYH:843:CH08:DISPUNITS") { field(DESC, "Display units, ch. 08") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 8, 0) CHAN_UNITS") field(ZRVL, "0") field(ZRST, "Invalid") field(ONVL, "1") field(ONST, "Gy") field(TWVL, "2") field(TWST, "Gy/h") field(THVL, "3") field(THST, "Sv") field(FRVL, "4") field(FRST, "Sv/h") field(FVVL, "5") field(FVST, "IPS") field(SXVL, "6") field(SXST, "Bq") field(SVVL, "7") field(SVST, "Bq/cm2") field(EIVL, "8") field(EIST, "Bq/l") field(NIVL, "9") field(NIST, "R") field(TEVL, "10") field(TEST, "R/h") field(ELVL, "11") field(ELST, "User 1") field(TVVL, "12") field(TVST, "User 2") field(TTVL, "13") field(TTST, "User 3") field(FTVL, "14") field(FTST, "User 4") field(FFVL, "15") field(FFST, "User 5") field(SCAN, "I/O Intr") } # This record sets the display units record(stringout, "RADM:BSYH:843:CH08:USERUNITS") { field(DESC, "User units, ch. 08") field(OUT, "RADM:BSYH:843:CH08:MEAS.EGU PP") field(VAL, "$(EGU)") field(PINI, "1") info(autosaveFields, "VAL") } record(ai, "RADM:BSYH:843:CH08:DISPFACTOR") { field(DESC, "Display factor, ch. 08") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 8, 0) CHAN_DISP_FACT") field(EGU, "") field(PREC, "2") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH08:PREUNIT") { field(DESC, "Pre-unit, ch. 08") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 8, 0) CHAN_PREUNIT") field(ZNAM, "None") field(ONAM, "Auto") field(SCAN, "I/O Intr") } record(mbbi, "RADM:BSYH:843:CH08:PROBETYPE") { field(DESC, "Channel type, ch. 08") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 8, 0) CHAN_TYPE") field(ZRVL, "0") field(ZRST, "Unknown") field(ONVL, "1") field(ONST, "FHT 191N") field(TWVL, "2") field(TWST, "FHT 191T") field(THVL, "3") field(THST, "FHT 641D") field(FRVL, "4") field(FRST, "FHT 641P") field(FVVL, "5") field(FVST, "FHT 671 Y") field(SXVL, "6") field(SXST, "FHT 751") field(SVVL, "7") field(SVST, "FHZ 621 G-L") field(EIVL, "8") field(EIST, "FHZ 691") field(NIVL, "9") field(NIST, "SRD 2000") field(TEVL, "10") field(TEST, "FH 40G 1") field(ELVL, "11") field(ELST, "FH 40G 2") field(TVVL, "12") field(TVST, "Analog 1") field(TTVL, "13") field(TTST, "Analog 1") field(FTVL, "14") field(FTST, "Digital 1") field(FFVL, "15") field(FFST, "Digital 2") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH08:PORT") { field(DESC, "Port, ch. 08") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 8, 0) CHAN_PORT") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH08:DECODE") { field(DESC, "Decode, ch. 08") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 8, 0) CHAN_DECODE") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH08:ADDR") { field(DESC, "Address, ch. 08") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 8, 0) CHAN_ADDR") field(SCAN, "I/O Intr") } #--- Chan. 09 -------------------------------- # This record is the Nth channel's measured value. Units depend on the particular # probe and are set in the USERUNITS record below record(ai, "RADM:BSYH:843:CH09:MEAS") { field(DESC, "Meas. value, ch. 09") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 9, 0) MEAS") field(EGU, "") field(PREC, "3") field(LOLO, "") field(LOW, "") field(HIGH, "") field(HIHI, "") field(HYST, "0.5") field(LLSV, "NO_ALARM") field(LSV, "NO_ALARM") field(HSV, "MINOR") field(HHSV, "MAJOR") field(SCAN, "I/O Intr") info(autosaveFields, "LOLO LOW HIGH HIHI HYST LLSV LSV HSV HHSV") } record(longin, "RADM:BSYH:843:CH09:STATUS") { field(DESC, "Meas. val. status, ch. 09") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 9, 0) MEAS_STATUS") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH09:STATE") { field(DESC, "Channel state, ch. 09") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 9, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") field(SCAN, "I/O Intr") } record(bo, "RADM:BSYH:843:CH09:STATE_SET") { field(DESC, "Set channel state, ch. 09") field(DTYP, "asynInt32") field(OUT, "@asyn(FHT_BSYH_843, 9, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") info(asyn:READBACK, "1") } record(mbbi, "RADM:BSYH:843:CH09:DISPUNITS") { field(DESC, "Display units, ch. 09") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 9, 0) CHAN_UNITS") field(ZRVL, "0") field(ZRST, "Invalid") field(ONVL, "1") field(ONST, "Gy") field(TWVL, "2") field(TWST, "Gy/h") field(THVL, "3") field(THST, "Sv") field(FRVL, "4") field(FRST, "Sv/h") field(FVVL, "5") field(FVST, "IPS") field(SXVL, "6") field(SXST, "Bq") field(SVVL, "7") field(SVST, "Bq/cm2") field(EIVL, "8") field(EIST, "Bq/l") field(NIVL, "9") field(NIST, "R") field(TEVL, "10") field(TEST, "R/h") field(ELVL, "11") field(ELST, "User 1") field(TVVL, "12") field(TVST, "User 2") field(TTVL, "13") field(TTST, "User 3") field(FTVL, "14") field(FTST, "User 4") field(FFVL, "15") field(FFST, "User 5") field(SCAN, "I/O Intr") } # This record sets the display units record(stringout, "RADM:BSYH:843:CH09:USERUNITS") { field(DESC, "User units, ch. 09") field(OUT, "RADM:BSYH:843:CH09:MEAS.EGU PP") field(VAL, "$(EGU)") field(PINI, "1") info(autosaveFields, "VAL") } record(ai, "RADM:BSYH:843:CH09:DISPFACTOR") { field(DESC, "Display factor, ch. 09") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 9, 0) CHAN_DISP_FACT") field(EGU, "") field(PREC, "2") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH09:PREUNIT") { field(DESC, "Pre-unit, ch. 09") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 9, 0) CHAN_PREUNIT") field(ZNAM, "None") field(ONAM, "Auto") field(SCAN, "I/O Intr") } record(mbbi, "RADM:BSYH:843:CH09:PROBETYPE") { field(DESC, "Channel type, ch. 09") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 9, 0) CHAN_TYPE") field(ZRVL, "0") field(ZRST, "Unknown") field(ONVL, "1") field(ONST, "FHT 191N") field(TWVL, "2") field(TWST, "FHT 191T") field(THVL, "3") field(THST, "FHT 641D") field(FRVL, "4") field(FRST, "FHT 641P") field(FVVL, "5") field(FVST, "FHT 671 Y") field(SXVL, "6") field(SXST, "FHT 751") field(SVVL, "7") field(SVST, "FHZ 621 G-L") field(EIVL, "8") field(EIST, "FHZ 691") field(NIVL, "9") field(NIST, "SRD 2000") field(TEVL, "10") field(TEST, "FH 40G 1") field(ELVL, "11") field(ELST, "FH 40G 2") field(TVVL, "12") field(TVST, "Analog 1") field(TTVL, "13") field(TTST, "Analog 1") field(FTVL, "14") field(FTST, "Digital 1") field(FFVL, "15") field(FFST, "Digital 2") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH09:PORT") { field(DESC, "Port, ch. 09") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 9, 0) CHAN_PORT") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH09:DECODE") { field(DESC, "Decode, ch. 09") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 9, 0) CHAN_DECODE") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH09:ADDR") { field(DESC, "Address, ch. 09") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 9, 0) CHAN_ADDR") field(SCAN, "I/O Intr") } #--- Chan. 10 -------------------------------- # This record is the Nth channel's measured value. Units depend on the particular # probe and are set in the USERUNITS record below record(ai, "RADM:BSYH:843:CH10:MEAS") { field(DESC, "Meas. value, ch. 10") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 10, 0) MEAS") field(EGU, "") field(PREC, "3") field(LOLO, "") field(LOW, "") field(HIGH, "") field(HIHI, "") field(HYST, "0.5") field(LLSV, "NO_ALARM") field(LSV, "NO_ALARM") field(HSV, "MINOR") field(HHSV, "MAJOR") field(SCAN, "I/O Intr") info(autosaveFields, "LOLO LOW HIGH HIHI HYST LLSV LSV HSV HHSV") } record(longin, "RADM:BSYH:843:CH10:STATUS") { field(DESC, "Meas. val. status, ch. 10") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 10, 0) MEAS_STATUS") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH10:STATE") { field(DESC, "Channel state, ch. 10") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 10, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") field(SCAN, "I/O Intr") } record(bo, "RADM:BSYH:843:CH10:STATE_SET") { field(DESC, "Set channel state, ch. 10") field(DTYP, "asynInt32") field(OUT, "@asyn(FHT_BSYH_843, 10, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") info(asyn:READBACK, "1") } record(mbbi, "RADM:BSYH:843:CH10:DISPUNITS") { field(DESC, "Display units, ch. 10") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 10, 0) CHAN_UNITS") field(ZRVL, "0") field(ZRST, "Invalid") field(ONVL, "1") field(ONST, "Gy") field(TWVL, "2") field(TWST, "Gy/h") field(THVL, "3") field(THST, "Sv") field(FRVL, "4") field(FRST, "Sv/h") field(FVVL, "5") field(FVST, "IPS") field(SXVL, "6") field(SXST, "Bq") field(SVVL, "7") field(SVST, "Bq/cm2") field(EIVL, "8") field(EIST, "Bq/l") field(NIVL, "9") field(NIST, "R") field(TEVL, "10") field(TEST, "R/h") field(ELVL, "11") field(ELST, "User 1") field(TVVL, "12") field(TVST, "User 2") field(TTVL, "13") field(TTST, "User 3") field(FTVL, "14") field(FTST, "User 4") field(FFVL, "15") field(FFST, "User 5") field(SCAN, "I/O Intr") } # This record sets the display units record(stringout, "RADM:BSYH:843:CH10:USERUNITS") { field(DESC, "User units, ch. 10") field(OUT, "RADM:BSYH:843:CH10:MEAS.EGU PP") field(VAL, "$(EGU)") field(PINI, "1") info(autosaveFields, "VAL") } record(ai, "RADM:BSYH:843:CH10:DISPFACTOR") { field(DESC, "Display factor, ch. 10") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 10, 0) CHAN_DISP_FACT") field(EGU, "") field(PREC, "2") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH10:PREUNIT") { field(DESC, "Pre-unit, ch. 10") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 10, 0) CHAN_PREUNIT") field(ZNAM, "None") field(ONAM, "Auto") field(SCAN, "I/O Intr") } record(mbbi, "RADM:BSYH:843:CH10:PROBETYPE") { field(DESC, "Channel type, ch. 10") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 10, 0) CHAN_TYPE") field(ZRVL, "0") field(ZRST, "Unknown") field(ONVL, "1") field(ONST, "FHT 191N") field(TWVL, "2") field(TWST, "FHT 191T") field(THVL, "3") field(THST, "FHT 641D") field(FRVL, "4") field(FRST, "FHT 641P") field(FVVL, "5") field(FVST, "FHT 671 Y") field(SXVL, "6") field(SXST, "FHT 751") field(SVVL, "7") field(SVST, "FHZ 621 G-L") field(EIVL, "8") field(EIST, "FHZ 691") field(NIVL, "9") field(NIST, "SRD 2000") field(TEVL, "10") field(TEST, "FH 40G 1") field(ELVL, "11") field(ELST, "FH 40G 2") field(TVVL, "12") field(TVST, "Analog 1") field(TTVL, "13") field(TTST, "Analog 1") field(FTVL, "14") field(FTST, "Digital 1") field(FFVL, "15") field(FFST, "Digital 2") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH10:PORT") { field(DESC, "Port, ch. 10") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 10, 0) CHAN_PORT") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH10:DECODE") { field(DESC, "Decode, ch. 10") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 10, 0) CHAN_DECODE") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH10:ADDR") { field(DESC, "Address, ch. 10") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 10, 0) CHAN_ADDR") field(SCAN, "I/O Intr") } #--- Chan. 11 -------------------------------- # This record is the Nth channel's measured value. Units depend on the particular # probe and are set in the USERUNITS record below record(ai, "RADM:BSYH:843:CH11:MEAS") { field(DESC, "Meas. value, ch. 11") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 11, 0) MEAS") field(EGU, "") field(PREC, "3") field(LOLO, "") field(LOW, "") field(HIGH, "") field(HIHI, "") field(HYST, "0.5") field(LLSV, "NO_ALARM") field(LSV, "NO_ALARM") field(HSV, "MINOR") field(HHSV, "MAJOR") field(SCAN, "I/O Intr") info(autosaveFields, "LOLO LOW HIGH HIHI HYST LLSV LSV HSV HHSV") } record(longin, "RADM:BSYH:843:CH11:STATUS") { field(DESC, "Meas. val. status, ch. 11") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 11, 0) MEAS_STATUS") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH11:STATE") { field(DESC, "Channel state, ch. 11") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 11, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") field(SCAN, "I/O Intr") } record(bo, "RADM:BSYH:843:CH11:STATE_SET") { field(DESC, "Set channel state, ch. 11") field(DTYP, "asynInt32") field(OUT, "@asyn(FHT_BSYH_843, 11, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") info(asyn:READBACK, "1") } record(mbbi, "RADM:BSYH:843:CH11:DISPUNITS") { field(DESC, "Display units, ch. 11") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 11, 0) CHAN_UNITS") field(ZRVL, "0") field(ZRST, "Invalid") field(ONVL, "1") field(ONST, "Gy") field(TWVL, "2") field(TWST, "Gy/h") field(THVL, "3") field(THST, "Sv") field(FRVL, "4") field(FRST, "Sv/h") field(FVVL, "5") field(FVST, "IPS") field(SXVL, "6") field(SXST, "Bq") field(SVVL, "7") field(SVST, "Bq/cm2") field(EIVL, "8") field(EIST, "Bq/l") field(NIVL, "9") field(NIST, "R") field(TEVL, "10") field(TEST, "R/h") field(ELVL, "11") field(ELST, "User 1") field(TVVL, "12") field(TVST, "User 2") field(TTVL, "13") field(TTST, "User 3") field(FTVL, "14") field(FTST, "User 4") field(FFVL, "15") field(FFST, "User 5") field(SCAN, "I/O Intr") } # This record sets the display units record(stringout, "RADM:BSYH:843:CH11:USERUNITS") { field(DESC, "User units, ch. 11") field(OUT, "RADM:BSYH:843:CH11:MEAS.EGU PP") field(VAL, "$(EGU)") field(PINI, "1") info(autosaveFields, "VAL") } record(ai, "RADM:BSYH:843:CH11:DISPFACTOR") { field(DESC, "Display factor, ch. 11") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 11, 0) CHAN_DISP_FACT") field(EGU, "") field(PREC, "2") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH11:PREUNIT") { field(DESC, "Pre-unit, ch. 11") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 11, 0) CHAN_PREUNIT") field(ZNAM, "None") field(ONAM, "Auto") field(SCAN, "I/O Intr") } record(mbbi, "RADM:BSYH:843:CH11:PROBETYPE") { field(DESC, "Channel type, ch. 11") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 11, 0) CHAN_TYPE") field(ZRVL, "0") field(ZRST, "Unknown") field(ONVL, "1") field(ONST, "FHT 191N") field(TWVL, "2") field(TWST, "FHT 191T") field(THVL, "3") field(THST, "FHT 641D") field(FRVL, "4") field(FRST, "FHT 641P") field(FVVL, "5") field(FVST, "FHT 671 Y") field(SXVL, "6") field(SXST, "FHT 751") field(SVVL, "7") field(SVST, "FHZ 621 G-L") field(EIVL, "8") field(EIST, "FHZ 691") field(NIVL, "9") field(NIST, "SRD 2000") field(TEVL, "10") field(TEST, "FH 40G 1") field(ELVL, "11") field(ELST, "FH 40G 2") field(TVVL, "12") field(TVST, "Analog 1") field(TTVL, "13") field(TTST, "Analog 1") field(FTVL, "14") field(FTST, "Digital 1") field(FFVL, "15") field(FFST, "Digital 2") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH11:PORT") { field(DESC, "Port, ch. 11") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 11, 0) CHAN_PORT") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH11:DECODE") { field(DESC, "Decode, ch. 11") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 11, 0) CHAN_DECODE") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH11:ADDR") { field(DESC, "Address, ch. 11") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 11, 0) CHAN_ADDR") field(SCAN, "I/O Intr") } #--- Chan. 12 -------------------------------- # This record is the Nth channel's measured value. Units depend on the particular # probe and are set in the USERUNITS record below record(ai, "RADM:BSYH:843:CH12:MEAS") { field(DESC, "Meas. value, ch. 12") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 12, 0) MEAS") field(EGU, "") field(PREC, "3") field(LOLO, "") field(LOW, "") field(HIGH, "") field(HIHI, "") field(HYST, "0.5") field(LLSV, "NO_ALARM") field(LSV, "NO_ALARM") field(HSV, "MINOR") field(HHSV, "MAJOR") field(SCAN, "I/O Intr") info(autosaveFields, "LOLO LOW HIGH HIHI HYST LLSV LSV HSV HHSV") } record(longin, "RADM:BSYH:843:CH12:STATUS") { field(DESC, "Meas. val. status, ch. 12") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 12, 0) MEAS_STATUS") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH12:STATE") { field(DESC, "Channel state, ch. 12") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 12, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") field(SCAN, "I/O Intr") } record(bo, "RADM:BSYH:843:CH12:STATE_SET") { field(DESC, "Set channel state, ch. 12") field(DTYP, "asynInt32") field(OUT, "@asyn(FHT_BSYH_843, 12, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") info(asyn:READBACK, "1") } record(mbbi, "RADM:BSYH:843:CH12:DISPUNITS") { field(DESC, "Display units, ch. 12") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 12, 0) CHAN_UNITS") field(ZRVL, "0") field(ZRST, "Invalid") field(ONVL, "1") field(ONST, "Gy") field(TWVL, "2") field(TWST, "Gy/h") field(THVL, "3") field(THST, "Sv") field(FRVL, "4") field(FRST, "Sv/h") field(FVVL, "5") field(FVST, "IPS") field(SXVL, "6") field(SXST, "Bq") field(SVVL, "7") field(SVST, "Bq/cm2") field(EIVL, "8") field(EIST, "Bq/l") field(NIVL, "9") field(NIST, "R") field(TEVL, "10") field(TEST, "R/h") field(ELVL, "11") field(ELST, "User 1") field(TVVL, "12") field(TVST, "User 2") field(TTVL, "13") field(TTST, "User 3") field(FTVL, "14") field(FTST, "User 4") field(FFVL, "15") field(FFST, "User 5") field(SCAN, "I/O Intr") } # This record sets the display units record(stringout, "RADM:BSYH:843:CH12:USERUNITS") { field(DESC, "User units, ch. 12") field(OUT, "RADM:BSYH:843:CH12:MEAS.EGU PP") field(VAL, "$(EGU)") field(PINI, "1") info(autosaveFields, "VAL") } record(ai, "RADM:BSYH:843:CH12:DISPFACTOR") { field(DESC, "Display factor, ch. 12") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 12, 0) CHAN_DISP_FACT") field(EGU, "") field(PREC, "2") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH12:PREUNIT") { field(DESC, "Pre-unit, ch. 12") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 12, 0) CHAN_PREUNIT") field(ZNAM, "None") field(ONAM, "Auto") field(SCAN, "I/O Intr") } record(mbbi, "RADM:BSYH:843:CH12:PROBETYPE") { field(DESC, "Channel type, ch. 12") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 12, 0) CHAN_TYPE") field(ZRVL, "0") field(ZRST, "Unknown") field(ONVL, "1") field(ONST, "FHT 191N") field(TWVL, "2") field(TWST, "FHT 191T") field(THVL, "3") field(THST, "FHT 641D") field(FRVL, "4") field(FRST, "FHT 641P") field(FVVL, "5") field(FVST, "FHT 671 Y") field(SXVL, "6") field(SXST, "FHT 751") field(SVVL, "7") field(SVST, "FHZ 621 G-L") field(EIVL, "8") field(EIST, "FHZ 691") field(NIVL, "9") field(NIST, "SRD 2000") field(TEVL, "10") field(TEST, "FH 40G 1") field(ELVL, "11") field(ELST, "FH 40G 2") field(TVVL, "12") field(TVST, "Analog 1") field(TTVL, "13") field(TTST, "Analog 1") field(FTVL, "14") field(FTST, "Digital 1") field(FFVL, "15") field(FFST, "Digital 2") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH12:PORT") { field(DESC, "Port, ch. 12") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 12, 0) CHAN_PORT") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH12:DECODE") { field(DESC, "Decode, ch. 12") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 12, 0) CHAN_DECODE") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH12:ADDR") { field(DESC, "Address, ch. 12") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 12, 0) CHAN_ADDR") field(SCAN, "I/O Intr") } #--- Chan. 13 -------------------------------- # This record is the Nth channel's measured value. Units depend on the particular # probe and are set in the USERUNITS record below record(ai, "RADM:BSYH:843:CH13:MEAS") { field(DESC, "Meas. value, ch. 13") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 13, 0) MEAS") field(EGU, "") field(PREC, "3") field(LOLO, "") field(LOW, "") field(HIGH, "") field(HIHI, "") field(HYST, "0.5") field(LLSV, "NO_ALARM") field(LSV, "NO_ALARM") field(HSV, "MINOR") field(HHSV, "MAJOR") field(SCAN, "I/O Intr") info(autosaveFields, "LOLO LOW HIGH HIHI HYST LLSV LSV HSV HHSV") } record(longin, "RADM:BSYH:843:CH13:STATUS") { field(DESC, "Meas. val. status, ch. 13") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 13, 0) MEAS_STATUS") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH13:STATE") { field(DESC, "Channel state, ch. 13") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 13, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") field(SCAN, "I/O Intr") } record(bo, "RADM:BSYH:843:CH13:STATE_SET") { field(DESC, "Set channel state, ch. 13") field(DTYP, "asynInt32") field(OUT, "@asyn(FHT_BSYH_843, 13, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") info(asyn:READBACK, "1") } record(mbbi, "RADM:BSYH:843:CH13:DISPUNITS") { field(DESC, "Display units, ch. 13") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 13, 0) CHAN_UNITS") field(ZRVL, "0") field(ZRST, "Invalid") field(ONVL, "1") field(ONST, "Gy") field(TWVL, "2") field(TWST, "Gy/h") field(THVL, "3") field(THST, "Sv") field(FRVL, "4") field(FRST, "Sv/h") field(FVVL, "5") field(FVST, "IPS") field(SXVL, "6") field(SXST, "Bq") field(SVVL, "7") field(SVST, "Bq/cm2") field(EIVL, "8") field(EIST, "Bq/l") field(NIVL, "9") field(NIST, "R") field(TEVL, "10") field(TEST, "R/h") field(ELVL, "11") field(ELST, "User 1") field(TVVL, "12") field(TVST, "User 2") field(TTVL, "13") field(TTST, "User 3") field(FTVL, "14") field(FTST, "User 4") field(FFVL, "15") field(FFST, "User 5") field(SCAN, "I/O Intr") } # This record sets the display units record(stringout, "RADM:BSYH:843:CH13:USERUNITS") { field(DESC, "User units, ch. 13") field(OUT, "RADM:BSYH:843:CH13:MEAS.EGU PP") field(VAL, "$(EGU)") field(PINI, "1") info(autosaveFields, "VAL") } record(ai, "RADM:BSYH:843:CH13:DISPFACTOR") { field(DESC, "Display factor, ch. 13") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 13, 0) CHAN_DISP_FACT") field(EGU, "") field(PREC, "2") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH13:PREUNIT") { field(DESC, "Pre-unit, ch. 13") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 13, 0) CHAN_PREUNIT") field(ZNAM, "None") field(ONAM, "Auto") field(SCAN, "I/O Intr") } record(mbbi, "RADM:BSYH:843:CH13:PROBETYPE") { field(DESC, "Channel type, ch. 13") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 13, 0) CHAN_TYPE") field(ZRVL, "0") field(ZRST, "Unknown") field(ONVL, "1") field(ONST, "FHT 191N") field(TWVL, "2") field(TWST, "FHT 191T") field(THVL, "3") field(THST, "FHT 641D") field(FRVL, "4") field(FRST, "FHT 641P") field(FVVL, "5") field(FVST, "FHT 671 Y") field(SXVL, "6") field(SXST, "FHT 751") field(SVVL, "7") field(SVST, "FHZ 621 G-L") field(EIVL, "8") field(EIST, "FHZ 691") field(NIVL, "9") field(NIST, "SRD 2000") field(TEVL, "10") field(TEST, "FH 40G 1") field(ELVL, "11") field(ELST, "FH 40G 2") field(TVVL, "12") field(TVST, "Analog 1") field(TTVL, "13") field(TTST, "Analog 1") field(FTVL, "14") field(FTST, "Digital 1") field(FFVL, "15") field(FFST, "Digital 2") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH13:PORT") { field(DESC, "Port, ch. 13") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 13, 0) CHAN_PORT") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH13:DECODE") { field(DESC, "Decode, ch. 13") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 13, 0) CHAN_DECODE") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH13:ADDR") { field(DESC, "Address, ch. 13") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 13, 0) CHAN_ADDR") field(SCAN, "I/O Intr") } #--- Chan. 14 -------------------------------- # This record is the Nth channel's measured value. Units depend on the particular # probe and are set in the USERUNITS record below record(ai, "RADM:BSYH:843:CH14:MEAS") { field(DESC, "Meas. value, ch. 14") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 14, 0) MEAS") field(EGU, "") field(PREC, "3") field(LOLO, "") field(LOW, "") field(HIGH, "") field(HIHI, "") field(HYST, "0.5") field(LLSV, "NO_ALARM") field(LSV, "NO_ALARM") field(HSV, "MINOR") field(HHSV, "MAJOR") field(SCAN, "I/O Intr") info(autosaveFields, "LOLO LOW HIGH HIHI HYST LLSV LSV HSV HHSV") } record(longin, "RADM:BSYH:843:CH14:STATUS") { field(DESC, "Meas. val. status, ch. 14") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 14, 0) MEAS_STATUS") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH14:STATE") { field(DESC, "Channel state, ch. 14") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 14, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") field(SCAN, "I/O Intr") } record(bo, "RADM:BSYH:843:CH14:STATE_SET") { field(DESC, "Set channel state, ch. 14") field(DTYP, "asynInt32") field(OUT, "@asyn(FHT_BSYH_843, 14, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") info(asyn:READBACK, "1") } record(mbbi, "RADM:BSYH:843:CH14:DISPUNITS") { field(DESC, "Display units, ch. 14") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 14, 0) CHAN_UNITS") field(ZRVL, "0") field(ZRST, "Invalid") field(ONVL, "1") field(ONST, "Gy") field(TWVL, "2") field(TWST, "Gy/h") field(THVL, "3") field(THST, "Sv") field(FRVL, "4") field(FRST, "Sv/h") field(FVVL, "5") field(FVST, "IPS") field(SXVL, "6") field(SXST, "Bq") field(SVVL, "7") field(SVST, "Bq/cm2") field(EIVL, "8") field(EIST, "Bq/l") field(NIVL, "9") field(NIST, "R") field(TEVL, "10") field(TEST, "R/h") field(ELVL, "11") field(ELST, "User 1") field(TVVL, "12") field(TVST, "User 2") field(TTVL, "13") field(TTST, "User 3") field(FTVL, "14") field(FTST, "User 4") field(FFVL, "15") field(FFST, "User 5") field(SCAN, "I/O Intr") } # This record sets the display units record(stringout, "RADM:BSYH:843:CH14:USERUNITS") { field(DESC, "User units, ch. 14") field(OUT, "RADM:BSYH:843:CH14:MEAS.EGU PP") field(VAL, "$(EGU)") field(PINI, "1") info(autosaveFields, "VAL") } record(ai, "RADM:BSYH:843:CH14:DISPFACTOR") { field(DESC, "Display factor, ch. 14") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 14, 0) CHAN_DISP_FACT") field(EGU, "") field(PREC, "2") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH14:PREUNIT") { field(DESC, "Pre-unit, ch. 14") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 14, 0) CHAN_PREUNIT") field(ZNAM, "None") field(ONAM, "Auto") field(SCAN, "I/O Intr") } record(mbbi, "RADM:BSYH:843:CH14:PROBETYPE") { field(DESC, "Channel type, ch. 14") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 14, 0) CHAN_TYPE") field(ZRVL, "0") field(ZRST, "Unknown") field(ONVL, "1") field(ONST, "FHT 191N") field(TWVL, "2") field(TWST, "FHT 191T") field(THVL, "3") field(THST, "FHT 641D") field(FRVL, "4") field(FRST, "FHT 641P") field(FVVL, "5") field(FVST, "FHT 671 Y") field(SXVL, "6") field(SXST, "FHT 751") field(SVVL, "7") field(SVST, "FHZ 621 G-L") field(EIVL, "8") field(EIST, "FHZ 691") field(NIVL, "9") field(NIST, "SRD 2000") field(TEVL, "10") field(TEST, "FH 40G 1") field(ELVL, "11") field(ELST, "FH 40G 2") field(TVVL, "12") field(TVST, "Analog 1") field(TTVL, "13") field(TTST, "Analog 1") field(FTVL, "14") field(FTST, "Digital 1") field(FFVL, "15") field(FFST, "Digital 2") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH14:PORT") { field(DESC, "Port, ch. 14") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 14, 0) CHAN_PORT") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH14:DECODE") { field(DESC, "Decode, ch. 14") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 14, 0) CHAN_DECODE") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH14:ADDR") { field(DESC, "Address, ch. 14") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 14, 0) CHAN_ADDR") field(SCAN, "I/O Intr") } #--- Chan. 15 -------------------------------- # This record is the Nth channel's measured value. Units depend on the particular # probe and are set in the USERUNITS record below record(ai, "RADM:BSYH:843:CH15:MEAS") { field(DESC, "Meas. value, ch. 15") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 15, 0) MEAS") field(EGU, "") field(PREC, "3") field(LOLO, "") field(LOW, "") field(HIGH, "") field(HIHI, "") field(HYST, "0.5") field(LLSV, "NO_ALARM") field(LSV, "NO_ALARM") field(HSV, "MINOR") field(HHSV, "MAJOR") field(SCAN, "I/O Intr") info(autosaveFields, "LOLO LOW HIGH HIHI HYST LLSV LSV HSV HHSV") } record(longin, "RADM:BSYH:843:CH15:STATUS") { field(DESC, "Meas. val. status, ch. 15") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 15, 0) MEAS_STATUS") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH15:STATE") { field(DESC, "Channel state, ch. 15") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 15, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") field(SCAN, "I/O Intr") } record(bo, "RADM:BSYH:843:CH15:STATE_SET") { field(DESC, "Set channel state, ch. 15") field(DTYP, "asynInt32") field(OUT, "@asyn(FHT_BSYH_843, 15, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") info(asyn:READBACK, "1") } record(mbbi, "RADM:BSYH:843:CH15:DISPUNITS") { field(DESC, "Display units, ch. 15") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 15, 0) CHAN_UNITS") field(ZRVL, "0") field(ZRST, "Invalid") field(ONVL, "1") field(ONST, "Gy") field(TWVL, "2") field(TWST, "Gy/h") field(THVL, "3") field(THST, "Sv") field(FRVL, "4") field(FRST, "Sv/h") field(FVVL, "5") field(FVST, "IPS") field(SXVL, "6") field(SXST, "Bq") field(SVVL, "7") field(SVST, "Bq/cm2") field(EIVL, "8") field(EIST, "Bq/l") field(NIVL, "9") field(NIST, "R") field(TEVL, "10") field(TEST, "R/h") field(ELVL, "11") field(ELST, "User 1") field(TVVL, "12") field(TVST, "User 2") field(TTVL, "13") field(TTST, "User 3") field(FTVL, "14") field(FTST, "User 4") field(FFVL, "15") field(FFST, "User 5") field(SCAN, "I/O Intr") } # This record sets the display units record(stringout, "RADM:BSYH:843:CH15:USERUNITS") { field(DESC, "User units, ch. 15") field(OUT, "RADM:BSYH:843:CH15:MEAS.EGU PP") field(VAL, "$(EGU)") field(PINI, "1") info(autosaveFields, "VAL") } record(ai, "RADM:BSYH:843:CH15:DISPFACTOR") { field(DESC, "Display factor, ch. 15") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 15, 0) CHAN_DISP_FACT") field(EGU, "") field(PREC, "2") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH15:PREUNIT") { field(DESC, "Pre-unit, ch. 15") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 15, 0) CHAN_PREUNIT") field(ZNAM, "None") field(ONAM, "Auto") field(SCAN, "I/O Intr") } record(mbbi, "RADM:BSYH:843:CH15:PROBETYPE") { field(DESC, "Channel type, ch. 15") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 15, 0) CHAN_TYPE") field(ZRVL, "0") field(ZRST, "Unknown") field(ONVL, "1") field(ONST, "FHT 191N") field(TWVL, "2") field(TWST, "FHT 191T") field(THVL, "3") field(THST, "FHT 641D") field(FRVL, "4") field(FRST, "FHT 641P") field(FVVL, "5") field(FVST, "FHT 671 Y") field(SXVL, "6") field(SXST, "FHT 751") field(SVVL, "7") field(SVST, "FHZ 621 G-L") field(EIVL, "8") field(EIST, "FHZ 691") field(NIVL, "9") field(NIST, "SRD 2000") field(TEVL, "10") field(TEST, "FH 40G 1") field(ELVL, "11") field(ELST, "FH 40G 2") field(TVVL, "12") field(TVST, "Analog 1") field(TTVL, "13") field(TTST, "Analog 1") field(FTVL, "14") field(FTST, "Digital 1") field(FFVL, "15") field(FFST, "Digital 2") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH15:PORT") { field(DESC, "Port, ch. 15") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 15, 0) CHAN_PORT") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH15:DECODE") { field(DESC, "Decode, ch. 15") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 15, 0) CHAN_DECODE") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH15:ADDR") { field(DESC, "Address, ch. 15") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 15, 0) CHAN_ADDR") field(SCAN, "I/O Intr") } #--- Chan. 16 -------------------------------- # This record is the Nth channel's measured value. Units depend on the particular # probe and are set in the USERUNITS record below record(ai, "RADM:BSYH:843:CH16:MEAS") { field(DESC, "Meas. value, ch. 16") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 16, 0) MEAS") field(EGU, "") field(PREC, "3") field(LOLO, "") field(LOW, "") field(HIGH, "") field(HIHI, "") field(HYST, "0.5") field(LLSV, "NO_ALARM") field(LSV, "NO_ALARM") field(HSV, "MINOR") field(HHSV, "MAJOR") field(SCAN, "I/O Intr") info(autosaveFields, "LOLO LOW HIGH HIHI HYST LLSV LSV HSV HHSV") } record(longin, "RADM:BSYH:843:CH16:STATUS") { field(DESC, "Meas. val. status, ch. 16") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 16, 0) MEAS_STATUS") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH16:STATE") { field(DESC, "Channel state, ch. 16") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 16, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") field(SCAN, "I/O Intr") } record(bo, "RADM:BSYH:843:CH16:STATE_SET") { field(DESC, "Set channel state, ch. 16") field(DTYP, "asynInt32") field(OUT, "@asyn(FHT_BSYH_843, 16, 0) CHAN_STATE") field(ZNAM, "Not Active") field(ONAM, "Active") field(ZSV, "MINOR") info(asyn:READBACK, "1") } record(mbbi, "RADM:BSYH:843:CH16:DISPUNITS") { field(DESC, "Display units, ch. 16") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 16, 0) CHAN_UNITS") field(ZRVL, "0") field(ZRST, "Invalid") field(ONVL, "1") field(ONST, "Gy") field(TWVL, "2") field(TWST, "Gy/h") field(THVL, "3") field(THST, "Sv") field(FRVL, "4") field(FRST, "Sv/h") field(FVVL, "5") field(FVST, "IPS") field(SXVL, "6") field(SXST, "Bq") field(SVVL, "7") field(SVST, "Bq/cm2") field(EIVL, "8") field(EIST, "Bq/l") field(NIVL, "9") field(NIST, "R") field(TEVL, "10") field(TEST, "R/h") field(ELVL, "11") field(ELST, "User 1") field(TVVL, "12") field(TVST, "User 2") field(TTVL, "13") field(TTST, "User 3") field(FTVL, "14") field(FTST, "User 4") field(FFVL, "15") field(FFST, "User 5") field(SCAN, "I/O Intr") } # This record sets the display units record(stringout, "RADM:BSYH:843:CH16:USERUNITS") { field(DESC, "User units, ch. 16") field(OUT, "RADM:BSYH:843:CH16:MEAS.EGU PP") field(VAL, "$(EGU)") field(PINI, "1") info(autosaveFields, "VAL") } record(ai, "RADM:BSYH:843:CH16:DISPFACTOR") { field(DESC, "Display factor, ch. 16") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 16, 0) CHAN_DISP_FACT") field(EGU, "") field(PREC, "2") field(SCAN, "I/O Intr") } record(bi, "RADM:BSYH:843:CH16:PREUNIT") { field(DESC, "Pre-unit, ch. 16") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 16, 0) CHAN_PREUNIT") field(ZNAM, "None") field(ONAM, "Auto") field(SCAN, "I/O Intr") } record(mbbi, "RADM:BSYH:843:CH16:PROBETYPE") { field(DESC, "Channel type, ch. 16") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 16, 0) CHAN_TYPE") field(ZRVL, "0") field(ZRST, "Unknown") field(ONVL, "1") field(ONST, "FHT 191N") field(TWVL, "2") field(TWST, "FHT 191T") field(THVL, "3") field(THST, "FHT 641D") field(FRVL, "4") field(FRST, "FHT 641P") field(FVVL, "5") field(FVST, "FHT 671 Y") field(SXVL, "6") field(SXST, "FHT 751") field(SVVL, "7") field(SVST, "FHZ 621 G-L") field(EIVL, "8") field(EIST, "FHZ 691") field(NIVL, "9") field(NIST, "SRD 2000") field(TEVL, "10") field(TEST, "FH 40G 1") field(ELVL, "11") field(ELST, "FH 40G 2") field(TVVL, "12") field(TVST, "Analog 1") field(TTVL, "13") field(TTST, "Analog 1") field(FTVL, "14") field(FTST, "Digital 1") field(FFVL, "15") field(FFST, "Digital 2") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH16:PORT") { field(DESC, "Port, ch. 16") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 16, 0) CHAN_PORT") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH16:DECODE") { field(DESC, "Decode, ch. 16") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 16, 0) CHAN_DECODE") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:CH16:ADDR") { field(DESC, "Address, ch. 16") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 16, 0) CHAN_ADDR") field(SCAN, "I/O Intr") } #--- 40G port 01 -------------------------------------- record(ai, "RADM:BSYH:843:40G01:MEAS") { field(DESC, "Meas. value, 40G port 01") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 1, 0) MEAS_40G") # field(EGU, "uSv/h") field(PREC, "3") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:40G01:STATUS") { field(DESC, "Meas. val. status, 40G port 01") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 1, 0) MEAS_STATUS_40G") field(SCAN, "I/O Intr") } record(ai, "RADM:BSYH:843:40G01:SAMPLETIME") { field(DESC, "Meas. time, 40G port 01") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 1, 0) MEAS_TIME_40G") field(EGU, "s") field(PREC, "0") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:40G01:PROBETYPE") { field(DESC, "Probe type, 40G port 01") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 1, 0) TYPE_40G") field(SCAN, "I/O Intr") } record(ai, "RADM:BSYH:843:40G01:CALFACT") { field(DESC, "Probe cal. factor, 40G port 01") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 1, 0) CAL_FACT_40G") field(EGU, "") field(PREC, "2") field(SCAN, "I/O Intr") } record(ai, "RADM:BSYH:843:40G01:DEADTIME") { field(DESC, "Probe dead time, 40G port 01") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 1, 0) DEAD_TIME_40G") field(EGU, "") field(PREC, "2") field(SCAN, "I/O Intr") } record(ai, "RADM:BSYH:843:40G01:DYNRNG") { field(DESC, "Probe dyn. range, 40G port 01") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 1, 0) DYN_RNG_40G") field(EGU, "") field(PREC, "2") field(SCAN, "I/O Intr") } record(ai, "RADM:BSYH:843:40G01:THRESH") { field(DESC, "Probe sw. thresh., 40G port 01") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 1, 0) SW_THR_40G") field(EGU, "") field(PREC, "2") field(SCAN, "I/O Intr") } record(stringin, "RADM:BSYH:843:40G01:CALDATE") { field(DESC, "Probe cal. date, 40G port 01") field(DTYP, "asynOctetRead") field(INP, "@asyn(FHT_BSYH_843, 1, 0) CAL_DATE_40G") field(SCAN, "I/O Intr") } #--- 40G port 02 -------------------------------------- record(ai, "RADM:BSYH:843:40G02:MEAS") { field(DESC, "Meas. value, 40G port 02") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 2, 0) MEAS_40G") # field(EGU, "uSv/h") field(PREC, "3") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:40G02:STATUS") { field(DESC, "Meas. val. status, 40G port 02") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 2, 0) MEAS_STATUS_40G") field(SCAN, "I/O Intr") } record(ai, "RADM:BSYH:843:40G02:SAMPLETIME") { field(DESC, "Meas. time, 40G port 02") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 2, 0) MEAS_TIME_40G") field(EGU, "s") field(PREC, "0") field(SCAN, "I/O Intr") } record(longin, "RADM:BSYH:843:40G02:PROBETYPE") { field(DESC, "Probe type, 40G port 02") field(DTYP, "asynInt32") field(INP, "@asyn(FHT_BSYH_843, 2, 0) TYPE_40G") field(SCAN, "I/O Intr") } record(ai, "RADM:BSYH:843:40G02:CALFACT") { field(DESC, "Probe cal. factor, 40G port 02") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 2, 0) CAL_FACT_40G") field(EGU, "") field(PREC, "2") field(SCAN, "I/O Intr") } record(ai, "RADM:BSYH:843:40G02:DEADTIME") { field(DESC, "Probe dead time, 40G port 02") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 2, 0) DEAD_TIME_40G") field(EGU, "") field(PREC, "2") field(SCAN, "I/O Intr") } record(ai, "RADM:BSYH:843:40G02:DYNRNG") { field(DESC, "Probe dyn. range, 40G port 02") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 2, 0) DYN_RNG_40G") field(EGU, "") field(PREC, "2") field(SCAN, "I/O Intr") } record(ai, "RADM:BSYH:843:40G02:THRESH") { field(DESC, "Probe sw. thresh., 40G port 02") field(DTYP, "asynFloat64") field(INP, "@asyn(FHT_BSYH_843, 2, 0) SW_THR_40G") field(EGU, "") field(PREC, "2") field(SCAN, "I/O Intr") } record(stringin, "RADM:BSYH:843:40G02:CALDATE") { field(DESC, "Probe cal. date, 40G port 02") field(DTYP, "asynOctetRead") field(INP, "@asyn(FHT_BSYH_843, 2, 0) CAL_DATE_40G") field(SCAN, "I/O Intr") } record(mbbo, "RADM:BSYH:843:CH_DISP01") { field(DESC, "Select Channel to display") field(ZRVL, "0") field(ZRST, "1") field(ONVL, "1") field(ONST, "2") field(TWVL, "2") field(TWST, "3") field(THVL, "3") field(THST, "4") field(FRVL, "4") field(FRST, "5") field(FVVL, "5") field(FVST, "6") field(SXVL, "6") field(SXST, "7") field(SVVL, "7") field(SVST, "8") field(EIVL, "8") field(EIST, "9") field(NIVL, "9") field(NIST, "10") field(TEVL, "10") field(TEST, "11") field(ELVL, "11") field(ELST, "12") field(TVVL, "12") field(TVST, "13") field(TTVL, "13") field(TTST, "14") field(FTVL, "14") field(FTST, "15") field(FTVL, "15") field(FTST, "16") field(VAL, "0") field(PINI, "1") info(autosaveFields, "VAL") } record(mbbo, "RADM:BSYH:843:CH_DISP02") { field(DESC, "Select Channel to display") field(ZRVL, "0") field(ZRST, "1") field(ONVL, "1") field(ONST, "2") field(TWVL, "2") field(TWST, "3") field(THVL, "3") field(THST, "4") field(FRVL, "4") field(FRST, "5") field(FVVL, "5") field(FVST, "6") field(SXVL, "6") field(SXST, "7") field(SVVL, "7") field(SVST, "8") field(EIVL, "8") field(EIST, "9") field(NIVL, "9") field(NIST, "10") field(TEVL, "10") field(TEST, "11") field(ELVL, "11") field(ELST, "12") field(TVVL, "12") field(TVST, "13") field(TTVL, "13") field(TTST, "14") field(FTVL, "14") field(FTST, "15") field(FTVL, "15") field(FTST, "16") field(VAL, "0") field(PINI, "1") info(autosaveFields, "VAL") } record(mbbo, "RADM:BSYH:843:CH_DISP03") { field(DESC, "Select Channel to display") field(ZRVL, "0") field(ZRST, "1") field(ONVL, "1") field(ONST, "2") field(TWVL, "2") field(TWST, "3") field(THVL, "3") field(THST, "4") field(FRVL, "4") field(FRST, "5") field(FVVL, "5") field(FVST, "6") field(SXVL, "6") field(SXST, "7") field(SVVL, "7") field(SVST, "8") field(EIVL, "8") field(EIST, "9") field(NIVL, "9") field(NIST, "10") field(TEVL, "10") field(TEST, "11") field(ELVL, "11") field(ELST, "12") field(TVVL, "12") field(TVST, "13") field(TTVL, "13") field(TTST, "14") field(FTVL, "14") field(FTST, "15") field(FTVL, "15") field(FTST, "16") field(VAL, "0") field(PINI, "1") info(autosaveFields, "VAL") }