#--- Device info ------------------------
record(stringout, "RADM:SITE:$(UNIT):LOCATION") {
    field(DESC, "Device location")
    field(VAL,  "Site")
    field(PINI, "1")
    info(autosaveFields, "VAL")
}

record(mbbo, "RADM:SITE:$(UNIT):TYPE") {
    field(DESC, "Device type")
    field(ZRVL, "0")
    field(ZRST, "Thermo FHT")
    field(ONVL, "1")
    field(ONST, "RadFET")
    field(TWVL, "2")
    field(TWST, "Air Mon Sys")
    field(THVL, "3")
    field(THST, "Periphal Mon Sys")
    field(FRVL, "4")
    field(FRST, "714 Gamma Detector")
    field(FVVL, "5")
    field(FVST, "Moveable Station")
    field(VAL,  "5")
    field(PINI, "1")
    info(autosaveFields, "VAL")
}

record(stringin, "RADM:SITE:$(UNIT):GENERIC_COMMAND") {
  field(DESC, "Generic Command interface")
  field(DTYP, "stream")
  field(INP, "@FHT6020.proto genericCommand(01) $(FPORT)")
}

record(mbbiDirect, "RADM:SITE:$(UNIT):SYSTEM_STATUS") {
  field(DESC, "Device System Status")
  field(FLNK, "RADM:SITE:$(UNIT):RESET_STATUS")
}

record(bi, "RADM:SITE:$(UNIT):RESET_STATUS") {
  field(DESC, "System Reset Status")
  field(DTYP, "Soft Channel")
  field(INP,  "RADM:SITE:$(UNIT):SYSTEM_STATUS.B0")
  field(ZNAM, "OK")
  field(ONAM, "Reset occured")
  field(OSV,  "MAJOR")
  field(FLNK, "RADM:SITE:$(UNIT):PROM_STATUS")
}

record(bi, "RADM:SITE:$(UNIT):PROM_STATUS") {
  field(DESC, "PROM Error Status")
  field(DTYP, "Soft Channel")
  field(INP,  "RADM:SITE:$(UNIT):SYSTEM_STATUS.B1")
  field(ZNAM, "OK")
  field(ONAM, "PROM Error")
  field(OSV,  "MAJOR")
  field(FLNK, "RADM:SITE:$(UNIT):RAM_STATUS")
}

record(bi, "RADM:SITE:$(UNIT):RAM_STATUS") {
  field(DESC, "RAM Error Status")
  field(DTYP, "Soft Channel")
  field(INP,  "RADM:SITE:$(UNIT):SYSTEM_STATUS.B2")
  field(ZNAM, "OK")
  field(ONAM, "RAM Error")
  field(OSV,  "MAJOR")
  field(FLNK, "RADM:SITE:$(UNIT):CONFIG_STATUS")
}

record(bi, "RADM:SITE:$(UNIT):CONFIG_STATUS") {
  field(DESC, "Configuration Status")
  field(DTYP, "Soft Channel")
  field(INP,  "RADM:SITE:$(UNIT):SYSTEM_STATUS.B3")
  field(ZNAM, "OK")
  field(ONAM, "Configuration Error")
  field(OSV,  "MAJOR")
  field(FLNK, "RADM:SITE:$(UNIT):HIST_CLEAR_STATUS")
}

record(bi, "RADM:SITE:$(UNIT):HIST_CLEAR_STATUS") {
  field(DESC, "History Clear Status")
  field(DTYP, "Soft Channel")
  field(INP,  "RADM:SITE:$(UNIT):SYSTEM_STATUS.B4")
  field(ZNAM, "OK")
  field(ONAM, "History Cleared")
  field(OSV,  "MAJOR")
  field(FLNK, "RADM:SITE:$(UNIT):BATTERY_STATUS")
}

record(bi, "RADM:SITE:$(UNIT):BATTERY_STATUS") {
  field(DESC, "Battery Voltage Status")
  field(DTYP, "Soft Channel")
  field(INP,  "RADM:SITE:$(UNIT):SYSTEM_STATUS.B5")
  field(ZNAM, "OK")
  field(ONAM, "Low Battery")
  field(OSV,  "MAJOR")
  field(FLNK, "RADM:SITE:$(UNIT):ALARM2_STATUS")
}

record(bi, "RADM:SITE:$(UNIT):ALARM2_STATUS") {
  field(DESC, "Alarm 2 Status")
  field(DTYP, "Soft Channel")
  field(INP,  "RADM:SITE:$(UNIT):SYSTEM_STATUS.BC")
  field(ZNAM, "OK")
  field(ONAM, "Alarm 2 occured")
  field(OSV,  "MAJOR")
  field(FLNK, "RADM:SITE:$(UNIT):ALARM1_STATUS")
}

record(bi, "RADM:SITE:$(UNIT):ALARM1_STATUS") {
  field(DESC, "Alarm 1 Status")
  field(DTYP, "Soft Channel")
  field(INP,  "RADM:SITE:$(UNIT):SYSTEM_STATUS.BD")
  field(ZNAM, "OK")
  field(ONAM, "Alarm 1 occured")
  field(OSV,  "MAJOR")
  field(FLNK, "RADM:SITE:$(UNIT):ERROR_STATUS")
}

record(bi, "RADM:SITE:$(UNIT):ERROR_STATUS") {
  field(DESC, "System Error Status")
  field(DTYP, "Soft Channel")
  field(INP,  "RADM:SITE:$(UNIT):SYSTEM_STATUS.BF")
  field(ZNAM, "OK")
  field(ONAM, "Error occured")
  field(OSV,  "MAJOR")
  field(FLNK, "RADM:SITE:$(UNIT):SYSTEM_ERRORCNT")
}

record(calcout, "RADM:SITE:$(UNIT):SYSTEM_ERRORCNT") {
  field(DESC, "Total num of system errors")
  field(INPA, "RADM:SITE:$(UNIT):RESET_STATUS")
  field(INPB, "RADM:SITE:$(UNIT):PROM_STATUS")
  field(INPC, "RADM:SITE:$(UNIT):RAM_STATUS")
  field(INPD, "RADM:SITE:$(UNIT):CONFIG_STATUS")
  field(INPE, "RADM:SITE:$(UNIT):HIST_CLEAR_STATUS")
  field(INPF, "RADM:SITE:$(UNIT):BATTERY_STATUS")
  field(INPG, "RADM:SITE:$(UNIT):ALARM2_STATUS")
  field(INPH, "RADM:SITE:$(UNIT):ALARM1_STATUS")
  field(INPI, "RADM:SITE:$(UNIT):ERROR_STATUS")
  field(CALC, "A+B+C+D+E+F+G+H+I")
  field(OCAL, "A+B+C+D+E+F+G+H+I > 0 ? 1 : 0")
  field(OUT,  "RADM:SITE:$(UNIT):SYSTEM_SUMMARY")
  field(FLNK, "RADM:SITE:$(UNIT):SYSTEM_SUMMARY")
}

record(bi, "RADM:SITE:$(UNIT):SYSTEM_SUMMARY") {
  field(DESC, "Summary of system error status")
  field(ZNAM, "No errors")
  field(ONAM, "System error")
  field(OSV,  "MAJOR")
}

record(ai, "RADM:SITE:$(UNIT):CH01:MEAS") {
  field(DESC, "Channel 01 Measured Value")
  field(EGU,  "mrem/h")
  field(LINR, "SLOPE")
  field(ASLO, "1.00")
  field(AOFF, "0")
  field(DTYP, "stream")
  field(INP,  "@FHT6020.proto getValue(01,01,RADM:SITE:$(UNIT):CH01) $(FPORT)")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(PREC, "5")
}

record(mbbiDirect, "RADM:SITE:$(UNIT):CH01:STATUS") {
  field(DESC, "Channel 01 System Status")
  field(FLNK, "RADM:SITE:$(UNIT):CH01:EEPROM")
}

record(bi, "RADM:SITE:$(UNIT):CH01:EEPROM") {
  field(DESC, "Probe EEPROM status")
  field(DTYP, "Soft Channel")
  field(INP,  "RADM:SITE:$(UNIT):CH01:STATUS.B8")
  field(ZNAM, "OK")
  field(ONAM, "EEPROM error")
  field(OSV,  "MAJOR")
  field(FLNK, "RADM:SITE:$(UNIT):CH01:SIGNAL")
}

record(bi, "RADM:SITE:$(UNIT):CH01:SIGNAL") {
  field(DESC, "Probe signal status")
  field(DTYP, "Soft Channel")
  field(INP,  "RADM:SITE:$(UNIT):CH01:STATUS.B9")
  field(ZNAM, "OK")
  field(ONAM, "Below failure threshold")
  field(OSV,  "MAJOR")
  field(FLNK, "RADM:SITE:$(UNIT):CH01:LOW")
}

record(bi, "RADM:SITE:$(UNIT):CH01:LOW") {
  field(DESC, "Probe out of range")
  field(DTYP, "Soft Channel")
  field(INP,  "RADM:SITE:$(UNIT):CH01:STATUS.BA")
  field(ZNAM, "OK")
  field(ONAM, "Below measuring range")
  field(OSV,  "MAJOR")
  field(FLNK, "RADM:SITE:$(UNIT):CH01:HIGH")
}

record(bi, "RADM:SITE:$(UNIT):CH01:HIGH") {
  field(DESC, "Probe out of range")
  field(DTYP, "Soft Channel")
  field(INP,  "RADM:SITE:$(UNIT):CH01:STATUS.BB")
  field(ZNAM, "OK")
  field(ONAM, "Above measuring range")
  field(OSV,  "MAJOR")
  field(FLNK, "RADM:SITE:$(UNIT):CH01:CONNECTED")
}

record(bi, "RADM:SITE:$(UNIT):CH01:CONNECTED") {
  field(DESC, "Probe connection status")
  field(DTYP, "Soft Channel")
  field(INP, "RADM:SITE:$(UNIT):CH01:STATUS.BE")
  field(ZNAM, "OK")
  field(ONAM, "Transfer error")
  field(OSV,  "MAJOR")
  field(FLNK, "RADM:SITE:$(UNIT):CH01:NBR")
}

record(bi, "RADM:SITE:$(UNIT):CH01:NBR"){ 
  field(DESC, "Background radiation alarm")
  field(DTYP, "Soft Channel")
  field(INP, "RADM:SITE:$(UNIT):CH01:STATUS.BF")
  field(ZNAM, "OK")
  field(ONAM, "Artificial radiation")
  field(OSV,  "MAJOR")
  field(FLNK, "RADM:SITE:$(UNIT):CH01:ERRORCNT")
}

record(calcout, "RADM:SITE:$(UNIT):CH01:ERRORCNT") {
  field(DESC, "Total num of channel 01 errors")
  field(INPA, "RADM:SITE:$(UNIT):CH01:EEPROM")
  field(INPB, "RADM:SITE:$(UNIT):CH01:SIGNAL")
  field(INPC, "RADM:SITE:$(UNIT):CH01:LOW")
  field(INPD, "RADM:SITE:$(UNIT):CH01:HIGH")
  field(INPE, "RADM:SITE:$(UNIT):CH01:CONNECTED")
  field(INPF, "RADM:SITE:$(UNIT):CH01:NBR")
  field(CALC, "A+B+C+D+E+F")
  field(OCAL, "A+B+C+D+E+F > 0 ? 1 : 0")
  field(OUT,  "RADM:SITE:$(UNIT):CH01:SUMMARY")
  field(FLNK, "RADM:SITE:$(UNIT):CH01:SUMMARY")
}

record(bi, "RADM:SITE:$(UNIT):CH01:SUMMARY") {
  field(DESC, "Summary of channel 01 error status")
  field(ZNAM, "No errors")
  field(ONAM, "Channel 01 error")
  field(OSV,  "MAJOR")
}

record(mbboDirect, "RADM:SITE:$(UNIT):CH01:LED") {
  field(DESC, "Channel 01 System/LED Status")
  field(DTYP, "Soft Channel")
  field(OUT,  "RADM:SITE:$(UNIT):SYSTEM_STATUS")
  field(FLNK, "RADM:SITE:$(UNIT):SYSTEM_STATUS")
}

record(ai, "RADM:SITE:$(UNIT):CH02:MEAS") {
  field(DESC, "Channel 02 Measured Value")
  field(EGU,  "mrem/h")
  field(LINR, "SLOPE")
  field(ASLO, "1.00")
  field(AOFF, "0")
  field(DTYP, "stream")
  field(INP,  "@FHT6020.proto getValue(01,02,RADM:SITE:$(UNIT):CH02) $(FPORT)")
  field(SCAN, "1 second")
  field(PINI, "YES")
  field(PREC, "5")
}

record(mbbiDirect, "RADM:SITE:$(UNIT):CH02:STATUS") {
  field(DESC, "Channel 02 System Status")
  field(FLNK, "RADM:SITE:$(UNIT):CH02:EEPROM")
}

record(bi, "RADM:SITE:$(UNIT):CH02:EEPROM") {
  field(DESC, "Probe EEPROM status")
  field(DTYP, "Soft Channel")
  field(INP,  "RADM:SITE:$(UNIT):CH02:STATUS.B8")
  field(ZNAM, "OK")
  field(ONAM, "EEPROM error")
  field(OSV,  "MAJOR")
  field(FLNK, "RADM:SITE:$(UNIT):CH02:SIGNAL")
}

record(bi, "RADM:SITE:$(UNIT):CH02:SIGNAL") {
  field(DESC, "Probe signal status")
  field(DTYP, "Soft Channel")
  field(INP,  "RADM:SITE:$(UNIT):CH02:STATUS.B9")
  field(ZNAM, "OK")
  field(ONAM, "Below failure threshold")
  field(OSV,  "MAJOR")
  field(FLNK, "RADM:SITE:$(UNIT):CH02:LOW")
}

record(bi, "RADM:SITE:$(UNIT):CH02:LOW") {
  field(DESC, "Probe out of range")
  field(DTYP, "Soft Channel")
  field(INP,  "RADM:SITE:$(UNIT):CH02:STATUS.BA")
  field(ZNAM, "OK")
  field(ONAM, "Below measuring range")
  field(OSV,  "MAJOR")
  field(FLNK, "RADM:SITE:$(UNIT):CH02:HIGH")
}

record(bi, "RADM:SITE:$(UNIT):CH02:HIGH") {
  field(DESC, "Probe out of range")
  field(DTYP, "Soft Channel")
  field(INP,  "RADM:SITE:$(UNIT):CH02:STATUS.BB")
  field(ZNAM, "OK")
  field(ONAM, "Above measuring range")
  field(OSV,  "MAJOR")
  field(FLNK, "RADM:SITE:$(UNIT):CH02:CONNECTED")
}

record(bi, "RADM:SITE:$(UNIT):CH02:CONNECTED") {
  field(DESC, "Probe connection status")
  field(DTYP, "Soft Channel")
  field(INP, "RADM:SITE:$(UNIT):CH02:STATUS.BE")
  field(ZNAM, "OK")
  field(ONAM, "Transfer error")
  field(OSV,  "MAJOR")
  field(FLNK, "RADM:SITE:$(UNIT):CH02:NBR")
}

record(bi, "RADM:SITE:$(UNIT):CH02:NBR"){ 
  field(DESC, "Background radiation alarm")
  field(DTYP, "Soft Channel")
  field(INP, "RADM:SITE:$(UNIT):CH02:STATUS.BF")
  field(ZNAM, "OK")
  field(ONAM, "Artificial radiation")
  field(OSV,  "MAJOR")
  field(FLNK, "RADM:SITE:$(UNIT):CH02:ERRORCNT")
}

record(calcout, "RADM:SITE:$(UNIT):CH02:ERRORCNT") {
  field(DESC, "Total num of channel 02 errors")
  field(INPA, "RADM:SITE:$(UNIT):CH02:EEPROM")
  field(INPB, "RADM:SITE:$(UNIT):CH02:SIGNAL")
  field(INPC, "RADM:SITE:$(UNIT):CH02:LOW")
  field(INPD, "RADM:SITE:$(UNIT):CH02:HIGH")
  field(INPE, "RADM:SITE:$(UNIT):CH02:CONNECTED")
  field(INPF, "RADM:SITE:$(UNIT):CH02:NBR")
  field(CALC, "A+B+C+D+E+F")
  field(OCAL, "A+B+C+D+E+F > 0 ? 1 : 0")
  field(OUT,  "RADM:SITE:$(UNIT):CH02:SUMMARY")
  field(FLNK, "RADM:SITE:$(UNIT):CH02:SUMMARY")
}

record(bi, "RADM:SITE:$(UNIT):CH02:SUMMARY") {
  field(DESC, "Summary of channel 02 error status")
  field(ZNAM, "No errors")
  field(ONAM, "Channel 02 error")
  field(OSV,  "MAJOR")
}

record(mbboDirect, "RADM:SITE:$(UNIT):CH02:LED") {
  field(DESC, "Channel 02 System/LED Status")
  field(DTYP, "Soft Channel")
  field(OUT,  "RADM:SITE:$(UNIT):SYSTEM_STATUS")
  field(FLNK, "RADM:SITE:$(UNIT):SYSTEM_STATUS")
}

record(ai, "STAT:$(UNIT):TIMEOUT_THRESH"){
      field(DESC, "Timeout Threshold Seconds")
      field(VAL, 3600)
}

record(calc, "STAT:$(UNIT):TIMEOUT_CNT") {
  field(DESC, "Counts number of timeouts from station")
  field(SCAN, "1 second")
  field(INPA, "RADM:SITE:$(UNIT):CH01:MEAS.SEVR")
  field(INPB, "RADM:SITE:$(UNIT):CH02:MEAS.SEVR")
  #if invalid increment count otherwise let it be
  field(CALC, "(A=3||B=3) ? VAL + 1 : VAL ")
  field(HIGH, 6)
  field(HIHI, 3600)
  field(HSV,MINOR)
  field(HHSV,MAJOR)
  field(VAL, 0)
}

record(calcout, "STAT:$(UNIT):TIMER"){
  field(DESC, "Timer for timeout counter")
  field(SCAN, "1 second")
  field(INPA, "STAT:$(UNIT):TIMEOUT_THRESH")
  field(VAL,   0)
  field(CALC, "(VAL + 1) % A")
  field(OOPT, "Transition To Zero")
  field(OUT , "STAT:$(UNIT):TIMEOUT_CNT")
}

record(calcout, "STAT:$(UNIT):CALC_SUM") {
  field(DESC, "Calc's overall station status")
  field(SCAN, "1 second")
  field(CALC, "A ||  B  || (C && D) || E")
  field(INPA, "RADM:SITE:$(UNIT):CH01:STATUS MS")
  field(INPB, "RADM:SITE:$(UNIT):CH02:STATUS MS")
  field(INPC, "RADM:SITE:$(UNIT):CH01:MEAS.SEVR MS")
  field(INPD, "RADM:SITE:$(UNIT):CH02:MEAS.SEVR MS")
  field(INPE, "RADM:SITE:$(UNIT):SYSTEM_SUMMARY MS")
  field(OUT, "STAT:$(UNIT):SUMMARY PP MS")
  field(IVOA, "Set output to IVOV")
  field(IVOV, "1")
}

record(bo, "STAT:$(UNIT):SUMMARY") {
  field(ZNAM, "Okay")
  field(ONAM, "Not Okay")
  field(OSV,  "MAJOR")
}