# intlk_count.template:
#
# Interlock fault counters
#----------------------------------
#==================================

#==================================
#
#==================================

record(longin, "$(PREF)$(SIG)_CNT_DELTA") {
  field(DESC, "Latest fault count")
  field(DTYP, "FEED Register Read")
  field(SCAN, "1 second")
  field(INP , "@name=$(NAME) reg=$(CNTREG)")
  field(FLNK, "$(PREF)$(SIG)_CNT_DELTASUB")
  info(feed:info:input, "$(PREF)$(SIG)_CNT_DELTA")
}

record(bi, "$(PREF)$(SIG)_CNTPV") {
  field(DESC, "$(SIG) previous valid state")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(bi, "$(PREF)$(SIG)_CNTP") {
  field(DESC, "$(SIG) previous state stored")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(bi, "$(PREF)$(SIG)_FLTV") {
  field(DESC, "$(SIG) value indicating fault")
  field(PINI, "YES")
  field(VAL, "$(FLTVAL)")
}

record(bi, "$(PREF)$(SIG)_BYPV") {
  field(DESC, "$(SIG) value indicating bypassed")
  field(PINI, "YES")
  field(VAL, "$(BYPVAL)")
}

record(bi, "$(PREF)$(SIG)_CNTET") {
  field(DESC, "$(SIG) increment counter every time")
  field(PINI, "YES")
  field(VAL, "$(ET=0)")
}

record(aSub, "$(PREF)$(SIG)_CNTSUB") {
  field(DESC, "$(SIG) fault count increment")
  field(INAM, "")
  field(SNAM, "Determine Fault Increment")
  field(SCAN, "Passive")
# Inputs
  field(FTA, "SHORT") 
# Include CP specificer in FLT macro if desired
  field(INPA, "$(FLT)")
  field(FTB, "SHORT") 
# Include CP specificer in BYP macro if desired
  field(INPB, "$(BYP)")
  field(FTC, "SHORT") 
  field(INPC, "$(PREF)$(SIG)_CNTPV")
  field(FTD, "SHORT") 
  field(INPD, "$(PREF)$(SIG)_FLTV")
  field(FTE, "SHORT") 
  field(INPE, "$(PREF)$(SIG)_BYPV")
  field(FTF, "SHORT") 
  field(INPF, "$(PREF)$(SIG)_CNTP")
  field(FTG, "SHORT") 
  field(INPG, "$(PREF)$(SIG)_CNTET")
# Outputs
# VALA = New 'previous' stored fault state
  field(FTVA, "SHORT")
  field(OUTA, "$(PREF)$(SIG)_CNTPV PP")
# VALB = Flag indicating states stored at least once
  field(FTVB, "SHORT")
  field(OUTB, "$(PREF)$(SIG)_CNTP PP")
# VALC = Increment fault counters
  field(FTVC, "SHORT")
  field(OUTC, "$(PREF)$(SIG)_CNTFO PP")
}

record(fanout, "$(PREF)$(SIG)_CNTFO") {
  field(DESC, "$(SIG) fault count")
  field(SELM, "All")
  field(LNK1, "$(PREF)$(SIG)_CNT")
  field(LNK2, "$(PREF)$(SIG)_CNTTC")
  field(LNK3, "$(PREF)$(SIG)_CNTUC")
}

record(calc, "$(PREF)$(SIG)_CNT") {
  field(DESC, "$(SIG) total fault count")
  field(CALC, "A+1")
  field(INPA, "$(PREF)$(SIG)_CNT")
  field(PINI, "YES")
  field(PREC, "0")
  info(autosaveFields,"VAL")
}

record(calcout, "$(PREF)$(SIG)_CNTTC") {
  field(DESC, "$(SIG) today fault count")
  field(CALC, "A+1")
  field(INPA, "$(PREF)$(SIG)_CNTT")
  field(OOPT, "Every Time")
  field(OUT,  "$(PREF)$(SIG)_CNTT PP")
  field(PREC, "0")
}

record(longin, "$(PREF)$(SIG)_CNTT") {
  field(DESC, "$(SIG) today fault count")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(longin, "$(PREF)$(SIG)_CNTY") {
  field(DESC, "$(SIG) yesterday fault count")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(calcout, "$(PREF)$(SIG)_CNTUC") {
  field(DESC, "$(SIG) user fault count")
  field(CALC, "A+1")
  field(INPA, "$(PREF)$(SIG)_CNTU")
  field(OOPT, "Every Time")
  field(PREC, "0")
  field(OUT,  "$(PREF)$(SIG)_CNTU PP")
}

record(longin, "$(PREF)$(SIG)_CNTU") {
  field(DESC, "$(SIG) user fault count")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(bo, "$(PREF)$(SIG)_CNTUCLR") {
  field(DESC, "Clear user fault count")
  field(OMSL, "supervisory")
  field(ZNAM, "Clear")
  field(ONAM, "Clear")
  field(OMSL, "closed_loop")
  field(DOL,  "0")
  field(OUT,  "$(PREF)$(SIG)_CNTU PP")
}

record(seq, "$(PREF)$(SIG)_CNTRO") {
  field(DESC, "Roll over interlock count")
  field(SELM, "All")
  field(DOL1, "$(PREF)$(SIG)_CNTT")
  field(LNK1, "$(PREF)$(SIG)_CNTY PP")
  field(DOL2, "0")
  field(LNK2, "$(PREF)$(SIG)_CNTT PP")
}