#================================== # Cavity 'station' mode # High-level mode control # Needs who/why records # When offline, force ADES and RFCTRL to 0 # Also in FEED, hook into IOC watchdog interlock # See statCav.template #================================== # If mode state/values change, # HWMODE, HWMODEDES, and set_hwmode # subroutine need updates # Plus communicate to SRF team record(mbbo, "$(PREF)HWMODE") { field(DESC, "Cavity admin status") field(OMSL, "supervisory") field(ZRST, "Online") field(ZRVL, "0") field(ONST, "Maintenance") field(ZRVL, "1") field(ONSV, "MINOR") field(TWST, "Offline") field(ZRVL, "2") field(TWSV, "MAJOR") field(THST, "Maintenance Done") field(THVL, "3") field(THSV, "MINOR") field(FRST, "Ready") field(FRVL, "4") field(FRSV, "MINOR") field(VAL, "0") field(PINI, "YES") field(FLNK, "$(PREF)HWMODE1_") field(ASG, "READONLY") info(autosaveFields, "VAL") } record(mbbo, "$(PREF)HWMODEDES") { field(DESC, "Requested cavity admin status") field(OMSL, "supervisory") field(ZRST, "Online") field(ZRVL, "0") field(ONST, "Maintenance") field(ONVL, "1") field(ONSV, "MINOR") field(TWST, "Offline") field(TWVL, "2") field(TWSV, "MAJOR") field(THST, "Maintenance Done") field(THVL, "3") field(THSV, "MINOR") field(FRST, "Ready") field(FRVL, "4") field(FRSV, "MINOR") field(VAL, "0") field(PINI, "YES") field(FLNK, "$(PREF)HWMODECLRMSG_") info(autosaveFields, "VAL") } record(calc, "$(PREF)HWMODE1_") { field(CALC, "A=2?1:2") field(INPA, "$(PREF)HWMODE") field(FLNK, "$(PREF)HWMODE2_") field(ASG, "READONLY") } record(seq, "$(PREF)HWMODE2_") { field(SELM, "Specified") field(SELL, "$(PREF)HWMODE1_") # If mode set offline field(DOL1, "1") field(LNK1, "$(PREF)HWMODE3_.PROC") # If mode set to other than offline field(DOL2, "1") field(LNK2, "$(PREF)HWMODE4_.PROC") field(ASG, "READONLY") } # If cavity offline # set ADES to 0, RFCTRL to Off # then disable puts to those records record(seq, "$(PREF)HWMODE3_") { field(SELM, "All") field(DOL1, "0") field(LNK1, "$(PREF)ADES PP") field(DOL2, "1") field(LNK2, "$(PREF)ADES.DISP") field(DOL3, "0") field(LNK3, "$(PREF)RFCTRL PP") field(DOL4, "1") field(LNK4, "$(PREF)RFCTRL.DISP") field(FLNK, "$(PREF)ADES_MAX_CALC") field(ASG, "READONLY") } # If cavity not offline # enable puts to those records record(seq, "$(PREF)HWMODE4_") { field(SELM, "All") field(DOL1, "0") field(LNK1, "$(PREF)ADES.DISP") field(DOL2, "0") field(LNK2, "$(PREF)RFCTRL.DISP") field(FLNK, "$(PREF)ADES_MAX_CALC") field(ASG, "READONLY") } record(stringin, "$(PREF)HWMODECLRSTR_") { field(VAL, "") field(PINI, "YES") } record(seq, "$(PREF)HWMODECANCEL") { field(SELM, "All") field(DOL0, "$(PREF)HWMODE") field(LNK0, "$(PREF)HWMODEDES PP") field(DOL1, "1") field(LNK1, "$(PREF)HWMODECLRWHO_.PROC") field(DOL2, "1") field(LNK2, "$(PREF)HWMODECLRWHY_.PROC") field(DOL3, "1") field(LNK3, "$(PREF)HWMODECLRMSG_.PROC") } record(seq, "$(PREF)HWMODECANCEL") { field(SELM, "All") field(DOL0, "$(PREF)HWMODE") field(LNK0, "$(PREF)HWMODEDES PP") field(DOL1, "1") field(LNK1, "$(PREF)HWMODECLRWHO_.PROC") field(DOL2, "1") field(LNK2, "$(PREF)HWMODECLRWHY_.PROC") field(DOL3, "1") field(LNK3, "$(PREF)HWMODECLRMSG_.PROC") } record(stringout, "$(PREF)HWMODECLRWHO_") { field(OMSL, "closed_loop") field(DOL, "\0") field(VAL, "\0") field(OUT, "$(PREF)HWMODEWHO PP") } record(aSub, "$(PREF)HWMODECLRWHY_") { field(SNAM, "note_clear") field(FTVA, "CHAR") field(NOVA, "80") field(OUTA, "$(PREF)HWMODEWHY PP") } record(stringout, "$(PREF)HWMODECLRMSG_") { field(OMSL, "closed_loop") field(DOL, "\0") field(VAL, "\0") field(OUT, "$(PREF)HWMODEMSG PP") } record(waveform, "$(PREF)HWMODEWHY") { field(NELM, "80") field(FTVL, "CHAR") field(PINI, "YES") } record(stringout, "$(PREF)HWMODEWHO") { field(VAL, "") field(PINI, "YES") } record(stringout, "$(PREF)HWMODEMSG") { field(DESC, "HWMODE change msg") field(OMSL, "supervisory") field(DOL, "") field(VAL, "") field(PINI, "YES") } record(mbbo, "$(PREF)HWMODEGO") { field(VAL, "0") field(PINI, "NO") field(FLNK, "$(PREF)HWMODESUB") } # Not enough inputs, to use 2 aSub records record(aSub, "$(PREF)HWMODESUB") { field(DESC, "Set cavity HW mode") field(SNAM, "set_hwmode") # Requested mode and description field(FTA, "SHORT") field(INPA, "$(PREF)HWMODEDES") field(FTB, "CHAR") field(NOB, "80") field(INPB, "$(PREF)HWMODEWHY") field(FTC, "STRING") field(NOC, "1") field(INPC, "$(PREF)HWMODEWHO") # Outputs field(FTVA, "SHORT") field(NOVA, "1") field(OUTA, "$(PREF)HWMODESUB_ PP") field(FTVB, "SHORT") field(NOVB, "1") field(OUTB, "$(PREF)HWMODE PP") field(FTVC, "CHAR") field(NOVC, "80") field(OUTC, "$(PREF)HWMODEWHY PP") field(FTVD, "STRING") field(NOVD, "1") field(OUTD, "$(PREF)HWMODEWHO PP") # Feedback to user field(FTVQ, "STRING") field(NOVQ, "1") field(OUTQ, "$(PREF)HWMODEMSG") # MSG updated every time, even if request fails field(FLNK, "$(PREF)HWMODEMSG_") info(autosaveFields, "VALQ") } record(stringout, "$(PREF)HWMODEMSG_") { field(OMSL, "closed_loop") field(DOL, "$(PREF)HWMODESUB.VALQ") field(OUT, "$(PREF)HWMODEMSG PP") } record(aSub, "$(PREF)HWMODESUB_") { field(DESC, "Set cavity HW mode") field(SNAM, "set_hwmode_hist") # Requested mode and description field(FTA, "CHAR") field(NOA, "80") field(INPA, "$(PREF)HWMODEWHY") field(FTB, "STRING") field(NOB, "1") field(INPB, "$(PREF)HWMODEWHO") # Previous event field(FTC, "CHAR") field(NOC, "80") field(INPC, "$(PREF)HWMODENOTE1") field(FTD, "STRING") field(NOD, "1") field(INPD, "$(PREF)HWMODENOTE1.DESC") field(FTE, "STRING") field(NOE, "1") field(INPE, "$(PREF)HWMODENOTE1TS") field(FTF, "STRING") field(NOF, "1") field(INPF, "$(PREF)HWMODENOTE1TS.DESC") # Previous event - 1 field(FTG, "CHAR") field(NOG, "80") field(INPG, "$(PREF)HWMODENOTE2") field(FTH, "STRING") field(NOH, "1") field(INPH, "$(PREF)HWMODENOTE2.DESC") field(FTI, "STRING") field(NOI, "1") field(INPI, "$(PREF)HWMODENOTE2TS") field(FTJ, "STRING") field(NOJ, "1") field(INPJ, "$(PREF)HWMODENOTE2TS.DESC") # Previous event - 2 field(FTK, "CHAR") field(NOK, "80") field(INPK, "$(PREF)HWMODENOTE3") field(FTL, "STRING") field(NOL, "1") field(INPL, "$(PREF)HWMODENOTE3.DESC") field(FTM, "STRING") field(NOM, "1") field(INPM, "$(PREF)HWMODENOTE3TS") field(FTN, "STRING") field(NON, "1") field(INPN, "$(PREF)HWMODENOTE3TS.DESC") # Previous event - 3 field(FTO, "CHAR") field(NOO, "80") field(INPO, "$(PREF)HWMODENOTE4") field(FTP, "STRING") field(NOP, "1") field(INPP, "$(PREF)HWMODENOTE4.DESC") field(FTQ, "STRING") field(NOQ, "1") field(INPQ, "$(PREF)HWMODENOTE4TS") field(FTR, "STRING") field(NOR, "1") field(INPR, "$(PREF)HWMODENOTE4TS.DESC") field(FTS, "SHORT") field(NOS, "1") field(INPS, "$(PREF)HWMODESUB.VALB") field(FTT, "STRING") field(NOT, "1") field(INPT, "$(PREF)NAME_") # Outputs # New event field(FTVA, "CHAR") field(NOVA, "80") field(OUTA, "$(PREF)HWMODENOTE1") field(FTVB, "STRING") field(NOVB, "1") field(OUTB, "$(PREF)HWMODENOTE1.DESC PP") field(FTVC, "STRING") field(NOVC, "1") field(OUTC, "$(PREF)HWMODENOTE1TS") field(FTVD, "STRING") field(NOVD, "1") field(OUTD, "$(PREF)HWMODENOTE1TS.DESC PP") # Newest event - 1 field(FTVE, "CHAR") field(NOVE, "80") field(OUTE, "$(PREF)HWMODENOTE2") field(FTVF, "STRING") field(NOVF, "1") field(OUTF, "$(PREF)HWMODENOTE2.DESC PP") field(FTVG, "STRING") field(NOVG, "1") field(OUTG, "$(PREF)HWMODENOTE2TS") field(FTVH, "STRING") field(NOVH, "1") field(OUTH, "$(PREF)HWMODENOTE2TS.DESC PP") # Newest event - 2 field(FTVI, "CHAR") field(NOVI, "80") field(OUTI, "$(PREF)HWMODENOTE3") field(FTVJ, "STRING") field(NOVJ, "1") field(OUTJ, "$(PREF)HWMODENOTE3.DESC PP") field(FTVK, "STRING") field(NOVK, "1") field(OUTK, "$(PREF)HWMODENOTE3TS") field(FTVL, "STRING") field(NOVL, "1") field(OUTL, "$(PREF)HWMODENOTE3TS.DESC PP") # Newest event - 3 field(FTVM, "CHAR") field(NOVM, "80") field(OUTM, "$(PREF)HWMODENOTE4") field(FTVN, "STRING") field(NOVN, "1") field(OUTN, "$(PREF)HWMODENOTE4.DESC PP") field(FTVO, "STRING") field(NOVO, "1") field(OUTO, "$(PREF)HWMODENOTE4TS") field(FTVP, "STRING") field(NOVP, "1") field(OUTP, "$(PREF)HWMODENOTE4TS.DESC PP") # Newest event - 4 field(FTVQ, "CHAR") field(NOVQ, "80") field(OUTQ, "$(PREF)HWMODENOTE5") field(FTVR, "STRING") field(NOVR, "1") field(OUTR, "$(PREF)HWMODENOTE5.DESC PP") field(FTVS, "STRING") field(NOVS, "1") field(OUTS, "$(PREF)HWMODENOTE5TS") field(FTVT, "STRING") field(NOVT, "1") field(OUTT, "$(PREF)HWMODENOTE5TS.DESC PP") } record(stringin, "$(PREF)NAME_") { field(VAL, "$(PREF)") field(PINI, "YES") }