#================================== #---------------------------------- # intlkCryoChas.template: # # Records used for interlock that # is driven by value of EPICS PV. # EPICS determines interlock state # and sets/clears register as needed # Instantiate one per relevant signal. #---------------------------------- #================================== #================================== # #================================== # Input A is determined interlock state # Input B is interlock state read from firmware # If they do not match, push A's value to FLT_SET record(calcout, "$(PREF)$(FLT)_WDOG") { field(DESC, "Set intlk reg if wrong") field(SCAN, "5 second") field(CALC, "A=B?1:0") field(INPA, "$(WDOGINP)") field(INPB, "$(PREF)$(FLT)_FLT NPP") field(OOPT, "When Zero") field(OCAL, "A") field(DOPT, "Use OCAL") field(OUT, "$(PREF)$(FLT)_FLT_SET PP") } record(longout, "$(PREF)$(FLT)_FLT_SET") { field(DTYP, "FEED Register Write") field(OMSL, "supervisory") field(OUT , "@name=$(NAME) reg=$(REG)") info(feed:info:output, "$(PREF)$(FLT)_FLT_SET") } record(longin, "$(PREF)REG$(FLT)_FLT") { field(DTYP, "FEED Register Read") field(SCAN, "1 second") field(INP , "@name=$(NAME) reg=$(REG)") field(FLNK, "$(PREF)$(FLT)_FLT") info(feed:info:input, "$(PREF)REG$(FLT)_FLT") } record(bi, "$(PREF)$(FLT)_FLT") { field(DESC, "Interlock status") field(ZNAM, "Ok") field(ONAM, "Fault") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") field(INP, "$(PREF)REG$(FLT)_FLT") } # No explicit latched status available, # so OR current & bypass status to # support logic displays record(bi, "$(PREF)$(FLT)_LTCH") { field(DESC, "Interlock latched status") field(SCAN, "1 second") field(ZNAM, "Ok") field(ONAM, "Fault") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") field(INP, "$(PREF)$(FLT)_LTCH_CALC PP") } record(calc, "$(PREF)$(FLT)_LTCH_CALC") { field(DESC, "OR current stat and bypass") field(CALC, "B?0:A=0?0:1") field(INPA, "$(PREF)$(FLT)_FLT NPP") field(INPB, "$(PREF)$(FLT)_BYP_RBV NPP") # field(ASG, "NOWRITE") } record(bo, "$(PREF)$(FLT)_BYP") { field(DESC, "Interlock bypass") field(ZNAM, "Not Bypassed") field(ONAM, "Bypassed") field(ZSV, "NO_ALARM") field(OSV, "MINOR") field(VAL, "0") field(PINI, "YES") field(FLNK, "$(PREF)REG$(FLT)_BYP") info(autosaveFields,"VAL") } record(bi, "$(PREF)$(FLT)_BYP_RBV") { field(DESC, "Interlock bypass status") field(ZNAM, "Not Bypassed") field(ONAM, "Bypassed") field(ZSV, "NO_ALARM") field(OSV, "MINOR") field(INP, "$(PREF)REG$(FLT)_BYP_RBV") } record(longin, "$(PREF)REG$(FLT)_BYP_RBV") { field(DESC, "$(DESC) fault byp") field(DTYP, "FEED Register Read") field(SCAN, "1 second") field(INP , "@name=$(NAME) reg=$(BYPREG)") field(FLNK, "$(PREF)$(FLT)_BYP_RBV") info(feed:info:input, "$(PREF)REG$(FLT)_BYP_RBV") } record(longout, "$(PREF)REG$(FLT)_BYP") { field(DESC, "$(DESC) fault byp") field(DTYP, "FEED Register Write") field(OMSL, "closed_loop") field(DOL, "$(PREF)$(FLT)_BYP MS") field(OUT , "@name=$(NAME) reg=$(BYPREG)") info(feed:info:output, "$(PREF)REG$(FLT)_BYP") } record(longin, "$(PREF)$(FLT)_INIT1_") { field(DTYP, "FEED On Connect") field(INP , "@name=$(NAME)") field(SCAN, "I/O Intr") field(PHAS, "0") field(FLNK, "$(PREF)$(FLT)_BYP") }