#================================== #---------------------------------- # cryoCavLerf.template: # # Support LERF communication with cryo #---------------------------------- #================================== #================================== # #================================== # Dissipated power calculation from AACTMEAN # Keep for now as comparison with AACT_SQR value # Remove when this later fully commissioned record(calc, "$(CM,undefined)10:RFCRYO_PWRDISS_CALC") { field(DESC, "Calc dissipated power") field(CALC, "A*A*1e12/B/C") field(EGU, "W") field(INPA, "$(CM,undefined)10:AACTMEAN CP") field(INPB, "$(CM,undefined)10:IMPED CP") field(INPC, "$(CM,undefined)10:Q0 CP") } # TODO: add source PV (when avail in FW) record(ao, "$(CM,undefined)10:RFCRYO_PWRDISS") { field(DESC, "Write gradient to cryo") field(DTYP, "EtherIP") field(OMSL, "closed_loop") field(DOL, "$(CM,undefined)00:RFCRYO_SUB.VALA") $(TEST,recursive) field(OUT, "@$(PLC,undefined) RF_1_CRF_1155_GRADIENT[$(CMCRYO,undefined)] S 1") field(EGU, "W") # field(ASG, "") field(FLNK, "$(CM,undefined)10:RFCRYO_HEARTBEATSTATCALC") } # Individual cavity heartbeats use 1 bit of mask record(calc, "$(CM,undefined)10:RFCRYO_HEARTBEATSTATCALC") { field(DESC, "RF->cryo heartbeat status") field(CALC, "(A>>(B-1))&1") field(INPA, "$(CM,undefined)00:RFCRYO_SUB.VALI") field(INPB, "1") field(TSEL, "$(CM,undefined)00:RFCRYO_STAT.TIME") field(FLNK, "$(CM,undefined)10:RFCRYO_HEARTBEATSTAT") } record(bi, "$(CM,undefined)10:RFCRYO_HEARTBEATSTAT") { field(DESC, "RF->cryo heartbeat status") field(INP, "$(CM,undefined)10:RFCRYO_HEARTBEATSTATCALC") field(ZNAM, "Fault") field(ZSV, "MAJOR") field(ONAM, "Ok") field(TSEL, "$(CM,undefined)00:RFCRYO_STAT.TIME") } #================================== #---------------------------------- # cryoCavLerf.template: # # Support LERF communication with cryo #---------------------------------- #================================== #================================== # #================================== # Dissipated power calculation from AACTMEAN # Keep for now as comparison with AACT_SQR value # Remove when this later fully commissioned record(calc, "$(CM,undefined)20:RFCRYO_PWRDISS_CALC") { field(DESC, "Calc dissipated power") field(CALC, "A*A*1e12/B/C") field(EGU, "W") field(INPA, "$(CM,undefined)20:AACTMEAN CP") field(INPB, "$(CM,undefined)20:IMPED CP") field(INPC, "$(CM,undefined)20:Q0 CP") } # TODO: add source PV (when avail in FW) record(ao, "$(CM,undefined)20:RFCRYO_PWRDISS") { field(DESC, "Write gradient to cryo") field(DTYP, "EtherIP") field(OMSL, "closed_loop") field(DOL, "$(CM,undefined)00:RFCRYO_SUB.VALB") $(TEST,recursive) field(OUT, "@$(PLC,undefined) RF_1_CRF_1255_GRADIENT[$(CMCRYO,undefined)] S 1") field(EGU, "W") # field(ASG, "") field(FLNK, "$(CM,undefined)20:RFCRYO_HEARTBEATSTATCALC") } # Individual cavity heartbeats use 1 bit of mask record(calc, "$(CM,undefined)20:RFCRYO_HEARTBEATSTATCALC") { field(DESC, "RF->cryo heartbeat status") field(CALC, "(A>>(B-1))&1") field(INPA, "$(CM,undefined)00:RFCRYO_SUB.VALI") field(INPB, "2") field(TSEL, "$(CM,undefined)00:RFCRYO_STAT.TIME") field(FLNK, "$(CM,undefined)20:RFCRYO_HEARTBEATSTAT") } record(bi, "$(CM,undefined)20:RFCRYO_HEARTBEATSTAT") { field(DESC, "RF->cryo heartbeat status") field(INP, "$(CM,undefined)20:RFCRYO_HEARTBEATSTATCALC") field(ZNAM, "Fault") field(ZSV, "MAJOR") field(ONAM, "Ok") field(TSEL, "$(CM,undefined)00:RFCRYO_STAT.TIME") } #================================== #---------------------------------- # cryoCavLerf.template: # # Support LERF communication with cryo #---------------------------------- #================================== #================================== # #================================== # Dissipated power calculation from AACTMEAN # Keep for now as comparison with AACT_SQR value # Remove when this later fully commissioned record(calc, "$(CM,undefined)30:RFCRYO_PWRDISS_CALC") { field(DESC, "Calc dissipated power") field(CALC, "A*A*1e12/B/C") field(EGU, "W") field(INPA, "$(CM,undefined)30:AACTMEAN CP") field(INPB, "$(CM,undefined)30:IMPED CP") field(INPC, "$(CM,undefined)30:Q0 CP") } # TODO: add source PV (when avail in FW) record(ao, "$(CM,undefined)30:RFCRYO_PWRDISS") { field(DESC, "Write gradient to cryo") field(DTYP, "EtherIP") field(OMSL, "closed_loop") field(DOL, "$(CM,undefined)00:RFCRYO_SUB.VALC") $(TEST,recursive) field(OUT, "@$(PLC,undefined) RF_1_CRF_1355_GRADIENT[$(CMCRYO,undefined)] S 1") field(EGU, "W") # field(ASG, "") field(FLNK, "$(CM,undefined)30:RFCRYO_HEARTBEATSTATCALC") } # Individual cavity heartbeats use 1 bit of mask record(calc, "$(CM,undefined)30:RFCRYO_HEARTBEATSTATCALC") { field(DESC, "RF->cryo heartbeat status") field(CALC, "(A>>(B-1))&1") field(INPA, "$(CM,undefined)00:RFCRYO_SUB.VALI") field(INPB, "3") field(TSEL, "$(CM,undefined)00:RFCRYO_STAT.TIME") field(FLNK, "$(CM,undefined)30:RFCRYO_HEARTBEATSTAT") } record(bi, "$(CM,undefined)30:RFCRYO_HEARTBEATSTAT") { field(DESC, "RF->cryo heartbeat status") field(INP, "$(CM,undefined)30:RFCRYO_HEARTBEATSTATCALC") field(ZNAM, "Fault") field(ZSV, "MAJOR") field(ONAM, "Ok") field(TSEL, "$(CM,undefined)00:RFCRYO_STAT.TIME") } #================================== #---------------------------------- # cryoCavLerf.template: # # Support LERF communication with cryo #---------------------------------- #================================== #================================== # #================================== # Dissipated power calculation from AACTMEAN # Keep for now as comparison with AACT_SQR value # Remove when this later fully commissioned record(calc, "$(CM,undefined)40:RFCRYO_PWRDISS_CALC") { field(DESC, "Calc dissipated power") field(CALC, "A*A*1e12/B/C") field(EGU, "W") field(INPA, "$(CM,undefined)40:AACTMEAN CP") field(INPB, "$(CM,undefined)40:IMPED CP") field(INPC, "$(CM,undefined)40:Q0 CP") } # TODO: add source PV (when avail in FW) record(ao, "$(CM,undefined)40:RFCRYO_PWRDISS") { field(DESC, "Write gradient to cryo") field(DTYP, "EtherIP") field(OMSL, "closed_loop") field(DOL, "$(CM,undefined)00:RFCRYO_SUB.VALD") $(TEST,recursive) field(OUT, "@$(PLC,undefined) RF_1_CRF_1455_GRADIENT[$(CMCRYO,undefined)] S 1") field(EGU, "W") # field(ASG, "") field(FLNK, "$(CM,undefined)40:RFCRYO_HEARTBEATSTATCALC") } # Individual cavity heartbeats use 1 bit of mask record(calc, "$(CM,undefined)40:RFCRYO_HEARTBEATSTATCALC") { field(DESC, "RF->cryo heartbeat status") field(CALC, "(A>>(B-1))&1") field(INPA, "$(CM,undefined)00:RFCRYO_SUB.VALI") field(INPB, "4") field(TSEL, "$(CM,undefined)00:RFCRYO_STAT.TIME") field(FLNK, "$(CM,undefined)40:RFCRYO_HEARTBEATSTAT") } record(bi, "$(CM,undefined)40:RFCRYO_HEARTBEATSTAT") { field(DESC, "RF->cryo heartbeat status") field(INP, "$(CM,undefined)40:RFCRYO_HEARTBEATSTATCALC") field(ZNAM, "Fault") field(ZSV, "MAJOR") field(ONAM, "Ok") field(TSEL, "$(CM,undefined)00:RFCRYO_STAT.TIME") } #================================== #---------------------------------- # cryoCavLerf.template: # # Support LERF communication with cryo #---------------------------------- #================================== #================================== # #================================== # Dissipated power calculation from AACTMEAN # Keep for now as comparison with AACT_SQR value # Remove when this later fully commissioned record(calc, "$(CM,undefined)50:RFCRYO_PWRDISS_CALC") { field(DESC, "Calc dissipated power") field(CALC, "A*A*1e12/B/C") field(EGU, "W") field(INPA, "$(CM,undefined)50:AACTMEAN CP") field(INPB, "$(CM,undefined)50:IMPED CP") field(INPC, "$(CM,undefined)50:Q0 CP") } # TODO: add source PV (when avail in FW) record(ao, "$(CM,undefined)50:RFCRYO_PWRDISS") { field(DESC, "Write gradient to cryo") field(DTYP, "EtherIP") field(OMSL, "closed_loop") field(DOL, "$(CM,undefined)00:RFCRYO_SUB.VALE") $(TEST,recursive) field(OUT, "@$(PLC,undefined) RF_1_CRF_1555_GRADIENT[$(CMCRYO,undefined)] S 1") field(EGU, "W") # field(ASG, "") field(FLNK, "$(CM,undefined)50:RFCRYO_HEARTBEATSTATCALC") } # Individual cavity heartbeats use 1 bit of mask record(calc, "$(CM,undefined)50:RFCRYO_HEARTBEATSTATCALC") { field(DESC, "RF->cryo heartbeat status") field(CALC, "(A>>(B-1))&1") field(INPA, "$(CM,undefined)00:RFCRYO_SUB.VALI") field(INPB, "5") field(TSEL, "$(CM,undefined)00:RFCRYO_STAT.TIME") field(FLNK, "$(CM,undefined)50:RFCRYO_HEARTBEATSTAT") } record(bi, "$(CM,undefined)50:RFCRYO_HEARTBEATSTAT") { field(DESC, "RF->cryo heartbeat status") field(INP, "$(CM,undefined)50:RFCRYO_HEARTBEATSTATCALC") field(ZNAM, "Fault") field(ZSV, "MAJOR") field(ONAM, "Ok") field(TSEL, "$(CM,undefined)00:RFCRYO_STAT.TIME") } #================================== #---------------------------------- # cryoCavLerf.template: # # Support LERF communication with cryo #---------------------------------- #================================== #================================== # #================================== # Dissipated power calculation from AACTMEAN # Keep for now as comparison with AACT_SQR value # Remove when this later fully commissioned record(calc, "$(CM,undefined)60:RFCRYO_PWRDISS_CALC") { field(DESC, "Calc dissipated power") field(CALC, "A*A*1e12/B/C") field(EGU, "W") field(INPA, "$(CM,undefined)60:AACTMEAN CP") field(INPB, "$(CM,undefined)60:IMPED CP") field(INPC, "$(CM,undefined)60:Q0 CP") } # TODO: add source PV (when avail in FW) record(ao, "$(CM,undefined)60:RFCRYO_PWRDISS") { field(DESC, "Write gradient to cryo") field(DTYP, "EtherIP") field(OMSL, "closed_loop") field(DOL, "$(CM,undefined)00:RFCRYO_SUB.VALF") $(TEST,recursive) field(OUT, "@$(PLC,undefined) RF_1_CRF_1655_GRADIENT[$(CMCRYO,undefined)] S 1") field(EGU, "W") # field(ASG, "") field(FLNK, "$(CM,undefined)60:RFCRYO_HEARTBEATSTATCALC") } # Individual cavity heartbeats use 1 bit of mask record(calc, "$(CM,undefined)60:RFCRYO_HEARTBEATSTATCALC") { field(DESC, "RF->cryo heartbeat status") field(CALC, "(A>>(B-1))&1") field(INPA, "$(CM,undefined)00:RFCRYO_SUB.VALI") field(INPB, "6") field(TSEL, "$(CM,undefined)00:RFCRYO_STAT.TIME") field(FLNK, "$(CM,undefined)60:RFCRYO_HEARTBEATSTAT") } record(bi, "$(CM,undefined)60:RFCRYO_HEARTBEATSTAT") { field(DESC, "RF->cryo heartbeat status") field(INP, "$(CM,undefined)60:RFCRYO_HEARTBEATSTATCALC") field(ZNAM, "Fault") field(ZSV, "MAJOR") field(ONAM, "Ok") field(TSEL, "$(CM,undefined)00:RFCRYO_STAT.TIME") } #================================== #---------------------------------- # cryoCavLerf.template: # # Support LERF communication with cryo #---------------------------------- #================================== #================================== # #================================== # Dissipated power calculation from AACTMEAN # Keep for now as comparison with AACT_SQR value # Remove when this later fully commissioned record(calc, "$(CM,undefined)70:RFCRYO_PWRDISS_CALC") { field(DESC, "Calc dissipated power") field(CALC, "A*A*1e12/B/C") field(EGU, "W") field(INPA, "$(CM,undefined)70:AACTMEAN CP") field(INPB, "$(CM,undefined)70:IMPED CP") field(INPC, "$(CM,undefined)70:Q0 CP") } # TODO: add source PV (when avail in FW) record(ao, "$(CM,undefined)70:RFCRYO_PWRDISS") { field(DESC, "Write gradient to cryo") field(DTYP, "EtherIP") field(OMSL, "closed_loop") field(DOL, "$(CM,undefined)00:RFCRYO_SUB.VALG") $(TEST,recursive) field(OUT, "@$(PLC,undefined) RF_1_CRF_1755_GRADIENT[$(CMCRYO,undefined)] S 1") field(EGU, "W") # field(ASG, "") field(FLNK, "$(CM,undefined)70:RFCRYO_HEARTBEATSTATCALC") } # Individual cavity heartbeats use 1 bit of mask record(calc, "$(CM,undefined)70:RFCRYO_HEARTBEATSTATCALC") { field(DESC, "RF->cryo heartbeat status") field(CALC, "(A>>(B-1))&1") field(INPA, "$(CM,undefined)00:RFCRYO_SUB.VALI") field(INPB, "7") field(TSEL, "$(CM,undefined)00:RFCRYO_STAT.TIME") field(FLNK, "$(CM,undefined)70:RFCRYO_HEARTBEATSTAT") } record(bi, "$(CM,undefined)70:RFCRYO_HEARTBEATSTAT") { field(DESC, "RF->cryo heartbeat status") field(INP, "$(CM,undefined)70:RFCRYO_HEARTBEATSTATCALC") field(ZNAM, "Fault") field(ZSV, "MAJOR") field(ONAM, "Ok") field(TSEL, "$(CM,undefined)00:RFCRYO_STAT.TIME") } #================================== #---------------------------------- # cryoCavLerf.template: # # Support LERF communication with cryo #---------------------------------- #================================== #================================== # #================================== # Dissipated power calculation from AACTMEAN # Keep for now as comparison with AACT_SQR value # Remove when this later fully commissioned record(calc, "$(CM,undefined)80:RFCRYO_PWRDISS_CALC") { field(DESC, "Calc dissipated power") field(CALC, "A*A*1e12/B/C") field(EGU, "W") field(INPA, "$(CM,undefined)80:AACTMEAN CP") field(INPB, "$(CM,undefined)80:IMPED CP") field(INPC, "$(CM,undefined)80:Q0 CP") } # TODO: add source PV (when avail in FW) record(ao, "$(CM,undefined)80:RFCRYO_PWRDISS") { field(DESC, "Write gradient to cryo") field(DTYP, "EtherIP") field(OMSL, "closed_loop") field(DOL, "$(CM,undefined)00:RFCRYO_SUB.VALH") $(TEST,recursive) field(OUT, "@$(PLC,undefined) RF_1_CRF_1855_GRADIENT[$(CMCRYO,undefined)] S 1") field(EGU, "W") # field(ASG, "") field(FLNK, "$(CM,undefined)80:RFCRYO_HEARTBEATSTATCALC") } # Individual cavity heartbeats use 1 bit of mask record(calc, "$(CM,undefined)80:RFCRYO_HEARTBEATSTATCALC") { field(DESC, "RF->cryo heartbeat status") field(CALC, "(A>>(B-1))&1") field(INPA, "$(CM,undefined)00:RFCRYO_SUB.VALI") field(INPB, "8") field(TSEL, "$(CM,undefined)00:RFCRYO_STAT.TIME") field(FLNK, "$(CM,undefined)80:RFCRYO_HEARTBEATSTAT") } record(bi, "$(CM,undefined)80:RFCRYO_HEARTBEATSTAT") { field(DESC, "RF->cryo heartbeat status") field(INP, "$(CM,undefined)80:RFCRYO_HEARTBEATSTATCALC") field(ZNAM, "Fault") field(ZSV, "MAJOR") field(ONAM, "Ok") field(TSEL, "$(CM,undefined)00:RFCRYO_STAT.TIME") } # Notes on process periods: # 1 second: LLRF reads amplitude-squared from FW, # calculates dissipated power, performs # checks, sends heartbeat to cryo # 1 second: LLRF reads Cryo HB/fault status # 2 second: Cryo changes its heartbeat, so LLRF # scanning every 1 second will detect change; # LLRF checks 10 times (10 seconds); if no # changes during that period, this is a heartbeat fault # Process subroutine after firmware AACT_SQR reads to # avoid stale data, which results in heartbeat counter # not updating. In that case, Cryo currently assumes # zero dissipated power. # 10/1/21: In current configuration, LLRF processes # data at 1 Hz and Cryo monitors 1 bit of heartbeat # for 10 seconds before registering the fault. record(fanout, "$(CM,recursive)00:RFCRYO_SUB_FO_") { field(DESC, "Process cryo records") field(SCAN, "1 second") field(SELM, "All") field(LNK1, "$(CM,recursive)10:AACT_SQR_READ") field(LNK2, "$(CM,recursive)20:AACT_SQR_READ") field(LNK3, "$(CM,recursive)30:AACT_SQR_READ") field(LNK4, "$(CM,recursive)40:AACT_SQR_READ") field(LNK5, "$(CM,recursive)50:AACT_SQR_READ") field(LNK6, "$(CM,recursive)00:RFCRYO_SUB_FO2_") } record(fanout, "$(CM,recursive)00:RFCRYO_SUB_FO2_") { field(DESC, "Process cryo records") field(SELM, "All") field(LNK1, "$(CM,recursive)60:AACT_SQR_READ") field(LNK2, "$(CM,recursive)70:AACT_SQR_READ") field(LNK3, "$(CM,recursive)80:AACT_SQR_READ") field(LNK4, "$(CM,recursive)00:RFCRYO_SUB_FO3_") } record(seq, "$(CM,recursive)00:RFCRYO_SUB_FO3_") { field(SELM, "All") field(DLY0, "0.5") field(LNK0, "$(CM,recursive)00:RFCRYO_SUB PP") } record(aSub, "$(CM,recursive)00:RFCRYO_SUB") { field(INAM, "asub_cryo_init") field(SNAM, "asub_cryo") field(DISV, "1") # Inputs # Subroutine checks PWRDISS severity and timestamp field(FTA, "DOUBLE") # cavity 1 amplitude field(INPA, "$(CM,recursive)10:PWRDISS") field(FTB, "DOUBLE") # cavity 2 amplitude field(INPB, "$(CM,recursive)20:PWRDISS") field(FTC, "DOUBLE") # cavity 3 amplitude field(INPC, "$(CM,recursive)30:PWRDISS") field(FTD, "DOUBLE") # cavity 4 amplitude field(INPD, "$(CM,recursive)40:PWRDISS") field(FTE, "DOUBLE") # cavity 5 amplitude field(INPE, "$(CM,recursive)50:PWRDISS") field(FTF, "DOUBLE") # cavity 6 amplitude field(INPF, "$(CM,recursive)60:PWRDISS") field(FTG, "DOUBLE") # cavity 7 amplitude field(INPG, "$(CM,recursive)70:PWRDISS") field(FTH, "DOUBLE") # cavity 8 amplitude field(INPH, "$(CM,recursive)80:PWRDISS") # Outputs # New value to send to cryo. If dissipated power # SEVR == INVALID or timestamp unchanged, send last value field(FTVA, "DOUBLE") # cavity 1 last valid amplitude field(OUTA, "$(CM,recursive)10:RFCRYO_PWRDISS PP") field(FTVB, "DOUBLE") # cavity 2 last valid amplitude field(OUTB, "$(CM,recursive)20:RFCRYO_PWRDISS PP") field(FTVC, "DOUBLE") # cavity 3 last valid amplitude field(OUTC, "$(CM,recursive)30:RFCRYO_PWRDISS PP") field(FTVD, "DOUBLE") # cavity 4 last valid amplitude field(OUTD, "$(CM,recursive)40:RFCRYO_PWRDISS PP") field(FTVE, "DOUBLE") # cavity 5 last valid amplitude field(OUTE, "$(CM,recursive)50:RFCRYO_PWRDISS PP") field(FTVF, "DOUBLE") # cavity 6 last valid amplitude field(OUTF, "$(CM,recursive)60:RFCRYO_PWRDISS PP") field(FTVG, "DOUBLE") # cavity 7 last valid amplitude field(OUTG, "$(CM,recursive)70:RFCRYO_PWRDISS PP") field(FTVH, "DOUBLE") # cavity 8 last valid amplitude field(OUTH, "$(CM,recursive)80:RFCRYO_PWRDISS PP") field(FTVI, "ULONG") # mask of valid amplitude field(FTVJ, "ULONG") # mask of heartbeat counters field(OUTJ, "$(CM,recursive)00:RFCRYO_STAT PP") field(NOVK, "16") field(FTVK, "ULONG") # PWRDISS timestamps } #================================== # Write heartbeat word to PLC #================================== record(mbboDirect, "$(CM,recursive)00:RFCRYO_STAT") { field(DESC, "Write heartbeat word to cryo") field(SCAN, "Passive") field(DTYP, "EtherIP") field(NOBT, "16") field(OMSL, "closed_loop") field(DOL, "$(CM,recursive)00:RFCRYO_SUB.VALJ") $(TEST,recursive) field(OUT, "@$(PLC,undefined) RF_1_CRF_0000_HEARTBEAT[$(CMCRYO,undefined)] B 0 S 1") } #================================== # Inhibit RF if cryo interlock fault # or cryo heartbeat not updating. #================================== # Use cryo PLC summary bit (not individual # He level/pressure bits) to determine fault record(calcout, "$(CM,recursive)00:CRYOPLC_CALC") { field(DESC, "Local CM cryo intlk status") field(SCAN, "$(CRYOSCAN,undefined)") field(CALC, "A&B?0:1") field(INPA, "$(CM,recursive)00:CRYOPLC_SUM") field(INPB, "$(CM,recursive)00:CRYOPLC_HEARTBEATSUM") field(FLNK, "$(CM,recursive)00:CRYOPLC_FLT") } # Match LLRF FW conventions: 0 = ok, 1 = fault record(bi, "$(CM,recursive)00:CRYOPLC_FLT") { field(DESC, "Local CM cryo intlk status") field(INP, "$(CM,recursive)00:CRYOPLC_CALC") field(ZNAM, "Ok") field(ONAM, "Fault") field(OSV, "MAJOR") } # Processed by intlkHeLerfCmCommon.template record(dfanout, "$(CM,recursive)00:CRYOSUM_FO") { field(DESC, "CM cryo fault") field(SELM, "All") field(OUTA, "$(CM,recursive)10:CRYO_TIME PP") field(OUTB, "$(CM,recursive)20:CRYO_TIME PP") field(OUTC, "$(CM,recursive)30:CRYO_TIME PP") field(OUTD, "$(CM,recursive)40:CRYO_TIME PP") field(OUTE, "$(CM,recursive)50:CRYO_TIME PP") field(OUTF, "$(CM,recursive)60:CRYO_TIME PP") field(OUTG, "$(CM,recursive)70:CRYO_TIME PP") field(OUTH, "$(CM,recursive)80:CRYO_TIME PP") } #================================== # Read status word from cryo PLC # and break out individual bits #================================== record(mbbiDirect, "$(CM,recursive)00:CRYOPLC_GETSTAT") { field(DESC, "Cryo overall health") field(SCAN, "1 second") field(DTYP, "EtherIP") $(TEST,recursive) field(INP, "@$(PLC,undefined) RF_1_CRF_0000_CM_STATUS[$(CMCRYO,undefined)] B 0") field(NOBT, "3") field(FLNK, "$(CM,recursive)00:CRYOPLC_SUM") } record(bi, "$(CM,recursive)00:CRYOPLC_SUM") { field(DESC, "CM cryo health summary") field(INP, "$(CM,recursive)00:CRYOPLC_GETSTAT.B0") field(ZNAM, "Fault") field(ZSV, "MAJOR") field(ONAM, "Ok") field(FLNK, "$(CM,recursive)00:CRYOPLC_HELEVEL") } record(bi, "$(CM,recursive)00:CRYOPLC_HELEVEL") { field(DESC, "CM cryo He level status") field(INP, "$(CM,recursive)00:CRYOPLC_GETSTAT.B1") field(ZNAM, "Fault") field(ZSV, "MAJOR") field(ONAM, "Ok") field(FLNK, "$(CM,recursive)00:CRYOPLC_HEPRES") } record(bi, "$(CM,recursive)00:CRYOPLC_HEPRES") { field(DESC, "CM cryo He press status") field(INP, "$(CM,recursive)00:CRYOPLC_GETSTAT.B2") field(ZNAM, "Fault") field(ZSV, "MAJOR") field(ONAM, "Ok") } # User-resettable diagnostic counters; currently # separate from the other LLRF interlock counters, # which increment on change-of-state and do not # increment if the interlock is bypassed record(calcout, "$(CM,recursive)00:CRYOPLC_SUM_CNTDC") { field(DESC, "Diagnostic fault counter") field(CALC, "A") field(INPA, "$(CM,recursive)00:CRYOPLC_SUM") field(INPB, "$(CM,recursive)00:CRYOPLC_SUM_CNTD") field(OOPT, "When Zero") field(DOPT, "Use OCAL") field(OCAL, "B>2^16?0:B+1") field(OUT, "$(CM,recursive)00:CRYOPLC_SUM_CNTD PP") } record(longin, "$(CM,recursive)00:CRYOPLC_SUM_CNTD") { field(DESC, "Diagnostic fault count") field(VAL, "0") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,recursive)00:CRYOPLC_SUM_CNTDCLR") { field(DESC, "Clear fault count") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,recursive)00:CRYOPLC_SUM_CNTD PP") } #================================== # Read heartbeat from cryo PLC # and determine if updating. #================================== record(bi, "$(CM,recursive)00:CRYOPLC_HEARTBEAT") { field(DESC, "Cryo heartbeat from PLC") field(SCAN, "1 second") field(DTYP, "EtherIP") $(TEST,recursive) field(INP, "@$(PLC,undefined) RF_1_CRF_0000_PLC_HEARTBEAT[$(CMCRYO,undefined)] B 0") field(ZNAM, "Low") field(ONAM, "High") } record(calc, "$(CM,recursive)00:CRYOPLC_HEARTBEATCALC") { field(SCAN, "1 second") field(CALC, "A") field(INPA, "$(CM,recursive)00:CRYOPLC_HEARTBEAT.RVAL MS") field(INPB, "$(CM,recursive)00:CRYOPLC_HEARTBEATCALC.VAL") field(FLNK, "$(CM,recursive)00:CRYOPLC_HEARTBEATERR") field(ASG, "READONLY") } record(calc, "$(CM,recursive)00:CRYOPLC_HEARTBEATERR") { field(CALC, "A=B?1:0") field(INPA, "$(CM,recursive)00:CRYOPLC_HEARTBEATCALC.A") field(INPB, "$(CM,recursive)00:CRYOPLC_HEARTBEATCALC.B") field(FLNK, "$(CM,recursive)00:CRYOPLC_HEARTBEATOK") field(ASG, "READONLY") } record(bi, "$(CM,recursive)00:CRYOPLC_HEARTBEATOK") { field(INP, "$(CM,recursive)00:CRYOPLC_HEARTBEATERR.VAL") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") field(ZNAM, "OK") field(ONAM, "FAULT") field(FLNK, "$(CM,recursive)00:CRYOPLC_HEARTBEATE01") field(ASG, "READONLY") } record(calc, "$(CM,recursive)00:CRYOPLC_HEARTBEATE10") { field(CALC, "A") field(INPA, "$(CM,recursive)00:CRYOPLC_HEARTBEATE09.B") field(INPB, "$(CM,recursive)00:CRYOPLC_HEARTBEATE10.VAL") field(FLNK, "$(CM,recursive)00:CRYOPLC_HEARTBEATECT") field(ASG, "READONLY") } record(calc, "$(CM,recursive)00:CRYOPLC_HEARTBEATE09") { field(CALC, "A") field(INPA, "$(CM,recursive)00:CRYOPLC_HEARTBEATE08.B") field(INPB, "$(CM,recursive)00:CRYOPLC_HEARTBEATE09.VAL") field(FLNK, "$(CM,recursive)00:CRYOPLC_HEARTBEATE10") field(ASG, "READONLY") } record(calc, "$(CM,recursive)00:CRYOPLC_HEARTBEATE08") { field(CALC, "A") field(INPA, "$(CM,recursive)00:CRYOPLC_HEARTBEATE07.B") field(INPB, "$(CM,recursive)00:CRYOPLC_HEARTBEATE08.VAL") field(FLNK, "$(CM,recursive)00:CRYOPLC_HEARTBEATE09") field(ASG, "READONLY") } record(calc, "$(CM,recursive)00:CRYOPLC_HEARTBEATE07") { field(CALC, "A") field(INPA, "$(CM,recursive)00:CRYOPLC_HEARTBEATE06.B") field(INPB, "$(CM,recursive)00:CRYOPLC_HEARTBEATE07.VAL") field(FLNK, "$(CM,recursive)00:CRYOPLC_HEARTBEATE08") field(ASG, "READONLY") } record(calc, "$(CM,recursive)00:CRYOPLC_HEARTBEATE06") { field(CALC, "A") field(INPA, "$(CM,recursive)00:CRYOPLC_HEARTBEATE05.B") field(INPB, "$(CM,recursive)00:CRYOPLC_HEARTBEATE06.VAL") field(FLNK, "$(CM,recursive)00:CRYOPLC_HEARTBEATE07") field(ASG, "READONLY") } record(calc, "$(CM,recursive)00:CRYOPLC_HEARTBEATE05") { field(INPA, "$(CM,recursive)00:CRYOPLC_HEARTBEATE04.B") field(INPB, "$(CM,recursive)00:CRYOPLC_HEARTBEATE05.VAL") field(FLNK, "$(CM,recursive)00:CRYOPLC_HEARTBEATE06") field(CALC, "A") field(ASG, "READONLY") } record(calc, "$(CM,recursive)00:CRYOPLC_HEARTBEATE04") { field(CALC, "A") field(INPA, "$(CM,recursive)00:CRYOPLC_HEARTBEATE03.B") field(INPB, "$(CM,recursive)00:CRYOPLC_HEARTBEATE04.VAL") field(FLNK, "$(CM,recursive)00:CRYOPLC_HEARTBEATE05") field(ASG, "READONLY") } record(calc, "$(CM,recursive)00:CRYOPLC_HEARTBEATE03") { field(CALC, "A") field(INPA, "$(CM,recursive)00:CRYOPLC_HEARTBEATE02.B") field(INPB, "$(CM,recursive)00:CRYOPLC_HEARTBEATE03.VAL") field(FLNK, "$(CM,recursive)00:CRYOPLC_HEARTBEATE04") field(ASG, "READONLY") } record(calc, "$(CM,recursive)00:CRYOPLC_HEARTBEATE02") { field(CALC, "A") field(INPA, "$(CM,recursive)00:CRYOPLC_HEARTBEATE01.B") field(INPB, "$(CM,recursive)00:CRYOPLC_HEARTBEATE02.VAL") field(FLNK, "$(CM,recursive)00:CRYOPLC_HEARTBEATE03") field(ASG, "READONLY") } record(calc, "$(CM,recursive)00:CRYOPLC_HEARTBEATE01") { field(CALC, "A") field(INPA, "$(CM,recursive)00:CRYOPLC_HEARTBEATERR.VAL") field(INPB, "$(CM,recursive)00:CRYOPLC_HEARTBEATE01.VAL") field(FLNK, "$(CM,recursive)00:CRYOPLC_HEARTBEATE02") field(ASG, "READONLY") } record(calc, "$(CM,recursive)00:CRYOPLC_HEARTBEATECT") { field(CALC, "A+B+C+D+E+F+G+H+I+J") field(INPA, "$(CM,recursive)00:CRYOPLC_HEARTBEATE01.VAL") field(INPB, "$(CM,recursive)00:CRYOPLC_HEARTBEATE02.VAL") field(INPC, "$(CM,recursive)00:CRYOPLC_HEARTBEATE03.VAL") field(INPD, "$(CM,recursive)00:CRYOPLC_HEARTBEATE04.VAL") field(INPE, "$(CM,recursive)00:CRYOPLC_HEARTBEATE05.VAL") field(INPF, "$(CM,recursive)00:CRYOPLC_HEARTBEATE06.VAL") field(INPG, "$(CM,recursive)00:CRYOPLC_HEARTBEATE07.VAL") field(INPH, "$(CM,recursive)00:CRYOPLC_HEARTBEATE08.VAL") field(INPI, "$(CM,recursive)00:CRYOPLC_HEARTBEATE09.VAL") field(INPJ, "$(CM,recursive)00:CRYOPLC_HEARTBEATE10.VAL") field(HIHI, "10") field(LOLO, "-1") field(HIGH, "8") field(LOW, "-1") field(HHSV, "MAJOR") field(LLSV, "MAJOR") field(HSV, "MINOR") field(LSV, "MAJOR") field(FLNK, "$(CM,recursive)00:CRYOPLC_HEARTBEATSUM") field(ASG, "READONLY") } # Consider it a heartbeat fault if HEARTBEATECT # severity is MAJOR (exceeded limit) or INVALID # (some other problem) record(calc, "$(CM,recursive)00:CRYOPLC_HEARTBEATCLC") { field(CALC, "A>=2?0:1") field(INPA, "$(CM,recursive)00:CRYOPLC_HEARTBEATECT.SEVR") field(ASG, "READONLY") } record(bi, "$(CM,recursive)00:CRYOPLC_HEARTBEATSUM") { field(INP, "$(CM,recursive)00:CRYOPLC_HEARTBEATCLC PP") field(ZSV, "MAJOR") field(ZNAM,"Fault") field(ONAM,"Ok") field(FLNK, "$(CM,recursive)00:CRYOPLC_HEARTBEATSUM_CNTDC") field(ASG, "READONLY") } record(calcout, "$(CM,recursive)00:CRYOPLC_HEARTBEATSUM_CNTDC") { field(DESC, "Diagnostic fault counter") field(CALC, "A") field(INPA, "$(CM,recursive)00:CRYOPLC_HEARTBEATSUM") field(INPB, "$(CM,recursive)00:CRYOPLC_HEARTBEATSUM_CNTD") field(OOPT, "When Zero") field(DOPT, "Use OCAL") field(OCAL, "B>2^16?0:B+1") field(OUT, "$(CM,recursive)00:CRYOPLC_HEARTBEATSUM_CNTD PP") } record(longin, "$(CM,recursive)00:CRYOPLC_HEARTBEATSUM_CNTD") { field(DESC, "Diagnostic fault count") field(VAL, "0") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,recursive)00:CRYOPLC_HEARTBEATSUM_CNTDCLR") { field(DESC, "Clear fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,recursive)00:CRYOPLC_HEARTBEATSUM_CNTD PP") }