#================================== #---------------------------------- # intlkHeLerfCmCommon.template: # # Cryo-module level records # to support LERF He interlocks # fed over CA by other systems # # Most signals here are not fail-safe: # 0 = ok, 1 = fault #---------------------------------- #================================== #================================== # #================================== # Value of 0 = ok, value of of 1 = fault record(bi, "$(PREF)CHL_INP") { field(DESC, "Mirror remote intlk PV") field(SCAN, "1 second") field(INP, "R4XXRFOFF NPP") field(ZNAM, "Ok") field(ONAM, "Fault") field(FLNK, "$(PREF)CHL_CALC") } record(calc, "$(PREF)CHL_CALC") { field(DESC, "Determine CHL fault") field(CALC, "B=3?E:A=C?D:E") field(INPA, "$(PREF)CHL_INP") field(INPB, "$(PREF)CHL_INP.SEVR") # C = remote pv ok value field(INPC, "0") # D = our internal ok value field(INPD, "0") # E = our internal fault value field(INPE, "1") field(FLNK, "$(PREF)CHL_LTCH_CALC") } record(calc, "$(PREF)CHL_LTCH_CALC") { field(DESC, "Determine CHL fault") field(CALC, "B=1?0:A") field(INPA, "$(PREF)CHL_CALC") field(INPB, "$(PREF)CHL_BYP") field(FLNK, "$(PREF)CHL_FLT") } record(bi, "$(PREF)CHL_FLT") { field(DESC, "Interlock status") field(ZNAM, "Ok") field(ONAM, "Fault") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") field(INP, "$(PREF)CHL_CALC") field(FLNK, "$(PREF)CHL_LTCH") } record(bi, "$(PREF)CHL_LTCH") { field(DESC, "Interlock status") field(ZNAM, "Ok") field(ONAM, "Fault") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") field(INP, "$(PREF)CHL_LTCH_CALC") field(FLNK, "$(PREF)CRYOSUM_CALC") } # Fault: 0 = ok, 1 = fault record(calc, "$(PREF)CRYOSUM_CALC") { field(DESC, "Cryo fault summary") field(CALC, "A+B=0?0:1") field(INPA, "$(PREF)CHL_LTCH") field(INPB, "$(PREF)CRYOPLC_FLTSUM") field(FLNK, "$(PREF)CRYOSUM_FLT") } record(bi, "$(PREF)CRYOSUM_FLT") { field(DESC, "Cryo fault summary") field(INP, "$(PREF)CRYOSUM_CALC") field(ZNAM, "Ok") field(ONAM, "Fault") field(OSV, "MAJOR") field(FLNK, "$(PREF)CRYOSUM_FO_CALC") } record(calcout, "$(PREF)CRYOSUM_FO_CALC") { field(DESC, "Cryo fault summary") field(CALC, "A") field(INPA, "$(PREF)CRYOSUM_FLT") field(OOPT, "When Zero") field(DOPT, "Use OCAL") # OCAL is RFS cryo interlock timeout in seconds # Set to large enough value to prevent nuisance # faults, but not so large to substantially # delay RF shutoff. field(OCAL, "3") # CRYOSUM_FO located in cryoCmLerf.template field(OUT, "$(PREF)CRYOSUM_FO PP") } record(bo, "$(PREF)CHL_BYP") { field(DESC, "Interlock bypass") field(ZNAM, "Not Bypassed") field(ONAM, "Bypassed") field(ZSV, "NO_ALARM") field(OSV, "MINOR") field(VAL, "0") field(PINI, "YES") info(autosaveFields,"VAL") } # Bypass support removed from common # databases because not desired in production. # (Firmware bypass still exists.) # But at LERF, it may be desirable to bypass # the interlock from the cryo PLC while # keeping the LERF/JLab cryo inputs record(bi, "$(PREF)CRYOPLC_BYP") { field(DESC, "Local CM cryo interlock bypass") field(ZNAM, "Not bypassed") field(ONAM, "Bypassed") field(OSV, "MINOR") field(VAL, "0") field(PINI, "YES") info(autosaveFields, "VAL") } record(calcout, "$(PREF)CRYOPLC_FLTSUM_CALC") { field(DESC, "Local CM cryo intlk with bypass") field(SCAN, "1 second") field(CALC, "A?0:B") field(INPA, "$(PREF)CRYOPLC_BYP") field(INPB, "$(PREF)CRYOPLC_FLT") field(FLNK, "$(PREF)CRYOPLC_FLTSUM") # field(ASG, "NOWRITE") } # Match LLRF FW conventions: 0 = ok, 1 = fault # Used by CRYOSUM_CALC record(bi, "$(PREF)CRYOPLC_FLTSUM") { field(DESC, "Local CM cryo intlk with bypass") field(INP, "$(PREF)CRYOPLC_FLTSUM_CALC") field(ZNAM, "Ok") field(ONAM, "Fault") field(OSV, "MAJOR") # field(ASG, "NOWRITE") }