# intlkHeLerfCmCommon.template:
#
# Cryo-module level records 
# to support LERF He interlocks
# fed over CA by other systems
#
# Most signals here are not fail-safe:
# 0 = ok, 1 = fault
#----------------------------------
#==================================

#==================================
#
#==================================

# Value of 0 = ok, value of of 1 = fault
record(bi, "$(PREF)CHL_INP") {
  field(DESC, "Mirror remote intlk PV")
  field(SCAN, "1 second")
  field(INP,  "R4XXRFOFF NPP")
  field(ZNAM, "Ok")
  field(ONAM, "Fault")
  field(FLNK, "$(PREF)HELEVEL_INP")
}

# Value of 0 = fault, anything else ok
record(longin, "$(PREF)HELEVEL_INP") {
  field(DESC, "Mirror remote intlk PV")
  field(INP,  "CLL:$(CRYOCM):2301:DS:ALM NPP")
  field(FLNK, "$(PREF)CHL_CALC")
}

record(calc, "$(PREF)CHL_CALC") {
  field(DESC, "Determine CHL fault")
  field(CALC, "B=3?E:A=C?D:E")
  field(INPA, "$(PREF)CHL_INP")
  field(INPB, "$(PREF)CHL_INP.SEVR")
# C = remote pv ok value
  field(INPC, "0")
# D = our internal ok value
  field(INPD, "0")
# E = our internal fault value
  field(INPE, "1")
  field(FLNK, "$(PREF)CHL_LTCH_CALC")
}

record(calc, "$(PREF)CHL_LTCH_CALC") {
  field(DESC, "Determine CHL fault")
  field(CALC, "B=1?0:A")
  field(INPA, "$(PREF)CHL_CALC")
  field(INPB, "$(PREF)CHL_BYP")
  field(FLNK, "$(PREF)CHL_FLT")
}

record(bi, "$(PREF)CHL_FLT") {
  field(DESC, "Interlock status")
  field(ZNAM, "Ok")
  field(ONAM, "Fault")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "MAJOR")
  field(INP,  "$(PREF)CHL_CALC")
  field(FLNK, "$(PREF)CHL_LTCH")
}

record(bi, "$(PREF)CHL_LTCH") {
  field(DESC, "Interlock status")
  field(ZNAM, "Ok")
  field(ONAM, "Fault")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "MAJOR")
  field(INP,  "$(PREF)CHL_LTCH_CALC")
  field(FLNK, "$(PREF)HELEVEL_CALC")
}

record(calc, "$(PREF)HELEVEL_CALC") {
  field(DESC, "Determine HeLevel fault")
  field(CALC, "B=3?E:A=C?E:D")
  field(INPA, "$(PREF)HELEVEL_INP")
  field(INPB, "$(PREF)HELEVEL_INP.SEVR")
# C = remote pv fault value
  field(INPC, "0")
# D = our internal ok value
  field(INPD, "0")
# E = our internal fault value
  field(INPE, "1")
  field(FLNK, "$(PREF)HELEVEL_LTCH_CALC")
}

record(calc, "$(PREF)HELEVEL_LTCH_CALC") {
  field(DESC, "Determine He level fault")
  field(CALC, "B=1?0:A")
  field(INPA, "$(PREF)HELEVEL_CALC")
  field(INPB, "$(PREF)HELEVEL_BYP")
  field(FLNK, "$(PREF)HELEVEL_FLT")
}

record(bi, "$(PREF)HELEVEL_FLT") {
  field(DESC, "Interlock status")
  field(ZNAM, "Ok")
  field(ONAM, "Fault")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "MAJOR")
  field(INP,  "$(PREF)HELEVEL_CALC")
  field(FLNK, "$(PREF)HELEVEL_LTCH")
}

record(bi, "$(PREF)HELEVEL_LTCH") {
  field(DESC, "Interlock status")
  field(ZNAM, "Ok")
  field(ONAM, "Fault")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "MAJOR")
  field(INP,  "$(PREF)HELEVEL_LTCH_CALC")
  field(FLNK, "$(PREF)CRYOSUM_CALC")
}

# Fault register: 0 = ok, 1 = fault
record(calcout, "$(PREF)CRYOSUM_CALC") {
  field(DESC, "Set intlk reg")
  field(SCAN, "1 second")
  field(CALC, "A=0&&B=0?0:1")
  field(INPA, "$(PREF)CHL_LTCH")
  field(INPB, "$(PREF)HELEVEL_LTCH")
  field(OOPT, "On Change")
  field(DOPT, "Use CALC")
  field(OUT,  "$(PREF)CRYOSUM_FO PP")
}

record(dfanout, "$(PREF)CRYOSUM_FO") {
  field(DESC, "Write He fault intlk regs")
  field(SELM, "All")
  field(OMSL, "closed_loop")
  field(DOL,  "$(PREF)CRYOSUM_CALC")
  field(OUTA, "$(PREF)CRYOSUMA_FLT_SET PP")
  field(OUTB, "$(PREF)CRYOSUMB_FLT_SET PP")
}

record(bo, "$(PREF)HELEVEL_BYP") {
  field(DESC, "Interlock bypass")
  field(ZNAM, "Not Bypassed")
  field(ONAM, "Bypassed")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "MAJOR")
  field(VAL,  "0")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(bo, "$(PREF)CHL_BYP") {
  field(DESC, "Interlock bypass")
  field(ZNAM, "Not Bypassed")
  field(ONAM, "Bypassed")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "MAJOR")
  field(VAL,  "0")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}