# TODO: Figure out if gradient
# data available. If so, reset
# that bit regularly. Also,
# determine if need intermediate
# buffer for GACT.

record(aSub, "$(CM)00:RFCRYO_STAT_SUB") {
  field(INAM, "")
  field(SNAM, "asub_cryo")
  field(SCAN, "$(CRYOSCAN)") 
# Inputs
#TODO: figure out processing chain of RF state
  field(FTA, "SHORT") # cavity 1 on/off
  field(INPA, "$(CM)10:RFSTATE")
  field(FTB, "SHORT") # cavity 2 on/off
  field(INPB, "$(CM)20:RFSTATE")
  field(FTC, "SHORT") # cavity 3 on/off
  field(INPC, "$(CM)30:RFSTATE")
  field(FTD, "SHORT") # cavity 4 on/off
  field(INPD, "$(CM)40:RFSTATE")
  field(FTE, "SHORT") # cavity 5 on/off
  field(INPE, "$(CM)50:RFSTATE")
  field(FTF, "SHORT") # cavity 6 on/off
  field(INPF, "$(CM)60:RFSTATE")
  field(FTG, "SHORT") # cavity 7 on/off
  field(INPG, "$(CM)70:RFSTATE")
  field(FTH, "SHORT") # cavity 8 on/off
  field(INPH, "$(CM)80:RFSTATE")
  field(FTI, "SHORT") # cavity 1 gradient data avail
  field(INPI, "$(CM)10:GDATA")
  field(FTJ, "SHORT") # cavity 2 gradient data avail
  field(INPJ, "$(CM)20:GDATA")
  field(FTK, "SHORT") # cavity 3 gradient data avail
  field(INPK, "$(CM)30:GDATA")
  field(FTL, "SHORT") # cavity 4 gradient data avail
  field(INPL, "$(CM)40:GDATA")
  field(FTM, "SHORT") # cavity 5 gradient data avail
  field(INPM, "$(CM)50:GDATA")
  field(FTN, "SHORT") # cavity 6 gradient data avail
  field(INPN, "$(CM)60:GDATA")
  field(FTO, "SHORT") # cavity 7 gradient data avail
  field(INPO, "$(CM)70:GDATA")
  field(FTP, "SHORT") # cavity 8 gradient data avail
  field(INPP, "$(CM)80:GDATA")
# Outputs
  field(FTVA, "LONG") # status word to cryo (add details)
  field(FTVB, "LONG") # mask to process other records
  field(FLNK, "$(CM)00:RFCRYO_STAT")
}

#==================================
# Write heartbeat and status to cryo PLC
#==================================

record(calc, "$(CM)00:RFCRYO_HEARTBEAT_CALC") {
  field(DESC, "Write heartbeat to cryo")
  field(CALC, "A=1?0:1")
  field(INPA, "$(CM)00:RFCRYO_HEARTBEAT_CALC NPP")
}

record(mbboDirect, "$(CM)00:RFCRYO_HEARTBEAT") {
  field(DESC, "Write heartbeat to cryo")
  field(SCAN, "$(CRYOSCAN)")
  field(DTYP, "EtherIP")
  field(OMSL, "closed_loop")
  field(DOL,  "$(CM)00:RFCRYO_HEARTBEAT_CALC PP")
  field(OUT, "@$(PLC) $(CMCRYO)HEART")
}

record(mbboDirect, "$(CM)00:RFCRYO_STAT") {
  field(DESC, "Write status word to cryo")
  field(SCAN, "$(CRYOSCAN)")
  field(DTYP, "EtherIP")
  field(OMSL, "closed_loop")
  field(DOL,  "$(CM)00:RFCRYO_STAT_SUB.VALA MSI PP")
# If invalid input, don't send value to cryo
  field(IVOA, "Don't drive outputs")
  field(NOBT, "16")
  field(OUT, "@$(PLC) $(CMCRYO)CAVSTATUS")
}

#==================================
# Inhibit RF if cryo interlock fault
# or cryo heartbeat not updating.
#
# If interlock is bypassed, then
# RF is permitted regardless of cryo
# status. This is for use at test
# stands.
#==================================

record(bi, "$(CM)00:CRYO_INTLK_BYP") {
  field(DESC, "Cryo interlock bypassed")
  field(ZNAM, "Not bypassed")
  field(ONAM, "Bypassed")
  field(OSV,  "MAJOR")
  field(VAL,  "0")
  field(PINI, "YES")
  info(autosaveFields, "VAL")
}

# TODO: Use full cryo status word or just overall ok bit?
record(calcout, "$(CM)00:RFCRYO_RFINHIB") {
  field(DESC, "Determine if cryo ok for RF")
  field(SCAN, "$(CRYOSCAN)")
# In CALC, result is non-zero so that
# it writes its output link the first time
  field(CALC, "C?2:(A&&B)?2:1")
# Use OCAL to calculate the actual output of 0 or 1
  field(OCAL, "C?1:(A&&B)?1:0")
  field(DOPT, "Use OCAL")
  field(INPA, "$(CM)00:CRYO_OK")
  field(INPB, "$(CM)00:CRYOHEARTBEAT_FLT")
  field(INPC, "$(CM)00:CRYO_INTLK_BYP")
  field(OOPT, "On Change")
  field(OUT,  "$(CM)00:RFINHIB PP")
}

record(dfanout, "$(CM)00:RFINHIB") {
  field(DESC, "Inhibit/permit RF for CM")
  field(SELM, "All")
  field(OMSL, "closed_loop")
  field(DOL,  "$(CM)00:RFCRYO_RFINHIB.OVAL")
  field(OUTA, "$(CM)10:RFINHIB PP")
  field(OUTB, "$(CM)20:RFINHIB PP")
  field(OUTC, "$(CM)30:RFINHIB PP")
  field(OUTD, "$(CM)40:RFINHIB PP")
  field(OUTE, "$(CM)50:RFINHIB PP")
  field(OUTF, "$(CM)60:RFINHIB PP")
  field(OUTG, "$(CM)70:RFINHIB PP")
  field(OUTH, "$(CM)80:RFINHIB PP")
}

#==================================
# Read status word from cryo PLC
# and break out individual bits
#==================================

record(mbbiDirect, "$(CM)00:CRYOPLC_GETSTAT") {
  field(DESC, "Cryo overall health")
  field(SCAN, "$(CRYOSCAN)")
  field(DTYP, "EtherIP")
  field(INP,  "@$(PLC) $(CMCRYO)PLCSTATUS")
  field(NOBT, "16")
  field(FLNK, "$(CM)00:CRYO_OK")
}

record(bi, "$(CM)00:CRYO_OK") {
  field(DESC, "Cryo health status")
  field(INP,  "$(CM)00:CRYOPLC_GETSTAT.B0")
  field(ZNAM, "Fault")
  field(ZSV,  "MAJOR")
  field(ONAM, "Ok")
  field(FLNK, "$(CM)00:HELEVEL_FLT")
}

record(bi, "$(CM)00:HELEVEL_FLT") {
  field(DESC, "Cryo He level status")
  field(INP,  "$(CM)00:CRYOPLC_GETSTAT.B1")
  field(ZNAM, "Fault")
  field(ZSV,  "MAJOR")
  field(ONAM, "Ok")
  field(FLNK, "$(CM)00:HEPRES_FLT")
}

record(bi, "$(CM)00:HEPRES_FLT") {
  field(DESC, "Cryo He press status")
  field(INP,  "$(CM)00:CRYOPLC_GETSTAT.B2")
  field(ZNAM, "Fault")
  field(ZSV,  "MAJOR")
  field(ONAM, "Ok")
  field(FLNK, "$(CM)00:RFHEARTBEAT_FLT")
}

record(bi, "$(CM)00:RFHEARTBEAT_FLT") {
  field(DESC, "Cryo receives RF heartbeat")
  field(INP,  "$(CM)00:CRYOPLC_GETSTAT.B3")
  field(ZNAM, "Fault")
  field(ZSV,  "MAJOR")
  field(ONAM, "Ok")
}

record(bo, "$(CM)00:HEPRES_BYP") {
  field(DESC, "Interlock bypass")
  field(ZNAM, "Not Bypassed")
  field(ONAM, "Bypassed")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "MAJOR")
  field(VAL,  "0")
  field(PINI, "YES")
#  field(ASG,  "EOICDESK")
  info(autosaveFields,"VAL")
}

record(bo, "$(CM)00:HELEVEL_BYP") {
  field(DESC, "Interlock bypass")
  field(ZNAM, "Not Bypassed")
  field(ONAM, "Bypassed")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "MAJOR")
  field(VAL,  "0")
  field(PINI, "YES")
#  field(ASG,  "EOICDESK")
  info(autosaveFields,"VAL")
}

record(bo, "$(CM)00:CRYOHEARTBEAT_BYP") {
  field(DESC, "Interlock bypass")
  field(ZNAM, "Not Bypassed")
  field(ONAM, "Bypassed")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "MAJOR")
  field(VAL,  "0")
  field(PINI, "YES")
#  field(ASG,  "EOICDESK")
  info(autosaveFields,"VAL")
}

#==================================
# Read heartbeat from cryo PLC
# and determine if updating.
# TODO: determine/implement what
# constitutes fault/ok
# TODO: consider if fault detection
# should be driven by heartbeat
# read or stay independent
# TODO: maximize severity through chain?
#==================================

record(mbbiDirect, "$(CM)00:CRYOPLC_HEARTBEAT") {
  field(DESC, "Cryo heartbeat from PLC")
  field(SCAN, "$(CRYOSCAN)")
  field(DTYP, "EtherIP")
  field(INP,  "@$(PLC) $(CMCRYO)PLCHEART")
}

record(calc, "$(CM)00:CRYOPLC_HEARTBEATCALC") {
#TODO: have HEARTBEAT FLNK here?
  field(SCAN, "$(CRYOSCAN)")
  field(CALC, "A")
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEAT MS")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATCALC.VAL")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATERR")
}

record(calc, "$(CM)00:CRYOPLC_HEARTBEATERR") {
  field(CALC, "A=B?1:0")
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEATCALC.A")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATCALC.B")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATOK")
}

record(bi, "$(CM)00:CRYOPLC_HEARTBEATOK") {
  field(INP, "$(CM)00:CRYOPLC_HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATE01")
}

record(calc, "$(CM)00:CRYOPLC_HEARTBEATE10") {
  field(CALC, "A")
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEATE09.B")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATE10.VAL")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATECT")
}

record(calc, "$(CM)00:CRYOPLC_HEARTBEATE09") {
  field(CALC, "A")
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEATE08.B")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATE09.VAL")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATE10")
}

record(calc, "$(CM)00:CRYOPLC_HEARTBEATE08") {
  field(CALC, "A")
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEATE07.B")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATE08.VAL")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATE09")
}

record(calc, "$(CM)00:CRYOPLC_HEARTBEATE07") {
  field(CALC, "A")
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEATE06.B")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATE07.VAL")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATE08")
}

record(calc, "$(CM)00:CRYOPLC_HEARTBEATE06") {
  field(CALC, "A")
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEATE05.B")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATE06.VAL")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATE07")
}

record(calc, "$(CM)00:CRYOPLC_HEARTBEATE05") {
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEATE04.B")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATE05.VAL")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATE06")
  field(CALC, "A")
}

record(calc, "$(CM)00:CRYOPLC_HEARTBEATE04") {
  field(CALC, "A")
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEATE03.B")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATE04.VAL")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATE05")
}

record(calc, "$(CM)00:CRYOPLC_HEARTBEATE03") {
  field(CALC, "A")
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEATE02.B")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATE03.VAL")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATE04")
}

record(calc, "$(CM)00:CRYOPLC_HEARTBEATE02") {
  field(CALC, "A")
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEATE01.B")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATE02.VAL")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATE03")
}

record(calc, "$(CM)00:CRYOPLC_HEARTBEATE01") {
  field(CALC, "A")
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEATERR.VAL")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATE01.VAL")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATE02")
}

record(calc, "$(CM)00:CRYOPLC_HEARTBEATECT") {
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEATE01.VAL")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATE02.VAL")
  field(INPC, "$(CM)00:CRYOPLC_HEARTBEATE03.VAL")
  field(INPD, "$(CM)00:CRYOPLC_HEARTBEATE04.VAL")
  field(INPE, "$(CM)00:CRYOPLC_HEARTBEATE05.VAL")
  field(INPF, "$(CM)00:CRYOPLC_HEARTBEATE06.VAL")
  field(INPG, "$(CM)00:CRYOPLC_HEARTBEATE07.VAL")
  field(INPH, "$(CM)00:CRYOPLC_HEARTBEATE08.VAL")
  field(INPI, "$(CM)00:CRYOPLC_HEARTBEATE09.VAL")
  field(INPJ, "$(CM)00:CRYOPLC_HEARTBEATE10.VAL")
  field(HIHI, "10")
  field(LOLO, "-1")
  field(HIGH, "8")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
  field(FLNK, "$(CM)00:CRYOHEARTBEAT_FLT")
}

# Consider it a heartbeat fault if HEARTBEATECT
# severity is MAJOR (exceeded limit) or INVALID
# (some other problem)
record(calc, "$(CM)00:CRYOPLC_HEARTBEATCLC") {
  field(CALC, "A>=2?0:1")
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEATECT.SEVR")
}

record(bi, "$(CM)00:CRYOHEARTBEAT_FLT") {
  field(INP, "$(CM)00:CRYOPLC_HEARTBEATCLC PP")
  field(ZSV, "MAJOR")
  field(ZNAM,"Fault")
  field(ONAM,"Ok")
}