# cryoCavLerf.template:
#
# Support LERF communication with cryo
#----------------------------------
#==================================

#==================================
#
#==================================

# Dissipated power calculation from AACTMEAN
# Keep for now as comparison with AACT_SQR value
# Remove when this later fully commissioned
record(calc, "$(CM)10:RFCRYO_PWRDISS_CALC") {
  field(DESC, "Calc dissipated power")
  field(CALC, "A*A*1e12/B/C")
  field(EGU, "W")
  field(INPA, "$(CM)10:AACTMEAN CP")
  field(INPB, "$(CM)10:IMPED CP")
  field(INPC, "$(CM)10:Q0 CP")
}

# TODO: add source PV (when avail in FW)
record(ao, "$(CM)10:RFCRYO_PWRDISS") {
  field(DESC, "Write gradient to cryo")
  field(DTYP, "EtherIP")
  field(OMSL, "closed_loop")
  field(DOL,  "$(CM)00:RFCRYO_SUB.VALA")
$(TEST)  field(OUT, "@$(PLC) RF_1_CRF_1155_GRADIENT[$(CMCRYO)] S 1")
  field(EGU, "W")
# field(ASG, "")
  field(FLNK, "$(CM)10:RFCRYO_HEARTBEATSTATCALC")
}

# Individual cavity heartbeats use 1 bit of mask
record(calc, "$(CM)10:RFCRYO_HEARTBEATSTATCALC") {
  field(DESC, "RF->cryo heartbeat status")
  field(CALC, "(A>>(B-1))&1")
  field(INPA, "$(CM)00:RFCRYO_SUB.VALI")
  field(INPB, "1")
  field(TSEL, "$(CM)00:RFCRYO_STAT.TIME")
  field(FLNK, "$(CM)10:RFCRYO_HEARTBEATSTAT")
}

record(bi, "$(CM)10:RFCRYO_HEARTBEATSTAT") {
  field(DESC, "RF->cryo heartbeat status")
  field(INP,  "$(CM)10:RFCRYO_HEARTBEATSTATCALC")
  field(ZNAM, "Fault")
  field(ZSV,  "MAJOR")
  field(ONAM, "Ok")
  field(TSEL, "$(CM)00:RFCRYO_STAT.TIME")
}
#==================================
#----------------------------------
# cryoCavLerf.template:
#
# Support LERF communication with cryo
#----------------------------------
#==================================

#==================================
#
#==================================

# Dissipated power calculation from AACTMEAN
# Keep for now as comparison with AACT_SQR value
# Remove when this later fully commissioned
record(calc, "$(CM)20:RFCRYO_PWRDISS_CALC") {
  field(DESC, "Calc dissipated power")
  field(CALC, "A*A*1e12/B/C")
  field(EGU, "W")
  field(INPA, "$(CM)20:AACTMEAN CP")
  field(INPB, "$(CM)20:IMPED CP")
  field(INPC, "$(CM)20:Q0 CP")
}

# TODO: add source PV (when avail in FW)
record(ao, "$(CM)20:RFCRYO_PWRDISS") {
  field(DESC, "Write gradient to cryo")
  field(DTYP, "EtherIP")
  field(OMSL, "closed_loop")
  field(DOL,  "$(CM)00:RFCRYO_SUB.VALB")
$(TEST)  field(OUT, "@$(PLC) RF_1_CRF_1255_GRADIENT[$(CMCRYO)] S 1")
  field(EGU, "W")
# field(ASG, "")
  field(FLNK, "$(CM)20:RFCRYO_HEARTBEATSTATCALC")
}

# Individual cavity heartbeats use 1 bit of mask
record(calc, "$(CM)20:RFCRYO_HEARTBEATSTATCALC") {
  field(DESC, "RF->cryo heartbeat status")
  field(CALC, "(A>>(B-1))&1")
  field(INPA, "$(CM)00:RFCRYO_SUB.VALI")
  field(INPB, "2")
  field(TSEL, "$(CM)00:RFCRYO_STAT.TIME")
  field(FLNK, "$(CM)20:RFCRYO_HEARTBEATSTAT")
}

record(bi, "$(CM)20:RFCRYO_HEARTBEATSTAT") {
  field(DESC, "RF->cryo heartbeat status")
  field(INP,  "$(CM)20:RFCRYO_HEARTBEATSTATCALC")
  field(ZNAM, "Fault")
  field(ZSV,  "MAJOR")
  field(ONAM, "Ok")
  field(TSEL, "$(CM)00:RFCRYO_STAT.TIME")
}
#==================================
#----------------------------------
# cryoCavLerf.template:
#
# Support LERF communication with cryo
#----------------------------------
#==================================

#==================================
#
#==================================

# Dissipated power calculation from AACTMEAN
# Keep for now as comparison with AACT_SQR value
# Remove when this later fully commissioned
record(calc, "$(CM)30:RFCRYO_PWRDISS_CALC") {
  field(DESC, "Calc dissipated power")
  field(CALC, "A*A*1e12/B/C")
  field(EGU, "W")
  field(INPA, "$(CM)30:AACTMEAN CP")
  field(INPB, "$(CM)30:IMPED CP")
  field(INPC, "$(CM)30:Q0 CP")
}

# TODO: add source PV (when avail in FW)
record(ao, "$(CM)30:RFCRYO_PWRDISS") {
  field(DESC, "Write gradient to cryo")
  field(DTYP, "EtherIP")
  field(OMSL, "closed_loop")
  field(DOL,  "$(CM)00:RFCRYO_SUB.VALC")
$(TEST)  field(OUT, "@$(PLC) RF_1_CRF_1355_GRADIENT[$(CMCRYO)] S 1")
  field(EGU, "W")
# field(ASG, "")
  field(FLNK, "$(CM)30:RFCRYO_HEARTBEATSTATCALC")
}

# Individual cavity heartbeats use 1 bit of mask
record(calc, "$(CM)30:RFCRYO_HEARTBEATSTATCALC") {
  field(DESC, "RF->cryo heartbeat status")
  field(CALC, "(A>>(B-1))&1")
  field(INPA, "$(CM)00:RFCRYO_SUB.VALI")
  field(INPB, "3")
  field(TSEL, "$(CM)00:RFCRYO_STAT.TIME")
  field(FLNK, "$(CM)30:RFCRYO_HEARTBEATSTAT")
}

record(bi, "$(CM)30:RFCRYO_HEARTBEATSTAT") {
  field(DESC, "RF->cryo heartbeat status")
  field(INP,  "$(CM)30:RFCRYO_HEARTBEATSTATCALC")
  field(ZNAM, "Fault")
  field(ZSV,  "MAJOR")
  field(ONAM, "Ok")
  field(TSEL, "$(CM)00:RFCRYO_STAT.TIME")
}
#==================================
#----------------------------------
# cryoCavLerf.template:
#
# Support LERF communication with cryo
#----------------------------------
#==================================

#==================================
#
#==================================

# Dissipated power calculation from AACTMEAN
# Keep for now as comparison with AACT_SQR value
# Remove when this later fully commissioned
record(calc, "$(CM)40:RFCRYO_PWRDISS_CALC") {
  field(DESC, "Calc dissipated power")
  field(CALC, "A*A*1e12/B/C")
  field(EGU, "W")
  field(INPA, "$(CM)40:AACTMEAN CP")
  field(INPB, "$(CM)40:IMPED CP")
  field(INPC, "$(CM)40:Q0 CP")
}

# TODO: add source PV (when avail in FW)
record(ao, "$(CM)40:RFCRYO_PWRDISS") {
  field(DESC, "Write gradient to cryo")
  field(DTYP, "EtherIP")
  field(OMSL, "closed_loop")
  field(DOL,  "$(CM)00:RFCRYO_SUB.VALD")
$(TEST)  field(OUT, "@$(PLC) RF_1_CRF_1455_GRADIENT[$(CMCRYO)] S 1")
  field(EGU, "W")
# field(ASG, "")
  field(FLNK, "$(CM)40:RFCRYO_HEARTBEATSTATCALC")
}

# Individual cavity heartbeats use 1 bit of mask
record(calc, "$(CM)40:RFCRYO_HEARTBEATSTATCALC") {
  field(DESC, "RF->cryo heartbeat status")
  field(CALC, "(A>>(B-1))&1")
  field(INPA, "$(CM)00:RFCRYO_SUB.VALI")
  field(INPB, "4")
  field(TSEL, "$(CM)00:RFCRYO_STAT.TIME")
  field(FLNK, "$(CM)40:RFCRYO_HEARTBEATSTAT")
}

record(bi, "$(CM)40:RFCRYO_HEARTBEATSTAT") {
  field(DESC, "RF->cryo heartbeat status")
  field(INP,  "$(CM)40:RFCRYO_HEARTBEATSTATCALC")
  field(ZNAM, "Fault")
  field(ZSV,  "MAJOR")
  field(ONAM, "Ok")
  field(TSEL, "$(CM)00:RFCRYO_STAT.TIME")
}
#==================================
#----------------------------------
# cryoCavLerf.template:
#
# Support LERF communication with cryo
#----------------------------------
#==================================

#==================================
#
#==================================

# Dissipated power calculation from AACTMEAN
# Keep for now as comparison with AACT_SQR value
# Remove when this later fully commissioned
record(calc, "$(CM)50:RFCRYO_PWRDISS_CALC") {
  field(DESC, "Calc dissipated power")
  field(CALC, "A*A*1e12/B/C")
  field(EGU, "W")
  field(INPA, "$(CM)50:AACTMEAN CP")
  field(INPB, "$(CM)50:IMPED CP")
  field(INPC, "$(CM)50:Q0 CP")
}

# TODO: add source PV (when avail in FW)
record(ao, "$(CM)50:RFCRYO_PWRDISS") {
  field(DESC, "Write gradient to cryo")
  field(DTYP, "EtherIP")
  field(OMSL, "closed_loop")
  field(DOL,  "$(CM)00:RFCRYO_SUB.VALE")
$(TEST)  field(OUT, "@$(PLC) RF_1_CRF_1555_GRADIENT[$(CMCRYO)] S 1")
  field(EGU, "W")
# field(ASG, "")
  field(FLNK, "$(CM)50:RFCRYO_HEARTBEATSTATCALC")
}

# Individual cavity heartbeats use 1 bit of mask
record(calc, "$(CM)50:RFCRYO_HEARTBEATSTATCALC") {
  field(DESC, "RF->cryo heartbeat status")
  field(CALC, "(A>>(B-1))&1")
  field(INPA, "$(CM)00:RFCRYO_SUB.VALI")
  field(INPB, "5")
  field(TSEL, "$(CM)00:RFCRYO_STAT.TIME")
  field(FLNK, "$(CM)50:RFCRYO_HEARTBEATSTAT")
}

record(bi, "$(CM)50:RFCRYO_HEARTBEATSTAT") {
  field(DESC, "RF->cryo heartbeat status")
  field(INP,  "$(CM)50:RFCRYO_HEARTBEATSTATCALC")
  field(ZNAM, "Fault")
  field(ZSV,  "MAJOR")
  field(ONAM, "Ok")
  field(TSEL, "$(CM)00:RFCRYO_STAT.TIME")
}
#==================================
#----------------------------------
# cryoCavLerf.template:
#
# Support LERF communication with cryo
#----------------------------------
#==================================

#==================================
#
#==================================

# Dissipated power calculation from AACTMEAN
# Keep for now as comparison with AACT_SQR value
# Remove when this later fully commissioned
record(calc, "$(CM)60:RFCRYO_PWRDISS_CALC") {
  field(DESC, "Calc dissipated power")
  field(CALC, "A*A*1e12/B/C")
  field(EGU, "W")
  field(INPA, "$(CM)60:AACTMEAN CP")
  field(INPB, "$(CM)60:IMPED CP")
  field(INPC, "$(CM)60:Q0 CP")
}

# TODO: add source PV (when avail in FW)
record(ao, "$(CM)60:RFCRYO_PWRDISS") {
  field(DESC, "Write gradient to cryo")
  field(DTYP, "EtherIP")
  field(OMSL, "closed_loop")
  field(DOL,  "$(CM)00:RFCRYO_SUB.VALF")
$(TEST)  field(OUT, "@$(PLC) RF_1_CRF_1655_GRADIENT[$(CMCRYO)] S 1")
  field(EGU, "W")
# field(ASG, "")
  field(FLNK, "$(CM)60:RFCRYO_HEARTBEATSTATCALC")
}

# Individual cavity heartbeats use 1 bit of mask
record(calc, "$(CM)60:RFCRYO_HEARTBEATSTATCALC") {
  field(DESC, "RF->cryo heartbeat status")
  field(CALC, "(A>>(B-1))&1")
  field(INPA, "$(CM)00:RFCRYO_SUB.VALI")
  field(INPB, "6")
  field(TSEL, "$(CM)00:RFCRYO_STAT.TIME")
  field(FLNK, "$(CM)60:RFCRYO_HEARTBEATSTAT")
}

record(bi, "$(CM)60:RFCRYO_HEARTBEATSTAT") {
  field(DESC, "RF->cryo heartbeat status")
  field(INP,  "$(CM)60:RFCRYO_HEARTBEATSTATCALC")
  field(ZNAM, "Fault")
  field(ZSV,  "MAJOR")
  field(ONAM, "Ok")
  field(TSEL, "$(CM)00:RFCRYO_STAT.TIME")
}
#==================================
#----------------------------------
# cryoCavLerf.template:
#
# Support LERF communication with cryo
#----------------------------------
#==================================

#==================================
#
#==================================

# Dissipated power calculation from AACTMEAN
# Keep for now as comparison with AACT_SQR value
# Remove when this later fully commissioned
record(calc, "$(CM)70:RFCRYO_PWRDISS_CALC") {
  field(DESC, "Calc dissipated power")
  field(CALC, "A*A*1e12/B/C")
  field(EGU, "W")
  field(INPA, "$(CM)70:AACTMEAN CP")
  field(INPB, "$(CM)70:IMPED CP")
  field(INPC, "$(CM)70:Q0 CP")
}

# TODO: add source PV (when avail in FW)
record(ao, "$(CM)70:RFCRYO_PWRDISS") {
  field(DESC, "Write gradient to cryo")
  field(DTYP, "EtherIP")
  field(OMSL, "closed_loop")
  field(DOL,  "$(CM)00:RFCRYO_SUB.VALG")
$(TEST)  field(OUT, "@$(PLC) RF_1_CRF_1755_GRADIENT[$(CMCRYO)] S 1")
  field(EGU, "W")
# field(ASG, "")
  field(FLNK, "$(CM)70:RFCRYO_HEARTBEATSTATCALC")
}

# Individual cavity heartbeats use 1 bit of mask
record(calc, "$(CM)70:RFCRYO_HEARTBEATSTATCALC") {
  field(DESC, "RF->cryo heartbeat status")
  field(CALC, "(A>>(B-1))&1")
  field(INPA, "$(CM)00:RFCRYO_SUB.VALI")
  field(INPB, "7")
  field(TSEL, "$(CM)00:RFCRYO_STAT.TIME")
  field(FLNK, "$(CM)70:RFCRYO_HEARTBEATSTAT")
}

record(bi, "$(CM)70:RFCRYO_HEARTBEATSTAT") {
  field(DESC, "RF->cryo heartbeat status")
  field(INP,  "$(CM)70:RFCRYO_HEARTBEATSTATCALC")
  field(ZNAM, "Fault")
  field(ZSV,  "MAJOR")
  field(ONAM, "Ok")
  field(TSEL, "$(CM)00:RFCRYO_STAT.TIME")
}
#==================================
#----------------------------------
# cryoCavLerf.template:
#
# Support LERF communication with cryo
#----------------------------------
#==================================

#==================================
#
#==================================

# Dissipated power calculation from AACTMEAN
# Keep for now as comparison with AACT_SQR value
# Remove when this later fully commissioned
record(calc, "$(CM)80:RFCRYO_PWRDISS_CALC") {
  field(DESC, "Calc dissipated power")
  field(CALC, "A*A*1e12/B/C")
  field(EGU, "W")
  field(INPA, "$(CM)80:AACTMEAN CP")
  field(INPB, "$(CM)80:IMPED CP")
  field(INPC, "$(CM)80:Q0 CP")
}

# TODO: add source PV (when avail in FW)
record(ao, "$(CM)80:RFCRYO_PWRDISS") {
  field(DESC, "Write gradient to cryo")
  field(DTYP, "EtherIP")
  field(OMSL, "closed_loop")
  field(DOL,  "$(CM)00:RFCRYO_SUB.VALH")
$(TEST)  field(OUT, "@$(PLC) RF_1_CRF_1855_GRADIENT[$(CMCRYO)] S 1")
  field(EGU, "W")
# field(ASG, "")
  field(FLNK, "$(CM)80:RFCRYO_HEARTBEATSTATCALC")
}

# Individual cavity heartbeats use 1 bit of mask
record(calc, "$(CM)80:RFCRYO_HEARTBEATSTATCALC") {
  field(DESC, "RF->cryo heartbeat status")
  field(CALC, "(A>>(B-1))&1")
  field(INPA, "$(CM)00:RFCRYO_SUB.VALI")
  field(INPB, "8")
  field(TSEL, "$(CM)00:RFCRYO_STAT.TIME")
  field(FLNK, "$(CM)80:RFCRYO_HEARTBEATSTAT")
}

record(bi, "$(CM)80:RFCRYO_HEARTBEATSTAT") {
  field(DESC, "RF->cryo heartbeat status")
  field(INP,  "$(CM)80:RFCRYO_HEARTBEATSTATCALC")
  field(ZNAM, "Fault")
  field(ZSV,  "MAJOR")
  field(ONAM, "Ok")
  field(TSEL, "$(CM)00:RFCRYO_STAT.TIME")
}
# Notes on process periods:
# 1 second: LLRF reads amplitude-squared from FW,
#           calculates dissipated power, performs
#           checks, sends heartbeat to cryo
# 1 second: LLRF reads Cryo HB/fault status
# 2 second: Cryo changes its heartbeat, so LLRF 
#           scanning every 1 second will detect change;
#           LLRF checks 10 times (10 seconds); if no
#           changes during that period, this is a heartbeat fault
# Process subroutine after firmware AACT_SQR reads to
# avoid stale data, which results in heartbeat counter
# not updating. In that case, Cryo currently assumes
# zero dissipated power.
# 10/1/21: In current configuration, LLRF processes
# data at 1 Hz and Cryo monitors 1 bit of heartbeat
# for 10 seconds before registering the fault.
record(fanout, "$(CM)00:RFCRYO_SUB_FO_") {
  field(DESC, "Process cryo records")
  field(SCAN, "1 second")
  field(SELM, "All")
  field(LNK1, "$(CM)10:AACT_SQR_READ")
  field(LNK2, "$(CM)20:AACT_SQR_READ")
  field(LNK3, "$(CM)30:AACT_SQR_READ")
  field(LNK4, "$(CM)40:AACT_SQR_READ")
  field(LNK5, "$(CM)50:AACT_SQR_READ")
  field(LNK6, "$(CM)00:RFCRYO_SUB_FO2_")
}
record(fanout, "$(CM)00:RFCRYO_SUB_FO2_") {
  field(DESC, "Process cryo records")
  field(SELM, "All")
  field(LNK1, "$(CM)60:AACT_SQR_READ")
  field(LNK2, "$(CM)70:AACT_SQR_READ")
  field(LNK3, "$(CM)80:AACT_SQR_READ")
  field(LNK4, "$(CM)00:RFCRYO_SUB_FO3_")
}
record(seq, "$(CM)00:RFCRYO_SUB_FO3_") {
  field(SELM, "All")
  field(DLY0, "0.5")
  field(LNK0, "$(CM)00:RFCRYO_SUB PP")
}

record(aSub, "$(CM)00:RFCRYO_SUB") {
  field(INAM, "asub_cryo_init")
  field(SNAM, "asub_cryo")
  field(DISV, "1")
# Inputs
# Subroutine checks PWRDISS severity and timestamp
  field(FTA, "DOUBLE") # cavity 1 amplitude
  field(INPA, "$(CM)10:PWRDISS")
  field(FTB, "DOUBLE") # cavity 2 amplitude
  field(INPB, "$(CM)20:PWRDISS")
  field(FTC, "DOUBLE") # cavity 3 amplitude
  field(INPC, "$(CM)30:PWRDISS")
  field(FTD, "DOUBLE") # cavity 4 amplitude
  field(INPD, "$(CM)40:PWRDISS")
  field(FTE, "DOUBLE") # cavity 5 amplitude
  field(INPE, "$(CM)50:PWRDISS")
  field(FTF, "DOUBLE") # cavity 6 amplitude
  field(INPF, "$(CM)60:PWRDISS")
  field(FTG, "DOUBLE") # cavity 7 amplitude
  field(INPG, "$(CM)70:PWRDISS")
  field(FTH, "DOUBLE") # cavity 8 amplitude
  field(INPH, "$(CM)80:PWRDISS")
# Outputs
# New value to send to cryo. If dissipated power
# SEVR == INVALID or timestamp unchanged, send last value
  field(FTVA, "DOUBLE") # cavity 1 last valid amplitude
  field(OUTA, "$(CM)10:RFCRYO_PWRDISS PP")
  field(FTVB, "DOUBLE") # cavity 2 last valid amplitude
  field(OUTB, "$(CM)20:RFCRYO_PWRDISS PP")
  field(FTVC, "DOUBLE") # cavity 3 last valid amplitude
  field(OUTC, "$(CM)30:RFCRYO_PWRDISS PP")
  field(FTVD, "DOUBLE") # cavity 4 last valid amplitude
  field(OUTD, "$(CM)40:RFCRYO_PWRDISS PP")
  field(FTVE, "DOUBLE") # cavity 5 last valid amplitude
  field(OUTE, "$(CM)50:RFCRYO_PWRDISS PP")
  field(FTVF, "DOUBLE") # cavity 6 last valid amplitude
  field(OUTF, "$(CM)60:RFCRYO_PWRDISS PP")
  field(FTVG, "DOUBLE") # cavity 7 last valid amplitude
  field(OUTG, "$(CM)70:RFCRYO_PWRDISS PP")
  field(FTVH, "DOUBLE") # cavity 8 last valid amplitude
  field(OUTH, "$(CM)80:RFCRYO_PWRDISS PP")
  field(FTVI, "ULONG")  # mask of valid amplitude
  field(FTVJ, "ULONG")  # mask of heartbeat counters
  field(OUTJ, "$(CM)00:RFCRYO_STAT PP")
  field(NOVK, "16")
  field(FTVK, "ULONG")  # PWRDISS timestamps
}

#==================================
# Write heartbeat word to PLC
#==================================

record(mbboDirect, "$(CM)00:RFCRYO_STAT") {
  field(DESC, "Write heartbeat word to cryo")
  field(SCAN, "Passive")
  field(DTYP, "EtherIP")
  field(NOBT, "16")
  field(OMSL, "closed_loop")
  field(DOL,  "$(CM)00:RFCRYO_SUB.VALJ")
$(TEST)  field(OUT,  "@$(PLC) RF_1_CRF_0000_HEARTBEAT[$(CMCRYO)] B 0 S 1")
}

#==================================
# Inhibit RF if cryo interlock fault
# or cryo heartbeat not updating.
#==================================

# Use cryo PLC summary bit (not individual
# He level/pressure bits) to determine fault
record(calcout, "$(CM)00:CRYOPLC_CALC") {
  field(DESC, "Local CM cryo intlk status")
  field(SCAN, "$(CRYOSCAN)")
  field(CALC, "A&B?0:1")
  field(INPA, "$(CM)00:CRYOPLC_SUM")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATSUM")
  field(FLNK, "$(CM)00:CRYOPLC_FLT")
}

# Match LLRF FW conventions: 0 = ok, 1 = fault
record(bi, "$(CM)00:CRYOPLC_FLT") {
  field(DESC, "Local CM cryo intlk status")
  field(INP,  "$(CM)00:CRYOPLC_CALC")
  field(ZNAM, "Ok")
  field(ONAM, "Fault")
  field(OSV,  "MAJOR")
}

# Processed by intlkHeLerfCmCommon.template
record(dfanout, "$(CM)00:CRYOSUM_FO") {
  field(DESC, "CM cryo fault")
  field(SELM, "All")
  field(OUTA, "$(CM)10:CRYO_TIME PP")
  field(OUTB, "$(CM)20:CRYO_TIME PP")
  field(OUTC, "$(CM)30:CRYO_TIME PP")
  field(OUTD, "$(CM)40:CRYO_TIME PP")
  field(OUTE, "$(CM)50:CRYO_TIME PP")
  field(OUTF, "$(CM)60:CRYO_TIME PP")
  field(OUTG, "$(CM)70:CRYO_TIME PP")
  field(OUTH, "$(CM)80:CRYO_TIME PP")
}

#==================================
# Read status word from cryo PLC
# and break out individual bits
#==================================

record(mbbiDirect, "$(CM)00:CRYOPLC_GETSTAT") {
  field(DESC, "Cryo overall health")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
$(TEST)  field(INP,  "@$(PLC) RF_1_CRF_0000_CM_STATUS[$(CMCRYO)] B 0")
  field(NOBT, "3")
  field(FLNK, "$(CM)00:CRYOPLC_SUM")
}

record(bi, "$(CM)00:CRYOPLC_SUM") {
  field(DESC, "CM cryo health summary")
  field(INP,  "$(CM)00:CRYOPLC_GETSTAT.B0")
  field(ZNAM, "Fault")
  field(ZSV,  "MAJOR")
  field(ONAM, "Ok")
  field(FLNK, "$(CM)00:CRYOPLC_HELEVEL")
}

record(bi, "$(CM)00:CRYOPLC_HELEVEL") {
  field(DESC, "CM cryo He level status")
  field(INP,  "$(CM)00:CRYOPLC_GETSTAT.B1")
  field(ZNAM, "Fault")
  field(ZSV,  "MAJOR")
  field(ONAM, "Ok")
  field(FLNK, "$(CM)00:CRYOPLC_HEPRES")
}

record(bi, "$(CM)00:CRYOPLC_HEPRES") {
  field(DESC, "CM cryo He press status")
  field(INP,  "$(CM)00:CRYOPLC_GETSTAT.B2")
  field(ZNAM, "Fault")
  field(ZSV,  "MAJOR")
  field(ONAM, "Ok")
}


# User-resettable diagnostic counters; currently
# separate from the other LLRF interlock counters,
# which increment on change-of-state and do not
# increment if the interlock is bypassed
record(calcout, "$(CM)00:CRYOPLC_SUM_CNTDC") {
  field(DESC, "Diagnostic fault counter")
  field(CALC, "A")
  field(INPA, "$(CM)00:CRYOPLC_SUM")
  field(INPB, "$(CM)00:CRYOPLC_SUM_CNTD")
  field(OOPT, "When Zero")
  field(DOPT, "Use OCAL")
  field(OCAL, "B>2^16?0:B+1")
  field(OUT, "$(CM)00:CRYOPLC_SUM_CNTD PP")
}

record(longin, "$(CM)00:CRYOPLC_SUM_CNTD") {
  field(DESC, "Diagnostic fault count")
  field(VAL,  "0")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(bo, "$(CM)00:CRYOPLC_SUM_CNTDCLR") {
  field(DESC, "Clear fault count")
  field(ZNAM, "Clear")
  field(ONAM, "Clear")
  field(OMSL, "closed_loop")
  field(DOL,  "0")
  field(OUT,  "$(CM)00:CRYOPLC_SUM_CNTD PP")
}

#==================================
# Read heartbeat from cryo PLC
# and determine if updating.
#==================================

record(bi, "$(CM)00:CRYOPLC_HEARTBEAT") {
  field(DESC, "Cryo heartbeat from PLC")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
$(TEST)  field(INP,  "@$(PLC) RF_1_CRF_0000_PLC_HEARTBEAT[$(CMCRYO)] B 0")
  field(ZNAM, "Low")
  field(ONAM, "High")
}

record(calc, "$(CM)00:CRYOPLC_HEARTBEATCALC") {
  field(SCAN, "1 second")
  field(CALC, "A")
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEAT.RVAL MS")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATCALC.VAL")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATERR")
  field(ASG,  "READONLY")
}

record(calc, "$(CM)00:CRYOPLC_HEARTBEATERR") {
  field(CALC, "A=B?1:0")
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEATCALC.A")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATCALC.B")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATOK")
  field(ASG,  "READONLY")
}

record(bi, "$(CM)00:CRYOPLC_HEARTBEATOK") {
  field(INP, "$(CM)00:CRYOPLC_HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATE01")
  field(ASG,  "READONLY")
}

record(calc, "$(CM)00:CRYOPLC_HEARTBEATE10") {
  field(CALC, "A")
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEATE09.B")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATE10.VAL")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATECT")
  field(ASG,  "READONLY")
}

record(calc, "$(CM)00:CRYOPLC_HEARTBEATE09") {
  field(CALC, "A")
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEATE08.B")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATE09.VAL")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATE10")
  field(ASG,  "READONLY")
}

record(calc, "$(CM)00:CRYOPLC_HEARTBEATE08") {
  field(CALC, "A")
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEATE07.B")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATE08.VAL")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATE09")
  field(ASG,  "READONLY")
}

record(calc, "$(CM)00:CRYOPLC_HEARTBEATE07") {
  field(CALC, "A")
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEATE06.B")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATE07.VAL")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATE08")
  field(ASG,  "READONLY")
}

record(calc, "$(CM)00:CRYOPLC_HEARTBEATE06") {
  field(CALC, "A")
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEATE05.B")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATE06.VAL")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATE07")
  field(ASG,  "READONLY")
}

record(calc, "$(CM)00:CRYOPLC_HEARTBEATE05") {
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEATE04.B")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATE05.VAL")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATE06")
  field(CALC, "A")
  field(ASG,  "READONLY")
}

record(calc, "$(CM)00:CRYOPLC_HEARTBEATE04") {
  field(CALC, "A")
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEATE03.B")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATE04.VAL")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATE05")
  field(ASG,  "READONLY")
}

record(calc, "$(CM)00:CRYOPLC_HEARTBEATE03") {
  field(CALC, "A")
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEATE02.B")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATE03.VAL")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATE04")
  field(ASG,  "READONLY")
}

record(calc, "$(CM)00:CRYOPLC_HEARTBEATE02") {
  field(CALC, "A")
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEATE01.B")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATE02.VAL")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATE03")
  field(ASG,  "READONLY")
}

record(calc, "$(CM)00:CRYOPLC_HEARTBEATE01") {
  field(CALC, "A")
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEATERR.VAL")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATE01.VAL")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATE02")
  field(ASG,  "READONLY")
}

record(calc, "$(CM)00:CRYOPLC_HEARTBEATECT") {
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEATE01.VAL")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATE02.VAL")
  field(INPC, "$(CM)00:CRYOPLC_HEARTBEATE03.VAL")
  field(INPD, "$(CM)00:CRYOPLC_HEARTBEATE04.VAL")
  field(INPE, "$(CM)00:CRYOPLC_HEARTBEATE05.VAL")
  field(INPF, "$(CM)00:CRYOPLC_HEARTBEATE06.VAL")
  field(INPG, "$(CM)00:CRYOPLC_HEARTBEATE07.VAL")
  field(INPH, "$(CM)00:CRYOPLC_HEARTBEATE08.VAL")
  field(INPI, "$(CM)00:CRYOPLC_HEARTBEATE09.VAL")
  field(INPJ, "$(CM)00:CRYOPLC_HEARTBEATE10.VAL")
  field(HIHI, "10")
  field(LOLO, "-1")
  field(HIGH, "8")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATSUM")
  field(ASG,  "READONLY")
}

# Consider it a heartbeat fault if HEARTBEATECT
# severity is MAJOR (exceeded limit) or INVALID
# (some other problem)
record(calc, "$(CM)00:CRYOPLC_HEARTBEATCLC") {
  field(CALC, "A>=2?0:1")
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEATECT.SEVR")
  field(ASG,  "READONLY")
}

record(bi, "$(CM)00:CRYOPLC_HEARTBEATSUM") {
  field(INP, "$(CM)00:CRYOPLC_HEARTBEATCLC PP")
  field(ZSV, "MAJOR")
  field(ZNAM,"Fault")
  field(ONAM,"Ok")
  field(FLNK, "$(CM)00:CRYOPLC_HEARTBEATSUM_CNTDC")
  field(ASG,  "READONLY")
}

record(calcout, "$(CM)00:CRYOPLC_HEARTBEATSUM_CNTDC") {
  field(DESC, "Diagnostic fault counter")
  field(CALC, "A")
  field(INPA, "$(CM)00:CRYOPLC_HEARTBEATSUM")
  field(INPB, "$(CM)00:CRYOPLC_HEARTBEATSUM_CNTD")
  field(OOPT, "When Zero")
  field(DOPT, "Use OCAL")
  field(OCAL, "B>2^16?0:B+1")
  field(OUT, "$(CM)00:CRYOPLC_HEARTBEATSUM_CNTD PP")
}

record(longin, "$(CM)00:CRYOPLC_HEARTBEATSUM_CNTD") {
  field(DESC, "Diagnostic fault count")
  field(VAL,  "0")
  field(PINI, "YES")
  info(autosaveFields,"VAL")
}

record(bo, "$(CM)00:CRYOPLC_HEARTBEATSUM_CNTDCLR") {
  field(DESC, "Clear fault count")
  field(OMSL, "supervisory")
  field(ZNAM, "Clear")
  field(ONAM, "Clear")
  field(OMSL, "closed_loop")
  field(DOL,  "0")
  field(OUT,  "$(CM)00:CRYOPLC_HEARTBEATSUM_CNTD PP")
}