# Per-device for PRC chassis # # Macros: # BASE - Our record prefix # CTRL - prefix used with feed_base.template # # JSON __metadata__ record(longin, "$(CHAS,undefined):SLOWABI") { field(DTYP, "FEED __metadata__") field(INP , "@name=$(NAME,undefined) reg=slow_abi_ver default=0") field(SCAN, "I/O Intr") # on connect } record(longin, "$(CHAS,undefined):TGENGRAN") { field(DESC, "TGEN granularity multiplier = 2^val") field(DTYP, "FEED __metadata__") field(INP , "@name=$(NAME,undefined) reg=tgen_granularity_log2 default=0") field(SCAN, "I/O Intr") # on connect } #================================== # On reconnect, set IF frequency #================================== record(longin, "$(CHAS,undefined):INIT1_") { field(DTYP, "FEED On Connect") field(INP , "@name=$(NAME,undefined)") field(SCAN, "I/O Intr") field(PHAS, "0") field(FLNK, "$(CHAS,undefined):INIT2_") } record(fanout, "$(CHAS,undefined):INIT2_") { field(LNK1, "$(CHAS,undefined):FREQ_SEL") field(LNK2, "$(CHAS,undefined):DF_FC_SRC") } # status monitoring # Read-only register clk_status_out: # 0: immediately after bitfile load, or after clock lost; needs setup # 1: transitional value during setup, system check in progress # 2: setup process completed successfully, data valid record(mbbi, "$(CHAS,undefined):CLK_STATUS") { field(DTYP, "FEED Register Read") field(INP , "@name=$(NAME,undefined) reg=clk_status_out") field(SCAN, "1 second") field(ZRVL, "0") field(ONVL, "1") field(TWVL, "2") field(ZRSV, "MAJOR") field(ONSV, "MAJOR") field(ZRST, "Invalid") field(ONST, "In Init") field(TWST, "Valid") field(TSE , "-2") field(FLNK, "$(CHAS,undefined):CLKCHK_") } # force driver into Error state, and disable polling, # when FPGA found in unconfigured state. record(calcout, "$(CHAS,undefined):CLKCHK_") { field(INPA, "$(CHAS,undefined):CLK_STATUS NPP MSI") field(IVOA, "Don't drive outputs") # INVALID == timeout, handled elsewhere field(CALC, "A") field(OOPT, "When Zero") field(OUT , "$(CHAS,undefined):CLKERR_.PROC PP") } record(stringout, "$(CHAS,undefined):CLKERR_") { field(DTYP, "FEED Force Error") field(OUT , "@name=$(NAME,undefined)") field(VAL , "Need Init") } record(calc, "$(CHAS,undefined):AGG_STS_") { field(INPA, "$(CHAS,undefined):CTRL_BASESTATUS_.SEVR CP MSS") field(INPB, "$(CHAS,undefined):CLK_STATUS.SEVR CP MSS") # CALC must do something with all inputs to run the MS logic # VAL is ignored field(CALC, "A+B") field(FLNK, "$(CHAS,undefined):STATUS") } record(stringin, "$(CHAS,undefined):STATUS") { field(INP , "$(CHAS,undefined):AGG_STS_.SEVR NPP MSS") } # TODO: consider alarms and initialization behavior record(mbbi, "$(CHAS,undefined):DF_FC_SRC_RBV") { field(DTYP, "FEED Register Read") field(SCAN, "1 second") field(INP , "@name=$(NAME,undefined) reg=cfreq_src_sel") field(TSE , "-2") field(ZRVL, "0") field(ZRST, "Loopback") field(ZRSV, "MAJOR") field(ONVL, "1") field(ONST, "Forward") field(ONSV, "MAJOR") field(TWVL, "2") field(TWST, "Reverse") field(TWSV, "MAJOR") field(THVL, "3") field(THST, "Cavity") info(feed:info:setting, "$(CHAS,undefined):DF_FC_SRC_RBV") } # LCLS-II: cryo interlock will rely on this, # must be set to Cavity record(mbbo, "$(CHAS,undefined):DF_FC_SRC") { field(DTYP, "FEED Register Write") field(OUT , "@name=$(NAME,undefined) reg=cfreq_src_sel") field(ZRVL, "0") field(ZRST, "Loopback") field(ONVL, "1") field(ONST, "Forward") field(TWVL, "2") field(TWST, "Reverse") field(THVL, "3") field(THST, "Cavity") field(VAL, "3") field(PINI, "YES") info(autosaveFields, "VAL") info(feed:info:setting, "$(CHAS,undefined):DF_FC_SRC") } record(mbbi, "$(CHAS,undefined):J18_RBV") { field(DTYP, "FEED Register Read") field(SCAN, "1 second") field(INP , "@name=$(NAME,undefined) reg=J18_debug") field(TSE , "-2") info(feed:info:setting, "$(CHAS,undefined):J18_RBV") } record(mbbo, "$(CHAS,undefined):FREQ_SEL") { field(DESC, "IF frequency FW selection") field(DTYP, "FEED Register Write") field(OMSL, "supervisory") field(ZRVL, "0") field(ZRST, "1.300e9 Hz") field(ONVL, "1") field(ONST, "3.900e9 Hz") field(VAL, "0") field(OUT , "@name=$(NAME,undefined) reg=if_out_sel wait=false") field(PINI, "YES") info(autosaveFields, "VAL") info(feed:info:setting, "$(CHAS,undefined):FREQ_SEL") } record(mbbi, "$(CHAS,undefined):FREQ_SEL_RBV") { field(DESC, "IF frequency FW selection") field(DTYP, "FEED Register Read") field(SCAN, "1 second") field(TSE , "-2") field(ZRVL, "0") field(ZRST, "1.300e9 Hz") field(ONVL, "1") field(ONST, "3.900e9 Hz") field(INP , "@name=$(NAME,undefined) reg=if_out_sel") info(feed:info:setting, "$(CHAS,undefined):FREQ_SEL_RBV") }