#================================== #---------------------------------- # intlkCountCmCommon.template: # # Interlock fault counters #---------------------------------- #================================== record(stringin,"$(CM,recursive)00:INTLK_CNTROT") { field(DTYP,"Soft Timestamp") field(INP,"@%H%M%S") field(SCAN,"5 second") field(FLNK,"$(CM,recursive)00:INTLK_CNTROC") } record(calcout,"$(CM,recursive)00:INTLK_CNTROC") { field(INPA,"$(CM,recursive)00:INTLK_CNTROT") field(CALC,"A>235950?1:0") field(OOPT,"Transition To Zero") field(OUT,"$(CM,recursive)00:INTLK_CNTRO1 PP") } record(fanout, "$(CM,recursive)00:INTLK_CNTRO1") { field(DESC, "Roll over interlock count") field(SELM, "All") field(LNK1, "$(CM,recursive)10:INTLK_CNTRO") field(LNK2, "$(CM,recursive)20:INTLK_CNTRO") field(LNK3, "$(CM,recursive)30:INTLK_CNTRO") field(LNK4, "$(CM,recursive)40:INTLK_CNTRO") field(LNK5, "$(CM,recursive)50:INTLK_CNTRO") field(LNK6, "$(CM,recursive)60:INTLK_CNTRO") field(FLNK, "$(CM,recursive)00:INTLK_CNTRO2") } record(fanout, "$(CM,recursive)00:INTLK_CNTRO2") { field(DESC, "Roll over interlock count") field(SELM, "All") field(LNK1, "$(CM,recursive)70:INTLK_CNTRO") field(LNK2, "$(CM,recursive)80:INTLK_CNTRO") field(LNK3, "$(CM,recursive)00:RESA:INTLK_CNTRO") field(LNK4, "$(CM,recursive)00:RESB:INTLK_CNTRO") } record(fanout, "$(CM,undefined)10:INTLK_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(LNK1, "$(CM,undefined)10:STEPTEMP_CNTRO") field(LNK2, "$(CM,undefined)10:CPLRTEMP1_CNTRO") field(LNK3, "$(CM,undefined)10:CPLRTEMP2_CNTRO") field(LNK4, "$(CM,undefined)10:QUENCH_CNTRO") }#================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)10:STEPTEMP_CNTC") { field(DESC, "STEPTEMP fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)10:STEPTEMP_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)10:STEPTEMP_CNTFO PP") } record(fanout, "$(CM,undefined)10:STEPTEMP_CNTFO") { field(DESC, "STEPTEMP fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)10:STEPTEMP_CNT") field(LNK2, "$(CM,undefined)10:STEPTEMP_CNTTC") field(LNK3, "$(CM,undefined)10:STEPTEMP_CNTUC") } record(calc, "$(CM,undefined)10:STEPTEMP_CNT") { field(DESC, "STEPTEMP total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:STEPTEMP_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)10:STEPTEMP_CNTTC") { field(DESC, "STEPTEMP today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:STEPTEMP_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)10:STEPTEMP_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)10:STEPTEMP_CNTT") { field(DESC, "STEPTEMP today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)10:STEPTEMP_CNTY") { field(DESC, "STEPTEMP yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)10:STEPTEMP_CNTUC") { field(DESC, "STEPTEMP user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:STEPTEMP_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)10:STEPTEMP_CNTU") } record(longin, "$(CM,undefined)10:STEPTEMP_CNTU") { field(DESC, "STEPTEMP user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)10:STEPTEMP_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)10:STEPTEMP_CNTU PP") } record(seq, "$(CM,undefined)10:STEPTEMP_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)10:STEPTEMP_CNTT") field(LNK1, "$(CM,undefined)10:STEPTEMP_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)10:STEPTEMP_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)10:CPLRTEMP1_CNTC") { field(DESC, "CPLRTEMP1 fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)10:CPLRTEMP1_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)10:CPLRTEMP1_CNTFO PP") } record(fanout, "$(CM,undefined)10:CPLRTEMP1_CNTFO") { field(DESC, "CPLRTEMP1 fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)10:CPLRTEMP1_CNT") field(LNK2, "$(CM,undefined)10:CPLRTEMP1_CNTTC") field(LNK3, "$(CM,undefined)10:CPLRTEMP1_CNTUC") } record(calc, "$(CM,undefined)10:CPLRTEMP1_CNT") { field(DESC, "CPLRTEMP1 total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:CPLRTEMP1_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)10:CPLRTEMP1_CNTTC") { field(DESC, "CPLRTEMP1 today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:CPLRTEMP1_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)10:CPLRTEMP1_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)10:CPLRTEMP1_CNTT") { field(DESC, "CPLRTEMP1 today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)10:CPLRTEMP1_CNTY") { field(DESC, "CPLRTEMP1 yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)10:CPLRTEMP1_CNTUC") { field(DESC, "CPLRTEMP1 user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:CPLRTEMP1_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)10:CPLRTEMP1_CNTU") } record(longin, "$(CM,undefined)10:CPLRTEMP1_CNTU") { field(DESC, "CPLRTEMP1 user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)10:CPLRTEMP1_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)10:CPLRTEMP1_CNTU PP") } record(seq, "$(CM,undefined)10:CPLRTEMP1_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)10:CPLRTEMP1_CNTT") field(LNK1, "$(CM,undefined)10:CPLRTEMP1_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)10:CPLRTEMP1_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)10:CPLRTEMP2_CNTC") { field(DESC, "CPLRTEMP2 fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)10:CPLRTEMP2_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)10:CPLRTEMP2_CNTFO PP") } record(fanout, "$(CM,undefined)10:CPLRTEMP2_CNTFO") { field(DESC, "CPLRTEMP2 fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)10:CPLRTEMP2_CNT") field(LNK2, "$(CM,undefined)10:CPLRTEMP2_CNTTC") field(LNK3, "$(CM,undefined)10:CPLRTEMP2_CNTUC") } record(calc, "$(CM,undefined)10:CPLRTEMP2_CNT") { field(DESC, "CPLRTEMP2 total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:CPLRTEMP2_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)10:CPLRTEMP2_CNTTC") { field(DESC, "CPLRTEMP2 today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:CPLRTEMP2_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)10:CPLRTEMP2_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)10:CPLRTEMP2_CNTT") { field(DESC, "CPLRTEMP2 today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)10:CPLRTEMP2_CNTY") { field(DESC, "CPLRTEMP2 yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)10:CPLRTEMP2_CNTUC") { field(DESC, "CPLRTEMP2 user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:CPLRTEMP2_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)10:CPLRTEMP2_CNTU") } record(longin, "$(CM,undefined)10:CPLRTEMP2_CNTU") { field(DESC, "CPLRTEMP2 user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)10:CPLRTEMP2_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)10:CPLRTEMP2_CNTU PP") } record(seq, "$(CM,undefined)10:CPLRTEMP2_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)10:CPLRTEMP2_CNTT") field(LNK1, "$(CM,undefined)10:CPLRTEMP2_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)10:CPLRTEMP2_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)10:QUENCH_CNTC") { field(DESC, "QUENCH fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)10:QUENCH_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)10:QUENCH_CNTFO PP") } record(fanout, "$(CM,undefined)10:QUENCH_CNTFO") { field(DESC, "QUENCH fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)10:QUENCH_CNT") field(LNK2, "$(CM,undefined)10:QUENCH_CNTTC") field(LNK3, "$(CM,undefined)10:QUENCH_CNTUC") } record(calc, "$(CM,undefined)10:QUENCH_CNT") { field(DESC, "QUENCH total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:QUENCH_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)10:QUENCH_CNTTC") { field(DESC, "QUENCH today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:QUENCH_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)10:QUENCH_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)10:QUENCH_CNTT") { field(DESC, "QUENCH today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)10:QUENCH_CNTY") { field(DESC, "QUENCH yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)10:QUENCH_CNTUC") { field(DESC, "QUENCH user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:QUENCH_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)10:QUENCH_CNTU") } record(longin, "$(CM,undefined)10:QUENCH_CNTU") { field(DESC, "QUENCH user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)10:QUENCH_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)10:QUENCH_CNTU PP") } record(seq, "$(CM,undefined)10:QUENCH_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)10:QUENCH_CNTT") field(LNK1, "$(CM,undefined)10:QUENCH_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)10:QUENCH_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)10:RESINTLK_CNTC") { field(DESC, "RESINTLK fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)10:RESINTLK_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)10:RESINTLK_CNTFO PP") } record(fanout, "$(CM,undefined)10:RESINTLK_CNTFO") { field(DESC, "RESINTLK fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)10:RESINTLK_CNT") field(LNK2, "$(CM,undefined)10:RESINTLK_CNTTC") field(LNK3, "$(CM,undefined)10:RESINTLK_CNTUC") } record(calc, "$(CM,undefined)10:RESINTLK_CNT") { field(DESC, "RESINTLK total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:RESINTLK_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)10:RESINTLK_CNTTC") { field(DESC, "RESINTLK today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:RESINTLK_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)10:RESINTLK_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)10:RESINTLK_CNTT") { field(DESC, "RESINTLK today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)10:RESINTLK_CNTY") { field(DESC, "RESINTLK yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)10:RESINTLK_CNTUC") { field(DESC, "RESINTLK user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:RESINTLK_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)10:RESINTLK_CNTU") } record(longin, "$(CM,undefined)10:RESINTLK_CNTU") { field(DESC, "RESINTLK user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)10:RESINTLK_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)10:RESINTLK_CNTU PP") } record(seq, "$(CM,undefined)10:RESINTLK_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)10:RESINTLK_CNTT") field(LNK1, "$(CM,undefined)10:RESINTLK_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)10:RESINTLK_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)10:RESLINK_CNTC") { field(DESC, "RESLINK fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)10:RESLINK_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)10:RESLINK_CNTFO PP") } record(fanout, "$(CM,undefined)10:RESLINK_CNTFO") { field(DESC, "RESLINK fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)10:RESLINK_CNT") field(LNK2, "$(CM,undefined)10:RESLINK_CNTTC") field(LNK3, "$(CM,undefined)10:RESLINK_CNTUC") } record(calc, "$(CM,undefined)10:RESLINK_CNT") { field(DESC, "RESLINK total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:RESLINK_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)10:RESLINK_CNTTC") { field(DESC, "RESLINK today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:RESLINK_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)10:RESLINK_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)10:RESLINK_CNTT") { field(DESC, "RESLINK today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)10:RESLINK_CNTY") { field(DESC, "RESLINK yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)10:RESLINK_CNTUC") { field(DESC, "RESLINK user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:RESLINK_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)10:RESLINK_CNTU") } record(longin, "$(CM,undefined)10:RESLINK_CNTU") { field(DESC, "RESLINK user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)10:RESLINK_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)10:RESLINK_CNTU PP") } record(seq, "$(CM,undefined)10:RESLINK_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)10:RESLINK_CNTT") field(LNK1, "$(CM,undefined)10:RESLINK_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)10:RESLINK_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)10:PLL_CNTC") { field(DESC, "PLL fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)10:PLL_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)10:PLL_CNTFO PP") } record(fanout, "$(CM,undefined)10:PLL_CNTFO") { field(DESC, "PLL fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)10:PLL_CNT") field(LNK2, "$(CM,undefined)10:PLL_CNTTC") field(LNK3, "$(CM,undefined)10:PLL_CNTUC") } record(calc, "$(CM,undefined)10:PLL_CNT") { field(DESC, "PLL total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:PLL_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)10:PLL_CNTTC") { field(DESC, "PLL today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:PLL_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)10:PLL_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)10:PLL_CNTT") { field(DESC, "PLL today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)10:PLL_CNTY") { field(DESC, "PLL yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)10:PLL_CNTUC") { field(DESC, "PLL user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:PLL_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)10:PLL_CNTU") } record(longin, "$(CM,undefined)10:PLL_CNTU") { field(DESC, "PLL user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)10:PLL_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)10:PLL_CNTU PP") } record(seq, "$(CM,undefined)10:PLL_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)10:PLL_CNTT") field(LNK1, "$(CM,undefined)10:PLL_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)10:PLL_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)10:IOCWDOG_CNTC") { field(DESC, "IOCWDOG fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)10:IOCWDOG_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)10:IOCWDOG_CNTFO PP") } record(fanout, "$(CM,undefined)10:IOCWDOG_CNTFO") { field(DESC, "IOCWDOG fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)10:IOCWDOG_CNT") field(LNK2, "$(CM,undefined)10:IOCWDOG_CNTTC") field(LNK3, "$(CM,undefined)10:IOCWDOG_CNTUC") } record(calc, "$(CM,undefined)10:IOCWDOG_CNT") { field(DESC, "IOCWDOG total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:IOCWDOG_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)10:IOCWDOG_CNTTC") { field(DESC, "IOCWDOG today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:IOCWDOG_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)10:IOCWDOG_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)10:IOCWDOG_CNTT") { field(DESC, "IOCWDOG today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)10:IOCWDOG_CNTY") { field(DESC, "IOCWDOG yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)10:IOCWDOG_CNTUC") { field(DESC, "IOCWDOG user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:IOCWDOG_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)10:IOCWDOG_CNTU") } record(longin, "$(CM,undefined)10:IOCWDOG_CNTU") { field(DESC, "IOCWDOG user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)10:IOCWDOG_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)10:IOCWDOG_CNTU PP") } record(seq, "$(CM,undefined)10:IOCWDOG_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)10:IOCWDOG_CNTT") field(LNK1, "$(CM,undefined)10:IOCWDOG_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)10:IOCWDOG_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)10:SSA_CNTC") { field(DESC, "SSA fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)10:SSA_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)10:SSA_CNTFO PP") } record(fanout, "$(CM,undefined)10:SSA_CNTFO") { field(DESC, "SSA fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)10:SSA_CNT") field(LNK2, "$(CM,undefined)10:SSA_CNTTC") field(LNK3, "$(CM,undefined)10:SSA_CNTUC") } record(calc, "$(CM,undefined)10:SSA_CNT") { field(DESC, "SSA total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:SSA_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)10:SSA_CNTTC") { field(DESC, "SSA today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:SSA_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)10:SSA_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)10:SSA_CNTT") { field(DESC, "SSA today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)10:SSA_CNTY") { field(DESC, "SSA yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)10:SSA_CNTUC") { field(DESC, "SSA user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:SSA_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)10:SSA_CNTU") } record(longin, "$(CM,undefined)10:SSA_CNTU") { field(DESC, "SSA user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)10:SSA_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)10:SSA_CNTU PP") } record(seq, "$(CM,undefined)10:SSA_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)10:SSA_CNTT") field(LNK1, "$(CM,undefined)10:SSA_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)10:SSA_CNTT PP") } record(fanout, "$(CM,undefined)20:INTLK_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(LNK1, "$(CM,undefined)20:STEPTEMP_CNTRO") field(LNK2, "$(CM,undefined)20:CPLRTEMP1_CNTRO") field(LNK3, "$(CM,undefined)20:CPLRTEMP2_CNTRO") field(LNK4, "$(CM,undefined)20:QUENCH_CNTRO") }#================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)20:STEPTEMP_CNTC") { field(DESC, "STEPTEMP fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)20:STEPTEMP_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)20:STEPTEMP_CNTFO PP") } record(fanout, "$(CM,undefined)20:STEPTEMP_CNTFO") { field(DESC, "STEPTEMP fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)20:STEPTEMP_CNT") field(LNK2, "$(CM,undefined)20:STEPTEMP_CNTTC") field(LNK3, "$(CM,undefined)20:STEPTEMP_CNTUC") } record(calc, "$(CM,undefined)20:STEPTEMP_CNT") { field(DESC, "STEPTEMP total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)20:STEPTEMP_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)20:STEPTEMP_CNTTC") { field(DESC, "STEPTEMP today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)20:STEPTEMP_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)20:STEPTEMP_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)20:STEPTEMP_CNTT") { field(DESC, "STEPTEMP today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)20:STEPTEMP_CNTY") { field(DESC, "STEPTEMP yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)20:STEPTEMP_CNTUC") { field(DESC, "STEPTEMP user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)20:STEPTEMP_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)20:STEPTEMP_CNTU") } record(longin, "$(CM,undefined)20:STEPTEMP_CNTU") { field(DESC, "STEPTEMP user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)20:STEPTEMP_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)20:STEPTEMP_CNTU PP") } record(seq, "$(CM,undefined)20:STEPTEMP_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)20:STEPTEMP_CNTT") field(LNK1, "$(CM,undefined)20:STEPTEMP_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)20:STEPTEMP_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)20:CPLRTEMP1_CNTC") { field(DESC, "CPLRTEMP1 fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)20:CPLRTEMP1_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)20:CPLRTEMP1_CNTFO PP") } record(fanout, "$(CM,undefined)20:CPLRTEMP1_CNTFO") { field(DESC, "CPLRTEMP1 fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)20:CPLRTEMP1_CNT") field(LNK2, "$(CM,undefined)20:CPLRTEMP1_CNTTC") field(LNK3, "$(CM,undefined)20:CPLRTEMP1_CNTUC") } record(calc, "$(CM,undefined)20:CPLRTEMP1_CNT") { field(DESC, "CPLRTEMP1 total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)20:CPLRTEMP1_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)20:CPLRTEMP1_CNTTC") { field(DESC, "CPLRTEMP1 today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)20:CPLRTEMP1_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)20:CPLRTEMP1_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)20:CPLRTEMP1_CNTT") { field(DESC, "CPLRTEMP1 today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)20:CPLRTEMP1_CNTY") { field(DESC, "CPLRTEMP1 yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)20:CPLRTEMP1_CNTUC") { field(DESC, "CPLRTEMP1 user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)20:CPLRTEMP1_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)20:CPLRTEMP1_CNTU") } record(longin, "$(CM,undefined)20:CPLRTEMP1_CNTU") { field(DESC, "CPLRTEMP1 user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)20:CPLRTEMP1_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)20:CPLRTEMP1_CNTU PP") } record(seq, "$(CM,undefined)20:CPLRTEMP1_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)20:CPLRTEMP1_CNTT") field(LNK1, "$(CM,undefined)20:CPLRTEMP1_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)20:CPLRTEMP1_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)20:CPLRTEMP2_CNTC") { field(DESC, "CPLRTEMP2 fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)20:CPLRTEMP2_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)20:CPLRTEMP2_CNTFO PP") } record(fanout, "$(CM,undefined)20:CPLRTEMP2_CNTFO") { field(DESC, "CPLRTEMP2 fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)20:CPLRTEMP2_CNT") field(LNK2, "$(CM,undefined)20:CPLRTEMP2_CNTTC") field(LNK3, "$(CM,undefined)20:CPLRTEMP2_CNTUC") } record(calc, "$(CM,undefined)20:CPLRTEMP2_CNT") { field(DESC, "CPLRTEMP2 total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)20:CPLRTEMP2_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)20:CPLRTEMP2_CNTTC") { field(DESC, "CPLRTEMP2 today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)20:CPLRTEMP2_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)20:CPLRTEMP2_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)20:CPLRTEMP2_CNTT") { field(DESC, "CPLRTEMP2 today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)20:CPLRTEMP2_CNTY") { field(DESC, "CPLRTEMP2 yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)20:CPLRTEMP2_CNTUC") { field(DESC, "CPLRTEMP2 user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)20:CPLRTEMP2_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)20:CPLRTEMP2_CNTU") } record(longin, "$(CM,undefined)20:CPLRTEMP2_CNTU") { field(DESC, "CPLRTEMP2 user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)20:CPLRTEMP2_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)20:CPLRTEMP2_CNTU PP") } record(seq, "$(CM,undefined)20:CPLRTEMP2_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)20:CPLRTEMP2_CNTT") field(LNK1, "$(CM,undefined)20:CPLRTEMP2_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)20:CPLRTEMP2_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)20:QUENCH_CNTC") { field(DESC, "QUENCH fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)20:QUENCH_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)20:QUENCH_CNTFO PP") } record(fanout, "$(CM,undefined)20:QUENCH_CNTFO") { field(DESC, "QUENCH fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)20:QUENCH_CNT") field(LNK2, "$(CM,undefined)20:QUENCH_CNTTC") field(LNK3, "$(CM,undefined)20:QUENCH_CNTUC") } record(calc, "$(CM,undefined)20:QUENCH_CNT") { field(DESC, "QUENCH total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)20:QUENCH_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)20:QUENCH_CNTTC") { field(DESC, "QUENCH today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)20:QUENCH_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)20:QUENCH_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)20:QUENCH_CNTT") { field(DESC, "QUENCH today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)20:QUENCH_CNTY") { field(DESC, "QUENCH yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)20:QUENCH_CNTUC") { field(DESC, "QUENCH user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)20:QUENCH_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)20:QUENCH_CNTU") } record(longin, "$(CM,undefined)20:QUENCH_CNTU") { field(DESC, "QUENCH user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)20:QUENCH_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)20:QUENCH_CNTU PP") } record(seq, "$(CM,undefined)20:QUENCH_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)20:QUENCH_CNTT") field(LNK1, "$(CM,undefined)20:QUENCH_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)20:QUENCH_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)20:RESINTLK_CNTC") { field(DESC, "RESINTLK fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)20:RESINTLK_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)20:RESINTLK_CNTFO PP") } record(fanout, "$(CM,undefined)20:RESINTLK_CNTFO") { field(DESC, "RESINTLK fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)20:RESINTLK_CNT") field(LNK2, "$(CM,undefined)20:RESINTLK_CNTTC") field(LNK3, "$(CM,undefined)20:RESINTLK_CNTUC") } record(calc, "$(CM,undefined)20:RESINTLK_CNT") { field(DESC, "RESINTLK total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)20:RESINTLK_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)20:RESINTLK_CNTTC") { field(DESC, "RESINTLK today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)20:RESINTLK_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)20:RESINTLK_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)20:RESINTLK_CNTT") { field(DESC, "RESINTLK today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)20:RESINTLK_CNTY") { field(DESC, "RESINTLK yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)20:RESINTLK_CNTUC") { field(DESC, "RESINTLK user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)20:RESINTLK_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)20:RESINTLK_CNTU") } record(longin, "$(CM,undefined)20:RESINTLK_CNTU") { field(DESC, "RESINTLK user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)20:RESINTLK_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)20:RESINTLK_CNTU PP") } record(seq, "$(CM,undefined)20:RESINTLK_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)20:RESINTLK_CNTT") field(LNK1, "$(CM,undefined)20:RESINTLK_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)20:RESINTLK_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)20:RESLINK_CNTC") { field(DESC, "RESLINK fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)20:RESLINK_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)20:RESLINK_CNTFO PP") } record(fanout, "$(CM,undefined)20:RESLINK_CNTFO") { field(DESC, "RESLINK fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)20:RESLINK_CNT") field(LNK2, "$(CM,undefined)20:RESLINK_CNTTC") field(LNK3, "$(CM,undefined)20:RESLINK_CNTUC") } record(calc, "$(CM,undefined)20:RESLINK_CNT") { field(DESC, "RESLINK total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)20:RESLINK_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)20:RESLINK_CNTTC") { field(DESC, "RESLINK today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)20:RESLINK_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)20:RESLINK_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)20:RESLINK_CNTT") { field(DESC, "RESLINK today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)20:RESLINK_CNTY") { field(DESC, "RESLINK yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)20:RESLINK_CNTUC") { field(DESC, "RESLINK user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)20:RESLINK_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)20:RESLINK_CNTU") } record(longin, "$(CM,undefined)20:RESLINK_CNTU") { field(DESC, "RESLINK user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)20:RESLINK_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)20:RESLINK_CNTU PP") } record(seq, "$(CM,undefined)20:RESLINK_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)20:RESLINK_CNTT") field(LNK1, "$(CM,undefined)20:RESLINK_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)20:RESLINK_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)20:PLL_CNTC") { field(DESC, "PLL fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)20:PLL_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)20:PLL_CNTFO PP") } record(fanout, "$(CM,undefined)20:PLL_CNTFO") { field(DESC, "PLL fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)20:PLL_CNT") field(LNK2, "$(CM,undefined)20:PLL_CNTTC") field(LNK3, "$(CM,undefined)20:PLL_CNTUC") } record(calc, "$(CM,undefined)20:PLL_CNT") { field(DESC, "PLL total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)20:PLL_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)20:PLL_CNTTC") { field(DESC, "PLL today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)20:PLL_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)20:PLL_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)20:PLL_CNTT") { field(DESC, "PLL today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)20:PLL_CNTY") { field(DESC, "PLL yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)20:PLL_CNTUC") { field(DESC, "PLL user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)20:PLL_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)20:PLL_CNTU") } record(longin, "$(CM,undefined)20:PLL_CNTU") { field(DESC, "PLL user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)20:PLL_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)20:PLL_CNTU PP") } record(seq, "$(CM,undefined)20:PLL_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)20:PLL_CNTT") field(LNK1, "$(CM,undefined)20:PLL_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)20:PLL_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)20:IOCWDOG_CNTC") { field(DESC, "IOCWDOG fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)20:IOCWDOG_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)20:IOCWDOG_CNTFO PP") } record(fanout, "$(CM,undefined)20:IOCWDOG_CNTFO") { field(DESC, "IOCWDOG fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)20:IOCWDOG_CNT") field(LNK2, "$(CM,undefined)20:IOCWDOG_CNTTC") field(LNK3, "$(CM,undefined)20:IOCWDOG_CNTUC") } record(calc, "$(CM,undefined)20:IOCWDOG_CNT") { field(DESC, "IOCWDOG total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)20:IOCWDOG_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)20:IOCWDOG_CNTTC") { field(DESC, "IOCWDOG today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)20:IOCWDOG_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)20:IOCWDOG_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)20:IOCWDOG_CNTT") { field(DESC, "IOCWDOG today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)20:IOCWDOG_CNTY") { field(DESC, "IOCWDOG yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)20:IOCWDOG_CNTUC") { field(DESC, "IOCWDOG user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)20:IOCWDOG_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)20:IOCWDOG_CNTU") } record(longin, "$(CM,undefined)20:IOCWDOG_CNTU") { field(DESC, "IOCWDOG user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)20:IOCWDOG_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)20:IOCWDOG_CNTU PP") } record(seq, "$(CM,undefined)20:IOCWDOG_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)20:IOCWDOG_CNTT") field(LNK1, "$(CM,undefined)20:IOCWDOG_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)20:IOCWDOG_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)20:SSA_CNTC") { field(DESC, "SSA fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)20:SSA_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)20:SSA_CNTFO PP") } record(fanout, "$(CM,undefined)20:SSA_CNTFO") { field(DESC, "SSA fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)20:SSA_CNT") field(LNK2, "$(CM,undefined)20:SSA_CNTTC") field(LNK3, "$(CM,undefined)20:SSA_CNTUC") } record(calc, "$(CM,undefined)20:SSA_CNT") { field(DESC, "SSA total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)20:SSA_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)20:SSA_CNTTC") { field(DESC, "SSA today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)20:SSA_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)20:SSA_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)20:SSA_CNTT") { field(DESC, "SSA today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)20:SSA_CNTY") { field(DESC, "SSA yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)20:SSA_CNTUC") { field(DESC, "SSA user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)20:SSA_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)20:SSA_CNTU") } record(longin, "$(CM,undefined)20:SSA_CNTU") { field(DESC, "SSA user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)20:SSA_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)20:SSA_CNTU PP") } record(seq, "$(CM,undefined)20:SSA_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)20:SSA_CNTT") field(LNK1, "$(CM,undefined)20:SSA_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)20:SSA_CNTT PP") } record(fanout, "$(CM,undefined)30:INTLK_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(LNK1, "$(CM,undefined)30:STEPTEMP_CNTRO") field(LNK2, "$(CM,undefined)30:CPLRTEMP1_CNTRO") field(LNK3, "$(CM,undefined)30:CPLRTEMP2_CNTRO") field(LNK4, "$(CM,undefined)30:QUENCH_CNTRO") }#================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)30:STEPTEMP_CNTC") { field(DESC, "STEPTEMP fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)30:STEPTEMP_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)30:STEPTEMP_CNTFO PP") } record(fanout, "$(CM,undefined)30:STEPTEMP_CNTFO") { field(DESC, "STEPTEMP fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)30:STEPTEMP_CNT") field(LNK2, "$(CM,undefined)30:STEPTEMP_CNTTC") field(LNK3, "$(CM,undefined)30:STEPTEMP_CNTUC") } record(calc, "$(CM,undefined)30:STEPTEMP_CNT") { field(DESC, "STEPTEMP total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)30:STEPTEMP_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)30:STEPTEMP_CNTTC") { field(DESC, "STEPTEMP today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)30:STEPTEMP_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)30:STEPTEMP_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)30:STEPTEMP_CNTT") { field(DESC, "STEPTEMP today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)30:STEPTEMP_CNTY") { field(DESC, "STEPTEMP yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)30:STEPTEMP_CNTUC") { field(DESC, "STEPTEMP user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)30:STEPTEMP_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)30:STEPTEMP_CNTU") } record(longin, "$(CM,undefined)30:STEPTEMP_CNTU") { field(DESC, "STEPTEMP user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)30:STEPTEMP_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)30:STEPTEMP_CNTU PP") } record(seq, "$(CM,undefined)30:STEPTEMP_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)30:STEPTEMP_CNTT") field(LNK1, "$(CM,undefined)30:STEPTEMP_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)30:STEPTEMP_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)30:CPLRTEMP1_CNTC") { field(DESC, "CPLRTEMP1 fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)30:CPLRTEMP1_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)30:CPLRTEMP1_CNTFO PP") } record(fanout, "$(CM,undefined)30:CPLRTEMP1_CNTFO") { field(DESC, "CPLRTEMP1 fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)30:CPLRTEMP1_CNT") field(LNK2, "$(CM,undefined)30:CPLRTEMP1_CNTTC") field(LNK3, "$(CM,undefined)30:CPLRTEMP1_CNTUC") } record(calc, "$(CM,undefined)30:CPLRTEMP1_CNT") { field(DESC, "CPLRTEMP1 total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)30:CPLRTEMP1_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)30:CPLRTEMP1_CNTTC") { field(DESC, "CPLRTEMP1 today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)30:CPLRTEMP1_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)30:CPLRTEMP1_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)30:CPLRTEMP1_CNTT") { field(DESC, "CPLRTEMP1 today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)30:CPLRTEMP1_CNTY") { field(DESC, "CPLRTEMP1 yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)30:CPLRTEMP1_CNTUC") { field(DESC, "CPLRTEMP1 user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)30:CPLRTEMP1_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)30:CPLRTEMP1_CNTU") } record(longin, "$(CM,undefined)30:CPLRTEMP1_CNTU") { field(DESC, "CPLRTEMP1 user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)30:CPLRTEMP1_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)30:CPLRTEMP1_CNTU PP") } record(seq, "$(CM,undefined)30:CPLRTEMP1_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)30:CPLRTEMP1_CNTT") field(LNK1, "$(CM,undefined)30:CPLRTEMP1_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)30:CPLRTEMP1_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)30:CPLRTEMP2_CNTC") { field(DESC, "CPLRTEMP2 fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)30:CPLRTEMP2_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)30:CPLRTEMP2_CNTFO PP") } record(fanout, "$(CM,undefined)30:CPLRTEMP2_CNTFO") { field(DESC, "CPLRTEMP2 fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)30:CPLRTEMP2_CNT") field(LNK2, "$(CM,undefined)30:CPLRTEMP2_CNTTC") field(LNK3, "$(CM,undefined)30:CPLRTEMP2_CNTUC") } record(calc, "$(CM,undefined)30:CPLRTEMP2_CNT") { field(DESC, "CPLRTEMP2 total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)30:CPLRTEMP2_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)30:CPLRTEMP2_CNTTC") { field(DESC, "CPLRTEMP2 today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)30:CPLRTEMP2_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)30:CPLRTEMP2_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)30:CPLRTEMP2_CNTT") { field(DESC, "CPLRTEMP2 today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)30:CPLRTEMP2_CNTY") { field(DESC, "CPLRTEMP2 yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)30:CPLRTEMP2_CNTUC") { field(DESC, "CPLRTEMP2 user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)30:CPLRTEMP2_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)30:CPLRTEMP2_CNTU") } record(longin, "$(CM,undefined)30:CPLRTEMP2_CNTU") { field(DESC, "CPLRTEMP2 user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)30:CPLRTEMP2_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)30:CPLRTEMP2_CNTU PP") } record(seq, "$(CM,undefined)30:CPLRTEMP2_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)30:CPLRTEMP2_CNTT") field(LNK1, "$(CM,undefined)30:CPLRTEMP2_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)30:CPLRTEMP2_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)30:QUENCH_CNTC") { field(DESC, "QUENCH fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)30:QUENCH_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)30:QUENCH_CNTFO PP") } record(fanout, "$(CM,undefined)30:QUENCH_CNTFO") { field(DESC, "QUENCH fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)30:QUENCH_CNT") field(LNK2, "$(CM,undefined)30:QUENCH_CNTTC") field(LNK3, "$(CM,undefined)30:QUENCH_CNTUC") } record(calc, "$(CM,undefined)30:QUENCH_CNT") { field(DESC, "QUENCH total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)30:QUENCH_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)30:QUENCH_CNTTC") { field(DESC, "QUENCH today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)30:QUENCH_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)30:QUENCH_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)30:QUENCH_CNTT") { field(DESC, "QUENCH today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)30:QUENCH_CNTY") { field(DESC, "QUENCH yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)30:QUENCH_CNTUC") { field(DESC, "QUENCH user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)30:QUENCH_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)30:QUENCH_CNTU") } record(longin, "$(CM,undefined)30:QUENCH_CNTU") { field(DESC, "QUENCH user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)30:QUENCH_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)30:QUENCH_CNTU PP") } record(seq, "$(CM,undefined)30:QUENCH_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)30:QUENCH_CNTT") field(LNK1, "$(CM,undefined)30:QUENCH_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)30:QUENCH_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)30:RESINTLK_CNTC") { field(DESC, "RESINTLK fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)30:RESINTLK_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)30:RESINTLK_CNTFO PP") } record(fanout, "$(CM,undefined)30:RESINTLK_CNTFO") { field(DESC, "RESINTLK fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)30:RESINTLK_CNT") field(LNK2, "$(CM,undefined)30:RESINTLK_CNTTC") field(LNK3, "$(CM,undefined)30:RESINTLK_CNTUC") } record(calc, "$(CM,undefined)30:RESINTLK_CNT") { field(DESC, "RESINTLK total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)30:RESINTLK_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)30:RESINTLK_CNTTC") { field(DESC, "RESINTLK today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)30:RESINTLK_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)30:RESINTLK_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)30:RESINTLK_CNTT") { field(DESC, "RESINTLK today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)30:RESINTLK_CNTY") { field(DESC, "RESINTLK yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)30:RESINTLK_CNTUC") { field(DESC, "RESINTLK user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)30:RESINTLK_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)30:RESINTLK_CNTU") } record(longin, "$(CM,undefined)30:RESINTLK_CNTU") { field(DESC, "RESINTLK user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)30:RESINTLK_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)30:RESINTLK_CNTU PP") } record(seq, "$(CM,undefined)30:RESINTLK_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)30:RESINTLK_CNTT") field(LNK1, "$(CM,undefined)30:RESINTLK_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)30:RESINTLK_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)30:RESLINK_CNTC") { field(DESC, "RESLINK fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)30:RESLINK_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)30:RESLINK_CNTFO PP") } record(fanout, "$(CM,undefined)30:RESLINK_CNTFO") { field(DESC, "RESLINK fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)30:RESLINK_CNT") field(LNK2, "$(CM,undefined)30:RESLINK_CNTTC") field(LNK3, "$(CM,undefined)30:RESLINK_CNTUC") } record(calc, "$(CM,undefined)30:RESLINK_CNT") { field(DESC, "RESLINK total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)30:RESLINK_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)30:RESLINK_CNTTC") { field(DESC, "RESLINK today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)30:RESLINK_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)30:RESLINK_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)30:RESLINK_CNTT") { field(DESC, "RESLINK today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)30:RESLINK_CNTY") { field(DESC, "RESLINK yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)30:RESLINK_CNTUC") { field(DESC, "RESLINK user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)30:RESLINK_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)30:RESLINK_CNTU") } record(longin, "$(CM,undefined)30:RESLINK_CNTU") { field(DESC, "RESLINK user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)30:RESLINK_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)30:RESLINK_CNTU PP") } record(seq, "$(CM,undefined)30:RESLINK_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)30:RESLINK_CNTT") field(LNK1, "$(CM,undefined)30:RESLINK_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)30:RESLINK_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)30:PLL_CNTC") { field(DESC, "PLL fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)30:PLL_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)30:PLL_CNTFO PP") } record(fanout, "$(CM,undefined)30:PLL_CNTFO") { field(DESC, "PLL fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)30:PLL_CNT") field(LNK2, "$(CM,undefined)30:PLL_CNTTC") field(LNK3, "$(CM,undefined)30:PLL_CNTUC") } record(calc, "$(CM,undefined)30:PLL_CNT") { field(DESC, "PLL total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)30:PLL_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)30:PLL_CNTTC") { field(DESC, "PLL today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)30:PLL_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)30:PLL_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)30:PLL_CNTT") { field(DESC, "PLL today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)30:PLL_CNTY") { field(DESC, "PLL yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)30:PLL_CNTUC") { field(DESC, "PLL user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)30:PLL_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)30:PLL_CNTU") } record(longin, "$(CM,undefined)30:PLL_CNTU") { field(DESC, "PLL user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)30:PLL_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)30:PLL_CNTU PP") } record(seq, "$(CM,undefined)30:PLL_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)30:PLL_CNTT") field(LNK1, "$(CM,undefined)30:PLL_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)30:PLL_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)30:IOCWDOG_CNTC") { field(DESC, "IOCWDOG fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)30:IOCWDOG_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)30:IOCWDOG_CNTFO PP") } record(fanout, "$(CM,undefined)30:IOCWDOG_CNTFO") { field(DESC, "IOCWDOG fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)30:IOCWDOG_CNT") field(LNK2, "$(CM,undefined)30:IOCWDOG_CNTTC") field(LNK3, "$(CM,undefined)30:IOCWDOG_CNTUC") } record(calc, "$(CM,undefined)30:IOCWDOG_CNT") { field(DESC, "IOCWDOG total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)30:IOCWDOG_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)30:IOCWDOG_CNTTC") { field(DESC, "IOCWDOG today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)30:IOCWDOG_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)30:IOCWDOG_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)30:IOCWDOG_CNTT") { field(DESC, "IOCWDOG today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)30:IOCWDOG_CNTY") { field(DESC, "IOCWDOG yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)30:IOCWDOG_CNTUC") { field(DESC, "IOCWDOG user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)30:IOCWDOG_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)30:IOCWDOG_CNTU") } record(longin, "$(CM,undefined)30:IOCWDOG_CNTU") { field(DESC, "IOCWDOG user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)30:IOCWDOG_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)30:IOCWDOG_CNTU PP") } record(seq, "$(CM,undefined)30:IOCWDOG_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)30:IOCWDOG_CNTT") field(LNK1, "$(CM,undefined)30:IOCWDOG_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)30:IOCWDOG_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)30:SSA_CNTC") { field(DESC, "SSA fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)30:SSA_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)30:SSA_CNTFO PP") } record(fanout, "$(CM,undefined)30:SSA_CNTFO") { field(DESC, "SSA fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)30:SSA_CNT") field(LNK2, "$(CM,undefined)30:SSA_CNTTC") field(LNK3, "$(CM,undefined)30:SSA_CNTUC") } record(calc, "$(CM,undefined)30:SSA_CNT") { field(DESC, "SSA total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)30:SSA_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)30:SSA_CNTTC") { field(DESC, "SSA today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)30:SSA_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)30:SSA_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)30:SSA_CNTT") { field(DESC, "SSA today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)30:SSA_CNTY") { field(DESC, "SSA yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)30:SSA_CNTUC") { field(DESC, "SSA user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)30:SSA_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)30:SSA_CNTU") } record(longin, "$(CM,undefined)30:SSA_CNTU") { field(DESC, "SSA user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)30:SSA_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)30:SSA_CNTU PP") } record(seq, "$(CM,undefined)30:SSA_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)30:SSA_CNTT") field(LNK1, "$(CM,undefined)30:SSA_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)30:SSA_CNTT PP") } record(fanout, "$(CM,undefined)40:INTLK_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(LNK1, "$(CM,undefined)40:STEPTEMP_CNTRO") field(LNK2, "$(CM,undefined)40:CPLRTEMP1_CNTRO") field(LNK3, "$(CM,undefined)40:CPLRTEMP2_CNTRO") field(LNK4, "$(CM,undefined)40:QUENCH_CNTRO") }#================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)40:STEPTEMP_CNTC") { field(DESC, "STEPTEMP fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)40:STEPTEMP_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)40:STEPTEMP_CNTFO PP") } record(fanout, "$(CM,undefined)40:STEPTEMP_CNTFO") { field(DESC, "STEPTEMP fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)40:STEPTEMP_CNT") field(LNK2, "$(CM,undefined)40:STEPTEMP_CNTTC") field(LNK3, "$(CM,undefined)40:STEPTEMP_CNTUC") } record(calc, "$(CM,undefined)40:STEPTEMP_CNT") { field(DESC, "STEPTEMP total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)40:STEPTEMP_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)40:STEPTEMP_CNTTC") { field(DESC, "STEPTEMP today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)40:STEPTEMP_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)40:STEPTEMP_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)40:STEPTEMP_CNTT") { field(DESC, "STEPTEMP today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)40:STEPTEMP_CNTY") { field(DESC, "STEPTEMP yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)40:STEPTEMP_CNTUC") { field(DESC, "STEPTEMP user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)40:STEPTEMP_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)40:STEPTEMP_CNTU") } record(longin, "$(CM,undefined)40:STEPTEMP_CNTU") { field(DESC, "STEPTEMP user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)40:STEPTEMP_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)40:STEPTEMP_CNTU PP") } record(seq, "$(CM,undefined)40:STEPTEMP_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)40:STEPTEMP_CNTT") field(LNK1, "$(CM,undefined)40:STEPTEMP_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)40:STEPTEMP_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)40:CPLRTEMP1_CNTC") { field(DESC, "CPLRTEMP1 fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)40:CPLRTEMP1_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)40:CPLRTEMP1_CNTFO PP") } record(fanout, "$(CM,undefined)40:CPLRTEMP1_CNTFO") { field(DESC, "CPLRTEMP1 fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)40:CPLRTEMP1_CNT") field(LNK2, "$(CM,undefined)40:CPLRTEMP1_CNTTC") field(LNK3, "$(CM,undefined)40:CPLRTEMP1_CNTUC") } record(calc, "$(CM,undefined)40:CPLRTEMP1_CNT") { field(DESC, "CPLRTEMP1 total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)40:CPLRTEMP1_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)40:CPLRTEMP1_CNTTC") { field(DESC, "CPLRTEMP1 today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)40:CPLRTEMP1_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)40:CPLRTEMP1_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)40:CPLRTEMP1_CNTT") { field(DESC, "CPLRTEMP1 today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)40:CPLRTEMP1_CNTY") { field(DESC, "CPLRTEMP1 yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)40:CPLRTEMP1_CNTUC") { field(DESC, "CPLRTEMP1 user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)40:CPLRTEMP1_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)40:CPLRTEMP1_CNTU") } record(longin, "$(CM,undefined)40:CPLRTEMP1_CNTU") { field(DESC, "CPLRTEMP1 user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)40:CPLRTEMP1_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)40:CPLRTEMP1_CNTU PP") } record(seq, "$(CM,undefined)40:CPLRTEMP1_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)40:CPLRTEMP1_CNTT") field(LNK1, "$(CM,undefined)40:CPLRTEMP1_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)40:CPLRTEMP1_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)40:CPLRTEMP2_CNTC") { field(DESC, "CPLRTEMP2 fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)40:CPLRTEMP2_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)40:CPLRTEMP2_CNTFO PP") } record(fanout, "$(CM,undefined)40:CPLRTEMP2_CNTFO") { field(DESC, "CPLRTEMP2 fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)40:CPLRTEMP2_CNT") field(LNK2, "$(CM,undefined)40:CPLRTEMP2_CNTTC") field(LNK3, "$(CM,undefined)40:CPLRTEMP2_CNTUC") } record(calc, "$(CM,undefined)40:CPLRTEMP2_CNT") { field(DESC, "CPLRTEMP2 total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)40:CPLRTEMP2_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)40:CPLRTEMP2_CNTTC") { field(DESC, "CPLRTEMP2 today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)40:CPLRTEMP2_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)40:CPLRTEMP2_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)40:CPLRTEMP2_CNTT") { field(DESC, "CPLRTEMP2 today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)40:CPLRTEMP2_CNTY") { field(DESC, "CPLRTEMP2 yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)40:CPLRTEMP2_CNTUC") { field(DESC, "CPLRTEMP2 user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)40:CPLRTEMP2_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)40:CPLRTEMP2_CNTU") } record(longin, "$(CM,undefined)40:CPLRTEMP2_CNTU") { field(DESC, "CPLRTEMP2 user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)40:CPLRTEMP2_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)40:CPLRTEMP2_CNTU PP") } record(seq, "$(CM,undefined)40:CPLRTEMP2_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)40:CPLRTEMP2_CNTT") field(LNK1, "$(CM,undefined)40:CPLRTEMP2_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)40:CPLRTEMP2_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)40:QUENCH_CNTC") { field(DESC, "QUENCH fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)40:QUENCH_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)40:QUENCH_CNTFO PP") } record(fanout, "$(CM,undefined)40:QUENCH_CNTFO") { field(DESC, "QUENCH fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)40:QUENCH_CNT") field(LNK2, "$(CM,undefined)40:QUENCH_CNTTC") field(LNK3, "$(CM,undefined)40:QUENCH_CNTUC") } record(calc, "$(CM,undefined)40:QUENCH_CNT") { field(DESC, "QUENCH total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)40:QUENCH_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)40:QUENCH_CNTTC") { field(DESC, "QUENCH today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)40:QUENCH_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)40:QUENCH_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)40:QUENCH_CNTT") { field(DESC, "QUENCH today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)40:QUENCH_CNTY") { field(DESC, "QUENCH yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)40:QUENCH_CNTUC") { field(DESC, "QUENCH user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)40:QUENCH_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)40:QUENCH_CNTU") } record(longin, "$(CM,undefined)40:QUENCH_CNTU") { field(DESC, "QUENCH user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)40:QUENCH_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)40:QUENCH_CNTU PP") } record(seq, "$(CM,undefined)40:QUENCH_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)40:QUENCH_CNTT") field(LNK1, "$(CM,undefined)40:QUENCH_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)40:QUENCH_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)40:RESINTLK_CNTC") { field(DESC, "RESINTLK fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)40:RESINTLK_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)40:RESINTLK_CNTFO PP") } record(fanout, "$(CM,undefined)40:RESINTLK_CNTFO") { field(DESC, "RESINTLK fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)40:RESINTLK_CNT") field(LNK2, "$(CM,undefined)40:RESINTLK_CNTTC") field(LNK3, "$(CM,undefined)40:RESINTLK_CNTUC") } record(calc, "$(CM,undefined)40:RESINTLK_CNT") { field(DESC, "RESINTLK total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)40:RESINTLK_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)40:RESINTLK_CNTTC") { field(DESC, "RESINTLK today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)40:RESINTLK_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)40:RESINTLK_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)40:RESINTLK_CNTT") { field(DESC, "RESINTLK today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)40:RESINTLK_CNTY") { field(DESC, "RESINTLK yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)40:RESINTLK_CNTUC") { field(DESC, "RESINTLK user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)40:RESINTLK_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)40:RESINTLK_CNTU") } record(longin, "$(CM,undefined)40:RESINTLK_CNTU") { field(DESC, "RESINTLK user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)40:RESINTLK_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)40:RESINTLK_CNTU PP") } record(seq, "$(CM,undefined)40:RESINTLK_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)40:RESINTLK_CNTT") field(LNK1, "$(CM,undefined)40:RESINTLK_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)40:RESINTLK_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)40:RESLINK_CNTC") { field(DESC, "RESLINK fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)40:RESLINK_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)40:RESLINK_CNTFO PP") } record(fanout, "$(CM,undefined)40:RESLINK_CNTFO") { field(DESC, "RESLINK fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)40:RESLINK_CNT") field(LNK2, "$(CM,undefined)40:RESLINK_CNTTC") field(LNK3, "$(CM,undefined)40:RESLINK_CNTUC") } record(calc, "$(CM,undefined)40:RESLINK_CNT") { field(DESC, "RESLINK total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)40:RESLINK_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)40:RESLINK_CNTTC") { field(DESC, "RESLINK today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)40:RESLINK_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)40:RESLINK_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)40:RESLINK_CNTT") { field(DESC, "RESLINK today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)40:RESLINK_CNTY") { field(DESC, "RESLINK yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)40:RESLINK_CNTUC") { field(DESC, "RESLINK user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)40:RESLINK_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)40:RESLINK_CNTU") } record(longin, "$(CM,undefined)40:RESLINK_CNTU") { field(DESC, "RESLINK user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)40:RESLINK_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)40:RESLINK_CNTU PP") } record(seq, "$(CM,undefined)40:RESLINK_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)40:RESLINK_CNTT") field(LNK1, "$(CM,undefined)40:RESLINK_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)40:RESLINK_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)40:PLL_CNTC") { field(DESC, "PLL fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)40:PLL_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)40:PLL_CNTFO PP") } record(fanout, "$(CM,undefined)40:PLL_CNTFO") { field(DESC, "PLL fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)40:PLL_CNT") field(LNK2, "$(CM,undefined)40:PLL_CNTTC") field(LNK3, "$(CM,undefined)40:PLL_CNTUC") } record(calc, "$(CM,undefined)40:PLL_CNT") { field(DESC, "PLL total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)40:PLL_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)40:PLL_CNTTC") { field(DESC, "PLL today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)40:PLL_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)40:PLL_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)40:PLL_CNTT") { field(DESC, "PLL today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)40:PLL_CNTY") { field(DESC, "PLL yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)40:PLL_CNTUC") { field(DESC, "PLL user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)40:PLL_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)40:PLL_CNTU") } record(longin, "$(CM,undefined)40:PLL_CNTU") { field(DESC, "PLL user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)40:PLL_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)40:PLL_CNTU PP") } record(seq, "$(CM,undefined)40:PLL_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)40:PLL_CNTT") field(LNK1, "$(CM,undefined)40:PLL_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)40:PLL_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)40:IOCWDOG_CNTC") { field(DESC, "IOCWDOG fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)40:IOCWDOG_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)40:IOCWDOG_CNTFO PP") } record(fanout, "$(CM,undefined)40:IOCWDOG_CNTFO") { field(DESC, "IOCWDOG fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)40:IOCWDOG_CNT") field(LNK2, "$(CM,undefined)40:IOCWDOG_CNTTC") field(LNK3, "$(CM,undefined)40:IOCWDOG_CNTUC") } record(calc, "$(CM,undefined)40:IOCWDOG_CNT") { field(DESC, "IOCWDOG total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)40:IOCWDOG_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)40:IOCWDOG_CNTTC") { field(DESC, "IOCWDOG today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)40:IOCWDOG_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)40:IOCWDOG_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)40:IOCWDOG_CNTT") { field(DESC, "IOCWDOG today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)40:IOCWDOG_CNTY") { field(DESC, "IOCWDOG yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)40:IOCWDOG_CNTUC") { field(DESC, "IOCWDOG user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)40:IOCWDOG_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)40:IOCWDOG_CNTU") } record(longin, "$(CM,undefined)40:IOCWDOG_CNTU") { field(DESC, "IOCWDOG user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)40:IOCWDOG_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)40:IOCWDOG_CNTU PP") } record(seq, "$(CM,undefined)40:IOCWDOG_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)40:IOCWDOG_CNTT") field(LNK1, "$(CM,undefined)40:IOCWDOG_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)40:IOCWDOG_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)40:SSA_CNTC") { field(DESC, "SSA fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)40:SSA_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)40:SSA_CNTFO PP") } record(fanout, "$(CM,undefined)40:SSA_CNTFO") { field(DESC, "SSA fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)40:SSA_CNT") field(LNK2, "$(CM,undefined)40:SSA_CNTTC") field(LNK3, "$(CM,undefined)40:SSA_CNTUC") } record(calc, "$(CM,undefined)40:SSA_CNT") { field(DESC, "SSA total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)40:SSA_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)40:SSA_CNTTC") { field(DESC, "SSA today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)40:SSA_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)40:SSA_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)40:SSA_CNTT") { field(DESC, "SSA today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)40:SSA_CNTY") { field(DESC, "SSA yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)40:SSA_CNTUC") { field(DESC, "SSA user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)40:SSA_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)40:SSA_CNTU") } record(longin, "$(CM,undefined)40:SSA_CNTU") { field(DESC, "SSA user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)40:SSA_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)40:SSA_CNTU PP") } record(seq, "$(CM,undefined)40:SSA_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)40:SSA_CNTT") field(LNK1, "$(CM,undefined)40:SSA_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)40:SSA_CNTT PP") } record(fanout, "$(CM,undefined)50:INTLK_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(LNK1, "$(CM,undefined)50:STEPTEMP_CNTRO") field(LNK2, "$(CM,undefined)50:CPLRTEMP1_CNTRO") field(LNK3, "$(CM,undefined)50:CPLRTEMP2_CNTRO") field(LNK4, "$(CM,undefined)50:QUENCH_CNTRO") }#================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)50:STEPTEMP_CNTC") { field(DESC, "STEPTEMP fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)50:STEPTEMP_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)50:STEPTEMP_CNTFO PP") } record(fanout, "$(CM,undefined)50:STEPTEMP_CNTFO") { field(DESC, "STEPTEMP fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)50:STEPTEMP_CNT") field(LNK2, "$(CM,undefined)50:STEPTEMP_CNTTC") field(LNK3, "$(CM,undefined)50:STEPTEMP_CNTUC") } record(calc, "$(CM,undefined)50:STEPTEMP_CNT") { field(DESC, "STEPTEMP total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)50:STEPTEMP_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)50:STEPTEMP_CNTTC") { field(DESC, "STEPTEMP today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)50:STEPTEMP_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)50:STEPTEMP_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)50:STEPTEMP_CNTT") { field(DESC, "STEPTEMP today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)50:STEPTEMP_CNTY") { field(DESC, "STEPTEMP yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)50:STEPTEMP_CNTUC") { field(DESC, "STEPTEMP user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)50:STEPTEMP_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)50:STEPTEMP_CNTU") } record(longin, "$(CM,undefined)50:STEPTEMP_CNTU") { field(DESC, "STEPTEMP user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)50:STEPTEMP_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)50:STEPTEMP_CNTU PP") } record(seq, "$(CM,undefined)50:STEPTEMP_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)50:STEPTEMP_CNTT") field(LNK1, "$(CM,undefined)50:STEPTEMP_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)50:STEPTEMP_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)50:CPLRTEMP1_CNTC") { field(DESC, "CPLRTEMP1 fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)50:CPLRTEMP1_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)50:CPLRTEMP1_CNTFO PP") } record(fanout, "$(CM,undefined)50:CPLRTEMP1_CNTFO") { field(DESC, "CPLRTEMP1 fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)50:CPLRTEMP1_CNT") field(LNK2, "$(CM,undefined)50:CPLRTEMP1_CNTTC") field(LNK3, "$(CM,undefined)50:CPLRTEMP1_CNTUC") } record(calc, "$(CM,undefined)50:CPLRTEMP1_CNT") { field(DESC, "CPLRTEMP1 total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)50:CPLRTEMP1_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)50:CPLRTEMP1_CNTTC") { field(DESC, "CPLRTEMP1 today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)50:CPLRTEMP1_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)50:CPLRTEMP1_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)50:CPLRTEMP1_CNTT") { field(DESC, "CPLRTEMP1 today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)50:CPLRTEMP1_CNTY") { field(DESC, "CPLRTEMP1 yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)50:CPLRTEMP1_CNTUC") { field(DESC, "CPLRTEMP1 user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)50:CPLRTEMP1_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)50:CPLRTEMP1_CNTU") } record(longin, "$(CM,undefined)50:CPLRTEMP1_CNTU") { field(DESC, "CPLRTEMP1 user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)50:CPLRTEMP1_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)50:CPLRTEMP1_CNTU PP") } record(seq, "$(CM,undefined)50:CPLRTEMP1_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)50:CPLRTEMP1_CNTT") field(LNK1, "$(CM,undefined)50:CPLRTEMP1_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)50:CPLRTEMP1_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)50:CPLRTEMP2_CNTC") { field(DESC, "CPLRTEMP2 fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)50:CPLRTEMP2_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)50:CPLRTEMP2_CNTFO PP") } record(fanout, "$(CM,undefined)50:CPLRTEMP2_CNTFO") { field(DESC, "CPLRTEMP2 fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)50:CPLRTEMP2_CNT") field(LNK2, "$(CM,undefined)50:CPLRTEMP2_CNTTC") field(LNK3, "$(CM,undefined)50:CPLRTEMP2_CNTUC") } record(calc, "$(CM,undefined)50:CPLRTEMP2_CNT") { field(DESC, "CPLRTEMP2 total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)50:CPLRTEMP2_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)50:CPLRTEMP2_CNTTC") { field(DESC, "CPLRTEMP2 today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)50:CPLRTEMP2_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)50:CPLRTEMP2_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)50:CPLRTEMP2_CNTT") { field(DESC, "CPLRTEMP2 today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)50:CPLRTEMP2_CNTY") { field(DESC, "CPLRTEMP2 yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)50:CPLRTEMP2_CNTUC") { field(DESC, "CPLRTEMP2 user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)50:CPLRTEMP2_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)50:CPLRTEMP2_CNTU") } record(longin, "$(CM,undefined)50:CPLRTEMP2_CNTU") { field(DESC, "CPLRTEMP2 user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)50:CPLRTEMP2_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)50:CPLRTEMP2_CNTU PP") } record(seq, "$(CM,undefined)50:CPLRTEMP2_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)50:CPLRTEMP2_CNTT") field(LNK1, "$(CM,undefined)50:CPLRTEMP2_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)50:CPLRTEMP2_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)50:QUENCH_CNTC") { field(DESC, "QUENCH fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)50:QUENCH_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)50:QUENCH_CNTFO PP") } record(fanout, "$(CM,undefined)50:QUENCH_CNTFO") { field(DESC, "QUENCH fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)50:QUENCH_CNT") field(LNK2, "$(CM,undefined)50:QUENCH_CNTTC") field(LNK3, "$(CM,undefined)50:QUENCH_CNTUC") } record(calc, "$(CM,undefined)50:QUENCH_CNT") { field(DESC, "QUENCH total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)50:QUENCH_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)50:QUENCH_CNTTC") { field(DESC, "QUENCH today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)50:QUENCH_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)50:QUENCH_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)50:QUENCH_CNTT") { field(DESC, "QUENCH today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)50:QUENCH_CNTY") { field(DESC, "QUENCH yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)50:QUENCH_CNTUC") { field(DESC, "QUENCH user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)50:QUENCH_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)50:QUENCH_CNTU") } record(longin, "$(CM,undefined)50:QUENCH_CNTU") { field(DESC, "QUENCH user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)50:QUENCH_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)50:QUENCH_CNTU PP") } record(seq, "$(CM,undefined)50:QUENCH_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)50:QUENCH_CNTT") field(LNK1, "$(CM,undefined)50:QUENCH_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)50:QUENCH_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)50:RESINTLK_CNTC") { field(DESC, "RESINTLK fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)50:RESINTLK_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)50:RESINTLK_CNTFO PP") } record(fanout, "$(CM,undefined)50:RESINTLK_CNTFO") { field(DESC, "RESINTLK fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)50:RESINTLK_CNT") field(LNK2, "$(CM,undefined)50:RESINTLK_CNTTC") field(LNK3, "$(CM,undefined)50:RESINTLK_CNTUC") } record(calc, "$(CM,undefined)50:RESINTLK_CNT") { field(DESC, "RESINTLK total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)50:RESINTLK_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)50:RESINTLK_CNTTC") { field(DESC, "RESINTLK today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)50:RESINTLK_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)50:RESINTLK_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)50:RESINTLK_CNTT") { field(DESC, "RESINTLK today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)50:RESINTLK_CNTY") { field(DESC, "RESINTLK yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)50:RESINTLK_CNTUC") { field(DESC, "RESINTLK user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)50:RESINTLK_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)50:RESINTLK_CNTU") } record(longin, "$(CM,undefined)50:RESINTLK_CNTU") { field(DESC, "RESINTLK user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)50:RESINTLK_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)50:RESINTLK_CNTU PP") } record(seq, "$(CM,undefined)50:RESINTLK_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)50:RESINTLK_CNTT") field(LNK1, "$(CM,undefined)50:RESINTLK_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)50:RESINTLK_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)50:RESLINK_CNTC") { field(DESC, "RESLINK fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)50:RESLINK_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)50:RESLINK_CNTFO PP") } record(fanout, "$(CM,undefined)50:RESLINK_CNTFO") { field(DESC, "RESLINK fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)50:RESLINK_CNT") field(LNK2, "$(CM,undefined)50:RESLINK_CNTTC") field(LNK3, "$(CM,undefined)50:RESLINK_CNTUC") } record(calc, "$(CM,undefined)50:RESLINK_CNT") { field(DESC, "RESLINK total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)50:RESLINK_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)50:RESLINK_CNTTC") { field(DESC, "RESLINK today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)50:RESLINK_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)50:RESLINK_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)50:RESLINK_CNTT") { field(DESC, "RESLINK today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)50:RESLINK_CNTY") { field(DESC, "RESLINK yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)50:RESLINK_CNTUC") { field(DESC, "RESLINK user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)50:RESLINK_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)50:RESLINK_CNTU") } record(longin, "$(CM,undefined)50:RESLINK_CNTU") { field(DESC, "RESLINK user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)50:RESLINK_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)50:RESLINK_CNTU PP") } record(seq, "$(CM,undefined)50:RESLINK_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)50:RESLINK_CNTT") field(LNK1, "$(CM,undefined)50:RESLINK_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)50:RESLINK_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)50:PLL_CNTC") { field(DESC, "PLL fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)50:PLL_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)50:PLL_CNTFO PP") } record(fanout, "$(CM,undefined)50:PLL_CNTFO") { field(DESC, "PLL fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)50:PLL_CNT") field(LNK2, "$(CM,undefined)50:PLL_CNTTC") field(LNK3, "$(CM,undefined)50:PLL_CNTUC") } record(calc, "$(CM,undefined)50:PLL_CNT") { field(DESC, "PLL total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)50:PLL_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)50:PLL_CNTTC") { field(DESC, "PLL today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)50:PLL_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)50:PLL_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)50:PLL_CNTT") { field(DESC, "PLL today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)50:PLL_CNTY") { field(DESC, "PLL yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)50:PLL_CNTUC") { field(DESC, "PLL user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)50:PLL_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)50:PLL_CNTU") } record(longin, "$(CM,undefined)50:PLL_CNTU") { field(DESC, "PLL user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)50:PLL_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)50:PLL_CNTU PP") } record(seq, "$(CM,undefined)50:PLL_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)50:PLL_CNTT") field(LNK1, "$(CM,undefined)50:PLL_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)50:PLL_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)50:IOCWDOG_CNTC") { field(DESC, "IOCWDOG fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)50:IOCWDOG_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)50:IOCWDOG_CNTFO PP") } record(fanout, "$(CM,undefined)50:IOCWDOG_CNTFO") { field(DESC, "IOCWDOG fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)50:IOCWDOG_CNT") field(LNK2, "$(CM,undefined)50:IOCWDOG_CNTTC") field(LNK3, "$(CM,undefined)50:IOCWDOG_CNTUC") } record(calc, "$(CM,undefined)50:IOCWDOG_CNT") { field(DESC, "IOCWDOG total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)50:IOCWDOG_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)50:IOCWDOG_CNTTC") { field(DESC, "IOCWDOG today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)50:IOCWDOG_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)50:IOCWDOG_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)50:IOCWDOG_CNTT") { field(DESC, "IOCWDOG today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)50:IOCWDOG_CNTY") { field(DESC, "IOCWDOG yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)50:IOCWDOG_CNTUC") { field(DESC, "IOCWDOG user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)50:IOCWDOG_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)50:IOCWDOG_CNTU") } record(longin, "$(CM,undefined)50:IOCWDOG_CNTU") { field(DESC, "IOCWDOG user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)50:IOCWDOG_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)50:IOCWDOG_CNTU PP") } record(seq, "$(CM,undefined)50:IOCWDOG_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)50:IOCWDOG_CNTT") field(LNK1, "$(CM,undefined)50:IOCWDOG_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)50:IOCWDOG_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)50:SSA_CNTC") { field(DESC, "SSA fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)50:SSA_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)50:SSA_CNTFO PP") } record(fanout, "$(CM,undefined)50:SSA_CNTFO") { field(DESC, "SSA fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)50:SSA_CNT") field(LNK2, "$(CM,undefined)50:SSA_CNTTC") field(LNK3, "$(CM,undefined)50:SSA_CNTUC") } record(calc, "$(CM,undefined)50:SSA_CNT") { field(DESC, "SSA total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)50:SSA_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)50:SSA_CNTTC") { field(DESC, "SSA today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)50:SSA_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)50:SSA_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)50:SSA_CNTT") { field(DESC, "SSA today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)50:SSA_CNTY") { field(DESC, "SSA yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)50:SSA_CNTUC") { field(DESC, "SSA user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)50:SSA_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)50:SSA_CNTU") } record(longin, "$(CM,undefined)50:SSA_CNTU") { field(DESC, "SSA user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)50:SSA_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)50:SSA_CNTU PP") } record(seq, "$(CM,undefined)50:SSA_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)50:SSA_CNTT") field(LNK1, "$(CM,undefined)50:SSA_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)50:SSA_CNTT PP") } record(fanout, "$(CM,undefined)60:INTLK_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(LNK1, "$(CM,undefined)60:STEPTEMP_CNTRO") field(LNK2, "$(CM,undefined)60:CPLRTEMP1_CNTRO") field(LNK3, "$(CM,undefined)60:CPLRTEMP2_CNTRO") field(LNK4, "$(CM,undefined)60:QUENCH_CNTRO") }#================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)60:STEPTEMP_CNTC") { field(DESC, "STEPTEMP fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)60:STEPTEMP_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)60:STEPTEMP_CNTFO PP") } record(fanout, "$(CM,undefined)60:STEPTEMP_CNTFO") { field(DESC, "STEPTEMP fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)60:STEPTEMP_CNT") field(LNK2, "$(CM,undefined)60:STEPTEMP_CNTTC") field(LNK3, "$(CM,undefined)60:STEPTEMP_CNTUC") } record(calc, "$(CM,undefined)60:STEPTEMP_CNT") { field(DESC, "STEPTEMP total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)60:STEPTEMP_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)60:STEPTEMP_CNTTC") { field(DESC, "STEPTEMP today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)60:STEPTEMP_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)60:STEPTEMP_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)60:STEPTEMP_CNTT") { field(DESC, "STEPTEMP today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)60:STEPTEMP_CNTY") { field(DESC, "STEPTEMP yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)60:STEPTEMP_CNTUC") { field(DESC, "STEPTEMP user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)60:STEPTEMP_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)60:STEPTEMP_CNTU") } record(longin, "$(CM,undefined)60:STEPTEMP_CNTU") { field(DESC, "STEPTEMP user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)60:STEPTEMP_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)60:STEPTEMP_CNTU PP") } record(seq, "$(CM,undefined)60:STEPTEMP_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)60:STEPTEMP_CNTT") field(LNK1, "$(CM,undefined)60:STEPTEMP_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)60:STEPTEMP_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)60:CPLRTEMP1_CNTC") { field(DESC, "CPLRTEMP1 fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)60:CPLRTEMP1_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)60:CPLRTEMP1_CNTFO PP") } record(fanout, "$(CM,undefined)60:CPLRTEMP1_CNTFO") { field(DESC, "CPLRTEMP1 fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)60:CPLRTEMP1_CNT") field(LNK2, "$(CM,undefined)60:CPLRTEMP1_CNTTC") field(LNK3, "$(CM,undefined)60:CPLRTEMP1_CNTUC") } record(calc, "$(CM,undefined)60:CPLRTEMP1_CNT") { field(DESC, "CPLRTEMP1 total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)60:CPLRTEMP1_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)60:CPLRTEMP1_CNTTC") { field(DESC, "CPLRTEMP1 today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)60:CPLRTEMP1_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)60:CPLRTEMP1_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)60:CPLRTEMP1_CNTT") { field(DESC, "CPLRTEMP1 today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)60:CPLRTEMP1_CNTY") { field(DESC, "CPLRTEMP1 yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)60:CPLRTEMP1_CNTUC") { field(DESC, "CPLRTEMP1 user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)60:CPLRTEMP1_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)60:CPLRTEMP1_CNTU") } record(longin, "$(CM,undefined)60:CPLRTEMP1_CNTU") { field(DESC, "CPLRTEMP1 user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)60:CPLRTEMP1_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)60:CPLRTEMP1_CNTU PP") } record(seq, "$(CM,undefined)60:CPLRTEMP1_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)60:CPLRTEMP1_CNTT") field(LNK1, "$(CM,undefined)60:CPLRTEMP1_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)60:CPLRTEMP1_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)60:CPLRTEMP2_CNTC") { field(DESC, "CPLRTEMP2 fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)60:CPLRTEMP2_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)60:CPLRTEMP2_CNTFO PP") } record(fanout, "$(CM,undefined)60:CPLRTEMP2_CNTFO") { field(DESC, "CPLRTEMP2 fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)60:CPLRTEMP2_CNT") field(LNK2, "$(CM,undefined)60:CPLRTEMP2_CNTTC") field(LNK3, "$(CM,undefined)60:CPLRTEMP2_CNTUC") } record(calc, "$(CM,undefined)60:CPLRTEMP2_CNT") { field(DESC, "CPLRTEMP2 total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)60:CPLRTEMP2_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)60:CPLRTEMP2_CNTTC") { field(DESC, "CPLRTEMP2 today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)60:CPLRTEMP2_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)60:CPLRTEMP2_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)60:CPLRTEMP2_CNTT") { field(DESC, "CPLRTEMP2 today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)60:CPLRTEMP2_CNTY") { field(DESC, "CPLRTEMP2 yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)60:CPLRTEMP2_CNTUC") { field(DESC, "CPLRTEMP2 user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)60:CPLRTEMP2_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)60:CPLRTEMP2_CNTU") } record(longin, "$(CM,undefined)60:CPLRTEMP2_CNTU") { field(DESC, "CPLRTEMP2 user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)60:CPLRTEMP2_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)60:CPLRTEMP2_CNTU PP") } record(seq, "$(CM,undefined)60:CPLRTEMP2_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)60:CPLRTEMP2_CNTT") field(LNK1, "$(CM,undefined)60:CPLRTEMP2_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)60:CPLRTEMP2_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)60:QUENCH_CNTC") { field(DESC, "QUENCH fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)60:QUENCH_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)60:QUENCH_CNTFO PP") } record(fanout, "$(CM,undefined)60:QUENCH_CNTFO") { field(DESC, "QUENCH fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)60:QUENCH_CNT") field(LNK2, "$(CM,undefined)60:QUENCH_CNTTC") field(LNK3, "$(CM,undefined)60:QUENCH_CNTUC") } record(calc, "$(CM,undefined)60:QUENCH_CNT") { field(DESC, "QUENCH total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)60:QUENCH_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)60:QUENCH_CNTTC") { field(DESC, "QUENCH today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)60:QUENCH_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)60:QUENCH_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)60:QUENCH_CNTT") { field(DESC, "QUENCH today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)60:QUENCH_CNTY") { field(DESC, "QUENCH yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)60:QUENCH_CNTUC") { field(DESC, "QUENCH user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)60:QUENCH_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)60:QUENCH_CNTU") } record(longin, "$(CM,undefined)60:QUENCH_CNTU") { field(DESC, "QUENCH user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)60:QUENCH_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)60:QUENCH_CNTU PP") } record(seq, "$(CM,undefined)60:QUENCH_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)60:QUENCH_CNTT") field(LNK1, "$(CM,undefined)60:QUENCH_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)60:QUENCH_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)60:RESINTLK_CNTC") { field(DESC, "RESINTLK fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)60:RESINTLK_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)60:RESINTLK_CNTFO PP") } record(fanout, "$(CM,undefined)60:RESINTLK_CNTFO") { field(DESC, "RESINTLK fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)60:RESINTLK_CNT") field(LNK2, "$(CM,undefined)60:RESINTLK_CNTTC") field(LNK3, "$(CM,undefined)60:RESINTLK_CNTUC") } record(calc, "$(CM,undefined)60:RESINTLK_CNT") { field(DESC, "RESINTLK total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)60:RESINTLK_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)60:RESINTLK_CNTTC") { field(DESC, "RESINTLK today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)60:RESINTLK_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)60:RESINTLK_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)60:RESINTLK_CNTT") { field(DESC, "RESINTLK today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)60:RESINTLK_CNTY") { field(DESC, "RESINTLK yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)60:RESINTLK_CNTUC") { field(DESC, "RESINTLK user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)60:RESINTLK_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)60:RESINTLK_CNTU") } record(longin, "$(CM,undefined)60:RESINTLK_CNTU") { field(DESC, "RESINTLK user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)60:RESINTLK_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)60:RESINTLK_CNTU PP") } record(seq, "$(CM,undefined)60:RESINTLK_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)60:RESINTLK_CNTT") field(LNK1, "$(CM,undefined)60:RESINTLK_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)60:RESINTLK_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)60:RESLINK_CNTC") { field(DESC, "RESLINK fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)60:RESLINK_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)60:RESLINK_CNTFO PP") } record(fanout, "$(CM,undefined)60:RESLINK_CNTFO") { field(DESC, "RESLINK fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)60:RESLINK_CNT") field(LNK2, "$(CM,undefined)60:RESLINK_CNTTC") field(LNK3, "$(CM,undefined)60:RESLINK_CNTUC") } record(calc, "$(CM,undefined)60:RESLINK_CNT") { field(DESC, "RESLINK total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)60:RESLINK_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)60:RESLINK_CNTTC") { field(DESC, "RESLINK today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)60:RESLINK_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)60:RESLINK_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)60:RESLINK_CNTT") { field(DESC, "RESLINK today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)60:RESLINK_CNTY") { field(DESC, "RESLINK yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)60:RESLINK_CNTUC") { field(DESC, "RESLINK user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)60:RESLINK_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)60:RESLINK_CNTU") } record(longin, "$(CM,undefined)60:RESLINK_CNTU") { field(DESC, "RESLINK user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)60:RESLINK_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)60:RESLINK_CNTU PP") } record(seq, "$(CM,undefined)60:RESLINK_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)60:RESLINK_CNTT") field(LNK1, "$(CM,undefined)60:RESLINK_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)60:RESLINK_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)60:PLL_CNTC") { field(DESC, "PLL fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)60:PLL_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)60:PLL_CNTFO PP") } record(fanout, "$(CM,undefined)60:PLL_CNTFO") { field(DESC, "PLL fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)60:PLL_CNT") field(LNK2, "$(CM,undefined)60:PLL_CNTTC") field(LNK3, "$(CM,undefined)60:PLL_CNTUC") } record(calc, "$(CM,undefined)60:PLL_CNT") { field(DESC, "PLL total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)60:PLL_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)60:PLL_CNTTC") { field(DESC, "PLL today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)60:PLL_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)60:PLL_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)60:PLL_CNTT") { field(DESC, "PLL today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)60:PLL_CNTY") { field(DESC, "PLL yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)60:PLL_CNTUC") { field(DESC, "PLL user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)60:PLL_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)60:PLL_CNTU") } record(longin, "$(CM,undefined)60:PLL_CNTU") { field(DESC, "PLL user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)60:PLL_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)60:PLL_CNTU PP") } record(seq, "$(CM,undefined)60:PLL_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)60:PLL_CNTT") field(LNK1, "$(CM,undefined)60:PLL_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)60:PLL_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)60:IOCWDOG_CNTC") { field(DESC, "IOCWDOG fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)60:IOCWDOG_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)60:IOCWDOG_CNTFO PP") } record(fanout, "$(CM,undefined)60:IOCWDOG_CNTFO") { field(DESC, "IOCWDOG fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)60:IOCWDOG_CNT") field(LNK2, "$(CM,undefined)60:IOCWDOG_CNTTC") field(LNK3, "$(CM,undefined)60:IOCWDOG_CNTUC") } record(calc, "$(CM,undefined)60:IOCWDOG_CNT") { field(DESC, "IOCWDOG total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)60:IOCWDOG_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)60:IOCWDOG_CNTTC") { field(DESC, "IOCWDOG today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)60:IOCWDOG_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)60:IOCWDOG_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)60:IOCWDOG_CNTT") { field(DESC, "IOCWDOG today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)60:IOCWDOG_CNTY") { field(DESC, "IOCWDOG yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)60:IOCWDOG_CNTUC") { field(DESC, "IOCWDOG user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)60:IOCWDOG_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)60:IOCWDOG_CNTU") } record(longin, "$(CM,undefined)60:IOCWDOG_CNTU") { field(DESC, "IOCWDOG user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)60:IOCWDOG_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)60:IOCWDOG_CNTU PP") } record(seq, "$(CM,undefined)60:IOCWDOG_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)60:IOCWDOG_CNTT") field(LNK1, "$(CM,undefined)60:IOCWDOG_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)60:IOCWDOG_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)60:SSA_CNTC") { field(DESC, "SSA fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)60:SSA_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)60:SSA_CNTFO PP") } record(fanout, "$(CM,undefined)60:SSA_CNTFO") { field(DESC, "SSA fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)60:SSA_CNT") field(LNK2, "$(CM,undefined)60:SSA_CNTTC") field(LNK3, "$(CM,undefined)60:SSA_CNTUC") } record(calc, "$(CM,undefined)60:SSA_CNT") { field(DESC, "SSA total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)60:SSA_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)60:SSA_CNTTC") { field(DESC, "SSA today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)60:SSA_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)60:SSA_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)60:SSA_CNTT") { field(DESC, "SSA today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)60:SSA_CNTY") { field(DESC, "SSA yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)60:SSA_CNTUC") { field(DESC, "SSA user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)60:SSA_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)60:SSA_CNTU") } record(longin, "$(CM,undefined)60:SSA_CNTU") { field(DESC, "SSA user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)60:SSA_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)60:SSA_CNTU PP") } record(seq, "$(CM,undefined)60:SSA_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)60:SSA_CNTT") field(LNK1, "$(CM,undefined)60:SSA_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)60:SSA_CNTT PP") } record(fanout, "$(CM,undefined)70:INTLK_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(LNK1, "$(CM,undefined)70:STEPTEMP_CNTRO") field(LNK2, "$(CM,undefined)70:CPLRTEMP1_CNTRO") field(LNK3, "$(CM,undefined)70:CPLRTEMP2_CNTRO") field(LNK4, "$(CM,undefined)70:QUENCH_CNTRO") }#================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)70:STEPTEMP_CNTC") { field(DESC, "STEPTEMP fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)70:STEPTEMP_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)70:STEPTEMP_CNTFO PP") } record(fanout, "$(CM,undefined)70:STEPTEMP_CNTFO") { field(DESC, "STEPTEMP fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)70:STEPTEMP_CNT") field(LNK2, "$(CM,undefined)70:STEPTEMP_CNTTC") field(LNK3, "$(CM,undefined)70:STEPTEMP_CNTUC") } record(calc, "$(CM,undefined)70:STEPTEMP_CNT") { field(DESC, "STEPTEMP total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)70:STEPTEMP_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)70:STEPTEMP_CNTTC") { field(DESC, "STEPTEMP today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)70:STEPTEMP_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)70:STEPTEMP_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)70:STEPTEMP_CNTT") { field(DESC, "STEPTEMP today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)70:STEPTEMP_CNTY") { field(DESC, "STEPTEMP yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)70:STEPTEMP_CNTUC") { field(DESC, "STEPTEMP user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)70:STEPTEMP_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)70:STEPTEMP_CNTU") } record(longin, "$(CM,undefined)70:STEPTEMP_CNTU") { field(DESC, "STEPTEMP user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)70:STEPTEMP_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)70:STEPTEMP_CNTU PP") } record(seq, "$(CM,undefined)70:STEPTEMP_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)70:STEPTEMP_CNTT") field(LNK1, "$(CM,undefined)70:STEPTEMP_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)70:STEPTEMP_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)70:CPLRTEMP1_CNTC") { field(DESC, "CPLRTEMP1 fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)70:CPLRTEMP1_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)70:CPLRTEMP1_CNTFO PP") } record(fanout, "$(CM,undefined)70:CPLRTEMP1_CNTFO") { field(DESC, "CPLRTEMP1 fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)70:CPLRTEMP1_CNT") field(LNK2, "$(CM,undefined)70:CPLRTEMP1_CNTTC") field(LNK3, "$(CM,undefined)70:CPLRTEMP1_CNTUC") } record(calc, "$(CM,undefined)70:CPLRTEMP1_CNT") { field(DESC, "CPLRTEMP1 total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)70:CPLRTEMP1_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)70:CPLRTEMP1_CNTTC") { field(DESC, "CPLRTEMP1 today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)70:CPLRTEMP1_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)70:CPLRTEMP1_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)70:CPLRTEMP1_CNTT") { field(DESC, "CPLRTEMP1 today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)70:CPLRTEMP1_CNTY") { field(DESC, "CPLRTEMP1 yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)70:CPLRTEMP1_CNTUC") { field(DESC, "CPLRTEMP1 user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)70:CPLRTEMP1_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)70:CPLRTEMP1_CNTU") } record(longin, "$(CM,undefined)70:CPLRTEMP1_CNTU") { field(DESC, "CPLRTEMP1 user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)70:CPLRTEMP1_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)70:CPLRTEMP1_CNTU PP") } record(seq, "$(CM,undefined)70:CPLRTEMP1_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)70:CPLRTEMP1_CNTT") field(LNK1, "$(CM,undefined)70:CPLRTEMP1_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)70:CPLRTEMP1_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)70:CPLRTEMP2_CNTC") { field(DESC, "CPLRTEMP2 fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)70:CPLRTEMP2_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)70:CPLRTEMP2_CNTFO PP") } record(fanout, "$(CM,undefined)70:CPLRTEMP2_CNTFO") { field(DESC, "CPLRTEMP2 fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)70:CPLRTEMP2_CNT") field(LNK2, "$(CM,undefined)70:CPLRTEMP2_CNTTC") field(LNK3, "$(CM,undefined)70:CPLRTEMP2_CNTUC") } record(calc, "$(CM,undefined)70:CPLRTEMP2_CNT") { field(DESC, "CPLRTEMP2 total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)70:CPLRTEMP2_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)70:CPLRTEMP2_CNTTC") { field(DESC, "CPLRTEMP2 today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)70:CPLRTEMP2_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)70:CPLRTEMP2_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)70:CPLRTEMP2_CNTT") { field(DESC, "CPLRTEMP2 today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)70:CPLRTEMP2_CNTY") { field(DESC, "CPLRTEMP2 yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)70:CPLRTEMP2_CNTUC") { field(DESC, "CPLRTEMP2 user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)70:CPLRTEMP2_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)70:CPLRTEMP2_CNTU") } record(longin, "$(CM,undefined)70:CPLRTEMP2_CNTU") { field(DESC, "CPLRTEMP2 user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)70:CPLRTEMP2_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)70:CPLRTEMP2_CNTU PP") } record(seq, "$(CM,undefined)70:CPLRTEMP2_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)70:CPLRTEMP2_CNTT") field(LNK1, "$(CM,undefined)70:CPLRTEMP2_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)70:CPLRTEMP2_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)70:QUENCH_CNTC") { field(DESC, "QUENCH fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)70:QUENCH_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)70:QUENCH_CNTFO PP") } record(fanout, "$(CM,undefined)70:QUENCH_CNTFO") { field(DESC, "QUENCH fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)70:QUENCH_CNT") field(LNK2, "$(CM,undefined)70:QUENCH_CNTTC") field(LNK3, "$(CM,undefined)70:QUENCH_CNTUC") } record(calc, "$(CM,undefined)70:QUENCH_CNT") { field(DESC, "QUENCH total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)70:QUENCH_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)70:QUENCH_CNTTC") { field(DESC, "QUENCH today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)70:QUENCH_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)70:QUENCH_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)70:QUENCH_CNTT") { field(DESC, "QUENCH today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)70:QUENCH_CNTY") { field(DESC, "QUENCH yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)70:QUENCH_CNTUC") { field(DESC, "QUENCH user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)70:QUENCH_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)70:QUENCH_CNTU") } record(longin, "$(CM,undefined)70:QUENCH_CNTU") { field(DESC, "QUENCH user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)70:QUENCH_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)70:QUENCH_CNTU PP") } record(seq, "$(CM,undefined)70:QUENCH_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)70:QUENCH_CNTT") field(LNK1, "$(CM,undefined)70:QUENCH_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)70:QUENCH_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)70:RESINTLK_CNTC") { field(DESC, "RESINTLK fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)70:RESINTLK_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)70:RESINTLK_CNTFO PP") } record(fanout, "$(CM,undefined)70:RESINTLK_CNTFO") { field(DESC, "RESINTLK fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)70:RESINTLK_CNT") field(LNK2, "$(CM,undefined)70:RESINTLK_CNTTC") field(LNK3, "$(CM,undefined)70:RESINTLK_CNTUC") } record(calc, "$(CM,undefined)70:RESINTLK_CNT") { field(DESC, "RESINTLK total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)70:RESINTLK_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)70:RESINTLK_CNTTC") { field(DESC, "RESINTLK today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)70:RESINTLK_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)70:RESINTLK_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)70:RESINTLK_CNTT") { field(DESC, "RESINTLK today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)70:RESINTLK_CNTY") { field(DESC, "RESINTLK yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)70:RESINTLK_CNTUC") { field(DESC, "RESINTLK user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)70:RESINTLK_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)70:RESINTLK_CNTU") } record(longin, "$(CM,undefined)70:RESINTLK_CNTU") { field(DESC, "RESINTLK user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)70:RESINTLK_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)70:RESINTLK_CNTU PP") } record(seq, "$(CM,undefined)70:RESINTLK_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)70:RESINTLK_CNTT") field(LNK1, "$(CM,undefined)70:RESINTLK_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)70:RESINTLK_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)70:RESLINK_CNTC") { field(DESC, "RESLINK fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)70:RESLINK_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)70:RESLINK_CNTFO PP") } record(fanout, "$(CM,undefined)70:RESLINK_CNTFO") { field(DESC, "RESLINK fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)70:RESLINK_CNT") field(LNK2, "$(CM,undefined)70:RESLINK_CNTTC") field(LNK3, "$(CM,undefined)70:RESLINK_CNTUC") } record(calc, "$(CM,undefined)70:RESLINK_CNT") { field(DESC, "RESLINK total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)70:RESLINK_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)70:RESLINK_CNTTC") { field(DESC, "RESLINK today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)70:RESLINK_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)70:RESLINK_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)70:RESLINK_CNTT") { field(DESC, "RESLINK today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)70:RESLINK_CNTY") { field(DESC, "RESLINK yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)70:RESLINK_CNTUC") { field(DESC, "RESLINK user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)70:RESLINK_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)70:RESLINK_CNTU") } record(longin, "$(CM,undefined)70:RESLINK_CNTU") { field(DESC, "RESLINK user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)70:RESLINK_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)70:RESLINK_CNTU PP") } record(seq, "$(CM,undefined)70:RESLINK_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)70:RESLINK_CNTT") field(LNK1, "$(CM,undefined)70:RESLINK_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)70:RESLINK_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)70:PLL_CNTC") { field(DESC, "PLL fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)70:PLL_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)70:PLL_CNTFO PP") } record(fanout, "$(CM,undefined)70:PLL_CNTFO") { field(DESC, "PLL fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)70:PLL_CNT") field(LNK2, "$(CM,undefined)70:PLL_CNTTC") field(LNK3, "$(CM,undefined)70:PLL_CNTUC") } record(calc, "$(CM,undefined)70:PLL_CNT") { field(DESC, "PLL total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)70:PLL_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)70:PLL_CNTTC") { field(DESC, "PLL today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)70:PLL_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)70:PLL_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)70:PLL_CNTT") { field(DESC, "PLL today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)70:PLL_CNTY") { field(DESC, "PLL yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)70:PLL_CNTUC") { field(DESC, "PLL user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)70:PLL_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)70:PLL_CNTU") } record(longin, "$(CM,undefined)70:PLL_CNTU") { field(DESC, "PLL user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)70:PLL_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)70:PLL_CNTU PP") } record(seq, "$(CM,undefined)70:PLL_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)70:PLL_CNTT") field(LNK1, "$(CM,undefined)70:PLL_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)70:PLL_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)70:IOCWDOG_CNTC") { field(DESC, "IOCWDOG fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)70:IOCWDOG_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)70:IOCWDOG_CNTFO PP") } record(fanout, "$(CM,undefined)70:IOCWDOG_CNTFO") { field(DESC, "IOCWDOG fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)70:IOCWDOG_CNT") field(LNK2, "$(CM,undefined)70:IOCWDOG_CNTTC") field(LNK3, "$(CM,undefined)70:IOCWDOG_CNTUC") } record(calc, "$(CM,undefined)70:IOCWDOG_CNT") { field(DESC, "IOCWDOG total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)70:IOCWDOG_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)70:IOCWDOG_CNTTC") { field(DESC, "IOCWDOG today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)70:IOCWDOG_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)70:IOCWDOG_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)70:IOCWDOG_CNTT") { field(DESC, "IOCWDOG today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)70:IOCWDOG_CNTY") { field(DESC, "IOCWDOG yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)70:IOCWDOG_CNTUC") { field(DESC, "IOCWDOG user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)70:IOCWDOG_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)70:IOCWDOG_CNTU") } record(longin, "$(CM,undefined)70:IOCWDOG_CNTU") { field(DESC, "IOCWDOG user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)70:IOCWDOG_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)70:IOCWDOG_CNTU PP") } record(seq, "$(CM,undefined)70:IOCWDOG_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)70:IOCWDOG_CNTT") field(LNK1, "$(CM,undefined)70:IOCWDOG_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)70:IOCWDOG_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)70:SSA_CNTC") { field(DESC, "SSA fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)70:SSA_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)70:SSA_CNTFO PP") } record(fanout, "$(CM,undefined)70:SSA_CNTFO") { field(DESC, "SSA fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)70:SSA_CNT") field(LNK2, "$(CM,undefined)70:SSA_CNTTC") field(LNK3, "$(CM,undefined)70:SSA_CNTUC") } record(calc, "$(CM,undefined)70:SSA_CNT") { field(DESC, "SSA total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)70:SSA_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)70:SSA_CNTTC") { field(DESC, "SSA today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)70:SSA_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)70:SSA_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)70:SSA_CNTT") { field(DESC, "SSA today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)70:SSA_CNTY") { field(DESC, "SSA yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)70:SSA_CNTUC") { field(DESC, "SSA user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)70:SSA_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)70:SSA_CNTU") } record(longin, "$(CM,undefined)70:SSA_CNTU") { field(DESC, "SSA user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)70:SSA_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)70:SSA_CNTU PP") } record(seq, "$(CM,undefined)70:SSA_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)70:SSA_CNTT") field(LNK1, "$(CM,undefined)70:SSA_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)70:SSA_CNTT PP") } record(fanout, "$(CM,undefined)80:INTLK_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(LNK1, "$(CM,undefined)80:STEPTEMP_CNTRO") field(LNK2, "$(CM,undefined)80:CPLRTEMP1_CNTRO") field(LNK3, "$(CM,undefined)80:CPLRTEMP2_CNTRO") field(LNK4, "$(CM,undefined)80:QUENCH_CNTRO") }#================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)80:STEPTEMP_CNTC") { field(DESC, "STEPTEMP fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)80:STEPTEMP_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)80:STEPTEMP_CNTFO PP") } record(fanout, "$(CM,undefined)80:STEPTEMP_CNTFO") { field(DESC, "STEPTEMP fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)80:STEPTEMP_CNT") field(LNK2, "$(CM,undefined)80:STEPTEMP_CNTTC") field(LNK3, "$(CM,undefined)80:STEPTEMP_CNTUC") } record(calc, "$(CM,undefined)80:STEPTEMP_CNT") { field(DESC, "STEPTEMP total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)80:STEPTEMP_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)80:STEPTEMP_CNTTC") { field(DESC, "STEPTEMP today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)80:STEPTEMP_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)80:STEPTEMP_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)80:STEPTEMP_CNTT") { field(DESC, "STEPTEMP today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)80:STEPTEMP_CNTY") { field(DESC, "STEPTEMP yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)80:STEPTEMP_CNTUC") { field(DESC, "STEPTEMP user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)80:STEPTEMP_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)80:STEPTEMP_CNTU") } record(longin, "$(CM,undefined)80:STEPTEMP_CNTU") { field(DESC, "STEPTEMP user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)80:STEPTEMP_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)80:STEPTEMP_CNTU PP") } record(seq, "$(CM,undefined)80:STEPTEMP_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)80:STEPTEMP_CNTT") field(LNK1, "$(CM,undefined)80:STEPTEMP_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)80:STEPTEMP_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)80:CPLRTEMP1_CNTC") { field(DESC, "CPLRTEMP1 fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)80:CPLRTEMP1_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)80:CPLRTEMP1_CNTFO PP") } record(fanout, "$(CM,undefined)80:CPLRTEMP1_CNTFO") { field(DESC, "CPLRTEMP1 fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)80:CPLRTEMP1_CNT") field(LNK2, "$(CM,undefined)80:CPLRTEMP1_CNTTC") field(LNK3, "$(CM,undefined)80:CPLRTEMP1_CNTUC") } record(calc, "$(CM,undefined)80:CPLRTEMP1_CNT") { field(DESC, "CPLRTEMP1 total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)80:CPLRTEMP1_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)80:CPLRTEMP1_CNTTC") { field(DESC, "CPLRTEMP1 today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)80:CPLRTEMP1_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)80:CPLRTEMP1_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)80:CPLRTEMP1_CNTT") { field(DESC, "CPLRTEMP1 today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)80:CPLRTEMP1_CNTY") { field(DESC, "CPLRTEMP1 yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)80:CPLRTEMP1_CNTUC") { field(DESC, "CPLRTEMP1 user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)80:CPLRTEMP1_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)80:CPLRTEMP1_CNTU") } record(longin, "$(CM,undefined)80:CPLRTEMP1_CNTU") { field(DESC, "CPLRTEMP1 user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)80:CPLRTEMP1_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)80:CPLRTEMP1_CNTU PP") } record(seq, "$(CM,undefined)80:CPLRTEMP1_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)80:CPLRTEMP1_CNTT") field(LNK1, "$(CM,undefined)80:CPLRTEMP1_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)80:CPLRTEMP1_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)80:CPLRTEMP2_CNTC") { field(DESC, "CPLRTEMP2 fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)80:CPLRTEMP2_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)80:CPLRTEMP2_CNTFO PP") } record(fanout, "$(CM,undefined)80:CPLRTEMP2_CNTFO") { field(DESC, "CPLRTEMP2 fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)80:CPLRTEMP2_CNT") field(LNK2, "$(CM,undefined)80:CPLRTEMP2_CNTTC") field(LNK3, "$(CM,undefined)80:CPLRTEMP2_CNTUC") } record(calc, "$(CM,undefined)80:CPLRTEMP2_CNT") { field(DESC, "CPLRTEMP2 total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)80:CPLRTEMP2_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)80:CPLRTEMP2_CNTTC") { field(DESC, "CPLRTEMP2 today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)80:CPLRTEMP2_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)80:CPLRTEMP2_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)80:CPLRTEMP2_CNTT") { field(DESC, "CPLRTEMP2 today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)80:CPLRTEMP2_CNTY") { field(DESC, "CPLRTEMP2 yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)80:CPLRTEMP2_CNTUC") { field(DESC, "CPLRTEMP2 user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)80:CPLRTEMP2_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)80:CPLRTEMP2_CNTU") } record(longin, "$(CM,undefined)80:CPLRTEMP2_CNTU") { field(DESC, "CPLRTEMP2 user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)80:CPLRTEMP2_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)80:CPLRTEMP2_CNTU PP") } record(seq, "$(CM,undefined)80:CPLRTEMP2_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)80:CPLRTEMP2_CNTT") field(LNK1, "$(CM,undefined)80:CPLRTEMP2_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)80:CPLRTEMP2_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)80:QUENCH_CNTC") { field(DESC, "QUENCH fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)80:QUENCH_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)80:QUENCH_CNTFO PP") } record(fanout, "$(CM,undefined)80:QUENCH_CNTFO") { field(DESC, "QUENCH fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)80:QUENCH_CNT") field(LNK2, "$(CM,undefined)80:QUENCH_CNTTC") field(LNK3, "$(CM,undefined)80:QUENCH_CNTUC") } record(calc, "$(CM,undefined)80:QUENCH_CNT") { field(DESC, "QUENCH total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)80:QUENCH_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)80:QUENCH_CNTTC") { field(DESC, "QUENCH today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)80:QUENCH_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)80:QUENCH_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)80:QUENCH_CNTT") { field(DESC, "QUENCH today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)80:QUENCH_CNTY") { field(DESC, "QUENCH yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)80:QUENCH_CNTUC") { field(DESC, "QUENCH user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)80:QUENCH_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)80:QUENCH_CNTU") } record(longin, "$(CM,undefined)80:QUENCH_CNTU") { field(DESC, "QUENCH user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)80:QUENCH_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)80:QUENCH_CNTU PP") } record(seq, "$(CM,undefined)80:QUENCH_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)80:QUENCH_CNTT") field(LNK1, "$(CM,undefined)80:QUENCH_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)80:QUENCH_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)80:RESINTLK_CNTC") { field(DESC, "RESINTLK fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)80:RESINTLK_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)80:RESINTLK_CNTFO PP") } record(fanout, "$(CM,undefined)80:RESINTLK_CNTFO") { field(DESC, "RESINTLK fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)80:RESINTLK_CNT") field(LNK2, "$(CM,undefined)80:RESINTLK_CNTTC") field(LNK3, "$(CM,undefined)80:RESINTLK_CNTUC") } record(calc, "$(CM,undefined)80:RESINTLK_CNT") { field(DESC, "RESINTLK total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)80:RESINTLK_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)80:RESINTLK_CNTTC") { field(DESC, "RESINTLK today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)80:RESINTLK_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)80:RESINTLK_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)80:RESINTLK_CNTT") { field(DESC, "RESINTLK today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)80:RESINTLK_CNTY") { field(DESC, "RESINTLK yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)80:RESINTLK_CNTUC") { field(DESC, "RESINTLK user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)80:RESINTLK_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)80:RESINTLK_CNTU") } record(longin, "$(CM,undefined)80:RESINTLK_CNTU") { field(DESC, "RESINTLK user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)80:RESINTLK_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)80:RESINTLK_CNTU PP") } record(seq, "$(CM,undefined)80:RESINTLK_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)80:RESINTLK_CNTT") field(LNK1, "$(CM,undefined)80:RESINTLK_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)80:RESINTLK_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)80:RESLINK_CNTC") { field(DESC, "RESLINK fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)80:RESLINK_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)80:RESLINK_CNTFO PP") } record(fanout, "$(CM,undefined)80:RESLINK_CNTFO") { field(DESC, "RESLINK fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)80:RESLINK_CNT") field(LNK2, "$(CM,undefined)80:RESLINK_CNTTC") field(LNK3, "$(CM,undefined)80:RESLINK_CNTUC") } record(calc, "$(CM,undefined)80:RESLINK_CNT") { field(DESC, "RESLINK total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)80:RESLINK_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)80:RESLINK_CNTTC") { field(DESC, "RESLINK today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)80:RESLINK_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)80:RESLINK_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)80:RESLINK_CNTT") { field(DESC, "RESLINK today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)80:RESLINK_CNTY") { field(DESC, "RESLINK yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)80:RESLINK_CNTUC") { field(DESC, "RESLINK user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)80:RESLINK_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)80:RESLINK_CNTU") } record(longin, "$(CM,undefined)80:RESLINK_CNTU") { field(DESC, "RESLINK user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)80:RESLINK_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)80:RESLINK_CNTU PP") } record(seq, "$(CM,undefined)80:RESLINK_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)80:RESLINK_CNTT") field(LNK1, "$(CM,undefined)80:RESLINK_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)80:RESLINK_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)80:PLL_CNTC") { field(DESC, "PLL fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)80:PLL_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)80:PLL_CNTFO PP") } record(fanout, "$(CM,undefined)80:PLL_CNTFO") { field(DESC, "PLL fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)80:PLL_CNT") field(LNK2, "$(CM,undefined)80:PLL_CNTTC") field(LNK3, "$(CM,undefined)80:PLL_CNTUC") } record(calc, "$(CM,undefined)80:PLL_CNT") { field(DESC, "PLL total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)80:PLL_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)80:PLL_CNTTC") { field(DESC, "PLL today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)80:PLL_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)80:PLL_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)80:PLL_CNTT") { field(DESC, "PLL today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)80:PLL_CNTY") { field(DESC, "PLL yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)80:PLL_CNTUC") { field(DESC, "PLL user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)80:PLL_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)80:PLL_CNTU") } record(longin, "$(CM,undefined)80:PLL_CNTU") { field(DESC, "PLL user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)80:PLL_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)80:PLL_CNTU PP") } record(seq, "$(CM,undefined)80:PLL_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)80:PLL_CNTT") field(LNK1, "$(CM,undefined)80:PLL_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)80:PLL_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)80:IOCWDOG_CNTC") { field(DESC, "IOCWDOG fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)80:IOCWDOG_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)80:IOCWDOG_CNTFO PP") } record(fanout, "$(CM,undefined)80:IOCWDOG_CNTFO") { field(DESC, "IOCWDOG fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)80:IOCWDOG_CNT") field(LNK2, "$(CM,undefined)80:IOCWDOG_CNTTC") field(LNK3, "$(CM,undefined)80:IOCWDOG_CNTUC") } record(calc, "$(CM,undefined)80:IOCWDOG_CNT") { field(DESC, "IOCWDOG total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)80:IOCWDOG_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)80:IOCWDOG_CNTTC") { field(DESC, "IOCWDOG today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)80:IOCWDOG_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)80:IOCWDOG_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)80:IOCWDOG_CNTT") { field(DESC, "IOCWDOG today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)80:IOCWDOG_CNTY") { field(DESC, "IOCWDOG yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)80:IOCWDOG_CNTUC") { field(DESC, "IOCWDOG user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)80:IOCWDOG_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)80:IOCWDOG_CNTU") } record(longin, "$(CM,undefined)80:IOCWDOG_CNTU") { field(DESC, "IOCWDOG user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)80:IOCWDOG_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)80:IOCWDOG_CNTU PP") } record(seq, "$(CM,undefined)80:IOCWDOG_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)80:IOCWDOG_CNTT") field(LNK1, "$(CM,undefined)80:IOCWDOG_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)80:IOCWDOG_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)80:SSA_CNTC") { field(DESC, "SSA fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)80:SSA_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)80:SSA_CNTFO PP") } record(fanout, "$(CM,undefined)80:SSA_CNTFO") { field(DESC, "SSA fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)80:SSA_CNT") field(LNK2, "$(CM,undefined)80:SSA_CNTTC") field(LNK3, "$(CM,undefined)80:SSA_CNTUC") } record(calc, "$(CM,undefined)80:SSA_CNT") { field(DESC, "SSA total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)80:SSA_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)80:SSA_CNTTC") { field(DESC, "SSA today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)80:SSA_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)80:SSA_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)80:SSA_CNTT") { field(DESC, "SSA today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)80:SSA_CNTY") { field(DESC, "SSA yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)80:SSA_CNTUC") { field(DESC, "SSA user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)80:SSA_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)80:SSA_CNTU") } record(longin, "$(CM,undefined)80:SSA_CNTU") { field(DESC, "SSA user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)80:SSA_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)80:SSA_CNTU PP") } record(seq, "$(CM,undefined)80:SSA_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)80:SSA_CNTT") field(LNK1, "$(CM,undefined)80:SSA_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)80:SSA_CNTT PP") } record(fanout, "$(CM,recursive)00:RESA:INTLK_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(LNK1, "$(CM,recursive)10:CPLRVACA_CNTRO") field(LNK2, "$(CM,recursive)00:BMLNVACA_CNTRO") field(LNK3, "$(CM,recursive)00:CRYOSUMA_CNTRO") } record(fanout, "$(CM,recursive)00:RESB:INTLK_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(LNK1, "$(CM,recursive)10:CPLRVACB_CNTRO") field(LNK2, "$(CM,recursive)00:BMLNVACB_CNTRO") field(LNK3, "$(CM,recursive)00:CRYOSUMB_CNTRO") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)10:CPLRVACA_CNTC") { field(DESC, "CPLRVACA fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)10:CPLRVACA_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)10:CPLRVACA_CNTFO PP") } record(fanout, "$(CM,undefined)10:CPLRVACA_CNTFO") { field(DESC, "CPLRVACA fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)10:CPLRVACA_CNT") field(LNK2, "$(CM,undefined)10:CPLRVACA_CNTTC") field(LNK3, "$(CM,undefined)10:CPLRVACA_CNTUC") } record(calc, "$(CM,undefined)10:CPLRVACA_CNT") { field(DESC, "CPLRVACA total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:CPLRVACA_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)10:CPLRVACA_CNTTC") { field(DESC, "CPLRVACA today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:CPLRVACA_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)10:CPLRVACA_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)10:CPLRVACA_CNTT") { field(DESC, "CPLRVACA today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)10:CPLRVACA_CNTY") { field(DESC, "CPLRVACA yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)10:CPLRVACA_CNTUC") { field(DESC, "CPLRVACA user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:CPLRVACA_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)10:CPLRVACA_CNTU") } record(longin, "$(CM,undefined)10:CPLRVACA_CNTU") { field(DESC, "CPLRVACA user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)10:CPLRVACA_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)10:CPLRVACA_CNTU PP") } record(seq, "$(CM,undefined)10:CPLRVACA_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)10:CPLRVACA_CNTT") field(LNK1, "$(CM,undefined)10:CPLRVACA_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)10:CPLRVACA_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)00:BMLNVACA_CNTC") { field(DESC, "BMLNVACA fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)00:BMLNVACA_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)00:BMLNVACA_CNTFO PP") } record(fanout, "$(CM,undefined)00:BMLNVACA_CNTFO") { field(DESC, "BMLNVACA fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)00:BMLNVACA_CNT") field(LNK2, "$(CM,undefined)00:BMLNVACA_CNTTC") field(LNK3, "$(CM,undefined)00:BMLNVACA_CNTUC") } record(calc, "$(CM,undefined)00:BMLNVACA_CNT") { field(DESC, "BMLNVACA total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)00:BMLNVACA_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)00:BMLNVACA_CNTTC") { field(DESC, "BMLNVACA today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)00:BMLNVACA_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)00:BMLNVACA_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)00:BMLNVACA_CNTT") { field(DESC, "BMLNVACA today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)00:BMLNVACA_CNTY") { field(DESC, "BMLNVACA yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)00:BMLNVACA_CNTUC") { field(DESC, "BMLNVACA user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)00:BMLNVACA_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)00:BMLNVACA_CNTU") } record(longin, "$(CM,undefined)00:BMLNVACA_CNTU") { field(DESC, "BMLNVACA user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)00:BMLNVACA_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)00:BMLNVACA_CNTU PP") } record(seq, "$(CM,undefined)00:BMLNVACA_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)00:BMLNVACA_CNTT") field(LNK1, "$(CM,undefined)00:BMLNVACA_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)00:BMLNVACA_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)00:CRYOSUMA_CNTC") { field(DESC, "CRYOSUMA fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)00:CRYOSUMA_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)00:CRYOSUMA_CNTFO PP") } record(fanout, "$(CM,undefined)00:CRYOSUMA_CNTFO") { field(DESC, "CRYOSUMA fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)00:CRYOSUMA_CNT") field(LNK2, "$(CM,undefined)00:CRYOSUMA_CNTTC") field(LNK3, "$(CM,undefined)00:CRYOSUMA_CNTUC") } record(calc, "$(CM,undefined)00:CRYOSUMA_CNT") { field(DESC, "CRYOSUMA total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)00:CRYOSUMA_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)00:CRYOSUMA_CNTTC") { field(DESC, "CRYOSUMA today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)00:CRYOSUMA_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)00:CRYOSUMA_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)00:CRYOSUMA_CNTT") { field(DESC, "CRYOSUMA today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)00:CRYOSUMA_CNTY") { field(DESC, "CRYOSUMA yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)00:CRYOSUMA_CNTUC") { field(DESC, "CRYOSUMA user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)00:CRYOSUMA_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)00:CRYOSUMA_CNTU") } record(longin, "$(CM,undefined)00:CRYOSUMA_CNTU") { field(DESC, "CRYOSUMA user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)00:CRYOSUMA_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)00:CRYOSUMA_CNTU PP") } record(seq, "$(CM,undefined)00:CRYOSUMA_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)00:CRYOSUMA_CNTT") field(LNK1, "$(CM,undefined)00:CRYOSUMA_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)00:CRYOSUMA_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)10:CPLRVACB_CNTC") { field(DESC, "CPLRVACB fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)10:CPLRVACB_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)10:CPLRVACB_CNTFO PP") } record(fanout, "$(CM,undefined)10:CPLRVACB_CNTFO") { field(DESC, "CPLRVACB fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)10:CPLRVACB_CNT") field(LNK2, "$(CM,undefined)10:CPLRVACB_CNTTC") field(LNK3, "$(CM,undefined)10:CPLRVACB_CNTUC") } record(calc, "$(CM,undefined)10:CPLRVACB_CNT") { field(DESC, "CPLRVACB total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:CPLRVACB_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)10:CPLRVACB_CNTTC") { field(DESC, "CPLRVACB today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:CPLRVACB_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)10:CPLRVACB_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)10:CPLRVACB_CNTT") { field(DESC, "CPLRVACB today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)10:CPLRVACB_CNTY") { field(DESC, "CPLRVACB yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)10:CPLRVACB_CNTUC") { field(DESC, "CPLRVACB user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)10:CPLRVACB_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)10:CPLRVACB_CNTU") } record(longin, "$(CM,undefined)10:CPLRVACB_CNTU") { field(DESC, "CPLRVACB user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)10:CPLRVACB_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)10:CPLRVACB_CNTU PP") } record(seq, "$(CM,undefined)10:CPLRVACB_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)10:CPLRVACB_CNTT") field(LNK1, "$(CM,undefined)10:CPLRVACB_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)10:CPLRVACB_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)00:BMLNVACB_CNTC") { field(DESC, "BMLNVACB fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)00:BMLNVACB_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)00:BMLNVACB_CNTFO PP") } record(fanout, "$(CM,undefined)00:BMLNVACB_CNTFO") { field(DESC, "BMLNVACB fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)00:BMLNVACB_CNT") field(LNK2, "$(CM,undefined)00:BMLNVACB_CNTTC") field(LNK3, "$(CM,undefined)00:BMLNVACB_CNTUC") } record(calc, "$(CM,undefined)00:BMLNVACB_CNT") { field(DESC, "BMLNVACB total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)00:BMLNVACB_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)00:BMLNVACB_CNTTC") { field(DESC, "BMLNVACB today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)00:BMLNVACB_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)00:BMLNVACB_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)00:BMLNVACB_CNTT") { field(DESC, "BMLNVACB today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)00:BMLNVACB_CNTY") { field(DESC, "BMLNVACB yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)00:BMLNVACB_CNTUC") { field(DESC, "BMLNVACB user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)00:BMLNVACB_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)00:BMLNVACB_CNTU") } record(longin, "$(CM,undefined)00:BMLNVACB_CNTU") { field(DESC, "BMLNVACB user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)00:BMLNVACB_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)00:BMLNVACB_CNTU PP") } record(seq, "$(CM,undefined)00:BMLNVACB_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)00:BMLNVACB_CNTT") field(LNK1, "$(CM,undefined)00:BMLNVACB_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)00:BMLNVACB_CNTT PP") } #================================== #---------------------------------- # intlk_count.template: # # Interlock fault counters #---------------------------------- #================================== #================================== # #================================== record(calcout, "$(CM,undefined)00:CRYOSUMB_CNTC") { field(DESC, "CRYOSUMB fault count") field(CALC, "A=B?1:0") field(INPA, "$(CM,undefined)00:CRYOSUMB_FLT CP") field(INPB, "1") field(OOPT, "When Non-zero") field(PREC, "0") field(OUT, "$(CM,undefined)00:CRYOSUMB_CNTFO PP") } record(fanout, "$(CM,undefined)00:CRYOSUMB_CNTFO") { field(DESC, "CRYOSUMB fault count") field(SELM, "All") field(LNK1, "$(CM,undefined)00:CRYOSUMB_CNT") field(LNK2, "$(CM,undefined)00:CRYOSUMB_CNTTC") field(LNK3, "$(CM,undefined)00:CRYOSUMB_CNTUC") } record(calc, "$(CM,undefined)00:CRYOSUMB_CNT") { field(DESC, "CRYOSUMB total fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)00:CRYOSUMB_CNT") field(PINI, "YES") field(PREC, "0") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)00:CRYOSUMB_CNTTC") { field(DESC, "CRYOSUMB today fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)00:CRYOSUMB_CNTT") field(OOPT, "Every Time") field(OUT, "$(CM,undefined)00:CRYOSUMB_CNTT") field(PREC, "0") } record(longin, "$(CM,undefined)00:CRYOSUMB_CNTT") { field(DESC, "CRYOSUMB today fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(longin, "$(CM,undefined)00:CRYOSUMB_CNTY") { field(DESC, "CRYOSUMB yesterday fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(calcout, "$(CM,undefined)00:CRYOSUMB_CNTUC") { field(DESC, "CRYOSUMB user fault count") field(CALC, "A+1") field(INPA, "$(CM,undefined)00:CRYOSUMB_CNTU") field(OOPT, "Every Time") field(PREC, "0") field(OUT, "$(CM,undefined)00:CRYOSUMB_CNTU") } record(longin, "$(CM,undefined)00:CRYOSUMB_CNTU") { field(DESC, "CRYOSUMB user fault count") field(PINI, "YES") info(autosaveFields,"VAL") } record(bo, "$(CM,undefined)00:CRYOSUMB_CNTUCLR") { field(DESC, "Clear user fault count") field(OMSL, "supervisory") field(ZNAM, "Clear") field(ONAM, "Clear") field(OMSL, "closed_loop") field(DOL, "0") field(OUT, "$(CM,undefined)00:CRYOSUMB_CNTU PP") } record(seq, "$(CM,undefined)00:CRYOSUMB_CNTRO") { field(DESC, "Roll over interlock count") field(SELM, "All") field(DOL1, "$(CM,undefined)00:CRYOSUMB_CNTT") field(LNK1, "$(CM,undefined)00:CRYOSUMB_CNTY PP") field(DOL2, "0") field(LNK2, "$(CM,undefined)00:CRYOSUMB_CNTT PP") }