# Abs:  LCLS Trigger records for Beam Switch Yard PM01
#
# Name: IOC-BSY0-PM01trig.substitutions
#
# Associated Display: evnt_bsy0_profileMon.edl
#
# Rem:  Instantiate one line for every trigger channel including ones not used. 
# There should be 3 lines for each PMC EVR without a transition module for the 3 front panel triggers.
# There should be 4 lines for each VME EVR without a transition module for the 4 front panel triggers.
# There should be 14 additional lines for each PMC or VME EVR that has a transition module.
# 
# Macros:
#	DEV	Name of the device being triggered up to and including the 3rd colon.  
#		Add a qualifying name after the 3rd colon, if necessary, to keep name unique.
#		If the trigger channel is not used, use "TRIG:<loca>:<unit>:" 
#		where <loca> is the location of your IOC and <unit> is xxyy, where xx = subsystem
#		and yy is 01, 02, etc.
#	DESC	Description.  Include MAD name in the description if applicable. 
#	POL	Initial polarity.  0 = normal, 1 = inverted.  Normally restored on reboot.
#	WID	Initial pulse width in nsec.                  Normally restored on reboot.
#	DES	Initial desired delay in nsec.                Normally restored on reboot.
#		Note: the DES value is with respect to IOC TREF (reference time) which is set in 
#		<ioc>pattern.substitution:
#		EVR delay = TREF + TDES - event code delay from the fiducial		
#	CTL	Initial state.     0 = disabled, 1 = enabled. Normally restored on reboot.
#	TEC	Trigger event code name.  To find all available event codes:
#		lclshome -> Event -> Events... (in the EVG IOC box).
#		This display brings up all the event that are beam-dependent.
#	        For events that are beam-independent (constant or standby), select 
#		"Time Slot 1 to 6 Event Codes" and find the event that you want to trigger your device.  
#		Use the middle-mouse-button in the Event Code column to find the PV name.  TEC is the 
#		part of the name between "IOC:IN20:EV01:" and "EVNT.A".
#		Also check sharepoint spreadsheet:
#		Controls -> Timing -> timingEventCodes
#	LOCA	Location of the EVR that triggers the device.  It is the second part of the 
#		EVR:<loca>:<unit>:CTRL record instantiated in <ioc>evr.db.
#	UNIT	Unit number of the EVR instantiated in <ioc>evr.db.
#	IOC	Name of IOC that contains the EVR, not including the 3rd colon.
#	DRVL and DRVH  Drive low and high limits for the trigger delay in nsec.
#	TCTL	Field in EVR:<loca>:<unit>:CTRL that enables/disables the trigger:
#		DGxE, where x=0 to 3   for front panel triggers.
#		OTPx, where x=0 to 0xD for transition module triggers.
#	TPOL	Field in EVR:<loca>:<unit>:CTRL for polarity: 
#		DGxP, where x=0 to 3   for front panel triggers.
#		OTxP, where x=0 to 0xD for transition module triggers.
#	TWID	Field in EVR:<loca>:<unit>:CTRL for pulse width: 
#		DGxW, where x=0 to 3   for front panel triggers.
#		OTxW, where x=0 to 0xD for transition module triggers.
#	TDES	Field in EVR:<loca>:<unit>:CTRL for delay: 
#		DGxD, where x=0 to 3   for front panel triggers.
#		OTxD, where x=0 to 0xD for transition module triggers.
#==============================================================================
# 
file evrDevTrig.db 
{
#           Device	    , Description    ,polarity,width,delay,event , EVR  , EVR,  IOC 
#			                                          code   ,location,unit
  pattern { DEV             ,  ESC           ,POL, WID, DES , TEC        , LOCA , UNIT, IOC          ,  DRVL  ,  DRVH   , TCTL , TPOL, TWID, TDES, CTL}
	  { PROF:BSYN:55:   , PR55           , 1 ,20000000,10, LCLSPROF  , BSY0 , PM01, IOC:BSY0:PM01, -2.8E06, 2.8E06  , DG0E , DG0P, DG0W, DG0D, 0  }
	  { PROF:BSY0:45:   , PR45           , 1 ,20000000,10, LCLSPROF  , BSY0 , PM01, IOC:BSY0:PM01, -2.8E06, 2.8E06  , DG1E , DG1P, DG1W, DG1D, 0  }
	  { TRIG:BSY0:MG01: , "Spare Trig 1" , 1 ,20000000,10, LCLSPROF  , BSY0 , PM01, IOC:BSY0:PM01, -2.8E06, 2.8E06  , DG2E , DG2P, DG2W, DG2D, 0  }
}

# End of file