#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi7") {
  field(DESC, "Port CLTS_RDA bit 7")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 7, 1, 1)")
  field(ZNAM, "Not_Enabled")
  field(ONAM, "Enabled")
  field(FLNK, "PPS:CLTS:1:HW_ENABLE_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:1:HW_ENABLE_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi7 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:1:HW_ENABLE_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:1:HW_ENABLE_A") {
  field(DESC, "RT-IN HW Enable")
  field(ZNAM, "Not_Enabled")
  field(ONAM, "Enabled")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb7",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb7")
#! Field("PLC:CLTS:PP13:CLTS_RDAb7.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb7.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb7.FLNK","PPS:CLTS:1:HW_ENABLE_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb7.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb7.VAL")
#! Record("PPS:CLTS:1:HW_ENABLE_A_calc",260,18,0,1,"PPS:CLTS:1:HW_ENABLE_A_calc")
#! Field("PPS:CLTS:1:HW_ENABLE_A_calc.INPA",16777215,0,"PPS:CLTS:1:HW_ENABLE_A_calc.INPA")
#! Link("PPS:CLTS:1:HW_ENABLE_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb7.VAL")
#! Field("PPS:CLTS:1:HW_ENABLE_A_calc.INPB",16777215,1,"PPS:CLTS:1:HW_ENABLE_A_calc.INPB")
#! Field("PPS:CLTS:1:HW_ENABLE_A_calc.OUT",16777215,1,"PPS:CLTS:1:HW_ENABLE_A_calc.OUT")
#! Link("PPS:CLTS:1:HW_ENABLE_A_calc.OUT","PPS:CLTS:1:HW_ENABLE_A.VAL")
#! Record("PPS:CLTS:1:HW_ENABLE_A",500,20,0,0,"PPS:CLTS:1:HW_ENABLE_A")
#! Field("PPS:CLTS:1:HW_ENABLE_A.VAL",16777215,1,"PPS:CLTS:1:HW_ENABLE_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi6") {
  field(DESC, "Port CLTS_RDA bit 6")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 6, 1, 1)")
  field(ZNAM, "NOT_OFF")
  field(ONAM, "OFF")
  field(FLNK, "PPS:CLTS:3:KICK_OFF_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:KICK_OFF_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi6 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:KICK_OFF_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:KICK_OFF_A") {
  field(DESC, "RT-IN CL-Kicker OFF status")
  field(ZNAM, "NOT_OFF")
  field(ONAM, "OFF")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb6",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb6")
#! Field("PLC:CLTS:PP13:CLTS_RDAb6.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb6.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb6.FLNK","PPS:CLTS:3:KICK_OFF_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb6.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb6.VAL")
#! Record("PPS:CLTS:3:KICK_OFF_A_calc",260,18,0,1,"PPS:CLTS:3:KICK_OFF_A_calc")
#! Field("PPS:CLTS:3:KICK_OFF_A_calc.INPA",16777215,0,"PPS:CLTS:3:KICK_OFF_A_calc.INPA")
#! Link("PPS:CLTS:3:KICK_OFF_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb6.VAL")
#! Field("PPS:CLTS:3:KICK_OFF_A_calc.INPB",16777215,1,"PPS:CLTS:3:KICK_OFF_A_calc.INPB")
#! Field("PPS:CLTS:3:KICK_OFF_A_calc.OUT",16777215,1,"PPS:CLTS:3:KICK_OFF_A_calc.OUT")
#! Link("PPS:CLTS:3:KICK_OFF_A_calc.OUT","PPS:CLTS:3:KICK_OFF_A.VAL")
#! Record("PPS:CLTS:3:KICK_OFF_A",500,20,0,0,"PPS:CLTS:3:KICK_OFF_A")
#! Field("PPS:CLTS:3:KICK_OFF_A.VAL",16777215,1,"PPS:CLTS:3:KICK_OFF_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi5") {
  field(DESC, "Port CLTS_RDA bit 5")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 5, 1, 1)")
  field(ZNAM, "NOT_OFF")
  field(ONAM, "OFF")
  field(FLNK, "PPS:CLTS:3:DCBEND_OFF_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:DCBEND_OFF_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi5 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:DCBEND_OFF_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:DCBEND_OFF_A") {
  field(DESC, "RT-IN CL-DC OFF status")
  field(ZNAM, "NOT_OFF")
  field(ONAM, "OFF")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb5",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb5")
#! Field("PLC:CLTS:PP13:CLTS_RDAb5.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb5.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb5.FLNK","PPS:CLTS:3:DCBEND_OFF_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb5.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb5.VAL")
#! Record("PPS:CLTS:3:DCBEND_OFF_A_calc",260,18,0,1,"PPS:CLTS:3:DCBEND_OFF_A_calc")
#! Field("PPS:CLTS:3:DCBEND_OFF_A_calc.INPA",16777215,0,"PPS:CLTS:3:DCBEND_OFF_A_calc.INPA")
#! Link("PPS:CLTS:3:DCBEND_OFF_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb5.VAL")
#! Field("PPS:CLTS:3:DCBEND_OFF_A_calc.INPB",16777215,1,"PPS:CLTS:3:DCBEND_OFF_A_calc.INPB")
#! Field("PPS:CLTS:3:DCBEND_OFF_A_calc.OUT",16777215,1,"PPS:CLTS:3:DCBEND_OFF_A_calc.OUT")
#! Link("PPS:CLTS:3:DCBEND_OFF_A_calc.OUT","PPS:CLTS:3:DCBEND_OFF_A.VAL")
#! Record("PPS:CLTS:3:DCBEND_OFF_A",500,20,0,0,"PPS:CLTS:3:DCBEND_OFF_A")
#! Field("PPS:CLTS:3:DCBEND_OFF_A.VAL",16777215,1,"PPS:CLTS:3:DCBEND_OFF_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi4") {
  field(DESC, "Port CLTS_RDA bit 4")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 4, 1, 1)")
  field(ZNAM, "NOT_OFF")
  field(ONAM, "OFF")
  field(FLNK, "PPS:CLTS:3:SEP_OFF_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:SEP_OFF_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi4 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:SEP_OFF_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:SEP_OFF_A") {
  field(DESC, "RT-IN CL-Septum OFF status")
  field(ZNAM, "NOT_OFF")
  field(ONAM, "OFF")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb4",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb4")
#! Field("PLC:CLTS:PP13:CLTS_RDAb4.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb4.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb4.FLNK","PPS:CLTS:3:SEP_OFF_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb4.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb4.VAL")
#! Record("PPS:CLTS:3:SEP_OFF_A_calc",260,18,0,1,"PPS:CLTS:3:SEP_OFF_A_calc")
#! Field("PPS:CLTS:3:SEP_OFF_A_calc.INPA",16777215,0,"PPS:CLTS:3:SEP_OFF_A_calc.INPA")
#! Link("PPS:CLTS:3:SEP_OFF_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb4.VAL")
#! Field("PPS:CLTS:3:SEP_OFF_A_calc.INPB",16777215,1,"PPS:CLTS:3:SEP_OFF_A_calc.INPB")
#! Field("PPS:CLTS:3:SEP_OFF_A_calc.OUT",16777215,1,"PPS:CLTS:3:SEP_OFF_A_calc.OUT")
#! Link("PPS:CLTS:3:SEP_OFF_A_calc.OUT","PPS:CLTS:3:SEP_OFF_A.VAL")
#! Record("PPS:CLTS:3:SEP_OFF_A",500,20,0,0,"PPS:CLTS:3:SEP_OFF_A")
#! Field("PPS:CLTS:3:SEP_OFF_A.VAL",16777215,1,"PPS:CLTS:3:SEP_OFF_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi3") {
  field(DESC, "Port CLTS_RDA bit 3")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 3, 1, 1)")
  field(ZNAM, "NOT_OFF")
  field(ONAM, "OFF")
  field(FLNK, "PPS:CLTS:3:MERGE_OFF_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:MERGE_OFF_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi3 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:MERGE_OFF_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:MERGE_OFF_A") {
  field(DESC, "RT-IN CL-Merge OFF status")
  field(ZNAM, "NOT_OFF")
  field(ONAM, "OFF")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb3",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb3")
#! Field("PLC:CLTS:PP13:CLTS_RDAb3.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb3.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb3.FLNK","PPS:CLTS:3:MERGE_OFF_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb3.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb3.VAL")
#! Record("PPS:CLTS:3:MERGE_OFF_A_calc",260,18,0,1,"PPS:CLTS:3:MERGE_OFF_A_calc")
#! Field("PPS:CLTS:3:MERGE_OFF_A_calc.INPA",16777215,0,"PPS:CLTS:3:MERGE_OFF_A_calc.INPA")
#! Link("PPS:CLTS:3:MERGE_OFF_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb3.VAL")
#! Field("PPS:CLTS:3:MERGE_OFF_A_calc.INPB",16777215,1,"PPS:CLTS:3:MERGE_OFF_A_calc.INPB")
#! Field("PPS:CLTS:3:MERGE_OFF_A_calc.OUT",16777215,1,"PPS:CLTS:3:MERGE_OFF_A_calc.OUT")
#! Link("PPS:CLTS:3:MERGE_OFF_A_calc.OUT","PPS:CLTS:3:MERGE_OFF_A.VAL")
#! Record("PPS:CLTS:3:MERGE_OFF_A",500,20,0,0,"PPS:CLTS:3:MERGE_OFF_A")
#! Field("PPS:CLTS:3:MERGE_OFF_A.VAL",16777215,1,"PPS:CLTS:3:MERGE_OFF_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi2") {
  field(DESC, "Port CLTS_RDA bit 2")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 2, 1, 1)")
  field(ZNAM, "NOT_OFF")
  field(ONAM, "OFF")
  field(FLNK, "PPS:LI28:3:HXR:KICKSEP_OFF_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:LI28:3:HXR:KICKSEP_OFF_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi2 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:LI28:3:HXR:KICKSEP_OFF_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:LI28:3:HXR:KICKSEP_OFF_A") {
  field(DESC, "RT-IN HX-KickerSepMrg Summary OFF")
  field(ZNAM, "NOT_OFF")
  field(ONAM, "OFF")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb2",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb2")
#! Field("PLC:CLTS:PP13:CLTS_RDAb2.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb2.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb2.FLNK","PPS:LI28:3:HXR:KICKSEP_OFF_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb2.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb2.VAL")
#! Record("PPS:LI28:3:HXR:KICKSEP_OFF_A_calc",260,18,0,1,"PPS:LI28:3:HXR:KICKSEP_OFF_A_calc")
#! Field("PPS:LI28:3:HXR:KICKSEP_OFF_A_calc.INPA",16777215,0,"PPS:LI28:3:HXR:KICKSEP_OFF_A_calc.INPA")
#! Link("PPS:LI28:3:HXR:KICKSEP_OFF_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb2.VAL")
#! Field("PPS:LI28:3:HXR:KICKSEP_OFF_A_calc.INPB",16777215,1,"PPS:LI28:3:HXR:KICKSEP_OFF_A_calc.INPB")
#! Field("PPS:LI28:3:HXR:KICKSEP_OFF_A_calc.OUT",16777215,1,"PPS:LI28:3:HXR:KICKSEP_OFF_A_calc.OUT")
#! Link("PPS:LI28:3:HXR:KICKSEP_OFF_A_calc.OUT","PPS:LI28:3:HXR:KICKSEP_OFF_A.VAL")
#! Record("PPS:LI28:3:HXR:KICKSEP_OFF_A",500,20,0,0,"PPS:LI28:3:HXR:KICKSEP_OFF_A")
#! Field("PPS:LI28:3:HXR:KICKSEP_OFF_A.VAL",16777215,1,"PPS:LI28:3:HXR:KICKSEP_OFF_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi1") {
  field(DESC, "Port CLTS_RDA bit 1")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 1, 1, 1)")
  field(ZNAM, "NOT_OFF")
  field(ONAM, "OFF")
  field(FLNK, "PPS:LI30:3:SXR:KICKSEP_OFF_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:LI30:3:SXR:KICKSEP_OFF_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi1 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:LI30:3:SXR:KICKSEP_OFF_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:LI30:3:SXR:KICKSEP_OFF_A") {
  field(DESC, "RT-IN SX-KickerSepMrg Summary OFF")
  field(ZNAM, "NOT_OFF")
  field(ONAM, "OFF")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb1",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb1")
#! Field("PLC:CLTS:PP13:CLTS_RDAb1.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb1.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb1.FLNK","PPS:LI30:3:SXR:KICKSEP_OFF_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb1.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb1.VAL")
#! Record("PPS:LI30:3:SXR:KICKSEP_OFF_A_calc",260,18,0,1,"PPS:LI30:3:SXR:KICKSEP_OFF_A_calc")
#! Field("PPS:LI30:3:SXR:KICKSEP_OFF_A_calc.INPA",16777215,0,"PPS:LI30:3:SXR:KICKSEP_OFF_A_calc.INPA")
#! Link("PPS:LI30:3:SXR:KICKSEP_OFF_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb1.VAL")
#! Field("PPS:LI30:3:SXR:KICKSEP_OFF_A_calc.INPB",16777215,1,"PPS:LI30:3:SXR:KICKSEP_OFF_A_calc.INPB")
#! Field("PPS:LI30:3:SXR:KICKSEP_OFF_A_calc.OUT",16777215,1,"PPS:LI30:3:SXR:KICKSEP_OFF_A_calc.OUT")
#! Link("PPS:LI30:3:SXR:KICKSEP_OFF_A_calc.OUT","PPS:LI30:3:SXR:KICKSEP_OFF_A.VAL")
#! Record("PPS:LI30:3:SXR:KICKSEP_OFF_A",500,20,0,0,"PPS:LI30:3:SXR:KICKSEP_OFF_A")
#! Field("PPS:LI30:3:SXR:KICKSEP_OFF_A.VAL",16777215,1,"PPS:LI30:3:SXR:KICKSEP_OFF_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi0") {
  field(DESC, "Port CLTS_RDA bit 0")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 0, 1, 1)")
  field(ZNAM, "NOT_IN")
  field(ONAM, "IN")
  field(FLNK, "STPR:CLTS:585:3:IN_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "STPR:CLTS:585:3:IN_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi0 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "STPR:CLTS:585:3:IN_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "STPR:CLTS:585:3:IN_A") {
  field(DESC, "RT-IN STP-CLTS IN")
  field(ZNAM, "NOT_IN")
  field(ONAM, "IN")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb0",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb0")
#! Field("PLC:CLTS:PP13:CLTS_RDAb0.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb0.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb0.FLNK","STPR:CLTS:585:3:IN_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb0.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb0.VAL")
#! Record("STPR:CLTS:585:3:IN_A_calc",260,18,0,1,"STPR:CLTS:585:3:IN_A_calc")
#! Field("STPR:CLTS:585:3:IN_A_calc.INPA",16777215,0,"STPR:CLTS:585:3:IN_A_calc.INPA")
#! Link("STPR:CLTS:585:3:IN_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb0.VAL")
#! Field("STPR:CLTS:585:3:IN_A_calc.INPB",16777215,1,"STPR:CLTS:585:3:IN_A_calc.INPB")
#! Field("STPR:CLTS:585:3:IN_A_calc.OUT",16777215,1,"STPR:CLTS:585:3:IN_A_calc.OUT")
#! Link("STPR:CLTS:585:3:IN_A_calc.OUT","STPR:CLTS:585:3:IN_A.VAL")
#! Record("STPR:CLTS:585:3:IN_A",500,20,0,0,"STPR:CLTS:585:3:IN_A")
#! Field("STPR:CLTS:585:3:IN_A.VAL",16777215,1,"STPR:CLTS:585:3:IN_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi15") {
  field(DESC, "Port CLTS_RDA bit 15")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 15, 1, 1)")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(FLNK, "STPR:BSYS:3:ST34_OUT_SUM_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "STPR:BSYS:3:ST34_OUT_SUM_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi15 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "STPR:BSYS:3:ST34_OUT_SUM_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "STPR:BSYS:3:ST34_OUT_SUM_A") {
  field(DESC, "RT-IN STP-34 Summary OUT")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb15",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb15")
#! Field("PLC:CLTS:PP13:CLTS_RDAb15.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb15.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb15.FLNK","STPR:BSYS:3:ST34_OUT_SUM_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb15.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb15.VAL")
#! Record("STPR:BSYS:3:ST34_OUT_SUM_A_calc",260,18,0,1,"STPR:BSYS:3:ST34_OUT_SUM_A_calc")
#! Field("STPR:BSYS:3:ST34_OUT_SUM_A_calc.INPA",16777215,0,"STPR:BSYS:3:ST34_OUT_SUM_A_calc.INPA")
#! Link("STPR:BSYS:3:ST34_OUT_SUM_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb15.VAL")
#! Field("STPR:BSYS:3:ST34_OUT_SUM_A_calc.INPB",16777215,1,"STPR:BSYS:3:ST34_OUT_SUM_A_calc.INPB")
#! Field("STPR:BSYS:3:ST34_OUT_SUM_A_calc.OUT",16777215,1,"STPR:BSYS:3:ST34_OUT_SUM_A_calc.OUT")
#! Link("STPR:BSYS:3:ST34_OUT_SUM_A_calc.OUT","STPR:BSYS:3:ST34_OUT_SUM_A.VAL")
#! Record("STPR:BSYS:3:ST34_OUT_SUM_A",500,20,0,0,"STPR:BSYS:3:ST34_OUT_SUM_A")
#! Field("STPR:BSYS:3:ST34_OUT_SUM_A.VAL",16777215,1,"STPR:BSYS:3:ST34_OUT_SUM_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi14") {
  field(DESC, "Port CLTS_RDA bit 14")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 14, 1, 1)")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(FLNK, "PPS:CLTS:1:HRTBT_INP_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:1:HRTBT_INP_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi14 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:1:HRTBT_INP_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:1:HRTBT_INP_A") {
  field(DESC, "RT-IN Heartbeat IN from opposite chain")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb14",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb14")
#! Field("PLC:CLTS:PP13:CLTS_RDAb14.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb14.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb14.FLNK","PPS:CLTS:1:HRTBT_INP_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb14.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb14.VAL")
#! Record("PPS:CLTS:1:HRTBT_INP_A_calc",260,18,0,1,"PPS:CLTS:1:HRTBT_INP_A_calc")
#! Field("PPS:CLTS:1:HRTBT_INP_A_calc.INPA",16777215,0,"PPS:CLTS:1:HRTBT_INP_A_calc.INPA")
#! Link("PPS:CLTS:1:HRTBT_INP_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb14.VAL")
#! Field("PPS:CLTS:1:HRTBT_INP_A_calc.INPB",16777215,1,"PPS:CLTS:1:HRTBT_INP_A_calc.INPB")
#! Field("PPS:CLTS:1:HRTBT_INP_A_calc.OUT",16777215,1,"PPS:CLTS:1:HRTBT_INP_A_calc.OUT")
#! Link("PPS:CLTS:1:HRTBT_INP_A_calc.OUT","PPS:CLTS:1:HRTBT_INP_A.VAL")
#! Record("PPS:CLTS:1:HRTBT_INP_A",500,20,0,0,"PPS:CLTS:1:HRTBT_INP_A")
#! Field("PPS:CLTS:1:HRTBT_INP_A.VAL",16777215,1,"PPS:CLTS:1:HRTBT_INP_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi13") {
  field(DESC, "Port CLTS_RDA bit 13")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 13, 1, 1)")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(FLNK, "PPS:CLTS:1:ACR_ENABLE_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:1:ACR_ENABLE_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi13 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:1:ACR_ENABLE_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:1:ACR_ENABLE_A") {
  field(DESC, "RT-IN CLTS Admin Enable (jumpered)")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb13",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb13")
#! Field("PLC:CLTS:PP13:CLTS_RDAb13.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb13.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb13.FLNK","PPS:CLTS:1:ACR_ENABLE_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb13.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb13.VAL")
#! Record("PPS:CLTS:1:ACR_ENABLE_A_calc",260,18,0,1,"PPS:CLTS:1:ACR_ENABLE_A_calc")
#! Field("PPS:CLTS:1:ACR_ENABLE_A_calc.INPA",16777215,0,"PPS:CLTS:1:ACR_ENABLE_A_calc.INPA")
#! Link("PPS:CLTS:1:ACR_ENABLE_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb13.VAL")
#! Field("PPS:CLTS:1:ACR_ENABLE_A_calc.INPB",16777215,1,"PPS:CLTS:1:ACR_ENABLE_A_calc.INPB")
#! Field("PPS:CLTS:1:ACR_ENABLE_A_calc.OUT",16777215,1,"PPS:CLTS:1:ACR_ENABLE_A_calc.OUT")
#! Link("PPS:CLTS:1:ACR_ENABLE_A_calc.OUT","PPS:CLTS:1:ACR_ENABLE_A.VAL")
#! Record("PPS:CLTS:1:ACR_ENABLE_A",500,20,0,0,"PPS:CLTS:1:ACR_ENABLE_A")
#! Field("PPS:CLTS:1:ACR_ENABLE_A.VAL",16777215,1,"PPS:CLTS:1:ACR_ENABLE_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi12") {
  field(DESC, "Port CLTS_RDA bit 12")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 12, 1, 1)")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(FLNK, "PPS:CLTS:1:HW_RESET_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:1:HW_RESET_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi12 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:1:HW_RESET_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:1:HW_RESET_A") {
  field(DESC, "RT-IN HW Reset")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb12",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb12")
#! Field("PLC:CLTS:PP13:CLTS_RDAb12.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb12.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb12.FLNK","PPS:CLTS:1:HW_RESET_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb12.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb12.VAL")
#! Record("PPS:CLTS:1:HW_RESET_A_calc",260,18,0,1,"PPS:CLTS:1:HW_RESET_A_calc")
#! Field("PPS:CLTS:1:HW_RESET_A_calc.INPA",16777215,0,"PPS:CLTS:1:HW_RESET_A_calc.INPA")
#! Link("PPS:CLTS:1:HW_RESET_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb12.VAL")
#! Field("PPS:CLTS:1:HW_RESET_A_calc.INPB",16777215,1,"PPS:CLTS:1:HW_RESET_A_calc.INPB")
#! Field("PPS:CLTS:1:HW_RESET_A_calc.OUT",16777215,1,"PPS:CLTS:1:HW_RESET_A_calc.OUT")
#! Link("PPS:CLTS:1:HW_RESET_A_calc.OUT","PPS:CLTS:1:HW_RESET_A.VAL")
#! Record("PPS:CLTS:1:HW_RESET_A",500,20,0,0,"PPS:CLTS:1:HW_RESET_A")
#! Field("PPS:CLTS:1:HW_RESET_A.VAL",16777215,1,"PPS:CLTS:1:HW_RESET_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi11") {
  field(DESC, "Port CLTS_RDA bit 11")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 11, 1, 1)")
  field(ZNAM, "Not_Complete")
  field(ONAM, "Complete")
  field(FLNK, "PPS:CLTS:3:KICK_INTLK_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:KICK_INTLK_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi11 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:KICK_INTLK_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:KICK_INTLK_A") {
  field(DESC, "RT-IN CL Kicker Interlock")
  field(ZNAM, "Not_Complete")
  field(ONAM, "Complete")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb11",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb11")
#! Field("PLC:CLTS:PP13:CLTS_RDAb11.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb11.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb11.FLNK","PPS:CLTS:3:KICK_INTLK_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb11.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb11.VAL")
#! Record("PPS:CLTS:3:KICK_INTLK_A_calc",260,18,0,1,"PPS:CLTS:3:KICK_INTLK_A_calc")
#! Field("PPS:CLTS:3:KICK_INTLK_A_calc.INPA",16777215,0,"PPS:CLTS:3:KICK_INTLK_A_calc.INPA")
#! Link("PPS:CLTS:3:KICK_INTLK_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb11.VAL")
#! Field("PPS:CLTS:3:KICK_INTLK_A_calc.INPB",16777215,1,"PPS:CLTS:3:KICK_INTLK_A_calc.INPB")
#! Field("PPS:CLTS:3:KICK_INTLK_A_calc.OUT",16777215,1,"PPS:CLTS:3:KICK_INTLK_A_calc.OUT")
#! Link("PPS:CLTS:3:KICK_INTLK_A_calc.OUT","PPS:CLTS:3:KICK_INTLK_A.VAL")
#! Record("PPS:CLTS:3:KICK_INTLK_A",500,20,0,0,"PPS:CLTS:3:KICK_INTLK_A")
#! Field("PPS:CLTS:3:KICK_INTLK_A.VAL",16777215,1,"PPS:CLTS:3:KICK_INTLK_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi10") {
  field(DESC, "Port CLTS_RDA bit 10")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 10, 1, 1)")
  field(ZNAM, "Not_Complete")
  field(ONAM, "Complete")
  field(FLNK, "PPS:CLTS:3:DCBEND_INTLK_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:DCBEND_INTLK_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi10 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:DCBEND_INTLK_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:DCBEND_INTLK_A") {
  field(DESC, "RT-IN CL DC Interlock")
  field(ZNAM, "Not_Complete")
  field(ONAM, "Complete")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb10",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb10")
#! Field("PLC:CLTS:PP13:CLTS_RDAb10.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb10.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb10.FLNK","PPS:CLTS:3:DCBEND_INTLK_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb10.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb10.VAL")
#! Record("PPS:CLTS:3:DCBEND_INTLK_A_calc",260,18,0,1,"PPS:CLTS:3:DCBEND_INTLK_A_calc")
#! Field("PPS:CLTS:3:DCBEND_INTLK_A_calc.INPA",16777215,0,"PPS:CLTS:3:DCBEND_INTLK_A_calc.INPA")
#! Link("PPS:CLTS:3:DCBEND_INTLK_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb10.VAL")
#! Field("PPS:CLTS:3:DCBEND_INTLK_A_calc.INPB",16777215,1,"PPS:CLTS:3:DCBEND_INTLK_A_calc.INPB")
#! Field("PPS:CLTS:3:DCBEND_INTLK_A_calc.OUT",16777215,1,"PPS:CLTS:3:DCBEND_INTLK_A_calc.OUT")
#! Link("PPS:CLTS:3:DCBEND_INTLK_A_calc.OUT","PPS:CLTS:3:DCBEND_INTLK_A.VAL")
#! Record("PPS:CLTS:3:DCBEND_INTLK_A",500,20,0,0,"PPS:CLTS:3:DCBEND_INTLK_A")
#! Field("PPS:CLTS:3:DCBEND_INTLK_A.VAL",16777215,1,"PPS:CLTS:3:DCBEND_INTLK_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi9") {
  field(DESC, "Port CLTS_RDA bit 9")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 9, 1, 1)")
  field(ZNAM, "Not_Complete")
  field(ONAM, "Complete")
  field(FLNK, "PPS:CLTS:3:SEP_INTLK_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:SEP_INTLK_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi9 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:SEP_INTLK_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:SEP_INTLK_A") {
  field(DESC, "RT-IN CL Septum Interlock")
  field(ZNAM, "Not_Complete")
  field(ONAM, "Complete")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb9",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb9")
#! Field("PLC:CLTS:PP13:CLTS_RDAb9.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb9.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb9.FLNK","PPS:CLTS:3:SEP_INTLK_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb9.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb9.VAL")
#! Record("PPS:CLTS:3:SEP_INTLK_A_calc",260,18,0,1,"PPS:CLTS:3:SEP_INTLK_A_calc")
#! Field("PPS:CLTS:3:SEP_INTLK_A_calc.INPA",16777215,0,"PPS:CLTS:3:SEP_INTLK_A_calc.INPA")
#! Link("PPS:CLTS:3:SEP_INTLK_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb9.VAL")
#! Field("PPS:CLTS:3:SEP_INTLK_A_calc.INPB",16777215,1,"PPS:CLTS:3:SEP_INTLK_A_calc.INPB")
#! Field("PPS:CLTS:3:SEP_INTLK_A_calc.OUT",16777215,1,"PPS:CLTS:3:SEP_INTLK_A_calc.OUT")
#! Link("PPS:CLTS:3:SEP_INTLK_A_calc.OUT","PPS:CLTS:3:SEP_INTLK_A.VAL")
#! Record("PPS:CLTS:3:SEP_INTLK_A",500,20,0,0,"PPS:CLTS:3:SEP_INTLK_A")
#! Field("PPS:CLTS:3:SEP_INTLK_A.VAL",16777215,1,"PPS:CLTS:3:SEP_INTLK_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi8") {
  field(DESC, "Port CLTS_RDA bit 8")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 8, 1, 1)")
  field(ZNAM, "Not_Complete")
  field(ONAM, "Complete")
  field(FLNK, "PPS:CLTS:3:MERGE_INTLK_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:MERGE_INTLK_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi8 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:MERGE_INTLK_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:MERGE_INTLK_A") {
  field(DESC, "RT-IN CL Merge Interlock")
  field(ZNAM, "Not_Complete")
  field(ONAM, "Complete")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb8",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb8")
#! Field("PLC:CLTS:PP13:CLTS_RDAb8.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb8.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb8.FLNK","PPS:CLTS:3:MERGE_INTLK_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb8.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb8.VAL")
#! Record("PPS:CLTS:3:MERGE_INTLK_A_calc",260,18,0,1,"PPS:CLTS:3:MERGE_INTLK_A_calc")
#! Field("PPS:CLTS:3:MERGE_INTLK_A_calc.INPA",16777215,0,"PPS:CLTS:3:MERGE_INTLK_A_calc.INPA")
#! Link("PPS:CLTS:3:MERGE_INTLK_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb8.VAL")
#! Field("PPS:CLTS:3:MERGE_INTLK_A_calc.INPB",16777215,1,"PPS:CLTS:3:MERGE_INTLK_A_calc.INPB")
#! Field("PPS:CLTS:3:MERGE_INTLK_A_calc.OUT",16777215,1,"PPS:CLTS:3:MERGE_INTLK_A_calc.OUT")
#! Link("PPS:CLTS:3:MERGE_INTLK_A_calc.OUT","PPS:CLTS:3:MERGE_INTLK_A.VAL")
#! Record("PPS:CLTS:3:MERGE_INTLK_A",500,20,0,0,"PPS:CLTS:3:MERGE_INTLK_A")
#! Field("PPS:CLTS:3:MERGE_INTLK_A.VAL",16777215,1,"PPS:CLTS:3:MERGE_INTLK_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi89") {
  field(DESC, "Port CLTS_RDA bit 89")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 89, 1, 1)")
  field(ZNAM, "NOT_ON")
  field(ONAM, "ON")
  field(FLNK, "PPS:CLTS:3:KICK_ON_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:KICK_ON_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi89 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:KICK_ON_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:KICK_ON_A") {
  field(DESC, "RT-OUT CL-Kicker ON status")
  field(ZNAM, "NOT_ON")
  field(ONAM, "ON")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb89",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb89")
#! Field("PLC:CLTS:PP13:CLTS_RDAb89.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb89.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb89.FLNK","PPS:CLTS:3:KICK_ON_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb89.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb89.VAL")
#! Record("PPS:CLTS:3:KICK_ON_A_calc",260,18,0,1,"PPS:CLTS:3:KICK_ON_A_calc")
#! Field("PPS:CLTS:3:KICK_ON_A_calc.INPA",16777215,0,"PPS:CLTS:3:KICK_ON_A_calc.INPA")
#! Link("PPS:CLTS:3:KICK_ON_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb89.VAL")
#! Field("PPS:CLTS:3:KICK_ON_A_calc.INPB",16777215,1,"PPS:CLTS:3:KICK_ON_A_calc.INPB")
#! Field("PPS:CLTS:3:KICK_ON_A_calc.OUT",16777215,1,"PPS:CLTS:3:KICK_ON_A_calc.OUT")
#! Link("PPS:CLTS:3:KICK_ON_A_calc.OUT","PPS:CLTS:3:KICK_ON_A.VAL")
#! Record("PPS:CLTS:3:KICK_ON_A",500,20,0,0,"PPS:CLTS:3:KICK_ON_A")
#! Field("PPS:CLTS:3:KICK_ON_A.VAL",16777215,1,"PPS:CLTS:3:KICK_ON_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi88") {
  field(DESC, "Port CLTS_RDA bit 88")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 88, 1, 1)")
  field(ZNAM, "NOT_ON")
  field(ONAM, "ON")
  field(FLNK, "PPS:CLTS:3:DCBEND_ON_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:DCBEND_ON_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi88 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:DCBEND_ON_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:DCBEND_ON_A") {
  field(DESC, "RT-OUT CL-DC ON status")
  field(ZNAM, "NOT_ON")
  field(ONAM, "ON")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb88",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb88")
#! Field("PLC:CLTS:PP13:CLTS_RDAb88.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb88.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb88.FLNK","PPS:CLTS:3:DCBEND_ON_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb88.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb88.VAL")
#! Record("PPS:CLTS:3:DCBEND_ON_A_calc",260,18,0,1,"PPS:CLTS:3:DCBEND_ON_A_calc")
#! Field("PPS:CLTS:3:DCBEND_ON_A_calc.INPA",16777215,0,"PPS:CLTS:3:DCBEND_ON_A_calc.INPA")
#! Link("PPS:CLTS:3:DCBEND_ON_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb88.VAL")
#! Field("PPS:CLTS:3:DCBEND_ON_A_calc.INPB",16777215,1,"PPS:CLTS:3:DCBEND_ON_A_calc.INPB")
#! Field("PPS:CLTS:3:DCBEND_ON_A_calc.OUT",16777215,1,"PPS:CLTS:3:DCBEND_ON_A_calc.OUT")
#! Link("PPS:CLTS:3:DCBEND_ON_A_calc.OUT","PPS:CLTS:3:DCBEND_ON_A.VAL")
#! Record("PPS:CLTS:3:DCBEND_ON_A",500,20,0,0,"PPS:CLTS:3:DCBEND_ON_A")
#! Field("PPS:CLTS:3:DCBEND_ON_A.VAL",16777215,1,"PPS:CLTS:3:DCBEND_ON_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi103") {
  field(DESC, "Port CLTS_RDA bit 103")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 103, 1, 1)")
  field(ZNAM, "NOT_ON")
  field(ONAM, "ON")
  field(FLNK, "PPS:CLTS:3:SEP_ON_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:SEP_ON_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi103 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:SEP_ON_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:SEP_ON_A") {
  field(DESC, "RT-OUT CL-Septum ON status")
  field(ZNAM, "NOT_ON")
  field(ONAM, "ON")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb103",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb103")
#! Field("PLC:CLTS:PP13:CLTS_RDAb103.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb103.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb103.FLNK","PPS:CLTS:3:SEP_ON_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb103.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb103.VAL")
#! Record("PPS:CLTS:3:SEP_ON_A_calc",260,18,0,1,"PPS:CLTS:3:SEP_ON_A_calc")
#! Field("PPS:CLTS:3:SEP_ON_A_calc.INPA",16777215,0,"PPS:CLTS:3:SEP_ON_A_calc.INPA")
#! Link("PPS:CLTS:3:SEP_ON_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb103.VAL")
#! Field("PPS:CLTS:3:SEP_ON_A_calc.INPB",16777215,1,"PPS:CLTS:3:SEP_ON_A_calc.INPB")
#! Field("PPS:CLTS:3:SEP_ON_A_calc.OUT",16777215,1,"PPS:CLTS:3:SEP_ON_A_calc.OUT")
#! Link("PPS:CLTS:3:SEP_ON_A_calc.OUT","PPS:CLTS:3:SEP_ON_A.VAL")
#! Record("PPS:CLTS:3:SEP_ON_A",500,20,0,0,"PPS:CLTS:3:SEP_ON_A")
#! Field("PPS:CLTS:3:SEP_ON_A.VAL",16777215,1,"PPS:CLTS:3:SEP_ON_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi102") {
  field(DESC, "Port CLTS_RDA bit 102")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 102, 1, 1)")
  field(ZNAM, "NOT_ON")
  field(ONAM, "ON")
  field(FLNK, "PPS:CLTS:3:MERGE_ON_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:MERGE_ON_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi102 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:MERGE_ON_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:MERGE_ON_A") {
  field(DESC, "RT-OUT CL-Merge ON status")
  field(ZNAM, "NOT_ON")
  field(ONAM, "ON")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb102",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb102")
#! Field("PLC:CLTS:PP13:CLTS_RDAb102.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb102.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb102.FLNK","PPS:CLTS:3:MERGE_ON_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb102.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb102.VAL")
#! Record("PPS:CLTS:3:MERGE_ON_A_calc",260,18,0,1,"PPS:CLTS:3:MERGE_ON_A_calc")
#! Field("PPS:CLTS:3:MERGE_ON_A_calc.INPA",16777215,0,"PPS:CLTS:3:MERGE_ON_A_calc.INPA")
#! Link("PPS:CLTS:3:MERGE_ON_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb102.VAL")
#! Field("PPS:CLTS:3:MERGE_ON_A_calc.INPB",16777215,1,"PPS:CLTS:3:MERGE_ON_A_calc.INPB")
#! Field("PPS:CLTS:3:MERGE_ON_A_calc.OUT",16777215,1,"PPS:CLTS:3:MERGE_ON_A_calc.OUT")
#! Link("PPS:CLTS:3:MERGE_ON_A_calc.OUT","PPS:CLTS:3:MERGE_ON_A.VAL")
#! Record("PPS:CLTS:3:MERGE_ON_A",500,20,0,0,"PPS:CLTS:3:MERGE_ON_A")
#! Field("PPS:CLTS:3:MERGE_ON_A.VAL",16777215,1,"PPS:CLTS:3:MERGE_ON_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi101") {
  field(DESC, "Port CLTS_RDA bit 101")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 101, 1, 1)")
  field(ZNAM, "NOT_PERMITTED")
  field(ONAM, "PERMITTED")
  field(FLNK, "PPS:CLTS:3:KICK_PERMIT_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:KICK_PERMIT_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi101 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:KICK_PERMIT_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:KICK_PERMIT_A") {
  field(DESC, "RT-OUT CL-Kicker Pwr Sply Pmt (Out)")
  field(ZNAM, "NOT_PERMITTED")
  field(ONAM, "PERMITTED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb101",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb101")
#! Field("PLC:CLTS:PP13:CLTS_RDAb101.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb101.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb101.FLNK","PPS:CLTS:3:KICK_PERMIT_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb101.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb101.VAL")
#! Record("PPS:CLTS:3:KICK_PERMIT_A_calc",260,18,0,1,"PPS:CLTS:3:KICK_PERMIT_A_calc")
#! Field("PPS:CLTS:3:KICK_PERMIT_A_calc.INPA",16777215,0,"PPS:CLTS:3:KICK_PERMIT_A_calc.INPA")
#! Link("PPS:CLTS:3:KICK_PERMIT_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb101.VAL")
#! Field("PPS:CLTS:3:KICK_PERMIT_A_calc.INPB",16777215,1,"PPS:CLTS:3:KICK_PERMIT_A_calc.INPB")
#! Field("PPS:CLTS:3:KICK_PERMIT_A_calc.OUT",16777215,1,"PPS:CLTS:3:KICK_PERMIT_A_calc.OUT")
#! Link("PPS:CLTS:3:KICK_PERMIT_A_calc.OUT","PPS:CLTS:3:KICK_PERMIT_A.VAL")
#! Record("PPS:CLTS:3:KICK_PERMIT_A",500,20,0,0,"PPS:CLTS:3:KICK_PERMIT_A")
#! Field("PPS:CLTS:3:KICK_PERMIT_A.VAL",16777215,1,"PPS:CLTS:3:KICK_PERMIT_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi100") {
  field(DESC, "Port CLTS_RDA bit 100")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 100, 1, 1)")
  field(ZNAM, "NOT_PERMITTED")
  field(ONAM, "PERMITTED")
  field(FLNK, "PPS:CLTS:3:DCBEND_PERMIT_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:DCBEND_PERMIT_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi100 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:DCBEND_PERMIT_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:DCBEND_PERMIT_A") {
  field(DESC, "RT-OUT CL-DC Pwr Sply Pmt (Out)")
  field(ZNAM, "NOT_PERMITTED")
  field(ONAM, "PERMITTED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb100",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb100")
#! Field("PLC:CLTS:PP13:CLTS_RDAb100.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb100.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb100.FLNK","PPS:CLTS:3:DCBEND_PERMIT_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb100.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb100.VAL")
#! Record("PPS:CLTS:3:DCBEND_PERMIT_A_calc",260,18,0,1,"PPS:CLTS:3:DCBEND_PERMIT_A_calc")
#! Field("PPS:CLTS:3:DCBEND_PERMIT_A_calc.INPA",16777215,0,"PPS:CLTS:3:DCBEND_PERMIT_A_calc.INPA")
#! Link("PPS:CLTS:3:DCBEND_PERMIT_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb100.VAL")
#! Field("PPS:CLTS:3:DCBEND_PERMIT_A_calc.INPB",16777215,1,"PPS:CLTS:3:DCBEND_PERMIT_A_calc.INPB")
#! Field("PPS:CLTS:3:DCBEND_PERMIT_A_calc.OUT",16777215,1,"PPS:CLTS:3:DCBEND_PERMIT_A_calc.OUT")
#! Link("PPS:CLTS:3:DCBEND_PERMIT_A_calc.OUT","PPS:CLTS:3:DCBEND_PERMIT_A.VAL")
#! Record("PPS:CLTS:3:DCBEND_PERMIT_A",500,20,0,0,"PPS:CLTS:3:DCBEND_PERMIT_A")
#! Field("PPS:CLTS:3:DCBEND_PERMIT_A.VAL",16777215,1,"PPS:CLTS:3:DCBEND_PERMIT_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi99") {
  field(DESC, "Port CLTS_RDA bit 99")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 99, 1, 1)")
  field(ZNAM, "NOT_PERMITTED")
  field(ONAM, "PERMITTED")
  field(FLNK, "PPS:CLTS:3:SEP_PERMIT_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:SEP_PERMIT_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi99 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:SEP_PERMIT_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:SEP_PERMIT_A") {
  field(DESC, "RT-OUT CL-Septum Pwr Sply Pmt (Out)")
  field(ZNAM, "NOT_PERMITTED")
  field(ONAM, "PERMITTED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb99",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb99")
#! Field("PLC:CLTS:PP13:CLTS_RDAb99.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb99.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb99.FLNK","PPS:CLTS:3:SEP_PERMIT_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb99.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb99.VAL")
#! Record("PPS:CLTS:3:SEP_PERMIT_A_calc",260,18,0,1,"PPS:CLTS:3:SEP_PERMIT_A_calc")
#! Field("PPS:CLTS:3:SEP_PERMIT_A_calc.INPA",16777215,0,"PPS:CLTS:3:SEP_PERMIT_A_calc.INPA")
#! Link("PPS:CLTS:3:SEP_PERMIT_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb99.VAL")
#! Field("PPS:CLTS:3:SEP_PERMIT_A_calc.INPB",16777215,1,"PPS:CLTS:3:SEP_PERMIT_A_calc.INPB")
#! Field("PPS:CLTS:3:SEP_PERMIT_A_calc.OUT",16777215,1,"PPS:CLTS:3:SEP_PERMIT_A_calc.OUT")
#! Link("PPS:CLTS:3:SEP_PERMIT_A_calc.OUT","PPS:CLTS:3:SEP_PERMIT_A.VAL")
#! Record("PPS:CLTS:3:SEP_PERMIT_A",500,20,0,0,"PPS:CLTS:3:SEP_PERMIT_A")
#! Field("PPS:CLTS:3:SEP_PERMIT_A.VAL",16777215,1,"PPS:CLTS:3:SEP_PERMIT_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi98") {
  field(DESC, "Port CLTS_RDA bit 98")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 98, 1, 1)")
  field(ZNAM, "NOT_PERMITTED")
  field(ONAM, "PERMITTED")
  field(FLNK, "PPS:CLTS:3:MERGE_PERMIT_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:MERGE_PERMIT_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi98 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:MERGE_PERMIT_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:MERGE_PERMIT_A") {
  field(DESC, "RT-OUT CL-Merge Pwr Sply Pmt (Out)")
  field(ZNAM, "NOT_PERMITTED")
  field(ONAM, "PERMITTED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb98",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb98")
#! Field("PLC:CLTS:PP13:CLTS_RDAb98.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb98.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb98.FLNK","PPS:CLTS:3:MERGE_PERMIT_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb98.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb98.VAL")
#! Record("PPS:CLTS:3:MERGE_PERMIT_A_calc",260,18,0,1,"PPS:CLTS:3:MERGE_PERMIT_A_calc")
#! Field("PPS:CLTS:3:MERGE_PERMIT_A_calc.INPA",16777215,0,"PPS:CLTS:3:MERGE_PERMIT_A_calc.INPA")
#! Link("PPS:CLTS:3:MERGE_PERMIT_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb98.VAL")
#! Field("PPS:CLTS:3:MERGE_PERMIT_A_calc.INPB",16777215,1,"PPS:CLTS:3:MERGE_PERMIT_A_calc.INPB")
#! Field("PPS:CLTS:3:MERGE_PERMIT_A_calc.OUT",16777215,1,"PPS:CLTS:3:MERGE_PERMIT_A_calc.OUT")
#! Link("PPS:CLTS:3:MERGE_PERMIT_A_calc.OUT","PPS:CLTS:3:MERGE_PERMIT_A.VAL")
#! Record("PPS:CLTS:3:MERGE_PERMIT_A",500,20,0,0,"PPS:CLTS:3:MERGE_PERMIT_A")
#! Field("PPS:CLTS:3:MERGE_PERMIT_A.VAL",16777215,1,"PPS:CLTS:3:MERGE_PERMIT_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi97") {
  field(DESC, "Port CLTS_RDA bit 97")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 97, 1, 1)")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(FLNK, "PPS:CLTS:1:HRTBT_OUTP_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:1:HRTBT_OUTP_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi97 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:1:HRTBT_OUTP_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:1:HRTBT_OUTP_A") {
  field(DESC, "RT-OUT Heartbeat OUT")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb97",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb97")
#! Field("PLC:CLTS:PP13:CLTS_RDAb97.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb97.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb97.FLNK","PPS:CLTS:1:HRTBT_OUTP_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb97.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb97.VAL")
#! Record("PPS:CLTS:1:HRTBT_OUTP_A_calc",260,18,0,1,"PPS:CLTS:1:HRTBT_OUTP_A_calc")
#! Field("PPS:CLTS:1:HRTBT_OUTP_A_calc.INPA",16777215,0,"PPS:CLTS:1:HRTBT_OUTP_A_calc.INPA")
#! Link("PPS:CLTS:1:HRTBT_OUTP_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb97.VAL")
#! Field("PPS:CLTS:1:HRTBT_OUTP_A_calc.INPB",16777215,1,"PPS:CLTS:1:HRTBT_OUTP_A_calc.INPB")
#! Field("PPS:CLTS:1:HRTBT_OUTP_A_calc.OUT",16777215,1,"PPS:CLTS:1:HRTBT_OUTP_A_calc.OUT")
#! Link("PPS:CLTS:1:HRTBT_OUTP_A_calc.OUT","PPS:CLTS:1:HRTBT_OUTP_A.VAL")
#! Record("PPS:CLTS:1:HRTBT_OUTP_A",500,20,0,0,"PPS:CLTS:1:HRTBT_OUTP_A")
#! Field("PPS:CLTS:1:HRTBT_OUTP_A.VAL",16777215,1,"PPS:CLTS:1:HRTBT_OUTP_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi96") {
  field(DESC, "Port CLTS_RDA bit 96")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 96, 1, 1)")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(FLNK, "PPS:CLTS:1:HWALRMWARN_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:1:HWALRMWARN_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi96 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:1:HWALRMWARN_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:1:HWALRMWARN_A") {
  field(DESC, "RT-OUT ACR Hardware alarm/warning")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb96",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb96")
#! Field("PLC:CLTS:PP13:CLTS_RDAb96.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb96.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb96.FLNK","PPS:CLTS:1:HWALRMWARN_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb96.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb96.VAL")
#! Record("PPS:CLTS:1:HWALRMWARN_A_calc",260,18,0,1,"PPS:CLTS:1:HWALRMWARN_A_calc")
#! Field("PPS:CLTS:1:HWALRMWARN_A_calc.INPA",16777215,0,"PPS:CLTS:1:HWALRMWARN_A_calc.INPA")
#! Link("PPS:CLTS:1:HWALRMWARN_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb96.VAL")
#! Field("PPS:CLTS:1:HWALRMWARN_A_calc.INPB",16777215,1,"PPS:CLTS:1:HWALRMWARN_A_calc.INPB")
#! Field("PPS:CLTS:1:HWALRMWARN_A_calc.OUT",16777215,1,"PPS:CLTS:1:HWALRMWARN_A_calc.OUT")
#! Link("PPS:CLTS:1:HWALRMWARN_A_calc.OUT","PPS:CLTS:1:HWALRMWARN_A.VAL")
#! Record("PPS:CLTS:1:HWALRMWARN_A",500,20,0,0,"PPS:CLTS:1:HWALRMWARN_A")
#! Field("PPS:CLTS:1:HWALRMWARN_A.VAL",16777215,1,"PPS:CLTS:1:HWALRMWARN_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi111") {
  field(DESC, "Port CLTS_RDA bit 111")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 111, 1, 1)")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(FLNK, "PPS:CLTS:1:HRTBT_OK_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:1:HRTBT_OK_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi111 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:1:HRTBT_OK_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:1:HRTBT_OK_A") {
  field(DESC, "RT Heartbeat OK")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb111",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb111")
#! Field("PLC:CLTS:PP13:CLTS_RDAb111.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb111.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb111.FLNK","PPS:CLTS:1:HRTBT_OK_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb111.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb111.VAL")
#! Record("PPS:CLTS:1:HRTBT_OK_A_calc",260,18,0,1,"PPS:CLTS:1:HRTBT_OK_A_calc")
#! Field("PPS:CLTS:1:HRTBT_OK_A_calc.INPA",16777215,0,"PPS:CLTS:1:HRTBT_OK_A_calc.INPA")
#! Link("PPS:CLTS:1:HRTBT_OK_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb111.VAL")
#! Field("PPS:CLTS:1:HRTBT_OK_A_calc.INPB",16777215,1,"PPS:CLTS:1:HRTBT_OK_A_calc.INPB")
#! Field("PPS:CLTS:1:HRTBT_OK_A_calc.OUT",16777215,1,"PPS:CLTS:1:HRTBT_OK_A_calc.OUT")
#! Link("PPS:CLTS:1:HRTBT_OK_A_calc.OUT","PPS:CLTS:1:HRTBT_OK_A.VAL")
#! Record("PPS:CLTS:1:HRTBT_OK_A",500,20,0,0,"PPS:CLTS:1:HRTBT_OK_A")
#! Field("PPS:CLTS:1:HRTBT_OK_A.VAL",16777215,1,"PPS:CLTS:1:HRTBT_OK_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi110") {
  field(DESC, "Port CLTS_RDA bit 110")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 110, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:1:HRTBT_OK_LTH_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:1:HRTBT_OK_LTH_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi110 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:1:HRTBT_OK_LTH_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:1:HRTBT_OK_LTH_A") {
  field(DESC, "LAT Heartbeat OK")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb110",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb110")
#! Field("PLC:CLTS:PP13:CLTS_RDAb110.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb110.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb110.FLNK","PPS:CLTS:1:HRTBT_OK_LTH_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb110.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb110.VAL")
#! Record("PPS:CLTS:1:HRTBT_OK_LTH_A_calc",260,18,0,1,"PPS:CLTS:1:HRTBT_OK_LTH_A_calc")
#! Field("PPS:CLTS:1:HRTBT_OK_LTH_A_calc.INPA",16777215,0,"PPS:CLTS:1:HRTBT_OK_LTH_A_calc.INPA")
#! Link("PPS:CLTS:1:HRTBT_OK_LTH_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb110.VAL")
#! Field("PPS:CLTS:1:HRTBT_OK_LTH_A_calc.INPB",16777215,1,"PPS:CLTS:1:HRTBT_OK_LTH_A_calc.INPB")
#! Field("PPS:CLTS:1:HRTBT_OK_LTH_A_calc.OUT",16777215,1,"PPS:CLTS:1:HRTBT_OK_LTH_A_calc.OUT")
#! Link("PPS:CLTS:1:HRTBT_OK_LTH_A_calc.OUT","PPS:CLTS:1:HRTBT_OK_LTH_A.VAL")
#! Record("PPS:CLTS:1:HRTBT_OK_LTH_A",500,20,0,0,"PPS:CLTS:1:HRTBT_OK_LTH_A")
#! Field("PPS:CLTS:1:HRTBT_OK_LTH_A.VAL",16777215,1,"PPS:CLTS:1:HRTBT_OK_LTH_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi109") {
  field(DESC, "Port CLTS_RDA bit 109")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 109, 1, 1)")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(FLNK, "PPS:CLTS:1:BCS_FAULT_OUT_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:1:BCS_FAULT_OUT_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi109 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:1:BCS_FAULT_OUT_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:1:BCS_FAULT_OUT_A") {
  field(DESC, "RT-OUT BCS Ok from PLC3")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb109",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb109")
#! Field("PLC:CLTS:PP13:CLTS_RDAb109.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb109.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb109.FLNK","PPS:CLTS:1:BCS_FAULT_OUT_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb109.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb109.VAL")
#! Record("PPS:CLTS:1:BCS_FAULT_OUT_A_calc",260,18,0,1,"PPS:CLTS:1:BCS_FAULT_OUT_A_calc")
#! Field("PPS:CLTS:1:BCS_FAULT_OUT_A_calc.INPA",16777215,0,"PPS:CLTS:1:BCS_FAULT_OUT_A_calc.INPA")
#! Link("PPS:CLTS:1:BCS_FAULT_OUT_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb109.VAL")
#! Field("PPS:CLTS:1:BCS_FAULT_OUT_A_calc.INPB",16777215,1,"PPS:CLTS:1:BCS_FAULT_OUT_A_calc.INPB")
#! Field("PPS:CLTS:1:BCS_FAULT_OUT_A_calc.OUT",16777215,1,"PPS:CLTS:1:BCS_FAULT_OUT_A_calc.OUT")
#! Link("PPS:CLTS:1:BCS_FAULT_OUT_A_calc.OUT","PPS:CLTS:1:BCS_FAULT_OUT_A.VAL")
#! Record("PPS:CLTS:1:BCS_FAULT_OUT_A",500,20,0,0,"PPS:CLTS:1:BCS_FAULT_OUT_A")
#! Field("PPS:CLTS:1:BCS_FAULT_OUT_A.VAL",16777215,1,"PPS:CLTS:1:BCS_FAULT_OUT_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi108") {
  field(DESC, "Port CLTS_RDA bit 108")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 108, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:3:KICK_OFF_LTH_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:KICK_OFF_LTH_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi108 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:KICK_OFF_LTH_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:KICK_OFF_LTH_A") {
  field(DESC, "LAT CL-Kicker OFF status")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb108",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb108")
#! Field("PLC:CLTS:PP13:CLTS_RDAb108.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb108.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb108.FLNK","PPS:CLTS:3:KICK_OFF_LTH_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb108.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb108.VAL")
#! Record("PPS:CLTS:3:KICK_OFF_LTH_A_calc",260,18,0,1,"PPS:CLTS:3:KICK_OFF_LTH_A_calc")
#! Field("PPS:CLTS:3:KICK_OFF_LTH_A_calc.INPA",16777215,0,"PPS:CLTS:3:KICK_OFF_LTH_A_calc.INPA")
#! Link("PPS:CLTS:3:KICK_OFF_LTH_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb108.VAL")
#! Field("PPS:CLTS:3:KICK_OFF_LTH_A_calc.INPB",16777215,1,"PPS:CLTS:3:KICK_OFF_LTH_A_calc.INPB")
#! Field("PPS:CLTS:3:KICK_OFF_LTH_A_calc.OUT",16777215,1,"PPS:CLTS:3:KICK_OFF_LTH_A_calc.OUT")
#! Link("PPS:CLTS:3:KICK_OFF_LTH_A_calc.OUT","PPS:CLTS:3:KICK_OFF_LTH_A.VAL")
#! Record("PPS:CLTS:3:KICK_OFF_LTH_A",500,20,0,0,"PPS:CLTS:3:KICK_OFF_LTH_A")
#! Field("PPS:CLTS:3:KICK_OFF_LTH_A.VAL",16777215,1,"PPS:CLTS:3:KICK_OFF_LTH_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi107") {
  field(DESC, "Port CLTS_RDA bit 107")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 107, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:3:DCBEND_OFF_LTH_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:DCBEND_OFF_LTH_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi107 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:DCBEND_OFF_LTH_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:DCBEND_OFF_LTH_A") {
  field(DESC, "LAT CL-DC OFF status")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb107",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb107")
#! Field("PLC:CLTS:PP13:CLTS_RDAb107.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb107.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb107.FLNK","PPS:CLTS:3:DCBEND_OFF_LTH_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb107.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb107.VAL")
#! Record("PPS:CLTS:3:DCBEND_OFF_LTH_A_calc",260,18,0,1,"PPS:CLTS:3:DCBEND_OFF_LTH_A_calc")
#! Field("PPS:CLTS:3:DCBEND_OFF_LTH_A_calc.INPA",16777215,0,"PPS:CLTS:3:DCBEND_OFF_LTH_A_calc.INPA")
#! Link("PPS:CLTS:3:DCBEND_OFF_LTH_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb107.VAL")
#! Field("PPS:CLTS:3:DCBEND_OFF_LTH_A_calc.INPB",16777215,1,"PPS:CLTS:3:DCBEND_OFF_LTH_A_calc.INPB")
#! Field("PPS:CLTS:3:DCBEND_OFF_LTH_A_calc.OUT",16777215,1,"PPS:CLTS:3:DCBEND_OFF_LTH_A_calc.OUT")
#! Link("PPS:CLTS:3:DCBEND_OFF_LTH_A_calc.OUT","PPS:CLTS:3:DCBEND_OFF_LTH_A.VAL")
#! Record("PPS:CLTS:3:DCBEND_OFF_LTH_A",500,20,0,0,"PPS:CLTS:3:DCBEND_OFF_LTH_A")
#! Field("PPS:CLTS:3:DCBEND_OFF_LTH_A.VAL",16777215,1,"PPS:CLTS:3:DCBEND_OFF_LTH_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi106") {
  field(DESC, "Port CLTS_RDA bit 106")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 106, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:3:SEP_OFF_LTH_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:SEP_OFF_LTH_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi106 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:SEP_OFF_LTH_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:SEP_OFF_LTH_A") {
  field(DESC, "LAT CL-Septum OFF status")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb106",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb106")
#! Field("PLC:CLTS:PP13:CLTS_RDAb106.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb106.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb106.FLNK","PPS:CLTS:3:SEP_OFF_LTH_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb106.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb106.VAL")
#! Record("PPS:CLTS:3:SEP_OFF_LTH_A_calc",260,18,0,1,"PPS:CLTS:3:SEP_OFF_LTH_A_calc")
#! Field("PPS:CLTS:3:SEP_OFF_LTH_A_calc.INPA",16777215,0,"PPS:CLTS:3:SEP_OFF_LTH_A_calc.INPA")
#! Link("PPS:CLTS:3:SEP_OFF_LTH_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb106.VAL")
#! Field("PPS:CLTS:3:SEP_OFF_LTH_A_calc.INPB",16777215,1,"PPS:CLTS:3:SEP_OFF_LTH_A_calc.INPB")
#! Field("PPS:CLTS:3:SEP_OFF_LTH_A_calc.OUT",16777215,1,"PPS:CLTS:3:SEP_OFF_LTH_A_calc.OUT")
#! Link("PPS:CLTS:3:SEP_OFF_LTH_A_calc.OUT","PPS:CLTS:3:SEP_OFF_LTH_A.VAL")
#! Record("PPS:CLTS:3:SEP_OFF_LTH_A",500,20,0,0,"PPS:CLTS:3:SEP_OFF_LTH_A")
#! Field("PPS:CLTS:3:SEP_OFF_LTH_A.VAL",16777215,1,"PPS:CLTS:3:SEP_OFF_LTH_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi105") {
  field(DESC, "Port CLTS_RDA bit 105")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 105, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:3:MERGE_OFF_LTH_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:MERGE_OFF_LTH_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi105 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:MERGE_OFF_LTH_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:MERGE_OFF_LTH_A") {
  field(DESC, "LAT CL-Merge OFF status")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb105",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb105")
#! Field("PLC:CLTS:PP13:CLTS_RDAb105.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb105.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb105.FLNK","PPS:CLTS:3:MERGE_OFF_LTH_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb105.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb105.VAL")
#! Record("PPS:CLTS:3:MERGE_OFF_LTH_A_calc",260,18,0,1,"PPS:CLTS:3:MERGE_OFF_LTH_A_calc")
#! Field("PPS:CLTS:3:MERGE_OFF_LTH_A_calc.INPA",16777215,0,"PPS:CLTS:3:MERGE_OFF_LTH_A_calc.INPA")
#! Link("PPS:CLTS:3:MERGE_OFF_LTH_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb105.VAL")
#! Field("PPS:CLTS:3:MERGE_OFF_LTH_A_calc.INPB",16777215,1,"PPS:CLTS:3:MERGE_OFF_LTH_A_calc.INPB")
#! Field("PPS:CLTS:3:MERGE_OFF_LTH_A_calc.OUT",16777215,1,"PPS:CLTS:3:MERGE_OFF_LTH_A_calc.OUT")
#! Link("PPS:CLTS:3:MERGE_OFF_LTH_A_calc.OUT","PPS:CLTS:3:MERGE_OFF_LTH_A.VAL")
#! Record("PPS:CLTS:3:MERGE_OFF_LTH_A",500,20,0,0,"PPS:CLTS:3:MERGE_OFF_LTH_A")
#! Field("PPS:CLTS:3:MERGE_OFF_LTH_A.VAL",16777215,1,"PPS:CLTS:3:MERGE_OFF_LTH_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi104") {
  field(DESC, "Port CLTS_RDA bit 104")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 104, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:LI28:3:HXR:KICKSEP_OFF_LTH_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:LI28:3:HXR:KICKSEP_OFF_LTH_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi104 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:LI28:3:HXR:KICKSEP_OFF_LTH_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:LI28:3:HXR:KICKSEP_OFF_LTH_A") {
  field(DESC, "LAT HX-KickerSepMrg Summary OFF")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb104",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb104")
#! Field("PLC:CLTS:PP13:CLTS_RDAb104.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb104.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb104.FLNK","PPS:LI28:3:HXR:KICKSEP_OFF_LTH_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb104.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb104.VAL")
#! Record("PPS:LI28:3:HXR:KICKSEP_OFF_LTH_A_calc",260,18,0,1,"PPS:LI28:3:HXR:KICKSEP_OFF_LTH_A_calc")
#! Field("PPS:LI28:3:HXR:KICKSEP_OFF_LTH_A_calc.INPA",16777215,0,"PPS:LI28:3:HXR:KICKSEP_OFF_LTH_A_calc.INPA")
#! Link("PPS:LI28:3:HXR:KICKSEP_OFF_LTH_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb104.VAL")
#! Field("PPS:LI28:3:HXR:KICKSEP_OFF_LTH_A_calc.INPB",16777215,1,"PPS:LI28:3:HXR:KICKSEP_OFF_LTH_A_calc.INPB")
#! Field("PPS:LI28:3:HXR:KICKSEP_OFF_LTH_A_calc.OUT",16777215,1,"PPS:LI28:3:HXR:KICKSEP_OFF_LTH_A_calc.OUT")
#! Link("PPS:LI28:3:HXR:KICKSEP_OFF_LTH_A_calc.OUT","PPS:LI28:3:HXR:KICKSEP_OFF_LTH_A.VAL")
#! Record("PPS:LI28:3:HXR:KICKSEP_OFF_LTH_A",500,20,0,0,"PPS:LI28:3:HXR:KICKSEP_OFF_LTH_A")
#! Field("PPS:LI28:3:HXR:KICKSEP_OFF_LTH_A.VAL",16777215,1,"PPS:LI28:3:HXR:KICKSEP_OFF_LTH_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi119") {
  field(DESC, "Port CLTS_RDA bit 119")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 119, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:LI30:3:SXR:KICKSEP_OFF_LTH_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:LI30:3:SXR:KICKSEP_OFF_LTH_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi119 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:LI30:3:SXR:KICKSEP_OFF_LTH_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:LI30:3:SXR:KICKSEP_OFF_LTH_A") {
  field(DESC, "LAT SX-KickerSepMrg Summary OFF")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb119",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb119")
#! Field("PLC:CLTS:PP13:CLTS_RDAb119.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb119.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb119.FLNK","PPS:LI30:3:SXR:KICKSEP_OFF_LTH_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb119.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb119.VAL")
#! Record("PPS:LI30:3:SXR:KICKSEP_OFF_LTH_A_calc",260,18,0,1,"PPS:LI30:3:SXR:KICKSEP_OFF_LTH_A_calc")
#! Field("PPS:LI30:3:SXR:KICKSEP_OFF_LTH_A_calc.INPA",16777215,0,"PPS:LI30:3:SXR:KICKSEP_OFF_LTH_A_calc.INPA")
#! Link("PPS:LI30:3:SXR:KICKSEP_OFF_LTH_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb119.VAL")
#! Field("PPS:LI30:3:SXR:KICKSEP_OFF_LTH_A_calc.INPB",16777215,1,"PPS:LI30:3:SXR:KICKSEP_OFF_LTH_A_calc.INPB")
#! Field("PPS:LI30:3:SXR:KICKSEP_OFF_LTH_A_calc.OUT",16777215,1,"PPS:LI30:3:SXR:KICKSEP_OFF_LTH_A_calc.OUT")
#! Link("PPS:LI30:3:SXR:KICKSEP_OFF_LTH_A_calc.OUT","PPS:LI30:3:SXR:KICKSEP_OFF_LTH_A.VAL")
#! Record("PPS:LI30:3:SXR:KICKSEP_OFF_LTH_A",500,20,0,0,"PPS:LI30:3:SXR:KICKSEP_OFF_LTH_A")
#! Field("PPS:LI30:3:SXR:KICKSEP_OFF_LTH_A.VAL",16777215,1,"PPS:LI30:3:SXR:KICKSEP_OFF_LTH_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi118") {
  field(DESC, "Port CLTS_RDA bit 118")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 118, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "STPR:CLTS:585:3:IN_LTH_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "STPR:CLTS:585:3:IN_LTH_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi118 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "STPR:CLTS:585:3:IN_LTH_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "STPR:CLTS:585:3:IN_LTH_A") {
  field(DESC, "LAT STP-CLTS IN")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb118",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb118")
#! Field("PLC:CLTS:PP13:CLTS_RDAb118.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb118.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb118.FLNK","STPR:CLTS:585:3:IN_LTH_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb118.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb118.VAL")
#! Record("STPR:CLTS:585:3:IN_LTH_A_calc",260,18,0,1,"STPR:CLTS:585:3:IN_LTH_A_calc")
#! Field("STPR:CLTS:585:3:IN_LTH_A_calc.INPA",16777215,0,"STPR:CLTS:585:3:IN_LTH_A_calc.INPA")
#! Link("STPR:CLTS:585:3:IN_LTH_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb118.VAL")
#! Field("STPR:CLTS:585:3:IN_LTH_A_calc.INPB",16777215,1,"STPR:CLTS:585:3:IN_LTH_A_calc.INPB")
#! Field("STPR:CLTS:585:3:IN_LTH_A_calc.OUT",16777215,1,"STPR:CLTS:585:3:IN_LTH_A_calc.OUT")
#! Link("STPR:CLTS:585:3:IN_LTH_A_calc.OUT","STPR:CLTS:585:3:IN_LTH_A.VAL")
#! Record("STPR:CLTS:585:3:IN_LTH_A",500,20,0,0,"STPR:CLTS:585:3:IN_LTH_A")
#! Field("STPR:CLTS:585:3:IN_LTH_A.VAL",16777215,1,"STPR:CLTS:585:3:IN_LTH_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi117") {
  field(DESC, "Port CLTS_RDA bit 117")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 117, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "STPR:BSYS:3:ST34_OUT_LTH_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "STPR:BSYS:3:ST34_OUT_LTH_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi117 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "STPR:BSYS:3:ST34_OUT_LTH_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "STPR:BSYS:3:ST34_OUT_LTH_A") {
  field(DESC, "LAT STP-34 Summary OUT")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb117",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb117")
#! Field("PLC:CLTS:PP13:CLTS_RDAb117.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb117.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb117.FLNK","STPR:BSYS:3:ST34_OUT_LTH_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb117.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb117.VAL")
#! Record("STPR:BSYS:3:ST34_OUT_LTH_A_calc",260,18,0,1,"STPR:BSYS:3:ST34_OUT_LTH_A_calc")
#! Field("STPR:BSYS:3:ST34_OUT_LTH_A_calc.INPA",16777215,0,"STPR:BSYS:3:ST34_OUT_LTH_A_calc.INPA")
#! Link("STPR:BSYS:3:ST34_OUT_LTH_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb117.VAL")
#! Field("STPR:BSYS:3:ST34_OUT_LTH_A_calc.INPB",16777215,1,"STPR:BSYS:3:ST34_OUT_LTH_A_calc.INPB")
#! Field("STPR:BSYS:3:ST34_OUT_LTH_A_calc.OUT",16777215,1,"STPR:BSYS:3:ST34_OUT_LTH_A_calc.OUT")
#! Link("STPR:BSYS:3:ST34_OUT_LTH_A_calc.OUT","STPR:BSYS:3:ST34_OUT_LTH_A.VAL")
#! Record("STPR:BSYS:3:ST34_OUT_LTH_A",500,20,0,0,"STPR:BSYS:3:ST34_OUT_LTH_A")
#! Field("STPR:BSYS:3:ST34_OUT_LTH_A.VAL",16777215,1,"STPR:BSYS:3:ST34_OUT_LTH_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi116") {
  field(DESC, "Port CLTS_RDA bit 116")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 116, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:1:ACR_ENABLE_LTH_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:1:ACR_ENABLE_LTH_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi116 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:1:ACR_ENABLE_LTH_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:1:ACR_ENABLE_LTH_A") {
  field(DESC, "LAT CLTS Admin Enable")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb116",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb116")
#! Field("PLC:CLTS:PP13:CLTS_RDAb116.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb116.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb116.FLNK","PPS:CLTS:1:ACR_ENABLE_LTH_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb116.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb116.VAL")
#! Record("PPS:CLTS:1:ACR_ENABLE_LTH_A_calc",260,18,0,1,"PPS:CLTS:1:ACR_ENABLE_LTH_A_calc")
#! Field("PPS:CLTS:1:ACR_ENABLE_LTH_A_calc.INPA",16777215,0,"PPS:CLTS:1:ACR_ENABLE_LTH_A_calc.INPA")
#! Link("PPS:CLTS:1:ACR_ENABLE_LTH_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb116.VAL")
#! Field("PPS:CLTS:1:ACR_ENABLE_LTH_A_calc.INPB",16777215,1,"PPS:CLTS:1:ACR_ENABLE_LTH_A_calc.INPB")
#! Field("PPS:CLTS:1:ACR_ENABLE_LTH_A_calc.OUT",16777215,1,"PPS:CLTS:1:ACR_ENABLE_LTH_A_calc.OUT")
#! Link("PPS:CLTS:1:ACR_ENABLE_LTH_A_calc.OUT","PPS:CLTS:1:ACR_ENABLE_LTH_A.VAL")
#! Record("PPS:CLTS:1:ACR_ENABLE_LTH_A",500,20,0,0,"PPS:CLTS:1:ACR_ENABLE_LTH_A")
#! Field("PPS:CLTS:1:ACR_ENABLE_LTH_A.VAL",16777215,1,"PPS:CLTS:1:ACR_ENABLE_LTH_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi115") {
  field(DESC, "Port CLTS_RDA bit 115")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 115, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:3:KICK_INTLK_LTH_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:KICK_INTLK_LTH_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi115 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:KICK_INTLK_LTH_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:KICK_INTLK_LTH_A") {
  field(DESC, "LAT CL Kicker Interlock")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb115",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb115")
#! Field("PLC:CLTS:PP13:CLTS_RDAb115.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb115.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb115.FLNK","PPS:CLTS:3:KICK_INTLK_LTH_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb115.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb115.VAL")
#! Record("PPS:CLTS:3:KICK_INTLK_LTH_A_calc",260,18,0,1,"PPS:CLTS:3:KICK_INTLK_LTH_A_calc")
#! Field("PPS:CLTS:3:KICK_INTLK_LTH_A_calc.INPA",16777215,0,"PPS:CLTS:3:KICK_INTLK_LTH_A_calc.INPA")
#! Link("PPS:CLTS:3:KICK_INTLK_LTH_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb115.VAL")
#! Field("PPS:CLTS:3:KICK_INTLK_LTH_A_calc.INPB",16777215,1,"PPS:CLTS:3:KICK_INTLK_LTH_A_calc.INPB")
#! Field("PPS:CLTS:3:KICK_INTLK_LTH_A_calc.OUT",16777215,1,"PPS:CLTS:3:KICK_INTLK_LTH_A_calc.OUT")
#! Link("PPS:CLTS:3:KICK_INTLK_LTH_A_calc.OUT","PPS:CLTS:3:KICK_INTLK_LTH_A.VAL")
#! Record("PPS:CLTS:3:KICK_INTLK_LTH_A",500,20,0,0,"PPS:CLTS:3:KICK_INTLK_LTH_A")
#! Field("PPS:CLTS:3:KICK_INTLK_LTH_A.VAL",16777215,1,"PPS:CLTS:3:KICK_INTLK_LTH_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi114") {
  field(DESC, "Port CLTS_RDA bit 114")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 114, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:3:DCBEND_INTLK_LTH_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:DCBEND_INTLK_LTH_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi114 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:DCBEND_INTLK_LTH_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:DCBEND_INTLK_LTH_A") {
  field(DESC, "LAT CL DC Interlock")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb114",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb114")
#! Field("PLC:CLTS:PP13:CLTS_RDAb114.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb114.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb114.FLNK","PPS:CLTS:3:DCBEND_INTLK_LTH_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb114.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb114.VAL")
#! Record("PPS:CLTS:3:DCBEND_INTLK_LTH_A_calc",260,18,0,1,"PPS:CLTS:3:DCBEND_INTLK_LTH_A_calc")
#! Field("PPS:CLTS:3:DCBEND_INTLK_LTH_A_calc.INPA",16777215,0,"PPS:CLTS:3:DCBEND_INTLK_LTH_A_calc.INPA")
#! Link("PPS:CLTS:3:DCBEND_INTLK_LTH_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb114.VAL")
#! Field("PPS:CLTS:3:DCBEND_INTLK_LTH_A_calc.INPB",16777215,1,"PPS:CLTS:3:DCBEND_INTLK_LTH_A_calc.INPB")
#! Field("PPS:CLTS:3:DCBEND_INTLK_LTH_A_calc.OUT",16777215,1,"PPS:CLTS:3:DCBEND_INTLK_LTH_A_calc.OUT")
#! Link("PPS:CLTS:3:DCBEND_INTLK_LTH_A_calc.OUT","PPS:CLTS:3:DCBEND_INTLK_LTH_A.VAL")
#! Record("PPS:CLTS:3:DCBEND_INTLK_LTH_A",500,20,0,0,"PPS:CLTS:3:DCBEND_INTLK_LTH_A")
#! Field("PPS:CLTS:3:DCBEND_INTLK_LTH_A.VAL",16777215,1,"PPS:CLTS:3:DCBEND_INTLK_LTH_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi113") {
  field(DESC, "Port CLTS_RDA bit 113")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 113, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:3:SEP_INTLK_LTH_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:SEP_INTLK_LTH_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi113 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:SEP_INTLK_LTH_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:SEP_INTLK_LTH_A") {
  field(DESC, "LAT CL Septum Interlock")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb113",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb113")
#! Field("PLC:CLTS:PP13:CLTS_RDAb113.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb113.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb113.FLNK","PPS:CLTS:3:SEP_INTLK_LTH_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb113.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb113.VAL")
#! Record("PPS:CLTS:3:SEP_INTLK_LTH_A_calc",260,18,0,1,"PPS:CLTS:3:SEP_INTLK_LTH_A_calc")
#! Field("PPS:CLTS:3:SEP_INTLK_LTH_A_calc.INPA",16777215,0,"PPS:CLTS:3:SEP_INTLK_LTH_A_calc.INPA")
#! Link("PPS:CLTS:3:SEP_INTLK_LTH_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb113.VAL")
#! Field("PPS:CLTS:3:SEP_INTLK_LTH_A_calc.INPB",16777215,1,"PPS:CLTS:3:SEP_INTLK_LTH_A_calc.INPB")
#! Field("PPS:CLTS:3:SEP_INTLK_LTH_A_calc.OUT",16777215,1,"PPS:CLTS:3:SEP_INTLK_LTH_A_calc.OUT")
#! Link("PPS:CLTS:3:SEP_INTLK_LTH_A_calc.OUT","PPS:CLTS:3:SEP_INTLK_LTH_A.VAL")
#! Record("PPS:CLTS:3:SEP_INTLK_LTH_A",500,20,0,0,"PPS:CLTS:3:SEP_INTLK_LTH_A")
#! Field("PPS:CLTS:3:SEP_INTLK_LTH_A.VAL",16777215,1,"PPS:CLTS:3:SEP_INTLK_LTH_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi112") {
  field(DESC, "Port CLTS_RDA bit 112")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 112, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:3:MERGE_INTLK_LTH_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:MERGE_INTLK_LTH_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi112 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:MERGE_INTLK_LTH_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:MERGE_INTLK_LTH_A") {
  field(DESC, "LAT CL Merge Interlock")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb112",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb112")
#! Field("PLC:CLTS:PP13:CLTS_RDAb112.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb112.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb112.FLNK","PPS:CLTS:3:MERGE_INTLK_LTH_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb112.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb112.VAL")
#! Record("PPS:CLTS:3:MERGE_INTLK_LTH_A_calc",260,18,0,1,"PPS:CLTS:3:MERGE_INTLK_LTH_A_calc")
#! Field("PPS:CLTS:3:MERGE_INTLK_LTH_A_calc.INPA",16777215,0,"PPS:CLTS:3:MERGE_INTLK_LTH_A_calc.INPA")
#! Link("PPS:CLTS:3:MERGE_INTLK_LTH_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb112.VAL")
#! Field("PPS:CLTS:3:MERGE_INTLK_LTH_A_calc.INPB",16777215,1,"PPS:CLTS:3:MERGE_INTLK_LTH_A_calc.INPB")
#! Field("PPS:CLTS:3:MERGE_INTLK_LTH_A_calc.OUT",16777215,1,"PPS:CLTS:3:MERGE_INTLK_LTH_A_calc.OUT")
#! Link("PPS:CLTS:3:MERGE_INTLK_LTH_A_calc.OUT","PPS:CLTS:3:MERGE_INTLK_LTH_A.VAL")
#! Record("PPS:CLTS:3:MERGE_INTLK_LTH_A",500,20,0,0,"PPS:CLTS:3:MERGE_INTLK_LTH_A")
#! Field("PPS:CLTS:3:MERGE_INTLK_LTH_A.VAL",16777215,1,"PPS:CLTS:3:MERGE_INTLK_LTH_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi127") {
  field(DESC, "Port CLTS_RDA bit 127")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 127, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:1:HB_FAULT_LTH_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:1:HB_FAULT_LTH_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi127 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:1:HB_FAULT_LTH_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:1:HB_FAULT_LTH_A") {
  field(DESC, "LAT Heartbeat Fault")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb127",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb127")
#! Field("PLC:CLTS:PP13:CLTS_RDAb127.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb127.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb127.FLNK","PPS:CLTS:1:HB_FAULT_LTH_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb127.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb127.VAL")
#! Record("PPS:CLTS:1:HB_FAULT_LTH_A_calc",260,18,0,1,"PPS:CLTS:1:HB_FAULT_LTH_A_calc")
#! Field("PPS:CLTS:1:HB_FAULT_LTH_A_calc.INPA",16777215,0,"PPS:CLTS:1:HB_FAULT_LTH_A_calc.INPA")
#! Link("PPS:CLTS:1:HB_FAULT_LTH_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb127.VAL")
#! Field("PPS:CLTS:1:HB_FAULT_LTH_A_calc.INPB",16777215,1,"PPS:CLTS:1:HB_FAULT_LTH_A_calc.INPB")
#! Field("PPS:CLTS:1:HB_FAULT_LTH_A_calc.OUT",16777215,1,"PPS:CLTS:1:HB_FAULT_LTH_A_calc.OUT")
#! Link("PPS:CLTS:1:HB_FAULT_LTH_A_calc.OUT","PPS:CLTS:1:HB_FAULT_LTH_A.VAL")
#! Record("PPS:CLTS:1:HB_FAULT_LTH_A",500,20,0,0,"PPS:CLTS:1:HB_FAULT_LTH_A")
#! Field("PPS:CLTS:1:HB_FAULT_LTH_A.VAL",16777215,1,"PPS:CLTS:1:HB_FAULT_LTH_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi126") {
  field(DESC, "Port CLTS_RDA bit 126")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 126, 1, 1)")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(FLNK, "PPS:CLTS:3:KICK_OK_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:KICK_OK_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi126 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:KICK_OK_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:KICK_OK_A") {
  field(DESC, "RT CL-Kicker status OK")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb126",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb126")
#! Field("PLC:CLTS:PP13:CLTS_RDAb126.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb126.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb126.FLNK","PPS:CLTS:3:KICK_OK_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb126.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb126.VAL")
#! Record("PPS:CLTS:3:KICK_OK_A_calc",260,18,0,1,"PPS:CLTS:3:KICK_OK_A_calc")
#! Field("PPS:CLTS:3:KICK_OK_A_calc.INPA",16777215,0,"PPS:CLTS:3:KICK_OK_A_calc.INPA")
#! Link("PPS:CLTS:3:KICK_OK_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb126.VAL")
#! Field("PPS:CLTS:3:KICK_OK_A_calc.INPB",16777215,1,"PPS:CLTS:3:KICK_OK_A_calc.INPB")
#! Field("PPS:CLTS:3:KICK_OK_A_calc.OUT",16777215,1,"PPS:CLTS:3:KICK_OK_A_calc.OUT")
#! Link("PPS:CLTS:3:KICK_OK_A_calc.OUT","PPS:CLTS:3:KICK_OK_A.VAL")
#! Record("PPS:CLTS:3:KICK_OK_A",500,20,0,0,"PPS:CLTS:3:KICK_OK_A")
#! Field("PPS:CLTS:3:KICK_OK_A.VAL",16777215,1,"PPS:CLTS:3:KICK_OK_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi125") {
  field(DESC, "Port CLTS_RDA bit 125")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 125, 1, 1)")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(FLNK, "PPS:CLTS:3:DCBEND_OK_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:DCBEND_OK_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi125 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:DCBEND_OK_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:DCBEND_OK_A") {
  field(DESC, "RT CL-DC status OK")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb125",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb125")
#! Field("PLC:CLTS:PP13:CLTS_RDAb125.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb125.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb125.FLNK","PPS:CLTS:3:DCBEND_OK_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb125.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb125.VAL")
#! Record("PPS:CLTS:3:DCBEND_OK_A_calc",260,18,0,1,"PPS:CLTS:3:DCBEND_OK_A_calc")
#! Field("PPS:CLTS:3:DCBEND_OK_A_calc.INPA",16777215,0,"PPS:CLTS:3:DCBEND_OK_A_calc.INPA")
#! Link("PPS:CLTS:3:DCBEND_OK_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb125.VAL")
#! Field("PPS:CLTS:3:DCBEND_OK_A_calc.INPB",16777215,1,"PPS:CLTS:3:DCBEND_OK_A_calc.INPB")
#! Field("PPS:CLTS:3:DCBEND_OK_A_calc.OUT",16777215,1,"PPS:CLTS:3:DCBEND_OK_A_calc.OUT")
#! Link("PPS:CLTS:3:DCBEND_OK_A_calc.OUT","PPS:CLTS:3:DCBEND_OK_A.VAL")
#! Record("PPS:CLTS:3:DCBEND_OK_A",500,20,0,0,"PPS:CLTS:3:DCBEND_OK_A")
#! Field("PPS:CLTS:3:DCBEND_OK_A.VAL",16777215,1,"PPS:CLTS:3:DCBEND_OK_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi124") {
  field(DESC, "Port CLTS_RDA bit 124")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 124, 1, 1)")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(FLNK, "PPS:CLTS:3:SEP_OK_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:SEP_OK_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi124 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:SEP_OK_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:SEP_OK_A") {
  field(DESC, "RT CL-Septum status OK")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb124",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb124")
#! Field("PLC:CLTS:PP13:CLTS_RDAb124.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb124.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb124.FLNK","PPS:CLTS:3:SEP_OK_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb124.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb124.VAL")
#! Record("PPS:CLTS:3:SEP_OK_A_calc",260,18,0,1,"PPS:CLTS:3:SEP_OK_A_calc")
#! Field("PPS:CLTS:3:SEP_OK_A_calc.INPA",16777215,0,"PPS:CLTS:3:SEP_OK_A_calc.INPA")
#! Link("PPS:CLTS:3:SEP_OK_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb124.VAL")
#! Field("PPS:CLTS:3:SEP_OK_A_calc.INPB",16777215,1,"PPS:CLTS:3:SEP_OK_A_calc.INPB")
#! Field("PPS:CLTS:3:SEP_OK_A_calc.OUT",16777215,1,"PPS:CLTS:3:SEP_OK_A_calc.OUT")
#! Link("PPS:CLTS:3:SEP_OK_A_calc.OUT","PPS:CLTS:3:SEP_OK_A.VAL")
#! Record("PPS:CLTS:3:SEP_OK_A",500,20,0,0,"PPS:CLTS:3:SEP_OK_A")
#! Field("PPS:CLTS:3:SEP_OK_A.VAL",16777215,1,"PPS:CLTS:3:SEP_OK_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi123") {
  field(DESC, "Port CLTS_RDA bit 123")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 123, 1, 1)")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(FLNK, "PPS:CLTS:3:MERGE_OK_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:MERGE_OK_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi123 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:MERGE_OK_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:MERGE_OK_A") {
  field(DESC, "RT CL-Merge status OK")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb123",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb123")
#! Field("PLC:CLTS:PP13:CLTS_RDAb123.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb123.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb123.FLNK","PPS:CLTS:3:MERGE_OK_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb123.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb123.VAL")
#! Record("PPS:CLTS:3:MERGE_OK_A_calc",260,18,0,1,"PPS:CLTS:3:MERGE_OK_A_calc")
#! Field("PPS:CLTS:3:MERGE_OK_A_calc.INPA",16777215,0,"PPS:CLTS:3:MERGE_OK_A_calc.INPA")
#! Link("PPS:CLTS:3:MERGE_OK_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb123.VAL")
#! Field("PPS:CLTS:3:MERGE_OK_A_calc.INPB",16777215,1,"PPS:CLTS:3:MERGE_OK_A_calc.INPB")
#! Field("PPS:CLTS:3:MERGE_OK_A_calc.OUT",16777215,1,"PPS:CLTS:3:MERGE_OK_A_calc.OUT")
#! Link("PPS:CLTS:3:MERGE_OK_A_calc.OUT","PPS:CLTS:3:MERGE_OK_A.VAL")
#! Record("PPS:CLTS:3:MERGE_OK_A",500,20,0,0,"PPS:CLTS:3:MERGE_OK_A")
#! Field("PPS:CLTS:3:MERGE_OK_A.VAL",16777215,1,"PPS:CLTS:3:MERGE_OK_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi122") {
  field(DESC, "Port CLTS_RDA bit 122")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 122, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:3:KICK_FAULT_LTH_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:KICK_FAULT_LTH_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi122 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:KICK_FAULT_LTH_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:KICK_FAULT_LTH_A") {
  field(DESC, "LAT CL-Kicker status fault")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb122",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb122")
#! Field("PLC:CLTS:PP13:CLTS_RDAb122.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb122.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb122.FLNK","PPS:CLTS:3:KICK_FAULT_LTH_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb122.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb122.VAL")
#! Record("PPS:CLTS:3:KICK_FAULT_LTH_A_calc",260,18,0,1,"PPS:CLTS:3:KICK_FAULT_LTH_A_calc")
#! Field("PPS:CLTS:3:KICK_FAULT_LTH_A_calc.INPA",16777215,0,"PPS:CLTS:3:KICK_FAULT_LTH_A_calc.INPA")
#! Link("PPS:CLTS:3:KICK_FAULT_LTH_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb122.VAL")
#! Field("PPS:CLTS:3:KICK_FAULT_LTH_A_calc.INPB",16777215,1,"PPS:CLTS:3:KICK_FAULT_LTH_A_calc.INPB")
#! Field("PPS:CLTS:3:KICK_FAULT_LTH_A_calc.OUT",16777215,1,"PPS:CLTS:3:KICK_FAULT_LTH_A_calc.OUT")
#! Link("PPS:CLTS:3:KICK_FAULT_LTH_A_calc.OUT","PPS:CLTS:3:KICK_FAULT_LTH_A.VAL")
#! Record("PPS:CLTS:3:KICK_FAULT_LTH_A",500,20,0,0,"PPS:CLTS:3:KICK_FAULT_LTH_A")
#! Field("PPS:CLTS:3:KICK_FAULT_LTH_A.VAL",16777215,1,"PPS:CLTS:3:KICK_FAULT_LTH_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi121") {
  field(DESC, "Port CLTS_RDA bit 121")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 121, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:3:DCBEND_FAULT_LTH_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:DCBEND_FAULT_LTH_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi121 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:DCBEND_FAULT_LTH_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:DCBEND_FAULT_LTH_A") {
  field(DESC, "LAT CL-DC status fault")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb121",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb121")
#! Field("PLC:CLTS:PP13:CLTS_RDAb121.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb121.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb121.FLNK","PPS:CLTS:3:DCBEND_FAULT_LTH_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb121.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb121.VAL")
#! Record("PPS:CLTS:3:DCBEND_FAULT_LTH_A_calc",260,18,0,1,"PPS:CLTS:3:DCBEND_FAULT_LTH_A_calc")
#! Field("PPS:CLTS:3:DCBEND_FAULT_LTH_A_calc.INPA",16777215,0,"PPS:CLTS:3:DCBEND_FAULT_LTH_A_calc.INPA")
#! Link("PPS:CLTS:3:DCBEND_FAULT_LTH_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb121.VAL")
#! Field("PPS:CLTS:3:DCBEND_FAULT_LTH_A_calc.INPB",16777215,1,"PPS:CLTS:3:DCBEND_FAULT_LTH_A_calc.INPB")
#! Field("PPS:CLTS:3:DCBEND_FAULT_LTH_A_calc.OUT",16777215,1,"PPS:CLTS:3:DCBEND_FAULT_LTH_A_calc.OUT")
#! Link("PPS:CLTS:3:DCBEND_FAULT_LTH_A_calc.OUT","PPS:CLTS:3:DCBEND_FAULT_LTH_A.VAL")
#! Record("PPS:CLTS:3:DCBEND_FAULT_LTH_A",500,20,0,0,"PPS:CLTS:3:DCBEND_FAULT_LTH_A")
#! Field("PPS:CLTS:3:DCBEND_FAULT_LTH_A.VAL",16777215,1,"PPS:CLTS:3:DCBEND_FAULT_LTH_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi120") {
  field(DESC, "Port CLTS_RDA bit 120")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 120, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:3:SEP_FAULT_LTH_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:SEP_FAULT_LTH_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi120 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:SEP_FAULT_LTH_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:SEP_FAULT_LTH_A") {
  field(DESC, "LAT CL-Septum status fault")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb120",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb120")
#! Field("PLC:CLTS:PP13:CLTS_RDAb120.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb120.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb120.FLNK","PPS:CLTS:3:SEP_FAULT_LTH_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb120.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb120.VAL")
#! Record("PPS:CLTS:3:SEP_FAULT_LTH_A_calc",260,18,0,1,"PPS:CLTS:3:SEP_FAULT_LTH_A_calc")
#! Field("PPS:CLTS:3:SEP_FAULT_LTH_A_calc.INPA",16777215,0,"PPS:CLTS:3:SEP_FAULT_LTH_A_calc.INPA")
#! Link("PPS:CLTS:3:SEP_FAULT_LTH_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb120.VAL")
#! Field("PPS:CLTS:3:SEP_FAULT_LTH_A_calc.INPB",16777215,1,"PPS:CLTS:3:SEP_FAULT_LTH_A_calc.INPB")
#! Field("PPS:CLTS:3:SEP_FAULT_LTH_A_calc.OUT",16777215,1,"PPS:CLTS:3:SEP_FAULT_LTH_A_calc.OUT")
#! Link("PPS:CLTS:3:SEP_FAULT_LTH_A_calc.OUT","PPS:CLTS:3:SEP_FAULT_LTH_A.VAL")
#! Record("PPS:CLTS:3:SEP_FAULT_LTH_A",500,20,0,0,"PPS:CLTS:3:SEP_FAULT_LTH_A")
#! Field("PPS:CLTS:3:SEP_FAULT_LTH_A.VAL",16777215,1,"PPS:CLTS:3:SEP_FAULT_LTH_A.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP13:Bi135") {
  field(DESC, "Port CLTS_RDA bit 135")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDA, 135, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:3:MERGE_FAULT_LTH_A_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:MERGE_FAULT_LTH_A_calc") {
  field(INPA, "PLC:CLTS:PP13:Bi135 NPP MS")
  field(INPB, "PLC:CLTS:PP13:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:MERGE_FAULT_LTH_A PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:MERGE_FAULT_LTH_A") {
  field(DESC, "LAT CL-Merge status fault")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP13:CLTS_RDAb135",20,19,0,0,"PLC:CLTS:PP13:CLTS_RDAb135")
#! Field("PLC:CLTS:PP13:CLTS_RDAb135.FLNK",16777215,1,"PLC:CLTS:PP13:CLTS_RDAb135.FLNK")
#! Link("PLC:CLTS:PP13:CLTS_RDAb135.FLNK","PPS:CLTS:3:MERGE_FAULT_LTH_A_calc")
#! Field("PLC:CLTS:PP13:CLTS_RDAb135.VAL",16777215,0,"PLC:CLTS:PP13:CLTS_RDAb135.VAL")
#! Record("PPS:CLTS:3:MERGE_FAULT_LTH_A_calc",260,18,0,1,"PPS:CLTS:3:MERGE_FAULT_LTH_A_calc")
#! Field("PPS:CLTS:3:MERGE_FAULT_LTH_A_calc.INPA",16777215,0,"PPS:CLTS:3:MERGE_FAULT_LTH_A_calc.INPA")
#! Link("PPS:CLTS:3:MERGE_FAULT_LTH_A_calc.INPA","PLC:CLTS:PP13:CLTS_RDAb135.VAL")
#! Field("PPS:CLTS:3:MERGE_FAULT_LTH_A_calc.INPB",16777215,1,"PPS:CLTS:3:MERGE_FAULT_LTH_A_calc.INPB")
#! Field("PPS:CLTS:3:MERGE_FAULT_LTH_A_calc.OUT",16777215,1,"PPS:CLTS:3:MERGE_FAULT_LTH_A_calc.OUT")
#! Link("PPS:CLTS:3:MERGE_FAULT_LTH_A_calc.OUT","PPS:CLTS:3:MERGE_FAULT_LTH_A.VAL")
#! Record("PPS:CLTS:3:MERGE_FAULT_LTH_A",500,20,0,0,"PPS:CLTS:3:MERGE_FAULT_LTH_A")
#! Field("PPS:CLTS:3:MERGE_FAULT_LTH_A.VAL",16777215,1,"PPS:CLTS:3:MERGE_FAULT_LTH_A.VAL")
record(bo, "PPS:CLTS:1:RESET_INTLK_A") {
  field(DESC, "PPS_Interlock_Reset_A")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(CLTS_WRTA, 7, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "Reset")
   field(ASG,  "MCC")
}

record(bo, "PPS:CLTS:1:PAUSEHB_A") {
  field(DESC, "PPS_Pause_Heartbeat_A")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(CLTS_WRTA, 6, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "Reset")
   field(ASG,  "MCC")
}

#==============================================================================
#
# Abs:  PILZ PNOZ PLC interface for accessing the right table/segment
#
# Name: pilz-plc-request.template
#
# Facility: LCLS Personnel Protection Controls
#
# Auth: 11-Dec-2018, Garth Brown   (GWBROWN)
# Rev : dd-mmm-yyyy, Reviewer's Name  (USERNAME)
#
# To specify which registers to read/write, you need to set the table and
# segment (see PNOZ docs). This set of PVs keeps them set to the correct values
# for reading either virtual I/O points or program stats such as project checksum.
# The PNOZ PLC also has occasional communications dropouts, where the PLC stops
# responding and the TCP connection must be reset. This happens more frequently
# the more communication there is with the PLC.
# While the vendor offers a PNOZ model with integrated Ethernet port which
# allows readback at different modbus addresses instead of needing to set
# table/segment, that interface also allows remote access to secure registers
# and PLC programming. For safety, that type of remote access is not allowed in
# our system. All of their products that don't allow remote access beyond our
# safety specs also require table/segment setting to choose which registers to
# read/write.
#
#-----------------------------------------------------------------------------
#  Mod:
#
#==============================================================================
#

record(longout, "PLC:CLTS:PP13:REQ_TABLE") {
	field(DESC, "Table to read/write")
	field(VAL, "9")
	field(OUT, "PLC:CLTS:PP13:REQ_TABLE_OUT PP")
	field(HOPR, "128")
	field(LOPR, "0")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}

# All the data we're interested in is: Tables 1 and 9, segment 1
# We only need table 1 once for check sums that don't change, so
# read it for a short time during startup, then switch to table 9.
record(calcout, "PLC:CLTS:PP13:TABLE_CYCLER")
{
	field( OUT, "PLC:CLTS:PP13:REQ_TABLE PP")
	field( CALC, "A:=(A+1)%3600;A=20?1:9")
	field( INPA, "0")
	field( SCAN, ".5 second")
}

record(calcout, "PLC:CLTS:PP13:SEG_CYCLER")
{
	field( OUT, "PLC:CLTS:PP13:REQ_SEG PP")
	field( CALC, "1")
	field( INPA, "0")
	field( SCAN, ".5 second")
}

# Records for disabling PVs when their reqest table isn't active
record(calc, "PLC:CLTS:PP13:TABLE_9_SEG_1")
{
	field( INPA, "PLC:CLTS:PP13:REQ_TABLE CP")
	field( INPB, "PLC:CLTS:PP13:REQ_SEG CP")
	field( INPC, "PLC:CLTS:PP13:REQ_TABLE_IN CP")
	field( INPD, "PLC:CLTS:PP13:REQ_SEG_IN CP")
	field(CALC, "A=9 & B=1 & C=9 & D=1")
}

record(calc, "PLC:CLTS:PP13:TABLE_1_SEG_1")
{
	field( INPA, "PLC:CLTS:PP13:REQ_TABLE CP")
	field( INPB, "PLC:CLTS:PP13:REQ_SEG CP")
	field( INPC, "PLC:CLTS:PP13:REQ_TABLE_IN CP")
	field( INPD, "PLC:CLTS:PP13:REQ_SEG_IN CP")
	field(CALC, "A=1 & B=1 & C=1 & D=1")
}

# The target PVs don't use the data, but this has 8 forward links,
# the number we need, while the fanout record only has 6.
record(dfanout, "PLC:CLTS:PP13:REQ_TABLE_OUT") {
	field(OUTA, "PLC:CLTS:PP13:REQ_TABLE_BIT0_CALC.A PP")
	field(OUTB, "PLC:CLTS:PP13:REQ_TABLE_BIT1_CALC.A PP")
	field(OUTC, "PLC:CLTS:PP13:REQ_TABLE_BIT2_CALC.A PP")
	field(OUTD, "PLC:CLTS:PP13:REQ_TABLE_BIT3_CALC.A PP")
	field(OUTE, "PLC:CLTS:PP13:REQ_TABLE_BIT4_CALC.A PP")
	field(OUTF, "PLC:CLTS:PP13:REQ_TABLE_BIT5_CALC.A PP")
	field(OUTG, "PLC:CLTS:PP13:REQ_TABLE_BIT6_CALC.A PP")
	field(OUTH, "PLC:CLTS:PP13:REQ_TABLE_BIT7_CALC.A PP")
	field(SDIS, "PLC:CLTS:PP13:REQ_TABLE_IN.PACT")
}

# The simpler approach of writing to the table/segment every few seconds caused
# TCP dropouts to happen several times an hour, compared to every day or two
# when we only ever read/wrote table 9 segment 1. These calcout records reduce
# the dropouts to around 5 a day by only writing the bits that need to change.

record(calcout, "PLC:CLTS:PP13:REQ_TABLE_BIT0_CALC") {
	field(INPA, "PLC:CLTS:PP13:REQ_TABLE_OUT")
	field(INPB, "PLC:CLTS:PP13:TABLE_BIT0 MS")
	field(INPC, "PLC:CLTS:PP13:REQ_TABLE_BIT0 MS")
	field(CALC, "(B#C)||(B#(A&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "A&1")
	field(OUT, "PLC:CLTS:PP13:REQ_TABLE_BIT0 PP")
}

record(calcout, "PLC:CLTS:PP13:REQ_TABLE_BIT1_CALC") {
	field(INPA, "PLC:CLTS:PP13:REQ_TABLE_OUT")
	field(INPB, "PLC:CLTS:PP13:TABLE_BIT1 MS")
	field(INPC, "PLC:CLTS:PP13:REQ_TABLE_BIT1 MS")
	field(CALC, "(B#C)||(B#((A>>1)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>1)&1")
	field(OUT, "PLC:CLTS:PP13:REQ_TABLE_BIT1 PP")
}

record(calcout, "PLC:CLTS:PP13:REQ_TABLE_BIT2_CALC") {
	field(INPA, "PLC:CLTS:PP13:REQ_TABLE_OUT")
	field(INPB, "PLC:CLTS:PP13:TABLE_BIT2 MS")
	field(INPC, "PLC:CLTS:PP13:REQ_TABLE_BIT2 MS")
	field(CALC, "(B#C)||(B#((A>>2)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>2)&1")
	field(OUT, "PLC:CLTS:PP13:REQ_TABLE_BIT2 PP")
}

record(calcout, "PLC:CLTS:PP13:REQ_TABLE_BIT3_CALC") {
	field(INPA, "PLC:CLTS:PP13:REQ_TABLE_OUT")
	field(INPB, "PLC:CLTS:PP13:TABLE_BIT3 MS")
	field(INPC, "PLC:CLTS:PP13:REQ_TABLE_BIT3 MS")
	field(CALC, "(B#C)||(B#((A>>3)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>3)&1")
	field(OUT, "PLC:CLTS:PP13:REQ_TABLE_BIT3 PP")
}

record(calcout, "PLC:CLTS:PP13:REQ_TABLE_BIT4_CALC") {
	field(INPA, "PLC:CLTS:PP13:REQ_TABLE_OUT")
	field(INPB, "PLC:CLTS:PP13:TABLE_BIT4 MS")
	field(INPC, "PLC:CLTS:PP13:REQ_TABLE_BIT4 MS")
	field(CALC, "(B#C)||(B#((A>>4)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>4)&1")
	field(OUT, "PLC:CLTS:PP13:REQ_TABLE_BIT4 PP")
}

record(calcout, "PLC:CLTS:PP13:REQ_TABLE_BIT5_CALC") {
	field(INPA, "PLC:CLTS:PP13:REQ_TABLE_OUT")
	field(INPB, "PLC:CLTS:PP13:TABLE_BIT5 MS")
	field(INPC, "PLC:CLTS:PP13:REQ_TABLE_BIT5 MS")
	field(CALC, "(B#C)||(B#((A>>5)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>5)&1")
	field(OUT, "PLC:CLTS:PP13:REQ_TABLE_BIT5 PP")
}

record(calcout, "PLC:CLTS:PP13:REQ_TABLE_BIT6_CALC") {
	field(INPA, "PLC:CLTS:PP13:REQ_TABLE_OUT")
	field(INPB, "PLC:CLTS:PP13:TABLE_BIT6 MS")
	field(INPC, "PLC:CLTS:PP13:REQ_TABLE_BIT6 MS")
	field(CALC, "(B#C)||(B#((A>>6)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>6)&1")
	field(OUT, "PLC:CLTS:PP13:REQ_TABLE_BIT6 PP")
}

record(calcout, "PLC:CLTS:PP13:REQ_TABLE_BIT7_CALC") {
	field(INPA, "PLC:CLTS:PP13:REQ_TABLE_OUT")
	field(INPB, "PLC:CLTS:PP13:TABLE_BIT7 MS")
	field(INPC, "PLC:CLTS:PP13:REQ_TABLE_BIT7 MS")
	field(CALC, "(B#C)||(B#((A>>7)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>7)&1")
	field(OUT, "PLC:CLTS:PP13:REQ_TABLE_BIT7 PP")
}


record(calcout, "PLC:CLTS:PP13:REQ_TABLE_IN") {
	field(DESC, "Table readback")
	field(INPA, "PLC:CLTS:PP13:TABLE_BIT0 CP MS")
	field(INPB, "PLC:CLTS:PP13:TABLE_BIT1 CP MS")
	field(INPC, "PLC:CLTS:PP13:TABLE_BIT2 CP MS")
	field(INPD, "PLC:CLTS:PP13:TABLE_BIT3 CP MS")
	field(INPE, "PLC:CLTS:PP13:TABLE_BIT4 CP MS")
	field(INPF, "PLC:CLTS:PP13:TABLE_BIT5 CP MS")
	field(INPG, "PLC:CLTS:PP13:TABLE_BIT6 CP MS")
	field(INPH, "PLC:CLTS:PP13:TABLE_BIT7 CP MS")
	field(CALC, "A+B*2+C*4+D*8+E*16+F*32+G*64+H*128")
	field(OUT, "PLC:CLTS:PP13:REQ_TABLE PP MS")
	#field(SDIS, "PLC:CLTS:PP13:REQ_TABLE_OUT.PACT")
}


record(longout, "PLC:CLTS:PP13:REQ_SEG") {
	field(DESC, "Segment to read/write")
	field(VAL, "1")
	field(OUT, "PLC:CLTS:PP13:REQ_SEG_OUT PP")
	field(HOPR, "128")
	field(LOPR, "0")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}

# The target PVs don't use the data, but this has 8 forward links,
# the number we need, while the fanout record only has 6.
record(dfanout, "PLC:CLTS:PP13:REQ_SEG_OUT") {
	field(OUTA, "PLC:CLTS:PP13:REQ_SEG_BIT0_CALC.A PP")
	field(OUTB, "PLC:CLTS:PP13:REQ_SEG_BIT1_CALC.A PP")
	field(OUTC, "PLC:CLTS:PP13:REQ_SEG_BIT2_CALC.A PP")
	field(OUTD, "PLC:CLTS:PP13:REQ_SEG_BIT3_CALC.A PP")
	field(OUTE, "PLC:CLTS:PP13:REQ_SEG_BIT4_CALC.A PP")
	field(OUTF, "PLC:CLTS:PP13:REQ_SEG_BIT5_CALC.A PP")
	field(OUTG, "PLC:CLTS:PP13:REQ_SEG_BIT6_CALC.A PP")
	field(OUTH, "PLC:CLTS:PP13:REQ_SEG_BIT7_CALC.A PP")
	field(SDIS, "PLC:CLTS:PP13:REQ_SEG_IN.PACT")
}

record(calcout, "PLC:CLTS:PP13:REQ_SEG_BIT0_CALC") {
	field(INPA, "PLC:CLTS:PP13:REQ_SEG_OUT")
	field(INPB, "PLC:CLTS:PP13:SEG_BIT0 CP MS")
	field(CALC, "(B#C)||(B#(A&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "A&1")
	field(OUT, "PLC:CLTS:PP13:REQ_SEG_BIT0 PP")
}

record(calcout, "PLC:CLTS:PP13:REQ_SEG_BIT1_CALC") {
	field(INPA, "PLC:CLTS:PP13:REQ_SEG_OUT")
	field(INPB, "PLC:CLTS:PP13:SEG_BIT1 MS")
	field(INPC, "PLC:CLTS:PP13:REQ_SEG_BIT1 MS")
	field(CALC, "(B#C)||(B#((A>>1)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>1)&1")
	field(OUT, "PLC:CLTS:PP13:REQ_SEG_BIT1 PP")
}

record(calcout, "PLC:CLTS:PP13:REQ_SEG_BIT2_CALC") {
	field(INPA, "PLC:CLTS:PP13:REQ_SEG_OUT")
	field(INPB, "PLC:CLTS:PP13:SEG_BIT2 MS")
	field(INPC, "PLC:CLTS:PP13:REQ_SEG_BIT2 MS")
	field(CALC, "(B#C)||(B#((A>>2)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>2)&1")
	field(OUT, "PLC:CLTS:PP13:REQ_SEG_BIT2 PP")
}

record(calcout, "PLC:CLTS:PP13:REQ_SEG_BIT3_CALC") {
	field(INPA, "PLC:CLTS:PP13:REQ_SEG_OUT")
	field(INPB, "PLC:CLTS:PP13:SEG_BIT3 MS")
	field(INPC, "PLC:CLTS:PP13:REQ_SEG_BIT3 MS")
	field(CALC, "(B#C)||(B#((A>>3)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>3)&1")
	field(OUT, "PLC:CLTS:PP13:REQ_SEG_BIT3 PP")
}

record(calcout, "PLC:CLTS:PP13:REQ_SEG_BIT4_CALC") {
	field(INPA, "PLC:CLTS:PP13:REQ_SEG_OUT")
	field(INPB, "PLC:CLTS:PP13:SEG_BIT4 MS")
	field(INPC, "PLC:CLTS:PP13:REQ_SEG_BIT4 MS")
	field(CALC, "(B#C)||(B#((A>>4)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>4)&1")
	field(OUT, "PLC:CLTS:PP13:REQ_SEG_BIT4 PP")
}

record(calcout, "PLC:CLTS:PP13:REQ_SEG_BIT5_CALC") {
	field(INPA, "PLC:CLTS:PP13:REQ_SEG_OUT")
	field(INPB, "PLC:CLTS:PP13:SEG_BIT5 MS")
	field(INPC, "PLC:CLTS:PP13:REQ_SEG_BIT5 MS")
	field(CALC, "(B#C)||(B#((A>>5)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>5)&1")
	field(OUT, "PLC:CLTS:PP13:REQ_SEG_BIT5 PP")
}

record(calcout, "PLC:CLTS:PP13:REQ_SEG_BIT6_CALC") {
	field(INPA, "PLC:CLTS:PP13:REQ_SEG_OUT")
	field(INPB, "PLC:CLTS:PP13:SEG_BIT6 MS")
	field(INPC, "PLC:CLTS:PP13:REQ_SEG_BIT6 MS")
	field(CALC, "(B#C)||(B#((A>>6)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>6)&1")
	field(OUT, "PLC:CLTS:PP13:REQ_SEG_BIT6 PP")
}

record(calcout, "PLC:CLTS:PP13:REQ_SEG_BIT7_CALC") {
	field(INPA, "PLC:CLTS:PP13:REQ_SEG_OUT")
	field(INPB, "PLC:CLTS:PP13:SEG_BIT7 MS")
	field(INPC, "PLC:CLTS:PP13:REQ_SEG_BIT7 MS")
	field(CALC, "(B#C)||(B#((A>>7)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>7)&1")
	field(OUT, "PLC:CLTS:PP13:REQ_SEG_BIT7 PP")
}

record(calcout, "PLC:CLTS:PP13:REQ_SEG_IN") {
	field(DESC, "Segment readback")
	field(INPA, "PLC:CLTS:PP13:SEG_BIT0 CP MS")
	field(INPB, "PLC:CLTS:PP13:SEG_BIT1 CP MS")
	field(INPC, "PLC:CLTS:PP13:SEG_BIT2 CP MS")
	field(INPD, "PLC:CLTS:PP13:SEG_BIT3 CP MS")
	field(INPE, "PLC:CLTS:PP13:SEG_BIT4 CP MS")
	field(INPF, "PLC:CLTS:PP13:SEG_BIT5 CP MS")
	field(INPG, "PLC:CLTS:PP13:SEG_BIT6 CP MS")
	field(INPH, "PLC:CLTS:PP13:SEG_BIT7 CP MS")
	field(CALC, "A+B*2+C*4+D*8+E*16+F*32+G*64+H*128")
	field(OUT, "PLC:CLTS:PP13:REQ_SEG PP MS")
	field(SDIS, "PLC:CLTS:PP13:REQ_SEG_OUT.PACT")
}

record(bi, "PLC:CLTS:PP13:LED_X1") {
	field(DESC, "PPS-X1_LED")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDA, 24, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "MAJOR")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP13:LED_X2") {
	field(DESC, "PPS-X2_LED")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDA, 25, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "MAJOR")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP13:PWLED") {
	field(DESC, "ODM-Power_LED_A")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDA, 26, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "MAJOR")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP13:RUNLED") {
	field(DESC, "ODM-Run_LED_A")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDA, 27, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "MAJOR")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP13:DIAGLED") {
	field(DESC, "ODM-Diag_LED_A")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDA, 28, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP13:FAULTLED") {
	field(DESC, "ODM-Fault_LED_A")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDA, 29, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP13:IFAULTLED") {
	field(DESC, "ODM-IFault_LED_A")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDA, 30, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP13:OFAULTLED") {
	field(DESC, "ODM-OFault_LED_A")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDA, 31, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP13:TABLE_BIT7") {
	field(DESC, "Table Read bit 7")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDA, 32, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP13:TABLE_BIT6") {
	field(DESC, "Table Read bit 6")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDA, 33, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP13:TABLE_BIT5") {
	field(DESC, "Table Read bit 5")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDA, 34, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP13:TABLE_BIT4") {
	field(DESC, "Table Read bit 4")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDA, 35, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP13:TABLE_BIT3") {
	field(DESC, "Table Read bit 3")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDA, 36, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP13:TABLE_BIT2") {
	field(DESC, "Table Read bit 2")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDA, 37, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP13:TABLE_BIT1") {
	field(DESC, "Table Read bit 1")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDA, 38, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP13:TABLE_BIT0") {
	field(DESC, "Table Read bit 0")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDA, 39, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP13:SEG_BIT7") {
	field(DESC, "Segment Read bit 7")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDA, 40, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP13:SEG_BIT6") {
	field(DESC, "Segment Read bit 6")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDA, 41, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP13:SEG_BIT5") {
	field(DESC, "Segment Read bit 5")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDA, 42, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP13:SEG_BIT4") {
	field(DESC, "Segment Read bit 4")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDA, 43, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP13:SEG_BIT3") {
	field(DESC, "Segment Read bit 3")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDA, 44, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP13:SEG_BIT2") {
	field(DESC, "Segment Read bit 2")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDA, 45, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP13:SEG_BIT1") {
	field(DESC, "Segment Read bit 1")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDA, 46, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP13:SEG_BIT0") {
	field(DESC, "Segment Read bit 0")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDA, 47, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}


record(bo, "PLC:CLTS:PP13:REQ_TABLE_BIT7") {
	field(DESC, "Table Request bit 7")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTA, 32, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP13:REQ_TABLE_BIT6") {
	field(DESC, "Table Request bit 6")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTA, 33, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP13:REQ_TABLE_BIT5") {
	field(DESC, "Table Request bit 5")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTA, 34, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP13:REQ_TABLE_BIT4") {
	field(DESC, "Table Request bit 4")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTA, 35, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP13:REQ_TABLE_BIT3") {
	field(DESC, "Table Request bit 3")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTA, 36, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP13:REQ_TABLE_BIT2") {
	field(DESC, "Table Request bit 2")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTA, 37, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP13:REQ_TABLE_BIT1") {
	field(DESC, "Table Request bit 1")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTA, 38, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP13:REQ_TABLE_BIT0") {
	field(DESC, "Table Request bit 0")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTA, 39, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP13:REQ_SEG_BIT7") {
	field(DESC, "Segment Request bit 7")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTA, 40, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP13:REQ_SEG_BIT6") {
	field(DESC, "Segment Request bit 6")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTA, 41, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP13:REQ_SEG_BIT5") {
	field(DESC, "Segment Request bit 5")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTA, 42, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP13:REQ_SEG_BIT4") {
	field(DESC, "Segment Request bit 4")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTA, 43, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP13:REQ_SEG_BIT3") {
	field(DESC, "Segment Request bit 3")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTA, 44, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP13:REQ_SEG_BIT2") {
	field(DESC, "Segment Request bit 2")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTA, 45, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP13:REQ_SEG_BIT1") {
	field(DESC, "Segment Request bit 1")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTA, 46, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP13:REQ_SEG_BIT0") {
	field(DESC, "Segment Request bit 0")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTA, 47, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND


record(longin, "PLC:CLTS:PP13:w0") {
  field(DESC, "CLTS CHAINA Checksum")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_WDA, 0, 0xFFFF, 1)")
  field(ASG,  "Internal")
}

record(longin, "PLC:CLTS:PP13:w1") {
  field(DESC, "CLTS CHAINA Checksum")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_WDA, 1, 0xFFFF, 1)")
  field(ASG,  "Internal")
}

record(longin, "PLC:CLTS:PP13:w2") {
  field(DESC, "Active Table and Segment")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_WDA, 2, 0xFFFF, 1)")
  field(FLNK, "PLC:CLTS:PP13:CHECKSUM_SDIS PP MS")
  field(ASG,  "Internal")
}

record(calc, "PLC:CLTS:PP13:CHECKSUM_SDIS") {
  field(INPA, "PLC:CLTS:PP13:w2 NPP MS")
  field(CALC, "A = 0X0101")
}

record(longin, "PLC:CLTS:PP13:w3") {
  field(DESC, "CLTS CHAINA Checksum")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_WDA, 3, 0xFFFF, 1)")
  field(FLNK, "PLC:CLTS:PP13:CHECKSUM_SAFE PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:CLTS:PP13:CHECKSUM_SAFE_calc") {
  field(INPA, "PLC:CLTS:PP13:w3 PP MS")
  field(INPB, "PLC:CLTS:PP13:CHECKSUM_SDIS PP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:CLTS:PP13:CHECKSUM_SAFE PP MS")
  field(ASG,  "Internal")
}

record(longin, "PLC:CLTS:PP13:CHECKSUM_SAFE") {
  field(DESC, "Check Sum Safe")
  field(FLNK, "PLC:CLTS:PP13:CHECKSUM_SAFE_calc PP MS")
  info(autosaveFields_pass0, "VAL")
}

record(longin, "PLC:CLTS:PP13:w4") {
  field(DESC, "CLTS CHAINA Checksum")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_WDA, 4, 0xFFFF, 1)")
  field(FLNK, "PLC:CLTS:PP13:PROJ_CHECKSUM_calc")
  field(ASG,  "Internal")
}

record(calcout, "PLC:CLTS:PP13:PROJ_CHECKSUM_calc") {
  field(INPA, "PLC:CLTS:PP13:w4 NPP MS")
  field(INPB, "PLC:CLTS:PP13:CHECKSUM_SDIS NPP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:CLTS:PP13:PROJ_CHECKSUM PP MS")
  field(ASG,  "Internal")
}

record(longin, "PLC:CLTS:PP13:PROJ_CHECKSUM") {
  field(DESC, "Total Project Check Sum")
  info(autosaveFields_pass0, "VAL")
}

record(longin, "PLC:CLTS:PP13:w5") {
  field(DESC, "CLTS CHAINA Checksum")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_WDA, 5, 0xFFFF, 1)")
  field(FLNK, "PLC:CLTS:PP13:DAY_MONTH_calc")
  field(ASG,  "Internal")
}

record(calcout, "PLC:CLTS:PP13:DAY_MONTH_calc") {
  field(INPA, "PLC:CLTS:PP13:w5 NPP MS")
  field(INPB, "PLC:CLTS:PP13:CHECKSUM_SDIS NPP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:CLTS:PP13:DAY_MONTH PP MS")
  field(ASG,  "Internal")
}

record(longin, "PLC:CLTS:PP13:DAY_MONTH") {
  field(DESC, "Raw day and month")
  field(ASG,  "Internal")
}

record(calc, "PLC:CLTS:PP13:PROJ_MONTH") {
  field(DESC, "Project creation day")
  field(INPA, "PLC:CLTS:PP13:DAY_MONTH CP MS")
  field(CALC, "A & 0xFF")
  info(autosaveFields_pass0, "VAL")
}

record(calc, "PLC:CLTS:PP13:PROJ_DAY") {
  field(DESC, "Project creation month")
  field(INPA, "PLC:CLTS:PP13:DAY_MONTH CP MS")
  field(CALC, "A >> 8")
  info(autosaveFields_pass0, "VAL")
}

record(longin, "PLC:CLTS:PP13:w6") {
  field(DESC, "Checksum word 6")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_WDA, 6, 0xFFFF, 1)")
  field(FLNK, "PLC:CLTS:PP13:PROJ_YEAR_calc")
  field(ASG,  "Internal")
}

record(calcout, "PLC:CLTS:PP13:PROJ_YEAR_calc") {
  field(INPA, "PLC:CLTS:PP13:w6 NPP MS")
  field(INPB, "PLC:CLTS:PP13:CHECKSUM_SDIS NPP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:CLTS:PP13:PROJ_YEAR PP MS")
  field(ASG,  "Internal")
}

record(longin, "PLC:CLTS:PP13:PROJ_YEAR") {
  field(DESC, "Project creation year.")
  info(autosaveFields_pass0, "VAL")
}

record(longin, "PLC:CLTS:PP13:w7") {
  field(DESC, "Checksum word 7")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_WDA, 7, 0xFFFF, 1)")
  field(FLNK, "PLC:CLTS:PP13:OP_HRS_MSB_calc")
  field(ASG,  "Internal")
}

record(calcout, "PLC:CLTS:PP13:OP_HRS_MSB_calc") {
  field(INPA, "PLC:CLTS:PP13:w7 NPP MS")
  field(INPB, "PLC:CLTS:PP13:CHECKSUM_SDIS NPP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:CLTS:PP13:OP_HRS_MSB PP MS")
  field(ASG,  "Internal")
}

record(longin, "PLC:CLTS:PP13:OP_HRS_MSB") {
  field(DESC, "Operation hours upper byte")
  field(ASG,  "Internal")
}

record(longin, "PLC:CLTS:PP13:w8") {
  field(DESC, "Checksum word 8")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_WDA, 8, 0xFFFF, 1)")
  field(FLNK, "PLC:CLTS:PP13:OP_HRS_LSB_calc")
  field(ASG,  "Internal")
}

record(calcout, "PLC:CLTS:PP13:OP_HRS_LSB_calc") {
  field(INPA, "PLC:CLTS:PP13:w8 NPP MS")
  field(INPB, "PLC:CLTS:PP13:CHECKSUM_SDIS NPP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:CLTS:PP13:OP_HRS_LSB PP MS")
  field(ASG,  "Internal")
}

record(longin, "PLC:CLTS:PP13:OP_HRS_LSB") {
  field(DESC, "Operation hours lower byte")
  field(ASG,  "Internal")
}

record(calc, "PLC:CLTS:PP13:OP_HOURS") {
  field(INPA, "PLC:CLTS:PP13:OP_HRS_MSB CP MS")
  field(INPB, "PLC:CLTS:PP13:OP_HRS_LSB CP MS")
  field(CALC, "(A << 8)+(B>>8)")
  info(autosaveFields_pass0, "VAL")
}

record(mbbi, "PLC:CLTS:PP13:BASE_MODEL") {
  field(DTYP, "Raw Soft Channel")
  field(NOBT, "8")
  field(INP, "PLC:CLTS:PP13:OP_HRS_LSB CP MS")
  field(ZRVL, "0x00")
  field(ONVL, "0x02")
  field(TWVL, "0x04")
  field(THVL, "0x03")
  field(FRVL, "0x20")
  field(FVVL, "0x22")
  field(SXVL, "0x24")
  field(SVVL, "0x23")
  field(EIVL, "0x50")
  field(NIVL, "0x51")
  field(TEVL, "0x52")
  field(ZRST, "PNOZ m1p")
  field(ONST, "PNOZ m0p")
  field(TWST, "PNOZ m2p")
  field(THST, "PNOZ m3p")
  field(FRST, "PNOZ m1p ETH")
  field(FVST, "PNOZ m0p ETH")
  field(SXST, "PNOZ m2p ETH")
  field(SVST, "PNOZ m3p ETH")
  field(EIST, "PNOZ mm0p")
  field(NIST, "PNOZ mm0.1p")
  field(TEST, "PNOZ mm0.2p")
}

# End of file
# Template for I/O statistics

record(bo,"PLC:CLTS:PP13:RDHistEnable") {
    field(DTYP,"asynUInt32Digital")
    field(OUT,"@asynMask(CLTS_RDA 0 0xFFFF)ENABLE_HISTOGRAM")
    field(ZNAM,"Disable")
    field(ONAM,"Enable")
}

record(bo, "PLC:CLTS:PP13:RDStatistics") {
    field(SCAN, "10 second")
    field(FLNK, "PLC:CLTS:PP13:RDHist.PROC")
}

record(waveform,"PLC:CLTS:PP13:RDHist") {
    field(DTYP,"asynInt32ArrayIn")
    field(INP,"@asyn(CLTS_RDA 0)READ_HISTOGRAM")
    field(FTVL,"LONG")
    field(NELM,"200")  # This number should match driver
    field(FLNK,"PLC:CLTS:PP13:RDHistTimeAxis.PROC")
}

record(waveform,"PLC:CLTS:PP13:RDHistTimeAxis") {
    field(DTYP,"asynInt32ArrayIn")
    field(INP,"@asyn(CLTS_RDA 0)HISTOGRAM_TIME_AXIS")
    field(FTVL,"LONG")
    field(NELM,"200")  # This number should match driver
    field(FLNK,"PLC:CLTS:PP13:RDReadOK.PROC")
}

record(longout,"PLC:CLTS:PP13:RDMsPerBin") {
    field(DTYP,"asynInt32")
    field(OUT,"@asyn(CLTS_RDA 0)HISTOGRAM_BIN_TIME")
    field(DRVL,"0")
    field(VAL,"1")
    field(PINI,"1")
}

record(longin,"PLC:CLTS:PP13:RDReadOK") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_RDA 0)READ_OK")
    field(FLNK,"PLC:CLTS:PP13:RDWriteOK.PROC")
}

record(longin,"PLC:CLTS:PP13:RDWriteOK") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_RDA 0)WRITE_OK")
    field(FLNK,"PLC:CLTS:PP13:RDIOErrors.PROC")
}

record(longin,"PLC:CLTS:PP13:RDIOErrors") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_RDA 0)IO_ERRORS")
    field(FLNK,"PLC:CLTS:PP13:RDLastIOTime.PROC")
}

record(longin,"PLC:CLTS:PP13:RDLastIOTime") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_RDA 0)LAST_IO_TIME")
    field(FLNK,"PLC:CLTS:PP13:RDMaxIOTime.PROC")
}

record(longin,"PLC:CLTS:PP13:RDMaxIOTime") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_RDA 0)MAX_IO_TIME")
}
# Template for I/O statistics

record(bo,"PLC:CLTS:PP13:WRTHistEnable") {
    field(DTYP,"asynUInt32Digital")
    field(OUT,"@asynMask(CLTS_WRTA 0 0xFFFF)ENABLE_HISTOGRAM")
    field(ZNAM,"Disable")
    field(ONAM,"Enable")
}

record(bo, "PLC:CLTS:PP13:WRTStatistics") {
    field(SCAN, "10 second")
    field(FLNK, "PLC:CLTS:PP13:WRTHist.PROC")
}

record(waveform,"PLC:CLTS:PP13:WRTHist") {
    field(DTYP,"asynInt32ArrayIn")
    field(INP,"@asyn(CLTS_WRTA 0)READ_HISTOGRAM")
    field(FTVL,"LONG")
    field(NELM,"200")  # This number should match driver
    field(FLNK,"PLC:CLTS:PP13:WRTHistTimeAxis.PROC")
}

record(waveform,"PLC:CLTS:PP13:WRTHistTimeAxis") {
    field(DTYP,"asynInt32ArrayIn")
    field(INP,"@asyn(CLTS_WRTA 0)HISTOGRAM_TIME_AXIS")
    field(FTVL,"LONG")
    field(NELM,"200")  # This number should match driver
    field(FLNK,"PLC:CLTS:PP13:WRTReadOK.PROC")
}

record(longout,"PLC:CLTS:PP13:WRTMsPerBin") {
    field(DTYP,"asynInt32")
    field(OUT,"@asyn(CLTS_WRTA 0)HISTOGRAM_BIN_TIME")
    field(DRVL,"0")
    field(VAL,"1")
    field(PINI,"1")
}

record(longin,"PLC:CLTS:PP13:WRTReadOK") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_WRTA 0)READ_OK")
    field(FLNK,"PLC:CLTS:PP13:WRTWriteOK.PROC")
}

record(longin,"PLC:CLTS:PP13:WRTWriteOK") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_WRTA 0)WRITE_OK")
    field(FLNK,"PLC:CLTS:PP13:WRTIOErrors.PROC")
}

record(longin,"PLC:CLTS:PP13:WRTIOErrors") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_WRTA 0)IO_ERRORS")
    field(FLNK,"PLC:CLTS:PP13:WRTLastIOTime.PROC")
}

record(longin,"PLC:CLTS:PP13:WRTLastIOTime") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_WRTA 0)LAST_IO_TIME")
    field(FLNK,"PLC:CLTS:PP13:WRTMaxIOTime.PROC")
}

record(longin,"PLC:CLTS:PP13:WRTMaxIOTime") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_WRTA 0)MAX_IO_TIME")
}
# Template for I/O statistics

record(bo,"PLC:CLTS:PP13:WDHistEnable") {
    field(DTYP,"asynUInt32Digital")
    field(OUT,"@asynMask(CLTS_WDA 0 0xFFFF)ENABLE_HISTOGRAM")
    field(ZNAM,"Disable")
    field(ONAM,"Enable")
}

record(bo, "PLC:CLTS:PP13:WDStatistics") {
    field(SCAN, "10 second")
    field(FLNK, "PLC:CLTS:PP13:WDHist.PROC")
}

record(waveform,"PLC:CLTS:PP13:WDHist") {
    field(DTYP,"asynInt32ArrayIn")
    field(INP,"@asyn(CLTS_WDA 0)READ_HISTOGRAM")
    field(FTVL,"LONG")
    field(NELM,"200")  # This number should match driver
    field(FLNK,"PLC:CLTS:PP13:WDHistTimeAxis.PROC")
}

record(waveform,"PLC:CLTS:PP13:WDHistTimeAxis") {
    field(DTYP,"asynInt32ArrayIn")
    field(INP,"@asyn(CLTS_WDA 0)HISTOGRAM_TIME_AXIS")
    field(FTVL,"LONG")
    field(NELM,"200")  # This number should match driver
    field(FLNK,"PLC:CLTS:PP13:WDReadOK.PROC")
}

record(longout,"PLC:CLTS:PP13:WDMsPerBin") {
    field(DTYP,"asynInt32")
    field(OUT,"@asyn(CLTS_WDA 0)HISTOGRAM_BIN_TIME")
    field(DRVL,"0")
    field(VAL,"1")
    field(PINI,"1")
}

record(longin,"PLC:CLTS:PP13:WDReadOK") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_WDA 0)READ_OK")
    field(FLNK,"PLC:CLTS:PP13:WDWriteOK.PROC")
}

record(longin,"PLC:CLTS:PP13:WDWriteOK") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_WDA 0)WRITE_OK")
    field(FLNK,"PLC:CLTS:PP13:WDIOErrors.PROC")
}

record(longin,"PLC:CLTS:PP13:WDIOErrors") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_WDA 0)IO_ERRORS")
    field(FLNK,"PLC:CLTS:PP13:WDLastIOTime.PROC")
}

record(longin,"PLC:CLTS:PP13:WDLastIOTime") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_WDA 0)LAST_IO_TIME")
    field(FLNK,"PLC:CLTS:PP13:WDMaxIOTime.PROC")
}

record(longin,"PLC:CLTS:PP13:WDMaxIOTime") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_WDA 0)MAX_IO_TIME")
}
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi7") {
  field(DESC, "Port CLTS_RDB bit 7")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 7, 1, 1)")
  field(ZNAM, "Not_Enabled")
  field(ONAM, "Enabled")
  field(FLNK, "PPS:CLTS:1:HW_ENABLE_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:1:HW_ENABLE_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi7 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:1:HW_ENABLE_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:1:HW_ENABLE_B") {
  field(DESC, "RT-IN HW Enable")
  field(ZNAM, "Not_Enabled")
  field(ONAM, "Enabled")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb7",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb7")
#! Field("PLC:CLTS:PP14:CLTS_RDBb7.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb7.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb7.FLNK","PPS:CLTS:1:HW_ENABLE_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb7.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb7.VAL")
#! Record("PPS:CLTS:1:HW_ENABLE_B_calc",260,18,0,1,"PPS:CLTS:1:HW_ENABLE_B_calc")
#! Field("PPS:CLTS:1:HW_ENABLE_B_calc.INPA",16777215,0,"PPS:CLTS:1:HW_ENABLE_B_calc.INPA")
#! Link("PPS:CLTS:1:HW_ENABLE_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb7.VAL")
#! Field("PPS:CLTS:1:HW_ENABLE_B_calc.INPB",16777215,1,"PPS:CLTS:1:HW_ENABLE_B_calc.INPB")
#! Field("PPS:CLTS:1:HW_ENABLE_B_calc.OUT",16777215,1,"PPS:CLTS:1:HW_ENABLE_B_calc.OUT")
#! Link("PPS:CLTS:1:HW_ENABLE_B_calc.OUT","PPS:CLTS:1:HW_ENABLE_B.VAL")
#! Record("PPS:CLTS:1:HW_ENABLE_B",500,20,0,0,"PPS:CLTS:1:HW_ENABLE_B")
#! Field("PPS:CLTS:1:HW_ENABLE_B.VAL",16777215,1,"PPS:CLTS:1:HW_ENABLE_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi6") {
  field(DESC, "Port CLTS_RDB bit 6")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 6, 1, 1)")
  field(ZNAM, "NOT_OFF")
  field(ONAM, "OFF")
  field(FLNK, "PPS:CLTS:3:KICK_OFF_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:KICK_OFF_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi6 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:KICK_OFF_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:KICK_OFF_B") {
  field(DESC, "RT-IN CL-Kicker OFF status")
  field(ZNAM, "NOT_OFF")
  field(ONAM, "OFF")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb6",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb6")
#! Field("PLC:CLTS:PP14:CLTS_RDBb6.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb6.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb6.FLNK","PPS:CLTS:3:KICK_OFF_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb6.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb6.VAL")
#! Record("PPS:CLTS:3:KICK_OFF_B_calc",260,18,0,1,"PPS:CLTS:3:KICK_OFF_B_calc")
#! Field("PPS:CLTS:3:KICK_OFF_B_calc.INPA",16777215,0,"PPS:CLTS:3:KICK_OFF_B_calc.INPA")
#! Link("PPS:CLTS:3:KICK_OFF_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb6.VAL")
#! Field("PPS:CLTS:3:KICK_OFF_B_calc.INPB",16777215,1,"PPS:CLTS:3:KICK_OFF_B_calc.INPB")
#! Field("PPS:CLTS:3:KICK_OFF_B_calc.OUT",16777215,1,"PPS:CLTS:3:KICK_OFF_B_calc.OUT")
#! Link("PPS:CLTS:3:KICK_OFF_B_calc.OUT","PPS:CLTS:3:KICK_OFF_B.VAL")
#! Record("PPS:CLTS:3:KICK_OFF_B",500,20,0,0,"PPS:CLTS:3:KICK_OFF_B")
#! Field("PPS:CLTS:3:KICK_OFF_B.VAL",16777215,1,"PPS:CLTS:3:KICK_OFF_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi5") {
  field(DESC, "Port CLTS_RDB bit 5")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 5, 1, 1)")
  field(ZNAM, "NOT_OFF")
  field(ONAM, "OFF")
  field(FLNK, "PPS:CLTS:3:DCBEND_OFF_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:DCBEND_OFF_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi5 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:DCBEND_OFF_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:DCBEND_OFF_B") {
  field(DESC, "RT-IN CL-DC OFF status")
  field(ZNAM, "NOT_OFF")
  field(ONAM, "OFF")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb5",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb5")
#! Field("PLC:CLTS:PP14:CLTS_RDBb5.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb5.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb5.FLNK","PPS:CLTS:3:DCBEND_OFF_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb5.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb5.VAL")
#! Record("PPS:CLTS:3:DCBEND_OFF_B_calc",260,18,0,1,"PPS:CLTS:3:DCBEND_OFF_B_calc")
#! Field("PPS:CLTS:3:DCBEND_OFF_B_calc.INPA",16777215,0,"PPS:CLTS:3:DCBEND_OFF_B_calc.INPA")
#! Link("PPS:CLTS:3:DCBEND_OFF_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb5.VAL")
#! Field("PPS:CLTS:3:DCBEND_OFF_B_calc.INPB",16777215,1,"PPS:CLTS:3:DCBEND_OFF_B_calc.INPB")
#! Field("PPS:CLTS:3:DCBEND_OFF_B_calc.OUT",16777215,1,"PPS:CLTS:3:DCBEND_OFF_B_calc.OUT")
#! Link("PPS:CLTS:3:DCBEND_OFF_B_calc.OUT","PPS:CLTS:3:DCBEND_OFF_B.VAL")
#! Record("PPS:CLTS:3:DCBEND_OFF_B",500,20,0,0,"PPS:CLTS:3:DCBEND_OFF_B")
#! Field("PPS:CLTS:3:DCBEND_OFF_B.VAL",16777215,1,"PPS:CLTS:3:DCBEND_OFF_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi4") {
  field(DESC, "Port CLTS_RDB bit 4")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 4, 1, 1)")
  field(ZNAM, "NOT_OFF")
  field(ONAM, "OFF")
  field(FLNK, "PPS:CLTS:3:SEP_OFF_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:SEP_OFF_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi4 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:SEP_OFF_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:SEP_OFF_B") {
  field(DESC, "RT-IN CL-Septum OFF status")
  field(ZNAM, "NOT_OFF")
  field(ONAM, "OFF")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb4",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb4")
#! Field("PLC:CLTS:PP14:CLTS_RDBb4.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb4.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb4.FLNK","PPS:CLTS:3:SEP_OFF_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb4.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb4.VAL")
#! Record("PPS:CLTS:3:SEP_OFF_B_calc",260,18,0,1,"PPS:CLTS:3:SEP_OFF_B_calc")
#! Field("PPS:CLTS:3:SEP_OFF_B_calc.INPA",16777215,0,"PPS:CLTS:3:SEP_OFF_B_calc.INPA")
#! Link("PPS:CLTS:3:SEP_OFF_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb4.VAL")
#! Field("PPS:CLTS:3:SEP_OFF_B_calc.INPB",16777215,1,"PPS:CLTS:3:SEP_OFF_B_calc.INPB")
#! Field("PPS:CLTS:3:SEP_OFF_B_calc.OUT",16777215,1,"PPS:CLTS:3:SEP_OFF_B_calc.OUT")
#! Link("PPS:CLTS:3:SEP_OFF_B_calc.OUT","PPS:CLTS:3:SEP_OFF_B.VAL")
#! Record("PPS:CLTS:3:SEP_OFF_B",500,20,0,0,"PPS:CLTS:3:SEP_OFF_B")
#! Field("PPS:CLTS:3:SEP_OFF_B.VAL",16777215,1,"PPS:CLTS:3:SEP_OFF_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi3") {
  field(DESC, "Port CLTS_RDB bit 3")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 3, 1, 1)")
  field(ZNAM, "NOT_OFF")
  field(ONAM, "OFF")
  field(FLNK, "PPS:CLTS:3:MERGE_OFF_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:MERGE_OFF_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi3 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:MERGE_OFF_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:MERGE_OFF_B") {
  field(DESC, "RT-IN CL-Merge OFF status")
  field(ZNAM, "NOT_OFF")
  field(ONAM, "OFF")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb3",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb3")
#! Field("PLC:CLTS:PP14:CLTS_RDBb3.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb3.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb3.FLNK","PPS:CLTS:3:MERGE_OFF_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb3.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb3.VAL")
#! Record("PPS:CLTS:3:MERGE_OFF_B_calc",260,18,0,1,"PPS:CLTS:3:MERGE_OFF_B_calc")
#! Field("PPS:CLTS:3:MERGE_OFF_B_calc.INPA",16777215,0,"PPS:CLTS:3:MERGE_OFF_B_calc.INPA")
#! Link("PPS:CLTS:3:MERGE_OFF_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb3.VAL")
#! Field("PPS:CLTS:3:MERGE_OFF_B_calc.INPB",16777215,1,"PPS:CLTS:3:MERGE_OFF_B_calc.INPB")
#! Field("PPS:CLTS:3:MERGE_OFF_B_calc.OUT",16777215,1,"PPS:CLTS:3:MERGE_OFF_B_calc.OUT")
#! Link("PPS:CLTS:3:MERGE_OFF_B_calc.OUT","PPS:CLTS:3:MERGE_OFF_B.VAL")
#! Record("PPS:CLTS:3:MERGE_OFF_B",500,20,0,0,"PPS:CLTS:3:MERGE_OFF_B")
#! Field("PPS:CLTS:3:MERGE_OFF_B.VAL",16777215,1,"PPS:CLTS:3:MERGE_OFF_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi2") {
  field(DESC, "Port CLTS_RDB bit 2")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 2, 1, 1)")
  field(ZNAM, "NOT_OFF")
  field(ONAM, "OFF")
  field(FLNK, "PPS:LI28:3:HXR:KICKSEP_OFF_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:LI28:3:HXR:KICKSEP_OFF_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi2 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:LI28:3:HXR:KICKSEP_OFF_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:LI28:3:HXR:KICKSEP_OFF_B") {
  field(DESC, "RT-IN HX-KickerSepMrg Summary OFF")
  field(ZNAM, "NOT_OFF")
  field(ONAM, "OFF")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb2",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb2")
#! Field("PLC:CLTS:PP14:CLTS_RDBb2.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb2.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb2.FLNK","PPS:LI28:3:HXR:KICKSEP_OFF_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb2.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb2.VAL")
#! Record("PPS:LI28:3:HXR:KICKSEP_OFF_B_calc",260,18,0,1,"PPS:LI28:3:HXR:KICKSEP_OFF_B_calc")
#! Field("PPS:LI28:3:HXR:KICKSEP_OFF_B_calc.INPA",16777215,0,"PPS:LI28:3:HXR:KICKSEP_OFF_B_calc.INPA")
#! Link("PPS:LI28:3:HXR:KICKSEP_OFF_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb2.VAL")
#! Field("PPS:LI28:3:HXR:KICKSEP_OFF_B_calc.INPB",16777215,1,"PPS:LI28:3:HXR:KICKSEP_OFF_B_calc.INPB")
#! Field("PPS:LI28:3:HXR:KICKSEP_OFF_B_calc.OUT",16777215,1,"PPS:LI28:3:HXR:KICKSEP_OFF_B_calc.OUT")
#! Link("PPS:LI28:3:HXR:KICKSEP_OFF_B_calc.OUT","PPS:LI28:3:HXR:KICKSEP_OFF_B.VAL")
#! Record("PPS:LI28:3:HXR:KICKSEP_OFF_B",500,20,0,0,"PPS:LI28:3:HXR:KICKSEP_OFF_B")
#! Field("PPS:LI28:3:HXR:KICKSEP_OFF_B.VAL",16777215,1,"PPS:LI28:3:HXR:KICKSEP_OFF_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi1") {
  field(DESC, "Port CLTS_RDB bit 1")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 1, 1, 1)")
  field(ZNAM, "NOT_OFF")
  field(ONAM, "OFF")
  field(FLNK, "PPS:LI30:3:SXR:KICKSEP_OFF_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:LI30:3:SXR:KICKSEP_OFF_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi1 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:LI30:3:SXR:KICKSEP_OFF_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:LI30:3:SXR:KICKSEP_OFF_B") {
  field(DESC, "RT-IN SX-KickerSepMrg Summary OFF")
  field(ZNAM, "NOT_OFF")
  field(ONAM, "OFF")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb1",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb1")
#! Field("PLC:CLTS:PP14:CLTS_RDBb1.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb1.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb1.FLNK","PPS:LI30:3:SXR:KICKSEP_OFF_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb1.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb1.VAL")
#! Record("PPS:LI30:3:SXR:KICKSEP_OFF_B_calc",260,18,0,1,"PPS:LI30:3:SXR:KICKSEP_OFF_B_calc")
#! Field("PPS:LI30:3:SXR:KICKSEP_OFF_B_calc.INPA",16777215,0,"PPS:LI30:3:SXR:KICKSEP_OFF_B_calc.INPA")
#! Link("PPS:LI30:3:SXR:KICKSEP_OFF_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb1.VAL")
#! Field("PPS:LI30:3:SXR:KICKSEP_OFF_B_calc.INPB",16777215,1,"PPS:LI30:3:SXR:KICKSEP_OFF_B_calc.INPB")
#! Field("PPS:LI30:3:SXR:KICKSEP_OFF_B_calc.OUT",16777215,1,"PPS:LI30:3:SXR:KICKSEP_OFF_B_calc.OUT")
#! Link("PPS:LI30:3:SXR:KICKSEP_OFF_B_calc.OUT","PPS:LI30:3:SXR:KICKSEP_OFF_B.VAL")
#! Record("PPS:LI30:3:SXR:KICKSEP_OFF_B",500,20,0,0,"PPS:LI30:3:SXR:KICKSEP_OFF_B")
#! Field("PPS:LI30:3:SXR:KICKSEP_OFF_B.VAL",16777215,1,"PPS:LI30:3:SXR:KICKSEP_OFF_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi0") {
  field(DESC, "Port CLTS_RDB bit 0")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 0, 1, 1)")
  field(ZNAM, "NOT_IN")
  field(ONAM, "IN")
  field(FLNK, "STPR:CLTS:585:3:IN_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "STPR:CLTS:585:3:IN_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi0 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "STPR:CLTS:585:3:IN_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "STPR:CLTS:585:3:IN_B") {
  field(DESC, "RT-IN STP-CLTS IN")
  field(ZNAM, "NOT_IN")
  field(ONAM, "IN")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb0",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb0")
#! Field("PLC:CLTS:PP14:CLTS_RDBb0.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb0.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb0.FLNK","STPR:CLTS:585:3:IN_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb0.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb0.VAL")
#! Record("STPR:CLTS:585:3:IN_B_calc",260,18,0,1,"STPR:CLTS:585:3:IN_B_calc")
#! Field("STPR:CLTS:585:3:IN_B_calc.INPA",16777215,0,"STPR:CLTS:585:3:IN_B_calc.INPA")
#! Link("STPR:CLTS:585:3:IN_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb0.VAL")
#! Field("STPR:CLTS:585:3:IN_B_calc.INPB",16777215,1,"STPR:CLTS:585:3:IN_B_calc.INPB")
#! Field("STPR:CLTS:585:3:IN_B_calc.OUT",16777215,1,"STPR:CLTS:585:3:IN_B_calc.OUT")
#! Link("STPR:CLTS:585:3:IN_B_calc.OUT","STPR:CLTS:585:3:IN_B.VAL")
#! Record("STPR:CLTS:585:3:IN_B",500,20,0,0,"STPR:CLTS:585:3:IN_B")
#! Field("STPR:CLTS:585:3:IN_B.VAL",16777215,1,"STPR:CLTS:585:3:IN_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi15") {
  field(DESC, "Port CLTS_RDB bit 15")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 15, 1, 1)")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(FLNK, "STPR:BSYS:3:ST34_OUT_SUM_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "STPR:BSYS:3:ST34_OUT_SUM_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi15 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "STPR:BSYS:3:ST34_OUT_SUM_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "STPR:BSYS:3:ST34_OUT_SUM_B") {
  field(DESC, "RT-IN STP-34 Summary OUT")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb15",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb15")
#! Field("PLC:CLTS:PP14:CLTS_RDBb15.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb15.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb15.FLNK","STPR:BSYS:3:ST34_OUT_SUM_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb15.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb15.VAL")
#! Record("STPR:BSYS:3:ST34_OUT_SUM_B_calc",260,18,0,1,"STPR:BSYS:3:ST34_OUT_SUM_B_calc")
#! Field("STPR:BSYS:3:ST34_OUT_SUM_B_calc.INPA",16777215,0,"STPR:BSYS:3:ST34_OUT_SUM_B_calc.INPA")
#! Link("STPR:BSYS:3:ST34_OUT_SUM_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb15.VAL")
#! Field("STPR:BSYS:3:ST34_OUT_SUM_B_calc.INPB",16777215,1,"STPR:BSYS:3:ST34_OUT_SUM_B_calc.INPB")
#! Field("STPR:BSYS:3:ST34_OUT_SUM_B_calc.OUT",16777215,1,"STPR:BSYS:3:ST34_OUT_SUM_B_calc.OUT")
#! Link("STPR:BSYS:3:ST34_OUT_SUM_B_calc.OUT","STPR:BSYS:3:ST34_OUT_SUM_B.VAL")
#! Record("STPR:BSYS:3:ST34_OUT_SUM_B",500,20,0,0,"STPR:BSYS:3:ST34_OUT_SUM_B")
#! Field("STPR:BSYS:3:ST34_OUT_SUM_B.VAL",16777215,1,"STPR:BSYS:3:ST34_OUT_SUM_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi14") {
  field(DESC, "Port CLTS_RDB bit 14")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 14, 1, 1)")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(FLNK, "PPS:CLTS:1:HRTBT_INP_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:1:HRTBT_INP_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi14 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:1:HRTBT_INP_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:1:HRTBT_INP_B") {
  field(DESC, "RT-IN Heartbeat IN from opposite chain")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb14",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb14")
#! Field("PLC:CLTS:PP14:CLTS_RDBb14.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb14.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb14.FLNK","PPS:CLTS:1:HRTBT_INP_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb14.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb14.VAL")
#! Record("PPS:CLTS:1:HRTBT_INP_B_calc",260,18,0,1,"PPS:CLTS:1:HRTBT_INP_B_calc")
#! Field("PPS:CLTS:1:HRTBT_INP_B_calc.INPA",16777215,0,"PPS:CLTS:1:HRTBT_INP_B_calc.INPA")
#! Link("PPS:CLTS:1:HRTBT_INP_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb14.VAL")
#! Field("PPS:CLTS:1:HRTBT_INP_B_calc.INPB",16777215,1,"PPS:CLTS:1:HRTBT_INP_B_calc.INPB")
#! Field("PPS:CLTS:1:HRTBT_INP_B_calc.OUT",16777215,1,"PPS:CLTS:1:HRTBT_INP_B_calc.OUT")
#! Link("PPS:CLTS:1:HRTBT_INP_B_calc.OUT","PPS:CLTS:1:HRTBT_INP_B.VAL")
#! Record("PPS:CLTS:1:HRTBT_INP_B",500,20,0,0,"PPS:CLTS:1:HRTBT_INP_B")
#! Field("PPS:CLTS:1:HRTBT_INP_B.VAL",16777215,1,"PPS:CLTS:1:HRTBT_INP_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi13") {
  field(DESC, "Port CLTS_RDB bit 13")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 13, 1, 1)")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(FLNK, "PPS:CLTS:1:ACR_ENABLE_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:1:ACR_ENABLE_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi13 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:1:ACR_ENABLE_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:1:ACR_ENABLE_B") {
  field(DESC, "RT-IN CLTS Admin Enable (jumpered)")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb13",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb13")
#! Field("PLC:CLTS:PP14:CLTS_RDBb13.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb13.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb13.FLNK","PPS:CLTS:1:ACR_ENABLE_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb13.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb13.VAL")
#! Record("PPS:CLTS:1:ACR_ENABLE_B_calc",260,18,0,1,"PPS:CLTS:1:ACR_ENABLE_B_calc")
#! Field("PPS:CLTS:1:ACR_ENABLE_B_calc.INPA",16777215,0,"PPS:CLTS:1:ACR_ENABLE_B_calc.INPA")
#! Link("PPS:CLTS:1:ACR_ENABLE_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb13.VAL")
#! Field("PPS:CLTS:1:ACR_ENABLE_B_calc.INPB",16777215,1,"PPS:CLTS:1:ACR_ENABLE_B_calc.INPB")
#! Field("PPS:CLTS:1:ACR_ENABLE_B_calc.OUT",16777215,1,"PPS:CLTS:1:ACR_ENABLE_B_calc.OUT")
#! Link("PPS:CLTS:1:ACR_ENABLE_B_calc.OUT","PPS:CLTS:1:ACR_ENABLE_B.VAL")
#! Record("PPS:CLTS:1:ACR_ENABLE_B",500,20,0,0,"PPS:CLTS:1:ACR_ENABLE_B")
#! Field("PPS:CLTS:1:ACR_ENABLE_B.VAL",16777215,1,"PPS:CLTS:1:ACR_ENABLE_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi12") {
  field(DESC, "Port CLTS_RDB bit 12")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 12, 1, 1)")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(FLNK, "PPS:CLTS:1:HW_RESET_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:1:HW_RESET_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi12 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:1:HW_RESET_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:1:HW_RESET_B") {
  field(DESC, "RT-IN HW Reset")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb12",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb12")
#! Field("PLC:CLTS:PP14:CLTS_RDBb12.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb12.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb12.FLNK","PPS:CLTS:1:HW_RESET_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb12.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb12.VAL")
#! Record("PPS:CLTS:1:HW_RESET_B_calc",260,18,0,1,"PPS:CLTS:1:HW_RESET_B_calc")
#! Field("PPS:CLTS:1:HW_RESET_B_calc.INPA",16777215,0,"PPS:CLTS:1:HW_RESET_B_calc.INPA")
#! Link("PPS:CLTS:1:HW_RESET_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb12.VAL")
#! Field("PPS:CLTS:1:HW_RESET_B_calc.INPB",16777215,1,"PPS:CLTS:1:HW_RESET_B_calc.INPB")
#! Field("PPS:CLTS:1:HW_RESET_B_calc.OUT",16777215,1,"PPS:CLTS:1:HW_RESET_B_calc.OUT")
#! Link("PPS:CLTS:1:HW_RESET_B_calc.OUT","PPS:CLTS:1:HW_RESET_B.VAL")
#! Record("PPS:CLTS:1:HW_RESET_B",500,20,0,0,"PPS:CLTS:1:HW_RESET_B")
#! Field("PPS:CLTS:1:HW_RESET_B.VAL",16777215,1,"PPS:CLTS:1:HW_RESET_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi11") {
  field(DESC, "Port CLTS_RDB bit 11")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 11, 1, 1)")
  field(ZNAM, "Not_Complete")
  field(ONAM, "Complete")
  field(FLNK, "PPS:CLTS:3:KICK_INTLK_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:KICK_INTLK_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi11 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:KICK_INTLK_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:KICK_INTLK_B") {
  field(DESC, "RT-IN CL Kicker Interlock")
  field(ZNAM, "Not_Complete")
  field(ONAM, "Complete")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb11",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb11")
#! Field("PLC:CLTS:PP14:CLTS_RDBb11.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb11.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb11.FLNK","PPS:CLTS:3:KICK_INTLK_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb11.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb11.VAL")
#! Record("PPS:CLTS:3:KICK_INTLK_B_calc",260,18,0,1,"PPS:CLTS:3:KICK_INTLK_B_calc")
#! Field("PPS:CLTS:3:KICK_INTLK_B_calc.INPA",16777215,0,"PPS:CLTS:3:KICK_INTLK_B_calc.INPA")
#! Link("PPS:CLTS:3:KICK_INTLK_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb11.VAL")
#! Field("PPS:CLTS:3:KICK_INTLK_B_calc.INPB",16777215,1,"PPS:CLTS:3:KICK_INTLK_B_calc.INPB")
#! Field("PPS:CLTS:3:KICK_INTLK_B_calc.OUT",16777215,1,"PPS:CLTS:3:KICK_INTLK_B_calc.OUT")
#! Link("PPS:CLTS:3:KICK_INTLK_B_calc.OUT","PPS:CLTS:3:KICK_INTLK_B.VAL")
#! Record("PPS:CLTS:3:KICK_INTLK_B",500,20,0,0,"PPS:CLTS:3:KICK_INTLK_B")
#! Field("PPS:CLTS:3:KICK_INTLK_B.VAL",16777215,1,"PPS:CLTS:3:KICK_INTLK_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi10") {
  field(DESC, "Port CLTS_RDB bit 10")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 10, 1, 1)")
  field(ZNAM, "Not_Complete")
  field(ONAM, "Complete")
  field(FLNK, "PPS:CLTS:3:DCBEND_INTLK_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:DCBEND_INTLK_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi10 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:DCBEND_INTLK_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:DCBEND_INTLK_B") {
  field(DESC, "RT-IN CL DC Interlock")
  field(ZNAM, "Not_Complete")
  field(ONAM, "Complete")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb10",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb10")
#! Field("PLC:CLTS:PP14:CLTS_RDBb10.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb10.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb10.FLNK","PPS:CLTS:3:DCBEND_INTLK_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb10.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb10.VAL")
#! Record("PPS:CLTS:3:DCBEND_INTLK_B_calc",260,18,0,1,"PPS:CLTS:3:DCBEND_INTLK_B_calc")
#! Field("PPS:CLTS:3:DCBEND_INTLK_B_calc.INPA",16777215,0,"PPS:CLTS:3:DCBEND_INTLK_B_calc.INPA")
#! Link("PPS:CLTS:3:DCBEND_INTLK_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb10.VAL")
#! Field("PPS:CLTS:3:DCBEND_INTLK_B_calc.INPB",16777215,1,"PPS:CLTS:3:DCBEND_INTLK_B_calc.INPB")
#! Field("PPS:CLTS:3:DCBEND_INTLK_B_calc.OUT",16777215,1,"PPS:CLTS:3:DCBEND_INTLK_B_calc.OUT")
#! Link("PPS:CLTS:3:DCBEND_INTLK_B_calc.OUT","PPS:CLTS:3:DCBEND_INTLK_B.VAL")
#! Record("PPS:CLTS:3:DCBEND_INTLK_B",500,20,0,0,"PPS:CLTS:3:DCBEND_INTLK_B")
#! Field("PPS:CLTS:3:DCBEND_INTLK_B.VAL",16777215,1,"PPS:CLTS:3:DCBEND_INTLK_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi9") {
  field(DESC, "Port CLTS_RDB bit 9")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 9, 1, 1)")
  field(ZNAM, "Not_Complete")
  field(ONAM, "Complete")
  field(FLNK, "PPS:CLTS:3:SEP_INTLK_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:SEP_INTLK_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi9 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:SEP_INTLK_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:SEP_INTLK_B") {
  field(DESC, "RT-IN CL Septum Interlock")
  field(ZNAM, "Not_Complete")
  field(ONAM, "Complete")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb9",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb9")
#! Field("PLC:CLTS:PP14:CLTS_RDBb9.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb9.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb9.FLNK","PPS:CLTS:3:SEP_INTLK_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb9.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb9.VAL")
#! Record("PPS:CLTS:3:SEP_INTLK_B_calc",260,18,0,1,"PPS:CLTS:3:SEP_INTLK_B_calc")
#! Field("PPS:CLTS:3:SEP_INTLK_B_calc.INPA",16777215,0,"PPS:CLTS:3:SEP_INTLK_B_calc.INPA")
#! Link("PPS:CLTS:3:SEP_INTLK_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb9.VAL")
#! Field("PPS:CLTS:3:SEP_INTLK_B_calc.INPB",16777215,1,"PPS:CLTS:3:SEP_INTLK_B_calc.INPB")
#! Field("PPS:CLTS:3:SEP_INTLK_B_calc.OUT",16777215,1,"PPS:CLTS:3:SEP_INTLK_B_calc.OUT")
#! Link("PPS:CLTS:3:SEP_INTLK_B_calc.OUT","PPS:CLTS:3:SEP_INTLK_B.VAL")
#! Record("PPS:CLTS:3:SEP_INTLK_B",500,20,0,0,"PPS:CLTS:3:SEP_INTLK_B")
#! Field("PPS:CLTS:3:SEP_INTLK_B.VAL",16777215,1,"PPS:CLTS:3:SEP_INTLK_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi8") {
  field(DESC, "Port CLTS_RDB bit 8")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 8, 1, 1)")
  field(ZNAM, "Not_Complete")
  field(ONAM, "Complete")
  field(FLNK, "PPS:CLTS:3:MERGE_INTLK_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:MERGE_INTLK_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi8 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:MERGE_INTLK_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:MERGE_INTLK_B") {
  field(DESC, "RT-IN CL Merge Interlock")
  field(ZNAM, "Not_Complete")
  field(ONAM, "Complete")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb8",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb8")
#! Field("PLC:CLTS:PP14:CLTS_RDBb8.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb8.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb8.FLNK","PPS:CLTS:3:MERGE_INTLK_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb8.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb8.VAL")
#! Record("PPS:CLTS:3:MERGE_INTLK_B_calc",260,18,0,1,"PPS:CLTS:3:MERGE_INTLK_B_calc")
#! Field("PPS:CLTS:3:MERGE_INTLK_B_calc.INPA",16777215,0,"PPS:CLTS:3:MERGE_INTLK_B_calc.INPA")
#! Link("PPS:CLTS:3:MERGE_INTLK_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb8.VAL")
#! Field("PPS:CLTS:3:MERGE_INTLK_B_calc.INPB",16777215,1,"PPS:CLTS:3:MERGE_INTLK_B_calc.INPB")
#! Field("PPS:CLTS:3:MERGE_INTLK_B_calc.OUT",16777215,1,"PPS:CLTS:3:MERGE_INTLK_B_calc.OUT")
#! Link("PPS:CLTS:3:MERGE_INTLK_B_calc.OUT","PPS:CLTS:3:MERGE_INTLK_B.VAL")
#! Record("PPS:CLTS:3:MERGE_INTLK_B",500,20,0,0,"PPS:CLTS:3:MERGE_INTLK_B")
#! Field("PPS:CLTS:3:MERGE_INTLK_B.VAL",16777215,1,"PPS:CLTS:3:MERGE_INTLK_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi89") {
  field(DESC, "Port CLTS_RDB bit 89")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 89, 1, 1)")
  field(ZNAM, "NOT_ON")
  field(ONAM, "ON")
  field(FLNK, "PPS:CLTS:3:KICK_ON_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:KICK_ON_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi89 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:KICK_ON_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:KICK_ON_B") {
  field(DESC, "RT-OUT CL-Kicker ON status")
  field(ZNAM, "NOT_ON")
  field(ONAM, "ON")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb89",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb89")
#! Field("PLC:CLTS:PP14:CLTS_RDBb89.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb89.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb89.FLNK","PPS:CLTS:3:KICK_ON_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb89.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb89.VAL")
#! Record("PPS:CLTS:3:KICK_ON_B_calc",260,18,0,1,"PPS:CLTS:3:KICK_ON_B_calc")
#! Field("PPS:CLTS:3:KICK_ON_B_calc.INPA",16777215,0,"PPS:CLTS:3:KICK_ON_B_calc.INPA")
#! Link("PPS:CLTS:3:KICK_ON_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb89.VAL")
#! Field("PPS:CLTS:3:KICK_ON_B_calc.INPB",16777215,1,"PPS:CLTS:3:KICK_ON_B_calc.INPB")
#! Field("PPS:CLTS:3:KICK_ON_B_calc.OUT",16777215,1,"PPS:CLTS:3:KICK_ON_B_calc.OUT")
#! Link("PPS:CLTS:3:KICK_ON_B_calc.OUT","PPS:CLTS:3:KICK_ON_B.VAL")
#! Record("PPS:CLTS:3:KICK_ON_B",500,20,0,0,"PPS:CLTS:3:KICK_ON_B")
#! Field("PPS:CLTS:3:KICK_ON_B.VAL",16777215,1,"PPS:CLTS:3:KICK_ON_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi88") {
  field(DESC, "Port CLTS_RDB bit 88")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 88, 1, 1)")
  field(ZNAM, "NOT_ON")
  field(ONAM, "ON")
  field(FLNK, "PPS:CLTS:3:DCBEND_ON_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:DCBEND_ON_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi88 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:DCBEND_ON_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:DCBEND_ON_B") {
  field(DESC, "RT-OUT CL-DC ON status")
  field(ZNAM, "NOT_ON")
  field(ONAM, "ON")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb88",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb88")
#! Field("PLC:CLTS:PP14:CLTS_RDBb88.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb88.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb88.FLNK","PPS:CLTS:3:DCBEND_ON_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb88.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb88.VAL")
#! Record("PPS:CLTS:3:DCBEND_ON_B_calc",260,18,0,1,"PPS:CLTS:3:DCBEND_ON_B_calc")
#! Field("PPS:CLTS:3:DCBEND_ON_B_calc.INPA",16777215,0,"PPS:CLTS:3:DCBEND_ON_B_calc.INPA")
#! Link("PPS:CLTS:3:DCBEND_ON_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb88.VAL")
#! Field("PPS:CLTS:3:DCBEND_ON_B_calc.INPB",16777215,1,"PPS:CLTS:3:DCBEND_ON_B_calc.INPB")
#! Field("PPS:CLTS:3:DCBEND_ON_B_calc.OUT",16777215,1,"PPS:CLTS:3:DCBEND_ON_B_calc.OUT")
#! Link("PPS:CLTS:3:DCBEND_ON_B_calc.OUT","PPS:CLTS:3:DCBEND_ON_B.VAL")
#! Record("PPS:CLTS:3:DCBEND_ON_B",500,20,0,0,"PPS:CLTS:3:DCBEND_ON_B")
#! Field("PPS:CLTS:3:DCBEND_ON_B.VAL",16777215,1,"PPS:CLTS:3:DCBEND_ON_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi103") {
  field(DESC, "Port CLTS_RDB bit 103")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 103, 1, 1)")
  field(ZNAM, "NOT_ON")
  field(ONAM, "ON")
  field(FLNK, "PPS:CLTS:3:SEP_ON_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:SEP_ON_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi103 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:SEP_ON_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:SEP_ON_B") {
  field(DESC, "RT-OUT CL-Septum ON status")
  field(ZNAM, "NOT_ON")
  field(ONAM, "ON")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb103",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb103")
#! Field("PLC:CLTS:PP14:CLTS_RDBb103.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb103.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb103.FLNK","PPS:CLTS:3:SEP_ON_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb103.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb103.VAL")
#! Record("PPS:CLTS:3:SEP_ON_B_calc",260,18,0,1,"PPS:CLTS:3:SEP_ON_B_calc")
#! Field("PPS:CLTS:3:SEP_ON_B_calc.INPA",16777215,0,"PPS:CLTS:3:SEP_ON_B_calc.INPA")
#! Link("PPS:CLTS:3:SEP_ON_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb103.VAL")
#! Field("PPS:CLTS:3:SEP_ON_B_calc.INPB",16777215,1,"PPS:CLTS:3:SEP_ON_B_calc.INPB")
#! Field("PPS:CLTS:3:SEP_ON_B_calc.OUT",16777215,1,"PPS:CLTS:3:SEP_ON_B_calc.OUT")
#! Link("PPS:CLTS:3:SEP_ON_B_calc.OUT","PPS:CLTS:3:SEP_ON_B.VAL")
#! Record("PPS:CLTS:3:SEP_ON_B",500,20,0,0,"PPS:CLTS:3:SEP_ON_B")
#! Field("PPS:CLTS:3:SEP_ON_B.VAL",16777215,1,"PPS:CLTS:3:SEP_ON_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi102") {
  field(DESC, "Port CLTS_RDB bit 102")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 102, 1, 1)")
  field(ZNAM, "NOT_ON")
  field(ONAM, "ON")
  field(FLNK, "PPS:CLTS:3:MERGE_ON_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:MERGE_ON_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi102 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:MERGE_ON_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:MERGE_ON_B") {
  field(DESC, "RT-OUT CL-Merge ON status")
  field(ZNAM, "NOT_ON")
  field(ONAM, "ON")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb102",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb102")
#! Field("PLC:CLTS:PP14:CLTS_RDBb102.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb102.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb102.FLNK","PPS:CLTS:3:MERGE_ON_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb102.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb102.VAL")
#! Record("PPS:CLTS:3:MERGE_ON_B_calc",260,18,0,1,"PPS:CLTS:3:MERGE_ON_B_calc")
#! Field("PPS:CLTS:3:MERGE_ON_B_calc.INPA",16777215,0,"PPS:CLTS:3:MERGE_ON_B_calc.INPA")
#! Link("PPS:CLTS:3:MERGE_ON_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb102.VAL")
#! Field("PPS:CLTS:3:MERGE_ON_B_calc.INPB",16777215,1,"PPS:CLTS:3:MERGE_ON_B_calc.INPB")
#! Field("PPS:CLTS:3:MERGE_ON_B_calc.OUT",16777215,1,"PPS:CLTS:3:MERGE_ON_B_calc.OUT")
#! Link("PPS:CLTS:3:MERGE_ON_B_calc.OUT","PPS:CLTS:3:MERGE_ON_B.VAL")
#! Record("PPS:CLTS:3:MERGE_ON_B",500,20,0,0,"PPS:CLTS:3:MERGE_ON_B")
#! Field("PPS:CLTS:3:MERGE_ON_B.VAL",16777215,1,"PPS:CLTS:3:MERGE_ON_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi101") {
  field(DESC, "Port CLTS_RDB bit 101")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 101, 1, 1)")
  field(ZNAM, "NOT_PERMITTED")
  field(ONAM, "PERMITTED")
  field(FLNK, "PPS:CLTS:3:KICK_PERMIT_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:KICK_PERMIT_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi101 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:KICK_PERMIT_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:KICK_PERMIT_B") {
  field(DESC, "RT-OUT CL-Kicker Pwr Sply Pmt (Out)")
  field(ZNAM, "NOT_PERMITTED")
  field(ONAM, "PERMITTED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb101",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb101")
#! Field("PLC:CLTS:PP14:CLTS_RDBb101.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb101.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb101.FLNK","PPS:CLTS:3:KICK_PERMIT_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb101.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb101.VAL")
#! Record("PPS:CLTS:3:KICK_PERMIT_B_calc",260,18,0,1,"PPS:CLTS:3:KICK_PERMIT_B_calc")
#! Field("PPS:CLTS:3:KICK_PERMIT_B_calc.INPA",16777215,0,"PPS:CLTS:3:KICK_PERMIT_B_calc.INPA")
#! Link("PPS:CLTS:3:KICK_PERMIT_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb101.VAL")
#! Field("PPS:CLTS:3:KICK_PERMIT_B_calc.INPB",16777215,1,"PPS:CLTS:3:KICK_PERMIT_B_calc.INPB")
#! Field("PPS:CLTS:3:KICK_PERMIT_B_calc.OUT",16777215,1,"PPS:CLTS:3:KICK_PERMIT_B_calc.OUT")
#! Link("PPS:CLTS:3:KICK_PERMIT_B_calc.OUT","PPS:CLTS:3:KICK_PERMIT_B.VAL")
#! Record("PPS:CLTS:3:KICK_PERMIT_B",500,20,0,0,"PPS:CLTS:3:KICK_PERMIT_B")
#! Field("PPS:CLTS:3:KICK_PERMIT_B.VAL",16777215,1,"PPS:CLTS:3:KICK_PERMIT_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi100") {
  field(DESC, "Port CLTS_RDB bit 100")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 100, 1, 1)")
  field(ZNAM, "NOT_PERMITTED")
  field(ONAM, "PERMITTED")
  field(FLNK, "PPS:CLTS:3:DCBEND_PERMIT_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:DCBEND_PERMIT_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi100 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:DCBEND_PERMIT_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:DCBEND_PERMIT_B") {
  field(DESC, "RT-OUT CL-DC Pwr Sply Pmt (Out)")
  field(ZNAM, "NOT_PERMITTED")
  field(ONAM, "PERMITTED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb100",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb100")
#! Field("PLC:CLTS:PP14:CLTS_RDBb100.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb100.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb100.FLNK","PPS:CLTS:3:DCBEND_PERMIT_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb100.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb100.VAL")
#! Record("PPS:CLTS:3:DCBEND_PERMIT_B_calc",260,18,0,1,"PPS:CLTS:3:DCBEND_PERMIT_B_calc")
#! Field("PPS:CLTS:3:DCBEND_PERMIT_B_calc.INPA",16777215,0,"PPS:CLTS:3:DCBEND_PERMIT_B_calc.INPA")
#! Link("PPS:CLTS:3:DCBEND_PERMIT_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb100.VAL")
#! Field("PPS:CLTS:3:DCBEND_PERMIT_B_calc.INPB",16777215,1,"PPS:CLTS:3:DCBEND_PERMIT_B_calc.INPB")
#! Field("PPS:CLTS:3:DCBEND_PERMIT_B_calc.OUT",16777215,1,"PPS:CLTS:3:DCBEND_PERMIT_B_calc.OUT")
#! Link("PPS:CLTS:3:DCBEND_PERMIT_B_calc.OUT","PPS:CLTS:3:DCBEND_PERMIT_B.VAL")
#! Record("PPS:CLTS:3:DCBEND_PERMIT_B",500,20,0,0,"PPS:CLTS:3:DCBEND_PERMIT_B")
#! Field("PPS:CLTS:3:DCBEND_PERMIT_B.VAL",16777215,1,"PPS:CLTS:3:DCBEND_PERMIT_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi99") {
  field(DESC, "Port CLTS_RDB bit 99")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 99, 1, 1)")
  field(ZNAM, "NOT_PERMITTED")
  field(ONAM, "PERMITTED")
  field(FLNK, "PPS:CLTS:3:SEP_PERMIT_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:SEP_PERMIT_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi99 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:SEP_PERMIT_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:SEP_PERMIT_B") {
  field(DESC, "RT-OUT CL-Septum Pwr Sply Pmt (Out)")
  field(ZNAM, "NOT_PERMITTED")
  field(ONAM, "PERMITTED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb99",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb99")
#! Field("PLC:CLTS:PP14:CLTS_RDBb99.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb99.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb99.FLNK","PPS:CLTS:3:SEP_PERMIT_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb99.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb99.VAL")
#! Record("PPS:CLTS:3:SEP_PERMIT_B_calc",260,18,0,1,"PPS:CLTS:3:SEP_PERMIT_B_calc")
#! Field("PPS:CLTS:3:SEP_PERMIT_B_calc.INPA",16777215,0,"PPS:CLTS:3:SEP_PERMIT_B_calc.INPA")
#! Link("PPS:CLTS:3:SEP_PERMIT_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb99.VAL")
#! Field("PPS:CLTS:3:SEP_PERMIT_B_calc.INPB",16777215,1,"PPS:CLTS:3:SEP_PERMIT_B_calc.INPB")
#! Field("PPS:CLTS:3:SEP_PERMIT_B_calc.OUT",16777215,1,"PPS:CLTS:3:SEP_PERMIT_B_calc.OUT")
#! Link("PPS:CLTS:3:SEP_PERMIT_B_calc.OUT","PPS:CLTS:3:SEP_PERMIT_B.VAL")
#! Record("PPS:CLTS:3:SEP_PERMIT_B",500,20,0,0,"PPS:CLTS:3:SEP_PERMIT_B")
#! Field("PPS:CLTS:3:SEP_PERMIT_B.VAL",16777215,1,"PPS:CLTS:3:SEP_PERMIT_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi98") {
  field(DESC, "Port CLTS_RDB bit 98")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 98, 1, 1)")
  field(ZNAM, "NOT_PERMITTED")
  field(ONAM, "PERMITTED")
  field(FLNK, "PPS:CLTS:3:MERGE_PERMIT_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:MERGE_PERMIT_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi98 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:MERGE_PERMIT_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:MERGE_PERMIT_B") {
  field(DESC, "RT-OUT CL-Merge Pwr Sply Pmt (Out)")
  field(ZNAM, "NOT_PERMITTED")
  field(ONAM, "PERMITTED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb98",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb98")
#! Field("PLC:CLTS:PP14:CLTS_RDBb98.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb98.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb98.FLNK","PPS:CLTS:3:MERGE_PERMIT_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb98.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb98.VAL")
#! Record("PPS:CLTS:3:MERGE_PERMIT_B_calc",260,18,0,1,"PPS:CLTS:3:MERGE_PERMIT_B_calc")
#! Field("PPS:CLTS:3:MERGE_PERMIT_B_calc.INPA",16777215,0,"PPS:CLTS:3:MERGE_PERMIT_B_calc.INPA")
#! Link("PPS:CLTS:3:MERGE_PERMIT_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb98.VAL")
#! Field("PPS:CLTS:3:MERGE_PERMIT_B_calc.INPB",16777215,1,"PPS:CLTS:3:MERGE_PERMIT_B_calc.INPB")
#! Field("PPS:CLTS:3:MERGE_PERMIT_B_calc.OUT",16777215,1,"PPS:CLTS:3:MERGE_PERMIT_B_calc.OUT")
#! Link("PPS:CLTS:3:MERGE_PERMIT_B_calc.OUT","PPS:CLTS:3:MERGE_PERMIT_B.VAL")
#! Record("PPS:CLTS:3:MERGE_PERMIT_B",500,20,0,0,"PPS:CLTS:3:MERGE_PERMIT_B")
#! Field("PPS:CLTS:3:MERGE_PERMIT_B.VAL",16777215,1,"PPS:CLTS:3:MERGE_PERMIT_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi97") {
  field(DESC, "Port CLTS_RDB bit 97")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 97, 1, 1)")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(FLNK, "PPS:CLTS:1:HRTBT_OUTP_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:1:HRTBT_OUTP_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi97 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:1:HRTBT_OUTP_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:1:HRTBT_OUTP_B") {
  field(DESC, "RT-OUT Heartbeat OUT")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb97",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb97")
#! Field("PLC:CLTS:PP14:CLTS_RDBb97.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb97.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb97.FLNK","PPS:CLTS:1:HRTBT_OUTP_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb97.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb97.VAL")
#! Record("PPS:CLTS:1:HRTBT_OUTP_B_calc",260,18,0,1,"PPS:CLTS:1:HRTBT_OUTP_B_calc")
#! Field("PPS:CLTS:1:HRTBT_OUTP_B_calc.INPA",16777215,0,"PPS:CLTS:1:HRTBT_OUTP_B_calc.INPA")
#! Link("PPS:CLTS:1:HRTBT_OUTP_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb97.VAL")
#! Field("PPS:CLTS:1:HRTBT_OUTP_B_calc.INPB",16777215,1,"PPS:CLTS:1:HRTBT_OUTP_B_calc.INPB")
#! Field("PPS:CLTS:1:HRTBT_OUTP_B_calc.OUT",16777215,1,"PPS:CLTS:1:HRTBT_OUTP_B_calc.OUT")
#! Link("PPS:CLTS:1:HRTBT_OUTP_B_calc.OUT","PPS:CLTS:1:HRTBT_OUTP_B.VAL")
#! Record("PPS:CLTS:1:HRTBT_OUTP_B",500,20,0,0,"PPS:CLTS:1:HRTBT_OUTP_B")
#! Field("PPS:CLTS:1:HRTBT_OUTP_B.VAL",16777215,1,"PPS:CLTS:1:HRTBT_OUTP_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi96") {
  field(DESC, "Port CLTS_RDB bit 96")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 96, 1, 1)")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(FLNK, "PPS:CLTS:1:HWALRMWARN_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:1:HWALRMWARN_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi96 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:1:HWALRMWARN_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:1:HWALRMWARN_B") {
  field(DESC, "RT-OUT ACR Hardware alarm/warning")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb96",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb96")
#! Field("PLC:CLTS:PP14:CLTS_RDBb96.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb96.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb96.FLNK","PPS:CLTS:1:HWALRMWARN_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb96.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb96.VAL")
#! Record("PPS:CLTS:1:HWALRMWARN_B_calc",260,18,0,1,"PPS:CLTS:1:HWALRMWARN_B_calc")
#! Field("PPS:CLTS:1:HWALRMWARN_B_calc.INPA",16777215,0,"PPS:CLTS:1:HWALRMWARN_B_calc.INPA")
#! Link("PPS:CLTS:1:HWALRMWARN_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb96.VAL")
#! Field("PPS:CLTS:1:HWALRMWARN_B_calc.INPB",16777215,1,"PPS:CLTS:1:HWALRMWARN_B_calc.INPB")
#! Field("PPS:CLTS:1:HWALRMWARN_B_calc.OUT",16777215,1,"PPS:CLTS:1:HWALRMWARN_B_calc.OUT")
#! Link("PPS:CLTS:1:HWALRMWARN_B_calc.OUT","PPS:CLTS:1:HWALRMWARN_B.VAL")
#! Record("PPS:CLTS:1:HWALRMWARN_B",500,20,0,0,"PPS:CLTS:1:HWALRMWARN_B")
#! Field("PPS:CLTS:1:HWALRMWARN_B.VAL",16777215,1,"PPS:CLTS:1:HWALRMWARN_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi111") {
  field(DESC, "Port CLTS_RDB bit 111")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 111, 1, 1)")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(FLNK, "PPS:CLTS:1:HRTBT_OK_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:1:HRTBT_OK_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi111 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:1:HRTBT_OK_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:1:HRTBT_OK_B") {
  field(DESC, "RT Heartbeat OK")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb111",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb111")
#! Field("PLC:CLTS:PP14:CLTS_RDBb111.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb111.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb111.FLNK","PPS:CLTS:1:HRTBT_OK_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb111.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb111.VAL")
#! Record("PPS:CLTS:1:HRTBT_OK_B_calc",260,18,0,1,"PPS:CLTS:1:HRTBT_OK_B_calc")
#! Field("PPS:CLTS:1:HRTBT_OK_B_calc.INPA",16777215,0,"PPS:CLTS:1:HRTBT_OK_B_calc.INPA")
#! Link("PPS:CLTS:1:HRTBT_OK_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb111.VAL")
#! Field("PPS:CLTS:1:HRTBT_OK_B_calc.INPB",16777215,1,"PPS:CLTS:1:HRTBT_OK_B_calc.INPB")
#! Field("PPS:CLTS:1:HRTBT_OK_B_calc.OUT",16777215,1,"PPS:CLTS:1:HRTBT_OK_B_calc.OUT")
#! Link("PPS:CLTS:1:HRTBT_OK_B_calc.OUT","PPS:CLTS:1:HRTBT_OK_B.VAL")
#! Record("PPS:CLTS:1:HRTBT_OK_B",500,20,0,0,"PPS:CLTS:1:HRTBT_OK_B")
#! Field("PPS:CLTS:1:HRTBT_OK_B.VAL",16777215,1,"PPS:CLTS:1:HRTBT_OK_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi110") {
  field(DESC, "Port CLTS_RDB bit 110")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 110, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:1:HRTBT_OK_LTH_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:1:HRTBT_OK_LTH_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi110 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:1:HRTBT_OK_LTH_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:1:HRTBT_OK_LTH_B") {
  field(DESC, "LAT Heartbeat OK")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb110",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb110")
#! Field("PLC:CLTS:PP14:CLTS_RDBb110.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb110.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb110.FLNK","PPS:CLTS:1:HRTBT_OK_LTH_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb110.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb110.VAL")
#! Record("PPS:CLTS:1:HRTBT_OK_LTH_B_calc",260,18,0,1,"PPS:CLTS:1:HRTBT_OK_LTH_B_calc")
#! Field("PPS:CLTS:1:HRTBT_OK_LTH_B_calc.INPA",16777215,0,"PPS:CLTS:1:HRTBT_OK_LTH_B_calc.INPA")
#! Link("PPS:CLTS:1:HRTBT_OK_LTH_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb110.VAL")
#! Field("PPS:CLTS:1:HRTBT_OK_LTH_B_calc.INPB",16777215,1,"PPS:CLTS:1:HRTBT_OK_LTH_B_calc.INPB")
#! Field("PPS:CLTS:1:HRTBT_OK_LTH_B_calc.OUT",16777215,1,"PPS:CLTS:1:HRTBT_OK_LTH_B_calc.OUT")
#! Link("PPS:CLTS:1:HRTBT_OK_LTH_B_calc.OUT","PPS:CLTS:1:HRTBT_OK_LTH_B.VAL")
#! Record("PPS:CLTS:1:HRTBT_OK_LTH_B",500,20,0,0,"PPS:CLTS:1:HRTBT_OK_LTH_B")
#! Field("PPS:CLTS:1:HRTBT_OK_LTH_B.VAL",16777215,1,"PPS:CLTS:1:HRTBT_OK_LTH_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi109") {
  field(DESC, "Port CLTS_RDB bit 109")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 109, 1, 1)")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(FLNK, "PPS:CLTS:1:BCS_FAULT_OUT_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:1:BCS_FAULT_OUT_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi109 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:1:BCS_FAULT_OUT_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:1:BCS_FAULT_OUT_B") {
  field(DESC, "RT-OUT BCS Ok from PLC3")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb109",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb109")
#! Field("PLC:CLTS:PP14:CLTS_RDBb109.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb109.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb109.FLNK","PPS:CLTS:1:BCS_FAULT_OUT_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb109.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb109.VAL")
#! Record("PPS:CLTS:1:BCS_FAULT_OUT_B_calc",260,18,0,1,"PPS:CLTS:1:BCS_FAULT_OUT_B_calc")
#! Field("PPS:CLTS:1:BCS_FAULT_OUT_B_calc.INPA",16777215,0,"PPS:CLTS:1:BCS_FAULT_OUT_B_calc.INPA")
#! Link("PPS:CLTS:1:BCS_FAULT_OUT_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb109.VAL")
#! Field("PPS:CLTS:1:BCS_FAULT_OUT_B_calc.INPB",16777215,1,"PPS:CLTS:1:BCS_FAULT_OUT_B_calc.INPB")
#! Field("PPS:CLTS:1:BCS_FAULT_OUT_B_calc.OUT",16777215,1,"PPS:CLTS:1:BCS_FAULT_OUT_B_calc.OUT")
#! Link("PPS:CLTS:1:BCS_FAULT_OUT_B_calc.OUT","PPS:CLTS:1:BCS_FAULT_OUT_B.VAL")
#! Record("PPS:CLTS:1:BCS_FAULT_OUT_B",500,20,0,0,"PPS:CLTS:1:BCS_FAULT_OUT_B")
#! Field("PPS:CLTS:1:BCS_FAULT_OUT_B.VAL",16777215,1,"PPS:CLTS:1:BCS_FAULT_OUT_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi108") {
  field(DESC, "Port CLTS_RDB bit 108")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 108, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:3:KICK_OFF_LTH_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:KICK_OFF_LTH_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi108 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:KICK_OFF_LTH_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:KICK_OFF_LTH_B") {
  field(DESC, "LAT CL-Kicker OFF status")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb108",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb108")
#! Field("PLC:CLTS:PP14:CLTS_RDBb108.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb108.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb108.FLNK","PPS:CLTS:3:KICK_OFF_LTH_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb108.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb108.VAL")
#! Record("PPS:CLTS:3:KICK_OFF_LTH_B_calc",260,18,0,1,"PPS:CLTS:3:KICK_OFF_LTH_B_calc")
#! Field("PPS:CLTS:3:KICK_OFF_LTH_B_calc.INPA",16777215,0,"PPS:CLTS:3:KICK_OFF_LTH_B_calc.INPA")
#! Link("PPS:CLTS:3:KICK_OFF_LTH_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb108.VAL")
#! Field("PPS:CLTS:3:KICK_OFF_LTH_B_calc.INPB",16777215,1,"PPS:CLTS:3:KICK_OFF_LTH_B_calc.INPB")
#! Field("PPS:CLTS:3:KICK_OFF_LTH_B_calc.OUT",16777215,1,"PPS:CLTS:3:KICK_OFF_LTH_B_calc.OUT")
#! Link("PPS:CLTS:3:KICK_OFF_LTH_B_calc.OUT","PPS:CLTS:3:KICK_OFF_LTH_B.VAL")
#! Record("PPS:CLTS:3:KICK_OFF_LTH_B",500,20,0,0,"PPS:CLTS:3:KICK_OFF_LTH_B")
#! Field("PPS:CLTS:3:KICK_OFF_LTH_B.VAL",16777215,1,"PPS:CLTS:3:KICK_OFF_LTH_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi107") {
  field(DESC, "Port CLTS_RDB bit 107")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 107, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:3:DCBEND_OFF_LTH_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:DCBEND_OFF_LTH_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi107 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:DCBEND_OFF_LTH_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:DCBEND_OFF_LTH_B") {
  field(DESC, "LAT CL-DC OFF status")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb107",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb107")
#! Field("PLC:CLTS:PP14:CLTS_RDBb107.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb107.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb107.FLNK","PPS:CLTS:3:DCBEND_OFF_LTH_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb107.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb107.VAL")
#! Record("PPS:CLTS:3:DCBEND_OFF_LTH_B_calc",260,18,0,1,"PPS:CLTS:3:DCBEND_OFF_LTH_B_calc")
#! Field("PPS:CLTS:3:DCBEND_OFF_LTH_B_calc.INPA",16777215,0,"PPS:CLTS:3:DCBEND_OFF_LTH_B_calc.INPA")
#! Link("PPS:CLTS:3:DCBEND_OFF_LTH_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb107.VAL")
#! Field("PPS:CLTS:3:DCBEND_OFF_LTH_B_calc.INPB",16777215,1,"PPS:CLTS:3:DCBEND_OFF_LTH_B_calc.INPB")
#! Field("PPS:CLTS:3:DCBEND_OFF_LTH_B_calc.OUT",16777215,1,"PPS:CLTS:3:DCBEND_OFF_LTH_B_calc.OUT")
#! Link("PPS:CLTS:3:DCBEND_OFF_LTH_B_calc.OUT","PPS:CLTS:3:DCBEND_OFF_LTH_B.VAL")
#! Record("PPS:CLTS:3:DCBEND_OFF_LTH_B",500,20,0,0,"PPS:CLTS:3:DCBEND_OFF_LTH_B")
#! Field("PPS:CLTS:3:DCBEND_OFF_LTH_B.VAL",16777215,1,"PPS:CLTS:3:DCBEND_OFF_LTH_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi106") {
  field(DESC, "Port CLTS_RDB bit 106")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 106, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:3:SEP_OFF_LTH_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:SEP_OFF_LTH_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi106 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:SEP_OFF_LTH_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:SEP_OFF_LTH_B") {
  field(DESC, "LAT CL-Septum OFF status")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb106",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb106")
#! Field("PLC:CLTS:PP14:CLTS_RDBb106.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb106.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb106.FLNK","PPS:CLTS:3:SEP_OFF_LTH_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb106.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb106.VAL")
#! Record("PPS:CLTS:3:SEP_OFF_LTH_B_calc",260,18,0,1,"PPS:CLTS:3:SEP_OFF_LTH_B_calc")
#! Field("PPS:CLTS:3:SEP_OFF_LTH_B_calc.INPA",16777215,0,"PPS:CLTS:3:SEP_OFF_LTH_B_calc.INPA")
#! Link("PPS:CLTS:3:SEP_OFF_LTH_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb106.VAL")
#! Field("PPS:CLTS:3:SEP_OFF_LTH_B_calc.INPB",16777215,1,"PPS:CLTS:3:SEP_OFF_LTH_B_calc.INPB")
#! Field("PPS:CLTS:3:SEP_OFF_LTH_B_calc.OUT",16777215,1,"PPS:CLTS:3:SEP_OFF_LTH_B_calc.OUT")
#! Link("PPS:CLTS:3:SEP_OFF_LTH_B_calc.OUT","PPS:CLTS:3:SEP_OFF_LTH_B.VAL")
#! Record("PPS:CLTS:3:SEP_OFF_LTH_B",500,20,0,0,"PPS:CLTS:3:SEP_OFF_LTH_B")
#! Field("PPS:CLTS:3:SEP_OFF_LTH_B.VAL",16777215,1,"PPS:CLTS:3:SEP_OFF_LTH_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi105") {
  field(DESC, "Port CLTS_RDB bit 105")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 105, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:3:MERGE_OFF_LTH_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:MERGE_OFF_LTH_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi105 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:MERGE_OFF_LTH_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:MERGE_OFF_LTH_B") {
  field(DESC, "LAT CL-Merge OFF status")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb105",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb105")
#! Field("PLC:CLTS:PP14:CLTS_RDBb105.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb105.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb105.FLNK","PPS:CLTS:3:MERGE_OFF_LTH_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb105.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb105.VAL")
#! Record("PPS:CLTS:3:MERGE_OFF_LTH_B_calc",260,18,0,1,"PPS:CLTS:3:MERGE_OFF_LTH_B_calc")
#! Field("PPS:CLTS:3:MERGE_OFF_LTH_B_calc.INPA",16777215,0,"PPS:CLTS:3:MERGE_OFF_LTH_B_calc.INPA")
#! Link("PPS:CLTS:3:MERGE_OFF_LTH_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb105.VAL")
#! Field("PPS:CLTS:3:MERGE_OFF_LTH_B_calc.INPB",16777215,1,"PPS:CLTS:3:MERGE_OFF_LTH_B_calc.INPB")
#! Field("PPS:CLTS:3:MERGE_OFF_LTH_B_calc.OUT",16777215,1,"PPS:CLTS:3:MERGE_OFF_LTH_B_calc.OUT")
#! Link("PPS:CLTS:3:MERGE_OFF_LTH_B_calc.OUT","PPS:CLTS:3:MERGE_OFF_LTH_B.VAL")
#! Record("PPS:CLTS:3:MERGE_OFF_LTH_B",500,20,0,0,"PPS:CLTS:3:MERGE_OFF_LTH_B")
#! Field("PPS:CLTS:3:MERGE_OFF_LTH_B.VAL",16777215,1,"PPS:CLTS:3:MERGE_OFF_LTH_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi104") {
  field(DESC, "Port CLTS_RDB bit 104")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 104, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:LI28:3:HXR:KICKSEP_OFF_LTH_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:LI28:3:HXR:KICKSEP_OFF_LTH_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi104 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:LI28:3:HXR:KICKSEP_OFF_LTH_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:LI28:3:HXR:KICKSEP_OFF_LTH_B") {
  field(DESC, "LAT HX-KickerSepMrg Summary OFF")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb104",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb104")
#! Field("PLC:CLTS:PP14:CLTS_RDBb104.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb104.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb104.FLNK","PPS:LI28:3:HXR:KICKSEP_OFF_LTH_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb104.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb104.VAL")
#! Record("PPS:LI28:3:HXR:KICKSEP_OFF_LTH_B_calc",260,18,0,1,"PPS:LI28:3:HXR:KICKSEP_OFF_LTH_B_calc")
#! Field("PPS:LI28:3:HXR:KICKSEP_OFF_LTH_B_calc.INPA",16777215,0,"PPS:LI28:3:HXR:KICKSEP_OFF_LTH_B_calc.INPA")
#! Link("PPS:LI28:3:HXR:KICKSEP_OFF_LTH_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb104.VAL")
#! Field("PPS:LI28:3:HXR:KICKSEP_OFF_LTH_B_calc.INPB",16777215,1,"PPS:LI28:3:HXR:KICKSEP_OFF_LTH_B_calc.INPB")
#! Field("PPS:LI28:3:HXR:KICKSEP_OFF_LTH_B_calc.OUT",16777215,1,"PPS:LI28:3:HXR:KICKSEP_OFF_LTH_B_calc.OUT")
#! Link("PPS:LI28:3:HXR:KICKSEP_OFF_LTH_B_calc.OUT","PPS:LI28:3:HXR:KICKSEP_OFF_LTH_B.VAL")
#! Record("PPS:LI28:3:HXR:KICKSEP_OFF_LTH_B",500,20,0,0,"PPS:LI28:3:HXR:KICKSEP_OFF_LTH_B")
#! Field("PPS:LI28:3:HXR:KICKSEP_OFF_LTH_B.VAL",16777215,1,"PPS:LI28:3:HXR:KICKSEP_OFF_LTH_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi119") {
  field(DESC, "Port CLTS_RDB bit 119")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 119, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:LI30:3:SXR:KICKSEP_OFF_LTH_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:LI30:3:SXR:KICKSEP_OFF_LTH_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi119 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:LI30:3:SXR:KICKSEP_OFF_LTH_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:LI30:3:SXR:KICKSEP_OFF_LTH_B") {
  field(DESC, "LAT SX-KickerSepMrg Summary OFF")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb119",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb119")
#! Field("PLC:CLTS:PP14:CLTS_RDBb119.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb119.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb119.FLNK","PPS:LI30:3:SXR:KICKSEP_OFF_LTH_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb119.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb119.VAL")
#! Record("PPS:LI30:3:SXR:KICKSEP_OFF_LTH_B_calc",260,18,0,1,"PPS:LI30:3:SXR:KICKSEP_OFF_LTH_B_calc")
#! Field("PPS:LI30:3:SXR:KICKSEP_OFF_LTH_B_calc.INPA",16777215,0,"PPS:LI30:3:SXR:KICKSEP_OFF_LTH_B_calc.INPA")
#! Link("PPS:LI30:3:SXR:KICKSEP_OFF_LTH_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb119.VAL")
#! Field("PPS:LI30:3:SXR:KICKSEP_OFF_LTH_B_calc.INPB",16777215,1,"PPS:LI30:3:SXR:KICKSEP_OFF_LTH_B_calc.INPB")
#! Field("PPS:LI30:3:SXR:KICKSEP_OFF_LTH_B_calc.OUT",16777215,1,"PPS:LI30:3:SXR:KICKSEP_OFF_LTH_B_calc.OUT")
#! Link("PPS:LI30:3:SXR:KICKSEP_OFF_LTH_B_calc.OUT","PPS:LI30:3:SXR:KICKSEP_OFF_LTH_B.VAL")
#! Record("PPS:LI30:3:SXR:KICKSEP_OFF_LTH_B",500,20,0,0,"PPS:LI30:3:SXR:KICKSEP_OFF_LTH_B")
#! Field("PPS:LI30:3:SXR:KICKSEP_OFF_LTH_B.VAL",16777215,1,"PPS:LI30:3:SXR:KICKSEP_OFF_LTH_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi118") {
  field(DESC, "Port CLTS_RDB bit 118")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 118, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "STPR:CLTS:585:3:IN_LTH_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "STPR:CLTS:585:3:IN_LTH_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi118 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "STPR:CLTS:585:3:IN_LTH_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "STPR:CLTS:585:3:IN_LTH_B") {
  field(DESC, "LAT STP-CLTS IN")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb118",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb118")
#! Field("PLC:CLTS:PP14:CLTS_RDBb118.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb118.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb118.FLNK","STPR:CLTS:585:3:IN_LTH_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb118.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb118.VAL")
#! Record("STPR:CLTS:585:3:IN_LTH_B_calc",260,18,0,1,"STPR:CLTS:585:3:IN_LTH_B_calc")
#! Field("STPR:CLTS:585:3:IN_LTH_B_calc.INPA",16777215,0,"STPR:CLTS:585:3:IN_LTH_B_calc.INPA")
#! Link("STPR:CLTS:585:3:IN_LTH_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb118.VAL")
#! Field("STPR:CLTS:585:3:IN_LTH_B_calc.INPB",16777215,1,"STPR:CLTS:585:3:IN_LTH_B_calc.INPB")
#! Field("STPR:CLTS:585:3:IN_LTH_B_calc.OUT",16777215,1,"STPR:CLTS:585:3:IN_LTH_B_calc.OUT")
#! Link("STPR:CLTS:585:3:IN_LTH_B_calc.OUT","STPR:CLTS:585:3:IN_LTH_B.VAL")
#! Record("STPR:CLTS:585:3:IN_LTH_B",500,20,0,0,"STPR:CLTS:585:3:IN_LTH_B")
#! Field("STPR:CLTS:585:3:IN_LTH_B.VAL",16777215,1,"STPR:CLTS:585:3:IN_LTH_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi117") {
  field(DESC, "Port CLTS_RDB bit 117")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 117, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "STPR:BSYS:3:ST34_OUT_LTH_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "STPR:BSYS:3:ST34_OUT_LTH_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi117 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "STPR:BSYS:3:ST34_OUT_LTH_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "STPR:BSYS:3:ST34_OUT_LTH_B") {
  field(DESC, "LAT STP-34 Summary OUT")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb117",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb117")
#! Field("PLC:CLTS:PP14:CLTS_RDBb117.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb117.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb117.FLNK","STPR:BSYS:3:ST34_OUT_LTH_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb117.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb117.VAL")
#! Record("STPR:BSYS:3:ST34_OUT_LTH_B_calc",260,18,0,1,"STPR:BSYS:3:ST34_OUT_LTH_B_calc")
#! Field("STPR:BSYS:3:ST34_OUT_LTH_B_calc.INPA",16777215,0,"STPR:BSYS:3:ST34_OUT_LTH_B_calc.INPA")
#! Link("STPR:BSYS:3:ST34_OUT_LTH_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb117.VAL")
#! Field("STPR:BSYS:3:ST34_OUT_LTH_B_calc.INPB",16777215,1,"STPR:BSYS:3:ST34_OUT_LTH_B_calc.INPB")
#! Field("STPR:BSYS:3:ST34_OUT_LTH_B_calc.OUT",16777215,1,"STPR:BSYS:3:ST34_OUT_LTH_B_calc.OUT")
#! Link("STPR:BSYS:3:ST34_OUT_LTH_B_calc.OUT","STPR:BSYS:3:ST34_OUT_LTH_B.VAL")
#! Record("STPR:BSYS:3:ST34_OUT_LTH_B",500,20,0,0,"STPR:BSYS:3:ST34_OUT_LTH_B")
#! Field("STPR:BSYS:3:ST34_OUT_LTH_B.VAL",16777215,1,"STPR:BSYS:3:ST34_OUT_LTH_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi116") {
  field(DESC, "Port CLTS_RDB bit 116")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 116, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:1:ACR_ENABLE_LTH_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:1:ACR_ENABLE_LTH_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi116 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:1:ACR_ENABLE_LTH_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:1:ACR_ENABLE_LTH_B") {
  field(DESC, "LAT CLTS Admin Enable")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb116",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb116")
#! Field("PLC:CLTS:PP14:CLTS_RDBb116.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb116.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb116.FLNK","PPS:CLTS:1:ACR_ENABLE_LTH_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb116.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb116.VAL")
#! Record("PPS:CLTS:1:ACR_ENABLE_LTH_B_calc",260,18,0,1,"PPS:CLTS:1:ACR_ENABLE_LTH_B_calc")
#! Field("PPS:CLTS:1:ACR_ENABLE_LTH_B_calc.INPA",16777215,0,"PPS:CLTS:1:ACR_ENABLE_LTH_B_calc.INPA")
#! Link("PPS:CLTS:1:ACR_ENABLE_LTH_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb116.VAL")
#! Field("PPS:CLTS:1:ACR_ENABLE_LTH_B_calc.INPB",16777215,1,"PPS:CLTS:1:ACR_ENABLE_LTH_B_calc.INPB")
#! Field("PPS:CLTS:1:ACR_ENABLE_LTH_B_calc.OUT",16777215,1,"PPS:CLTS:1:ACR_ENABLE_LTH_B_calc.OUT")
#! Link("PPS:CLTS:1:ACR_ENABLE_LTH_B_calc.OUT","PPS:CLTS:1:ACR_ENABLE_LTH_B.VAL")
#! Record("PPS:CLTS:1:ACR_ENABLE_LTH_B",500,20,0,0,"PPS:CLTS:1:ACR_ENABLE_LTH_B")
#! Field("PPS:CLTS:1:ACR_ENABLE_LTH_B.VAL",16777215,1,"PPS:CLTS:1:ACR_ENABLE_LTH_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi115") {
  field(DESC, "Port CLTS_RDB bit 115")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 115, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:3:KICK_INTLK_LTH_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:KICK_INTLK_LTH_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi115 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:KICK_INTLK_LTH_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:KICK_INTLK_LTH_B") {
  field(DESC, "LAT CL Kicker Interlock")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb115",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb115")
#! Field("PLC:CLTS:PP14:CLTS_RDBb115.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb115.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb115.FLNK","PPS:CLTS:3:KICK_INTLK_LTH_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb115.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb115.VAL")
#! Record("PPS:CLTS:3:KICK_INTLK_LTH_B_calc",260,18,0,1,"PPS:CLTS:3:KICK_INTLK_LTH_B_calc")
#! Field("PPS:CLTS:3:KICK_INTLK_LTH_B_calc.INPA",16777215,0,"PPS:CLTS:3:KICK_INTLK_LTH_B_calc.INPA")
#! Link("PPS:CLTS:3:KICK_INTLK_LTH_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb115.VAL")
#! Field("PPS:CLTS:3:KICK_INTLK_LTH_B_calc.INPB",16777215,1,"PPS:CLTS:3:KICK_INTLK_LTH_B_calc.INPB")
#! Field("PPS:CLTS:3:KICK_INTLK_LTH_B_calc.OUT",16777215,1,"PPS:CLTS:3:KICK_INTLK_LTH_B_calc.OUT")
#! Link("PPS:CLTS:3:KICK_INTLK_LTH_B_calc.OUT","PPS:CLTS:3:KICK_INTLK_LTH_B.VAL")
#! Record("PPS:CLTS:3:KICK_INTLK_LTH_B",500,20,0,0,"PPS:CLTS:3:KICK_INTLK_LTH_B")
#! Field("PPS:CLTS:3:KICK_INTLK_LTH_B.VAL",16777215,1,"PPS:CLTS:3:KICK_INTLK_LTH_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi114") {
  field(DESC, "Port CLTS_RDB bit 114")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 114, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:3:DCBEND_INTLK_LTH_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:DCBEND_INTLK_LTH_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi114 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:DCBEND_INTLK_LTH_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:DCBEND_INTLK_LTH_B") {
  field(DESC, "LAT CL DC Interlock")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb114",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb114")
#! Field("PLC:CLTS:PP14:CLTS_RDBb114.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb114.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb114.FLNK","PPS:CLTS:3:DCBEND_INTLK_LTH_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb114.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb114.VAL")
#! Record("PPS:CLTS:3:DCBEND_INTLK_LTH_B_calc",260,18,0,1,"PPS:CLTS:3:DCBEND_INTLK_LTH_B_calc")
#! Field("PPS:CLTS:3:DCBEND_INTLK_LTH_B_calc.INPA",16777215,0,"PPS:CLTS:3:DCBEND_INTLK_LTH_B_calc.INPA")
#! Link("PPS:CLTS:3:DCBEND_INTLK_LTH_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb114.VAL")
#! Field("PPS:CLTS:3:DCBEND_INTLK_LTH_B_calc.INPB",16777215,1,"PPS:CLTS:3:DCBEND_INTLK_LTH_B_calc.INPB")
#! Field("PPS:CLTS:3:DCBEND_INTLK_LTH_B_calc.OUT",16777215,1,"PPS:CLTS:3:DCBEND_INTLK_LTH_B_calc.OUT")
#! Link("PPS:CLTS:3:DCBEND_INTLK_LTH_B_calc.OUT","PPS:CLTS:3:DCBEND_INTLK_LTH_B.VAL")
#! Record("PPS:CLTS:3:DCBEND_INTLK_LTH_B",500,20,0,0,"PPS:CLTS:3:DCBEND_INTLK_LTH_B")
#! Field("PPS:CLTS:3:DCBEND_INTLK_LTH_B.VAL",16777215,1,"PPS:CLTS:3:DCBEND_INTLK_LTH_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi113") {
  field(DESC, "Port CLTS_RDB bit 113")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 113, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:3:SEP_INTLK_LTH_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:SEP_INTLK_LTH_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi113 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:SEP_INTLK_LTH_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:SEP_INTLK_LTH_B") {
  field(DESC, "LAT CL Septum Interlock")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb113",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb113")
#! Field("PLC:CLTS:PP14:CLTS_RDBb113.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb113.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb113.FLNK","PPS:CLTS:3:SEP_INTLK_LTH_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb113.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb113.VAL")
#! Record("PPS:CLTS:3:SEP_INTLK_LTH_B_calc",260,18,0,1,"PPS:CLTS:3:SEP_INTLK_LTH_B_calc")
#! Field("PPS:CLTS:3:SEP_INTLK_LTH_B_calc.INPA",16777215,0,"PPS:CLTS:3:SEP_INTLK_LTH_B_calc.INPA")
#! Link("PPS:CLTS:3:SEP_INTLK_LTH_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb113.VAL")
#! Field("PPS:CLTS:3:SEP_INTLK_LTH_B_calc.INPB",16777215,1,"PPS:CLTS:3:SEP_INTLK_LTH_B_calc.INPB")
#! Field("PPS:CLTS:3:SEP_INTLK_LTH_B_calc.OUT",16777215,1,"PPS:CLTS:3:SEP_INTLK_LTH_B_calc.OUT")
#! Link("PPS:CLTS:3:SEP_INTLK_LTH_B_calc.OUT","PPS:CLTS:3:SEP_INTLK_LTH_B.VAL")
#! Record("PPS:CLTS:3:SEP_INTLK_LTH_B",500,20,0,0,"PPS:CLTS:3:SEP_INTLK_LTH_B")
#! Field("PPS:CLTS:3:SEP_INTLK_LTH_B.VAL",16777215,1,"PPS:CLTS:3:SEP_INTLK_LTH_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi112") {
  field(DESC, "Port CLTS_RDB bit 112")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 112, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:3:MERGE_INTLK_LTH_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:MERGE_INTLK_LTH_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi112 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:MERGE_INTLK_LTH_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:MERGE_INTLK_LTH_B") {
  field(DESC, "LAT CL Merge Interlock")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb112",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb112")
#! Field("PLC:CLTS:PP14:CLTS_RDBb112.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb112.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb112.FLNK","PPS:CLTS:3:MERGE_INTLK_LTH_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb112.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb112.VAL")
#! Record("PPS:CLTS:3:MERGE_INTLK_LTH_B_calc",260,18,0,1,"PPS:CLTS:3:MERGE_INTLK_LTH_B_calc")
#! Field("PPS:CLTS:3:MERGE_INTLK_LTH_B_calc.INPA",16777215,0,"PPS:CLTS:3:MERGE_INTLK_LTH_B_calc.INPA")
#! Link("PPS:CLTS:3:MERGE_INTLK_LTH_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb112.VAL")
#! Field("PPS:CLTS:3:MERGE_INTLK_LTH_B_calc.INPB",16777215,1,"PPS:CLTS:3:MERGE_INTLK_LTH_B_calc.INPB")
#! Field("PPS:CLTS:3:MERGE_INTLK_LTH_B_calc.OUT",16777215,1,"PPS:CLTS:3:MERGE_INTLK_LTH_B_calc.OUT")
#! Link("PPS:CLTS:3:MERGE_INTLK_LTH_B_calc.OUT","PPS:CLTS:3:MERGE_INTLK_LTH_B.VAL")
#! Record("PPS:CLTS:3:MERGE_INTLK_LTH_B",500,20,0,0,"PPS:CLTS:3:MERGE_INTLK_LTH_B")
#! Field("PPS:CLTS:3:MERGE_INTLK_LTH_B.VAL",16777215,1,"PPS:CLTS:3:MERGE_INTLK_LTH_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi127") {
  field(DESC, "Port CLTS_RDB bit 127")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 127, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:1:HB_FAULT_LTH_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:1:HB_FAULT_LTH_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi127 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:1:HB_FAULT_LTH_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:1:HB_FAULT_LTH_B") {
  field(DESC, "LAT Heartbeat Fault")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb127",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb127")
#! Field("PLC:CLTS:PP14:CLTS_RDBb127.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb127.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb127.FLNK","PPS:CLTS:1:HB_FAULT_LTH_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb127.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb127.VAL")
#! Record("PPS:CLTS:1:HB_FAULT_LTH_B_calc",260,18,0,1,"PPS:CLTS:1:HB_FAULT_LTH_B_calc")
#! Field("PPS:CLTS:1:HB_FAULT_LTH_B_calc.INPA",16777215,0,"PPS:CLTS:1:HB_FAULT_LTH_B_calc.INPA")
#! Link("PPS:CLTS:1:HB_FAULT_LTH_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb127.VAL")
#! Field("PPS:CLTS:1:HB_FAULT_LTH_B_calc.INPB",16777215,1,"PPS:CLTS:1:HB_FAULT_LTH_B_calc.INPB")
#! Field("PPS:CLTS:1:HB_FAULT_LTH_B_calc.OUT",16777215,1,"PPS:CLTS:1:HB_FAULT_LTH_B_calc.OUT")
#! Link("PPS:CLTS:1:HB_FAULT_LTH_B_calc.OUT","PPS:CLTS:1:HB_FAULT_LTH_B.VAL")
#! Record("PPS:CLTS:1:HB_FAULT_LTH_B",500,20,0,0,"PPS:CLTS:1:HB_FAULT_LTH_B")
#! Field("PPS:CLTS:1:HB_FAULT_LTH_B.VAL",16777215,1,"PPS:CLTS:1:HB_FAULT_LTH_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi126") {
  field(DESC, "Port CLTS_RDB bit 126")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 126, 1, 1)")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(FLNK, "PPS:CLTS:3:KICK_OK_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:KICK_OK_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi126 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:KICK_OK_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:KICK_OK_B") {
  field(DESC, "RT CL-Kicker status OK")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb126",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb126")
#! Field("PLC:CLTS:PP14:CLTS_RDBb126.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb126.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb126.FLNK","PPS:CLTS:3:KICK_OK_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb126.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb126.VAL")
#! Record("PPS:CLTS:3:KICK_OK_B_calc",260,18,0,1,"PPS:CLTS:3:KICK_OK_B_calc")
#! Field("PPS:CLTS:3:KICK_OK_B_calc.INPA",16777215,0,"PPS:CLTS:3:KICK_OK_B_calc.INPA")
#! Link("PPS:CLTS:3:KICK_OK_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb126.VAL")
#! Field("PPS:CLTS:3:KICK_OK_B_calc.INPB",16777215,1,"PPS:CLTS:3:KICK_OK_B_calc.INPB")
#! Field("PPS:CLTS:3:KICK_OK_B_calc.OUT",16777215,1,"PPS:CLTS:3:KICK_OK_B_calc.OUT")
#! Link("PPS:CLTS:3:KICK_OK_B_calc.OUT","PPS:CLTS:3:KICK_OK_B.VAL")
#! Record("PPS:CLTS:3:KICK_OK_B",500,20,0,0,"PPS:CLTS:3:KICK_OK_B")
#! Field("PPS:CLTS:3:KICK_OK_B.VAL",16777215,1,"PPS:CLTS:3:KICK_OK_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi125") {
  field(DESC, "Port CLTS_RDB bit 125")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 125, 1, 1)")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(FLNK, "PPS:CLTS:3:DCBEND_OK_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:DCBEND_OK_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi125 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:DCBEND_OK_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:DCBEND_OK_B") {
  field(DESC, "RT CL-DC status OK")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb125",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb125")
#! Field("PLC:CLTS:PP14:CLTS_RDBb125.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb125.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb125.FLNK","PPS:CLTS:3:DCBEND_OK_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb125.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb125.VAL")
#! Record("PPS:CLTS:3:DCBEND_OK_B_calc",260,18,0,1,"PPS:CLTS:3:DCBEND_OK_B_calc")
#! Field("PPS:CLTS:3:DCBEND_OK_B_calc.INPA",16777215,0,"PPS:CLTS:3:DCBEND_OK_B_calc.INPA")
#! Link("PPS:CLTS:3:DCBEND_OK_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb125.VAL")
#! Field("PPS:CLTS:3:DCBEND_OK_B_calc.INPB",16777215,1,"PPS:CLTS:3:DCBEND_OK_B_calc.INPB")
#! Field("PPS:CLTS:3:DCBEND_OK_B_calc.OUT",16777215,1,"PPS:CLTS:3:DCBEND_OK_B_calc.OUT")
#! Link("PPS:CLTS:3:DCBEND_OK_B_calc.OUT","PPS:CLTS:3:DCBEND_OK_B.VAL")
#! Record("PPS:CLTS:3:DCBEND_OK_B",500,20,0,0,"PPS:CLTS:3:DCBEND_OK_B")
#! Field("PPS:CLTS:3:DCBEND_OK_B.VAL",16777215,1,"PPS:CLTS:3:DCBEND_OK_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi124") {
  field(DESC, "Port CLTS_RDB bit 124")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 124, 1, 1)")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(FLNK, "PPS:CLTS:3:SEP_OK_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:SEP_OK_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi124 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:SEP_OK_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:SEP_OK_B") {
  field(DESC, "RT CL-Septum status OK")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb124",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb124")
#! Field("PLC:CLTS:PP14:CLTS_RDBb124.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb124.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb124.FLNK","PPS:CLTS:3:SEP_OK_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb124.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb124.VAL")
#! Record("PPS:CLTS:3:SEP_OK_B_calc",260,18,0,1,"PPS:CLTS:3:SEP_OK_B_calc")
#! Field("PPS:CLTS:3:SEP_OK_B_calc.INPA",16777215,0,"PPS:CLTS:3:SEP_OK_B_calc.INPA")
#! Link("PPS:CLTS:3:SEP_OK_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb124.VAL")
#! Field("PPS:CLTS:3:SEP_OK_B_calc.INPB",16777215,1,"PPS:CLTS:3:SEP_OK_B_calc.INPB")
#! Field("PPS:CLTS:3:SEP_OK_B_calc.OUT",16777215,1,"PPS:CLTS:3:SEP_OK_B_calc.OUT")
#! Link("PPS:CLTS:3:SEP_OK_B_calc.OUT","PPS:CLTS:3:SEP_OK_B.VAL")
#! Record("PPS:CLTS:3:SEP_OK_B",500,20,0,0,"PPS:CLTS:3:SEP_OK_B")
#! Field("PPS:CLTS:3:SEP_OK_B.VAL",16777215,1,"PPS:CLTS:3:SEP_OK_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi123") {
  field(DESC, "Port CLTS_RDB bit 123")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 123, 1, 1)")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(FLNK, "PPS:CLTS:3:MERGE_OK_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:MERGE_OK_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi123 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:MERGE_OK_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:MERGE_OK_B") {
  field(DESC, "RT CL-Merge status OK")
  field(ZNAM, "Fault")
  field(ONAM, "Ok")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb123",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb123")
#! Field("PLC:CLTS:PP14:CLTS_RDBb123.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb123.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb123.FLNK","PPS:CLTS:3:MERGE_OK_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb123.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb123.VAL")
#! Record("PPS:CLTS:3:MERGE_OK_B_calc",260,18,0,1,"PPS:CLTS:3:MERGE_OK_B_calc")
#! Field("PPS:CLTS:3:MERGE_OK_B_calc.INPA",16777215,0,"PPS:CLTS:3:MERGE_OK_B_calc.INPA")
#! Link("PPS:CLTS:3:MERGE_OK_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb123.VAL")
#! Field("PPS:CLTS:3:MERGE_OK_B_calc.INPB",16777215,1,"PPS:CLTS:3:MERGE_OK_B_calc.INPB")
#! Field("PPS:CLTS:3:MERGE_OK_B_calc.OUT",16777215,1,"PPS:CLTS:3:MERGE_OK_B_calc.OUT")
#! Link("PPS:CLTS:3:MERGE_OK_B_calc.OUT","PPS:CLTS:3:MERGE_OK_B.VAL")
#! Record("PPS:CLTS:3:MERGE_OK_B",500,20,0,0,"PPS:CLTS:3:MERGE_OK_B")
#! Field("PPS:CLTS:3:MERGE_OK_B.VAL",16777215,1,"PPS:CLTS:3:MERGE_OK_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi122") {
  field(DESC, "Port CLTS_RDB bit 122")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 122, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:3:KICK_FAULT_LTH_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:KICK_FAULT_LTH_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi122 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:KICK_FAULT_LTH_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:KICK_FAULT_LTH_B") {
  field(DESC, "LAT CL-Kicker status fault")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb122",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb122")
#! Field("PLC:CLTS:PP14:CLTS_RDBb122.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb122.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb122.FLNK","PPS:CLTS:3:KICK_FAULT_LTH_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb122.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb122.VAL")
#! Record("PPS:CLTS:3:KICK_FAULT_LTH_B_calc",260,18,0,1,"PPS:CLTS:3:KICK_FAULT_LTH_B_calc")
#! Field("PPS:CLTS:3:KICK_FAULT_LTH_B_calc.INPA",16777215,0,"PPS:CLTS:3:KICK_FAULT_LTH_B_calc.INPA")
#! Link("PPS:CLTS:3:KICK_FAULT_LTH_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb122.VAL")
#! Field("PPS:CLTS:3:KICK_FAULT_LTH_B_calc.INPB",16777215,1,"PPS:CLTS:3:KICK_FAULT_LTH_B_calc.INPB")
#! Field("PPS:CLTS:3:KICK_FAULT_LTH_B_calc.OUT",16777215,1,"PPS:CLTS:3:KICK_FAULT_LTH_B_calc.OUT")
#! Link("PPS:CLTS:3:KICK_FAULT_LTH_B_calc.OUT","PPS:CLTS:3:KICK_FAULT_LTH_B.VAL")
#! Record("PPS:CLTS:3:KICK_FAULT_LTH_B",500,20,0,0,"PPS:CLTS:3:KICK_FAULT_LTH_B")
#! Field("PPS:CLTS:3:KICK_FAULT_LTH_B.VAL",16777215,1,"PPS:CLTS:3:KICK_FAULT_LTH_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi121") {
  field(DESC, "Port CLTS_RDB bit 121")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 121, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:3:DCBEND_FAULT_LTH_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:DCBEND_FAULT_LTH_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi121 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:DCBEND_FAULT_LTH_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:DCBEND_FAULT_LTH_B") {
  field(DESC, "LAT CL-DC status fault")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb121",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb121")
#! Field("PLC:CLTS:PP14:CLTS_RDBb121.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb121.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb121.FLNK","PPS:CLTS:3:DCBEND_FAULT_LTH_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb121.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb121.VAL")
#! Record("PPS:CLTS:3:DCBEND_FAULT_LTH_B_calc",260,18,0,1,"PPS:CLTS:3:DCBEND_FAULT_LTH_B_calc")
#! Field("PPS:CLTS:3:DCBEND_FAULT_LTH_B_calc.INPA",16777215,0,"PPS:CLTS:3:DCBEND_FAULT_LTH_B_calc.INPA")
#! Link("PPS:CLTS:3:DCBEND_FAULT_LTH_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb121.VAL")
#! Field("PPS:CLTS:3:DCBEND_FAULT_LTH_B_calc.INPB",16777215,1,"PPS:CLTS:3:DCBEND_FAULT_LTH_B_calc.INPB")
#! Field("PPS:CLTS:3:DCBEND_FAULT_LTH_B_calc.OUT",16777215,1,"PPS:CLTS:3:DCBEND_FAULT_LTH_B_calc.OUT")
#! Link("PPS:CLTS:3:DCBEND_FAULT_LTH_B_calc.OUT","PPS:CLTS:3:DCBEND_FAULT_LTH_B.VAL")
#! Record("PPS:CLTS:3:DCBEND_FAULT_LTH_B",500,20,0,0,"PPS:CLTS:3:DCBEND_FAULT_LTH_B")
#! Field("PPS:CLTS:3:DCBEND_FAULT_LTH_B.VAL",16777215,1,"PPS:CLTS:3:DCBEND_FAULT_LTH_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi120") {
  field(DESC, "Port CLTS_RDB bit 120")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 120, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:3:SEP_FAULT_LTH_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:SEP_FAULT_LTH_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi120 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:SEP_FAULT_LTH_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:SEP_FAULT_LTH_B") {
  field(DESC, "LAT CL-Septum status fault")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb120",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb120")
#! Field("PLC:CLTS:PP14:CLTS_RDBb120.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb120.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb120.FLNK","PPS:CLTS:3:SEP_FAULT_LTH_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb120.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb120.VAL")
#! Record("PPS:CLTS:3:SEP_FAULT_LTH_B_calc",260,18,0,1,"PPS:CLTS:3:SEP_FAULT_LTH_B_calc")
#! Field("PPS:CLTS:3:SEP_FAULT_LTH_B_calc.INPA",16777215,0,"PPS:CLTS:3:SEP_FAULT_LTH_B_calc.INPA")
#! Link("PPS:CLTS:3:SEP_FAULT_LTH_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb120.VAL")
#! Field("PPS:CLTS:3:SEP_FAULT_LTH_B_calc.INPB",16777215,1,"PPS:CLTS:3:SEP_FAULT_LTH_B_calc.INPB")
#! Field("PPS:CLTS:3:SEP_FAULT_LTH_B_calc.OUT",16777215,1,"PPS:CLTS:3:SEP_FAULT_LTH_B_calc.OUT")
#! Link("PPS:CLTS:3:SEP_FAULT_LTH_B_calc.OUT","PPS:CLTS:3:SEP_FAULT_LTH_B.VAL")
#! Record("PPS:CLTS:3:SEP_FAULT_LTH_B",500,20,0,0,"PPS:CLTS:3:SEP_FAULT_LTH_B")
#! Field("PPS:CLTS:3:SEP_FAULT_LTH_B.VAL",16777215,1,"PPS:CLTS:3:SEP_FAULT_LTH_B.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:CLTS:PP14:Bi135") {
  field(DESC, "Port CLTS_RDB bit 135")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_RDB, 135, 1, 1)")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(FLNK, "PPS:CLTS:3:MERGE_FAULT_LTH_B_calc PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PPS:CLTS:3:MERGE_FAULT_LTH_B_calc") {
  field(INPA, "PLC:CLTS:PP14:Bi135 NPP MS")
  field(INPB, "PLC:CLTS:PP14:TABLE_9_SEG_1 CP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PPS:CLTS:3:MERGE_FAULT_LTH_B PP MS")
  field(ASG,  "Internal")
}

record(bi, "PPS:CLTS:3:MERGE_FAULT_LTH_B") {
  field(DESC, "LAT CL-Merge status fault")
  field(ZNAM, "Not_Latched")
  field(ONAM, "Latched")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:CLTS:PP14:CLTS_RDBb135",20,19,0,0,"PLC:CLTS:PP14:CLTS_RDBb135")
#! Field("PLC:CLTS:PP14:CLTS_RDBb135.FLNK",16777215,1,"PLC:CLTS:PP14:CLTS_RDBb135.FLNK")
#! Link("PLC:CLTS:PP14:CLTS_RDBb135.FLNK","PPS:CLTS:3:MERGE_FAULT_LTH_B_calc")
#! Field("PLC:CLTS:PP14:CLTS_RDBb135.VAL",16777215,0,"PLC:CLTS:PP14:CLTS_RDBb135.VAL")
#! Record("PPS:CLTS:3:MERGE_FAULT_LTH_B_calc",260,18,0,1,"PPS:CLTS:3:MERGE_FAULT_LTH_B_calc")
#! Field("PPS:CLTS:3:MERGE_FAULT_LTH_B_calc.INPA",16777215,0,"PPS:CLTS:3:MERGE_FAULT_LTH_B_calc.INPA")
#! Link("PPS:CLTS:3:MERGE_FAULT_LTH_B_calc.INPA","PLC:CLTS:PP14:CLTS_RDBb135.VAL")
#! Field("PPS:CLTS:3:MERGE_FAULT_LTH_B_calc.INPB",16777215,1,"PPS:CLTS:3:MERGE_FAULT_LTH_B_calc.INPB")
#! Field("PPS:CLTS:3:MERGE_FAULT_LTH_B_calc.OUT",16777215,1,"PPS:CLTS:3:MERGE_FAULT_LTH_B_calc.OUT")
#! Link("PPS:CLTS:3:MERGE_FAULT_LTH_B_calc.OUT","PPS:CLTS:3:MERGE_FAULT_LTH_B.VAL")
#! Record("PPS:CLTS:3:MERGE_FAULT_LTH_B",500,20,0,0,"PPS:CLTS:3:MERGE_FAULT_LTH_B")
#! Field("PPS:CLTS:3:MERGE_FAULT_LTH_B.VAL",16777215,1,"PPS:CLTS:3:MERGE_FAULT_LTH_B.VAL")
record(bo, "PPS:CLTS:1:RESET_INTLK_B") {
  field(DESC, "PPS_Interlock_Reset_B")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(CLTS_WRTB, 7, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "Reset")
   field(ASG,  "MCC")
}

record(bo, "PPS:CLTS:1:PAUSEHB_B") {
  field(DESC, "PPS_Pause_Heartbeat_B")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(CLTS_WRTB, 6, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "Reset")
   field(ASG,  "MCC")
}

#==============================================================================
#
# Abs:  PILZ PNOZ PLC interface for accessing the right table/segment
#
# Name: pilz-plc-request.template
#
# Facility: LCLS Personnel Protection Controls
#
# Auth: 11-Dec-2018, Garth Brown   (GWBROWN)
# Rev : dd-mmm-yyyy, Reviewer's Name  (USERNAME)
#
# To specify which registers to read/write, you need to set the table and
# segment (see PNOZ docs). This set of PVs keeps them set to the correct values
# for reading either virtual I/O points or program stats such as project checksum.
# The PNOZ PLC also has occasional communications dropouts, where the PLC stops
# responding and the TCP connection must be reset. This happens more frequently
# the more communication there is with the PLC.
# While the vendor offers a PNOZ model with integrated Ethernet port which
# allows readback at different modbus addresses instead of needing to set
# table/segment, that interface also allows remote access to secure registers
# and PLC programming. For safety, that type of remote access is not allowed in
# our system. All of their products that don't allow remote access beyond our
# safety specs also require table/segment setting to choose which registers to
# read/write.
#
#-----------------------------------------------------------------------------
#  Mod:
#
#==============================================================================
#

record(longout, "PLC:CLTS:PP14:REQ_TABLE") {
	field(DESC, "Table to read/write")
	field(VAL, "9")
	field(OUT, "PLC:CLTS:PP14:REQ_TABLE_OUT PP")
	field(HOPR, "128")
	field(LOPR, "0")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}

# All the data we're interested in is: Tables 1 and 9, segment 1
# We only need table 1 once for check sums that don't change, so
# read it for a short time during startup, then switch to table 9.
record(calcout, "PLC:CLTS:PP14:TABLE_CYCLER")
{
	field( OUT, "PLC:CLTS:PP14:REQ_TABLE PP")
	field( CALC, "A:=(A+1)%3600;A=20?1:9")
	field( INPA, "0")
	field( SCAN, ".5 second")
}

record(calcout, "PLC:CLTS:PP14:SEG_CYCLER")
{
	field( OUT, "PLC:CLTS:PP14:REQ_SEG PP")
	field( CALC, "1")
	field( INPA, "0")
	field( SCAN, ".5 second")
}

# Records for disabling PVs when their reqest table isn't active
record(calc, "PLC:CLTS:PP14:TABLE_9_SEG_1")
{
	field( INPA, "PLC:CLTS:PP14:REQ_TABLE CP")
	field( INPB, "PLC:CLTS:PP14:REQ_SEG CP")
	field( INPC, "PLC:CLTS:PP14:REQ_TABLE_IN CP")
	field( INPD, "PLC:CLTS:PP14:REQ_SEG_IN CP")
	field(CALC, "A=9 & B=1 & C=9 & D=1")
}

record(calc, "PLC:CLTS:PP14:TABLE_1_SEG_1")
{
	field( INPA, "PLC:CLTS:PP14:REQ_TABLE CP")
	field( INPB, "PLC:CLTS:PP14:REQ_SEG CP")
	field( INPC, "PLC:CLTS:PP14:REQ_TABLE_IN CP")
	field( INPD, "PLC:CLTS:PP14:REQ_SEG_IN CP")
	field(CALC, "A=1 & B=1 & C=1 & D=1")
}

# The target PVs don't use the data, but this has 8 forward links,
# the number we need, while the fanout record only has 6.
record(dfanout, "PLC:CLTS:PP14:REQ_TABLE_OUT") {
	field(OUTA, "PLC:CLTS:PP14:REQ_TABLE_BIT0_CALC.A PP")
	field(OUTB, "PLC:CLTS:PP14:REQ_TABLE_BIT1_CALC.A PP")
	field(OUTC, "PLC:CLTS:PP14:REQ_TABLE_BIT2_CALC.A PP")
	field(OUTD, "PLC:CLTS:PP14:REQ_TABLE_BIT3_CALC.A PP")
	field(OUTE, "PLC:CLTS:PP14:REQ_TABLE_BIT4_CALC.A PP")
	field(OUTF, "PLC:CLTS:PP14:REQ_TABLE_BIT5_CALC.A PP")
	field(OUTG, "PLC:CLTS:PP14:REQ_TABLE_BIT6_CALC.A PP")
	field(OUTH, "PLC:CLTS:PP14:REQ_TABLE_BIT7_CALC.A PP")
	field(SDIS, "PLC:CLTS:PP14:REQ_TABLE_IN.PACT")
}

# The simpler approach of writing to the table/segment every few seconds caused
# TCP dropouts to happen several times an hour, compared to every day or two
# when we only ever read/wrote table 9 segment 1. These calcout records reduce
# the dropouts to around 5 a day by only writing the bits that need to change.

record(calcout, "PLC:CLTS:PP14:REQ_TABLE_BIT0_CALC") {
	field(INPA, "PLC:CLTS:PP14:REQ_TABLE_OUT")
	field(INPB, "PLC:CLTS:PP14:TABLE_BIT0 MS")
	field(INPC, "PLC:CLTS:PP14:REQ_TABLE_BIT0 MS")
	field(CALC, "(B#C)||(B#(A&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "A&1")
	field(OUT, "PLC:CLTS:PP14:REQ_TABLE_BIT0 PP")
}

record(calcout, "PLC:CLTS:PP14:REQ_TABLE_BIT1_CALC") {
	field(INPA, "PLC:CLTS:PP14:REQ_TABLE_OUT")
	field(INPB, "PLC:CLTS:PP14:TABLE_BIT1 MS")
	field(INPC, "PLC:CLTS:PP14:REQ_TABLE_BIT1 MS")
	field(CALC, "(B#C)||(B#((A>>1)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>1)&1")
	field(OUT, "PLC:CLTS:PP14:REQ_TABLE_BIT1 PP")
}

record(calcout, "PLC:CLTS:PP14:REQ_TABLE_BIT2_CALC") {
	field(INPA, "PLC:CLTS:PP14:REQ_TABLE_OUT")
	field(INPB, "PLC:CLTS:PP14:TABLE_BIT2 MS")
	field(INPC, "PLC:CLTS:PP14:REQ_TABLE_BIT2 MS")
	field(CALC, "(B#C)||(B#((A>>2)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>2)&1")
	field(OUT, "PLC:CLTS:PP14:REQ_TABLE_BIT2 PP")
}

record(calcout, "PLC:CLTS:PP14:REQ_TABLE_BIT3_CALC") {
	field(INPA, "PLC:CLTS:PP14:REQ_TABLE_OUT")
	field(INPB, "PLC:CLTS:PP14:TABLE_BIT3 MS")
	field(INPC, "PLC:CLTS:PP14:REQ_TABLE_BIT3 MS")
	field(CALC, "(B#C)||(B#((A>>3)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>3)&1")
	field(OUT, "PLC:CLTS:PP14:REQ_TABLE_BIT3 PP")
}

record(calcout, "PLC:CLTS:PP14:REQ_TABLE_BIT4_CALC") {
	field(INPA, "PLC:CLTS:PP14:REQ_TABLE_OUT")
	field(INPB, "PLC:CLTS:PP14:TABLE_BIT4 MS")
	field(INPC, "PLC:CLTS:PP14:REQ_TABLE_BIT4 MS")
	field(CALC, "(B#C)||(B#((A>>4)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>4)&1")
	field(OUT, "PLC:CLTS:PP14:REQ_TABLE_BIT4 PP")
}

record(calcout, "PLC:CLTS:PP14:REQ_TABLE_BIT5_CALC") {
	field(INPA, "PLC:CLTS:PP14:REQ_TABLE_OUT")
	field(INPB, "PLC:CLTS:PP14:TABLE_BIT5 MS")
	field(INPC, "PLC:CLTS:PP14:REQ_TABLE_BIT5 MS")
	field(CALC, "(B#C)||(B#((A>>5)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>5)&1")
	field(OUT, "PLC:CLTS:PP14:REQ_TABLE_BIT5 PP")
}

record(calcout, "PLC:CLTS:PP14:REQ_TABLE_BIT6_CALC") {
	field(INPA, "PLC:CLTS:PP14:REQ_TABLE_OUT")
	field(INPB, "PLC:CLTS:PP14:TABLE_BIT6 MS")
	field(INPC, "PLC:CLTS:PP14:REQ_TABLE_BIT6 MS")
	field(CALC, "(B#C)||(B#((A>>6)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>6)&1")
	field(OUT, "PLC:CLTS:PP14:REQ_TABLE_BIT6 PP")
}

record(calcout, "PLC:CLTS:PP14:REQ_TABLE_BIT7_CALC") {
	field(INPA, "PLC:CLTS:PP14:REQ_TABLE_OUT")
	field(INPB, "PLC:CLTS:PP14:TABLE_BIT7 MS")
	field(INPC, "PLC:CLTS:PP14:REQ_TABLE_BIT7 MS")
	field(CALC, "(B#C)||(B#((A>>7)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>7)&1")
	field(OUT, "PLC:CLTS:PP14:REQ_TABLE_BIT7 PP")
}


record(calcout, "PLC:CLTS:PP14:REQ_TABLE_IN") {
	field(DESC, "Table readback")
	field(INPA, "PLC:CLTS:PP14:TABLE_BIT0 CP MS")
	field(INPB, "PLC:CLTS:PP14:TABLE_BIT1 CP MS")
	field(INPC, "PLC:CLTS:PP14:TABLE_BIT2 CP MS")
	field(INPD, "PLC:CLTS:PP14:TABLE_BIT3 CP MS")
	field(INPE, "PLC:CLTS:PP14:TABLE_BIT4 CP MS")
	field(INPF, "PLC:CLTS:PP14:TABLE_BIT5 CP MS")
	field(INPG, "PLC:CLTS:PP14:TABLE_BIT6 CP MS")
	field(INPH, "PLC:CLTS:PP14:TABLE_BIT7 CP MS")
	field(CALC, "A+B*2+C*4+D*8+E*16+F*32+G*64+H*128")
	field(OUT, "PLC:CLTS:PP14:REQ_TABLE PP MS")
	#field(SDIS, "PLC:CLTS:PP14:REQ_TABLE_OUT.PACT")
}


record(longout, "PLC:CLTS:PP14:REQ_SEG") {
	field(DESC, "Segment to read/write")
	field(VAL, "1")
	field(OUT, "PLC:CLTS:PP14:REQ_SEG_OUT PP")
	field(HOPR, "128")
	field(LOPR, "0")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}

# The target PVs don't use the data, but this has 8 forward links,
# the number we need, while the fanout record only has 6.
record(dfanout, "PLC:CLTS:PP14:REQ_SEG_OUT") {
	field(OUTA, "PLC:CLTS:PP14:REQ_SEG_BIT0_CALC.A PP")
	field(OUTB, "PLC:CLTS:PP14:REQ_SEG_BIT1_CALC.A PP")
	field(OUTC, "PLC:CLTS:PP14:REQ_SEG_BIT2_CALC.A PP")
	field(OUTD, "PLC:CLTS:PP14:REQ_SEG_BIT3_CALC.A PP")
	field(OUTE, "PLC:CLTS:PP14:REQ_SEG_BIT4_CALC.A PP")
	field(OUTF, "PLC:CLTS:PP14:REQ_SEG_BIT5_CALC.A PP")
	field(OUTG, "PLC:CLTS:PP14:REQ_SEG_BIT6_CALC.A PP")
	field(OUTH, "PLC:CLTS:PP14:REQ_SEG_BIT7_CALC.A PP")
	field(SDIS, "PLC:CLTS:PP14:REQ_SEG_IN.PACT")
}

record(calcout, "PLC:CLTS:PP14:REQ_SEG_BIT0_CALC") {
	field(INPA, "PLC:CLTS:PP14:REQ_SEG_OUT")
	field(INPB, "PLC:CLTS:PP14:SEG_BIT0 CP MS")
	field(CALC, "(B#C)||(B#(A&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "A&1")
	field(OUT, "PLC:CLTS:PP14:REQ_SEG_BIT0 PP")
}

record(calcout, "PLC:CLTS:PP14:REQ_SEG_BIT1_CALC") {
	field(INPA, "PLC:CLTS:PP14:REQ_SEG_OUT")
	field(INPB, "PLC:CLTS:PP14:SEG_BIT1 MS")
	field(INPC, "PLC:CLTS:PP14:REQ_SEG_BIT1 MS")
	field(CALC, "(B#C)||(B#((A>>1)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>1)&1")
	field(OUT, "PLC:CLTS:PP14:REQ_SEG_BIT1 PP")
}

record(calcout, "PLC:CLTS:PP14:REQ_SEG_BIT2_CALC") {
	field(INPA, "PLC:CLTS:PP14:REQ_SEG_OUT")
	field(INPB, "PLC:CLTS:PP14:SEG_BIT2 MS")
	field(INPC, "PLC:CLTS:PP14:REQ_SEG_BIT2 MS")
	field(CALC, "(B#C)||(B#((A>>2)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>2)&1")
	field(OUT, "PLC:CLTS:PP14:REQ_SEG_BIT2 PP")
}

record(calcout, "PLC:CLTS:PP14:REQ_SEG_BIT3_CALC") {
	field(INPA, "PLC:CLTS:PP14:REQ_SEG_OUT")
	field(INPB, "PLC:CLTS:PP14:SEG_BIT3 MS")
	field(INPC, "PLC:CLTS:PP14:REQ_SEG_BIT3 MS")
	field(CALC, "(B#C)||(B#((A>>3)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>3)&1")
	field(OUT, "PLC:CLTS:PP14:REQ_SEG_BIT3 PP")
}

record(calcout, "PLC:CLTS:PP14:REQ_SEG_BIT4_CALC") {
	field(INPA, "PLC:CLTS:PP14:REQ_SEG_OUT")
	field(INPB, "PLC:CLTS:PP14:SEG_BIT4 MS")
	field(INPC, "PLC:CLTS:PP14:REQ_SEG_BIT4 MS")
	field(CALC, "(B#C)||(B#((A>>4)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>4)&1")
	field(OUT, "PLC:CLTS:PP14:REQ_SEG_BIT4 PP")
}

record(calcout, "PLC:CLTS:PP14:REQ_SEG_BIT5_CALC") {
	field(INPA, "PLC:CLTS:PP14:REQ_SEG_OUT")
	field(INPB, "PLC:CLTS:PP14:SEG_BIT5 MS")
	field(INPC, "PLC:CLTS:PP14:REQ_SEG_BIT5 MS")
	field(CALC, "(B#C)||(B#((A>>5)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>5)&1")
	field(OUT, "PLC:CLTS:PP14:REQ_SEG_BIT5 PP")
}

record(calcout, "PLC:CLTS:PP14:REQ_SEG_BIT6_CALC") {
	field(INPA, "PLC:CLTS:PP14:REQ_SEG_OUT")
	field(INPB, "PLC:CLTS:PP14:SEG_BIT6 MS")
	field(INPC, "PLC:CLTS:PP14:REQ_SEG_BIT6 MS")
	field(CALC, "(B#C)||(B#((A>>6)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>6)&1")
	field(OUT, "PLC:CLTS:PP14:REQ_SEG_BIT6 PP")
}

record(calcout, "PLC:CLTS:PP14:REQ_SEG_BIT7_CALC") {
	field(INPA, "PLC:CLTS:PP14:REQ_SEG_OUT")
	field(INPB, "PLC:CLTS:PP14:SEG_BIT7 MS")
	field(INPC, "PLC:CLTS:PP14:REQ_SEG_BIT7 MS")
	field(CALC, "(B#C)||(B#((A>>7)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>7)&1")
	field(OUT, "PLC:CLTS:PP14:REQ_SEG_BIT7 PP")
}

record(calcout, "PLC:CLTS:PP14:REQ_SEG_IN") {
	field(DESC, "Segment readback")
	field(INPA, "PLC:CLTS:PP14:SEG_BIT0 CP MS")
	field(INPB, "PLC:CLTS:PP14:SEG_BIT1 CP MS")
	field(INPC, "PLC:CLTS:PP14:SEG_BIT2 CP MS")
	field(INPD, "PLC:CLTS:PP14:SEG_BIT3 CP MS")
	field(INPE, "PLC:CLTS:PP14:SEG_BIT4 CP MS")
	field(INPF, "PLC:CLTS:PP14:SEG_BIT5 CP MS")
	field(INPG, "PLC:CLTS:PP14:SEG_BIT6 CP MS")
	field(INPH, "PLC:CLTS:PP14:SEG_BIT7 CP MS")
	field(CALC, "A+B*2+C*4+D*8+E*16+F*32+G*64+H*128")
	field(OUT, "PLC:CLTS:PP14:REQ_SEG PP MS")
	field(SDIS, "PLC:CLTS:PP14:REQ_SEG_OUT.PACT")
}

record(bi, "PLC:CLTS:PP14:LED_X1") {
	field(DESC, "PPS-X1_LED")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDB, 24, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "MAJOR")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP14:LED_X2") {
	field(DESC, "PPS-X2_LED")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDB, 25, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "MAJOR")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP14:PWLED") {
	field(DESC, "ODM-Power_LED_A")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDB, 26, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "MAJOR")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP14:RUNLED") {
	field(DESC, "ODM-Run_LED_A")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDB, 27, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "MAJOR")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP14:DIAGLED") {
	field(DESC, "ODM-Diag_LED_A")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDB, 28, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP14:FAULTLED") {
	field(DESC, "ODM-Fault_LED_A")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDB, 29, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP14:IFAULTLED") {
	field(DESC, "ODM-IFault_LED_A")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDB, 30, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP14:OFAULTLED") {
	field(DESC, "ODM-OFault_LED_A")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDB, 31, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP14:TABLE_BIT7") {
	field(DESC, "Table Read bit 7")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDB, 32, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP14:TABLE_BIT6") {
	field(DESC, "Table Read bit 6")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDB, 33, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP14:TABLE_BIT5") {
	field(DESC, "Table Read bit 5")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDB, 34, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP14:TABLE_BIT4") {
	field(DESC, "Table Read bit 4")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDB, 35, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP14:TABLE_BIT3") {
	field(DESC, "Table Read bit 3")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDB, 36, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP14:TABLE_BIT2") {
	field(DESC, "Table Read bit 2")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDB, 37, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP14:TABLE_BIT1") {
	field(DESC, "Table Read bit 1")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDB, 38, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP14:TABLE_BIT0") {
	field(DESC, "Table Read bit 0")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDB, 39, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP14:SEG_BIT7") {
	field(DESC, "Segment Read bit 7")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDB, 40, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP14:SEG_BIT6") {
	field(DESC, "Segment Read bit 6")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDB, 41, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP14:SEG_BIT5") {
	field(DESC, "Segment Read bit 5")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDB, 42, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP14:SEG_BIT4") {
	field(DESC, "Segment Read bit 4")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDB, 43, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP14:SEG_BIT3") {
	field(DESC, "Segment Read bit 3")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDB, 44, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP14:SEG_BIT2") {
	field(DESC, "Segment Read bit 2")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDB, 45, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP14:SEG_BIT1") {
	field(DESC, "Segment Read bit 1")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDB, 46, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:CLTS:PP14:SEG_BIT0") {
	field(DESC, "Segment Read bit 0")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(CLTS_RDB, 47, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}


record(bo, "PLC:CLTS:PP14:REQ_TABLE_BIT7") {
	field(DESC, "Table Request bit 7")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTB, 32, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP14:REQ_TABLE_BIT6") {
	field(DESC, "Table Request bit 6")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTB, 33, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP14:REQ_TABLE_BIT5") {
	field(DESC, "Table Request bit 5")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTB, 34, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP14:REQ_TABLE_BIT4") {
	field(DESC, "Table Request bit 4")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTB, 35, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP14:REQ_TABLE_BIT3") {
	field(DESC, "Table Request bit 3")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTB, 36, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP14:REQ_TABLE_BIT2") {
	field(DESC, "Table Request bit 2")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTB, 37, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP14:REQ_TABLE_BIT1") {
	field(DESC, "Table Request bit 1")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTB, 38, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP14:REQ_TABLE_BIT0") {
	field(DESC, "Table Request bit 0")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTB, 39, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP14:REQ_SEG_BIT7") {
	field(DESC, "Segment Request bit 7")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTB, 40, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP14:REQ_SEG_BIT6") {
	field(DESC, "Segment Request bit 6")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTB, 41, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP14:REQ_SEG_BIT5") {
	field(DESC, "Segment Request bit 5")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTB, 42, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP14:REQ_SEG_BIT4") {
	field(DESC, "Segment Request bit 4")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTB, 43, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP14:REQ_SEG_BIT3") {
	field(DESC, "Segment Request bit 3")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTB, 44, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP14:REQ_SEG_BIT2") {
	field(DESC, "Segment Request bit 2")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTB, 45, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP14:REQ_SEG_BIT1") {
	field(DESC, "Segment Request bit 1")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTB, 46, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:CLTS:PP14:REQ_SEG_BIT0") {
	field(DESC, "Segment Request bit 0")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(CLTS_WRTB, 47, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND


record(longin, "PLC:CLTS:PP14:w0") {
  field(DESC, "CLTS CHAINB Checksum")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_WDB, 0, 0xFFFF, 1)")
  field(ASG,  "Internal")
}

record(longin, "PLC:CLTS:PP14:w1") {
  field(DESC, "CLTS CHAINB Checksum")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_WDB, 1, 0xFFFF, 1)")
  field(ASG,  "Internal")
}

record(longin, "PLC:CLTS:PP14:w2") {
  field(DESC, "Active Table and Segment")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_WDB, 2, 0xFFFF, 1)")
  field(FLNK, "PLC:CLTS:PP14:CHECKSUM_SDIS PP MS")
  field(ASG,  "Internal")
}

record(calc, "PLC:CLTS:PP14:CHECKSUM_SDIS") {
  field(INPA, "PLC:CLTS:PP14:w2 NPP MS")
  field(CALC, "A = 0X0101")
}

record(longin, "PLC:CLTS:PP14:w3") {
  field(DESC, "CLTS CHAINB Checksum")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_WDB, 3, 0xFFFF, 1)")
  field(FLNK, "PLC:CLTS:PP14:CHECKSUM_SAFE PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:CLTS:PP14:CHECKSUM_SAFE_calc") {
  field(INPA, "PLC:CLTS:PP14:w3 PP MS")
  field(INPB, "PLC:CLTS:PP14:CHECKSUM_SDIS PP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:CLTS:PP14:CHECKSUM_SAFE PP MS")
  field(ASG,  "Internal")
}

record(longin, "PLC:CLTS:PP14:CHECKSUM_SAFE") {
  field(DESC, "Check Sum Safe")
  field(FLNK, "PLC:CLTS:PP14:CHECKSUM_SAFE_calc PP MS")
  info(autosaveFields_pass0, "VAL")
}

record(longin, "PLC:CLTS:PP14:w4") {
  field(DESC, "CLTS CHAINB Checksum")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_WDB, 4, 0xFFFF, 1)")
  field(FLNK, "PLC:CLTS:PP14:PROJ_CHECKSUM_calc")
  field(ASG,  "Internal")
}

record(calcout, "PLC:CLTS:PP14:PROJ_CHECKSUM_calc") {
  field(INPA, "PLC:CLTS:PP14:w4 NPP MS")
  field(INPB, "PLC:CLTS:PP14:CHECKSUM_SDIS NPP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:CLTS:PP14:PROJ_CHECKSUM PP MS")
  field(ASG,  "Internal")
}

record(longin, "PLC:CLTS:PP14:PROJ_CHECKSUM") {
  field(DESC, "Total Project Check Sum")
  info(autosaveFields_pass0, "VAL")
}

record(longin, "PLC:CLTS:PP14:w5") {
  field(DESC, "CLTS CHAINB Checksum")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_WDB, 5, 0xFFFF, 1)")
  field(FLNK, "PLC:CLTS:PP14:DAY_MONTH_calc")
  field(ASG,  "Internal")
}

record(calcout, "PLC:CLTS:PP14:DAY_MONTH_calc") {
  field(INPA, "PLC:CLTS:PP14:w5 NPP MS")
  field(INPB, "PLC:CLTS:PP14:CHECKSUM_SDIS NPP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:CLTS:PP14:DAY_MONTH PP MS")
  field(ASG,  "Internal")
}

record(longin, "PLC:CLTS:PP14:DAY_MONTH") {
  field(DESC, "Raw day and month")
  field(ASG,  "Internal")
}

record(calc, "PLC:CLTS:PP14:PROJ_MONTH") {
  field(DESC, "Project creation day")
  field(INPA, "PLC:CLTS:PP14:DAY_MONTH CP MS")
  field(CALC, "A & 0xFF")
  info(autosaveFields_pass0, "VAL")
}

record(calc, "PLC:CLTS:PP14:PROJ_DAY") {
  field(DESC, "Project creation month")
  field(INPA, "PLC:CLTS:PP14:DAY_MONTH CP MS")
  field(CALC, "A >> 8")
  info(autosaveFields_pass0, "VAL")
}

record(longin, "PLC:CLTS:PP14:w6") {
  field(DESC, "Checksum word 6")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_WDB, 6, 0xFFFF, 1)")
  field(FLNK, "PLC:CLTS:PP14:PROJ_YEAR_calc")
  field(ASG,  "Internal")
}

record(calcout, "PLC:CLTS:PP14:PROJ_YEAR_calc") {
  field(INPA, "PLC:CLTS:PP14:w6 NPP MS")
  field(INPB, "PLC:CLTS:PP14:CHECKSUM_SDIS NPP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:CLTS:PP14:PROJ_YEAR PP MS")
  field(ASG,  "Internal")
}

record(longin, "PLC:CLTS:PP14:PROJ_YEAR") {
  field(DESC, "Project creation year.")
  info(autosaveFields_pass0, "VAL")
}

record(longin, "PLC:CLTS:PP14:w7") {
  field(DESC, "Checksum word 7")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_WDB, 7, 0xFFFF, 1)")
  field(FLNK, "PLC:CLTS:PP14:OP_HRS_MSB_calc")
  field(ASG,  "Internal")
}

record(calcout, "PLC:CLTS:PP14:OP_HRS_MSB_calc") {
  field(INPA, "PLC:CLTS:PP14:w7 NPP MS")
  field(INPB, "PLC:CLTS:PP14:CHECKSUM_SDIS NPP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:CLTS:PP14:OP_HRS_MSB PP MS")
  field(ASG,  "Internal")
}

record(longin, "PLC:CLTS:PP14:OP_HRS_MSB") {
  field(DESC, "Operation hours upper byte")
  field(ASG,  "Internal")
}

record(longin, "PLC:CLTS:PP14:w8") {
  field(DESC, "Checksum word 8")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(CLTS_WDB, 8, 0xFFFF, 1)")
  field(FLNK, "PLC:CLTS:PP14:OP_HRS_LSB_calc")
  field(ASG,  "Internal")
}

record(calcout, "PLC:CLTS:PP14:OP_HRS_LSB_calc") {
  field(INPA, "PLC:CLTS:PP14:w8 NPP MS")
  field(INPB, "PLC:CLTS:PP14:CHECKSUM_SDIS NPP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:CLTS:PP14:OP_HRS_LSB PP MS")
  field(ASG,  "Internal")
}

record(longin, "PLC:CLTS:PP14:OP_HRS_LSB") {
  field(DESC, "Operation hours lower byte")
  field(ASG,  "Internal")
}

record(calc, "PLC:CLTS:PP14:OP_HOURS") {
  field(INPA, "PLC:CLTS:PP14:OP_HRS_MSB CP MS")
  field(INPB, "PLC:CLTS:PP14:OP_HRS_LSB CP MS")
  field(CALC, "(A << 8)+(B>>8)")
  info(autosaveFields_pass0, "VAL")
}

record(mbbi, "PLC:CLTS:PP14:BASE_MODEL") {
  field(DTYP, "Raw Soft Channel")
  field(NOBT, "8")
  field(INP, "PLC:CLTS:PP14:OP_HRS_LSB CP MS")
  field(ZRVL, "0x00")
  field(ONVL, "0x02")
  field(TWVL, "0x04")
  field(THVL, "0x03")
  field(FRVL, "0x20")
  field(FVVL, "0x22")
  field(SXVL, "0x24")
  field(SVVL, "0x23")
  field(EIVL, "0x50")
  field(NIVL, "0x51")
  field(TEVL, "0x52")
  field(ZRST, "PNOZ m1p")
  field(ONST, "PNOZ m0p")
  field(TWST, "PNOZ m2p")
  field(THST, "PNOZ m3p")
  field(FRST, "PNOZ m1p ETH")
  field(FVST, "PNOZ m0p ETH")
  field(SXST, "PNOZ m2p ETH")
  field(SVST, "PNOZ m3p ETH")
  field(EIST, "PNOZ mm0p")
  field(NIST, "PNOZ mm0.1p")
  field(TEST, "PNOZ mm0.2p")
}

# End of file
# Template for I/O statistics

record(bo,"PLC:CLTS:PP14:RDHistEnable") {
    field(DTYP,"asynUInt32Digital")
    field(OUT,"@asynMask(CLTS_RDB 0 0xFFFF)ENABLE_HISTOGRAM")
    field(ZNAM,"Disable")
    field(ONAM,"Enable")
}

record(bo, "PLC:CLTS:PP14:RDStatistics") {
    field(SCAN, "10 second")
    field(FLNK, "PLC:CLTS:PP14:RDHist.PROC")
}

record(waveform,"PLC:CLTS:PP14:RDHist") {
    field(DTYP,"asynInt32ArrayIn")
    field(INP,"@asyn(CLTS_RDB 0)READ_HISTOGRAM")
    field(FTVL,"LONG")
    field(NELM,"200")  # This number should match driver
    field(FLNK,"PLC:CLTS:PP14:RDHistTimeAxis.PROC")
}

record(waveform,"PLC:CLTS:PP14:RDHistTimeAxis") {
    field(DTYP,"asynInt32ArrayIn")
    field(INP,"@asyn(CLTS_RDB 0)HISTOGRAM_TIME_AXIS")
    field(FTVL,"LONG")
    field(NELM,"200")  # This number should match driver
    field(FLNK,"PLC:CLTS:PP14:RDReadOK.PROC")
}

record(longout,"PLC:CLTS:PP14:RDMsPerBin") {
    field(DTYP,"asynInt32")
    field(OUT,"@asyn(CLTS_RDB 0)HISTOGRAM_BIN_TIME")
    field(DRVL,"0")
    field(VAL,"1")
    field(PINI,"1")
}

record(longin,"PLC:CLTS:PP14:RDReadOK") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_RDB 0)READ_OK")
    field(FLNK,"PLC:CLTS:PP14:RDWriteOK.PROC")
}

record(longin,"PLC:CLTS:PP14:RDWriteOK") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_RDB 0)WRITE_OK")
    field(FLNK,"PLC:CLTS:PP14:RDIOErrors.PROC")
}

record(longin,"PLC:CLTS:PP14:RDIOErrors") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_RDB 0)IO_ERRORS")
    field(FLNK,"PLC:CLTS:PP14:RDLastIOTime.PROC")
}

record(longin,"PLC:CLTS:PP14:RDLastIOTime") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_RDB 0)LAST_IO_TIME")
    field(FLNK,"PLC:CLTS:PP14:RDMaxIOTime.PROC")
}

record(longin,"PLC:CLTS:PP14:RDMaxIOTime") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_RDB 0)MAX_IO_TIME")
}
# Template for I/O statistics

record(bo,"PLC:CLTS:PP14:WRTHistEnable") {
    field(DTYP,"asynUInt32Digital")
    field(OUT,"@asynMask(CLTS_WRTB 0 0xFFFF)ENABLE_HISTOGRAM")
    field(ZNAM,"Disable")
    field(ONAM,"Enable")
}

record(bo, "PLC:CLTS:PP14:WRTStatistics") {
    field(SCAN, "10 second")
    field(FLNK, "PLC:CLTS:PP14:WRTHist.PROC")
}

record(waveform,"PLC:CLTS:PP14:WRTHist") {
    field(DTYP,"asynInt32ArrayIn")
    field(INP,"@asyn(CLTS_WRTB 0)READ_HISTOGRAM")
    field(FTVL,"LONG")
    field(NELM,"200")  # This number should match driver
    field(FLNK,"PLC:CLTS:PP14:WRTHistTimeAxis.PROC")
}

record(waveform,"PLC:CLTS:PP14:WRTHistTimeAxis") {
    field(DTYP,"asynInt32ArrayIn")
    field(INP,"@asyn(CLTS_WRTB 0)HISTOGRAM_TIME_AXIS")
    field(FTVL,"LONG")
    field(NELM,"200")  # This number should match driver
    field(FLNK,"PLC:CLTS:PP14:WRTReadOK.PROC")
}

record(longout,"PLC:CLTS:PP14:WRTMsPerBin") {
    field(DTYP,"asynInt32")
    field(OUT,"@asyn(CLTS_WRTB 0)HISTOGRAM_BIN_TIME")
    field(DRVL,"0")
    field(VAL,"1")
    field(PINI,"1")
}

record(longin,"PLC:CLTS:PP14:WRTReadOK") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_WRTB 0)READ_OK")
    field(FLNK,"PLC:CLTS:PP14:WRTWriteOK.PROC")
}

record(longin,"PLC:CLTS:PP14:WRTWriteOK") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_WRTB 0)WRITE_OK")
    field(FLNK,"PLC:CLTS:PP14:WRTIOErrors.PROC")
}

record(longin,"PLC:CLTS:PP14:WRTIOErrors") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_WRTB 0)IO_ERRORS")
    field(FLNK,"PLC:CLTS:PP14:WRTLastIOTime.PROC")
}

record(longin,"PLC:CLTS:PP14:WRTLastIOTime") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_WRTB 0)LAST_IO_TIME")
    field(FLNK,"PLC:CLTS:PP14:WRTMaxIOTime.PROC")
}

record(longin,"PLC:CLTS:PP14:WRTMaxIOTime") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_WRTB 0)MAX_IO_TIME")
}
# Template for I/O statistics

record(bo,"PLC:CLTS:PP14:WDHistEnable") {
    field(DTYP,"asynUInt32Digital")
    field(OUT,"@asynMask(CLTS_WDB 0 0xFFFF)ENABLE_HISTOGRAM")
    field(ZNAM,"Disable")
    field(ONAM,"Enable")
}

record(bo, "PLC:CLTS:PP14:WDStatistics") {
    field(SCAN, "10 second")
    field(FLNK, "PLC:CLTS:PP14:WDHist.PROC")
}

record(waveform,"PLC:CLTS:PP14:WDHist") {
    field(DTYP,"asynInt32ArrayIn")
    field(INP,"@asyn(CLTS_WDB 0)READ_HISTOGRAM")
    field(FTVL,"LONG")
    field(NELM,"200")  # This number should match driver
    field(FLNK,"PLC:CLTS:PP14:WDHistTimeAxis.PROC")
}

record(waveform,"PLC:CLTS:PP14:WDHistTimeAxis") {
    field(DTYP,"asynInt32ArrayIn")
    field(INP,"@asyn(CLTS_WDB 0)HISTOGRAM_TIME_AXIS")
    field(FTVL,"LONG")
    field(NELM,"200")  # This number should match driver
    field(FLNK,"PLC:CLTS:PP14:WDReadOK.PROC")
}

record(longout,"PLC:CLTS:PP14:WDMsPerBin") {
    field(DTYP,"asynInt32")
    field(OUT,"@asyn(CLTS_WDB 0)HISTOGRAM_BIN_TIME")
    field(DRVL,"0")
    field(VAL,"1")
    field(PINI,"1")
}

record(longin,"PLC:CLTS:PP14:WDReadOK") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_WDB 0)READ_OK")
    field(FLNK,"PLC:CLTS:PP14:WDWriteOK.PROC")
}

record(longin,"PLC:CLTS:PP14:WDWriteOK") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_WDB 0)WRITE_OK")
    field(FLNK,"PLC:CLTS:PP14:WDIOErrors.PROC")
}

record(longin,"PLC:CLTS:PP14:WDIOErrors") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_WDB 0)IO_ERRORS")
    field(FLNK,"PLC:CLTS:PP14:WDLastIOTime.PROC")
}

record(longin,"PLC:CLTS:PP14:WDLastIOTime") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_WDB 0)LAST_IO_TIME")
    field(FLNK,"PLC:CLTS:PP14:WDMaxIOTime.PROC")
}

record(longin,"PLC:CLTS:PP14:WDMaxIOTime") {
    field(DTYP,"asynInt32")
    field(INP,"@asyn(CLTS_WDB 0)MAX_IO_TIME")
}