record(bi, "PPS:UND0:1:SECURELOOPA") {
  field(DESC, "Security_Loop_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_00[0]")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:SECURELOOPA",20,31,0,0,"PPS:UND0:1:SECURELOOPA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:STPERMA") {
  field(DESC, "Stopper_Perm_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_00[1]")
  field(ZNAM, "NOT_ENABLE")
  field(ONAM, "ENABLE")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:STPERMA",20,31,0,0,"PPS:UND0:1:STPERMA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:INTLKA") {
  field(DESC, "INTERLOCKS_CMPLT_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_00[2]")
  field(ZNAM, "NOT_COMPLETE")
  field(ONAM, "COMPLETE")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:INTLKA",20,31,0,0,"PPS:UND0:1:INTLKA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:SRCHRESETA") {
  field(DESC, "Search_Lat_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_00[4]")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:SRCHRESETA",20,31,0,0,"PPS:UND0:1:SRCHRESETA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:SRCHPRSETMUA") {
  field(DESC, "BTH_SP_Mu_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_00[6]")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:SRCHPRSETMUA",20,31,0,0,"PPS:LTU0:1:SRCHPRSETMUA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:SRCHPRSETWA") {
  field(DESC, "BTH_SP_WM_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_00[7]")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:SRCHPRSETWA",20,31,0,0,"PPS:LTU0:1:SRCHPRSETWA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:SRCHPRSETWA") {
  field(DESC, "UND_SP_W_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_00[8]")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:SRCHPRSETWA",20,31,0,0,"PPS:UND0:1:SRCHPRSETWA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:SRCHPRSETEA") {
  field(DESC, "UND_SP_E_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_00[9]")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:SRCHPRSETEA",20,31,0,0,"PPS:UND0:1:SRCHPRSETEA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:EMEROFFA") {
  field(DESC, "BTH_EO_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_00[10]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:EMEROFFA",20,31,0,0,"PPS:LTU0:1:EMEROFFA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:EMEREXITWA") {
  field(DESC, "BTH_EE_WM_LAT_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_00[11]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:EMEREXITWA",20,31,0,0,"PPS:LTU0:1:EMEREXITWA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:EMEREXITEA") {
  field(DESC, "BTH_EE_E_LAT_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_00[12]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:EMEREXITEA",20,31,0,0,"PPS:LTU0:1:EMEREXITEA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:KBANK1ECOMA") {
  field(DESC, "BTH_KB1_E_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_00[13]")
  field(ZNAM, "NOT_COMPLETE")
  field(ONAM, "COMPLETE")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:KBANK1ECOMA",20,31,0,0,"PPS:LTU0:1:KBANK1ECOMA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:KBANK2ECOMA") {
  field(DESC, "BTH_KB2_E_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_00[14]")
  field(ZNAM, "NOT_COMPLETE")
  field(ONAM, "COMPLETE")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:KBANK2ECOMA",20,31,0,0,"PPS:LTU0:1:KBANK2ECOMA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:KBANKELATA") {
  field(DESC, "BTH_KB_E_LAT_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_00[15]")
  field(ZNAM, "NOT_LATCHED")
  field(ONAM, "LATCHED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:KBANKELATA",20,31,0,0,"PPS:LTU0:1:KBANKELATA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:DOORWA") {
  field(DESC, "BTH_Door_WM_SUM_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_00[16]")
  field(ZNAM, "NOT_CLOSED")
  field(ONAM, "CLOSED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:DOORWA",20,31,0,0,"PPS:LTU0:1:DOORWA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:DOORWLATA") {
  field(DESC, "BTH_Door_WM_LAT_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_00[17]")
  field(ZNAM, "NOT_LATCHED")
  field(ONAM, "LATCHED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:DOORWLATA",20,31,0,0,"PPS:LTU0:1:DOORWLATA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:GATEWA") {
  field(DESC, "BTH_Gate_WM_SUM_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_00[18]")
  field(ZNAM, "NOT_CLOSED")
  field(ONAM, "CLOSED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:GATEWA",20,31,0,0,"PPS:LTU0:1:GATEWA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:GATEWLATA") {
  field(DESC, "BTH_Gate_WM_LAT_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_00[19]")
  field(ZNAM, "NOT_LATCHED")
  field(ONAM, "LATCHED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:GATEWLATA",20,31,0,0,"PPS:LTU0:1:GATEWLATA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:DOOREA") {
  field(DESC, "BTH_Door_E_SUM_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_00[20]")
  field(ZNAM, "NOT_CLOSED")
  field(ONAM, "CLOSED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:DOOREA",20,31,0,0,"PPS:LTU0:1:DOOREA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:DOORELATA") {
  field(DESC, "BTH_Door_E_LAT_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_00[21]")
  field(ZNAM, "NOT_LATCHED")
  field(ONAM, "LATCHED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:DOORELATA",20,31,0,0,"PPS:LTU0:1:DOORELATA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:GATEEA") {
  field(DESC, "BTH_Gate_E_SUM_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_00[22]")
  field(ZNAM, "NOT_CLOSED")
  field(ONAM, "CLOSED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:GATEEA",20,31,0,0,"PPS:LTU0:1:GATEEA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:GATEELATA") {
  field(DESC, "BTH_Gate_E_LAT_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_00[23]")
  field(ZNAM, "NOT_LATCHED")
  field(ONAM, "LATCHED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:GATEELATA",20,31,0,0,"PPS:LTU0:1:GATEELATA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:SECURELOOPB") {
  field(DESC, "Security_Loop_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_01[0]")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:SECURELOOPB",20,31,0,0,"PPS:UND0:1:SECURELOOPB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:STPERMB") {
  field(DESC, "Stopper_Perm_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_01[1]")
  field(ZNAM, "NOT_ENABLE")
  field(ONAM, "ENABLE")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:STPERMB",20,31,0,0,"PPS:UND0:1:STPERMB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:INTLKB") {
  field(DESC, "INTERLOCKS_CMPLT_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_01[2]")
  field(ZNAM, "NOT_COMPLETE")
  field(ONAM, "COMPLETE")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:INTLKB",20,31,0,0,"PPS:UND0:1:INTLKB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:SRCHRESETB") {
  field(DESC, "Search_Lat_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_01[4]")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:SRCHRESETB",20,31,0,0,"PPS:UND0:1:SRCHRESETB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:SRCHPRSETMUB") {
  field(DESC, "BTH_SP_Mu_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_01[6]")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:SRCHPRSETMUB",20,31,0,0,"PPS:LTU0:1:SRCHPRSETMUB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:SRCHPRSETWB") {
  field(DESC, "BTH_SP_WM_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_01[7]")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:SRCHPRSETWB",20,31,0,0,"PPS:LTU0:1:SRCHPRSETWB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:SRCHPRSETWB") {
  field(DESC, "UND_SP_W_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_01[8]")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:SRCHPRSETWB",20,31,0,0,"PPS:UND0:1:SRCHPRSETWB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:SRCHPRSETEB") {
  field(DESC, "UND_SP_E_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_01[9]")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:SRCHPRSETEB",20,31,0,0,"PPS:UND0:1:SRCHPRSETEB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:EMEROFFB") {
  field(DESC, "BTH_EO_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_01[10]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:EMEROFFB",20,31,0,0,"PPS:LTU0:1:EMEROFFB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:EMEREXITWB") {
  field(DESC, "BTH_EE_WM_LAT_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_01[11]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:EMEREXITWB",20,31,0,0,"PPS:LTU0:1:EMEREXITWB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:EMEREXITEB") {
  field(DESC, "BTH_EE_E_LAT_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_01[12]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:EMEREXITEB",20,31,0,0,"PPS:LTU0:1:EMEREXITEB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:KBANK1ECOMB") {
  field(DESC, "BTH_KB1_E_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_01[13]")
  field(ZNAM, "NOT_COMPLETE")
  field(ONAM, "COMPLETE")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:KBANK1ECOMB",20,31,0,0,"PPS:LTU0:1:KBANK1ECOMB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:KBANK2ECOMB") {
  field(DESC, "BTH_KB2_E_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_01[14]")
  field(ZNAM, "NOT_COMPLETE")
  field(ONAM, "COMPLETE")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:KBANK2ECOMB",20,31,0,0,"PPS:LTU0:1:KBANK2ECOMB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:KBANKELATB") {
  field(DESC, "BTH_KB_E_LAT_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_01[15]")
  field(ZNAM, "NOT_LATCHED")
  field(ONAM, "LATCHED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:KBANKELATB",20,31,0,0,"PPS:LTU0:1:KBANKELATB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:DOORWB") {
  field(DESC, "BTH_Door_WM_SUM_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_01[16]")
  field(ZNAM, "NOT_CLOSED")
  field(ONAM, "CLOSED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:DOORWB",20,31,0,0,"PPS:LTU0:1:DOORWB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:DOORWLATB") {
  field(DESC, "BTH_Door_WM_LAT_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_01[17]")
  field(ZNAM, "NOT_LATCHED")
  field(ONAM, "LATCHED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:DOORWLATB",20,31,0,0,"PPS:LTU0:1:DOORWLATB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:GATEWB") {
  field(DESC, "BTH_Gate_WM_SUM_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_01[18]")
  field(ZNAM, "NOT_CLOSED")
  field(ONAM, "CLOSED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:GATEWB",20,31,0,0,"PPS:LTU0:1:GATEWB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:GATEWLATB") {
  field(DESC, "BTH_Gate_WM_LAT_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_01[19]")
  field(ZNAM, "NOT_LATCHED")
  field(ONAM, "LATCHED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:GATEWLATB",20,31,0,0,"PPS:LTU0:1:GATEWLATB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:DOOREB") {
  field(DESC, "BTH_Door_E_SUM_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_01[20]")
  field(ZNAM, "NOT_CLOSED")
  field(ONAM, "CLOSED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:DOOREB",20,31,0,0,"PPS:LTU0:1:DOOREB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:DOORELATB") {
  field(DESC, "BTH_Door_E_LAT_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_01[21]")
  field(ZNAM, "NOT_LATCHED")
  field(ONAM, "LATCHED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:DOORELATB",20,31,0,0,"PPS:LTU0:1:DOORELATB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:GATEEB") {
  field(DESC, "BTH_Gate_E_SUM_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_01[22]")
  field(ZNAM, "NOT_CLOSED")
  field(ONAM, "CLOSED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:GATEEB",20,31,0,0,"PPS:LTU0:1:GATEEB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:GATEELATB") {
  field(DESC, "BTH_Gate_E_LAT_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_01[23]")
  field(ZNAM, "NOT_LATCHED")
  field(ONAM, "LATCHED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:GATEELATB",20,31,0,0,"PPS:LTU0:1:GATEELATB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:EMEROFFA") {
  field(DESC, "UND_EO_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_02[0]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:EMEROFFA",20,31,0,0,"PPS:UND0:1:EMEROFFA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:EMEREXITEA") {
  field(DESC, "UND_EE_E_LAT_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_02[1]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:EMEREXITEA",20,31,0,0,"PPS:UND0:1:EMEREXITEA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:GATEWA") {
  field(DESC, "UND_Gate_W_SUM_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_02[2]")
  field(ZNAM, "NOT_CLOSED")
  field(ONAM, "CLOSED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:GATEWA",20,31,0,0,"PPS:UND0:1:GATEWA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:GATEWLATA") {
  field(DESC, "UND_Gate_W_LAT_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_02[3]")
  field(ZNAM, "NOT_LATCHED")
  field(ONAM, "LATCHED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:GATEWLATA",20,31,0,0,"PPS:UND0:1:GATEWLATA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:GATEEA") {
  field(DESC, "UND_Gate_E_SUM_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_02[4]")
  field(ZNAM, "NOT_CLOSED")
  field(ONAM, "CLOSED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:GATEEA",20,31,0,0,"PPS:UND0:1:GATEEA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:GATEELATA") {
  field(DESC, "UND_Gate_E_LAT_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_02[5]")
  field(ZNAM, "NOT_LATCHED")
  field(ONAM, "LATCHED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:GATEELATA",20,31,0,0,"PPS:UND0:1:GATEELATA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:EMEROFFB") {
  field(DESC, "UND_EO_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_03[0]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:EMEROFFB",20,31,0,0,"PPS:UND0:1:EMEROFFB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:EMEREXITEB") {
  field(DESC, "UND_EE_E_LAT_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_03[1]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:EMEREXITEB",20,31,0,0,"PPS:UND0:1:EMEREXITEB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:GATEWB") {
  field(DESC, "UND_Gate_W_SUM_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_03[2]")
  field(ZNAM, "NOT_CLOSED")
  field(ONAM, "CLOSED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:GATEWB",20,31,0,0,"PPS:UND0:1:GATEWB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:GATEWLATB") {
  field(DESC, "UND_Gate_W_LAT_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_03[3]")
  field(ZNAM, "NOT_LATCHED")
  field(ONAM, "LATCHED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:GATEWLATB",20,31,0,0,"PPS:UND0:1:GATEWLATB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:GATEEB") {
  field(DESC, "UND_Gate_E_SUM_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_03[4]")
  field(ZNAM, "NOT_CLOSED")
  field(ONAM, "CLOSED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:GATEEB",20,31,0,0,"PPS:UND0:1:GATEEB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:GATEELATB") {
  field(DESC, "UND_Gate_E_LAT_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_03[5]")
  field(ZNAM, "NOT_LATCHED")
  field(ONAM, "LATCHED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:GATEELATB",20,31,0,0,"PPS:UND0:1:GATEELATB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:DMP0:1:SRCHPRSET1B") {
  field(DESC, "DMP_SP_1_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_03[6]")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:DMP0:1:SRCHPRSET1B",20,31,0,0,"PPS:DMP0:1:SRCHPRSET1B")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:SRCHPRSETEL") {
  field(DESC, "S_Preset_BTHW_Egress_LED")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_04[0]")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:SRCHPRSETEL",20,31,0,0,"PPS:LTU0:1:SRCHPRSETEL")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:SRCHPRSETMUL") {
  field(DESC, "S_Preset_BTHW_Muon_LED")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_04[1]")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:SRCHPRSETMUL",20,31,0,0,"PPS:LTU0:1:SRCHPRSETMUL")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:SRCHPRSETWL") {
  field(DESC, "S_Preset_BTHWM_LED")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_04[2]")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:SRCHPRSETWL",20,31,0,0,"PPS:LTU0:1:SRCHPRSETWL")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:SRCHPRSETEL") {
  field(DESC, "S_Preset_BTHW_UNDE_LED")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_04[3]")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:SRCHPRSETEL",20,31,0,0,"PPS:UND0:1:SRCHPRSETEL")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:SRCHPRSETWL") {
  field(DESC, "S_Preset_BTHW_UNDW__LED")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_04[4]")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:SRCHPRSETWL",20,31,0,0,"PPS:UND0:1:SRCHPRSETWL")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:SRCHRSETEL") {
  field(DESC, "S_Reset_BTH_E_LED")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_04[5]")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:SRCHRSETEL",20,31,0,0,"PPS:LTU0:1:SRCHRSETEL")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:PERMACC") {
  field(DESC, "PA_BTH_E")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_04[9]")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:PERMACC",20,31,0,0,"PPS:UND0:1:PERMACC")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:CTRLACC") {
  field(DESC, "CA_BTH_E")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_04[10]")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:CTRLACC",20,31,0,0,"PPS:UND0:1:CTRLACC")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:NOACC") {
  field(DESC, "NA_BTH_E")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_04[11]")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:NOACC",20,31,0,0,"PPS:UND0:1:NOACC")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:MAGLOCKE") {
  field(DESC, "Mlock_Switch_BTH_E")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_04[16]")
  field(ZNAM, "NOT_LOCKED")
  field(ONAM, "LOCKED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:MAGLOCKE",20,31,0,0,"PPS:LTU0:1:MAGLOCKE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:CBWVIO") {
  field(DESC, "BTHW_CrashBar_Violation")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_04[21]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:CBWVIO",20,31,0,0,"PPS:LTU0:1:CBWVIO")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:CBEVIO") {
  field(DESC, "BTH_E_CrashBar_Violation")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_04[22]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:CBEVIO",20,31,0,0,"PPS:LTU0:1:CBEVIO")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:LTU0:1:CBVIO") {
  field(DESC, "DMP_CrashBar_Violation")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_04[23]")
  field(ZNAM, "GREEN")
  field(ONAM, "RED")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:LTU0:1:CBVIO",20,31,0,0,"PPS:LTU0:1:CBVIO")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:172:PPSTRIPA") {
  field(DESC, "BTM1_TRPA")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[0]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:172:PPSTRIPA",20,31,0,0,"BTM:LTU0:172:PPSTRIPA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:172:PPSTRIPB") {
  field(DESC, "BTM1_TRPB")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[1]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:172:PPSTRIPB",20,31,0,0,"BTM:LTU0:172:PPSTRIPB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:226:PPSTRIPA") {
  field(DESC, "BTM2_TRPA")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[2]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:226:PPSTRIPA",20,31,0,0,"BTM:LTU0:226:PPSTRIPA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:226:PPSTRIPB") {
  field(DESC, "BTM2_TRPB")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[3]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:226:PPSTRIPB",20,31,0,0,"BTM:LTU0:226:PPSTRIPB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:300:PPSTRIPA") {
  field(DESC, "BTM3_TRPA")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[4]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:300:PPSTRIPA",20,31,0,0,"BTM:LTU0:300:PPSTRIPA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:300:PPSTRIPB") {
  field(DESC, "BTM3_TRPB")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[5]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:300:PPSTRIPB",20,31,0,0,"BTM:LTU0:300:PPSTRIPB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:440:PPSTRIPA") {
  field(DESC, "BTM4_TRPA")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[6]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:440:PPSTRIPA",20,31,0,0,"BTM:LTU0:440:PPSTRIPA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:440:PPSTRIPB") {
  field(DESC, "BTM4_TRPB")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[7]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:440:PPSTRIPB",20,31,0,0,"BTM:LTU0:440:PPSTRIPB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:507:PPSTRIPA") {
  field(DESC, "BTM5_TRPA")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[8]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:507:PPSTRIPA",20,31,0,0,"BTM:LTU0:507:PPSTRIPA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:507:PPSTRIPB") {
  field(DESC, "BTM5_TRPB")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[9]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:507:PPSTRIPB",20,31,0,0,"BTM:LTU0:507:PPSTRIPB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:645:PPSTRIPA") {
  field(DESC, "BTM6_TRPA")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[10]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:645:PPSTRIPA",20,31,0,0,"BTM:LTU0:645:PPSTRIPA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:645:PPSTRIPB") {
  field(DESC, "BTM6_TRPB")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[11]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:645:PPSTRIPB",20,31,0,0,"BTM:LTU0:645:PPSTRIPB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:648:PPSTRIPA") {
  field(DESC, "BTM7_TRPA")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[12]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:648:PPSTRIPA",20,31,0,0,"BTM:LTU0:648:PPSTRIPA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:648:PPSTRIPB") {
  field(DESC, "BTM7_TRPB")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[13]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:648:PPSTRIPB",20,31,0,0,"BTM:LTU0:648:PPSTRIPB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:687:PPSTRIPA") {
  field(DESC, "BTM8_TRPA")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[14]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:687:PPSTRIPA",20,31,0,0,"BTM:LTU0:687:PPSTRIPA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:687:PPSTRIPB") {
  field(DESC, "BTM8_TRPB")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[15]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:687:PPSTRIPB",20,31,0,0,"BTM:LTU0:687:PPSTRIPB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:717:PPSTRIPA") {
  field(DESC, "BTM9_TRPA")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[16]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:717:PPSTRIPA",20,31,0,0,"BTM:LTU0:717:PPSTRIPA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:717:PPSTRIPB") {
  field(DESC, "BTM9_TRPB")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[17]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:717:PPSTRIPB",20,31,0,0,"BTM:LTU0:717:PPSTRIPB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:451:PPSTRIPA") {
  field(DESC, "BTM10_TRPA")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[18]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:451:PPSTRIPA",20,31,0,0,"BTM:DMP0:451:PPSTRIPA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:451:PPSTRIPB") {
  field(DESC, "BTM10_TRPB")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[19]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:451:PPSTRIPB",20,31,0,0,"BTM:DMP0:451:PPSTRIPB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:699:PPSTRIPA") {
  field(DESC, "BTM11_TRPA")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[20]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:699:PPSTRIPA",20,31,0,0,"BTM:DMP0:699:PPSTRIPA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:699:PPSTRIPB") {
  field(DESC, "BTM11_TRPB")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[21]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:699:PPSTRIPB",20,31,0,0,"BTM:DMP0:699:PPSTRIPB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:711:PPSTRIPA") {
  field(DESC, "BTM12_TRPA")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[22]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:711:PPSTRIPA",20,31,0,0,"BTM:DMP0:711:PPSTRIPA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:711:PPSTRIPB") {
  field(DESC, "BTM12_TRPB")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[23]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:711:PPSTRIPB",20,31,0,0,"BTM:DMP0:711:PPSTRIPB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:741:PPSTRIPA") {
  field(DESC, "BTM13_TRPA")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[24]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:741:PPSTRIPA",20,31,0,0,"BTM:DMP0:741:PPSTRIPA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:741:PPSTRIPB") {
  field(DESC, "BTM13_TRPB")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[25]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:741:PPSTRIPB",20,31,0,0,"BTM:DMP0:741:PPSTRIPB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:771:PPSTRIPA") {
  field(DESC, "BTM14_TRPA")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[26]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:771:PPSTRIPA",20,31,0,0,"BTM:DMP0:771:PPSTRIPA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:771:PPSTRIPB") {
  field(DESC, "BTM14_TRPB")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[27]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:771:PPSTRIPB",20,31,0,0,"BTM:DMP0:771:PPSTRIPB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:801:PPSTRIPA") {
  field(DESC, "BTM15_TRPA")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[28]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:801:PPSTRIPA",20,31,0,0,"BTM:DMP0:801:PPSTRIPA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:801:PPSTRIPB") {
  field(DESC, "BTM15_TRPB")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[29]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:801:PPSTRIPB",20,31,0,0,"BTM:DMP0:801:PPSTRIPB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:999:PPSTRIPA") {
  field(DESC, "BTM16_TRPA")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[30]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:999:PPSTRIPA",20,31,0,0,"BTM:DMP0:999:PPSTRIPA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:999:PPSTRIPB") {
  field(DESC, "BTM16_TRPB")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_05[31]")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:999:PPSTRIPB",20,31,0,0,"BTM:DMP0:999:PPSTRIPB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:BSY0:1:BSP_IN_SUM") {
  field(DESC, "BSY_BTH_BSP")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_06[0]")
  field(ZNAM, "NOT_IN")
  field(ONAM, "IN")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:BSY0:1:BSP_IN_SUM",20,31,0,0,"PPS:BSY0:1:BSP_IN_SUM")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:LOOPA") {
  field(DESC, "Loop_A_Cmplt")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_06[16]")
  field(ZNAM, "NOT_COMPLETE")
  field(ONAM, "COMPLETE")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:LOOPA",20,31,0,0,"PPS:UND0:1:LOOPA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:LOOPLATA") {
  field(DESC, "Loop_A_Lat")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_06[17]")
  field(ZNAM, "NOT_LATCHED")
  field(ONAM, "LATCHED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:LOOPLATA",20,31,0,0,"PPS:UND0:1:LOOPLATA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:LOOPB") {
  field(DESC, "Loop_B_Cmplt")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_06[18]")
  field(ZNAM, "NOT_COMPLETE")
  field(ONAM, "COMPLETE")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:LOOPB",20,31,0,0,"PPS:UND0:1:LOOPB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:LOOPLATB") {
  field(DESC, "Loop_B_Lat")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_06[19]")
  field(ZNAM, "NOT_LATCHED")
  field(ONAM, "LATCHED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:LOOPLATB",20,31,0,0,"PPS:UND0:1:LOOPLATB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:LOOPNOTA") {
  field(DESC, "Loop_A_NOT_Cmplt")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_06[20]")
  field(ZNAM, "COMPLETE")
  field(ONAM, "NOT_COMPLET")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:LOOPNOTA",20,31,0,0,"PPS:UND0:1:LOOPNOTA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:LOOPNOTB") {
  field(DESC, "Loop_B_NOT_Cmplt")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_06[21]")
  field(ZNAM, "COMPLETE")
  field(ONAM, "NOT_COMPLETE")
  field(ZSV, "NO_ALARM")
  field(OSV, "MINOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:LOOPNOTB",20,31,0,0,"PPS:UND0:1:LOOPNOTB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:XTCAVOFFA") {
  field(DESC, "XTCAV_OFF_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_06[22]")
  field(ZNAM, "NOT_OFF")
  field(ONAM, "OFF")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:XTCAVOFFA",20,31,0,0,"PPS:UND0:1:XTCAVOFFA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:XTCAVOFFB") {
  field(DESC, "XTCAV_OFF_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_06[23]")
  field(ZNAM, "NOT_OFF")
  field(ONAM, "OFF")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:XTCAVOFFB",20,31,0,0,"PPS:UND0:1:XTCAVOFFB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:XTCAVPERMA") {
  field(DESC, "XTCAV_PERMIT_A")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_06[24]")
  field(ZNAM, "NO_PERMIT")
  field(ONAM, "PERMIT")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:XTCAVPERMA",20,31,0,0,"PPS:UND0:1:XTCAVPERMA")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:XTCAVPERMB") {
  field(DESC, "XTCAV_PERMIT_B")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_06[25]")
  field(ZNAM, "NO_PERMIT")
  field(ONAM, "PERMIT")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:XTCAVPERMB",20,31,0,0,"PPS:UND0:1:XTCAVPERMB")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "PPS:UND0:1:XTCAVDISABLE") {
  field(DESC, "XTCAV_DISABLE")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_1.Data_06[26]")
  field(ZNAM, "NOT_DISABLED")
  field(ONAM, "DISABLED")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PPS:UND0:1:XTCAVDISABLE",20,31,0,0,"PPS:UND0:1:XTCAVDISABLE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:172:VENTTIMEOUT") {
  field(DESC, "BTM1_Vent_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_00[0]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:172:VENTTIMEOUT",20,31,0,0,"BTM:LTU0:172:VENTTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:226:VENTTIMEOUT") {
  field(DESC, "BTM2_Vent_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_00[1]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:226:VENTTIMEOUT",20,31,0,0,"BTM:LTU0:226:VENTTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:300:VENTTIMEOUT") {
  field(DESC, "BTM3_Vent_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_00[2]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:300:VENTTIMEOUT",20,31,0,0,"BTM:LTU0:300:VENTTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:440:VENTTIMEOUT") {
  field(DESC, "BTM4_Vent_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_00[3]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:440:VENTTIMEOUT",20,31,0,0,"BTM:LTU0:440:VENTTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:507:VENTTIMEOUT") {
  field(DESC, "BTM5_Vent_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_00[4]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:507:VENTTIMEOUT",20,31,0,0,"BTM:LTU0:507:VENTTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:645:VENTTIMEOUT") {
  field(DESC, "BTM6_Vent_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_00[5]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:645:VENTTIMEOUT",20,31,0,0,"BTM:LTU0:645:VENTTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:648:VENTTIMEOUT") {
  field(DESC, "BTM7_Vent_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_00[6]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:648:VENTTIMEOUT",20,31,0,0,"BTM:LTU0:648:VENTTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:687:VENTTIMEOUT") {
  field(DESC, "BTM8_Vent_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_00[7]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:687:VENTTIMEOUT",20,31,0,0,"BTM:LTU0:687:VENTTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:717:VENTTIMEOUT") {
  field(DESC, "BTM9_Vent_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_00[8]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:717:VENTTIMEOUT",20,31,0,0,"BTM:LTU0:717:VENTTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:451:VENTTIMEOUT") {
  field(DESC, "BTM10_Vent_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_00[9]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:451:VENTTIMEOUT",20,31,0,0,"BTM:DMP0:451:VENTTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:699:VENTTIMEOUT") {
  field(DESC, "BTM11_Vent_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_00[10]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:699:VENTTIMEOUT",20,31,0,0,"BTM:DMP0:699:VENTTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:711:VENTTIMEOUT") {
  field(DESC, "BTM12_Vent_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_00[11]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:711:VENTTIMEOUT",20,31,0,0,"BTM:DMP0:711:VENTTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:741:VENTTIMEOUT") {
  field(DESC, "BTM13_Vent_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_00[12]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:741:VENTTIMEOUT",20,31,0,0,"BTM:DMP0:741:VENTTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:771:VENTTIMEOUT") {
  field(DESC, "BTM14_Vent_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_00[13]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:771:VENTTIMEOUT",20,31,0,0,"BTM:DMP0:771:VENTTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:801:VENTTIMEOUT") {
  field(DESC, "BTM15_Vent_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_00[14]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:801:VENTTIMEOUT",20,31,0,0,"BTM:DMP0:801:VENTTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:999:VENTTIMEOUT") {
  field(DESC, "BTM16_Vent_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_00[15]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:999:VENTTIMEOUT",20,31,0,0,"BTM:DMP0:999:VENTTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:172:FILLTIMEOUT") {
  field(DESC, "BTM1_Fill_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_01[0]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:172:FILLTIMEOUT",20,31,0,0,"BTM:LTU0:172:FILLTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:226:FILLTIMEOUT") {
  field(DESC, "BTM2_Fill_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_01[1]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:226:FILLTIMEOUT",20,31,0,0,"BTM:LTU0:226:FILLTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:300:FILLTIMEOUT") {
  field(DESC, "BTM3_Fill_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_01[2]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:300:FILLTIMEOUT",20,31,0,0,"BTM:LTU0:300:FILLTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:440:FILLTIMEOUT") {
  field(DESC, "BTM4_Fill_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_01[3]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:440:FILLTIMEOUT",20,31,0,0,"BTM:LTU0:440:FILLTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:507:FILLTIMEOUT") {
  field(DESC, "BTM5_Fill_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_01[4]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:507:FILLTIMEOUT",20,31,0,0,"BTM:LTU0:507:FILLTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:645:FILLTIMEOUT") {
  field(DESC, "BTM6_Fill_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_01[5]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:645:FILLTIMEOUT",20,31,0,0,"BTM:LTU0:645:FILLTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:648:FILLTIMEOUT") {
  field(DESC, "BTM7_Fill_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_01[6]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:648:FILLTIMEOUT",20,31,0,0,"BTM:LTU0:648:FILLTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:687:FILLTIMEOUT") {
  field(DESC, "BTM8_Fill_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_01[7]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:687:FILLTIMEOUT",20,31,0,0,"BTM:LTU0:687:FILLTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:717:FILLTIMEOUT") {
  field(DESC, "BTM9_Fill_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_01[8]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:717:FILLTIMEOUT",20,31,0,0,"BTM:LTU0:717:FILLTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:451:FILLTIMEOUT") {
  field(DESC, "BTM10_Fill_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_01[9]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:451:FILLTIMEOUT",20,31,0,0,"BTM:DMP0:451:FILLTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:699:FILLTIMEOUT") {
  field(DESC, "BTM11_Fill_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_01[10]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:699:FILLTIMEOUT",20,31,0,0,"BTM:DMP0:699:FILLTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:711:FILLTIMEOUT") {
  field(DESC, "BTM12_Fill_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_01[11]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:711:FILLTIMEOUT",20,31,0,0,"BTM:DMP0:711:FILLTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:741:FILLTIMEOUT") {
  field(DESC, "BTM13_Fill_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_01[12]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:741:FILLTIMEOUT",20,31,0,0,"BTM:DMP0:741:FILLTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:771:FILLTIMEOUT") {
  field(DESC, "BTM14_Fill_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_01[13]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:771:FILLTIMEOUT",20,31,0,0,"BTM:DMP0:771:FILLTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:801:FILLTIMEOUT") {
  field(DESC, "BTM15_Fill_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_01[14]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:801:FILLTIMEOUT",20,31,0,0,"BTM:DMP0:801:FILLTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:999:FILLTIMEOUT") {
  field(DESC, "BTM16_Fill_Timeout")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_01[15]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:999:FILLTIMEOUT",20,31,0,0,"BTM:DMP0:999:FILLTIMEOUT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:172:FLOWRATEFAULT") {
  field(DESC, "BTM1_Flow_Rate_Exceeded")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_02[0]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:172:FLOWRATEFAULT",20,31,0,0,"BTM:LTU0:172:FLOWRATEFAULT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:226:FLOWRATEFAULT") {
  field(DESC, "BTM2_Flow_Rate_Exceeded")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_02[1]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:226:FLOWRATEFAULT",20,31,0,0,"BTM:LTU0:226:FLOWRATEFAULT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:300:FLOWRATEFAULT") {
  field(DESC, "BTM3_Flow_Rate_Exceeded")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_02[2]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:300:FLOWRATEFAULT",20,31,0,0,"BTM:LTU0:300:FLOWRATEFAULT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:440:FLOWRATEFAULT") {
  field(DESC, "BTM4_Flow_Rate_Exceeded")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_02[3]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:440:FLOWRATEFAULT",20,31,0,0,"BTM:LTU0:440:FLOWRATEFAULT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:507:FLOWRATEFAULT") {
  field(DESC, "BTM5_Flow_Rate_Exceeded")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_02[4]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:507:FLOWRATEFAULT",20,31,0,0,"BTM:LTU0:507:FLOWRATEFAULT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:645:FLOWRATEFAULT") {
  field(DESC, "BTM6_Flow_Rate_Exceeded")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_02[5]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:645:FLOWRATEFAULT",20,31,0,0,"BTM:LTU0:645:FLOWRATEFAULT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:648:FLOWRATEFAULT") {
  field(DESC, "BTM7_Flow_Rate_Exceeded")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_02[6]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:648:FLOWRATEFAULT",20,31,0,0,"BTM:LTU0:648:FLOWRATEFAULT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:687:FLOWRATEFAULT") {
  field(DESC, "BTM8_Flow_Rate_Exceeded")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_02[7]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:687:FLOWRATEFAULT",20,31,0,0,"BTM:LTU0:687:FLOWRATEFAULT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:717:FLOWRATEFAULT") {
  field(DESC, "BTM9_Flow_Rate_Exceeded")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_02[8]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:717:FLOWRATEFAULT",20,31,0,0,"BTM:LTU0:717:FLOWRATEFAULT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:451:FLOWRATEFAULT") {
  field(DESC, "BTM10_Flow_Rate_Exceeded")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_02[9]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:451:FLOWRATEFAULT",20,31,0,0,"BTM:DMP0:451:FLOWRATEFAULT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:699:FLOWRATEFAULT") {
  field(DESC, "BTM11_Flow_Rate_Exceeded")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_02[10]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:699:FLOWRATEFAULT",20,31,0,0,"BTM:DMP0:699:FLOWRATEFAULT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:711:FLOWRATEFAULT") {
  field(DESC, "BTM12_Flow_Rate_Exceeded")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_02[11]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:711:FLOWRATEFAULT",20,31,0,0,"BTM:DMP0:711:FLOWRATEFAULT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:741:FLOWRATEFAULT") {
  field(DESC, "BTM13_Flow_Rate_Exceeded")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_02[12]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:741:FLOWRATEFAULT",20,31,0,0,"BTM:DMP0:741:FLOWRATEFAULT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:771:FLOWRATEFAULT") {
  field(DESC, "BTM14_Flow_Rate_Exceeded")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_02[13]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:771:FLOWRATEFAULT",20,31,0,0,"BTM:DMP0:771:FLOWRATEFAULT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:801:FLOWRATEFAULT") {
  field(DESC, "BTM15_Flow_Rate_Exceeded")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_02[14]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:801:FLOWRATEFAULT",20,31,0,0,"BTM:DMP0:801:FLOWRATEFAULT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:999:FLOWRATEFAULT") {
  field(DESC, "BTM16_Flow_Rate_Exceeded")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_02[15]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:999:FLOWRATEFAULT",20,31,0,0,"BTM:DMP0:999:FLOWRATEFAULT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:172:OVERPRESSURE") {
  field(DESC, "BTM1_Over_Pressure")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_03[0]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:172:OVERPRESSURE",20,31,0,0,"BTM:LTU0:172:OVERPRESSURE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:226:OVERPRESSURE") {
  field(DESC, "BTM2_Over_Pressure")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_03[1]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:226:OVERPRESSURE",20,31,0,0,"BTM:LTU0:226:OVERPRESSURE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:300:OVERPRESSURE") {
  field(DESC, "BTM3_Over_Pressure")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_03[2]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:300:OVERPRESSURE",20,31,0,0,"BTM:LTU0:300:OVERPRESSURE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:440:OVERPRESSURE") {
  field(DESC, "BTM4_Over_Pressure")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_03[3]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:440:OVERPRESSURE",20,31,0,0,"BTM:LTU0:440:OVERPRESSURE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:507:OVERPRESSURE") {
  field(DESC, "BTM5_Over_Pressure")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_03[4]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:507:OVERPRESSURE",20,31,0,0,"BTM:LTU0:507:OVERPRESSURE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:645:OVERPRESSURE") {
  field(DESC, "BTM6_Over_Pressure")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_03[5]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:645:OVERPRESSURE",20,31,0,0,"BTM:LTU0:645:OVERPRESSURE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:648:OVERPRESSURE") {
  field(DESC, "BTM7_Over_Pressure")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_03[6]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:648:OVERPRESSURE",20,31,0,0,"BTM:LTU0:648:OVERPRESSURE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:687:OVERPRESSURE") {
  field(DESC, "BTM8_Over_Pressure")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_03[7]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:687:OVERPRESSURE",20,31,0,0,"BTM:LTU0:687:OVERPRESSURE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:717:OVERPRESSURE") {
  field(DESC, "BTM9_Over_Pressure")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_03[8]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:717:OVERPRESSURE",20,31,0,0,"BTM:LTU0:717:OVERPRESSURE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:451:OVERPRESSURE") {
  field(DESC, "BTM10_Over_Pressure")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_03[9]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:451:OVERPRESSURE",20,31,0,0,"BTM:DMP0:451:OVERPRESSURE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:699:OVERPRESSURE") {
  field(DESC, "BTM11_Over_Pressure")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_03[10]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:699:OVERPRESSURE",20,31,0,0,"BTM:DMP0:699:OVERPRESSURE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:711:OVERPRESSURE") {
  field(DESC, "BTM12_Over_Pressure")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_03[11]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:711:OVERPRESSURE",20,31,0,0,"BTM:DMP0:711:OVERPRESSURE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:741:OVERPRESSURE") {
  field(DESC, "BTM13_Over_Pressure")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_03[12]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:741:OVERPRESSURE",20,31,0,0,"BTM:DMP0:741:OVERPRESSURE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:771:OVERPRESSURE") {
  field(DESC, "BTM14_Over_Pressure")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_03[13]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:771:OVERPRESSURE",20,31,0,0,"BTM:DMP0:771:OVERPRESSURE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:801:OVERPRESSURE") {
  field(DESC, "BTM15_Over_Pressure")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_03[14]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:801:OVERPRESSURE",20,31,0,0,"BTM:DMP0:801:OVERPRESSURE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:999:OVERPRESSURE") {
  field(DESC, "BTM16_Over_Pressure")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_03[15]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:999:OVERPRESSURE",20,31,0,0,"BTM:DMP0:999:OVERPRESSURE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:172:LOPRESSRSTRT") {
  field(DESC, "BTM1_Low_Pressure_Start")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_04[0]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:172:LOPRESSRSTRT",20,31,0,0,"BTM:LTU0:172:LOPRESSRSTRT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:226:LOPRESSRSTRT") {
  field(DESC, "BTM2_Low_Pressure_Start")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_04[1]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:226:LOPRESSRSTRT",20,31,0,0,"BTM:LTU0:226:LOPRESSRSTRT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:300:LOPRESSRSTRT") {
  field(DESC, "BTM3_Low_Pressure_Start")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_04[2]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:300:LOPRESSRSTRT",20,31,0,0,"BTM:LTU0:300:LOPRESSRSTRT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:440:LOPRESSRSTRT") {
  field(DESC, "BTM4_Low_Pressure_Start")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_04[3]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:440:LOPRESSRSTRT",20,31,0,0,"BTM:LTU0:440:LOPRESSRSTRT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:507:LOPRESSRSTRT") {
  field(DESC, "BTM5_Low_Pressure_Start")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_04[4]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:507:LOPRESSRSTRT",20,31,0,0,"BTM:LTU0:507:LOPRESSRSTRT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:645:LOPRESSRSTRT") {
  field(DESC, "BTM6_Low_Pressure_Start")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_04[5]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:645:LOPRESSRSTRT",20,31,0,0,"BTM:LTU0:645:LOPRESSRSTRT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:648:LOPRESSRSTRT") {
  field(DESC, "BTM7_Low_Pressure_Start")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_04[6]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:648:LOPRESSRSTRT",20,31,0,0,"BTM:LTU0:648:LOPRESSRSTRT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:687:LOPRESSRSTRT") {
  field(DESC, "BTM8_Low_Pressure_Start")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_04[7]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:687:LOPRESSRSTRT",20,31,0,0,"BTM:LTU0:687:LOPRESSRSTRT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:717:LOPRESSRSTRT") {
  field(DESC, "BTM9_Low_Pressure_Start")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_04[8]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:717:LOPRESSRSTRT",20,31,0,0,"BTM:LTU0:717:LOPRESSRSTRT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:451:LOPRESSRSTRT") {
  field(DESC, "BTM10_Low_Pressure_Start")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_04[9]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:451:LOPRESSRSTRT",20,31,0,0,"BTM:DMP0:451:LOPRESSRSTRT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:699:LOPRESSRSTRT") {
  field(DESC, "BTM11_Low_Pressure_Start")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_04[10]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:699:LOPRESSRSTRT",20,31,0,0,"BTM:DMP0:699:LOPRESSRSTRT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:711:LOPRESSRSTRT") {
  field(DESC, "BTM12_Low_Pressure_Start")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_04[11]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:711:LOPRESSRSTRT",20,31,0,0,"BTM:DMP0:711:LOPRESSRSTRT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:741:LOPRESSRSTRT") {
  field(DESC, "BTM13_Low_Pressure_Start")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_04[12]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:741:LOPRESSRSTRT",20,31,0,0,"BTM:DMP0:741:LOPRESSRSTRT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:771:LOPRESSRSTRT") {
  field(DESC, "BTM14_Low_Pressure_Start")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_04[13]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:771:LOPRESSRSTRT",20,31,0,0,"BTM:DMP0:771:LOPRESSRSTRT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:801:LOPRESSRSTRT") {
  field(DESC, "BTM15_Low_Pressure_Start")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_04[14]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:801:LOPRESSRSTRT",20,31,0,0,"BTM:DMP0:801:LOPRESSRSTRT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:999:LOPRESSRSTRT") {
  field(DESC, "BTM16_Low_Pressure_Start")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_04[15]")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:999:LOPRESSRSTRT",20,31,0,0,"BTM:DMP0:999:LOPRESSRSTRT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:172:UNITTEST") {
  field(DESC, "BTM1_Unit_Test")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_05[0]")
  field(ZNAM, "OK")
  field(ONAM, "RUNNING")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:172:UNITTEST",20,31,0,0,"BTM:LTU0:172:UNITTEST")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:226:UNITTEST") {
  field(DESC, "BTM2_Unit_Test")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_05[1]")
  field(ZNAM, "OK")
  field(ONAM, "RUNNING")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:226:UNITTEST",20,31,0,0,"BTM:LTU0:226:UNITTEST")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:300:UNITTEST") {
  field(DESC, "BTM3_Unit_Test")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_05[2]")
  field(ZNAM, "OK")
  field(ONAM, "RUNNING")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:300:UNITTEST",20,31,0,0,"BTM:LTU0:300:UNITTEST")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:440:UNITTEST") {
  field(DESC, "BTM4_Unit_Test")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_05[3]")
  field(ZNAM, "OK")
  field(ONAM, "RUNNING")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:440:UNITTEST",20,31,0,0,"BTM:LTU0:440:UNITTEST")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:507:UNITTEST") {
  field(DESC, "BTM5_Unit_Test")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_05[4]")
  field(ZNAM, "OK")
  field(ONAM, "RUNNING")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:507:UNITTEST",20,31,0,0,"BTM:LTU0:507:UNITTEST")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:645:UNITTEST") {
  field(DESC, "BTM6_Unit_Test")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_05[5]")
  field(ZNAM, "OK")
  field(ONAM, "RUNNING")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:645:UNITTEST",20,31,0,0,"BTM:LTU0:645:UNITTEST")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:648:UNITTEST") {
  field(DESC, "BTM7_Unit_Test")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_05[6]")
  field(ZNAM, "OK")
  field(ONAM, "RUNNING")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:648:UNITTEST",20,31,0,0,"BTM:LTU0:648:UNITTEST")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:687:UNITTEST") {
  field(DESC, "BTM8_Unit_Test")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_05[7]")
  field(ZNAM, "OK")
  field(ONAM, "RUNNING")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:687:UNITTEST",20,31,0,0,"BTM:LTU0:687:UNITTEST")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:LTU0:717:UNITTEST") {
  field(DESC, "BTM9_Unit_Test")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_05[8]")
  field(ZNAM, "OK")
  field(ONAM, "RUNNING")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:LTU0:717:UNITTEST",20,31,0,0,"BTM:LTU0:717:UNITTEST")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:451:UNITTEST") {
  field(DESC, "BTM10_Unit_Test")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_05[9]")
  field(ZNAM, "OK")
  field(ONAM, "RUNNING")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:451:UNITTEST",20,31,0,0,"BTM:DMP0:451:UNITTEST")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:699:UNITTEST") {
  field(DESC, "BTM11_Unit_Test")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_05[10]")
  field(ZNAM, "OK")
  field(ONAM, "RUNNING")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:699:UNITTEST",20,31,0,0,"BTM:DMP0:699:UNITTEST")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:711:UNITTEST") {
  field(DESC, "BTM12_Unit_Test")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_05[11]")
  field(ZNAM, "OK")
  field(ONAM, "RUNNING")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:711:UNITTEST",20,31,0,0,"BTM:DMP0:711:UNITTEST")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:741:UNITTEST") {
  field(DESC, "BTM13_Unit_Test")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_05[12]")
  field(ZNAM, "OK")
  field(ONAM, "RUNNING")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:741:UNITTEST",20,31,0,0,"BTM:DMP0:741:UNITTEST")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:771:UNITTEST") {
  field(DESC, "BTM14_Unit_Test")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_05[13]")
  field(ZNAM, "OK")
  field(ONAM, "RUNNING")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:771:UNITTEST",20,31,0,0,"BTM:DMP0:771:UNITTEST")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:801:UNITTEST") {
  field(DESC, "BTM15_Unit_Test")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_05[14]")
  field(ZNAM, "OK")
  field(ONAM, "RUNNING")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:801:UNITTEST",20,31,0,0,"BTM:DMP0:801:UNITTEST")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(bi, "BTM:DMP0:999:UNITTEST") {
  field(DESC, "BTM16_Unit_Test")
  field(SCAN, ".1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_8.Data_05[15]")
  field(ZNAM, "OK")
  field(ONAM, "RUNNING")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BTM:DMP0:999:UNITTEST",20,31,0,0,"BTM:DMP0:999:UNITTEST")
record(ai,"BTM:LTU0:172:PPSTRIPPRSSR") {
  field(DESC, "BTM1_Trip_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_2.Data_00")
  field(HIHI, "13")
  field(LOLO, "5")
  field(HIGH, "10")
  field(LOW, "8")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:LTU0:172:PPSRSETPRSSR") {
  field(DESC, "BTM1_Reset_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_2.Data_01")
  field(HIHI, "15")
  field(LOLO, "7")
  field(HIGH, "12")
  field(LOW, "10")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:LTU0:226:PPSTRIPPRSSR") {
  field(DESC, "BTM2_Trip_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_2.Data_02")
  field(HIHI, "13")
  field(LOLO, "5")
  field(HIGH, "10")
  field(LOW, "8")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:LTU0:226:PPSRSETPRSSR") {
  field(DESC, "BTM2_Reset_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_2.Data_03")
  field(HIHI, "15")
  field(LOLO, "7")
  field(HIGH, "12")
  field(LOW, "10")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:LTU0:300:PPSTRIPPRSSR") {
  field(DESC, "BTM3_Trip_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_2.Data_04")
  field(HIHI, "13")
  field(LOLO, "5")
  field(HIGH, "10")
  field(LOW, "8")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:LTU0:300:PPSRSETPRSSR") {
  field(DESC, "BTM3_Reset_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_2.Data_05")
  field(HIHI, "15")
  field(LOLO, "7")
  field(HIGH, "12")
  field(LOW, "10")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:LTU0:440:PPSTRIPPRSSR") {
  field(DESC, "BTM4_Trip_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_2.Data_06")
  field(HIHI, "13")
  field(LOLO, "5")
  field(HIGH, "10")
  field(LOW, "8")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:LTU0:440:PPSRSETPRSSR") {
  field(DESC, "BTM4_Reset_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_2.Data_07")
  field(HIHI, "15")
  field(LOLO, "7")
  field(HIGH, "12")
  field(LOW, "10")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:LTU0:507:PPSTRIPPRSSR") {
  field(DESC, "BTM5_Trip_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_3.Data_00")
  field(HIHI, "13")
  field(LOLO, "5")
  field(HIGH, "10")
  field(LOW, "8")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:LTU0:507:PPSRSETPRSSR") {
  field(DESC, "BTM5_Reset_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_3.Data_01")
  field(HIHI, "15")
  field(LOLO, "7")
  field(HIGH, "12")
  field(LOW, "10")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:LTU0:645:PPSTRIPPRSSR") {
  field(DESC, "BTM6_Trip_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_3.Data_02")
  field(HIHI, "13")
  field(LOLO, "5")
  field(HIGH, "10")
  field(LOW, "8")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:LTU0:645:PPSRSETPRSSR") {
  field(DESC, "BTM6_Reset_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_3.Data_03")
  field(HIHI, "15")
  field(LOLO, "7")
  field(HIGH, "12")
  field(LOW, "10")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:LTU0:648:PPSTRIPPRSSR") {
  field(DESC, "BTM7_Trip_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_3.Data_04")
  field(HIHI, "13")
  field(LOLO, "5")
  field(HIGH, "10")
  field(LOW, "8")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:LTU0:648:PPSRSETPRSSR") {
  field(DESC, "BTM7_Reset_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_3.Data_05")
  field(HIHI, "15")
  field(LOLO, "7")
  field(HIGH, "12")
  field(LOW, "10")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:LTU0:687:PPSTRIPPRSSR") {
  field(DESC, "BTM8_Trip_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_3.Data_06")
  field(HIHI, "13")
  field(LOLO, "5")
  field(HIGH, "10")
  field(LOW, "8")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:LTU0:687:PPSRSETPRSSR") {
  field(DESC, "BTM8_Reset_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_3.Data_07")
  field(HIHI, "15")
  field(LOLO, "7")
  field(HIGH, "12")
  field(LOW, "10")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:LTU0:717:PPSTRIPPRSSR") {
  field(DESC, "BTM9_Trip_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_4.Data_00")
  field(HIHI, "13")
  field(LOLO, "5")
  field(HIGH, "10")
  field(LOW, "8")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:LTU0:717:PPSRSETPRSSR") {
  field(DESC, "BTM9_Reset_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_4.Data_01")
  field(HIHI, "15")
  field(LOLO, "7")
  field(HIGH, "12")
  field(LOW, "10")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:DMP0:451:PPSTRIPPRSSR") {
  field(DESC, "BTM10_Trip_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_4.Data_02")
  field(HIHI, "13")
  field(LOLO, "5")
  field(HIGH, "10")
  field(LOW, "8")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:DMP0:451:PPSRSETPRSSR") {
  field(DESC, "BTM10_Reset_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_4.Data_03")
  field(HIHI, "15")
  field(LOLO, "7")
  field(HIGH, "12")
  field(LOW, "10")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:DMP0:699:PPSTRIPPRSSR") {
  field(DESC, "BTM11_Trip_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_4.Data_04")
  field(HIHI, "13")
  field(LOLO, "5")
  field(HIGH, "10")
  field(LOW, "8")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:DMP0:699:PPSRSETPRSSR") {
  field(DESC, "BTM11_Reset_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_4.Data_05")
  field(HIHI, "15")
  field(LOLO, "7")
  field(HIGH, "12")
  field(LOW, "10")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:DMP0:711:PPSTRIPPRSSR") {
  field(DESC, "BTM12_Trip_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_4.Data_06")
  field(HIHI, "13")
  field(LOLO, "5")
  field(HIGH, "10")
  field(LOW, "8")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:DMP0:711:PPSRSETPRSSR") {
  field(DESC, "BTM12_Reset_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_4.Data_07")
  field(HIHI, "15")
  field(LOLO, "7")
  field(HIGH, "12")
  field(LOW, "10")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:DMP0:741:PPSTRIPPRSSR") {
  field(DESC, "BTM13_Trip_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_5.Data_00")
  field(HIHI, "13")
  field(LOLO, "5")
  field(HIGH, "10")
  field(LOW, "8")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:DMP0:741:PPSRSETPRSSR") {
  field(DESC, "BTM13_Reset_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_5.Data_01")
  field(HIHI, "15")
  field(LOLO, "7")
  field(HIGH, "12")
  field(LOW, "10")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:DMP0:771:PPSTRIPPRSSR") {
  field(DESC, "BTM14_Trip_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_5.Data_02")
  field(HIHI, "13")
  field(LOLO, "5")
  field(HIGH, "10")
  field(LOW, "8")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:DMP0:771:PPSRSETPRSSR") {
  field(DESC, "BTM14_Reset_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_5.Data_03")
  field(HIHI, "15")
  field(LOLO, "7")
  field(HIGH, "12")
  field(LOW, "10")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:DMP0:801:PPSTRIPPRSSR") {
  field(DESC, "BTM15_Trip_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_5.Data_04")
  field(HIHI, "13")
  field(LOLO, "5")
  field(HIGH, "10")
  field(LOW, "8")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:DMP0:801:PPSRSETPRSSR") {
  field(DESC, "BTM15_Reset_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_5.Data_05")
  field(HIHI, "15")
  field(LOLO, "7")
  field(HIGH, "12")
  field(LOW, "10")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:DMP0:999:PPSTRIPPRSSR") {
  field(DESC, "BTM16_Trip_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_5.Data_06")
  field(HIHI, "13")
  field(LOLO, "5")
  field(HIGH, "10")
  field(LOW, "8")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:DMP0:999:PPSRSETPRSSR") {
  field(DESC, "BTM16_Reset_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_5.Data_07")
  field(HIHI, "15")
  field(LOLO, "7")
  field(HIGH, "12")
  field(LOW, "10")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:LTU0:172:PPSPRSSR") {
  field(DESC, "BTM1_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_6.Data_00")
  field(HIHI, "17")
  field(LOLO, "10")
  field(HIGH, "16")
  field(LOW, "11")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:LTU0:226:PPSPRSSR") {
  field(DESC, "BTM2_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_6.Data_01")
  field(HIHI, "17")
  field(LOLO, "10")
  field(HIGH, "16")
  field(LOW, "11")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:LTU0:300:PPSPRSSR") {
  field(DESC, "BTM3_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_6.Data_02")
  field(HIHI, "17")
  field(LOLO, "10")
  field(HIGH, "16")
  field(LOW, "11")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:LTU0:440:PPSPRSSR") {
  field(DESC, "BTM4_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_6.Data_03")
  field(HIHI, "17")
  field(LOLO, "10")
  field(HIGH, "16")
  field(LOW, "11")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:LTU0:507:PPSPRSSR") {
  field(DESC, "BTM5_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_6.Data_04")
  field(HIHI, "17")
  field(LOLO, "10")
  field(HIGH, "16")
  field(LOW, "11")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:LTU0:645:PPSPRSSR") {
  field(DESC, "BTM6_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_6.Data_05")
  field(HIHI, "17")
  field(LOLO, "10")
  field(HIGH, "16")
  field(LOW, "11")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:LTU0:648:PPSPRSSR") {
  field(DESC, "BTM7_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_6.Data_06")
  field(HIHI, "17")
  field(LOLO, "10")
  field(HIGH, "16")
  field(LOW, "11")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:LTU0:687:PPSPRSSR") {
  field(DESC, "BTM8_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_6.Data_07")
  field(HIHI, "17")
  field(LOLO, "10")
  field(HIGH, "16")
  field(LOW, "11")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:LTU0:717:PPSPRSSR") {
  field(DESC, "BTM9_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_7.Data_00")
  field(HIHI, "17")
  field(LOLO, "10")
  field(HIGH, "16")
  field(LOW, "11")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:DMP0:451:PPSPRSSR") {
  field(DESC, "BTM10_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_7.Data_01")
  field(HIHI, "17")
  field(LOLO, "10")
  field(HIGH, "16")
  field(LOW, "11")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:DMP0:699:PPSPRSSR") {
  field(DESC, "BTM11_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_7.Data_02")
  field(HIHI, "17")
  field(LOLO, "10")
  field(HIGH, "16")
  field(LOW, "11")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:DMP0:711:PPSPRSSR") {
  field(DESC, "BTM12_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_7.Data_03")
  field(HIHI, "17")
  field(LOLO, "10")
  field(HIGH, "16")
  field(LOW, "11")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:DMP0:741:PPSPRSSR") {
  field(DESC, "BTM13_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_7.Data_04")
  field(HIHI, "17")
  field(LOLO, "10")
  field(HIGH, "16")
  field(LOW, "11")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:DMP0:771:PPSPRSSR") {
  field(DESC, "BTM14_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_7.Data_05")
  field(HIHI, "17")
  field(LOLO, "10")
  field(HIGH, "16")
  field(LOW, "11")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:DMP0:801:PPSPRSSR") {
  field(DESC, "BTM15_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_7.Data_06")
  field(HIHI, "17")
  field(LOLO, "10")
  field(HIGH, "16")
  field(LOW, "11")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}
record(ai,"BTM:DMP0:999:PPSPRSSR") {
  field(DESC, "BTM16_Pressure")
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PPS_UND_EPICS_7.Data_07")
  field(HIHI, "17")
  field(LOLO, "10")
  field(HIGH, "16")
  field(LOW, "11")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
}

record(calc, "PPS:UND0:1:CALCSCRELOOP") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:UND0:1:SECURELOOP")
  field(CALC, "A&&B")
  field(INPA, "PPS:UND0:1:SECURELOOPA MS")
  field(INPB, "PPS:UND0:1:SECURELOOPB MS")
}

record(bi, "PPS:UND0:1:SECURELOOP") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(INP, "PPS:UND0:1:CALCSCRELOOP MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:UND0:1:CALCINTLKCOM") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:UND0:1:INTLK")
  field(CALC, "A&&B")
  field(INPA, "PPS:UND0:1:INTLKA MS")
  field(INPB, "PPS:UND0:1:INTLKB MS")
}

record(bi, "PPS:UND0:1:INTLK") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "NOT_COMPLETE")
  field(ONAM, "COMPLETE")
  field(INP, "PPS:UND0:1:CALCINTLKCOM MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:UND0:1:CALCSRCHRSET") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:UND0:1:SRCHRESET")
  field(CALC, "A&&B")
  field(INPA, "PPS:UND0:1:SRCHRESETA MS")
  field(INPB, "PPS:UND0:1:SRCHRESETB MS")
}

record(bi, "PPS:UND0:1:SRCHRESET") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(INP, "PPS:UND0:1:CALCSRCHRSET MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:LTU0:1:CALCSRCPSTMU") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:LTU0:1:SRCHPRSETMU")
  field(CALC, "A&&B")
  field(INPA, "PPS:LTU0:1:SRCHPRSETMUA MS")
  field(INPB, "PPS:LTU0:1:SRCHPRSETMUB MS")
}

record(bi, "PPS:LTU0:1:SRCHPRSETMU") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(INP, "PPS:LTU0:1:CALCSRCPSTMU MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:LTU0:1:CALCSRCPSTW") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:LTU0:1:SRCHPRSETW")
  field(CALC, "A&&B")
  field(INPA, "PPS:LTU0:1:SRCHPRSETWA MS")
  field(INPB, "PPS:LTU0:1:SRCHPRSETWB MS")
}

record(bi, "PPS:LTU0:1:SRCHPRSETW") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(INP, "PPS:LTU0:1:CALCSRCPSTW MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:UND0:1:CALCSRCPSTW") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:UND0:1:SRCHPRSETW")
  field(CALC, "A&&B")
  field(INPA, "PPS:UND0:1:SRCHPRSETWA MS")
  field(INPB, "PPS:UND0:1:SRCHPRSETWB MS")
}

record(bi, "PPS:UND0:1:SRCHPRSETW") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(INP, "PPS:UND0:1:CALCSRCPSTW MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:UND0:1:CALCSRCPSTE") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:UND0:1:SRCHPRSETE")
  field(CALC, "A&&B")
  field(INPA, "PPS:UND0:1:SRCHPRSETEA MS")
  field(INPB, "PPS:UND0:1:SRCHPRSETEB MS")
}

record(bi, "PPS:UND0:1:SRCHPRSETE") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(INP, "PPS:UND0:1:CALCSRCPSTE MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:LTU0:1:CALCEMEROFF") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:LTU0:1:EMEROFF")
  field(CALC, "A&&B")
  field(INPA, "PPS:LTU0:1:EMEROFFA MS")
  field(INPB, "PPS:LTU0:1:EMEROFFB MS")
}

record(bi, "PPS:LTU0:1:EMEROFF") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(INP, "PPS:LTU0:1:CALCEMEROFF MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:LTU0:1:CALCEMREXTW") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:LTU0:1:EMEREXITW")
  field(CALC, "A&&B")
  field(INPA, "PPS:LTU0:1:EMEREXITWA MS")
  field(INPB, "PPS:LTU0:1:EMEREXITWB MS")
}

record(bi, "PPS:LTU0:1:EMEREXITW") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(INP, "PPS:LTU0:1:CALCEMREXTW MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:LTU0:1:CALCEMREXTE") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:LTU0:1:EMEREXITE")
  field(CALC, "A&&B")
  field(INPA, "PPS:LTU0:1:EMEREXITEA MS")
  field(INPB, "PPS:LTU0:1:EMEREXITEB MS")
}

record(bi, "PPS:LTU0:1:EMEREXITE") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(INP, "PPS:LTU0:1:CALCEMREXTE MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:LTU0:1:CALCKBNK1ECM") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:LTU0:1:KBANK1ECOM")
  field(CALC, "A&&B")
  field(INPA, "PPS:LTU0:1:KBANK1ECOMA MS")
  field(INPB, "PPS:LTU0:1:KBANK1ECOMB MS")
}

record(bi, "PPS:LTU0:1:KBANK1ECOM") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "NOT_COMPLETE")
  field(ONAM, "COMPLETE")
  field(INP, "PPS:LTU0:1:CALCKBNK1ECM MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:LTU0:1:CALCKBNK2ECM") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:LTU0:1:KBANK2ECOM")
  field(CALC, "A&&B")
  field(INPA, "PPS:LTU0:1:KBANK2ECOMA MS")
  field(INPB, "PPS:LTU0:1:KBANK2ECOMB MS")
}

record(bi, "PPS:LTU0:1:KBANK2ECOM") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "NOT_COMPLETE")
  field(ONAM, "COMPLETE")
  field(INP, "PPS:LTU0:1:CALCKBNK2ECM MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:LTU0:1:CALCKBNKELAT") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:LTU0:1:KBANKELAT")
  field(CALC, "A&&B")
  field(INPA, "PPS:LTU0:1:KBANKELATA MS")
  field(INPB, "PPS:LTU0:1:KBANKELATB MS")
}

record(bi, "PPS:LTU0:1:KBANKELAT") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "NOT_LATCHED")
  field(ONAM, "LATCHED")
  field(INP, "PPS:LTU0:1:CALCKBNKELAT MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:LTU0:1:CALCDOORW") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:LTU0:1:DOORW")
  field(CALC, "A&&B")
  field(INPA, "PPS:LTU0:1:DOORWA MS")
  field(INPB, "PPS:LTU0:1:DOORWB MS")
}

record(bi, "PPS:LTU0:1:DOORW") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "NOT_CLOSED")
  field(ONAM, "CLOSED")
  field(INP, "PPS:LTU0:1:CALCDOORW MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:LTU0:1:CALCDORWLAT") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:LTU0:1:DOORWLAT")
  field(CALC, "A&&B")
  field(INPA, "PPS:LTU0:1:DOORWLATA MS")
  field(INPB, "PPS:LTU0:1:DOORWLATB MS")
}

record(bi, "PPS:LTU0:1:DOORWLAT") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "NOT_LATCHED")
  field(ONAM, "LATCHED")
  field(INP, "PPS:LTU0:1:CALCDORWLAT MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:LTU0:1:CALCGATEW") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:LTU0:1:GATEW")
  field(CALC, "A&&B")
  field(INPA, "PPS:LTU0:1:GATEWA MS")
  field(INPB, "PPS:LTU0:1:GATEWB MS")
}

record(bi, "PPS:LTU0:1:GATEW") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "NOT_CLOSED")
  field(ONAM, "CLOSED")
  field(INP, "PPS:LTU0:1:CALCGATEW MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:LTU0:1:CALCGATWLAT") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:LTU0:1:GATEWLAT")
  field(CALC, "A&&B")
  field(INPA, "PPS:LTU0:1:GATEWLATA MS")
  field(INPB, "PPS:LTU0:1:GATEWLATB MS")
}

record(bi, "PPS:LTU0:1:GATEWLAT") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "NOT_LATCHED")
  field(ONAM, "LATCHED")
  field(INP, "PPS:LTU0:1:CALCGATWLAT MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:LTU0:1:CALCDOORE") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:LTU0:1:DOORE")
  field(CALC, "A&&B")
  field(INPA, "PPS:LTU0:1:DOOREA MS")
  field(INPB, "PPS:LTU0:1:DOOREB MS")
}

record(bi, "PPS:LTU0:1:DOORE") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "NOT_CLOSED")
  field(ONAM, "CLOSED")
  field(INP, "PPS:LTU0:1:CALCDOORE MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:LTU0:1:CALCDOORELAT") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:LTU0:1:DOORELAT")
  field(CALC, "A&&B")
  field(INPA, "PPS:LTU0:1:DOORELATA MS")
  field(INPB, "PPS:LTU0:1:DOORELATB MS")
}

record(bi, "PPS:LTU0:1:DOORELAT") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "NOT_LATCHED")
  field(ONAM, "LATCHED")
  field(INP, "PPS:LTU0:1:CALCDOORELAT MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:LTU0:1:CALCGATEE") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:LTU0:1:GATEE")
  field(CALC, "A&&B")
  field(INPA, "PPS:LTU0:1:GATEEA MS")
  field(INPB, "PPS:LTU0:1:GATEEB MS")
}

record(bi, "PPS:LTU0:1:GATEE") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "NOT_CLOSED")
  field(ONAM, "CLOSED")
  field(INP, "PPS:LTU0:1:CALCGATEE MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:LTU0:1:CALCGATEELAT") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:LTU0:1:GATEELAT")
  field(CALC, "A&&B")
  field(INPA, "PPS:LTU0:1:GATEELATA MS")
  field(INPB, "PPS:LTU0:1:GATEELATB MS")
}

record(bi, "PPS:LTU0:1:GATEELAT") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "NOT_LATCHED")
  field(ONAM, "LATCHED")
  field(INP, "PPS:LTU0:1:CALCGATEELAT MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:LTU0:1:CALCKBNKECM") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:LTU0:1:KBANKECOM")
  field(CALC, "A&&B")
  field(INPA, "PPS:LTU0:1:KBANK1ECOM MS")
  field(INPB, "PPS:LTU0:1:KBANK2ECOM MS")
}

record(bi, "PPS:LTU0:1:KBANKECOM") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "NOT_COMPLETE")
  field(ONAM, "COMPLETE")
  field(INP, "PPS:LTU0:1:CALCKBNKECM MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:UND0:1:CALCEMEROFF") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:UND0:1:EMEROFF")
  field(CALC, "A&&B")
  field(INPA, "PPS:UND0:1:EMEROFFA MS")
  field(INPB, "PPS:UND0:1:EMEROFFB MS")
}

record(bi, "PPS:UND0:1:EMEROFF") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(INP, "PPS:UND0:1:CALCEMEROFF MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:UND0:1:CALCEMREXTE") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:UND0:1:EMEREXITE")
  field(CALC, "A&&B")
  field(INPA, "PPS:UND0:1:EMEREXITEA MS")
  field(INPB, "PPS:UND0:1:EMEREXITEB MS")
}

record(bi, "PPS:UND0:1:EMEREXITE") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(INP, "PPS:UND0:1:CALCEMREXTE MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:UND0:1:CALCGATEW") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:UND0:1:GATEW")
  field(CALC, "A&&B")
  field(INPA, "PPS:UND0:1:GATEWA MS")
  field(INPB, "PPS:UND0:1:GATEWB MS")
}

record(bi, "PPS:UND0:1:GATEW") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "NOT_CLOSED")
  field(ONAM, "CLOSED")
  field(INP, "PPS:UND0:1:CALCGATEW MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:UND0:1:CALCGATEWLAT") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:UND0:1:GATEWLAT")
  field(CALC, "A&&B")
  field(INPA, "PPS:UND0:1:GATEWLATA MS")
  field(INPB, "PPS:UND0:1:GATEWLATB MS")
}

record(bi, "PPS:UND0:1:GATEWLAT") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "NOT_LATCHED")
  field(ONAM, "LATCHED")
  field(INP, "PPS:UND0:1:CALCGATEWLAT MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:UND0:1:CALCGATEE") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:UND0:1:GATEE")
  field(CALC, "A&&B")
  field(INPA, "PPS:UND0:1:GATEEA MS")
  field(INPB, "PPS:UND0:1:GATEEB MS")
}

record(bi, "PPS:UND0:1:GATEE") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "NOT_CLOSED")
  field(ONAM, "CLOSED")
  field(INP, "PPS:UND0:1:CALCGATEE MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:UND0:1:CALCGATEELAT") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:UND0:1:GATEELAT")
  field(CALC, "A&&B")
  field(INPA, "PPS:UND0:1:GATEELATA MS")
  field(INPB, "PPS:UND0:1:GATEELATB MS")
}

record(bi, "PPS:UND0:1:GATEELAT") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "NOT_LATCHED")
  field(ONAM, "LATCHED")
  field(INP, "PPS:UND0:1:CALCGATEELAT MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "BTM:LTU0:172:CALCSUM") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "BTM:LTU0:172:PPSTRIP")
  field(CALC, "A&&B")
  field(INPA, "BTM:LTU0:172:PPSTRIPA MS")
  field(INPB, "BTM:LTU0:172:PPSTRIPB MS")
}

record(bi, "BTM:LTU0:172:PPSTRIP") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(INP, "BTM:LTU0:172:CALCSUM MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "BTM:LTU0:226:CALCSUM") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "BTM:LTU0:226:PPSTRIP")
  field(CALC, "A&&B")
  field(INPA, "BTM:LTU0:226:PPSTRIPA MS")
  field(INPB, "BTM:LTU0:226:PPSTRIPB MS")
}

record(bi, "BTM:LTU0:226:PPSTRIP") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(INP, "BTM:LTU0:226:CALCSUM MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "BTM:LTU0:300:CALCSUM") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "BTM:LTU0:300:PPSTRIP")
  field(CALC, "A&&B")
  field(INPA, "BTM:LTU0:300:PPSTRIPA MS")
  field(INPB, "BTM:LTU0:300:PPSTRIPB MS")
}

record(bi, "BTM:LTU0:300:PPSTRIP") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(INP, "BTM:LTU0:300:CALCSUM MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "BTM:LTU0:440:CALCSUM") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "BTM:LTU0:440:PPSTRIP")
  field(CALC, "A&&B")
  field(INPA, "BTM:LTU0:440:PPSTRIPA MS")
  field(INPB, "BTM:LTU0:440:PPSTRIPB MS")
}

record(bi, "BTM:LTU0:440:PPSTRIP") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(INP, "BTM:LTU0:440:CALCSUM MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "BTM:LTU0:507:CALCSUM") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "BTM:LTU0:507:PPSTRIP")
  field(CALC, "A&&B")
  field(INPA, "BTM:LTU0:507:PPSTRIPA MS")
  field(INPB, "BTM:LTU0:507:PPSTRIPB MS")
}

record(bi, "BTM:LTU0:507:PPSTRIP") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(INP, "BTM:LTU0:507:CALCSUM MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "BTM:LTU0:645:CALCSUM") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "BTM:LTU0:645:PPSTRIP")
  field(CALC, "A&&B")
  field(INPA, "BTM:LTU0:645:PPSTRIPA MS")
  field(INPB, "BTM:LTU0:645:PPSTRIPB MS")
}

record(bi, "BTM:LTU0:645:PPSTRIP") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(INP, "BTM:LTU0:645:CALCSUM MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "BTM:LTU0:648:CALCSUM") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "BTM:LTU0:648:PPSTRIP")
  field(CALC, "A&&B")
  field(INPA, "BTM:LTU0:648:PPSTRIPA MS")
  field(INPB, "BTM:LTU0:648:PPSTRIPB MS")
}

record(bi, "BTM:LTU0:648:PPSTRIP") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(INP, "BTM:LTU0:648:CALCSUM MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "BTM:LTU0:687:CALCSUM") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "BTM:LTU0:687:PPSTRIP")
  field(CALC, "A&&B")
  field(INPA, "BTM:LTU0:687:PPSTRIPA MS")
  field(INPB, "BTM:LTU0:687:PPSTRIPB MS")
}

record(bi, "BTM:LTU0:687:PPSTRIP") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(INP, "BTM:LTU0:687:CALCSUM MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "BTM:LTU0:717:CALCSUM") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "BTM:LTU0:717:PPSTRIP")
  field(CALC, "A&&B")
  field(INPA, "BTM:LTU0:717:PPSTRIPA MS")
  field(INPB, "BTM:LTU0:717:PPSTRIPB MS")
}

record(bi, "BTM:LTU0:717:PPSTRIP") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(INP, "BTM:LTU0:717:CALCSUM MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "BTM:DMP0:451:CALCSUM") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "BTM:DMP0:451:PPSTRIP")
  field(CALC, "A&&B")
  field(INPA, "BTM:DMP0:451:PPSTRIPA MS")
  field(INPB, "BTM:DMP0:451:PPSTRIPB MS")
}

record(bi, "BTM:DMP0:451:PPSTRIP") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(INP, "BTM:DMP0:451:CALCSUM MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "BTM:DMP0:699:CALCSUM") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "BTM:DMP0:699:PPSTRIP")
  field(CALC, "A&&B")
  field(INPA, "BTM:DMP0:699:PPSTRIPA MS")
  field(INPB, "BTM:DMP0:699:PPSTRIPB MS")
}

record(bi, "BTM:DMP0:699:PPSTRIP") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(INP, "BTM:DMP0:699:CALCSUM MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "BTM:DMP0:711:CALCSUM") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "BTM:DMP0:711:PPSTRIP")
  field(CALC, "A&&B")
  field(INPA, "BTM:DMP0:711:PPSTRIPA MS")
  field(INPB, "BTM:DMP0:711:PPSTRIPB MS")
}

record(bi, "BTM:DMP0:711:PPSTRIP") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(INP, "BTM:DMP0:711:CALCSUM MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "BTM:DMP0:741:CALCSUM") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "BTM:DMP0:741:PPSTRIP")
  field(CALC, "A&&B")
  field(INPA, "BTM:DMP0:741:PPSTRIPA MS")
  field(INPB, "BTM:DMP0:741:PPSTRIPB MS")
}

record(bi, "BTM:DMP0:741:PPSTRIP") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(INP, "BTM:DMP0:741:CALCSUM MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "BTM:DMP0:771:CALCSUM") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "BTM:DMP0:771:PPSTRIP")
  field(CALC, "A&&B")
  field(INPA, "BTM:DMP0:771:PPSTRIPA MS")
  field(INPB, "BTM:DMP0:771:PPSTRIPB MS")
}

record(bi, "BTM:DMP0:771:PPSTRIP") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(INP, "BTM:DMP0:771:CALCSUM MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "BTM:DMP0:801:CALCSUM") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "BTM:DMP0:801:PPSTRIP")
  field(CALC, "A&&B")
  field(INPA, "BTM:DMP0:801:PPSTRIPA MS")
  field(INPB, "BTM:DMP0:801:PPSTRIPB MS")
}

record(bi, "BTM:DMP0:801:PPSTRIP") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(INP, "BTM:DMP0:801:CALCSUM MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "BTM:DMP0:999:CALCSUM") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "BTM:DMP0:999:PPSTRIP")
  field(CALC, "A&&B")
  field(INPA, "BTM:DMP0:999:PPSTRIPA MS")
  field(INPB, "BTM:DMP0:999:PPSTRIPB MS")
}

record(bi, "BTM:DMP0:999:PPSTRIP") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(INP, "BTM:DMP0:999:CALCSUM MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:UND0:1:CALCLOOPSUM") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:UND0:1:LOOP")
  field(CALC, "A&&B")
  field(INPA, "PPS:UND0:1:LOOPA MS")
  field(INPB, "PPS:UND0:1:LOOPB MS")
}

record(bi, "PPS:UND0:1:LOOP") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "NOT_COMPLETE")
  field(ONAM, "COMPLETE")
  field(INP, "PPS:UND0:1:CALCLOOPSUM MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:UND0:1:CALCLOOPLSUM") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:UND0:1:LOOPLAT")
  field(CALC, "A&&B")
  field(INPA, "PPS:UND0:1:LOOPLATA MS")
  field(INPB, "PPS:UND0:1:LOOPLATB MS")
}

record(bi, "PPS:UND0:1:LOOPLAT") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "NOT_LATCHED")
  field(ONAM, "LATCHED")
  field(INP, "PPS:UND0:1:CALCLOOPLSUM MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:UND0:1:CALCLOOPNSUM") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:UND0:1:LOOPNOT")
  field(CALC, "A&&B")
  field(INPA, "PPS:UND0:1:LOOPNOTA MS")
  field(INPB, "PPS:UND0:1:LOOPNOTB MS")
}

record(bi, "PPS:UND0:1:LOOPNOT") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "COMPLETE")
  field(ONAM, "NOT_COMPLETE")
  field(INP, "PPS:UND0:1:CALCLOOPNSUM MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:UND0:1:CALCSTPERMSUM") {
  field(SCAN, ".1 second")
  field(DESC, "summary_calculation")
  field(FLNK, "PPS:UND0:1:STPERM")
  field(CALC, "A&&B")
  field(INPA, "PPS:UND0:1:STPERMA MS")
  field(INPB, "PPS:UND0:1:STPERMB MS")
}

record(bi, "PPS:UND0:1:STPERM") {
  field(SCAN, "Passive")
  field(DESC, "summary")
  field(DTYP, "Soft Channel")
  field(ZNAM, "NOT_ENABLE")
  field(ONAM, "ENABLE")
  field(INP, "PPS:UND0:1:CALCSTPERMSUM MS")
  field(ZSV,  "NO_ALARM")
  field(OSV,  "NO_ALARM")

}



record(calc, "PPS:LTU0:1:CALCKBNKESM") {
  field(SCAN, ".1 second")
  field(FLNK, "PPS:LTU0:1:KBANKESUM")
  field(CALC, "!B?A:A&&B?2:3")
  field(INPA, "PPS:LTU0:1:KBANKECOM MS")
  field(INPB, "PPS:LTU0:1:KBANKELAT MS")
}


record(mbbi, "PPS:LTU0:1:KBANKESUM") {
  field(SCAN, "Passive")
  field(ZRST, "NOT_COMPLETE")
  field(ONST, "COMPLETE")
  field(TWST, "LATCHED")
  field(INP, "PPS:LTU0:1:CALCKBNKESM MS")
  field(ZRSV, "MAJOR")
  field(ONSV, "MINOR")
  field(TWSV, "NO_ALARM")
  field(THST, "INVALID")
  field(THSV, "INVALID")
}


record(calc, "PPS:LTU0:1:CALCDOORWSM") {
  field(SCAN, ".1 second")
  field(FLNK, "PPS:LTU0:1:DOORWSUM")
  field(CALC, "!B?A:A&&B?2:3")
  field(INPA, "PPS:LTU0:1:DOORW MS")
  field(INPB, "PPS:LTU0:1:DOORWLAT MS")
}


record(mbbi, "PPS:LTU0:1:DOORWSUM") {
  field(SCAN, "Passive")
  field(ZRST, "NOT_CLOSED")
  field(ONST, "CLOSED")
  field(TWST, "LATCHED")
  field(INP, "PPS:LTU0:1:CALCDOORWSM MS")
  field(ZRSV, "MAJOR")
  field(ONSV, "MINOR")
  field(TWSV, "NO_ALARM")
  field(THST, "INVALID")
  field(THSV, "INVALID")
}


record(calc, "PPS:LTU0:1:CALCGATEWSM") {
  field(SCAN, ".1 second")
  field(FLNK, "PPS:LTU0:1:GATEWSUM")
  field(CALC, "!B?A:A&&B?2:3")
  field(INPA, "PPS:LTU0:1:GATEW MS")
  field(INPB, "PPS:LTU0:1:GATEWLAT MS")
}


record(mbbi, "PPS:LTU0:1:GATEWSUM") {
  field(SCAN, "Passive")
  field(ZRST, "NOT_CLOSED")
  field(ONST, "CLOSED")
  field(TWST, "LATCHED")
  field(INP, "PPS:LTU0:1:CALCGATEWSM MS")
  field(ZRSV, "MAJOR")
  field(ONSV, "MINOR")
  field(TWSV, "NO_ALARM")
  field(THST, "INVALID")
  field(THSV, "INVALID")
}


record(calc, "PPS:LTU0:1:CALCDOORESM") {
  field(SCAN, ".1 second")
  field(FLNK, "PPS:LTU0:1:DOORESUM")
  field(CALC, "!B?A:A&&B?2:3")
  field(INPA, "PPS:LTU0:1:DOORE MS")
  field(INPB, "PPS:LTU0:1:DOORELAT MS")
}


record(mbbi, "PPS:LTU0:1:DOORESUM") {
  field(SCAN, "Passive")
  field(ZRST, "NOT_CLOSED")
  field(ONST, "CLOSED")
  field(TWST, "LATCHED")
  field(INP, "PPS:LTU0:1:CALCDOORESM MS")
  field(ZRSV, "MAJOR")
  field(ONSV, "MINOR")
  field(TWSV, "NO_ALARM")
  field(THST, "INVALID")
  field(THSV, "INVALID")
}


record(calc, "PPS:LTU0:1:CALCGATEESM") {
  field(SCAN, ".1 second")
  field(FLNK, "PPS:LTU0:1:GATEESUM")
  field(CALC, "!B?A:A&&B?2:3")
  field(INPA, "PPS:LTU0:1:GATEE MS")
  field(INPB, "PPS:LTU0:1:GATEELAT MS")
}


record(mbbi, "PPS:LTU0:1:GATEESUM") {
  field(SCAN, "Passive")
  field(ZRST, "NOT_CLOSED")
  field(ONST, "CLOSED")
  field(TWST, "LATCHED")
  field(INP, "PPS:LTU0:1:CALCGATEESM MS")
  field(ZRSV, "MAJOR")
  field(ONSV, "MINOR")
  field(TWSV, "NO_ALARM")
  field(THST, "INVALID")
  field(THSV, "INVALID")
}


record(calc, "PPS:UND0:1:CALCGATEWSM") {
  field(SCAN, ".1 second")
  field(FLNK, "PPS:UND0:1:GATEWSUM")
  field(CALC, "!B?A:A&&B?2:3")
  field(INPA, "PPS:UND0:1:GATEW MS")
  field(INPB, "PPS:UND0:1:GATEWLAT MS")
}


record(mbbi, "PPS:UND0:1:GATEWSUM") {
  field(SCAN, "Passive")
  field(ZRST, "NOT_CLOSED")
  field(ONST, "CLOSED")
  field(TWST, "LATCHED")
  field(INP, "PPS:UND0:1:CALCGATEWSM MS")
  field(ZRSV, "MAJOR")
  field(ONSV, "MINOR")
  field(TWSV, "NO_ALARM")
  field(THST, "INVALID")
  field(THSV, "INVALID")
}


record(calc, "PPS:UND0:1:CALCGATEESM") {
  field(SCAN, ".1 second")
  field(FLNK, "PPS:UND0:1:GATEESUM")
  field(CALC, "!B?A:A&&B?2:3")
  field(INPA, "PPS:UND0:1:GATEE MS")
  field(INPB, "PPS:UND0:1:GATEELAT MS")
}


record(mbbi, "PPS:UND0:1:GATEESUM") {
  field(SCAN, "Passive")
  field(ZRST, "NOT_CLOSED")
  field(ONST, "CLOSED")
  field(TWST, "LATCHED")
  field(INP, "PPS:UND0:1:CALCGATEESM MS")
  field(ZRSV, "MAJOR")
  field(ONSV, "MINOR")
  field(TWSV, "NO_ALARM")
  field(THST, "INVALID")
  field(THSV, "INVALID")
}

#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(calcout, "BSOIC:LTU0:1:NEUTRONACT") {
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(CALC, "B*(10^(A*0.5))")
  field(INPA, "BSOIC:LTU0:1:NEUTRONRAW.VAL")
  field(INPB, "0.001")
  field(EGU, "mr/hour")
  field(HOPR, "10")
  field(LOPR, "0")
  field(HIHI, "9")
  field(LOLO, "0")
  field(HIGH, "8")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(ADEL, "-1")
}


record(ai, "BSOIC:LTU0:1:NEUTRONRAW") {
  field(DESC, "Analog Input")
  field(SCAN, "I/O Intr")
  field(DTYP, "IP330")
  field(INP, "@AI1-UND0-1-PPS:4:DATA")
  field(PREC, "3")
  field(EGUF, "10")
  field(EGUL, "0")
  field(HOPR, "10")
  field(LOPR, "0")
  field(ADEL, "0")
  field(MDEL, "0")
  field(HIHI, "9")
  field(HIGH, "8")
  field(LOW, "-1")
  field(LOLO, "-1")
  field(EGU, "V")
  field(LINR, "LINEAR")
  field(HHSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(LLSV, "MAJOR")
  field(FLNK, "BSOIC:LTU0:1:NEUTRONACT")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BSOIC:LTU0:1:NEUTRONACT",440,88,0,0,"BSOIC:LTU0:1:NEUTRONACT")
#! Field("BSOIC:LTU0:1:NEUTRONACT.INPA",16777215,0,"BSOIC:LTU0:1:NEUTRONACT.INPA")
#! Link("BSOIC:LTU0:1:NEUTRONACT.INPA","BSOIC:LTU0:1:NEUTRONRAW.VAL")
#! Field("BSOIC:LTU0:1:NEUTRONACT.INPB",16777215,1,"BSOIC:LTU0:1:NEUTRONACT.INPB")
#! Record("BSOIC:LTU0:1:NEUTRONRAW",20,18,0,0,"BSOIC:LTU0:1:NEUTRONRAW")
#! Field("BSOIC:LTU0:1:NEUTRONRAW.VAL",16777215,1,"BSOIC:LTU0:1:NEUTRONRAW.VAL")
#! Field("BSOIC:LTU0:1:NEUTRONRAW.FLNK",16777215,1,"BSOIC:LTU0:1:NEUTRONRAW.FLNK")
#! Link("BSOIC:LTU0:1:NEUTRONRAW.FLNK","BSOIC:LTU0:1:NEUTRONACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(calcout, "BSOIC:LTU0:1:GAMMAACT") {
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(CALC, "B*(10^(A*0.5))")
  field(INPA, "BSOIC:LTU0:1:GAMMARAW.VAL")
  field(INPB, "0.01")
  field(EGU, "mr/hour")
  field(HOPR, "10")
  field(LOPR, "0")
  field(HIHI, "9")
  field(LOLO, "0.5")
  field(HIGH, "8")
  field(LOW, "1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(ADEL, "0")
}


record(ai, "BSOIC:LTU0:1:GAMMARAW") {
  field(DESC, "Analog Input")
  field(SCAN, "I/O Intr")
  field(DTYP, "IP330")
  field(INP, "@AI1-UND0-1-PPS:5:DATA")
  field(PREC, "3")
  field(EGUF, "10")
  field(EGUL, "0")
  field(HOPR, "10")
  field(LOPR, "0")
  field(ADEL, "0")
  field(MDEL, "0")
  field(HIHI, "9")
  field(HIGH, "8")
  field(LOW, "4")
  field(LOLO, "0.5")
  field(EGU, "V")
  field(LINR, "LINEAR")
  field(HHSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(LLSV, "MAJOR")
  field(FLNK, "BSOIC:LTU0:1:GAMMAACT")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BSOIC:LTU0:1:GAMMAACT",440,88,0,0,"BSOIC:LTU0:1:GAMMAACT")
#! Field("BSOIC:LTU0:1:GAMMAACT.INPA",16777215,0,"BSOIC:LTU0:1:GAMMAACT.INPA")
#! Link("BSOIC:LTU0:1:GAMMAACT.INPA","BSOIC:LTU0:1:GAMMARAW.VAL")
#! Field("BSOIC:LTU0:1:GAMMAACT.INPB",16777215,1,"BSOIC:LTU0:1:GAMMAACT.INPB")
#! Record("BSOIC:LTU0:1:GAMMARAW",20,18,0,0,"BSOIC:LTU0:1:GAMMARAW")
#! Field("BSOIC:LTU0:1:GAMMARAW.VAL",16777215,1,"BSOIC:LTU0:1:GAMMARAW.VAL")
#! Field("BSOIC:LTU0:1:GAMMARAW.FLNK",16777215,1,"BSOIC:LTU0:1:GAMMARAW.FLNK")
#! Link("BSOIC:LTU0:1:GAMMARAW.FLNK","BSOIC:LTU0:1:GAMMAACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(calcout, "BSOIC:LTU0:4:NEUTRONACT") {
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(CALC, "B*(10^(A*0.5))")
  field(INPA, "BSOIC:LTU0:4:NEUTRONRAW.VAL")
  field(INPB, "0.001")
  field(EGU, "mr/hour")
  field(HOPR, "10")
  field(LOPR, "0")
  field(HIHI, "9")
  field(LOLO, "0")
  field(HIGH, "8")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(ADEL, "-1")
}


record(ai, "BSOIC:LTU0:4:NEUTRONRAW") {
  field(DESC, "Analog Input")
  field(SCAN, "I/O Intr")
  field(DTYP, "IP330")
  field(INP, "@AI1-UND0-1-PPS:6:DATA")
  field(PREC, "3")
  field(EGUF, "10")
  field(EGUL, "0")
  field(HOPR, "10")
  field(LOPR, "0")
  field(ADEL, "0")
  field(MDEL, "0")
  field(HIHI, "9")
  field(HIGH, "8")
  field(LOW, "-1")
  field(LOLO, "-1")
  field(EGU, "V")
  field(LINR, "LINEAR")
  field(HHSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(LLSV, "MAJOR")
  field(FLNK, "BSOIC:LTU0:4:NEUTRONACT")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BSOIC:LTU0:4:NEUTRONACT",440,88,0,0,"BSOIC:LTU0:4:NEUTRONACT")
#! Field("BSOIC:LTU0:4:NEUTRONACT.INPA",16777215,0,"BSOIC:LTU0:4:NEUTRONACT.INPA")
#! Link("BSOIC:LTU0:4:NEUTRONACT.INPA","BSOIC:LTU0:4:NEUTRONRAW.VAL")
#! Field("BSOIC:LTU0:4:NEUTRONACT.INPB",16777215,1,"BSOIC:LTU0:4:NEUTRONACT.INPB")
#! Record("BSOIC:LTU0:4:NEUTRONRAW",20,18,0,0,"BSOIC:LTU0:4:NEUTRONRAW")
#! Field("BSOIC:LTU0:4:NEUTRONRAW.VAL",16777215,1,"BSOIC:LTU0:4:NEUTRONRAW.VAL")
#! Field("BSOIC:LTU0:4:NEUTRONRAW.FLNK",16777215,1,"BSOIC:LTU0:4:NEUTRONRAW.FLNK")
#! Link("BSOIC:LTU0:4:NEUTRONRAW.FLNK","BSOIC:LTU0:4:NEUTRONACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(calcout, "BSOIC:LTU0:4:GAMMAACT") {
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(CALC, "B*(10^(A*0.5))")
  field(INPA, "BSOIC:LTU0:4:GAMMARAW.VAL")
  field(INPB, "0.01")
  field(EGU, "mr/hour")
  field(HOPR, "10")
  field(LOPR, "0")
  field(HIHI, "9")
  field(LOLO, "0.5")
  field(HIGH, "8")
  field(LOW, "1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(ADEL, "0")
}


record(ai, "BSOIC:LTU0:4:GAMMARAW") {
  field(DESC, "Analog Input")
  field(SCAN, "I/O Intr")
  field(DTYP, "IP330")
  field(INP, "@AI1-UND0-1-PPS:7:DATA")
  field(PREC, "3")
  field(EGUF, "10")
  field(EGUL, "0")
  field(HOPR, "10")
  field(LOPR, "0")
  field(ADEL, "0")
  field(MDEL, "0")
  field(HIHI, "9")
  field(HIGH, "8")
  field(LOW, "4")
  field(LOLO, "0.5")
  field(EGU, "V")
  field(LINR, "LINEAR")
  field(HHSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(LLSV, "MAJOR")
  field(FLNK, "BSOIC:LTU0:4:GAMMAACT")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BSOIC:LTU0:4:GAMMAACT",440,88,0,0,"BSOIC:LTU0:4:GAMMAACT")
#! Field("BSOIC:LTU0:4:GAMMAACT.INPA",16777215,0,"BSOIC:LTU0:4:GAMMAACT.INPA")
#! Link("BSOIC:LTU0:4:GAMMAACT.INPA","BSOIC:LTU0:4:GAMMARAW.VAL")
#! Field("BSOIC:LTU0:4:GAMMAACT.INPB",16777215,1,"BSOIC:LTU0:4:GAMMAACT.INPB")
#! Record("BSOIC:LTU0:4:GAMMARAW",20,18,0,0,"BSOIC:LTU0:4:GAMMARAW")
#! Field("BSOIC:LTU0:4:GAMMARAW.VAL",16777215,1,"BSOIC:LTU0:4:GAMMARAW.VAL")
#! Field("BSOIC:LTU0:4:GAMMARAW.FLNK",16777215,1,"BSOIC:LTU0:4:GAMMARAW.FLNK")
#! Link("BSOIC:LTU0:4:GAMMARAW.FLNK","BSOIC:LTU0:4:GAMMAACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(calcout, "BSOIC:LTU0:5:NEUTRONACT") {
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(CALC, "B*(10^(A*0.5))")
  field(INPA, "BSOIC:LTU0:5:NEUTRONRAW.VAL")
  field(INPB, "0.001")
  field(EGU, "mr/hour")
  field(HOPR, "10")
  field(LOPR, "0")
  field(HIHI, "9")
  field(LOLO, "0")
  field(HIGH, "8")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(ADEL, "-1")
}


record(ai, "BSOIC:LTU0:5:NEUTRONRAW") {
  field(DESC, "Analog Input")
  field(SCAN, "I/O Intr")
  field(DTYP, "IP330")
  field(INP, "@AI1-UND0-1-PPS:8:DATA")
  field(PREC, "3")
  field(EGUF, "10")
  field(EGUL, "0")
  field(HOPR, "10")
  field(LOPR, "0")
  field(ADEL, "0")
  field(MDEL, "0")
  field(HIHI, "9")
  field(HIGH, "8")
  field(LOW, "-1")
  field(LOLO, "-1")
  field(EGU, "V")
  field(LINR, "LINEAR")
  field(HHSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(LLSV, "MAJOR")
  field(FLNK, "BSOIC:LTU0:5:NEUTRONACT")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BSOIC:LTU0:5:NEUTRONACT",440,88,0,0,"BSOIC:LTU0:5:NEUTRONACT")
#! Field("BSOIC:LTU0:5:NEUTRONACT.INPA",16777215,0,"BSOIC:LTU0:5:NEUTRONACT.INPA")
#! Link("BSOIC:LTU0:5:NEUTRONACT.INPA","BSOIC:LTU0:5:NEUTRONRAW.VAL")
#! Field("BSOIC:LTU0:5:NEUTRONACT.INPB",16777215,1,"BSOIC:LTU0:5:NEUTRONACT.INPB")
#! Record("BSOIC:LTU0:5:NEUTRONRAW",20,18,0,0,"BSOIC:LTU0:5:NEUTRONRAW")
#! Field("BSOIC:LTU0:5:NEUTRONRAW.VAL",16777215,1,"BSOIC:LTU0:5:NEUTRONRAW.VAL")
#! Field("BSOIC:LTU0:5:NEUTRONRAW.FLNK",16777215,1,"BSOIC:LTU0:5:NEUTRONRAW.FLNK")
#! Link("BSOIC:LTU0:5:NEUTRONRAW.FLNK","BSOIC:LTU0:5:NEUTRONACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(calcout, "BSOIC:LTU0:5:GAMMAACT") {
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(CALC, "B*(10^(A*0.5))")
  field(INPA, "BSOIC:LTU0:5:GAMMARAW.VAL")
  field(INPB, "0.01")
  field(EGU, "mr/hour")
  field(HOPR, "10")
  field(LOPR, "0")
  field(HIHI, "9")
  field(LOLO, "0.5")
  field(HIGH, "8")
  field(LOW, "1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(ADEL, "0")
}


record(ai, "BSOIC:LTU0:5:GAMMARAW") {
  field(DESC, "Analog Input")
  field(SCAN, "I/O Intr")
  field(DTYP, "IP330")
  field(INP, "@AI1-UND0-1-PPS:9:DATA")
  field(PREC, "3")
  field(EGUF, "10")
  field(EGUL, "0")
  field(HOPR, "10")
  field(LOPR, "0")
  field(ADEL, "0")
  field(MDEL, "0")
  field(HIHI, "9")
  field(HIGH, "8")
  field(LOW, "4")
  field(LOLO, "0.5")
  field(EGU, "V")
  field(LINR, "LINEAR")
  field(HHSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(LLSV, "MAJOR")
  field(FLNK, "BSOIC:LTU0:5:GAMMAACT")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BSOIC:LTU0:5:GAMMAACT",440,88,0,0,"BSOIC:LTU0:5:GAMMAACT")
#! Field("BSOIC:LTU0:5:GAMMAACT.INPA",16777215,0,"BSOIC:LTU0:5:GAMMAACT.INPA")
#! Link("BSOIC:LTU0:5:GAMMAACT.INPA","BSOIC:LTU0:5:GAMMARAW.VAL")
#! Field("BSOIC:LTU0:5:GAMMAACT.INPB",16777215,1,"BSOIC:LTU0:5:GAMMAACT.INPB")
#! Record("BSOIC:LTU0:5:GAMMARAW",20,18,0,0,"BSOIC:LTU0:5:GAMMARAW")
#! Field("BSOIC:LTU0:5:GAMMARAW.VAL",16777215,1,"BSOIC:LTU0:5:GAMMARAW.VAL")
#! Field("BSOIC:LTU0:5:GAMMARAW.FLNK",16777215,1,"BSOIC:LTU0:5:GAMMARAW.FLNK")
#! Link("BSOIC:LTU0:5:GAMMARAW.FLNK","BSOIC:LTU0:5:GAMMAACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(calcout, "BSOIC:SPR1:1:NEUTRONACT") {
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(CALC, "B*(10^(A*0.5))")
  field(INPA, "BSOIC:SPR1:1:NEUTRONRAW.VAL")
  field(INPB, "0.001")
  field(EGU, "mr/hour")
  field(HOPR, "10")
  field(LOPR, "0")
  field(HIHI, "9")
  field(LOLO, "0")
  field(HIGH, "8")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(ADEL, "-1")
}


record(ai, "BSOIC:SPR1:1:NEUTRONRAW") {
  field(DESC, "Analog Input")
  field(SCAN, "I/O Intr")
  field(DTYP, "IP330")
  field(INP, "@AI1-UND0-1-PPS:12:DATA")
  field(PREC, "3")
  field(EGUF, "10")
  field(EGUL, "0")
  field(HOPR, "10")
  field(LOPR, "0")
  field(ADEL, "0")
  field(MDEL, "0")
  field(HIHI, "9")
  field(HIGH, "8")
  field(LOW, "-1")
  field(LOLO, "-1")
  field(EGU, "V")
  field(LINR, "LINEAR")
  field(HHSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(LLSV, "MAJOR")
  field(FLNK, "BSOIC:SPR1:1:NEUTRONACT")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BSOIC:SPR1:1:NEUTRONACT",440,88,0,0,"BSOIC:SPR1:1:NEUTRONACT")
#! Field("BSOIC:SPR1:1:NEUTRONACT.INPA",16777215,0,"BSOIC:SPR1:1:NEUTRONACT.INPA")
#! Link("BSOIC:SPR1:1:NEUTRONACT.INPA","BSOIC:SPR1:1:NEUTRONRAW.VAL")
#! Field("BSOIC:SPR1:1:NEUTRONACT.INPB",16777215,1,"BSOIC:SPR1:1:NEUTRONACT.INPB")
#! Record("BSOIC:SPR1:1:NEUTRONRAW",20,18,0,0,"BSOIC:SPR1:1:NEUTRONRAW")
#! Field("BSOIC:SPR1:1:NEUTRONRAW.VAL",16777215,1,"BSOIC:SPR1:1:NEUTRONRAW.VAL")
#! Field("BSOIC:SPR1:1:NEUTRONRAW.FLNK",16777215,1,"BSOIC:SPR1:1:NEUTRONRAW.FLNK")
#! Link("BSOIC:SPR1:1:NEUTRONRAW.FLNK","BSOIC:SPR1:1:NEUTRONACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(calcout, "BSOIC:SPR1:1:GAMMAACT") {
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(CALC, "B*(10^(A*0.5))")
  field(INPA, "BSOIC:SPR1:1:GAMMARAW.VAL")
  field(INPB, "0.01")
  field(EGU, "mr/hour")
  field(HOPR, "10")
  field(LOPR, "0")
  field(HIHI, "9")
  field(LOLO, "0.5")
  field(HIGH, "8")
  field(LOW, "1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(ADEL, "0")
}


record(ai, "BSOIC:SPR1:1:GAMMARAW") {
  field(DESC, "Analog Input")
  field(SCAN, "I/O Intr")
  field(DTYP, "IP330")
  field(INP, "@AI1-UND0-1-PPS:13:DATA")
  field(PREC, "3")
  field(EGUF, "10")
  field(EGUL, "0")
  field(HOPR, "10")
  field(LOPR, "0")
  field(ADEL, "0")
  field(MDEL, "0")
  field(HIHI, "9")
  field(HIGH, "8")
  field(LOW, "4")
  field(LOLO, "0.5")
  field(EGU, "V")
  field(LINR, "LINEAR")
  field(HHSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(LLSV, "MAJOR")
  field(FLNK, "BSOIC:SPR1:1:GAMMAACT")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BSOIC:SPR1:1:GAMMAACT",440,88,0,0,"BSOIC:SPR1:1:GAMMAACT")
#! Field("BSOIC:SPR1:1:GAMMAACT.INPA",16777215,0,"BSOIC:SPR1:1:GAMMAACT.INPA")
#! Link("BSOIC:SPR1:1:GAMMAACT.INPA","BSOIC:SPR1:1:GAMMARAW.VAL")
#! Field("BSOIC:SPR1:1:GAMMAACT.INPB",16777215,1,"BSOIC:SPR1:1:GAMMAACT.INPB")
#! Record("BSOIC:SPR1:1:GAMMARAW",20,18,0,0,"BSOIC:SPR1:1:GAMMARAW")
#! Field("BSOIC:SPR1:1:GAMMARAW.VAL",16777215,1,"BSOIC:SPR1:1:GAMMARAW.VAL")
#! Field("BSOIC:SPR1:1:GAMMARAW.FLNK",16777215,1,"BSOIC:SPR1:1:GAMMARAW.FLNK")
#! Link("BSOIC:SPR1:1:GAMMARAW.FLNK","BSOIC:SPR1:1:GAMMAACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(calcout, "BSOIC:UND0:1:NEUTRONACT") {
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(CALC, "B*(10^(A*0.5))")
  field(INPA, "BSOIC:UND0:1:NEUTRONRAW.VAL")
  field(INPB, "0.001")
  field(EGU, "mr/hour")
  field(HOPR, "10")
  field(LOPR, "0")
  field(HIHI, "9")
  field(LOLO, "0")
  field(HIGH, "8")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(ADEL, "-1")
}


record(ai, "BSOIC:UND0:1:NEUTRONRAW") {
  field(DESC, "Analog Input")
  field(SCAN, "I/O Intr")
  field(DTYP, "IP330")
  field(INP, "@AI1-UND0-1-PPS:16:DATA")
  field(PREC, "3")
  field(EGUF, "10")
  field(EGUL, "0")
  field(HOPR, "10")
  field(LOPR, "0")
  field(ADEL, "0")
  field(MDEL, "0")
  field(HIHI, "9")
  field(HIGH, "8")
  field(LOW, "-1")
  field(LOLO, "-1")
  field(EGU, "V")
  field(LINR, "LINEAR")
  field(HHSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(LLSV, "MAJOR")
  field(FLNK, "BSOIC:UND0:1:NEUTRONACT")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BSOIC:UND0:1:NEUTRONACT",440,88,0,0,"BSOIC:UND0:1:NEUTRONACT")
#! Field("BSOIC:UND0:1:NEUTRONACT.INPA",16777215,0,"BSOIC:UND0:1:NEUTRONACT.INPA")
#! Link("BSOIC:UND0:1:NEUTRONACT.INPA","BSOIC:UND0:1:NEUTRONRAW.VAL")
#! Field("BSOIC:UND0:1:NEUTRONACT.INPB",16777215,1,"BSOIC:UND0:1:NEUTRONACT.INPB")
#! Record("BSOIC:UND0:1:NEUTRONRAW",20,18,0,0,"BSOIC:UND0:1:NEUTRONRAW")
#! Field("BSOIC:UND0:1:NEUTRONRAW.VAL",16777215,1,"BSOIC:UND0:1:NEUTRONRAW.VAL")
#! Field("BSOIC:UND0:1:NEUTRONRAW.FLNK",16777215,1,"BSOIC:UND0:1:NEUTRONRAW.FLNK")
#! Link("BSOIC:UND0:1:NEUTRONRAW.FLNK","BSOIC:UND0:1:NEUTRONACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(calcout, "BSOIC:UND0:1:GAMMAACT") {
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(CALC, "B*(10^(A*0.5))")
  field(INPA, "BSOIC:UND0:1:GAMMARAW.VAL")
  field(INPB, "0.01")
  field(EGU, "mr/hour")
  field(HOPR, "10")
  field(LOPR, "0")
  field(HIHI, "9")
  field(LOLO, "0.5")
  field(HIGH, "8")
  field(LOW, "1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(ADEL, "0")
}


record(ai, "BSOIC:UND0:1:GAMMARAW") {
  field(DESC, "Analog Input")
  field(SCAN, "I/O Intr")
  field(DTYP, "IP330")
  field(INP, "@AI1-UND0-1-PPS:17:DATA")
  field(PREC, "3")
  field(EGUF, "10")
  field(EGUL, "0")
  field(HOPR, "10")
  field(LOPR, "0")
  field(ADEL, "0")
  field(MDEL, "0")
  field(HIHI, "9")
  field(HIGH, "8")
  field(LOW, "4")
  field(LOLO, "0.5")
  field(EGU, "V")
  field(LINR, "LINEAR")
  field(HHSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(LLSV, "MAJOR")
  field(FLNK, "BSOIC:UND0:1:GAMMAACT")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BSOIC:UND0:1:GAMMAACT",440,88,0,0,"BSOIC:UND0:1:GAMMAACT")
#! Field("BSOIC:UND0:1:GAMMAACT.INPA",16777215,0,"BSOIC:UND0:1:GAMMAACT.INPA")
#! Link("BSOIC:UND0:1:GAMMAACT.INPA","BSOIC:UND0:1:GAMMARAW.VAL")
#! Field("BSOIC:UND0:1:GAMMAACT.INPB",16777215,1,"BSOIC:UND0:1:GAMMAACT.INPB")
#! Record("BSOIC:UND0:1:GAMMARAW",20,18,0,0,"BSOIC:UND0:1:GAMMARAW")
#! Field("BSOIC:UND0:1:GAMMARAW.VAL",16777215,1,"BSOIC:UND0:1:GAMMARAW.VAL")
#! Field("BSOIC:UND0:1:GAMMARAW.FLNK",16777215,1,"BSOIC:UND0:1:GAMMARAW.FLNK")
#! Link("BSOIC:UND0:1:GAMMARAW.FLNK","BSOIC:UND0:1:GAMMAACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(calcout, "BSOIC:FEE0:1:NEUTRONACT") {
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(CALC, "B*(10^(A*0.5))")
  field(INPA, "BSOIC:FEE0:1:NEUTRONRAW.VAL")
  field(INPB, "0.001")
  field(EGU, "mr/hour")
  field(HOPR, "10")
  field(LOPR, "0")
  field(HIHI, "9")
  field(LOLO, "0")
  field(HIGH, "8")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(ADEL, "-1")
}


record(ai, "BSOIC:FEE0:1:NEUTRONRAW") {
  field(DESC, "Analog Input")
  field(SCAN, "I/O Intr")
  field(DTYP, "IP330")
  field(INP, "@AI1-UND0-1-PPS:18:DATA")
  field(PREC, "3")
  field(EGUF, "10")
  field(EGUL, "0")
  field(HOPR, "10")
  field(LOPR, "0")
  field(ADEL, "0")
  field(MDEL, "0")
  field(HIHI, "9")
  field(HIGH, "8")
  field(LOW, "-1")
  field(LOLO, "-1")
  field(EGU, "V")
  field(LINR, "LINEAR")
  field(HHSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(LLSV, "MAJOR")
  field(FLNK, "BSOIC:FEE0:1:NEUTRONACT")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BSOIC:FEE0:1:NEUTRONACT",440,88,0,0,"BSOIC:FEE0:1:NEUTRONACT")
#! Field("BSOIC:FEE0:1:NEUTRONACT.INPA",16777215,0,"BSOIC:FEE0:1:NEUTRONACT.INPA")
#! Link("BSOIC:FEE0:1:NEUTRONACT.INPA","BSOIC:FEE0:1:NEUTRONRAW.VAL")
#! Field("BSOIC:FEE0:1:NEUTRONACT.INPB",16777215,1,"BSOIC:FEE0:1:NEUTRONACT.INPB")
#! Record("BSOIC:FEE0:1:NEUTRONRAW",20,18,0,0,"BSOIC:FEE0:1:NEUTRONRAW")
#! Field("BSOIC:FEE0:1:NEUTRONRAW.VAL",16777215,1,"BSOIC:FEE0:1:NEUTRONRAW.VAL")
#! Field("BSOIC:FEE0:1:NEUTRONRAW.FLNK",16777215,1,"BSOIC:FEE0:1:NEUTRONRAW.FLNK")
#! Link("BSOIC:FEE0:1:NEUTRONRAW.FLNK","BSOIC:FEE0:1:NEUTRONACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(calcout, "BSOIC:FEE0:1:GAMMAACT") {
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(CALC, "B*(10^(A*0.5))")
  field(INPA, "BSOIC:FEE0:1:GAMMARAW.VAL")
  field(INPB, "0.01")
  field(EGU, "mr/hour")
  field(HOPR, "10")
  field(LOPR, "0")
  field(HIHI, "9")
  field(LOLO, "0.5")
  field(HIGH, "8")
  field(LOW, "1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(ADEL, "0")
}


record(ai, "BSOIC:FEE0:1:GAMMARAW") {
  field(DESC, "Analog Input")
  field(SCAN, "I/O Intr")
  field(DTYP, "IP330")
  field(INP, "@AI1-UND0-1-PPS:19:DATA")
  field(PREC, "3")
  field(EGUF, "10")
  field(EGUL, "0")
  field(HOPR, "10")
  field(LOPR, "0")
  field(ADEL, "0")
  field(MDEL, "0")
  field(HIHI, "9")
  field(HIGH, "8")
  field(LOW, "4")
  field(LOLO, "0.5")
  field(EGU, "V")
  field(LINR, "LINEAR")
  field(HHSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(LLSV, "MAJOR")
  field(FLNK, "BSOIC:FEE0:1:GAMMAACT")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BSOIC:FEE0:1:GAMMAACT",440,88,0,0,"BSOIC:FEE0:1:GAMMAACT")
#! Field("BSOIC:FEE0:1:GAMMAACT.INPA",16777215,0,"BSOIC:FEE0:1:GAMMAACT.INPA")
#! Link("BSOIC:FEE0:1:GAMMAACT.INPA","BSOIC:FEE0:1:GAMMARAW.VAL")
#! Field("BSOIC:FEE0:1:GAMMAACT.INPB",16777215,1,"BSOIC:FEE0:1:GAMMAACT.INPB")
#! Record("BSOIC:FEE0:1:GAMMARAW",20,18,0,0,"BSOIC:FEE0:1:GAMMARAW")
#! Field("BSOIC:FEE0:1:GAMMARAW.VAL",16777215,1,"BSOIC:FEE0:1:GAMMARAW.VAL")
#! Field("BSOIC:FEE0:1:GAMMARAW.FLNK",16777215,1,"BSOIC:FEE0:1:GAMMARAW.FLNK")
#! Link("BSOIC:FEE0:1:GAMMARAW.FLNK","BSOIC:FEE0:1:GAMMAACT")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBDEND


record(calcout, "BSOIC:LTU0:2:GAMMAACT") {
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(CALC, "B*(10^(A*0.6))")
  field(INPA, "BSOIC:LTU0:2:GAMMARAW.VAL")
  field(INPB, "1")
  field(EGU, "mr/hour")
  field(HOPR, "10")
  field(LOPR, "0")
  field(HIHI, "7")
  field(LOLO, "1.1")
  field(HIGH, "6")
  field(LOW, "1.5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(ADEL, "0")
}

record(ai, "BSOIC:LTU0:2:GAMMARAW") {
  field(DESC, "Analog Input")
  field(SCAN, "I/O Intr")
  field(DTYP, "IP330")
  field(INP, "@AI1-UND0-1-PPS:1:DATA")
  field(PREC, "3")
  field(EGUF, "10")
  field(EGUL, "0")
  field(HOPR, "10")
  field(LOPR, "0")
  field(ADEL, "0")
  field(MDEL, "0")
  field(HIHI, "9")
  field(HIGH, "7")
  field(LOW, "1.5")
  field(LOLO, "0.1")
  field(EGU, "V")
  field(LINR, "LINEAR")
  field(HHSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(LLSV, "MAJOR")
  field(FLNK, "BSOIC:LTU0:2:GAMMAACT")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BSOIC:LTU0:2:GAMMAACT",440,88,0,0,"BSOIC:LTU0:2:GAMMAACT")
#! Field("BSOIC:LTU0:2:GAMMAACT.INPA",16777215,0,"BSOIC:LTU0:2:GAMMAACT.INPA")
#! Link("BSOIC:LTU0:2:GAMMAACT.INPA","BSOIC:LTU0:2:GAMMARAW.VAL")
#! Field("BSOIC:LTU0:2:GAMMAACT.INPB",16777215,1,"BSOIC:LTU0:2:GAMMAACT.INPB")
#! Record("BSOIC:LTU0:2:GAMMARAW",20,18,0,0,"BSOIC:LTU0:2:GAMMARAW")
#! Field("BSOIC:LTU0:2:GAMMARAW.VAL",16777215,1,"BSOIC:LTU0:2:GAMMARAW.VAL")
#! Field("BSOIC:LTU0:2:GAMMARAW.FLNK",16777215,1,"BSOIC:LTU0:2:GAMMARAW.FLNK")
#! Link("BSOIC:LTU0:2:GAMMARAW.FLNK","BSOIC:LTU0:2:GAMMAACT")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBDEND


record(calcout, "BSOIC:LTU0:3:GAMMAACT") {
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(CALC, "B*(10^(A*0.6))")
  field(INPA, "BSOIC:LTU0:3:GAMMARAW.VAL")
  field(INPB, "1")
  field(EGU, "mr/hour")
  field(HOPR, "10")
  field(LOPR, "0")
  field(HIHI, "7")
  field(LOLO, "1.1")
  field(HIGH, "6")
  field(LOW, "1.5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(ADEL, "0")
}

record(ai, "BSOIC:LTU0:3:GAMMARAW") {
  field(DESC, "Analog Input")
  field(SCAN, "I/O Intr")
  field(DTYP, "IP330")
  field(INP, "@AI1-UND0-1-PPS:15:DATA")
  field(PREC, "3")
  field(EGUF, "10")
  field(EGUL, "0")
  field(HOPR, "10")
  field(LOPR, "0")
  field(ADEL, "0")
  field(MDEL, "0")
  field(HIHI, "9")
  field(HIGH, "7")
  field(LOW, "1.5")
  field(LOLO, "0.1")
  field(EGU, "V")
  field(LINR, "LINEAR")
  field(HHSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(LLSV, "MAJOR")
  field(FLNK, "BSOIC:LTU0:3:GAMMAACT")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BSOIC:LTU0:3:GAMMAACT",440,88,0,0,"BSOIC:LTU0:3:GAMMAACT")
#! Field("BSOIC:LTU0:3:GAMMAACT.INPA",16777215,0,"BSOIC:LTU0:3:GAMMAACT.INPA")
#! Link("BSOIC:LTU0:3:GAMMAACT.INPA","BSOIC:LTU0:3:GAMMARAW.VAL")
#! Field("BSOIC:LTU0:3:GAMMAACT.INPB",16777215,1,"BSOIC:LTU0:3:GAMMAACT.INPB")
#! Record("BSOIC:LTU0:3:GAMMARAW",20,18,0,0,"BSOIC:LTU0:3:GAMMARAW")
#! Field("BSOIC:LTU0:3:GAMMARAW.VAL",16777215,1,"BSOIC:LTU0:3:GAMMARAW.VAL")
#! Field("BSOIC:LTU0:3:GAMMARAW.FLNK",16777215,1,"BSOIC:LTU0:3:GAMMARAW.FLNK")
#! Link("BSOIC:LTU0:3:GAMMARAW.FLNK","BSOIC:LTU0:3:GAMMAACT")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBDEND


record(calcout, "BSOIC:LTU0:6:GAMMAACT") {
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(CALC, "B*(10^(A*0.6))")
  field(INPA, "BSOIC:LTU0:6:GAMMARAW.VAL")
  field(INPB, "1")
  field(EGU, "mr/hour")
  field(HOPR, "10")
  field(LOPR, "0")
  field(HIHI, "7")
  field(LOLO, "1.1")
  field(HIGH, "6")
  field(LOW, "1.5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(ADEL, "0")
}

record(ai, "BSOIC:LTU0:6:GAMMARAW") {
  field(DESC, "Analog Input")
  field(SCAN, "I/O Intr")
  field(DTYP, "IP330")
  field(INP, "@AI1-UND0-1-PPS:11:DATA")
  field(PREC, "3")
  field(EGUF, "10")
  field(EGUL, "0")
  field(HOPR, "10")
  field(LOPR, "0")
  field(ADEL, "0")
  field(MDEL, "0")
  field(HIHI, "9")
  field(HIGH, "7")
  field(LOW, "1.5")
  field(LOLO, "0.1")
  field(EGU, "V")
  field(LINR, "LINEAR")
  field(HHSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(LLSV, "MAJOR")
  field(FLNK, "BSOIC:LTU0:6:GAMMAACT")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BSOIC:LTU0:6:GAMMAACT",440,88,0,0,"BSOIC:LTU0:6:GAMMAACT")
#! Field("BSOIC:LTU0:6:GAMMAACT.INPA",16777215,0,"BSOIC:LTU0:6:GAMMAACT.INPA")
#! Link("BSOIC:LTU0:6:GAMMAACT.INPA","BSOIC:LTU0:6:GAMMARAW.VAL")
#! Field("BSOIC:LTU0:6:GAMMAACT.INPB",16777215,1,"BSOIC:LTU0:6:GAMMAACT.INPB")
#! Record("BSOIC:LTU0:6:GAMMARAW",20,18,0,0,"BSOIC:LTU0:6:GAMMARAW")
#! Field("BSOIC:LTU0:6:GAMMARAW.VAL",16777215,1,"BSOIC:LTU0:6:GAMMARAW.VAL")
#! Field("BSOIC:LTU0:6:GAMMARAW.FLNK",16777215,1,"BSOIC:LTU0:6:GAMMARAW.FLNK")
#! Link("BSOIC:LTU0:6:GAMMARAW.FLNK","BSOIC:LTU0:6:GAMMAACT")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBDEND


record(calcout, "BSOIC:LTU0:8:GAMMAACT") {
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(CALC, "B*(10^(A*0.6))")
  field(INPA, "BSOIC:LTU0:8:GAMMARAW.VAL")
  field(INPB, "1")
  field(EGU, "mr/hour")
  field(HOPR, "10")
  field(LOPR, "0")
  field(HIHI, "7")
  field(LOLO, "1.1")
  field(HIGH, "6")
  field(LOW, "1.5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(ADEL, "0")
}

record(ai, "BSOIC:LTU0:8:GAMMARAW") {
  field(DESC, "Analog Input")
  field(SCAN, "I/O Intr")
  field(DTYP, "IP330")
  field(INP, "@AI1-UND0-1-PPS:20:DATA")
  field(PREC, "3")
  field(EGUF, "10")
  field(EGUL, "0")
  field(HOPR, "10")
  field(LOPR, "0")
  field(ADEL, "0")
  field(MDEL, "0")
  field(HIHI, "9")
  field(HIGH, "7")
  field(LOW, "1.5")
  field(LOLO, "0.1")
  field(EGU, "V")
  field(LINR, "LINEAR")
  field(HHSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(LLSV, "MAJOR")
  field(FLNK, "BSOIC:LTU0:8:GAMMAACT")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BSOIC:LTU0:8:GAMMAACT",440,88,0,0,"BSOIC:LTU0:8:GAMMAACT")
#! Field("BSOIC:LTU0:8:GAMMAACT.INPA",16777215,0,"BSOIC:LTU0:8:GAMMAACT.INPA")
#! Link("BSOIC:LTU0:8:GAMMAACT.INPA","BSOIC:LTU0:8:GAMMARAW.VAL")
#! Field("BSOIC:LTU0:8:GAMMAACT.INPB",16777215,1,"BSOIC:LTU0:8:GAMMAACT.INPB")
#! Record("BSOIC:LTU0:8:GAMMARAW",20,18,0,0,"BSOIC:LTU0:8:GAMMARAW")
#! Field("BSOIC:LTU0:8:GAMMARAW.VAL",16777215,1,"BSOIC:LTU0:8:GAMMARAW.VAL")
#! Field("BSOIC:LTU0:8:GAMMARAW.FLNK",16777215,1,"BSOIC:LTU0:8:GAMMARAW.FLNK")
#! Link("BSOIC:LTU0:8:GAMMARAW.FLNK","BSOIC:LTU0:8:GAMMAACT")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBDEND


record(calcout, "BSOIC:LTU0:9:GAMMAACT") {
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(CALC, "B*(10^(A*0.6))")
  field(INPA, "BSOIC:LTU0:9:GAMMARAW.VAL")
  field(INPB, "1")
  field(EGU, "mr/hour")
  field(HOPR, "10")
  field(LOPR, "0")
  field(HIHI, "7")
  field(LOLO, "1.1")
  field(HIGH, "6")
  field(LOW, "1.5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(ADEL, "0")
}

record(ai, "BSOIC:LTU0:9:GAMMARAW") {
  field(DESC, "Analog Input")
  field(SCAN, "I/O Intr")
  field(DTYP, "IP330")
  field(INP, "@AI1-UND0-1-PPS:21:DATA")
  field(PREC, "3")
  field(EGUF, "10")
  field(EGUL, "0")
  field(HOPR, "10")
  field(LOPR, "0")
  field(ADEL, "0")
  field(MDEL, "0")
  field(HIHI, "9")
  field(HIGH, "7")
  field(LOW, "1.5")
  field(LOLO, "0.1")
  field(EGU, "V")
  field(LINR, "LINEAR")
  field(HHSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(LLSV, "MAJOR")
  field(FLNK, "BSOIC:LTU0:9:GAMMAACT")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("BSOIC:LTU0:9:GAMMAACT",440,88,0,0,"BSOIC:LTU0:9:GAMMAACT")
#! Field("BSOIC:LTU0:9:GAMMAACT.INPA",16777215,0,"BSOIC:LTU0:9:GAMMAACT.INPA")
#! Link("BSOIC:LTU0:9:GAMMAACT.INPA","BSOIC:LTU0:9:GAMMARAW.VAL")
#! Field("BSOIC:LTU0:9:GAMMAACT.INPB",16777215,1,"BSOIC:LTU0:9:GAMMAACT.INPB")
#! Record("BSOIC:LTU0:9:GAMMARAW",20,18,0,0,"BSOIC:LTU0:9:GAMMARAW")
#! Field("BSOIC:LTU0:9:GAMMARAW.VAL",16777215,1,"BSOIC:LTU0:9:GAMMARAW.VAL")
#! Field("BSOIC:LTU0:9:GAMMARAW.FLNK",16777215,1,"BSOIC:LTU0:9:GAMMARAW.FLNK")
#! Link("BSOIC:LTU0:9:GAMMARAW.FLNK","BSOIC:LTU0:9:GAMMAACT")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BSOIC:LTU0:1:STATE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-UND0-1-PPS P0 B2")
  field(ZNAM, "WARNING")
  field(ONAM, "OK")
  field(ZSV,  "MINOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "BSOBTH01 warning state")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:LTU0:1:STATE",2160,2153,0,1,"BSOIC:LTU0:1:STATE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BSOIC:LTU0:4:STATE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-UND0-1-PPS P0 B3")
  field(ZNAM, "WARNING")
  field(ONAM, "OK")
  field(ZSV,  "MINOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "BSOBTH04 warning state")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:LTU0:4:STATE",2160,2153,0,1,"BSOIC:LTU0:4:STATE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BSOIC:LTU0:5:STATE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-UND0-1-PPS P0 B4")
  field(ZNAM, "WARNING")
  field(ONAM, "OK")
  field(ZSV,  "MINOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "BSOBTH05 warning state")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:LTU0:5:STATE",2160,2153,0,1,"BSOIC:LTU0:5:STATE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BSOIC:SPR1:1:STATE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-UND0-1-PPS P0 B6")
  field(ZNAM, "WARNING")
  field(ONAM, "OK")
  field(ZSV,  "MINOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "BSOIC7 Spare warning state")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:SPR1:1:STATE",2160,2153,0,1,"BSOIC:SPR1:1:STATE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BSOIC:UND0:1:STATE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-UND0-1-PPS P1 B0")
  field(ZNAM, "WARNING")
  field(ONAM, "OK")
  field(ZSV,  "MINOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "BSOUND0 warning state")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:UND0:1:STATE",2160,2153,0,1,"BSOIC:UND0:1:STATE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BSOIC:FEE0:1:STATE") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-UND0-1-PPS P1 B1")
  field(ZNAM, "WARNING")
  field(ONAM, "OK")
  field(ZSV,  "MINOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "BSOFEE01 warning state")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:FEE0:1:STATE",2160,2153,0,1,"BSOIC:FEE0:1:STATE")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BSOIC:LTU0:2:PPSTRIP") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-UND0-2-PPS P0 B0")
  field(ZNAM, "TRIP")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "BSOBTH02 PPS TRIP")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:LTU0:2:PPSTRIP",2160,2153,0,1,"BSOIC:LTU0:2:PPSTRIP")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BSOIC:LTU0:1:PPSTRIP") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-UND0-2-PPS P0 B4")
  field(ZNAM, "TRIP")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "BSOBTH01 PPS TRIP")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:LTU0:1:PPSTRIP",2160,2153,0,1,"BSOIC:LTU0:1:PPSTRIP")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BSOIC:LTU0:1:EQUIPFAIL") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-UND0-2-PPS P0 B5")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "BSOBTH01 equip failure")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:LTU0:1:EQUIPFAIL",2160,2153,0,1,"BSOIC:LTU0:1:EQUIPFAIL")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BSOIC:LTU0:4:PPSTRIP") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-UND0-2-PPS P0 B6")
  field(ZNAM, "TRIP")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "BSOBTH04 PPS TRIP")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:LTU0:4:PPSTRIP",2160,2153,0,1,"BSOIC:LTU0:4:PPSTRIP")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BSOIC:LTU0:4:EQUIPFAIL") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-UND0-2-PPS P0 B7")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "BSOBTH04 equip failure")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:LTU0:4:EQUIPFAIL",2160,2153,0,1,"BSOIC:LTU0:4:EQUIPFAIL")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BSOIC:LTU0:5:PPSTRIP") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-UND0-2-PPS P1 B0")
  field(ZNAM, "TRIP")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "BSOBTH05 PPS TRIP")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:LTU0:5:PPSTRIP",2160,2153,0,1,"BSOIC:LTU0:5:PPSTRIP")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BSOIC:LTU0:5:EQUIPFAIL") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-UND0-2-PPS P1 B1")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "BSOBTH05 equip failure")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:LTU0:5:EQUIPFAIL",2160,2153,0,1,"BSOIC:LTU0:5:EQUIPFAIL")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BSOIC:LTU0:6:PPSTRIP") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-UND0-2-PPS P1 B2")
  field(ZNAM, "TRIP")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "BSOBTH06 PPS TRIP")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:LTU0:6:PPSTRIP",2160,2153,0,1,"BSOIC:LTU0:6:PPSTRIP")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BSOIC:SPR1:1:PPSTRIP") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-UND0-2-PPS P1 B4")
  field(ZNAM, "TRIP")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "BSOIC7 PPS TRIP")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:SPR1:1:PPSTRIP",2160,2153,0,1,"BSOIC:SPR1:1:PPSTRIP")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BSOIC:SPR1:1:EQUIPFAIL") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-UND0-2-PPS P1 B5")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "BSOIC7 equip failure")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:SPR1:1:EQUIPFAIL",2160,2153,0,1,"BSOIC:SPR1:1:EQUIPFAIL")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BSOIC:LTU0:3:PPSTRIP") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-UND0-2-PPS P1 B6")
  field(ZNAM, "TRIP")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "BSOBTH03 PPS TRIP")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:LTU0:3:PPSTRIP",2160,2153,0,1,"BSOIC:LTU0:3:PPSTRIP")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BSOIC:UND0:1:PPSTRIP") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-UND0-2-PPS P2 B0")
  field(ZNAM, "TRIP")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "BSOUND0 PPS TRIP")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:UND0:1:PPSTRIP",2160,2153,0,1,"BSOIC:UND0:1:PPSTRIP")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BSOIC:UND0:1:EQUIPFAIL") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-UND0-2-PPS P2 B1")
  field(ZNAM, "FAULT")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "BSOUND0 equip failure")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:UND0:1:EQUIPFAIL",2160,2153,0,1,"BSOIC:UND0:1:EQUIPFAIL")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BSOIC:LTU0:8:PPSTRIP") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-UND0-2-PPS P3 B0")
  field(ZNAM, "TRIP")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "BSOBTH08 PPS TRIP")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:LTU0:8:PPSTRIP",2160,2153,0,1,"BSOIC:LTU0:8:PPSTRIP")
#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND



record(bi, "BSOIC:LTU0:9:PPSTRIP") {
  field(SCAN, ".1 second")
  field(DTYP, "XYCOM-2440")
  field(INP, "@DI-UND0-2-PPS P3 B1")
  field(ZNAM, "TRIP")
  field(ONAM, "OK")
  field(ZSV,  "MAJOR")
  field(OSV,  "NO_ALARM")
  field(DESC, "BSOBTH09 PPS TRIP")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:LTU0:9:PPSTRIP",2160,2153,0,1,"BSOIC:LTU0:9:PPSTRIP")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND


record(bo, "BSOIC:LTU0:2:RESET") {
  field(DESC, "BSOIC01 reset command")
#  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(FLNK, "BSOIC:LTU0:2:RESETH")
  field(OUT, "BSOIC:LTU0:2:RESETH")
  field(ZNAM, "NOT_RESET")
  field(ONAM, "RESET")
  field(ASG,  "DEFAULT")
  field(VAL, "0")
}

record(bo, "BSOIC:LTU0:2:RESETH") {
  field(DESC, "BSOIC01 reset command")
  field(SCAN, "Passive")
  field(DTYP, "XYCOM-2445")
  field(OUT, "@DO-UND0-1-PPS P0 B0")
  field(ZNAM, "NOT_RESET")
  field(ONAM, "RESET")
  field(ASG,  "DEFAULT")
  field(HIGH, ".25")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:LTU0:2:RESET",2140,2152,0,1,"BSOIC:LTU0:2:RESET")
#! Field("BSOIC:LTU0:2:RESET.FLNK",16777215,1,"BSOIC:LTU0:2:RESET.FLNK")
#! Link("BSOIC:LTU0:2:RESET.FLNK","BSOIC:LTU0:2:RESETH")
#! Field("BSOIC:LTU0:2:RESET.OUT",16777215,1,"BSOIC:LTU0:2:RESET.OUT")
#! Link("BSOIC:LTU0:2:RESET.OUT","BSOIC:LTU0:2:RESETH.VAL")
#! Record("BSOIC:LTU0:2:RESETH",2460,2226,0,0,"BSOIC:LTU0:2:RESETH")
#! Field("BSOIC:LTU0:2:RESETH.VAL",16777215,0,"BSOIC:LTU0:2:RESETH.VAL")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND


record(bo, "BSOIC:LTU0:1:RESET") {
  field(DESC, "BSOIC03 reset command")
#  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(FLNK, "BSOIC:LTU0:1:RESETH")
  field(OUT, "BSOIC:LTU0:1:RESETH")
  field(ZNAM, "NOT_RESET")
  field(ONAM, "RESET")
  field(ASG,  "DEFAULT")
  field(VAL, "0")
}

record(bo, "BSOIC:LTU0:1:RESETH") {
  field(DESC, "BSOIC03 reset command")
  field(SCAN, "Passive")
  field(DTYP, "XYCOM-2445")
  field(OUT, "@DO-UND0-1-PPS P0 B2")
  field(ZNAM, "NOT_RESET")
  field(ONAM, "RESET")
  field(ASG,  "DEFAULT")
  field(HIGH, ".25")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:LTU0:1:RESET",2140,2152,0,1,"BSOIC:LTU0:1:RESET")
#! Field("BSOIC:LTU0:1:RESET.FLNK",16777215,1,"BSOIC:LTU0:1:RESET.FLNK")
#! Link("BSOIC:LTU0:1:RESET.FLNK","BSOIC:LTU0:1:RESETH")
#! Field("BSOIC:LTU0:1:RESET.OUT",16777215,1,"BSOIC:LTU0:1:RESET.OUT")
#! Link("BSOIC:LTU0:1:RESET.OUT","BSOIC:LTU0:1:RESETH.VAL")
#! Record("BSOIC:LTU0:1:RESETH",2460,2226,0,0,"BSOIC:LTU0:1:RESETH")
#! Field("BSOIC:LTU0:1:RESETH.VAL",16777215,0,"BSOIC:LTU0:1:RESETH.VAL")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND


record(bo, "BSOIC:LTU0:4:RESET") {
  field(DESC, "BSOIC04 reset command")
#  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(FLNK, "BSOIC:LTU0:4:RESETH")
  field(OUT, "BSOIC:LTU0:4:RESETH")
  field(ZNAM, "NOT_RESET")
  field(ONAM, "RESET")
  field(ASG,  "DEFAULT")
  field(VAL, "0")
}

record(bo, "BSOIC:LTU0:4:RESETH") {
  field(DESC, "BSOIC04 reset command")
  field(SCAN, "Passive")
  field(DTYP, "XYCOM-2445")
  field(OUT, "@DO-UND0-1-PPS P0 B3")
  field(ZNAM, "NOT_RESET")
  field(ONAM, "RESET")
  field(ASG,  "DEFAULT")
  field(HIGH, ".25")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:LTU0:4:RESET",2140,2152,0,1,"BSOIC:LTU0:4:RESET")
#! Field("BSOIC:LTU0:4:RESET.FLNK",16777215,1,"BSOIC:LTU0:4:RESET.FLNK")
#! Link("BSOIC:LTU0:4:RESET.FLNK","BSOIC:LTU0:4:RESETH")
#! Field("BSOIC:LTU0:4:RESET.OUT",16777215,1,"BSOIC:LTU0:4:RESET.OUT")
#! Link("BSOIC:LTU0:4:RESET.OUT","BSOIC:LTU0:4:RESETH.VAL")
#! Record("BSOIC:LTU0:4:RESETH",2460,2226,0,0,"BSOIC:LTU0:4:RESETH")
#! Field("BSOIC:LTU0:4:RESETH.VAL",16777215,0,"BSOIC:LTU0:4:RESETH.VAL")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND


record(bo, "BSOIC:LTU0:5:RESET") {
  field(DESC, "BSOIC05 reset command")
#  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(FLNK, "BSOIC:LTU0:5:RESETH")
  field(OUT, "BSOIC:LTU0:5:RESETH")
  field(ZNAM, "NOT_RESET")
  field(ONAM, "RESET")
  field(ASG,  "DEFAULT")
  field(VAL, "0")
}

record(bo, "BSOIC:LTU0:5:RESETH") {
  field(DESC, "BSOIC05 reset command")
  field(SCAN, "Passive")
  field(DTYP, "XYCOM-2445")
  field(OUT, "@DO-UND0-1-PPS P0 B4")
  field(ZNAM, "NOT_RESET")
  field(ONAM, "RESET")
  field(ASG,  "DEFAULT")
  field(HIGH, ".25")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:LTU0:5:RESET",2140,2152,0,1,"BSOIC:LTU0:5:RESET")
#! Field("BSOIC:LTU0:5:RESET.FLNK",16777215,1,"BSOIC:LTU0:5:RESET.FLNK")
#! Link("BSOIC:LTU0:5:RESET.FLNK","BSOIC:LTU0:5:RESETH")
#! Field("BSOIC:LTU0:5:RESET.OUT",16777215,1,"BSOIC:LTU0:5:RESET.OUT")
#! Link("BSOIC:LTU0:5:RESET.OUT","BSOIC:LTU0:5:RESETH.VAL")
#! Record("BSOIC:LTU0:5:RESETH",2460,2226,0,0,"BSOIC:LTU0:5:RESETH")
#! Field("BSOIC:LTU0:5:RESETH.VAL",16777215,0,"BSOIC:LTU0:5:RESETH.VAL")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND


record(bo, "BSOIC:LTU0:6:RESET") {
  field(DESC, "BSOIC06 reset command")
#  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(FLNK, "BSOIC:LTU0:6:RESETH")
  field(OUT, "BSOIC:LTU0:6:RESETH")
  field(ZNAM, "NOT_RESET")
  field(ONAM, "RESET")
  field(ASG,  "DEFAULT")
  field(VAL, "0")
}

record(bo, "BSOIC:LTU0:6:RESETH") {
  field(DESC, "BSOIC06 reset command")
  field(SCAN, "Passive")
  field(DTYP, "XYCOM-2445")
  field(OUT, "@DO-UND0-1-PPS P0 B5")
  field(ZNAM, "NOT_RESET")
  field(ONAM, "RESET")
  field(ASG,  "DEFAULT")
  field(HIGH, ".25")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:LTU0:6:RESET",2140,2152,0,1,"BSOIC:LTU0:6:RESET")
#! Field("BSOIC:LTU0:6:RESET.FLNK",16777215,1,"BSOIC:LTU0:6:RESET.FLNK")
#! Link("BSOIC:LTU0:6:RESET.FLNK","BSOIC:LTU0:6:RESETH")
#! Field("BSOIC:LTU0:6:RESET.OUT",16777215,1,"BSOIC:LTU0:6:RESET.OUT")
#! Link("BSOIC:LTU0:6:RESET.OUT","BSOIC:LTU0:6:RESETH.VAL")
#! Record("BSOIC:LTU0:6:RESETH",2460,2226,0,0,"BSOIC:LTU0:6:RESETH")
#! Field("BSOIC:LTU0:6:RESETH.VAL",16777215,0,"BSOIC:LTU0:6:RESETH.VAL")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND


record(bo, "BSOIC:SPR1:1:RESET") {
  field(DESC, "BSOIC07 reset command")
#  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(FLNK, "BSOIC:SPR1:1:RESETH")
  field(OUT, "BSOIC:SPR1:1:RESETH")
  field(ZNAM, "NOT_RESET")
  field(ONAM, "RESET")
  field(ASG,  "DEFAULT")
  field(VAL, "0")
}

record(bo, "BSOIC:SPR1:1:RESETH") {
  field(DESC, "BSOIC07 reset command")
  field(SCAN, "Passive")
  field(DTYP, "XYCOM-2445")
  field(OUT, "@DO-UND0-1-PPS P0 B6")
  field(ZNAM, "NOT_RESET")
  field(ONAM, "RESET")
  field(ASG,  "DEFAULT")
  field(HIGH, ".25")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:SPR1:1:RESET",2140,2152,0,1,"BSOIC:SPR1:1:RESET")
#! Field("BSOIC:SPR1:1:RESET.FLNK",16777215,1,"BSOIC:SPR1:1:RESET.FLNK")
#! Link("BSOIC:SPR1:1:RESET.FLNK","BSOIC:SPR1:1:RESETH")
#! Field("BSOIC:SPR1:1:RESET.OUT",16777215,1,"BSOIC:SPR1:1:RESET.OUT")
#! Link("BSOIC:SPR1:1:RESET.OUT","BSOIC:SPR1:1:RESETH.VAL")
#! Record("BSOIC:SPR1:1:RESETH",2460,2226,0,0,"BSOIC:SPR1:1:RESETH")
#! Field("BSOIC:SPR1:1:RESETH.VAL",16777215,0,"BSOIC:SPR1:1:RESETH.VAL")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND


record(bo, "BSOIC:LTU0:3:RESET") {
  field(DESC, "BSOIC08 reset command")
#  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(FLNK, "BSOIC:LTU0:3:RESETH")
  field(OUT, "BSOIC:LTU0:3:RESETH")
  field(ZNAM, "NOT_RESET")
  field(ONAM, "RESET")
  field(ASG,  "DEFAULT")
  field(VAL, "0")
}

record(bo, "BSOIC:LTU0:3:RESETH") {
  field(DESC, "BSOIC08 reset command")
  field(SCAN, "Passive")
  field(DTYP, "XYCOM-2445")
  field(OUT, "@DO-UND0-1-PPS P0 B7")
  field(ZNAM, "NOT_RESET")
  field(ONAM, "RESET")
  field(ASG,  "DEFAULT")
  field(HIGH, ".25")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:LTU0:3:RESET",2140,2152,0,1,"BSOIC:LTU0:3:RESET")
#! Field("BSOIC:LTU0:3:RESET.FLNK",16777215,1,"BSOIC:LTU0:3:RESET.FLNK")
#! Link("BSOIC:LTU0:3:RESET.FLNK","BSOIC:LTU0:3:RESETH")
#! Field("BSOIC:LTU0:3:RESET.OUT",16777215,1,"BSOIC:LTU0:3:RESET.OUT")
#! Link("BSOIC:LTU0:3:RESET.OUT","BSOIC:LTU0:3:RESETH.VAL")
#! Record("BSOIC:LTU0:3:RESETH",2460,2226,0,0,"BSOIC:LTU0:3:RESETH")
#! Field("BSOIC:LTU0:3:RESETH.VAL",16777215,0,"BSOIC:LTU0:3:RESETH.VAL")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND


record(bo, "BSOIC:UND0:1:RESET") {
  field(DESC, "BSOIC09 reset command")
#  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(FLNK, "BSOIC:UND0:1:RESETH")
  field(OUT, "BSOIC:UND0:1:RESETH")
  field(ZNAM, "NOT_RESET")
  field(ONAM, "RESET")
  field(ASG,  "DEFAULT")
  field(VAL, "0")
}

record(bo, "BSOIC:UND0:1:RESETH") {
  field(DESC, "BSOIC09 reset command")
  field(SCAN, "Passive")
  field(DTYP, "XYCOM-2445")
  field(OUT, "@DO-UND0-1-PPS P1 B0")
  field(ZNAM, "NOT_RESET")
  field(ONAM, "RESET")
  field(ASG,  "DEFAULT")
  field(HIGH, ".25")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:UND0:1:RESET",2140,2152,0,1,"BSOIC:UND0:1:RESET")
#! Field("BSOIC:UND0:1:RESET.FLNK",16777215,1,"BSOIC:UND0:1:RESET.FLNK")
#! Link("BSOIC:UND0:1:RESET.FLNK","BSOIC:UND0:1:RESETH")
#! Field("BSOIC:UND0:1:RESET.OUT",16777215,1,"BSOIC:UND0:1:RESET.OUT")
#! Link("BSOIC:UND0:1:RESET.OUT","BSOIC:UND0:1:RESETH.VAL")
#! Record("BSOIC:UND0:1:RESETH",2460,2226,0,0,"BSOIC:UND0:1:RESETH")
#! Field("BSOIC:UND0:1:RESETH.VAL",16777215,0,"BSOIC:UND0:1:RESETH.VAL")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/bcs.dbd")
#! DBDEND


record(bo, "BSOIC:FEE0:1:RESET") {
  field(DESC, "BSOIC10 reset command")
#  field(SCAN, "Passive")
  field(PINI, "YES")
  field(DTYP, "Soft Channel")
  field(FLNK, "BSOIC:FEE0:1:RESETH")
  field(OUT, "BSOIC:FEE0:1:RESETH")
  field(ZNAM, "NOT_RESET")
  field(ONAM, "RESET")
  field(ASG,  "DEFAULT")
  field(VAL, "0")
}

record(bo, "BSOIC:FEE0:1:RESETH") {
  field(DESC, "BSOIC10 reset command")
  field(SCAN, "Passive")
  field(DTYP, "XYCOM-2445")
  field(OUT, "@DO-UND0-1-PPS P1 B1")
  field(ZNAM, "NOT_RESET")
  field(ONAM, "RESET")
  field(ASG,  "DEFAULT")
  field(HIGH, ".25")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOIC:FEE0:1:RESET",2140,2152,0,1,"BSOIC:FEE0:1:RESET")
#! Field("BSOIC:FEE0:1:RESET.FLNK",16777215,1,"BSOIC:FEE0:1:RESET.FLNK")
#! Link("BSOIC:FEE0:1:RESET.FLNK","BSOIC:FEE0:1:RESETH")
#! Field("BSOIC:FEE0:1:RESET.OUT",16777215,1,"BSOIC:FEE0:1:RESET.OUT")
#! Link("BSOIC:FEE0:1:RESET.OUT","BSOIC:FEE0:1:RESETH.VAL")
#! Record("BSOIC:FEE0:1:RESETH",2460,2226,0,0,"BSOIC:FEE0:1:RESETH")
#! Field("BSOIC:FEE0:1:RESETH.VAL",16777215,0,"BSOIC:FEE0:1:RESETH.VAL")

record(bo,"PPS:UND0:1:PERMACCSET") {
  field(DESC, "IOC_Permitted_Access_BTH")
  field(DTYP, "EtherIP")
  field(SCAN, ".1 second")
  field(OUT, "@PLC:UND0:PPS1 PPS_UND_EPICS_0.Data_00[0]")
  field(HIGH, "3")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ASG,  "MCC")
}


record(bo,"PPS:UND0:1:CTRLACCSET") {
  field(DESC, "IOC_Controlled_Access_BTH")
  field(DTYP, "EtherIP")
  field(SCAN, ".1 second")
  field(OUT, "@PLC:UND0:PPS1 PPS_UND_EPICS_0.Data_00[1]")
  field(HIGH, "3")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ASG,  "MCC")
}


record(bo,"PPS:UND0:1:NOACCSET") {
  field(DESC, "IOC_No_Access_BTH")
  field(DTYP, "EtherIP")
  field(SCAN, ".1 second")
  field(OUT, "@PLC:UND0:PPS1 PPS_UND_EPICS_0.Data_00[2]")
  field(HIGH, "3")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ASG,  "MCC")
}


record(bo,"PPS:UND0:1:KBANKSET") {
  field(DESC, "IOC_Keybank_Release_BTH")
  field(DTYP, "EtherIP")
  field(SCAN, ".1 second")
  field(OUT, "@PLC:UND0:PPS1 PPS_UND_EPICS_0.Data_01[0]")
  field(HIGH, "3")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ASG,  "MCC")
}


record(bo,"PPS:UND0:1:DOORSWSET") {
  field(DESC, "IOC_Door_Release_BTH")
  field(DTYP, "EtherIP")
  field(SCAN, ".1 second")
  field(OUT, "@PLC:UND0:PPS1 PPS_UND_EPICS_0.Data_01[1]")
  field(HIGH, "3")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ASG,  "MCC")
}


record(bo,"PPS:UND0:1:INTLKRESET") {
  field(DESC, "IOC_Interlock_Reset_BTH")
  field(DTYP, "EtherIP")
  field(SCAN, ".1 second")
  field(OUT, "@PLC:UND0:PPS1 PPS_UND_EPICS_0.Data_01[2]")
  field(HIGH, "3")
  field(ZNAM, "NOT_RESET")
  field(ONAM, "RESET")
  field(ASG,  "MCC")
}


record(bo,"PPS:UND0:1:SRCHRESETSET") {
  field(DESC, "IOC_Search_Reset_BTH")
  field(DTYP, "EtherIP")
  field(SCAN, ".1 second")
  field(OUT, "@PLC:UND0:PPS1 PPS_UND_EPICS_0.Data_01[3]")
  field(HIGH, "3")
  field(ZNAM, "NOT_RESET")
  field(ONAM, "RESET")
  field(ASG,  "MCC")
}


record(bo,"BTM:LTU0:172:IOCTEST") {
  field(DESC, "IOC_Test_BTM1")
  field(DTYP, "EtherIP")
  field(SCAN, ".1 second")
  field(OUT, "@PLC:UND0:PPS1 PPS_UND_EPICS_0.Data_02[0]")
  field(HIGH, "3")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ASG,  "MCC")
}


record(bo,"BTM:LTU0:226:IOCTEST") {
  field(DESC, "IOC_Test_BTM2")
  field(DTYP, "EtherIP")
  field(SCAN, ".1 second")
  field(OUT, "@PLC:UND0:PPS1 PPS_UND_EPICS_0.Data_02[1]")
  field(HIGH, "3")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ASG,  "MCC")
}


record(bo,"BTM:LTU0:300:IOCTEST") {
  field(DESC, "IOC_Test_BTM3")
  field(DTYP, "EtherIP")
  field(SCAN, ".1 second")
  field(OUT, "@PLC:UND0:PPS1 PPS_UND_EPICS_0.Data_02[2]")
  field(HIGH, "3")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ASG,  "MCC")
}


record(bo,"BTM:LTU0:440:IOCTEST") {
  field(DESC, "IOC_Test_BTM4")
  field(DTYP, "EtherIP")
  field(SCAN, ".1 second")
  field(OUT, "@PLC:UND0:PPS1 PPS_UND_EPICS_0.Data_02[3]")
  field(HIGH, "3")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ASG,  "MCC")
}


record(bo,"BTM:LTU0:507:IOCTEST") {
  field(DESC, "IOC_Test_BTM5")
  field(DTYP, "EtherIP")
  field(SCAN, ".1 second")
  field(OUT, "@PLC:UND0:PPS1 PPS_UND_EPICS_0.Data_02[4]")
  field(HIGH, "3")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ASG,  "MCC")
}


record(bo,"BTM:LTU0:645:IOCTEST") {
  field(DESC, "IOC_Test_BTM6")
  field(DTYP, "EtherIP")
  field(SCAN, ".1 second")
  field(OUT, "@PLC:UND0:PPS1 PPS_UND_EPICS_0.Data_02[5]")
  field(HIGH, "3")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ASG,  "MCC")
}


record(bo,"BTM:LTU0:648:IOCTEST") {
  field(DESC, "IOC_Test_BTM7")
  field(DTYP, "EtherIP")
  field(SCAN, ".1 second")
  field(OUT, "@PLC:UND0:PPS1 PPS_UND_EPICS_0.Data_02[6]")
  field(HIGH, "3")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ASG,  "MCC")
}


record(bo,"BTM:LTU0:687:IOCTEST") {
  field(DESC, "IOC_Test_BTM8")
  field(DTYP, "EtherIP")
  field(SCAN, ".1 second")
  field(OUT, "@PLC:UND0:PPS1 PPS_UND_EPICS_0.Data_02[7]")
  field(HIGH, "3")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ASG,  "MCC")
}


record(bo,"BTM:LTU0:717:IOCTEST") {
  field(DESC, "IOC_Test_BTM9")
  field(DTYP, "EtherIP")
  field(SCAN, ".1 second")
  field(OUT, "@PLC:UND0:PPS1 PPS_UND_EPICS_0.Data_02[8]")
  field(HIGH, "3")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ASG,  "MCC")
}


record(bo,"BTM:DMP0:451:IOCTEST") {
  field(DESC, "IOC_Test_BTM10")
  field(DTYP, "EtherIP")
  field(SCAN, ".1 second")
  field(OUT, "@PLC:UND0:PPS1 PPS_UND_EPICS_0.Data_02[9]")
  field(HIGH, "3")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ASG,  "MCC")
}


record(bo,"BTM:DMP0:699:IOCTEST") {
  field(DESC, "IOC_Test_BTM11")
  field(DTYP, "EtherIP")
  field(SCAN, ".1 second")
  field(OUT, "@PLC:UND0:PPS1 PPS_UND_EPICS_0.Data_02[10]")
  field(HIGH, "3")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ASG,  "MCC")
}


record(bo,"BTM:DMP0:711:IOCTEST") {
  field(DESC, "IOC_Test_BTM12")
  field(DTYP, "EtherIP")
  field(SCAN, ".1 second")
  field(OUT, "@PLC:UND0:PPS1 PPS_UND_EPICS_0.Data_02[11]")
  field(HIGH, "3")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ASG,  "MCC")
}


record(bo,"BTM:DMP0:741:IOCTEST") {
  field(DESC, "IOC_Test_BTM13")
  field(DTYP, "EtherIP")
  field(SCAN, ".1 second")
  field(OUT, "@PLC:UND0:PPS1 PPS_UND_EPICS_0.Data_02[12]")
  field(HIGH, "3")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ASG,  "MCC")
}


record(bo,"BTM:DMP0:771:IOCTEST") {
  field(DESC, "IOC_Test_BTM14")
  field(DTYP, "EtherIP")
  field(SCAN, ".1 second")
  field(OUT, "@PLC:UND0:PPS1 PPS_UND_EPICS_0.Data_02[13]")
  field(HIGH, "3")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ASG,  "MCC")
}


record(bo,"BTM:DMP0:801:IOCTEST") {
  field(DESC, "IOC_Test_BTM15")
  field(DTYP, "EtherIP")
  field(SCAN, ".1 second")
  field(OUT, "@PLC:UND0:PPS1 PPS_UND_EPICS_0.Data_02[14]")
  field(HIGH, "3")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ASG,  "MCC")
}


record(bo,"BTM:DMP0:999:IOCTEST") {
  field(DESC, "IOC_Test_BTM16")
  field(DTYP, "EtherIP")
  field(SCAN, ".1 second")
  field(OUT, "@PLC:UND0:PPS1 PPS_UND_EPICS_0.Data_02[15]")
  field(HIGH, "3")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ASG,  "MCC")
}


record(bo,"PPS:UND0:1:IOCTESTRESET") {
  field(DESC, "IOC_Test_Reset")
  field(DTYP, "EtherIP")
  field(SCAN, ".1 second")
  field(OUT, "@PLC:UND0:PPS1 PPS_UND_EPICS_0.Data_02[16]")
  field(HIGH, "3")
  field(ZNAM, "NOT_SET")
  field(ONAM, "SET")
  field(ASG,  "MCC")
}

#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND



record(calcout, "PPS:LTU0:1:CBWCHL_CALC_CNT") {
  field(DESC, "Crash Door Latch CALC")
  field(SCAN, "Passive")
  field(PINI, "YES")
  field(INPA, "PPS:LTU0:1:CBWVIO CP")
  field(INPB, "PPS:LTU0:1:CBWCHL_CNT.VAL")
  field(CALC, "A")
  field(OUT, "PPS:LTU0:1:CBWCHL_CNT.VAL PP")
  field(OOPT, "Transition To Non-zero")
  field(DOPT, "Use OCAL")
  field(OCAL, "B+1")
  info(autosaveFields_pass0, "VAL")
}

record(ai, "PPS:LTU0:1:CBWCHL_CNT") {
  field(DESC, "Crash Door Latch Counter")
  field(SCAN, "Passive")
  field(PINI, "YES")
  field(VAL, "0")
  field(EGU, "Faults")
  field(LOPR, "0")
  info(autosaveFields_pass0, "VAL")
}

#! Further lines contain data used by VisualDCT
#! View(2639,2581,1.2)
#! Record("PPS:LTU0:1:CBWCHL_CALC_CNT",2400,2260,0,1,"PPS:LTU0:1:CBWCHL_CALC_CNT")
#! Field("PPS:LTU0:1:CBWCHL_CALC_CNT.INPA",16777215,0,"PPS:LTU0:1:CBWCHL_CALC_CNT.INPA")
#! Link("PPS:LTU0:1:CBWCHL_CALC_CNT.INPA","PPS:LTU0:1:CBWCHL/INPA")
#! Field("PPS:LTU0:1:CBWCHL_CALC_CNT.INPB",16777215,1,"PPS:LTU0:1:CBWCHL_CALC_CNT.INPB")
#! Link("PPS:LTU0:1:CBWCHL_CALC_CNT.INPB","PPS:LTU0:1:CBWCHL_CNT.VAL")
#! Field("PPS:LTU0:1:CBWCHL_CALC_CNT.OUT",16777215,1,"PPS:LTU0:1:CBWCHL_CALC_CNT.OUT")
#! Link("PPS:LTU0:1:CBWCHL_CALC_CNT.OUT","PPS:LTU0:1:CBWCHL_CNT.VAL")
#! Connector("PPS:LTU0:1:CBWCHL/INPA",null,2260,2480,16777215,"",3)
#! Record("PPS:LTU0:1:CBWCHL_CNT",2760,2337,0,1,"PPS:LTU0:1:CBWCHL_CNT")
#! Field("PPS:LTU0:1:CBWCHL_CNT.VAL",16777215,0,"PPS:LTU0:1:CBWCHL_CNT.VAL")
#! TextBox(TB0,2180,2460,2360,2440,0,"Dialog",12,1,13369344,"Door Violation Latch PV",null)
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND



record(calcout, "PPS:LTU0:1:CBECHL_CALC_CNT") {
  field(DESC, "Crash Door Latch CALC")
  field(SCAN, "Passive")
  field(PINI, "YES")
  field(INPA, "PPS:LTU0:1:CBEVIO CP")
  field(INPB, "PPS:LTU0:1:CBECHL_CNT.VAL")
  field(CALC, "A")
  field(OUT, "PPS:LTU0:1:CBECHL_CNT.VAL PP")
  field(OOPT, "Transition To Non-zero")
  field(DOPT, "Use OCAL")
  field(OCAL, "B+1")
  info(autosaveFields_pass0, "VAL")
}

record(ai, "PPS:LTU0:1:CBECHL_CNT") {
  field(DESC, "Crash Door Latch Counter")
  field(SCAN, "Passive")
  field(PINI, "YES")
  field(VAL, "0")
  field(EGU, "Faults")
  field(LOPR, "0")
  info(autosaveFields_pass0, "VAL")
}

#! Further lines contain data used by VisualDCT
#! View(2639,2581,1.2)
#! Record("PPS:LTU0:1:CBECHL_CALC_CNT",2400,2260,0,1,"PPS:LTU0:1:CBECHL_CALC_CNT")
#! Field("PPS:LTU0:1:CBECHL_CALC_CNT.INPA",16777215,0,"PPS:LTU0:1:CBECHL_CALC_CNT.INPA")
#! Link("PPS:LTU0:1:CBECHL_CALC_CNT.INPA","PPS:LTU0:1:CBECHL/INPA")
#! Field("PPS:LTU0:1:CBECHL_CALC_CNT.INPB",16777215,1,"PPS:LTU0:1:CBECHL_CALC_CNT.INPB")
#! Link("PPS:LTU0:1:CBECHL_CALC_CNT.INPB","PPS:LTU0:1:CBECHL_CNT.VAL")
#! Field("PPS:LTU0:1:CBECHL_CALC_CNT.OUT",16777215,1,"PPS:LTU0:1:CBECHL_CALC_CNT.OUT")
#! Link("PPS:LTU0:1:CBECHL_CALC_CNT.OUT","PPS:LTU0:1:CBECHL_CNT.VAL")
#! Connector("PPS:LTU0:1:CBECHL/INPA",null,2260,2480,16777215,"",3)
#! Record("PPS:LTU0:1:CBECHL_CNT",2760,2337,0,1,"PPS:LTU0:1:CBECHL_CNT")
#! Field("PPS:LTU0:1:CBECHL_CNT.VAL",16777215,0,"PPS:LTU0:1:CBECHL_CNT.VAL")
#! TextBox(TB0,2180,2460,2360,2440,0,"Dialog",12,1,13369344,"Door Violation Latch PV",null)
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/bcsSoft.dbd")
#! DBDEND



record(bi, "BSOC:LTU0:1:PPSTRIP") {
  field(DESC, "BSOIC BSOBTHW01")
  field(SCAN, "1 second")
  field(DTYP, "Bk9000_KL1408")
  field(INP, "@bkhf-bsy0-pp01:4:R_DIG_IN_1")
  field(ZNAM, "TRIP")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOC:LTU0:1:PPSTRIP",2180,2132,0,1,"BSOC:LTU0:1:PPSTRIP")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/bcsSoft.dbd")
#! DBDEND



record(bi, "BSOC:LTU0:2:PPSTRIP") {
  field(DESC, "BSOIC BSOBTHW02")
  field(SCAN, "1 second")
  field(DTYP, "Bk9000_KL1408")
  field(INP, "@bkhf-bsy0-pp01:4:R_DIG_IN_2")
  field(ZNAM, "TRIP")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOC:LTU0:2:PPSTRIP",2180,2132,0,1,"BSOC:LTU0:2:PPSTRIP")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/bcsSoft.dbd")
#! DBDEND



record(bi, "BSOC:LTU0:3:PPSTRIP") {
  field(DESC, "BSOIC BSOBTHW03")
  field(SCAN, "1 second")
  field(DTYP, "Bk9000_KL1408")
  field(INP, "@bkhf-bsy0-pp01:4:R_DIG_IN_3")
  field(ZNAM, "TRIP")
  field(ONAM, "OK")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOC:LTU0:3:PPSTRIP",2180,2132,0,1,"BSOC:LTU0:3:PPSTRIP")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/bcsSoft.dbd")
#! DBDEND



record(bi, "PPS:BSY0:1:AREASECURE") {
  field(DESC, "BSY Area Secure")
  field(SCAN, "1 second")
  field(DTYP, "Bk9000_KL1408")
  field(INP, "@bkhf-bsy0-pp01:4:R_DIG_IN_4")
  field(ZNAM, "NOT_SECURE")
  field(ONAM, "SECURE")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("PPS:BSY0:1:AREASECURE",2180,2132,0,1,"PPS:BSY0:1:AREASECURE")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/bcsSoft.dbd")
#! DBDEND



record(bi, "PPS:BSY0:1:DOORSUM") {
  field(DESC, "BSY Door Closed Summary")
  field(SCAN, "1 second")
  field(DTYP, "Bk9000_KL1408")
  field(INP, "@bkhf-bsy0-pp01:4:R_DIG_IN_5")
  field(ZNAM, "NOT_CLOSED")
  field(ONAM, "CLOSED")
  field(ZSV, "MAJOR")
  field(OSV, "NO_ALARM")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("PPS:BSY0:1:DOORSUM",2180,2132,0,1,"PPS:BSY0:1:DOORSUM")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/bcsSoft.dbd")
#! DBDEND



record(bi, "PPS:BSY0:1:SEARCHREQ") {
  field(DESC, "BSY Search Required")
  field(SCAN, "1 second")
  field(DTYP, "Bk9000_KL1408")
  field(INP, "@bkhf-bsy0-pp01:4:R_DIG_IN_6")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("PPS:BSY0:1:SEARCHREQ",2180,2132,0,1,"PPS:BSY0:1:SEARCHREQ")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/bcsSoft.dbd")
#! DBDEND



record(bo, "BSOC:LTU0:1:RESET") {
  field(DESC, "BSOIC BSOBTHW01 Reset")
  field(PINI, "YES")
  field(DTYP, "Bk9000_KL2408")
  field(DOL, "1")
  field(OUT, "@bkhf-bsy0-pp01:5:W_DIG_OUT_3")
  field(ZNAM, "NO_RESET")
  field(ONAM, "RESET")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG,  "MCC")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOC:LTU0:1:RESET",2180,2119,0,1,"BSOC:LTU0:1:RESET")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/bcsSoft.dbd")
#! DBDEND



record(bo, "BSOC:LTU0:2:RESET") {
  field(DESC, "BSOIC BSOBTHW02 Reset")
  field(PINI, "YES")
  field(DTYP, "Bk9000_KL2408")
  field(DOL, "1")
  field(OUT, "@bkhf-bsy0-pp01:5:W_DIG_OUT_4")
  field(ZNAM, "NO_RESET")
  field(ONAM, "RESET")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG,  "MCC")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOC:LTU0:2:RESET",2180,2119,0,1,"BSOC:LTU0:2:RESET")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/bcsSoft.dbd")
#! DBDEND



record(bo, "BSOC:LTU0:3:RESET") {
  field(DESC, "BSOIC BSOBTHW03 Reset")
  field(PINI, "YES")
  field(DTYP, "Bk9000_KL2408")
  field(DOL, "1")
  field(OUT, "@bkhf-bsy0-pp01:5:W_DIG_OUT_5")
  field(ZNAM, "NO_RESET")
  field(ONAM, "RESET")
  field(ZSV, "NO_ALARM")
  field(OSV, "NO_ALARM")
  field(ASG,  "MCC")
}

#! Further lines contain data used by VisualDCT
#! View(2000,2115,1.0)
#! Record("BSOC:LTU0:3:RESET",2180,2119,0,1,"BSOC:LTU0:3:RESET")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBDEND



record(ai, "BSOC:LTU0:1:GAMMARAW") {
  field(DESC, "BS0BTHW01 raw analog")
  field(SCAN, "1 second")
  field(DTYP, "Bk9000_KL3408")
  field(INP, "@bkhf-bsy0-pp01:6:R_ANA_IN_1")
  field(PREC, "3")
  field(ADEL, "0.1")
  field(EGUF, "10")
  field(EGUL, "-10")
  field(HIGH, "1.7")
  field(HIHI, "5")
  field(HOPR, "10")
  field(HYST, "0")
  field(LOLO, "0")
  field(LOPR, "0")
  field(LOW, "0.1")
  field(MDEL, "0")
  field(SMOO, "0")
  field(EGU, "V")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(LINR, "LINEAR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.1)
#! Record("BSOC:LTU0:1:GAMMARAW",20,22,0,0,"BSOC:LTU0:1:GAMMARAW")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBDEND



record(ai, "BSOC:LTU0:2:GAMMARAW") {
  field(DESC, "BS0BTHW02 raw analog")
  field(SCAN, "1 second")
  field(DTYP, "Bk9000_KL3408")
  field(INP, "@bkhf-bsy0-pp01:6:R_ANA_IN_2")
  field(PREC, "3")
  field(ADEL, "0.1")
  field(EGUF, "10")
  field(EGUL, "-10")
  field(HIGH, "1.7")
  field(HIHI, "5")
  field(HOPR, "10")
  field(HYST, "0")
  field(LOLO, "0")
  field(LOPR, "0")
  field(LOW, "0.1")
  field(MDEL, "0")
  field(SMOO, "0")
  field(EGU, "V")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(LINR, "LINEAR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.1)
#! Record("BSOC:LTU0:2:GAMMARAW",20,22,0,0,"BSOC:LTU0:2:GAMMARAW")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBDEND



record(ai, "BSOC:LTU0:3:GAMMARAW") {
  field(DESC, "BS0BTHW03 raw analog")
  field(SCAN, "1 second")
  field(DTYP, "Bk9000_KL3408")
  field(INP, "@bkhf-bsy0-pp01:6:R_ANA_IN_3")
  field(PREC, "3")
  field(ADEL, "0.1")
  field(EGUF, "10")
  field(EGUL, "-10")
  field(HIGH, "1.5")
  field(HIHI, "5")
  field(HOPR, "10")
  field(HYST, "0")
  field(LOLO, "0")
  field(LOPR, "0")
  field(LOW, "0.1")
  field(MDEL, "0")
  field(SMOO, "0")
  field(EGU, "V")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(LINR, "LINEAR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.1)
#! Record("BSOC:LTU0:3:GAMMARAW",20,22,0,0,"BSOC:LTU0:3:GAMMARAW")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBDEND


record(calcout, "BSOC:LTU0:1:GAMMAACT") {
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(CALC, "B*(10^(A*C))")
  field(INPA, "BSOC:LTU0:1:GAMMARAW CPP")
  field(INPB, "1.0")
  field(EGU, "mr/hr")
  field(HOPR, "10")
  field(LOPR, "0")
  field(HIHI, "10")
  field(LOLO, "0")
  field(HIGH, "7.0")
  field(LOW, "1.5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(ADEL, "0.2")
  field(INPC, "0.6")
}

#! Further lines contain data used by VisualDCT
#! View(147,99,1.3)
#! Record("BSOC:LTU0:1:GAMMAACT",400,134,0,0,"BSOC:LTU0:1:GAMMAACT")
#! Field("BSOC:LTU0:1:GAMMAACT.INPA",16777215,1,"BSOC:LTU0:1:GAMMAACT.INPA")
#! Field("BSOC:LTU0:1:GAMMAACT.INPB",16777215,1,"BSOC:LTU0:1:GAMMAACT.INPB")
#! Field("BSOC:LTU0:1:GAMMAACT.INPC",16777215,1,"BSOC:LTU0:1:GAMMAACT.INPC")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBDEND


record(calcout, "BSOC:LTU0:2:GAMMAACT") {
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(CALC, "B*(10^(A*C))")
  field(INPA, "BSOC:LTU0:2:GAMMARAW CPP")
  field(INPB, "1.0")
  field(EGU, "mr/hr")
  field(HOPR, "10")
  field(LOPR, "0")
  field(HIHI, "10")
  field(LOLO, "0")
  field(HIGH, "7.0")
  field(LOW, "1.5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(ADEL, "0.2")
  field(INPC, "0.6")
}

#! Further lines contain data used by VisualDCT
#! View(147,99,1.3)
#! Record("BSOC:LTU0:2:GAMMAACT",400,134,0,0,"BSOC:LTU0:2:GAMMAACT")
#! Field("BSOC:LTU0:2:GAMMAACT.INPA",16777215,1,"BSOC:LTU0:2:GAMMAACT.INPA")
#! Field("BSOC:LTU0:2:GAMMAACT.INPB",16777215,1,"BSOC:LTU0:2:GAMMAACT.INPB")
#! Field("BSOC:LTU0:2:GAMMAACT.INPC",16777215,1,"BSOC:LTU0:2:GAMMAACT.INPC")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBDEND


record(calcout, "BSOC:LTU0:3:GAMMAACT") {
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(CALC, "B*(10^(A*C))")
  field(INPA, "BSOC:LTU0:3:GAMMARAW CPP")
  field(INPB, "1.0")
  field(EGU, "mr/hr")
  field(HOPR, "12")
  field(LOPR, "0")
  field(HIHI, "12")
  field(LOLO, "0")
  field(HIGH, "7.0")
  field(LOW, "1.5")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MINOR")
  field(ADEL, "0.2")
  field(INPC, "0.6")
}

#! Further lines contain data used by VisualDCT
#! View(147,99,1.3)
#! Record("BSOC:LTU0:3:GAMMAACT",400,134,0,0,"BSOC:LTU0:3:GAMMAACT")
#! Field("BSOC:LTU0:3:GAMMAACT.INPA",16777215,1,"BSOC:LTU0:3:GAMMAACT.INPA")
#! Field("BSOC:LTU0:3:GAMMAACT.INPB",16777215,1,"BSOC:LTU0:3:GAMMAACT.INPB")
#! Field("BSOC:LTU0:3:GAMMAACT.INPC",16777215,1,"BSOC:LTU0:3:GAMMAACT.INPC")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND



record(calcout, "BSOC:LTU0:1:CALCALARMSM2") {
  field(SCAN, "2 second")
  field(CALC, "(!B)*A")
  field(INPA, "BSOC:LTU0:1:CALCALARMSM1.SEVR")
  field(INPB, "BSOC:LTU0:1:MODE")
  field(OUT, "BSOC:LTU0:1:ALARMSUM PP")
  field(OOPT, "Every Time")
}

record(calcout, "BSOC:LTU0:1:CALCALARMSM1") {
  field(SCAN, "2 second")
  field(CALC, "A")
  field(INPA, "BSOC:LTU0:1:PPSTRIP MS")
  field(INPB, "BSOC:LTU0:1:GAMMAACT MS")
}


record(mbbi, "BSOC:LTU0:1:ALARMSUM") {
  field(DESC, "BSOC:LTU0:1 alarm sum")
  field(ZRVL, "0")
  field(ONVL, "1")
  field(TWVL, "2")
  field(THVL, "3")
  field(ZRST, "NO_ALARM")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(THST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
}

#! Further lines contain data used by VisualDCT
#! View(3250,3365,1.0)
#! Record("BSOC:LTU0:1:CALCALARMSM2",3720,3560,0,1,"BSOC:LTU0:1:CALCALARMSM2")
#! Field("BSOC:LTU0:1:CALCALARMSM2.INPA",16777215,0,"BSOC:LTU0:1:CALCALARMSM2.INPA")
#! Link("BSOC:LTU0:1:CALCALARMSM2.INPA","BSOC:LTU0:1:CALCALARMSM1.SEVR")
#! Field("BSOC:LTU0:1:CALCALARMSM2.INPB",16777215,1,"BSOC:LTU0:1:CALCALARMSM2.INPB")
#! Field("BSOC:LTU0:1:CALCALARMSM2.OUT",16777215,1,"BSOC:LTU0:1:CALCALARMSM2.OUT")
#! Link("BSOC:LTU0:1:CALCALARMSM2.OUT","BSOC:LTU0:1:ALARMSUM.VAL")
#! Record("BSOC:LTU0:1:CALCALARMSM1",3400,3548,0,1,"BSOC:LTU0:1:CALCALARMSM1")
#! Field("BSOC:LTU0:1:CALCALARMSM1.INPA",16777215,1,"BSOC:LTU0:1:CALCALARMSM1.INPA")
#! Field("BSOC:LTU0:1:CALCALARMSM1.INPB",16777215,1,"BSOC:LTU0:1:CALCALARMSM1.INPB")
#! Field("BSOC:LTU0:1:CALCALARMSM1.SEVR",16777215,1,"BSOC:LTU0:1:CALCALARMSM1.SEVR")
#! Record("BSOC:LTU0:1:ALARMSUM",4020,3503,0,1,"BSOC:LTU0:1:ALARMSUM")
#! Field("BSOC:LTU0:1:ALARMSUM.VAL",16777215,0,"BSOC:LTU0:1:ALARMSUM.VAL")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND



record(calcout, "BSOC:LTU0:2:CALCALARMSM2") {
  field(SCAN, "2 second")
  field(CALC, "(!B)*A")
  field(INPA, "BSOC:LTU0:2:CALCALARMSM1.SEVR")
  field(INPB, "BSOC:LTU0:2:MODE")
  field(OUT, "BSOC:LTU0:2:ALARMSUM PP")
  field(OOPT, "Every Time")
}

record(calcout, "BSOC:LTU0:2:CALCALARMSM1") {
  field(SCAN, "2 second")
  field(CALC, "A")
  field(INPA, "BSOC:LTU0:2:PPSTRIP MS")
  field(INPB, "BSOC:LTU0:2:GAMMAACT MS")
}


record(mbbi, "BSOC:LTU0:2:ALARMSUM") {
  field(DESC, "BSOC:LTU0:2 alarm sum")
  field(ZRVL, "0")
  field(ONVL, "1")
  field(TWVL, "2")
  field(THVL, "3")
  field(ZRST, "NO_ALARM")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(THST, "INVALID")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "INVALID")
}

#! Further lines contain data used by VisualDCT
#! View(3250,3365,1.0)
#! Record("BSOC:LTU0:2:CALCALARMSM2",3720,3560,0,1,"BSOC:LTU0:2:CALCALARMSM2")
#! Field("BSOC:LTU0:2:CALCALARMSM2.INPA",16777215,0,"BSOC:LTU0:2:CALCALARMSM2.INPA")
#! Link("BSOC:LTU0:2:CALCALARMSM2.INPA","BSOC:LTU0:2:CALCALARMSM1.SEVR")
#! Field("BSOC:LTU0:2:CALCALARMSM2.INPB",16777215,1,"BSOC:LTU0:2:CALCALARMSM2.INPB")
#! Field("BSOC:LTU0:2:CALCALARMSM2.OUT",16777215,1,"BSOC:LTU0:2:CALCALARMSM2.OUT")
#! Link("BSOC:LTU0:2:CALCALARMSM2.OUT","BSOC:LTU0:2:ALARMSUM.VAL")
#! Record("BSOC:LTU0:2:CALCALARMSM1",3400,3548,0,1,"BSOC:LTU0:2:CALCALARMSM1")
#! Field("BSOC:LTU0:2:CALCALARMSM1.INPA",16777215,1,"BSOC:LTU0:2:CALCALARMSM1.INPA")
#! Field("BSOC:LTU0:2:CALCALARMSM1.INPB",16777215,1,"BSOC:LTU0:2:CALCALARMSM1.INPB")
#! Field("BSOC:LTU0:2:CALCALARMSM1.SEVR",16777215,1,"BSOC:LTU0:2:CALCALARMSM1.SEVR")
#! Record("BSOC:LTU0:2:ALARMSUM",4020,3503,0,1,"BSOC:LTU0:2:ALARMSUM")
#! Field("BSOC:LTU0:2:ALARMSUM.VAL",16777215,0,"BSOC:LTU0:2:ALARMSUM.VAL")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND


record(bi, "BSOC:LTU0:3:WARNINGMODE") {
  field(DESC, "Warning bypass stat")
  field(PINI, "YES")
  field(OSV, "MINOR")
  field(ZNAM, "Active")
  field(ONAM, "Bypass")
  field(VAL, "0")
  field(FLNK, "BSOC:LTU0:3:CALCWARNING")
  field(ASG,  "MCC")
  info(autosaveFields_pass0, "VAL")
}


record(calcout, "BSOC:LTU0:3:CALCWARNING") {
  field(CALC, "(!A)*B")
  field(INPA, "BSOC:LTU0:3:WARNINGMODE")
  field(INPB, "BSOC:LTU0:3:GAMMAACT.SEVR")
  field(HIHI, "1")
  field(HHSV, "MINOR")
  field(SCAN, "2 second")
}

#! Further lines contain data used by VisualDCT
#! View(3250,3365,1.0)
#! Record("BSOC:LTU0:3:WARNINGMODE",3440,3386,0,1,"BSOC:LTU0:3:WARNINGMODE")
#! Field("BSOC:LTU0:3:WARNINGMODE.VAL",16777215,1,"BSOC:LTU0:3:WARNINGMODE.VAL")
#! Field("BSOC:LTU0:3:WARNINGMODE.FLNK",16777215,1,"BSOC:LTU0:3:WARNINGMODE.FLNK")
#! Link("BSOC:LTU0:3:WARNINGMODE.FLNK","BSOC:LTU0:3:CALCWARNING")
#! Record("BSOC:LTU0:3:CALCWARNING",3760,3400,0,0,"BSOC:LTU0:3:CALCWARNING")
#! Field("BSOC:LTU0:3:CALCWARNING.INPA",16777215,0,"BSOC:LTU0:3:CALCWARNING.INPA")
#! Link("BSOC:LTU0:3:CALCWARNING.INPA","BSOC:LTU0:3:WARNINGMODE.VAL")
#! Field("BSOC:LTU0:3:CALCWARNING.INPB",16777215,1,"BSOC:LTU0:3:CALCWARNING.INPB")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND


record(bi, "BSOIC:LTU0:2:WARNINGMODE") {
  field(DESC, "Warning bypass stat")
  field(PINI, "YES")
  field(OSV, "MINOR")
  field(ZNAM, "Active")
  field(ONAM, "Bypass")
  field(VAL, "0")
  field(FLNK, "BSOIC:LTU0:2:CALCWARNING")
  field(ASG,  "MCC")
  info(autosaveFields_pass0, "VAL")
}


record(calcout, "BSOIC:LTU0:2:CALCWARNING") {
  field(CALC, "(!A)*B")
  field(INPA, "BSOIC:LTU0:2:WARNINGMODE")
  field(INPB, "BSOIC:LTU0:2:GAMMAACT.SEVR")
  field(HIHI, "1")
  field(HHSV, "MINOR")
  field(SCAN, "2 second")
}

#! Further lines contain data used by VisualDCT
#! View(3250,3365,1.0)
#! Record("BSOIC:LTU0:2:WARNINGMODE",3440,3386,0,1,"BSOIC:LTU0:2:WARNINGMODE")
#! Field("BSOIC:LTU0:2:WARNINGMODE.VAL",16777215,1,"BSOIC:LTU0:2:WARNINGMODE.VAL")
#! Field("BSOIC:LTU0:2:WARNINGMODE.FLNK",16777215,1,"BSOIC:LTU0:2:WARNINGMODE.FLNK")
#! Link("BSOIC:LTU0:2:WARNINGMODE.FLNK","BSOIC:LTU0:2:CALCWARNING")
#! Record("BSOIC:LTU0:2:CALCWARNING",3760,3400,0,0,"BSOIC:LTU0:2:CALCWARNING")
#! Field("BSOIC:LTU0:2:CALCWARNING.INPA",16777215,0,"BSOIC:LTU0:2:CALCWARNING.INPA")
#! Link("BSOIC:LTU0:2:CALCWARNING.INPA","BSOIC:LTU0:2:WARNINGMODE.VAL")
#! Field("BSOIC:LTU0:2:CALCWARNING.INPB",16777215,1,"BSOIC:LTU0:2:CALCWARNING.INPB")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND


record(bi, "BSOIC:LTU0:3:WARNINGMODE") {
  field(DESC, "Warning bypass stat")
  field(PINI, "YES")
  field(OSV, "MINOR")
  field(ZNAM, "Active")
  field(ONAM, "Bypass")
  field(VAL, "0")
  field(FLNK, "BSOIC:LTU0:3:CALCWARNING")
  field(ASG,  "MCC")
  info(autosaveFields_pass0, "VAL")
}


record(calcout, "BSOIC:LTU0:3:CALCWARNING") {
  field(CALC, "(!A)*B")
  field(INPA, "BSOIC:LTU0:3:WARNINGMODE")
  field(INPB, "BSOIC:LTU0:3:GAMMAACT.SEVR")
  field(HIHI, "1")
  field(HHSV, "MINOR")
  field(SCAN, "2 second")
}

#! Further lines contain data used by VisualDCT
#! View(3250,3365,1.0)
#! Record("BSOIC:LTU0:3:WARNINGMODE",3440,3386,0,1,"BSOIC:LTU0:3:WARNINGMODE")
#! Field("BSOIC:LTU0:3:WARNINGMODE.VAL",16777215,1,"BSOIC:LTU0:3:WARNINGMODE.VAL")
#! Field("BSOIC:LTU0:3:WARNINGMODE.FLNK",16777215,1,"BSOIC:LTU0:3:WARNINGMODE.FLNK")
#! Link("BSOIC:LTU0:3:WARNINGMODE.FLNK","BSOIC:LTU0:3:CALCWARNING")
#! Record("BSOIC:LTU0:3:CALCWARNING",3760,3400,0,0,"BSOIC:LTU0:3:CALCWARNING")
#! Field("BSOIC:LTU0:3:CALCWARNING.INPA",16777215,0,"BSOIC:LTU0:3:CALCWARNING.INPA")
#! Link("BSOIC:LTU0:3:CALCWARNING.INPA","BSOIC:LTU0:3:WARNINGMODE.VAL")
#! Field("BSOIC:LTU0:3:CALCWARNING.INPB",16777215,1,"BSOIC:LTU0:3:CALCWARNING.INPB")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND


record(bi, "BSOIC:LTU0:8:WARNINGMODE") {
  field(DESC, "Warning bypass stat")
  field(PINI, "YES")
  field(OSV, "MINOR")
  field(ZNAM, "Active")
  field(ONAM, "Bypass")
  field(VAL, "0")
  field(FLNK, "BSOIC:LTU0:8:CALCWARNING")
  field(ASG,  "MCC")
  info(autosaveFields_pass0, "VAL")
}


record(calcout, "BSOIC:LTU0:8:CALCWARNING") {
  field(CALC, "(!A)*B")
  field(INPA, "BSOIC:LTU0:8:WARNINGMODE")
  field(INPB, "BSOIC:LTU0:8:GAMMAACT.SEVR")
  field(HIHI, "1")
  field(HHSV, "MINOR")
  field(SCAN, "2 second")
}

#! Further lines contain data used by VisualDCT
#! View(3250,3365,1.0)
#! Record("BSOIC:LTU0:8:WARNINGMODE",3440,3386,0,1,"BSOIC:LTU0:8:WARNINGMODE")
#! Field("BSOIC:LTU0:8:WARNINGMODE.VAL",16777215,1,"BSOIC:LTU0:8:WARNINGMODE.VAL")
#! Field("BSOIC:LTU0:8:WARNINGMODE.FLNK",16777215,1,"BSOIC:LTU0:8:WARNINGMODE.FLNK")
#! Link("BSOIC:LTU0:8:WARNINGMODE.FLNK","BSOIC:LTU0:8:CALCWARNING")
#! Record("BSOIC:LTU0:8:CALCWARNING",3760,3400,0,0,"BSOIC:LTU0:8:CALCWARNING")
#! Field("BSOIC:LTU0:8:CALCWARNING.INPA",16777215,0,"BSOIC:LTU0:8:CALCWARNING.INPA")
#! Link("BSOIC:LTU0:8:CALCWARNING.INPA","BSOIC:LTU0:8:WARNINGMODE.VAL")
#! Field("BSOIC:LTU0:8:CALCWARNING.INPB",16777215,1,"BSOIC:LTU0:8:CALCWARNING.INPB")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND


record(bi, "BSOIC:LTU0:9:WARNINGMODE") {
  field(DESC, "Warning bypass stat")
  field(PINI, "YES")
  field(OSV, "MINOR")
  field(ZNAM, "Active")
  field(ONAM, "Bypass")
  field(VAL, "0")
  field(FLNK, "BSOIC:LTU0:9:CALCWARNING")
  field(ASG,  "MCC")
  info(autosaveFields_pass0, "VAL")
}


record(calcout, "BSOIC:LTU0:9:CALCWARNING") {
  field(CALC, "(!A)*B")
  field(INPA, "BSOIC:LTU0:9:WARNINGMODE")
  field(INPB, "BSOIC:LTU0:9:GAMMAACT.SEVR")
  field(HIHI, "1")
  field(HHSV, "MINOR")
  field(SCAN, "2 second")
}

#! Further lines contain data used by VisualDCT
#! View(3250,3365,1.0)
#! Record("BSOIC:LTU0:9:WARNINGMODE",3440,3386,0,1,"BSOIC:LTU0:9:WARNINGMODE")
#! Field("BSOIC:LTU0:9:WARNINGMODE.VAL",16777215,1,"BSOIC:LTU0:9:WARNINGMODE.VAL")
#! Field("BSOIC:LTU0:9:WARNINGMODE.FLNK",16777215,1,"BSOIC:LTU0:9:WARNINGMODE.FLNK")
#! Link("BSOIC:LTU0:9:WARNINGMODE.FLNK","BSOIC:LTU0:9:CALCWARNING")
#! Record("BSOIC:LTU0:9:CALCWARNING",3760,3400,0,0,"BSOIC:LTU0:9:CALCWARNING")
#! Field("BSOIC:LTU0:9:CALCWARNING.INPA",16777215,0,"BSOIC:LTU0:9:CALCWARNING.INPA")
#! Link("BSOIC:LTU0:9:CALCWARNING.INPA","BSOIC:LTU0:9:WARNINGMODE.VAL")
#! Field("BSOIC:LTU0:9:CALCWARNING.INPB",16777215,1,"BSOIC:LTU0:9:CALCWARNING.INPB")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND


record(bi, "BSOIC:LTU0:6:WARNINGMODE") {
  field(DESC, "Warning bypass stat")
  field(PINI, "YES")
  field(OSV, "MINOR")
  field(ZNAM, "Active")
  field(ONAM, "Bypass")
  field(VAL, "0")
  field(FLNK, "BSOIC:LTU0:6:CALCWARNING")
  field(ASG,  "MCC")
  info(autosaveFields_pass0, "VAL")
}


record(calcout, "BSOIC:LTU0:6:CALCWARNING") {
  field(CALC, "(!A)*B")
  field(INPA, "BSOIC:LTU0:6:WARNINGMODE")
  field(INPB, "BSOIC:LTU0:6:GAMMAACT.SEVR")
  field(HIHI, "1")
  field(HHSV, "MINOR")
  field(SCAN, "2 second")
}

#! Further lines contain data used by VisualDCT
#! View(3250,3365,1.0)
#! Record("BSOIC:LTU0:6:WARNINGMODE",3440,3386,0,1,"BSOIC:LTU0:6:WARNINGMODE")
#! Field("BSOIC:LTU0:6:WARNINGMODE.VAL",16777215,1,"BSOIC:LTU0:6:WARNINGMODE.VAL")
#! Field("BSOIC:LTU0:6:WARNINGMODE.FLNK",16777215,1,"BSOIC:LTU0:6:WARNINGMODE.FLNK")
#! Link("BSOIC:LTU0:6:WARNINGMODE.FLNK","BSOIC:LTU0:6:CALCWARNING")
#! Record("BSOIC:LTU0:6:CALCWARNING",3760,3400,0,0,"BSOIC:LTU0:6:CALCWARNING")
#! Field("BSOIC:LTU0:6:CALCWARNING.INPA",16777215,0,"BSOIC:LTU0:6:CALCWARNING.INPA")
#! Link("BSOIC:LTU0:6:CALCWARNING.INPA","BSOIC:LTU0:6:WARNINGMODE.VAL")
#! Field("BSOIC:LTU0:6:CALCWARNING.INPB",16777215,1,"BSOIC:LTU0:6:CALCWARNING.INPB")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND


record(bi, "BSOC:LTU0:1:WARNINGMODE") {
  field(DESC, "Warning bypass stat")
  field(PINI, "YES")
  field(OSV, "MINOR")
  field(ZNAM, "Active")
  field(ONAM, "Bypass")
  field(FLNK, "BSOC:LTU0:1:CALCWARNING")
  field(VAL, "0")
  field(ASG,  "MCC")
}

# Note: autobypass when autobypass PV is 0
record(calcout, "BSOC:LTU0:1:CALCWARNING") {
  field(CALC, "(!A)*B*(!C)")
  field(INPA, "BSOC:LTU0:1:WARNINGMODE")
  field(INPB, "BSOC:LTU0:1:GAMMAACT.SEVR CPP")
  field(INPC, "BSOC:LTU0:1:MODE CPP")
  field(SCAN, "2 second")
}

#! Further lines contain data used by VisualDCT
#! View(3250,3365,1.0)
#! Record("BSOC:LTU0:1:WARNINGMODE",3440,3386,0,1,"BSOC:LTU0:1:WARNINGMODE")
#! Field("BSOC:LTU0:1:WARNINGMODE.VAL",16777215,1,"BSOC:LTU0:1:WARNINGMODE.VAL")
#! Field("BSOC:LTU0:1:WARNINGMODE.FLNK",16777215,1,"BSOC:LTU0:1:WARNINGMODE.FLNK")
#! Link("BSOC:LTU0:1:WARNINGMODE.FLNK","BSOC:LTU0:1:CALCWARNING")
#! Record("BSOC:LTU0:1:CALCWARNING",3760,3414,0,0,"BSOC:LTU0:1:CALCWARNING")
#! Field("BSOC:LTU0:1:CALCWARNING.INPA",16777215,0,"BSOC:LTU0:1:CALCWARNING.INPA")
#! Link("BSOC:LTU0:1:CALCWARNING.INPA","BSOC:LTU0:1:WARNINGMODE.VAL")
#! Field("BSOC:LTU0:1:CALCWARNING.INPB",16777215,1,"BSOC:LTU0:1:CALCWARNING.INPB")
#! Field("BSOC:LTU0:1:CALCWARNING.INPC",16777215,1,"BSOC:LTU0:1:CALCWARNING.INPC")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND


record(bi, "BSOC:LTU0:2:WARNINGMODE") {
  field(DESC, "Warning bypass stat")
  field(PINI, "YES")
  field(OSV, "MINOR")
  field(ZNAM, "Active")
  field(ONAM, "Bypass")
  field(FLNK, "BSOC:LTU0:2:CALCWARNING")
  field(VAL, "0")
  field(ASG,  "MCC")
}

# Note: autobypass when autobypass PV is 0
record(calcout, "BSOC:LTU0:2:CALCWARNING") {
  field(CALC, "(!A)*B*(!C)")
  field(INPA, "BSOC:LTU0:2:WARNINGMODE")
  field(INPB, "BSOC:LTU0:2:GAMMAACT.SEVR CPP")
  field(INPC, "BSOC:LTU0:2:MODE CPP")
  field(SCAN, "2 second")
}

#! Further lines contain data used by VisualDCT
#! View(3250,3365,1.0)
#! Record("BSOC:LTU0:2:WARNINGMODE",3440,3386,0,1,"BSOC:LTU0:2:WARNINGMODE")
#! Field("BSOC:LTU0:2:WARNINGMODE.VAL",16777215,1,"BSOC:LTU0:2:WARNINGMODE.VAL")
#! Field("BSOC:LTU0:2:WARNINGMODE.FLNK",16777215,1,"BSOC:LTU0:2:WARNINGMODE.FLNK")
#! Link("BSOC:LTU0:2:WARNINGMODE.FLNK","BSOC:LTU0:2:CALCWARNING")
#! Record("BSOC:LTU0:2:CALCWARNING",3760,3414,0,0,"BSOC:LTU0:2:CALCWARNING")
#! Field("BSOC:LTU0:2:CALCWARNING.INPA",16777215,0,"BSOC:LTU0:2:CALCWARNING.INPA")
#! Link("BSOC:LTU0:2:CALCWARNING.INPA","BSOC:LTU0:2:WARNINGMODE.VAL")
#! Field("BSOC:LTU0:2:CALCWARNING.INPB",16777215,1,"BSOC:LTU0:2:CALCWARNING.INPB")
#! Field("BSOC:LTU0:2:CALCWARNING.INPC",16777215,1,"BSOC:LTU0:2:CALCWARNING.INPC")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND


record(bi, "BTM:LTU0:172:WARNINGMODE") {
  field(DESC, "Warning bypass stat")
  field(PINI, "YES")
  field(OSV, "MINOR")
  field(ZNAM, "Active")
  field(ONAM, "Bypass")
  field(VAL, "0")
  field(FLNK, "BTM:LTU0:172:CALCWARNING")
  field(ASG,  "MCC")
  info(autosaveFields_pass0, "VAL")
}


record(calcout, "BTM:LTU0:172:CALCWARNING") {
  field(CALC, "(!A)*B")
  field(INPA, "BTM:LTU0:172:WARNINGMODE")
  field(INPB, "BTM:LTU0:172:PPSPRSSR.SEVR")
  field(HIHI, "1")
  field(HHSV, "MINOR")
  field(SCAN, "2 second")
}

#! Further lines contain data used by VisualDCT
#! View(3250,3365,1.0)
#! Record("BTM:LTU0:172:WARNINGMODE",3440,3386,0,1,"BTM:LTU0:172:WARNINGMODE")
#! Field("BTM:LTU0:172:WARNINGMODE.VAL",16777215,1,"BTM:LTU0:172:WARNINGMODE.VAL")
#! Field("BTM:LTU0:172:WARNINGMODE.FLNK",16777215,1,"BTM:LTU0:172:WARNINGMODE.FLNK")
#! Link("BTM:LTU0:172:WARNINGMODE.FLNK","BTM:LTU0:172:CALCWARNING")
#! Record("BTM:LTU0:172:CALCWARNING",3760,3400,0,0,"BTM:LTU0:172:CALCWARNING")
#! Field("BTM:LTU0:172:CALCWARNING.INPA",16777215,0,"BTM:LTU0:172:CALCWARNING.INPA")
#! Link("BTM:LTU0:172:CALCWARNING.INPA","BTM:LTU0:172:WARNINGMODE.VAL")
#! Field("BTM:LTU0:172:CALCWARNING.INPB",16777215,1,"BTM:LTU0:172:CALCWARNING.INPB")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND


record(bi, "BTM:LTU0:226:WARNINGMODE") {
  field(DESC, "Warning bypass stat")
  field(PINI, "YES")
  field(OSV, "MINOR")
  field(ZNAM, "Active")
  field(ONAM, "Bypass")
  field(VAL, "0")
  field(FLNK, "BTM:LTU0:226:CALCWARNING")
  field(ASG,  "MCC")
  info(autosaveFields_pass0, "VAL")
}


record(calcout, "BTM:LTU0:226:CALCWARNING") {
  field(CALC, "(!A)*B")
  field(INPA, "BTM:LTU0:226:WARNINGMODE")
  field(INPB, "BTM:LTU0:226:PPSPRSSR.SEVR")
  field(HIHI, "1")
  field(HHSV, "MINOR")
  field(SCAN, "2 second")
}

#! Further lines contain data used by VisualDCT
#! View(3250,3365,1.0)
#! Record("BTM:LTU0:226:WARNINGMODE",3440,3386,0,1,"BTM:LTU0:226:WARNINGMODE")
#! Field("BTM:LTU0:226:WARNINGMODE.VAL",16777215,1,"BTM:LTU0:226:WARNINGMODE.VAL")
#! Field("BTM:LTU0:226:WARNINGMODE.FLNK",16777215,1,"BTM:LTU0:226:WARNINGMODE.FLNK")
#! Link("BTM:LTU0:226:WARNINGMODE.FLNK","BTM:LTU0:226:CALCWARNING")
#! Record("BTM:LTU0:226:CALCWARNING",3760,3400,0,0,"BTM:LTU0:226:CALCWARNING")
#! Field("BTM:LTU0:226:CALCWARNING.INPA",16777215,0,"BTM:LTU0:226:CALCWARNING.INPA")
#! Link("BTM:LTU0:226:CALCWARNING.INPA","BTM:LTU0:226:WARNINGMODE.VAL")
#! Field("BTM:LTU0:226:CALCWARNING.INPB",16777215,1,"BTM:LTU0:226:CALCWARNING.INPB")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND


record(bi, "BTM:LTU0:300:WARNINGMODE") {
  field(DESC, "Warning bypass stat")
  field(PINI, "YES")
  field(OSV, "MINOR")
  field(ZNAM, "Active")
  field(ONAM, "Bypass")
  field(VAL, "0")
  field(FLNK, "BTM:LTU0:300:CALCWARNING")
  field(ASG,  "MCC")
  info(autosaveFields_pass0, "VAL")
}


record(calcout, "BTM:LTU0:300:CALCWARNING") {
  field(CALC, "(!A)*B")
  field(INPA, "BTM:LTU0:300:WARNINGMODE")
  field(INPB, "BTM:LTU0:300:PPSPRSSR.SEVR")
  field(HIHI, "1")
  field(HHSV, "MINOR")
  field(SCAN, "2 second")
}

#! Further lines contain data used by VisualDCT
#! View(3250,3365,1.0)
#! Record("BTM:LTU0:300:WARNINGMODE",3440,3386,0,1,"BTM:LTU0:300:WARNINGMODE")
#! Field("BTM:LTU0:300:WARNINGMODE.VAL",16777215,1,"BTM:LTU0:300:WARNINGMODE.VAL")
#! Field("BTM:LTU0:300:WARNINGMODE.FLNK",16777215,1,"BTM:LTU0:300:WARNINGMODE.FLNK")
#! Link("BTM:LTU0:300:WARNINGMODE.FLNK","BTM:LTU0:300:CALCWARNING")
#! Record("BTM:LTU0:300:CALCWARNING",3760,3400,0,0,"BTM:LTU0:300:CALCWARNING")
#! Field("BTM:LTU0:300:CALCWARNING.INPA",16777215,0,"BTM:LTU0:300:CALCWARNING.INPA")
#! Link("BTM:LTU0:300:CALCWARNING.INPA","BTM:LTU0:300:WARNINGMODE.VAL")
#! Field("BTM:LTU0:300:CALCWARNING.INPB",16777215,1,"BTM:LTU0:300:CALCWARNING.INPB")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND


record(bi, "BTM:LTU0:440:WARNINGMODE") {
  field(DESC, "Warning bypass stat")
  field(PINI, "YES")
  field(OSV, "MINOR")
  field(ZNAM, "Active")
  field(ONAM, "Bypass")
  field(VAL, "0")
  field(FLNK, "BTM:LTU0:440:CALCWARNING")
  field(ASG,  "MCC")
  info(autosaveFields_pass0, "VAL")
}


record(calcout, "BTM:LTU0:440:CALCWARNING") {
  field(CALC, "(!A)*B")
  field(INPA, "BTM:LTU0:440:WARNINGMODE")
  field(INPB, "BTM:LTU0:440:PPSPRSSR.SEVR")
  field(HIHI, "1")
  field(HHSV, "MINOR")
  field(SCAN, "2 second")
}

#! Further lines contain data used by VisualDCT
#! View(3250,3365,1.0)
#! Record("BTM:LTU0:440:WARNINGMODE",3440,3386,0,1,"BTM:LTU0:440:WARNINGMODE")
#! Field("BTM:LTU0:440:WARNINGMODE.VAL",16777215,1,"BTM:LTU0:440:WARNINGMODE.VAL")
#! Field("BTM:LTU0:440:WARNINGMODE.FLNK",16777215,1,"BTM:LTU0:440:WARNINGMODE.FLNK")
#! Link("BTM:LTU0:440:WARNINGMODE.FLNK","BTM:LTU0:440:CALCWARNING")
#! Record("BTM:LTU0:440:CALCWARNING",3760,3400,0,0,"BTM:LTU0:440:CALCWARNING")
#! Field("BTM:LTU0:440:CALCWARNING.INPA",16777215,0,"BTM:LTU0:440:CALCWARNING.INPA")
#! Link("BTM:LTU0:440:CALCWARNING.INPA","BTM:LTU0:440:WARNINGMODE.VAL")
#! Field("BTM:LTU0:440:CALCWARNING.INPB",16777215,1,"BTM:LTU0:440:CALCWARNING.INPB")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND


record(bi, "BTM:LTU0:507:WARNINGMODE") {
  field(DESC, "Warning bypass stat")
  field(PINI, "YES")
  field(OSV, "MINOR")
  field(ZNAM, "Active")
  field(ONAM, "Bypass")
  field(VAL, "0")
  field(FLNK, "BTM:LTU0:507:CALCWARNING")
  field(ASG,  "MCC")
  info(autosaveFields_pass0, "VAL")
}


record(calcout, "BTM:LTU0:507:CALCWARNING") {
  field(CALC, "(!A)*B")
  field(INPA, "BTM:LTU0:507:WARNINGMODE")
  field(INPB, "BTM:LTU0:507:PPSPRSSR.SEVR")
  field(HIHI, "1")
  field(HHSV, "MINOR")
  field(SCAN, "2 second")
}

#! Further lines contain data used by VisualDCT
#! View(3250,3365,1.0)
#! Record("BTM:LTU0:507:WARNINGMODE",3440,3386,0,1,"BTM:LTU0:507:WARNINGMODE")
#! Field("BTM:LTU0:507:WARNINGMODE.VAL",16777215,1,"BTM:LTU0:507:WARNINGMODE.VAL")
#! Field("BTM:LTU0:507:WARNINGMODE.FLNK",16777215,1,"BTM:LTU0:507:WARNINGMODE.FLNK")
#! Link("BTM:LTU0:507:WARNINGMODE.FLNK","BTM:LTU0:507:CALCWARNING")
#! Record("BTM:LTU0:507:CALCWARNING",3760,3400,0,0,"BTM:LTU0:507:CALCWARNING")
#! Field("BTM:LTU0:507:CALCWARNING.INPA",16777215,0,"BTM:LTU0:507:CALCWARNING.INPA")
#! Link("BTM:LTU0:507:CALCWARNING.INPA","BTM:LTU0:507:WARNINGMODE.VAL")
#! Field("BTM:LTU0:507:CALCWARNING.INPB",16777215,1,"BTM:LTU0:507:CALCWARNING.INPB")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND


record(bi, "BTM:LTU0:645:WARNINGMODE") {
  field(DESC, "Warning bypass stat")
  field(PINI, "YES")
  field(OSV, "MINOR")
  field(ZNAM, "Active")
  field(ONAM, "Bypass")
  field(VAL, "0")
  field(FLNK, "BTM:LTU0:645:CALCWARNING")
  field(ASG,  "MCC")
  info(autosaveFields_pass0, "VAL")
}


record(calcout, "BTM:LTU0:645:CALCWARNING") {
  field(CALC, "(!A)*B")
  field(INPA, "BTM:LTU0:645:WARNINGMODE")
  field(INPB, "BTM:LTU0:645:PPSPRSSR.SEVR")
  field(HIHI, "1")
  field(HHSV, "MINOR")
  field(SCAN, "2 second")
}

#! Further lines contain data used by VisualDCT
#! View(3250,3365,1.0)
#! Record("BTM:LTU0:645:WARNINGMODE",3440,3386,0,1,"BTM:LTU0:645:WARNINGMODE")
#! Field("BTM:LTU0:645:WARNINGMODE.VAL",16777215,1,"BTM:LTU0:645:WARNINGMODE.VAL")
#! Field("BTM:LTU0:645:WARNINGMODE.FLNK",16777215,1,"BTM:LTU0:645:WARNINGMODE.FLNK")
#! Link("BTM:LTU0:645:WARNINGMODE.FLNK","BTM:LTU0:645:CALCWARNING")
#! Record("BTM:LTU0:645:CALCWARNING",3760,3400,0,0,"BTM:LTU0:645:CALCWARNING")
#! Field("BTM:LTU0:645:CALCWARNING.INPA",16777215,0,"BTM:LTU0:645:CALCWARNING.INPA")
#! Link("BTM:LTU0:645:CALCWARNING.INPA","BTM:LTU0:645:WARNINGMODE.VAL")
#! Field("BTM:LTU0:645:CALCWARNING.INPB",16777215,1,"BTM:LTU0:645:CALCWARNING.INPB")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND


record(bi, "BTM:LTU0:648:WARNINGMODE") {
  field(DESC, "Warning bypass stat")
  field(PINI, "YES")
  field(OSV, "MINOR")
  field(ZNAM, "Active")
  field(ONAM, "Bypass")
  field(VAL, "0")
  field(FLNK, "BTM:LTU0:648:CALCWARNING")
  field(ASG,  "MCC")
  info(autosaveFields_pass0, "VAL")
}


record(calcout, "BTM:LTU0:648:CALCWARNING") {
  field(CALC, "(!A)*B")
  field(INPA, "BTM:LTU0:648:WARNINGMODE")
  field(INPB, "BTM:LTU0:648:PPSPRSSR.SEVR")
  field(HIHI, "1")
  field(HHSV, "MINOR")
  field(SCAN, "2 second")
}

#! Further lines contain data used by VisualDCT
#! View(3250,3365,1.0)
#! Record("BTM:LTU0:648:WARNINGMODE",3440,3386,0,1,"BTM:LTU0:648:WARNINGMODE")
#! Field("BTM:LTU0:648:WARNINGMODE.VAL",16777215,1,"BTM:LTU0:648:WARNINGMODE.VAL")
#! Field("BTM:LTU0:648:WARNINGMODE.FLNK",16777215,1,"BTM:LTU0:648:WARNINGMODE.FLNK")
#! Link("BTM:LTU0:648:WARNINGMODE.FLNK","BTM:LTU0:648:CALCWARNING")
#! Record("BTM:LTU0:648:CALCWARNING",3760,3400,0,0,"BTM:LTU0:648:CALCWARNING")
#! Field("BTM:LTU0:648:CALCWARNING.INPA",16777215,0,"BTM:LTU0:648:CALCWARNING.INPA")
#! Link("BTM:LTU0:648:CALCWARNING.INPA","BTM:LTU0:648:WARNINGMODE.VAL")
#! Field("BTM:LTU0:648:CALCWARNING.INPB",16777215,1,"BTM:LTU0:648:CALCWARNING.INPB")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND


record(bi, "BTM:LTU0:687:WARNINGMODE") {
  field(DESC, "Warning bypass stat")
  field(PINI, "YES")
  field(OSV, "MINOR")
  field(ZNAM, "Active")
  field(ONAM, "Bypass")
  field(VAL, "0")
  field(FLNK, "BTM:LTU0:687:CALCWARNING")
  field(ASG,  "MCC")
  info(autosaveFields_pass0, "VAL")
}


record(calcout, "BTM:LTU0:687:CALCWARNING") {
  field(CALC, "(!A)*B")
  field(INPA, "BTM:LTU0:687:WARNINGMODE")
  field(INPB, "BTM:LTU0:687:PPSPRSSR.SEVR")
  field(HIHI, "1")
  field(HHSV, "MINOR")
  field(SCAN, "2 second")
}

#! Further lines contain data used by VisualDCT
#! View(3250,3365,1.0)
#! Record("BTM:LTU0:687:WARNINGMODE",3440,3386,0,1,"BTM:LTU0:687:WARNINGMODE")
#! Field("BTM:LTU0:687:WARNINGMODE.VAL",16777215,1,"BTM:LTU0:687:WARNINGMODE.VAL")
#! Field("BTM:LTU0:687:WARNINGMODE.FLNK",16777215,1,"BTM:LTU0:687:WARNINGMODE.FLNK")
#! Link("BTM:LTU0:687:WARNINGMODE.FLNK","BTM:LTU0:687:CALCWARNING")
#! Record("BTM:LTU0:687:CALCWARNING",3760,3400,0,0,"BTM:LTU0:687:CALCWARNING")
#! Field("BTM:LTU0:687:CALCWARNING.INPA",16777215,0,"BTM:LTU0:687:CALCWARNING.INPA")
#! Link("BTM:LTU0:687:CALCWARNING.INPA","BTM:LTU0:687:WARNINGMODE.VAL")
#! Field("BTM:LTU0:687:CALCWARNING.INPB",16777215,1,"BTM:LTU0:687:CALCWARNING.INPB")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND


record(bi, "BTM:LTU0:717:WARNINGMODE") {
  field(DESC, "Warning bypass stat")
  field(PINI, "YES")
  field(OSV, "MINOR")
  field(ZNAM, "Active")
  field(ONAM, "Bypass")
  field(VAL, "0")
  field(FLNK, "BTM:LTU0:717:CALCWARNING")
  field(ASG,  "MCC")
  info(autosaveFields_pass0, "VAL")
}


record(calcout, "BTM:LTU0:717:CALCWARNING") {
  field(CALC, "(!A)*B")
  field(INPA, "BTM:LTU0:717:WARNINGMODE")
  field(INPB, "BTM:LTU0:717:PPSPRSSR.SEVR")
  field(HIHI, "1")
  field(HHSV, "MINOR")
  field(SCAN, "2 second")
}

#! Further lines contain data used by VisualDCT
#! View(3250,3365,1.0)
#! Record("BTM:LTU0:717:WARNINGMODE",3440,3386,0,1,"BTM:LTU0:717:WARNINGMODE")
#! Field("BTM:LTU0:717:WARNINGMODE.VAL",16777215,1,"BTM:LTU0:717:WARNINGMODE.VAL")
#! Field("BTM:LTU0:717:WARNINGMODE.FLNK",16777215,1,"BTM:LTU0:717:WARNINGMODE.FLNK")
#! Link("BTM:LTU0:717:WARNINGMODE.FLNK","BTM:LTU0:717:CALCWARNING")
#! Record("BTM:LTU0:717:CALCWARNING",3760,3400,0,0,"BTM:LTU0:717:CALCWARNING")
#! Field("BTM:LTU0:717:CALCWARNING.INPA",16777215,0,"BTM:LTU0:717:CALCWARNING.INPA")
#! Link("BTM:LTU0:717:CALCWARNING.INPA","BTM:LTU0:717:WARNINGMODE.VAL")
#! Field("BTM:LTU0:717:CALCWARNING.INPB",16777215,1,"BTM:LTU0:717:CALCWARNING.INPB")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND


record(bi, "BTM:DMP0:451:WARNINGMODE") {
  field(DESC, "Warning bypass stat")
  field(PINI, "YES")
  field(OSV, "MINOR")
  field(ZNAM, "Active")
  field(ONAM, "Bypass")
  field(VAL, "0")
  field(FLNK, "BTM:DMP0:451:CALCWARNING")
  field(ASG,  "MCC")
  info(autosaveFields_pass0, "VAL")
}


record(calcout, "BTM:DMP0:451:CALCWARNING") {
  field(CALC, "(!A)*B")
  field(INPA, "BTM:DMP0:451:WARNINGMODE")
  field(INPB, "BTM:DMP0:451:PPSPRSSR.SEVR")
  field(HIHI, "1")
  field(HHSV, "MINOR")
  field(SCAN, "2 second")
}

#! Further lines contain data used by VisualDCT
#! View(3250,3365,1.0)
#! Record("BTM:DMP0:451:WARNINGMODE",3440,3386,0,1,"BTM:DMP0:451:WARNINGMODE")
#! Field("BTM:DMP0:451:WARNINGMODE.VAL",16777215,1,"BTM:DMP0:451:WARNINGMODE.VAL")
#! Field("BTM:DMP0:451:WARNINGMODE.FLNK",16777215,1,"BTM:DMP0:451:WARNINGMODE.FLNK")
#! Link("BTM:DMP0:451:WARNINGMODE.FLNK","BTM:DMP0:451:CALCWARNING")
#! Record("BTM:DMP0:451:CALCWARNING",3760,3400,0,0,"BTM:DMP0:451:CALCWARNING")
#! Field("BTM:DMP0:451:CALCWARNING.INPA",16777215,0,"BTM:DMP0:451:CALCWARNING.INPA")
#! Link("BTM:DMP0:451:CALCWARNING.INPA","BTM:DMP0:451:WARNINGMODE.VAL")
#! Field("BTM:DMP0:451:CALCWARNING.INPB",16777215,1,"BTM:DMP0:451:CALCWARNING.INPB")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND


record(bi, "BTM:DMP0:699:WARNINGMODE") {
  field(DESC, "Warning bypass stat")
  field(PINI, "YES")
  field(OSV, "MINOR")
  field(ZNAM, "Active")
  field(ONAM, "Bypass")
  field(VAL, "0")
  field(FLNK, "BTM:DMP0:699:CALCWARNING")
  field(ASG,  "MCC")
  info(autosaveFields_pass0, "VAL")
}


record(calcout, "BTM:DMP0:699:CALCWARNING") {
  field(CALC, "(!A)*B")
  field(INPA, "BTM:DMP0:699:WARNINGMODE")
  field(INPB, "BTM:DMP0:699:PPSPRSSR.SEVR")
  field(HIHI, "1")
  field(HHSV, "MINOR")
  field(SCAN, "2 second")
}

#! Further lines contain data used by VisualDCT
#! View(3250,3365,1.0)
#! Record("BTM:DMP0:699:WARNINGMODE",3440,3386,0,1,"BTM:DMP0:699:WARNINGMODE")
#! Field("BTM:DMP0:699:WARNINGMODE.VAL",16777215,1,"BTM:DMP0:699:WARNINGMODE.VAL")
#! Field("BTM:DMP0:699:WARNINGMODE.FLNK",16777215,1,"BTM:DMP0:699:WARNINGMODE.FLNK")
#! Link("BTM:DMP0:699:WARNINGMODE.FLNK","BTM:DMP0:699:CALCWARNING")
#! Record("BTM:DMP0:699:CALCWARNING",3760,3400,0,0,"BTM:DMP0:699:CALCWARNING")
#! Field("BTM:DMP0:699:CALCWARNING.INPA",16777215,0,"BTM:DMP0:699:CALCWARNING.INPA")
#! Link("BTM:DMP0:699:CALCWARNING.INPA","BTM:DMP0:699:WARNINGMODE.VAL")
#! Field("BTM:DMP0:699:CALCWARNING.INPB",16777215,1,"BTM:DMP0:699:CALCWARNING.INPB")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND


record(bi, "BTM:DMP0:711:WARNINGMODE") {
  field(DESC, "Warning bypass stat")
  field(PINI, "YES")
  field(OSV, "MINOR")
  field(ZNAM, "Active")
  field(ONAM, "Bypass")
  field(VAL, "0")
  field(FLNK, "BTM:DMP0:711:CALCWARNING")
  field(ASG,  "MCC")
  info(autosaveFields_pass0, "VAL")
}


record(calcout, "BTM:DMP0:711:CALCWARNING") {
  field(CALC, "(!A)*B")
  field(INPA, "BTM:DMP0:711:WARNINGMODE")
  field(INPB, "BTM:DMP0:711:PPSPRSSR.SEVR")
  field(HIHI, "1")
  field(HHSV, "MINOR")
  field(SCAN, "2 second")
}

#! Further lines contain data used by VisualDCT
#! View(3250,3365,1.0)
#! Record("BTM:DMP0:711:WARNINGMODE",3440,3386,0,1,"BTM:DMP0:711:WARNINGMODE")
#! Field("BTM:DMP0:711:WARNINGMODE.VAL",16777215,1,"BTM:DMP0:711:WARNINGMODE.VAL")
#! Field("BTM:DMP0:711:WARNINGMODE.FLNK",16777215,1,"BTM:DMP0:711:WARNINGMODE.FLNK")
#! Link("BTM:DMP0:711:WARNINGMODE.FLNK","BTM:DMP0:711:CALCWARNING")
#! Record("BTM:DMP0:711:CALCWARNING",3760,3400,0,0,"BTM:DMP0:711:CALCWARNING")
#! Field("BTM:DMP0:711:CALCWARNING.INPA",16777215,0,"BTM:DMP0:711:CALCWARNING.INPA")
#! Link("BTM:DMP0:711:CALCWARNING.INPA","BTM:DMP0:711:WARNINGMODE.VAL")
#! Field("BTM:DMP0:711:CALCWARNING.INPB",16777215,1,"BTM:DMP0:711:CALCWARNING.INPB")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND


record(bi, "BTM:DMP0:741:WARNINGMODE") {
  field(DESC, "Warning bypass stat")
  field(PINI, "YES")
  field(OSV, "MINOR")
  field(ZNAM, "Active")
  field(ONAM, "Bypass")
  field(VAL, "0")
  field(FLNK, "BTM:DMP0:741:CALCWARNING")
  field(ASG,  "MCC")
  info(autosaveFields_pass0, "VAL")
}


record(calcout, "BTM:DMP0:741:CALCWARNING") {
  field(CALC, "(!A)*B")
  field(INPA, "BTM:DMP0:741:WARNINGMODE")
  field(INPB, "BTM:DMP0:741:PPSPRSSR.SEVR")
  field(HIHI, "1")
  field(HHSV, "MINOR")
  field(SCAN, "2 second")
}

#! Further lines contain data used by VisualDCT
#! View(3250,3365,1.0)
#! Record("BTM:DMP0:741:WARNINGMODE",3440,3386,0,1,"BTM:DMP0:741:WARNINGMODE")
#! Field("BTM:DMP0:741:WARNINGMODE.VAL",16777215,1,"BTM:DMP0:741:WARNINGMODE.VAL")
#! Field("BTM:DMP0:741:WARNINGMODE.FLNK",16777215,1,"BTM:DMP0:741:WARNINGMODE.FLNK")
#! Link("BTM:DMP0:741:WARNINGMODE.FLNK","BTM:DMP0:741:CALCWARNING")
#! Record("BTM:DMP0:741:CALCWARNING",3760,3400,0,0,"BTM:DMP0:741:CALCWARNING")
#! Field("BTM:DMP0:741:CALCWARNING.INPA",16777215,0,"BTM:DMP0:741:CALCWARNING.INPA")
#! Link("BTM:DMP0:741:CALCWARNING.INPA","BTM:DMP0:741:WARNINGMODE.VAL")
#! Field("BTM:DMP0:741:CALCWARNING.INPB",16777215,1,"BTM:DMP0:741:CALCWARNING.INPB")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND


record(bi, "BTM:DMP0:771:WARNINGMODE") {
  field(DESC, "Warning bypass stat")
  field(PINI, "YES")
  field(OSV, "MINOR")
  field(ZNAM, "Active")
  field(ONAM, "Bypass")
  field(VAL, "0")
  field(FLNK, "BTM:DMP0:771:CALCWARNING")
  field(ASG,  "MCC")
  info(autosaveFields_pass0, "VAL")
}


record(calcout, "BTM:DMP0:771:CALCWARNING") {
  field(CALC, "(!A)*B")
  field(INPA, "BTM:DMP0:771:WARNINGMODE")
  field(INPB, "BTM:DMP0:771:PPSPRSSR.SEVR")
  field(HIHI, "1")
  field(HHSV, "MINOR")
  field(SCAN, "2 second")
}

#! Further lines contain data used by VisualDCT
#! View(3250,3365,1.0)
#! Record("BTM:DMP0:771:WARNINGMODE",3440,3386,0,1,"BTM:DMP0:771:WARNINGMODE")
#! Field("BTM:DMP0:771:WARNINGMODE.VAL",16777215,1,"BTM:DMP0:771:WARNINGMODE.VAL")
#! Field("BTM:DMP0:771:WARNINGMODE.FLNK",16777215,1,"BTM:DMP0:771:WARNINGMODE.FLNK")
#! Link("BTM:DMP0:771:WARNINGMODE.FLNK","BTM:DMP0:771:CALCWARNING")
#! Record("BTM:DMP0:771:CALCWARNING",3760,3400,0,0,"BTM:DMP0:771:CALCWARNING")
#! Field("BTM:DMP0:771:CALCWARNING.INPA",16777215,0,"BTM:DMP0:771:CALCWARNING.INPA")
#! Link("BTM:DMP0:771:CALCWARNING.INPA","BTM:DMP0:771:WARNINGMODE.VAL")
#! Field("BTM:DMP0:771:CALCWARNING.INPB",16777215,1,"BTM:DMP0:771:CALCWARNING.INPB")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND


record(bi, "BTM:DMP0:801:WARNINGMODE") {
  field(DESC, "Warning bypass stat")
  field(PINI, "YES")
  field(OSV, "MINOR")
  field(ZNAM, "Active")
  field(ONAM, "Bypass")
  field(VAL, "0")
  field(FLNK, "BTM:DMP0:801:CALCWARNING")
  field(ASG,  "MCC")
  info(autosaveFields_pass0, "VAL")
}


record(calcout, "BTM:DMP0:801:CALCWARNING") {
  field(CALC, "(!A)*B")
  field(INPA, "BTM:DMP0:801:WARNINGMODE")
  field(INPB, "BTM:DMP0:801:PPSPRSSR.SEVR")
  field(HIHI, "1")
  field(HHSV, "MINOR")
  field(SCAN, "2 second")
}

#! Further lines contain data used by VisualDCT
#! View(3250,3365,1.0)
#! Record("BTM:DMP0:801:WARNINGMODE",3440,3386,0,1,"BTM:DMP0:801:WARNINGMODE")
#! Field("BTM:DMP0:801:WARNINGMODE.VAL",16777215,1,"BTM:DMP0:801:WARNINGMODE.VAL")
#! Field("BTM:DMP0:801:WARNINGMODE.FLNK",16777215,1,"BTM:DMP0:801:WARNINGMODE.FLNK")
#! Link("BTM:DMP0:801:WARNINGMODE.FLNK","BTM:DMP0:801:CALCWARNING")
#! Record("BTM:DMP0:801:CALCWARNING",3760,3400,0,0,"BTM:DMP0:801:CALCWARNING")
#! Field("BTM:DMP0:801:CALCWARNING.INPA",16777215,0,"BTM:DMP0:801:CALCWARNING.INPA")
#! Link("BTM:DMP0:801:CALCWARNING.INPA","BTM:DMP0:801:WARNINGMODE.VAL")
#! Field("BTM:DMP0:801:CALCWARNING.INPB",16777215,1,"BTM:DMP0:801:CALCWARNING.INPB")
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/ppsIoc.dbd")
#! DBDEND


record(bi, "BTM:DMP0:999:WARNINGMODE") {
  field(DESC, "Warning bypass stat")
  field(PINI, "YES")
  field(OSV, "MINOR")
  field(ZNAM, "Active")
  field(ONAM, "Bypass")
  field(VAL, "0")
  field(FLNK, "BTM:DMP0:999:CALCWARNING")
  field(ASG,  "MCC")
  info(autosaveFields_pass0, "VAL")
}


record(calcout, "BTM:DMP0:999:CALCWARNING") {
  field(CALC, "(!A)*B")
  field(INPA, "BTM:DMP0:999:WARNINGMODE")
  field(INPB, "BTM:DMP0:999:PPSPRSSR.SEVR")
  field(HIHI, "1")
  field(HHSV, "MINOR")
  field(SCAN, "2 second")
}

#! Further lines contain data used by VisualDCT
#! View(3250,3365,1.0)
#! Record("BTM:DMP0:999:WARNINGMODE",3440,3386,0,1,"BTM:DMP0:999:WARNINGMODE")
#! Field("BTM:DMP0:999:WARNINGMODE.VAL",16777215,1,"BTM:DMP0:999:WARNINGMODE.VAL")
#! Field("BTM:DMP0:999:WARNINGMODE.FLNK",16777215,1,"BTM:DMP0:999:WARNINGMODE.FLNK")
#! Link("BTM:DMP0:999:WARNINGMODE.FLNK","BTM:DMP0:999:CALCWARNING")
#! Record("BTM:DMP0:999:CALCWARNING",3760,3400,0,0,"BTM:DMP0:999:CALCWARNING")
#! Field("BTM:DMP0:999:CALCWARNING.INPA",16777215,0,"BTM:DMP0:999:CALCWARNING.INPA")
#! Link("BTM:DMP0:999:CALCWARNING.INPA","BTM:DMP0:999:WARNINGMODE.VAL")
#! Field("BTM:DMP0:999:CALCWARNING.INPB",16777215,1,"BTM:DMP0:999:CALCWARNING.INPB")
#alias("canonicalName","alias")
alias("BTM:LTU0:226:PPSPRSSR","BTM:LTU0:221:PPSPRSSR")
alias("BTM:LTU0:226:PPSTRIPPRSSR","BTM:LTU0:221:PPSTRIPPRSSR")
alias("BTM:LTU0:226:PPSRSETPRSSR","BTM:LTU0:221:PPSRSETPRSSR")
alias("BTM:LTU0:226:VENTTIMEOUT","BTM:LTU0:221:VENTTIMEOUT")
alias("BTM:LTU0:226:FILLTIMEOUT","BTM:LTU0:221:FILLTIMEOUT")
alias("BTM:LTU0:226:FLOWRATEFAULT","BTM:LTU0:221:FLOWRATEFAULT")
alias("BTM:LTU0:226:OVERPRESSURE","BTM:LTU0:221:OVERPRESSURE")
alias("BTM:LTU0:226:LOPRESSRSTRT","BTM:LTU0:221:LOPRESSRSTRT")
alias("BTM:LTU0:226:UNITTEST","BTM:LTU0:221:UNITTEST")
alias("BTM:LTU0:226:CALCWARNING","BTM:LTU0:221:CALCWARNING")
alias("BTM:LTU0:226:WARNINGMODE","BTM:LTU0:221:WARNINGMODE")
alias("BTM:LTU0:226:PPSTRIPA","BTM:LTU0:221:PPSTRIPA")
alias("BTM:LTU0:226:PPSTRIPB","BTM:LTU0:221:PPSTRIPB")
alias("BTM:LTU0:226:PPSTRIP","BTM:LTU0:221:PPSTRIP")
alias("BTM:LTU0:226:IOCTEST","BTM:LTU0:221:IOCTEST")
#alias("canonicalName","alias")
alias("BTM:LTU0:648:PPSPRSSR","BTM:LTU0:716:PPSPRSSR")
alias("BTM:LTU0:648:PPSTRIPPRSSR","BTM:LTU0:716:PPSTRIPPRSSR")
alias("BTM:LTU0:648:PPSRSETPRSSR","BTM:LTU0:716:PPSRSETPRSSR")
alias("BTM:LTU0:648:VENTTIMEOUT","BTM:LTU0:716:VENTTIMEOUT")
alias("BTM:LTU0:648:FILLTIMEOUT","BTM:LTU0:716:FILLTIMEOUT")
alias("BTM:LTU0:648:FLOWRATEFAULT","BTM:LTU0:716:FLOWRATEFAULT")
alias("BTM:LTU0:648:OVERPRESSURE","BTM:LTU0:716:OVERPRESSURE")
alias("BTM:LTU0:648:LOPRESSRSTRT","BTM:LTU0:716:LOPRESSRSTRT")
alias("BTM:LTU0:648:UNITTEST","BTM:LTU0:716:UNITTEST")
alias("BTM:LTU0:648:CALCWARNING","BTM:LTU0:716:CALCWARNING")
alias("BTM:LTU0:648:WARNINGMODE","BTM:LTU0:716:WARNINGMODE")
alias("BTM:LTU0:648:PPSTRIPA","BTM:LTU0:716:PPSTRIPA")
alias("BTM:LTU0:648:PPSTRIPB","BTM:LTU0:716:PPSTRIPB")
alias("BTM:LTU0:648:PPSTRIP","BTM:LTU0:716:PPSTRIP")
alias("BTM:LTU0:648:IOCTEST","BTM:LTU0:716:IOCTEST")
#alias("canonicalName","alias")
alias("BTM:LTU0:687:PPSPRSSR","BTM:DMP0:311:PPSPRSSR")
alias("BTM:LTU0:687:PPSTRIPPRSSR","BTM:DMP0:311:PPSTRIPPRSSR")
alias("BTM:LTU0:687:PPSRSETPRSSR","BTM:DMP0:311:PPSRSETPRSSR")
alias("BTM:LTU0:687:VENTTIMEOUT","BTM:DMP0:311:VENTTIMEOUT")
alias("BTM:LTU0:687:FILLTIMEOUT","BTM:DMP0:311:FILLTIMEOUT")
alias("BTM:LTU0:687:FLOWRATEFAULT","BTM:DMP0:311:FLOWRATEFAULT")
alias("BTM:LTU0:687:OVERPRESSURE","BTM:DMP0:311:OVERPRESSURE")
alias("BTM:LTU0:687:LOPRESSRSTRT","BTM:DMP0:311:LOPRESSRSTRT")
alias("BTM:LTU0:687:UNITTEST","BTM:DMP0:311:UNITTEST")
alias("BTM:LTU0:687:CALCWARNING","BTM:DMP0:311:CALCWARNING")
alias("BTM:LTU0:687:WARNINGMODE","BTM:DMP0:311:WARNINGMODE")
alias("BTM:LTU0:687:PPSTRIPA","BTM:DMP0:311:PPSTRIPA")
alias("BTM:LTU0:687:PPSTRIPB","BTM:DMP0:311:PPSTRIPB")
alias("BTM:LTU0:687:PPSTRIP","BTM:DMP0:311:PPSTRIP")
alias("BTM:LTU0:687:IOCTEST","BTM:DMP0:311:IOCTEST")
#alias("canonicalName","alias")
alias("BTM:LTU0:717:PPSPRSSR","BTM:DMP0:423:PPSPRSSR")
alias("BTM:LTU0:717:PPSTRIPPRSSR","BTM:DMP0:423:PPSTRIPPRSSR")
alias("BTM:LTU0:717:PPSRSETPRSSR","BTM:DMP0:423:PPSRSETPRSSR")
alias("BTM:LTU0:717:VENTTIMEOUT","BTM:DMP0:423:VENTTIMEOUT")
alias("BTM:LTU0:717:FILLTIMEOUT","BTM:DMP0:423:FILLTIMEOUT")
alias("BTM:LTU0:717:FLOWRATEFAULT","BTM:DMP0:423:FLOWRATEFAULT")
alias("BTM:LTU0:717:OVERPRESSURE","BTM:DMP0:423:OVERPRESSURE")
alias("BTM:LTU0:717:LOPRESSRSTRT","BTM:DMP0:423:LOPRESSRSTRT")
alias("BTM:LTU0:717:UNITTEST","BTM:DMP0:423:UNITTEST")
alias("BTM:LTU0:717:CALCWARNING","BTM:DMP0:423:CALCWARNING")
alias("BTM:LTU0:717:WARNINGMODE","BTM:DMP0:423:WARNINGMODE")
alias("BTM:LTU0:717:PPSTRIPA","BTM:DMP0:423:PPSTRIPA")
alias("BTM:LTU0:717:PPSTRIPB","BTM:DMP0:423:PPSTRIPB")
alias("BTM:LTU0:717:PPSTRIP","BTM:DMP0:423:PPSTRIP")
alias("BTM:LTU0:717:IOCTEST","BTM:DMP0:423:IOCTEST")

record(calcout, "PPS:UND0:1:CLSRCHRESETS") {
  field(SCAN, "1 second")
  field(FLNK, "PPS:UND0:1:SRCHRSETALSM")
  field(CALC, "A+2*B")
  field(INPA, "PPS:UND0:1:SRCHRESET")
  field(INPB, "PPS:UND0:1:PERMACC")
  field(OUT, "PPS:UND0:1:SRCHRSETALSM.VAL")
}


record(mbbi, "PPS:UND0:1:SRCHRSETALSM") {
  field(ZRVL, "0")
  field(ONVL, "1")
  field(TWVL, "2")
  field(THVL, "3")
  field(ZRST, "NOT_SET")
  field(ONST, "SET")
  field(TWST, "NOT_SET")
  field(THST, "INCONSISTENT")
  field(ZRSV, "MAJOR")
  field(ONSV, "NO_ALARM")
  field(TWSV, "NO_ALARM")
  field(THSV, "INVALID")
  field(DESC, "Search Reset alarm sum")
}

record(calcout, "PPS:DMP0:1:CLSRCHRESETS") {
  field(SCAN, "1 second")
  field(FLNK, "PPS:DMP0:1:SRCHRSETALSM")
  field(CALC, "A+2*B")
  field(INPA, "PPS:DMP0:1:SRCHRESET")
  field(INPB, "PPS:DMP0:1:PERMACC")
  field(OUT, "PPS:DMP0:1:SRCHRSETALSM.VAL")
}


record(mbbi, "PPS:DMP0:1:SRCHRSETALSM") {
  field(ZRVL, "0")
  field(ONVL, "1")
  field(TWVL, "2")
  field(THVL, "3")
  field(ZRST, "NOT_SET")
  field(ONST, "SET")
  field(TWST, "NOT_SET")
  field(THST, "INCONSISTENT")
  field(ZRSV, "MAJOR")
  field(ONSV, "NO_ALARM")
  field(TWSV, "NO_ALARM")
  field(THSV, "INVALID")
  field(DESC, "Search Reset alarm sum")
}
#! Generated by VisualDCT v2.6
#! DBDSTART
#! DBD("../../dbd/pps.dbd")
#! DBDEND


record(calc, "PPS:UND0:1:CALCSUMACCS") {
  field(SCAN, "1 second")
  field(FLNK, "PPS:UND0:1:SUMACCESS")
  field(CALC, "A&&!B&&!C?1:!A&&B&&!C?2:!A&&!B&&C?3:0")
  field(INPA, "PPS:UND0:1:NOACC MS")
  field(INPB, "PPS:UND0:1:CTRLACC MS")
  field(INPC, "PPS:UND0:1:PERMACC MS")
}

record(mbbi, "PPS:UND0:1:SUMACCESS") {
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(INP, "PPS:UND0:1:CALCSUMACCS.VAL MS")
  field(ZRST, "UNDEFINED")
  field(ONST, "NO")
  field(TWST, "CONTROLLED")
  field(THST, "PERMITTED")
  field(ZRSV, "MAJOR")
  field(ONSV, "NO_ALARM")
  field(TWSV, "MAJOR")
  field(THSV, "MAJOR")
}

record(mbbi, "PPS:DMP0:1:SUMACCESS") {
  field(SCAN, "Passive")
  field(DTYP, "Soft Channel")
  field(INP, "PPS:DMP0:1:CALCSUMACCS.VAL MS")
  field(ZRST, "UNDEFINED")
  field(ONST, "NO")
  field(TWST, "CONTROLLED")
  field(THST, "PERMITTED")
  field(ZRSV, "MAJOR")
  field(ONSV, "NO_ALARM")
  field(TWSV, "MAJOR")
  field(THSV, "MAJOR")
}

record(calc, "PPS:DMP0:1:CALCSUMACCS") {
  field(SCAN, "1 second")
  field(FLNK, "PPS:DMP0:1:SUMACCESS")
  field(CALC, "A&&!B&&!C?1:!A&&B&&!C?2:!A&&!B&&C?3:0")
  field(INPA, "PPS:DMP0:1:NOACC MS")
  field(INPB, "PPS:DMP0:1:CTRLACC MS")
  field(INPC, "PPS:DMP0:1:PERMACC MS")
}

record(calcout, "BSOC:LTU0:1:CALCMODE") {
  field(SCAN, "2 second")
  field(CALC, "A")
  field(INPA, "PPS:UND0:1:LOOPLAT CPP")
  field(OUT, "BSOC:LTU0:1:MODE PP")
  field(OOPT, "Every Time")
}

record(bi, "BSOC:LTU0:1:MODE") {
  field(DESC, "BSOBTW01 bypass mode")
  field(OSV, "MINOR")
  field(ZNAM, "ACTIVE")
  field(ONAM, "BYPASS")
  field(PINI, "YES")
}

record(calcout, "BSOC:LTU0:2:CALCMODE") {
  field(SCAN, "2 second")
  field(CALC, "A")
  field(INPA, "PPS:UND0:1:LOOPLAT CPP")
  field(OUT, "BSOC:LTU0:2:MODE.VAL PP")
  field(OOPT, "Every Time")
}

record(bi, "BSOC:LTU0:2:MODE") {
  field(DESC, "BSOBTW02 bypass mode")
  field(OSV, "MINOR")
  field(ZNAM, "ACTIVE")
  field(ONAM, "BYPASS")
  field(PINI, "YES")
}


record(calc, "PPS:SYS0:1:LI28BSYALMSM") {
  field(SCAN, "2 second")
  field(CALC, "A")
  field(INPA, "BTM:LI28:PP01:STATSUMY CA MS")
  field(INPB, "BTM:BSYH:PP01:STATSUMY CA MS")
  field(INPC, "BTM:BSYA:PP01:STATSUMY CA MS")
}

#! Generated by VisualDCT v2.5
#! DBDSTART
#! DBDEND


record(ai, "PLC:UND0:PPS1:STATUSRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[5]")
  field(FLNK, "PLC:UND0:PPS1:DEVICESTATUSRAW")
}

record(ai, "PLC:UND0:PPS1:MODELRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[6]")
  field(FLNK, "PLC:UND0:PPS1:MODELCALC")
}

record(ai, "PLC:UND0:PPS1:UPTIMESEC") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[17]")
  field(FLNK, "PLC:UND0:PPS1:UPTIMEHOURS PP MS")
}

record(calc, "PLC:UND0:PPS1:UPTIMEHOURS") {
  field(FLNK, "PLC:UND0:PPS1:UPTIMEMINUTES PP MS")
  field(CALC, "FLOOR(A/3600)")
  field(INPA, "PLC:UND0:PPS1:UPTIMESEC")
  field(EGU, "Hours")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC NPP MS")
}

record(calc, "PLC:UND0:PPS1:UPTIMEMINUTES") {
  field(FLNK, "PLC:UND0:PPS1:UPTIMESECONDS PP MS")
  field(CALC, "FLOOR((A%3600)/60)")
  field(INPA, "PLC:UND0:PPS1:UPTIMESEC")
  field(EGU, "Minutes")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(calc, "PLC:UND0:PPS1:UPTIMESECONDS") {
  field(CALC, "A%60")
  field(INPA, "PLC:UND0:PPS1:UPTIMESEC")
  field(EGU, "Seconds")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(bi, "PLC:UND0:PPS1:HEARTBEATRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[19] B 0")
  field(ZNAM, "ZERO")
  field(ONAM, "ONE")
  field(FLNK, "PLC:UND0:PPS1:COMMLINK")
}

record(mbbi, "PLC:UND0:PPS1:MODEL") {
  field(INP, "PLC:UND0:PPS1:MODELCALC NPP MS")
  field(ZRST, "UNKNOWN")
  field(ONST, "CTL_LGX_L61")
  field(TWST, "CTL_LGX_5555")
  field(THST, "CTL_LTX_5550")
  field(FRST, "CMP_LGX_L32")
}

record(ai, "PLC:UND0:PPS1:FWVERSIONRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[7]")
  field(FLNK, "PLC:UND0:PPS1:FWVERSIONMAJ")
}

record(calc, "PLC:UND0:PPS1:FWVERSIONMAJ") {
  field(FLNK, "PLC:UND0:PPS1:FWVERSIONMIN")
  field(CALC, "A%16")
  field(INPA, "PLC:UND0:PPS1:FWVERSIONRAW NPP MS")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(calc, "PLC:UND0:PPS1:FWVERSIONMIN") {
  field(CALC, "(A/256)%16")
  field(INPA, "PLC:UND0:PPS1:FWVERSIONRAW NPP MS")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(calc, "PLC:UND0:PPS1:MODELCALC") {
  field(FLNK, "PLC:UND0:PPS1:MODEL")
  field(CALC, "A=54?1:A=51?2:A=3?3:A=77?4:0")
  field(INPA, "PLC:UND0:PPS1:MODELRAW NPP MS")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(calc, "PLC:UND0:PPS1:DEVICESTATUSCALC") {
  field(FLNK, "PLC:UND0:PPS1:DEVICESTATUS")
  field(CALC, "A=B?1:A=C?2:A=D?3:A=E?4:A=F?5:A=G?6:0")
  field(INPA, "PLC:UND0:PPS1:DEVICESTATUSRAW NPP MS")
  field(INPB, "0x7")
  field(INPC, "0x6")
  field(INPD, "0x5")
  field(INPE, "0x4")
  field(INPF, "0x1")
}

record(calc, "PLC:UND0:PPS1:DEVICESTATUSRAW") {
  field(FLNK, "PLC:UND0:PPS1:DEVICESTATUSCALC")
  field(CALC, "A>>4&B")
  field(INPA, "PLC:UND0:PPS1:STATUSRAW")
  field(INPB, "0xF")
  field(INPC, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(mbbi, "PLC:UND0:PPS1:DEVICESTATUS") {
  field(FLNK, "PLC:UND0:PPS1:FAULTSTATUSRAW")
  field(INP, "PLC:UND0:PPS1:DEVICESTATUSCALC NPP MS")
  field(ZRST, "UNKNOWN")
  field(ONST, "PROGRAM")
  field(TWST, "RUN")
  field(THST, "FAULTED")
  field(FRST, "FLASH_ERROR")
  field(FVST, "FLASHING")
  field(ZRSV, "MAJOR")
  field(ONSV, "MAJOR")
  field(TWSV, "NO_ALARM")
  field(THSV, "MAJOR")
  field(FRSV, "MAJOR")
  field(FVSV, "MAJOR")
}

record(calc, "PLC:UND0:PPS1:FAULTSTATUSRAW") {
  field(FLNK, "PLC:UND0:PPS1:FAULTSTATUSCALC")
  field(CALC, "A>>8&B")
  field(INPA, "PLC:UND0:PPS1:STATUSRAW")
  field(INPB, "0xF")
  field(INPC, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(calc, "PLC:UND0:PPS1:FAULTSTATUSCALC") {
  field(FLNK, "PLC:UND0:PPS1:FAULTSTATUS")
  field(CALC, "A=B?1:A=C?2:A=D?3:A=E?4:0")
  field(INPA, "PLC:UND0:PPS1:FAULTSTATUSRAW NPP MS")
  field(INPB, "0x0004")
  field(INPC, "0x0003")
  field(INPD, "0x0002")
  field(INPE, "0x0001")
}

record(mbbi, "PLC:UND0:PPS1:FAULTSTATUS") {
  field(FLNK, "PLC:UND0:PPS1:KEYSTATUSRAW")
  field(INP, "PLC:UND0:PPS1:FAULTSTATUSCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MAJOR_UNRECOVBL")
  field(TWST, "MAJOR_RECOVBL")
  field(THST, "MINOR_UNRECOVBL")
  field(FRST, "MINOR_RECOVBL")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MAJOR")
  field(TWSV, "MAJOR")
  field(THSV, "MINOR")
  field(FRSV, "NO_ALARM")
}

record(calc, "PLC:UND0:PPS1:KEYSTATUSRAW") {
  field(FLNK, "PLC:UND0:PPS1:KEYSTATUSCALC")
  field(CALC, "A>>12&B")
  field(INPA, "PLC:UND0:PPS1:STATUSRAW")
  field(INPB, "0x3")
  field(INPC, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(calc, "PLC:UND0:PPS1:KEYSTATUSCALC") {
  field(FLNK, "PLC:UND0:PPS1:KEYSTATUS")
  field(CALC, "A=B?1:A=C?2:A=D?3:0")
  field(INPA, "PLC:UND0:PPS1:KEYSTATUSRAW NPP MS")
  field(INPB, "0x3")
  field(INPC, "0x2")
  field(INPD, "0x1")
}

record(mbbi, "PLC:UND0:PPS1:KEYSTATUS") {
  field(INP, "PLC:UND0:PPS1:KEYSTATUSCALC NPP MS")
  field(ZRST, "UNKNOWN")
  field(ONST, "REMOTE")
  field(TWST, "PROGRAM")
  field(THST, "RUN")
  field(ZRSV, "MAJOR")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(THSV, "NO_ALARM")
}

record(ai, "PLC:UND0:PPS1:MAJORFAULTRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[8]")
  field(FLNK, "PLC:UND0:PPS1:FAULTPOWERCALC")
}

record(ai, "PLC:UND0:PPS1:MINORFAULTRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[9]")
}

record(calc, "PLC:UND0:PPS1:FAULTPOWERCALC") {
  field(FLNK, "PLC:UND0:PPS1:FAULTPOWER")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:UND0:PPS1:MAJORFAULTRAW")
  field(INPB, "PLC:UND0:PPS1:MINORFAULTRAW")
  field(INPC, "0x2")
  field(INPD, "PLC:UND0:PPS1:HEARTBEATCLC NPP MS")
}

record(mbbi, "PLC:UND0:PPS1:FAULTPOWER") {
  field(FLNK, "PLC:UND0:PPS1:FAULTIOCALC")
  field(INP, "PLC:UND0:PPS1:FAULTPOWERCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
}

record(calc, "PLC:UND0:PPS1:FAULTIOCALC") {
  field(FLNK, "PLC:UND0:PPS1:FAULTIO")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:UND0:PPS1:MAJORFAULTRAW")
  field(INPB, "PLC:UND0:PPS1:MINORFAULTRAW")
  field(INPC, "0x8")
  field(INPD, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(mbbi, "PLC:UND0:PPS1:FAULTIO") {
  field(FLNK, "PLC:UND0:PPS1:FAULTPROGRAMCALC")
  field(INP, "PLC:UND0:PPS1:FAULTIOCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
}

record(calc, "PLC:UND0:PPS1:FAULTPROGRAMCALC") {
  field(FLNK, "PLC:UND0:PPS1:FAULTPROGRAM")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:UND0:PPS1:MAJORFAULTRAW")
  field(INPB, "PLC:UND0:PPS1:MINORFAULTRAW")
  field(INPC, "0x10")
  field(INPD, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(mbbi, "PLC:UND0:PPS1:FAULTPROGRAM") {
  field(FLNK, "PLC:UND0:PPS1:FAULTFLTHNDLCALC")
  field(INP, "PLC:UND0:PPS1:FAULTPROGRAMCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
}

record(mbbi, "PLC:UND0:PPS1:FAULTFLTHNDL") {
  field(FLNK, "PLC:UND0:PPS1:FAULTWTCHDOGCALC")
  field(INP, "PLC:UND0:PPS1:FAULTFLTHNDLCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
}

record(calc, "PLC:UND0:PPS1:FAULTFLTHNDLCALC") {
  field(FLNK, "PLC:UND0:PPS1:FAULTFLTHNDL")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:UND0:PPS1:MAJORFAULTRAW")
  field(INPB, "PLC:UND0:PPS1:MINORFAULTRAW")
  field(INPC, "0x20")
  field(INPD, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(calc, "PLC:UND0:PPS1:FAULTWTCHDOGCALC") {
  field(FLNK, "PLC:UND0:PPS1:FAULTWTCHDOG")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:UND0:PPS1:MAJORFAULTRAW")
  field(INPB, "PLC:UND0:PPS1:MINORFAULTRAW")
  field(INPC, "0x40")
  field(INPD, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(mbbi, "PLC:UND0:PPS1:FAULTWTCHDOG") {
  field(FLNK, "PLC:UND0:PPS1:FAULTSTACKCALC")
  field(INP, "PLC:UND0:PPS1:FAULTWTCHDOGCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
}

record(calc, "PLC:UND0:PPS1:FAULTSTACKCALC") {
  field(FLNK, "PLC:UND0:PPS1:FAULTSTACK")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:UND0:PPS1:MAJORFAULTRAW")
  field(INPB, "PLC:UND0:PPS1:MINORFAULTRAW")
  field(INPC, "0x80")
  field(INPD, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}


record(mbbi, "PLC:UND0:PPS1:FAULTSTACK") {
  field(FLNK, "PLC:UND0:PPS1:FAULTMODECHGCALC")
  field(INP, "PLC:UND0:PPS1:FAULTSTACKCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "NO_ALARM")
  field(TWSV, "MAJOR")
}

record(calc, "PLC:UND0:PPS1:FAULTMODECHGCALC") {
  field(FLNK, "PLC:UND0:PPS1:FAULTMODECHG")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:UND0:PPS1:MAJORFAULTRAW")
  field(INPB, "PLC:UND0:PPS1:MINORFAULTRAW")
  field(INPC, "0x100")
  field(INPD, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(mbbi, "PLC:UND0:PPS1:FAULTMODECHG") {
  field(FLNK, "PLC:UND0:PPS1:FAULTSERIALCALC")
  field(INP, "PLC:UND0:PPS1:FAULTMODECHGCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
}

record(calc, "PLC:UND0:PPS1:FAULTSERIALCALC") {
  field(FLNK, "PLC:UND0:PPS1:FAULTSERIAL")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:UND0:PPS1:MAJORFAULTRAW")
  field(INPB, "PLC:UND0:PPS1:MINORFAULTRAW")
  field(INPC, "0x200")
  field(INPD, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(mbbi, "PLC:UND0:PPS1:FAULTSERIAL") {
  field(FLNK, "PLC:UND0:PPS1:FAULTBATTERYCALC")
  field(INP, "PLC:UND0:PPS1:FAULTSERIALCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
}

record(mbbi, "PLC:UND0:PPS1:FAULTBATTERY") {
  field(FLNK, "PLC:UND0:PPS1:FAULTMOTIONCALC")
  field(INP, "PLC:UND0:PPS1:FAULTBATTERYCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
}

record(calc, "PLC:UND0:PPS1:FAULTBATTERYCALC") {
  field(FLNK, "PLC:UND0:PPS1:FAULTBATTERY")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:UND0:PPS1:MAJORFAULTRAW")
  field(INPB, "PLC:UND0:PPS1:MINORFAULTRAW")
  field(INPC, "0x400")
  field(INPD, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(calc, "PLC:UND0:PPS1:FAULTMOTIONCALC") {
  field(FLNK, "PLC:UND0:PPS1:FAULTMOTION")
  field(CALC, "A&C?2:B&C?1:0")
  field(INPA, "PLC:UND0:PPS1:MAJORFAULTRAW")
  field(INPB, "PLC:UND0:PPS1:MINORFAULTRAW")
  field(INPC, "0x800")
  field(INPD, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(mbbi, "PLC:UND0:PPS1:FAULTMOTION") {
  field(INP, "PLC:UND0:PPS1:FAULTMOTIONCALC NPP MS")
  field(ZRST, "NONE")
  field(ONST, "MINOR")
  field(TWST, "MAJOR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
}

record(ai, "PLC:UND0:PPS1:VERSIONMAJORDES") {
  field(PINI, "YES")
  field(FLNK, "PLC:UND0:PPS1:VERSIONMAJORCALCHI")
  field(VAL, "2")
  field(PREC, "0")
}

record(calcout, "PLC:UND0:PPS1:VERSIONMAJORCALCHI") {
  field(FLNK, "PLC:UND0:PPS1:VERSIONMAJORCALCLO")
  field(CALC, "A+1")
  field(INPA, "PLC:UND0:PPS1:VERSIONMAJORDES")
  field(OUT, "PLC:UND0:PPS1:VERSIONMAJOR.HIGH")
}

record(calcout, "PLC:UND0:PPS1:VERSIONMAJORCALCLO") {
  field(CALC, "A-1")
  field(INPA, "PLC:UND0:PPS1:VERSIONMAJORDES")
  field(OUT, "PLC:UND0:PPS1:VERSIONMAJOR.LOW")
}

record(ai, "PLC:UND0:PPS1:VERSIONMINORDES") {
  field(PINI, "YES")
  field(FLNK, "PLC:UND0:PPS1:VERSIONMINORCALCHI")
  field(VAL, "0")
  field(PREC, "0")
}

record(calcout, "PLC:UND0:PPS1:VERSIONMINORCALCLO") {
  field(CALC, "A-1")
  field(INPA, "PLC:UND0:PPS1:VERSIONMINORDES.VAL")
  field(OUT, "PLC:UND0:PPS1:VERSIONMINOR.LOW")
}

record(calcout, "PLC:UND0:PPS1:VERSIONMINORCALCHI") {
  field(FLNK, "PLC:UND0:PPS1:VERSIONMINORCALCLO")
  field(CALC, "A+1")
  field(INPA, "PLC:UND0:PPS1:VERSIONMINORDES.VAL")
  field(OUT, "PLC:UND0:PPS1:VERSIONMINOR.HIGH")
}

record(ai, "PLC:UND0:PPS1:VERSIONREVDES") {
  field(PINI, "YES")
  field(FLNK, "PLC:UND0:PPS1:VERSIONREVCALCHI")
  field(VAL, "0")
  field(PREC, "0")
}

record(calcout, "PLC:UND0:PPS1:VERSIONREVCALCHI") {
  field(FLNK, "PLC:UND0:PPS1:VERSIONREVCALCLO")
  field(CALC, "A+1")
  field(INPA, "PLC:UND0:PPS1:VERSIONREVDES.VAL")
  field(OUT, "PLC:UND0:PPS1:VERSIONREV.HIGH")
}

record(calcout, "PLC:UND0:PPS1:VERSIONREVCALCLO") {
  field(CALC, "A-1")
  field(INPA, "PLC:UND0:PPS1:VERSIONREVDES.VAL")
  field(OUT, "PLC:UND0:PPS1:VERSIONREV.LOW")
}

record(calc, "PLC:UND0:PPS1:HEARTBEATCALC") {
  field(FLNK, "PLC:UND0:PPS1:HEARTBEATERR")
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:HEARTBEATRAW")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCALC")
}

record(bi, "PLC:UND0:PPS1:HEARTBEATOK") {
  field(FLNK, "PLC:UND0:PPS1:HEARTBEATE01")
  field(INP, "PLC:UND0:PPS1:HEARTBEATERR.VAL")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  field(ZNAM, "OK")
  field(ONAM, "FAULT")
}

record(calc, "PLC:UND0:PPS1:HEARTBEATERR") {
  field(FLNK, "PLC:UND0:PPS1:HEARTBEATOK")
  field(CALC, "A=B?1:0")
  field(INPA, "PLC:UND0:PPS1:HEARTBEATCALC.A")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCALC.B")
}

record(calc, "PLC:UND0:PPS1:HEARTBEATECT") {
  field(FLNK, "PLC:UND0:PPS1:HEARTBEATSUM")
  field(CALC, "A+B+C+D+E+F+G+H+I+J")
  field(INPA, "PLC:UND0:PPS1:HEARTBEATE01")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATE02")
  field(INPC, "PLC:UND0:PPS1:HEARTBEATE03")
  field(INPD, "PLC:UND0:PPS1:HEARTBEATE04")
  field(INPE, "PLC:UND0:PPS1:HEARTBEATE05")
  field(INPF, "PLC:UND0:PPS1:HEARTBEATE06")
  field(INPG, "PLC:UND0:PPS1:HEARTBEATE07")
  field(INPH, "PLC:UND0:PPS1:HEARTBEATE08")
  field(INPI, "PLC:UND0:PPS1:HEARTBEATE09")
  field(INPJ, "PLC:UND0:PPS1:HEARTBEATE10")
  field(HIHI, "7")
  field(LOLO, "-1")
  field(HIGH, "5")
  field(LOW, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
  field(HSV, "MINOR")
  field(LSV, "MAJOR")
}

record(calc, "PLC:UND0:PPS1:HEARTBEATE09") {
  field(FLNK, "PLC:UND0:PPS1:HEARTBEATE10")
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:HEARTBEATE08.B")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATE09.VAL")
}

record(calc, "PLC:UND0:PPS1:HEARTBEATE08") {
  field(FLNK, "PLC:UND0:PPS1:HEARTBEATE09")
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:HEARTBEATE07.B")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATE08.VAL")
}

record(calc, "PLC:UND0:PPS1:HEARTBEATE07") {
  field(FLNK, "PLC:UND0:PPS1:HEARTBEATE08")
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:HEARTBEATE06.B")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATE07.VAL")
}

record(calc, "PLC:UND0:PPS1:HEARTBEATE06") {
  field(FLNK, "PLC:UND0:PPS1:HEARTBEATE07")
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:HEARTBEATE05.B")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATE06.VAL")
}

record(calc, "PLC:UND0:PPS1:HEARTBEATE05") {
  field(FLNK, "PLC:UND0:PPS1:HEARTBEATE06")
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:HEARTBEATE04.B")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATE05.VAL")
}

record(calc, "PLC:UND0:PPS1:HEARTBEATE04") {
  field(FLNK, "PLC:UND0:PPS1:HEARTBEATE05")
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:HEARTBEATE03.B")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATE04.VAL")
}

record(calc, "PLC:UND0:PPS1:HEARTBEATE03") {
  field(FLNK, "PLC:UND0:PPS1:HEARTBEATE04")
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:HEARTBEATE02.B")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATE03.VAL")
}

record(calc, "PLC:UND0:PPS1:HEARTBEATE02") {
  field(FLNK, "PLC:UND0:PPS1:HEARTBEATE03")
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:HEARTBEATE01.B")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATE02.VAL")
}

record(calc, "PLC:UND0:PPS1:HEARTBEATE01") {
  field(FLNK, "PLC:UND0:PPS1:HEARTBEATE02")
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:HEARTBEATERR")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATE01.VAL")
}

record(calc, "PLC:UND0:PPS1:HEARTBEATCLC") {
  field(CALC, "A=0?0:A=1?0:A-2?3:A=3?3:4")
  field(INPA, "PLC:UND0:PPS1:HEARTBEATECT.SEVR")
  field(HIHI, "4")
  field(HHSV, "INVALID")
}

record(mbbi, "PLC:UND0:PPS1:HEARTBEATSUM") {
  field(FLNK, "PLC:UND0:PPS1:HEARTBEATCLC")
  field(INP, "PLC:UND0:PPS1:HEARTBEATECT.SEVR")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "MINOR")
  field(TWSV, "MAJOR")
  field(ZRST, "PRESENT")
  field(ONST, "INTERMITTENT")
  field(TWST, "ABSENT")
}

record(ai, "PLC:UND0:PPS1:UPTIMEDAYRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[18]")
  field(FLNK, "PLC:UND0:PPS1:UPTIMEDAY")
}

record(calc, "PLC:UND0:PPS1:UPTIMEDAY") {
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:UPTIMEDAYRAW")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(ai, "PLC:UND0:PPS1:TODYEARRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[10]")
  field(FLNK, "PLC:UND0:PPS1:TODYEAR")
}

record(ai, "PLC:UND0:PPS1:TODDAYRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[12]")
  field(SCAN, "1 second")
  field(FLNK, "PLC:UND0:PPS1:TODDAY")
}

record(ai, "PLC:UND0:PPS1:TODMONTHRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[11]")
  field(FLNK, "PLC:UND0:PPS1:TODMONTH")
  field(SCAN, "1 second")
}

record(ai, "PLC:UND0:PPS1:TODHOURRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[13]")
  field(FLNK, "PLC:UND0:PPS1:TODHOUR")
}

record(ai, "PLC:UND0:PPS1:TODMINUTERAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[14]")
  field(FLNK, "PLC:UND0:PPS1:TODMINUTE")
  field(SCAN, "1 second")
}

record(ai, "PLC:UND0:PPS1:TODSECONDRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[15]")
  field(SCAN, "1 second")
  field(FLNK, "PLC:UND0:PPS1:TODSECOND")
}

record(calc, "PLC:UND0:PPS1:TODYEAR") {
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:TODYEARRAW NPP MS")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(calc, "PLC:UND0:PPS1:TODMONTH") {
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:TODMONTHRAW NPP MS")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(calc, "PLC:UND0:PPS1:TODDAY") {
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:TODDAYRAW NPP MS")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(calc, "PLC:UND0:PPS1:TODHOUR") {
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:TODHOURRAW NPP MS")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(calc, "PLC:UND0:PPS1:TODMINUTE") {
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:TODMINUTERAW NPP MS")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(calc, "PLC:UND0:PPS1:TODSECOND") {
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:TODSECONDRAW NPP MS")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(ai, "PLC:UND0:PPS1:VERSIONMAJORRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[36]")
  field(HYST, "1")
  field(FLNK, "PLC:UND0:PPS1:VERSIONMAJOR")
}

record(ai, "PLC:UND0:PPS1:VERSIONMINORRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[37]")
  field(FLNK, "PLC:UND0:PPS1:VERSIONMINOR")
}

record(calc, "PLC:UND0:PPS1:VERSIONMAJOR") {
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:VERSIONMAJORRAW NPP MS")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
  field(HSV, "MAJOR")
  field(LSV, "MAJOR")
}

record(calc, "PLC:UND0:PPS1:VERSIONMINOR") {
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:VERSIONMINORRAW NPP MS")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
  field(HSV, "MAJOR")
  field(LSV, "MAJOR")
}

record(ai, "PLC:UND0:PPS1:VERSIONREVRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[38]")
  field(FLNK, "PLC:UND0:PPS1:VERSIONREV")
}

record(calc, "PLC:UND0:PPS1:VERSIONREV") {
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:VERSIONREVRAW NPP MS")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
  field(HSV, "MAJOR")
  field(LSV, "MAJOR")
}

record(ai, "PLC:UND0:PPS1:SERIALNUMBERRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[4]")
  field(FLNK, "PLC:UND0:PPS1:SERIALNUMBER")
}

record(calc, "PLC:UND0:PPS1:SERIALNUMBER") {
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:SERIALNUMBERRAW NPP MS")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(mbbi, "PLC:UND0:PPS1:COMMLINK") {
  field(FLNK, "PLC:UND0:PPS1:HEARTBEATCALC")
  field(INP, "PLC:UND0:PPS1:HEARTBEATRAW.SEVR")
  field(ZRST, "OK")
  field(ONST, "OK")
  field(TWST, "OK")
  field(THST, "FAULT")
  field(ZRSV, "NO_ALARM")
  field(ONSV, "NO_ALARM")
  field(TWSV, "NO_ALARM")
  field(THSV, "MAJOR")
}

record(calc, "PLC:UND0:PPS1:HEARTBEATE10") {
  field(FLNK, "PLC:UND0:PPS1:HEARTBEATECT")
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:HEARTBEATE09.B")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATE10.VAL")
}

record(ai, "PLC:UND0:PPS1:DOCPREFIXRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:UND0:PPS1:DOCPREFIXCALC")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[31]")
}

record(calc, "PLC:UND0:PPS1:DOCPREFIXCALC") {
  field(FLNK, "PLC:UND0:PPS1:DOCPREFIX")
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:DOCPREFIXRAW")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(mbbi, "PLC:UND0:PPS1:DOCPREFIX") {
  field(INP, "PLC:UND0:PPS1:DOCPREFIXCALC NPP MS")
  field(ZRVL, "0")
  field(ONVL, "1")
  field(ZRST, "NONE")
  field(ONST, "SD")
  field(TWVL, "2")
  field(THVL, "3")
  field(FRVL, "4")
  field(FVVL, "5")
  field(SXVL, "6")
  field(SVVL, "7")
  field(EIVL, "8")
  field(NIVL, "9")
  field(TEVL, "10")
  field(ELVL, "11")
  field(TWST, "BD")
  field(THST, "DL")
  field(FRST, "EI")
  field(FVST, "FC")
  field(SXST, "FS")
  field(SVST, "IM")
  field(EIST, "LD")
  field(NIST, "OM")
  field(TEST, "QT")
  field(ELST, "WD")
}

record(ai, "PLC:UND0:PPS1:DOCSERIESRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:UND0:PPS1:DOCSERIES")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[32]")
}

record(calc, "PLC:UND0:PPS1:DOCSERIES") {
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:DOCSERIESRAW.VAL")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(ai, "PLC:UND0:PPS1:DOCBASERAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:UND0:PPS1:DOCBASE")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[33]")
}

record(calc, "PLC:UND0:PPS1:DOCBASE") {
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:DOCBASERAW.VAL")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(ai, "PLC:UND0:PPS1:DOCSUFFIXRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:UND0:PPS1:DOCSUFFIX")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[34]")
}

record(calc, "PLC:UND0:PPS1:DOCSUFFIX") {
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:DOCSUFFIXRAW")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(ai, "PLC:UND0:PPS1:DOCREVRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(FLNK, "PLC:UND0:PPS1:DOCREV")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[35]")
}

record(calc, "PLC:UND0:PPS1:DOCREV") {
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:DOCREVRAW")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(stringin, "PLC:UND0:PPS1:SUBSYSTEM") {
  field(PINI, "YES")
  field(VAL, "PPS")
}

record(ai, "PLC:UND0:PPS1:PLCADMINVMAJRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[0]")
  field(SCAN, "1 second")
  field(FLNK, "PLC:UND0:PPS1:PLCADMINVMAJ")
}

record(calc, "PLC:UND0:PPS1:PLCADMINVMAJ") {
  field(INPA, "PLC:UND0:PPS1:PLCADMINVMAJRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
  field(PREC, "0")
  field(HIHI, "2")
  field(LOLO, "0")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
}

record(ai, "PLC:UND0:PPS1:PLCADMINVMINRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[1]")
  field(SCAN, "1 second")
  field(FLNK, "PLC:UND0:PPS1:PLCADMINVMIN")
}

record(calc, "PLC:UND0:PPS1:PLCADMINVMIN") {
  field(INPA, "PLC:UND0:PPS1:PLCADMINVMINRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
  field(PREC, "0")
  field(HIHI, "1")
  field(LOLO, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
}

record(ai, "PLC:UND0:PPS1:PLCADMINVREVRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[2]")
  field(SCAN, "1 second")
  field(FLNK, "PLC:UND0:PPS1:PLCADMINVREV")
}

record(calc, "PLC:UND0:PPS1:PLCADMINVREV") {
  field(INPA, "PLC:UND0:PPS1:PLCADMINVREVRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
  field(PREC, "0")
  field(HIHI, "3")
  field(LOLO, "-1")
  field(HHSV, "MAJOR")
  field(LLSV, "MAJOR")
}

record(ai, "PLC:UND0:PPS1:PROGPLCATMAXRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[23]")
  field(SCAN, "1 second")
  field(FLNK, "PLC:UND0:PPS1:PROGPLCATMAX")
}

record(ai, "PLC:UND0:PPS1:PROGPLCATLSTRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[22]")
  field(FLNK, "PLC:UND0:PPS1:PROGPLCATLST")
}

record(calc, "PLC:UND0:PPS1:PROGPLCATLST") {
  field(INPA, "PLC:UND0:PPS1:PROGPLCATLSTRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(calc, "PLC:UND0:PPS1:PROGPLCATMAX") {
  field(INPA, "PLC:UND0:PPS1:PROGPLCATMAXRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(stringin, "PLC:UND0:PPS1:PLCADMINTAG") {
  field(PINI, "YES")
  field(VAL, "PLCADMIN_PLC_LTU0_PP01")
}

record(ai, "PLC:UND0:PPS1:TASKMAINTLSTRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[20]")
  field(FLNK, "PLC:UND0:PPS1:TASKMAINTLST")
}

record(calc, "PLC:UND0:PPS1:TASKMAINTLST") {
  field(INPA, "PLC:UND0:PPS1:TASKMAINTLSTRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(ai, "PLC:UND0:PPS1:TASKMAINTMAXRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[21]")
  field(FLNK, "PLC:UND0:PPS1:TASKMAINTMAX")
  field(SCAN, "1 second")
}

record(calc, "PLC:UND0:PPS1:TASKMAINTMAX") {
  field(INPA, "PLC:UND0:PPS1:TASKMAINTMAXRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(ai, "PLC:UND0:PPS1:PROG1TLSTRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[24]")
  field(FLNK, "PLC:UND0:PPS1:PROG1TLST")
}

record(ai, "PLC:UND0:PPS1:PROG1TMAXRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[25]")
  field(SCAN, "1 second")
  field(FLNK, "PLC:UND0:PPS1:PROG1TMAX")
}

record(calc, "PLC:UND0:PPS1:PROG1TLST") {
  field(INPA, "PLC:UND0:PPS1:PROG1TLSTRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(calc, "PLC:UND0:PPS1:PROG1TMAX") {
  field(INPA, "PLC:UND0:PPS1:PROG1TMAXRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(ai, "PLC:UND0:PPS1:PROG2TLSTRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[26]")
  field(FLNK, "PLC:UND0:PPS1:PROG2TLST")
}

record(ai, "PLC:UND0:PPS1:PROG2TMAXRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[27]")
  field(SCAN, "1 second")
  field(FLNK, "PLC:UND0:PPS1:PROG2TMAX")
}

record(calc, "PLC:UND0:PPS1:PROG2TLST") {
  field(INPA, "PLC:UND0:PPS1:PROG2TLSTRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(calc, "PLC:UND0:PPS1:PROG2TMAX") {
  field(INPA, "PLC:UND0:PPS1:PROG2TMAXRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(ai, "PLC:UND0:PPS1:PROG3TLSTRAW") {
  field(SCAN, "1 second")
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[28]")
  field(FLNK, "PLC:UND0:PPS1:PROG3TLST")
}

record(ai, "PLC:UND0:PPS1:PROG3TMAXRAW") {
  field(DTYP, "EtherIP")
  field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01[29]")
  field(SCAN, "1 second")
  field(FLNK, "PLC:UND0:PPS1:PROG3TMAX")
}

record(calc, "PLC:UND0:PPS1:PROG3TMAX") {
  field(INPA, "PLC:UND0:PPS1:PROG3TMAXRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(calc, "PLC:UND0:PPS1:PROG3TLST") {
  field(INPA, "PLC:UND0:PPS1:PROG3TLSTRAW.VAL")
  field(CALC, "A")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATCLC MS")
}

record(calc, "PLC:UND0:PPS1:STATSUMY") {
  field(SCAN, "1 second")
  field(CALC, "A")
  field(INPA, "PLC:UND0:PPS1:STATSUMY.SEVR")
  field(INPB, "PLC:UND0:PPS1:HEARTBEATSUM MS")
  field(INPC, "PLC:UND0:PPS1:FAULTSTATUS MS")
  field(INPD, "PLC:UND0:PPS1:KEYSTATUS MS")
  field(INPE, "PLC:UND0:PPS1:DEVICESTATUS MS")
  field(INPF, "PLC:UND0:PPS1:VERSIONMAJOR MS")
  field(INPG, "PLC:UND0:PPS1:VERSIONMINOR MS")
  field(INPH, "PLC:UND0:PPS1:VERSIONREV MS")
}

#! Further lines contain data used by VisualDCT
#! View(935,906,0.9)
#! Record("PLC:UND0:PPS1:STATUSRAW",2160,3987,0,1,"PLC:UND0:PPS1:STATUSRAW")
#! Field("PLC:UND0:PPS1:STATUSRAW.FLNK",16777215,1,"PLC:UND0:PPS1:STATUSRAW.FLNK")
#! Link("PLC:UND0:PPS1:STATUSRAW.FLNK","PLC:UND0:PPS1:DEVICESTATUSRAW")
#! Field("PLC:UND0:PPS1:STATUSRAW.VAL",16777215,1,"PLC:UND0:PPS1:STATUSRAW.VAL")
#! Record("PLC:UND0:PPS1:MODELRAW",4120,7,0,0,"PLC:UND0:PPS1:MODELRAW")
#! Field("PLC:UND0:PPS1:MODELRAW.FLNK",16777215,1,"PLC:UND0:PPS1:MODELRAW.FLNK")
#! Link("PLC:UND0:PPS1:MODELRAW.FLNK","PLC:UND0:PPS1:MODELCALC")
#! Field("PLC:UND0:PPS1:MODELRAW.VAL",16777215,0,"PLC:UND0:PPS1:MODELRAW.VAL")
#! Record("PLC:UND0:PPS1:UPTIMESEC",4280,1787,0,0,"PLC:UND0:PPS1:UPTIMESEC")
#! Field("PLC:UND0:PPS1:UPTIMESEC.FLNK",16777215,1,"PLC:UND0:PPS1:UPTIMESEC.FLNK")
#! Link("PLC:UND0:PPS1:UPTIMESEC.FLNK","PLC:UND0:PPS1:UPTIMEHOURS")
#! Field("PLC:UND0:PPS1:UPTIMESEC.VAL",16777215,1,"PLC:UND0:PPS1:UPTIMESEC.VAL")
#! Record("PLC:UND0:PPS1:UPTIMEHOURS",4540,1794,0,0,"PLC:UND0:PPS1:UPTIMEHOURS")
#! Field("PLC:UND0:PPS1:UPTIMEHOURS.INPA",16777215,0,"PLC:UND0:PPS1:UPTIMEHOURS.INPA")
#! Link("PLC:UND0:PPS1:UPTIMEHOURS.INPA","PLC:UND0:PPS1:UPTIMESEC.VAL")
#! Field("PLC:UND0:PPS1:UPTIMEHOURS.FLNK",16777215,1,"PLC:UND0:PPS1:UPTIMEHOURS.FLNK")
#! Link("PLC:UND0:PPS1:UPTIMEHOURS.FLNK","PLC:UND0:PPS1:UPTIMEMINUTES")
#! Field("PLC:UND0:PPS1:UPTIMEHOURS.INPB",16777215,0,"PLC:UND0:PPS1:UPTIMEHOURS.INPB")
#! Link("PLC:UND0:PPS1:UPTIMEHOURS.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:UPTIMEMINUTES",4580,2014,0,1,"PLC:UND0:PPS1:UPTIMEMINUTES")
#! Field("PLC:UND0:PPS1:UPTIMEMINUTES.INPA",16777215,0,"PLC:UND0:PPS1:UPTIMEMINUTES.INPA")
#! Link("PLC:UND0:PPS1:UPTIMEMINUTES.INPA","PLC:UND0:PPS1:UPTIMESEC.VAL")
#! Field("PLC:UND0:PPS1:UPTIMEMINUTES.FLNK",16777215,1,"PLC:UND0:PPS1:UPTIMEMINUTES.FLNK")
#! Link("PLC:UND0:PPS1:UPTIMEMINUTES.FLNK","PLC:UND0:PPS1:UPTIMESECONDS")
#! Field("PLC:UND0:PPS1:UPTIMEMINUTES.INPB",16777215,0,"PLC:UND0:PPS1:UPTIMEMINUTES.INPB")
#! Link("PLC:UND0:PPS1:UPTIMEMINUTES.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:UPTIMESECONDS",4620,2227,0,1,"PLC:UND0:PPS1:UPTIMESECONDS")
#! Field("PLC:UND0:PPS1:UPTIMESECONDS.INPA",16777215,0,"PLC:UND0:PPS1:UPTIMESECONDS.INPA")
#! Link("PLC:UND0:PPS1:UPTIMESECONDS.INPA","PLC:UND0:PPS1:UPTIMESEC.VAL")
#! Field("PLC:UND0:PPS1:UPTIMESECONDS.INPB",16777215,0,"PLC:UND0:PPS1:UPTIMESECONDS.INPB")
#! Link("PLC:UND0:PPS1:UPTIMESECONDS.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:HEARTBEATRAW",60,79,0,1,"PLC:UND0:PPS1:HEARTBEATRAW")
#! Field("PLC:UND0:PPS1:HEARTBEATRAW.FLNK",16777215,1,"PLC:UND0:PPS1:HEARTBEATRAW.FLNK")
#! Link("PLC:UND0:PPS1:HEARTBEATRAW.FLNK","PLC:UND0:PPS1:COMMLINK")
#! Field("PLC:UND0:PPS1:HEARTBEATRAW.SEVR",16777215,1,"PLC:UND0:PPS1:HEARTBEATRAW.SEVR")
#! Field("PLC:UND0:PPS1:HEARTBEATRAW.VAL",16777215,1,"PLC:UND0:PPS1:HEARTBEATRAW.VAL")
#! Record("PLC:UND0:PPS1:MODEL",4640,54,0,0,"PLC:UND0:PPS1:MODEL")
#! Field("PLC:UND0:PPS1:MODEL.INP",16777215,0,"PLC:UND0:PPS1:MODEL.INP")
#! Link("PLC:UND0:PPS1:MODEL.INP","PLC:UND0:PPS1:MODELCALC.VAL")
#! Record("PLC:UND0:PPS1:FWVERSIONRAW",4180,227,0,0,"PLC:UND0:PPS1:FWVERSIONRAW")
#! Field("PLC:UND0:PPS1:FWVERSIONRAW.FLNK",16777215,1,"PLC:UND0:PPS1:FWVERSIONRAW.FLNK")
#! Link("PLC:UND0:PPS1:FWVERSIONRAW.FLNK","PLC:UND0:PPS1:FWVERSIONMAJ")
#! Field("PLC:UND0:PPS1:FWVERSIONRAW.VAL",16777215,1,"PLC:UND0:PPS1:FWVERSIONRAW.VAL")
#! Record("PLC:UND0:PPS1:FWVERSIONMAJ",4460,247,0,0,"PLC:UND0:PPS1:FWVERSIONMAJ")
#! Field("PLC:UND0:PPS1:FWVERSIONMAJ.FLNK",16777215,1,"PLC:UND0:PPS1:FWVERSIONMAJ.FLNK")
#! Link("PLC:UND0:PPS1:FWVERSIONMAJ.FLNK","PLC:UND0:PPS1:FWVERSIONMIN")
#! Field("PLC:UND0:PPS1:FWVERSIONMAJ.INPA",16777215,0,"PLC:UND0:PPS1:FWVERSIONMAJ.INPA")
#! Link("PLC:UND0:PPS1:FWVERSIONMAJ.INPA","PLC:UND0:PPS1:FWVERSIONRAW.VAL")
#! Field("PLC:UND0:PPS1:FWVERSIONMAJ.INPB",16777215,0,"PLC:UND0:PPS1:FWVERSIONMAJ.INPB")
#! Link("PLC:UND0:PPS1:FWVERSIONMAJ.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:FWVERSIONMIN",4720,322,0,0,"PLC:UND0:PPS1:FWVERSIONMIN")
#! Field("PLC:UND0:PPS1:FWVERSIONMIN.INPA",16777215,0,"PLC:UND0:PPS1:FWVERSIONMIN.INPA")
#! Link("PLC:UND0:PPS1:FWVERSIONMIN.INPA","PLC:UND0:PPS1:FWVERSIONRAW.VAL")
#! Field("PLC:UND0:PPS1:FWVERSIONMIN.INPB",16777215,0,"PLC:UND0:PPS1:FWVERSIONMIN.INPB")
#! Link("PLC:UND0:PPS1:FWVERSIONMIN.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:MODELCALC",4380,27,0,0,"PLC:UND0:PPS1:MODELCALC")
#! Field("PLC:UND0:PPS1:MODELCALC.INPA",16777215,0,"PLC:UND0:PPS1:MODELCALC.INPA")
#! Link("PLC:UND0:PPS1:MODELCALC.INPA","PLC:UND0:PPS1:MODELRAW.VAL")
#! Field("PLC:UND0:PPS1:MODELCALC.FLNK",16777215,1,"PLC:UND0:PPS1:MODELCALC.FLNK")
#! Link("PLC:UND0:PPS1:MODELCALC.FLNK","PLC:UND0:PPS1:MODEL")
#! Field("PLC:UND0:PPS1:MODELCALC.VAL",16777215,0,"PLC:UND0:PPS1:MODELCALC.VAL")
#! Field("PLC:UND0:PPS1:MODELCALC.INPB",16777215,0,"PLC:UND0:PPS1:MODELCALC.INPB")
#! Link("PLC:UND0:PPS1:MODELCALC.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:DEVICESTATUSCALC",2760,3930,0,0,"PLC:UND0:PPS1:DEVICESTATUSCALC")
#! Field("PLC:UND0:PPS1:DEVICESTATUSCALC.FLNK",16777215,1,"PLC:UND0:PPS1:DEVICESTATUSCALC.FLNK")
#! Link("PLC:UND0:PPS1:DEVICESTATUSCALC.FLNK","PLC:UND0:PPS1:DEVICESTATUS")
#! Field("PLC:UND0:PPS1:DEVICESTATUSCALC.INPA",16777215,0,"PLC:UND0:PPS1:DEVICESTATUSCALC.INPA")
#! Link("PLC:UND0:PPS1:DEVICESTATUSCALC.INPA","PLC:UND0:PPS1:DEVICESTATUSRAW.VAL")
#! Field("PLC:UND0:PPS1:DEVICESTATUSCALC.VAL",16777215,1,"PLC:UND0:PPS1:DEVICESTATUSCALC.VAL")
#! Record("PLC:UND0:PPS1:DEVICESTATUSRAW",2480,3974,0,0,"PLC:UND0:PPS1:DEVICESTATUSRAW")
#! Field("PLC:UND0:PPS1:DEVICESTATUSRAW.FLNK",16777215,1,"PLC:UND0:PPS1:DEVICESTATUSRAW.FLNK")
#! Link("PLC:UND0:PPS1:DEVICESTATUSRAW.FLNK","PLC:UND0:PPS1:DEVICESTATUSCALC")
#! Field("PLC:UND0:PPS1:DEVICESTATUSRAW.INPA",16777215,0,"PLC:UND0:PPS1:DEVICESTATUSRAW.INPA")
#! Link("PLC:UND0:PPS1:DEVICESTATUSRAW.INPA","PLC:UND0:PPS1:STATUSRAW.VAL")
#! Field("PLC:UND0:PPS1:DEVICESTATUSRAW.VAL",16777215,1,"PLC:UND0:PPS1:DEVICESTATUSRAW.VAL")
#! Field("PLC:UND0:PPS1:DEVICESTATUSRAW.INPC",16777215,1,"PLC:UND0:PPS1:DEVICESTATUSRAW.INPC")
#! Link("PLC:UND0:PPS1:DEVICESTATUSRAW.INPC","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:DEVICESTATUS",3040,3926,0,0,"PLC:UND0:PPS1:DEVICESTATUS")
#! Field("PLC:UND0:PPS1:DEVICESTATUS.INP",16777215,0,"PLC:UND0:PPS1:DEVICESTATUS.INP")
#! Link("PLC:UND0:PPS1:DEVICESTATUS.INP","PLC:UND0:PPS1:DEVICESTATUSCALC.VAL")
#! Field("PLC:UND0:PPS1:DEVICESTATUS.FLNK",16777215,0,"PLC:UND0:PPS1:DEVICESTATUS.FLNK")
#! Link("PLC:UND0:PPS1:DEVICESTATUS.FLNK","PLC:UND0:PPS1:FAULTSTATUSRAW")
#! Field("PLC:UND0:PPS1:DEVICESTATUS.VAL",16777215,0,"PLC:UND0:PPS1:DEVICESTATUS.VAL")
#! Record("PLC:UND0:PPS1:FAULTSTATUSRAW",2480,4274,0,1,"PLC:UND0:PPS1:FAULTSTATUSRAW")
#! Field("PLC:UND0:PPS1:FAULTSTATUSRAW.FLNK",16777215,1,"PLC:UND0:PPS1:FAULTSTATUSRAW.FLNK")
#! Link("PLC:UND0:PPS1:FAULTSTATUSRAW.FLNK","PLC:UND0:PPS1:FAULTSTATUSCALC")
#! Field("PLC:UND0:PPS1:FAULTSTATUSRAW.INPA",16777215,0,"PLC:UND0:PPS1:FAULTSTATUSRAW.INPA")
#! Link("PLC:UND0:PPS1:FAULTSTATUSRAW.INPA","PLC:UND0:PPS1:STATUSRAW.VAL")
#! Field("PLC:UND0:PPS1:FAULTSTATUSRAW.VAL",16777215,1,"PLC:UND0:PPS1:FAULTSTATUSRAW.VAL")
#! Field("PLC:UND0:PPS1:FAULTSTATUSRAW.INPC",16777215,1,"PLC:UND0:PPS1:FAULTSTATUSRAW.INPC")
#! Link("PLC:UND0:PPS1:FAULTSTATUSRAW.INPC","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:FAULTSTATUSCALC",2760,4225,0,0,"PLC:UND0:PPS1:FAULTSTATUSCALC")
#! Field("PLC:UND0:PPS1:FAULTSTATUSCALC.FLNK",16777215,1,"PLC:UND0:PPS1:FAULTSTATUSCALC.FLNK")
#! Link("PLC:UND0:PPS1:FAULTSTATUSCALC.FLNK","PLC:UND0:PPS1:FAULTSTATUS")
#! Field("PLC:UND0:PPS1:FAULTSTATUSCALC.INPA",16777215,0,"PLC:UND0:PPS1:FAULTSTATUSCALC.INPA")
#! Link("PLC:UND0:PPS1:FAULTSTATUSCALC.INPA","PLC:UND0:PPS1:FAULTSTATUSRAW.VAL")
#! Field("PLC:UND0:PPS1:FAULTSTATUSCALC.VAL",16777215,1,"PLC:UND0:PPS1:FAULTSTATUSCALC.VAL")
#! Record("PLC:UND0:PPS1:FAULTSTATUS",3040,4254,0,0,"PLC:UND0:PPS1:FAULTSTATUS")
#! Field("PLC:UND0:PPS1:FAULTSTATUS.INP",16777215,0,"PLC:UND0:PPS1:FAULTSTATUS.INP")
#! Link("PLC:UND0:PPS1:FAULTSTATUS.INP","PLC:UND0:PPS1:FAULTSTATUSCALC.VAL")
#! Field("PLC:UND0:PPS1:FAULTSTATUS.FLNK",16777215,0,"PLC:UND0:PPS1:FAULTSTATUS.FLNK")
#! Link("PLC:UND0:PPS1:FAULTSTATUS.FLNK","PLC:UND0:PPS1:KEYSTATUSRAW")
#! Field("PLC:UND0:PPS1:FAULTSTATUS.VAL",16777215,0,"PLC:UND0:PPS1:FAULTSTATUS.VAL")
#! Record("PLC:UND0:PPS1:KEYSTATUSRAW",2480,4594,0,1,"PLC:UND0:PPS1:KEYSTATUSRAW")
#! Field("PLC:UND0:PPS1:KEYSTATUSRAW.FLNK",16777215,1,"PLC:UND0:PPS1:KEYSTATUSRAW.FLNK")
#! Link("PLC:UND0:PPS1:KEYSTATUSRAW.FLNK","PLC:UND0:PPS1:KEYSTATUSCALC")
#! Field("PLC:UND0:PPS1:KEYSTATUSRAW.INPA",16777215,0,"PLC:UND0:PPS1:KEYSTATUSRAW.INPA")
#! Link("PLC:UND0:PPS1:KEYSTATUSRAW.INPA","PLC:UND0:PPS1:STATUSRAW.VAL")
#! Field("PLC:UND0:PPS1:KEYSTATUSRAW.VAL",16777215,1,"PLC:UND0:PPS1:KEYSTATUSRAW.VAL")
#! Field("PLC:UND0:PPS1:KEYSTATUSRAW.INPC",16777215,1,"PLC:UND0:PPS1:KEYSTATUSRAW.INPC")
#! Link("PLC:UND0:PPS1:KEYSTATUSRAW.INPC","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:KEYSTATUSCALC",2760,4579,0,0,"PLC:UND0:PPS1:KEYSTATUSCALC")
#! Field("PLC:UND0:PPS1:KEYSTATUSCALC.FLNK",16777215,1,"PLC:UND0:PPS1:KEYSTATUSCALC.FLNK")
#! Link("PLC:UND0:PPS1:KEYSTATUSCALC.FLNK","PLC:UND0:PPS1:KEYSTATUS")
#! Field("PLC:UND0:PPS1:KEYSTATUSCALC.INPA",16777215,0,"PLC:UND0:PPS1:KEYSTATUSCALC.INPA")
#! Link("PLC:UND0:PPS1:KEYSTATUSCALC.INPA","PLC:UND0:PPS1:KEYSTATUSRAW.VAL")
#! Field("PLC:UND0:PPS1:KEYSTATUSCALC.VAL",16777215,1,"PLC:UND0:PPS1:KEYSTATUSCALC.VAL")
#! Record("PLC:UND0:PPS1:KEYSTATUS",3040,4577,0,0,"PLC:UND0:PPS1:KEYSTATUS")
#! Field("PLC:UND0:PPS1:KEYSTATUS.INP",16777215,0,"PLC:UND0:PPS1:KEYSTATUS.INP")
#! Link("PLC:UND0:PPS1:KEYSTATUS.INP","PLC:UND0:PPS1:KEYSTATUSCALC.VAL")
#! Field("PLC:UND0:PPS1:KEYSTATUS.VAL",16777215,0,"PLC:UND0:PPS1:KEYSTATUS.VAL")
#! Record("PLC:UND0:PPS1:MAJORFAULTRAW",4020,2427,0,0,"PLC:UND0:PPS1:MAJORFAULTRAW")
#! Field("PLC:UND0:PPS1:MAJORFAULTRAW.FLNK",16777215,1,"PLC:UND0:PPS1:MAJORFAULTRAW.FLNK")
#! Link("PLC:UND0:PPS1:MAJORFAULTRAW.FLNK","PLC:UND0:PPS1:FAULTPOWERCALC")
#! Field("PLC:UND0:PPS1:MAJORFAULTRAW.VAL",16777215,1,"PLC:UND0:PPS1:MAJORFAULTRAW.VAL")
#! Record("PLC:UND0:PPS1:MINORFAULTRAW",4000,2622,0,0,"PLC:UND0:PPS1:MINORFAULTRAW")
#! Field("PLC:UND0:PPS1:MINORFAULTRAW.VAL",16777215,1,"PLC:UND0:PPS1:MINORFAULTRAW.VAL")
#! Record("PLC:UND0:PPS1:FAULTPOWERCALC",4360,2559,0,0,"PLC:UND0:PPS1:FAULTPOWERCALC")
#! Field("PLC:UND0:PPS1:FAULTPOWERCALC.INPA",16777215,0,"PLC:UND0:PPS1:FAULTPOWERCALC.INPA")
#! Link("PLC:UND0:PPS1:FAULTPOWERCALC.INPA","PLC:UND0:PPS1:MAJORFAULTRAW.VAL")
#! Field("PLC:UND0:PPS1:FAULTPOWERCALC.INPB",16777215,0,"PLC:UND0:PPS1:FAULTPOWERCALC.INPB")
#! Link("PLC:UND0:PPS1:FAULTPOWERCALC.INPB","PLC:UND0:PPS1:MINORFAULTRAW.VAL")
#! Field("PLC:UND0:PPS1:FAULTPOWERCALC.FLNK",16777215,1,"PLC:UND0:PPS1:FAULTPOWERCALC.FLNK")
#! Link("PLC:UND0:PPS1:FAULTPOWERCALC.FLNK","PLC:UND0:PPS1:FAULTPOWER")
#! Field("PLC:UND0:PPS1:FAULTPOWERCALC.VAL",16777215,1,"PLC:UND0:PPS1:FAULTPOWERCALC.VAL")
#! Field("PLC:UND0:PPS1:FAULTPOWERCALC.INPD",16777215,0,"PLC:UND0:PPS1:FAULTPOWERCALC.INPD")
#! Link("PLC:UND0:PPS1:FAULTPOWERCALC.INPD","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:FAULTPOWER",4640,2590,0,0,"PLC:UND0:PPS1:FAULTPOWER")
#! Field("PLC:UND0:PPS1:FAULTPOWER.INP",16777215,0,"PLC:UND0:PPS1:FAULTPOWER.INP")
#! Link("PLC:UND0:PPS1:FAULTPOWER.INP","PLC:UND0:PPS1:FAULTPOWERCALC.VAL")
#! Field("PLC:UND0:PPS1:FAULTPOWER.FLNK",16777215,0,"PLC:UND0:PPS1:FAULTPOWER.FLNK")
#! Link("PLC:UND0:PPS1:FAULTPOWER.FLNK","PLC:UND0:PPS1:FAULTIOCALC")
#! Record("PLC:UND0:PPS1:FAULTIOCALC",4360,2799,0,1,"PLC:UND0:PPS1:FAULTIOCALC")
#! Field("PLC:UND0:PPS1:FAULTIOCALC.FLNK",16777215,1,"PLC:UND0:PPS1:FAULTIOCALC.FLNK")
#! Link("PLC:UND0:PPS1:FAULTIOCALC.FLNK","PLC:UND0:PPS1:FAULTIO")
#! Field("PLC:UND0:PPS1:FAULTIOCALC.INPA",16777215,0,"PLC:UND0:PPS1:FAULTIOCALC.INPA")
#! Link("PLC:UND0:PPS1:FAULTIOCALC.INPA","PLC:UND0:PPS1:MAJORFAULTRAW.VAL")
#! Field("PLC:UND0:PPS1:FAULTIOCALC.INPB",16777215,0,"PLC:UND0:PPS1:FAULTIOCALC.INPB")
#! Link("PLC:UND0:PPS1:FAULTIOCALC.INPB","PLC:UND0:PPS1:MINORFAULTRAW.VAL")
#! Field("PLC:UND0:PPS1:FAULTIOCALC.VAL",16777215,1,"PLC:UND0:PPS1:FAULTIOCALC.VAL")
#! Field("PLC:UND0:PPS1:FAULTIOCALC.INPD",16777215,0,"PLC:UND0:PPS1:FAULTIOCALC.INPD")
#! Link("PLC:UND0:PPS1:FAULTIOCALC.INPD","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:FAULTIO",4640,2830,0,0,"PLC:UND0:PPS1:FAULTIO")
#! Field("PLC:UND0:PPS1:FAULTIO.INP",16777215,0,"PLC:UND0:PPS1:FAULTIO.INP")
#! Link("PLC:UND0:PPS1:FAULTIO.INP","PLC:UND0:PPS1:FAULTIOCALC.VAL")
#! Field("PLC:UND0:PPS1:FAULTIO.FLNK",16777215,0,"PLC:UND0:PPS1:FAULTIO.FLNK")
#! Link("PLC:UND0:PPS1:FAULTIO.FLNK","PLC:UND0:PPS1:FAULTPROGRAMCALC")
#! Record("PLC:UND0:PPS1:FAULTPROGRAMCALC",4360,3039,0,1,"PLC:UND0:PPS1:FAULTPROGRAMCALC")
#! Field("PLC:UND0:PPS1:FAULTPROGRAMCALC.FLNK",16777215,1,"PLC:UND0:PPS1:FAULTPROGRAMCALC.FLNK")
#! Link("PLC:UND0:PPS1:FAULTPROGRAMCALC.FLNK","PLC:UND0:PPS1:FAULTPROGRAM")
#! Field("PLC:UND0:PPS1:FAULTPROGRAMCALC.INPA",16777215,0,"PLC:UND0:PPS1:FAULTPROGRAMCALC.INPA")
#! Link("PLC:UND0:PPS1:FAULTPROGRAMCALC.INPA","PLC:UND0:PPS1:MAJORFAULTRAW.VAL")
#! Field("PLC:UND0:PPS1:FAULTPROGRAMCALC.INPB",16777215,0,"PLC:UND0:PPS1:FAULTPROGRAMCALC.INPB")
#! Link("PLC:UND0:PPS1:FAULTPROGRAMCALC.INPB","PLC:UND0:PPS1:MINORFAULTRAW.VAL")
#! Field("PLC:UND0:PPS1:FAULTPROGRAMCALC.VAL",16777215,1,"PLC:UND0:PPS1:FAULTPROGRAMCALC.VAL")
#! Field("PLC:UND0:PPS1:FAULTPROGRAMCALC.INPD",16777215,0,"PLC:UND0:PPS1:FAULTPROGRAMCALC.INPD")
#! Link("PLC:UND0:PPS1:FAULTPROGRAMCALC.INPD","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:FAULTPROGRAM",4640,3070,0,0,"PLC:UND0:PPS1:FAULTPROGRAM")
#! Field("PLC:UND0:PPS1:FAULTPROGRAM.INP",16777215,0,"PLC:UND0:PPS1:FAULTPROGRAM.INP")
#! Link("PLC:UND0:PPS1:FAULTPROGRAM.INP","PLC:UND0:PPS1:FAULTPROGRAMCALC.VAL")
#! Field("PLC:UND0:PPS1:FAULTPROGRAM.FLNK",16777215,0,"PLC:UND0:PPS1:FAULTPROGRAM.FLNK")
#! Link("PLC:UND0:PPS1:FAULTPROGRAM.FLNK","PLC:UND0:PPS1:FAULTFLTHNDLCALC")
#! Record("PLC:UND0:PPS1:FAULTFLTHNDL",4640,3310,0,0,"PLC:UND0:PPS1:FAULTFLTHNDL")
#! Field("PLC:UND0:PPS1:FAULTFLTHNDL.INP",16777215,0,"PLC:UND0:PPS1:FAULTFLTHNDL.INP")
#! Link("PLC:UND0:PPS1:FAULTFLTHNDL.INP","PLC:UND0:PPS1:FAULTFLTHNDLCALC.VAL")
#! Field("PLC:UND0:PPS1:FAULTFLTHNDL.FLNK",16777215,0,"PLC:UND0:PPS1:FAULTFLTHNDL.FLNK")
#! Link("PLC:UND0:PPS1:FAULTFLTHNDL.FLNK","PLC:UND0:PPS1:FAULTWTCHDOGCALC")
#! Record("PLC:UND0:PPS1:FAULTFLTHNDLCALC",4360,3279,0,1,"PLC:UND0:PPS1:FAULTFLTHNDLCALC")
#! Field("PLC:UND0:PPS1:FAULTFLTHNDLCALC.FLNK",16777215,1,"PLC:UND0:PPS1:FAULTFLTHNDLCALC.FLNK")
#! Link("PLC:UND0:PPS1:FAULTFLTHNDLCALC.FLNK","PLC:UND0:PPS1:FAULTFLTHNDL")
#! Field("PLC:UND0:PPS1:FAULTFLTHNDLCALC.INPA",16777215,0,"PLC:UND0:PPS1:FAULTFLTHNDLCALC.INPA")
#! Link("PLC:UND0:PPS1:FAULTFLTHNDLCALC.INPA","PLC:UND0:PPS1:MAJORFAULTRAW.VAL")
#! Field("PLC:UND0:PPS1:FAULTFLTHNDLCALC.INPB",16777215,0,"PLC:UND0:PPS1:FAULTFLTHNDLCALC.INPB")
#! Link("PLC:UND0:PPS1:FAULTFLTHNDLCALC.INPB","PLC:UND0:PPS1:MINORFAULTRAW.VAL")
#! Field("PLC:UND0:PPS1:FAULTFLTHNDLCALC.VAL",16777215,1,"PLC:UND0:PPS1:FAULTFLTHNDLCALC.VAL")
#! Field("PLC:UND0:PPS1:FAULTFLTHNDLCALC.INPD",16777215,0,"PLC:UND0:PPS1:FAULTFLTHNDLCALC.INPD")
#! Link("PLC:UND0:PPS1:FAULTFLTHNDLCALC.INPD","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:FAULTWTCHDOGCALC",4360,3499,0,1,"PLC:UND0:PPS1:FAULTWTCHDOGCALC")
#! Field("PLC:UND0:PPS1:FAULTWTCHDOGCALC.FLNK",16777215,1,"PLC:UND0:PPS1:FAULTWTCHDOGCALC.FLNK")
#! Link("PLC:UND0:PPS1:FAULTWTCHDOGCALC.FLNK","PLC:UND0:PPS1:FAULTWTCHDOG")
#! Field("PLC:UND0:PPS1:FAULTWTCHDOGCALC.INPA",16777215,0,"PLC:UND0:PPS1:FAULTWTCHDOGCALC.INPA")
#! Link("PLC:UND0:PPS1:FAULTWTCHDOGCALC.INPA","PLC:UND0:PPS1:MAJORFAULTRAW.VAL")
#! Field("PLC:UND0:PPS1:FAULTWTCHDOGCALC.INPB",16777215,0,"PLC:UND0:PPS1:FAULTWTCHDOGCALC.INPB")
#! Link("PLC:UND0:PPS1:FAULTWTCHDOGCALC.INPB","PLC:UND0:PPS1:MINORFAULTRAW.VAL")
#! Field("PLC:UND0:PPS1:FAULTWTCHDOGCALC.VAL",16777215,1,"PLC:UND0:PPS1:FAULTWTCHDOGCALC.VAL")
#! Field("PLC:UND0:PPS1:FAULTWTCHDOGCALC.INPD",16777215,0,"PLC:UND0:PPS1:FAULTWTCHDOGCALC.INPD")
#! Link("PLC:UND0:PPS1:FAULTWTCHDOGCALC.INPD","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:FAULTWTCHDOG",4640,3530,0,0,"PLC:UND0:PPS1:FAULTWTCHDOG")
#! Field("PLC:UND0:PPS1:FAULTWTCHDOG.INP",16777215,0,"PLC:UND0:PPS1:FAULTWTCHDOG.INP")
#! Link("PLC:UND0:PPS1:FAULTWTCHDOG.INP","PLC:UND0:PPS1:FAULTWTCHDOGCALC.VAL")
#! Field("PLC:UND0:PPS1:FAULTWTCHDOG.FLNK",16777215,0,"PLC:UND0:PPS1:FAULTWTCHDOG.FLNK")
#! Link("PLC:UND0:PPS1:FAULTWTCHDOG.FLNK","PLC:UND0:PPS1:FAULTSTACKCALC")
#! Record("PLC:UND0:PPS1:FAULTSTACKCALC",4360,3719,0,1,"PLC:UND0:PPS1:FAULTSTACKCALC")
#! Field("PLC:UND0:PPS1:FAULTSTACKCALC.FLNK",16777215,1,"PLC:UND0:PPS1:FAULTSTACKCALC.FLNK")
#! Link("PLC:UND0:PPS1:FAULTSTACKCALC.FLNK","PLC:UND0:PPS1:FAULTSTACK")
#! Field("PLC:UND0:PPS1:FAULTSTACKCALC.INPA",16777215,0,"PLC:UND0:PPS1:FAULTSTACKCALC.INPA")
#! Link("PLC:UND0:PPS1:FAULTSTACKCALC.INPA","PLC:UND0:PPS1:MAJORFAULTRAW.VAL")
#! Field("PLC:UND0:PPS1:FAULTSTACKCALC.INPB",16777215,0,"PLC:UND0:PPS1:FAULTSTACKCALC.INPB")
#! Link("PLC:UND0:PPS1:FAULTSTACKCALC.INPB","PLC:UND0:PPS1:MINORFAULTRAW.VAL")
#! Field("PLC:UND0:PPS1:FAULTSTACKCALC.VAL",16777215,1,"PLC:UND0:PPS1:FAULTSTACKCALC.VAL")
#! Field("PLC:UND0:PPS1:FAULTSTACKCALC.INPD",16777215,0,"PLC:UND0:PPS1:FAULTSTACKCALC.INPD")
#! Link("PLC:UND0:PPS1:FAULTSTACKCALC.INPD","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:FAULTSTACK",4640,3750,0,0,"PLC:UND0:PPS1:FAULTSTACK")
#! Field("PLC:UND0:PPS1:FAULTSTACK.INP",16777215,0,"PLC:UND0:PPS1:FAULTSTACK.INP")
#! Link("PLC:UND0:PPS1:FAULTSTACK.INP","PLC:UND0:PPS1:FAULTSTACKCALC.VAL")
#! Field("PLC:UND0:PPS1:FAULTSTACK.FLNK",16777215,0,"PLC:UND0:PPS1:FAULTSTACK.FLNK")
#! Link("PLC:UND0:PPS1:FAULTSTACK.FLNK","PLC:UND0:PPS1:FAULTMODECHGCALC")
#! Record("PLC:UND0:PPS1:FAULTMODECHGCALC",4360,3939,0,1,"PLC:UND0:PPS1:FAULTMODECHGCALC")
#! Field("PLC:UND0:PPS1:FAULTMODECHGCALC.FLNK",16777215,1,"PLC:UND0:PPS1:FAULTMODECHGCALC.FLNK")
#! Link("PLC:UND0:PPS1:FAULTMODECHGCALC.FLNK","PLC:UND0:PPS1:FAULTMODECHG")
#! Field("PLC:UND0:PPS1:FAULTMODECHGCALC.INPA",16777215,0,"PLC:UND0:PPS1:FAULTMODECHGCALC.INPA")
#! Link("PLC:UND0:PPS1:FAULTMODECHGCALC.INPA","PLC:UND0:PPS1:MAJORFAULTRAW.VAL")
#! Field("PLC:UND0:PPS1:FAULTMODECHGCALC.INPB",16777215,0,"PLC:UND0:PPS1:FAULTMODECHGCALC.INPB")
#! Link("PLC:UND0:PPS1:FAULTMODECHGCALC.INPB","PLC:UND0:PPS1:MINORFAULTRAW.VAL")
#! Field("PLC:UND0:PPS1:FAULTMODECHGCALC.VAL",16777215,1,"PLC:UND0:PPS1:FAULTMODECHGCALC.VAL")
#! Field("PLC:UND0:PPS1:FAULTMODECHGCALC.INPD",16777215,0,"PLC:UND0:PPS1:FAULTMODECHGCALC.INPD")
#! Link("PLC:UND0:PPS1:FAULTMODECHGCALC.INPD","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:FAULTMODECHG",4640,3970,0,0,"PLC:UND0:PPS1:FAULTMODECHG")
#! Field("PLC:UND0:PPS1:FAULTMODECHG.INP",16777215,0,"PLC:UND0:PPS1:FAULTMODECHG.INP")
#! Link("PLC:UND0:PPS1:FAULTMODECHG.INP","PLC:UND0:PPS1:FAULTMODECHGCALC.VAL")
#! Field("PLC:UND0:PPS1:FAULTMODECHG.FLNK",16777215,0,"PLC:UND0:PPS1:FAULTMODECHG.FLNK")
#! Link("PLC:UND0:PPS1:FAULTMODECHG.FLNK","PLC:UND0:PPS1:FAULTSERIALCALC")
#! Record("PLC:UND0:PPS1:FAULTSERIALCALC",4360,4159,0,1,"PLC:UND0:PPS1:FAULTSERIALCALC")
#! Field("PLC:UND0:PPS1:FAULTSERIALCALC.FLNK",16777215,1,"PLC:UND0:PPS1:FAULTSERIALCALC.FLNK")
#! Link("PLC:UND0:PPS1:FAULTSERIALCALC.FLNK","PLC:UND0:PPS1:FAULTSERIAL")
#! Field("PLC:UND0:PPS1:FAULTSERIALCALC.INPA",16777215,0,"PLC:UND0:PPS1:FAULTSERIALCALC.INPA")
#! Link("PLC:UND0:PPS1:FAULTSERIALCALC.INPA","PLC:UND0:PPS1:MAJORFAULTRAW.VAL")
#! Field("PLC:UND0:PPS1:FAULTSERIALCALC.INPB",16777215,0,"PLC:UND0:PPS1:FAULTSERIALCALC.INPB")
#! Link("PLC:UND0:PPS1:FAULTSERIALCALC.INPB","PLC:UND0:PPS1:MINORFAULTRAW.VAL")
#! Field("PLC:UND0:PPS1:FAULTSERIALCALC.VAL",16777215,1,"PLC:UND0:PPS1:FAULTSERIALCALC.VAL")
#! Field("PLC:UND0:PPS1:FAULTSERIALCALC.INPD",16777215,0,"PLC:UND0:PPS1:FAULTSERIALCALC.INPD")
#! Link("PLC:UND0:PPS1:FAULTSERIALCALC.INPD","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:FAULTSERIAL",4640,4190,0,0,"PLC:UND0:PPS1:FAULTSERIAL")
#! Field("PLC:UND0:PPS1:FAULTSERIAL.INP",16777215,0,"PLC:UND0:PPS1:FAULTSERIAL.INP")
#! Link("PLC:UND0:PPS1:FAULTSERIAL.INP","PLC:UND0:PPS1:FAULTSERIALCALC.VAL")
#! Field("PLC:UND0:PPS1:FAULTSERIAL.FLNK",16777215,0,"PLC:UND0:PPS1:FAULTSERIAL.FLNK")
#! Link("PLC:UND0:PPS1:FAULTSERIAL.FLNK","PLC:UND0:PPS1:FAULTBATTERYCALC")
#! Record("PLC:UND0:PPS1:FAULTBATTERY",4640,4410,0,0,"PLC:UND0:PPS1:FAULTBATTERY")
#! Field("PLC:UND0:PPS1:FAULTBATTERY.INP",16777215,0,"PLC:UND0:PPS1:FAULTBATTERY.INP")
#! Link("PLC:UND0:PPS1:FAULTBATTERY.INP","PLC:UND0:PPS1:FAULTBATTERYCALC.VAL")
#! Field("PLC:UND0:PPS1:FAULTBATTERY.FLNK",16777215,0,"PLC:UND0:PPS1:FAULTBATTERY.FLNK")
#! Link("PLC:UND0:PPS1:FAULTBATTERY.FLNK","PLC:UND0:PPS1:FAULTMOTIONCALC")
#! Record("PLC:UND0:PPS1:FAULTBATTERYCALC",4360,4379,0,1,"PLC:UND0:PPS1:FAULTBATTERYCALC")
#! Field("PLC:UND0:PPS1:FAULTBATTERYCALC.FLNK",16777215,1,"PLC:UND0:PPS1:FAULTBATTERYCALC.FLNK")
#! Link("PLC:UND0:PPS1:FAULTBATTERYCALC.FLNK","PLC:UND0:PPS1:FAULTBATTERY")
#! Field("PLC:UND0:PPS1:FAULTBATTERYCALC.INPA",16777215,0,"PLC:UND0:PPS1:FAULTBATTERYCALC.INPA")
#! Link("PLC:UND0:PPS1:FAULTBATTERYCALC.INPA","PLC:UND0:PPS1:MAJORFAULTRAW.VAL")
#! Field("PLC:UND0:PPS1:FAULTBATTERYCALC.INPB",16777215,0,"PLC:UND0:PPS1:FAULTBATTERYCALC.INPB")
#! Link("PLC:UND0:PPS1:FAULTBATTERYCALC.INPB","PLC:UND0:PPS1:MINORFAULTRAW.VAL")
#! Field("PLC:UND0:PPS1:FAULTBATTERYCALC.VAL",16777215,1,"PLC:UND0:PPS1:FAULTBATTERYCALC.VAL")
#! Field("PLC:UND0:PPS1:FAULTBATTERYCALC.INPD",16777215,0,"PLC:UND0:PPS1:FAULTBATTERYCALC.INPD")
#! Link("PLC:UND0:PPS1:FAULTBATTERYCALC.INPD","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:FAULTMOTIONCALC",4360,4599,0,1,"PLC:UND0:PPS1:FAULTMOTIONCALC")
#! Field("PLC:UND0:PPS1:FAULTMOTIONCALC.FLNK",16777215,1,"PLC:UND0:PPS1:FAULTMOTIONCALC.FLNK")
#! Link("PLC:UND0:PPS1:FAULTMOTIONCALC.FLNK","PLC:UND0:PPS1:FAULTMOTION")
#! Field("PLC:UND0:PPS1:FAULTMOTIONCALC.INPA",16777215,0,"PLC:UND0:PPS1:FAULTMOTIONCALC.INPA")
#! Link("PLC:UND0:PPS1:FAULTMOTIONCALC.INPA","PLC:UND0:PPS1:MAJORFAULTRAW.VAL")
#! Field("PLC:UND0:PPS1:FAULTMOTIONCALC.INPB",16777215,0,"PLC:UND0:PPS1:FAULTMOTIONCALC.INPB")
#! Link("PLC:UND0:PPS1:FAULTMOTIONCALC.INPB","PLC:UND0:PPS1:MINORFAULTRAW.VAL")
#! Field("PLC:UND0:PPS1:FAULTMOTIONCALC.VAL",16777215,1,"PLC:UND0:PPS1:FAULTMOTIONCALC.VAL")
#! Field("PLC:UND0:PPS1:FAULTMOTIONCALC.INPD",16777215,0,"PLC:UND0:PPS1:FAULTMOTIONCALC.INPD")
#! Link("PLC:UND0:PPS1:FAULTMOTIONCALC.INPD","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:FAULTMOTION",4640,4645,0,0,"PLC:UND0:PPS1:FAULTMOTION")
#! Field("PLC:UND0:PPS1:FAULTMOTION.INP",16777215,0,"PLC:UND0:PPS1:FAULTMOTION.INP")
#! Link("PLC:UND0:PPS1:FAULTMOTION.INP","PLC:UND0:PPS1:FAULTMOTIONCALC.VAL")
#! Record("PLC:UND0:PPS1:VERSIONMAJORDES",2160,2867,0,1,"PLC:UND0:PPS1:VERSIONMAJORDES")
#! Field("PLC:UND0:PPS1:VERSIONMAJORDES.FLNK",16777215,1,"PLC:UND0:PPS1:VERSIONMAJORDES.FLNK")
#! Link("PLC:UND0:PPS1:VERSIONMAJORDES.FLNK","PLC:UND0:PPS1:VERSIONMAJORCALCHI")
#! Field("PLC:UND0:PPS1:VERSIONMAJORDES.VAL",16777215,1,"PLC:UND0:PPS1:VERSIONMAJORDES.VAL")
#! Record("PLC:UND0:PPS1:VERSIONMAJORCALCHI",2420,2687,0,0,"PLC:UND0:PPS1:VERSIONMAJORCALCHI")
#! Field("PLC:UND0:PPS1:VERSIONMAJORCALCHI.INPA",16777215,0,"PLC:UND0:PPS1:VERSIONMAJORCALCHI.INPA")
#! Link("PLC:UND0:PPS1:VERSIONMAJORCALCHI.INPA","PLC:UND0:PPS1:VERSIONMAJORDES.VAL")
#! Field("PLC:UND0:PPS1:VERSIONMAJORCALCHI.OUT",16777215,1,"PLC:UND0:PPS1:VERSIONMAJORCALCHI.OUT")
#! Link("PLC:UND0:PPS1:VERSIONMAJORCALCHI.OUT","PLC:UND0:PPS1:VERSIONMAJOR.HIGH")
#! Field("PLC:UND0:PPS1:VERSIONMAJORCALCHI.FLNK",16777215,1,"PLC:UND0:PPS1:VERSIONMAJORCALCHI.FLNK")
#! Link("PLC:UND0:PPS1:VERSIONMAJORCALCHI.FLNK","PLC:UND0:PPS1:VERSIONMAJORCALCLO")
#! Record("PLC:UND0:PPS1:VERSIONMAJORCALCLO",2460,2922,0,1,"PLC:UND0:PPS1:VERSIONMAJORCALCLO")
#! Field("PLC:UND0:PPS1:VERSIONMAJORCALCLO.INPA",16777215,0,"PLC:UND0:PPS1:VERSIONMAJORCALCLO.INPA")
#! Link("PLC:UND0:PPS1:VERSIONMAJORCALCLO.INPA","PLC:UND0:PPS1:VERSIONMAJORDES.VAL")
#! Field("PLC:UND0:PPS1:VERSIONMAJORCALCLO.OUT",16777215,1,"PLC:UND0:PPS1:VERSIONMAJORCALCLO.OUT")
#! Link("PLC:UND0:PPS1:VERSIONMAJORCALCLO.OUT","PLC:UND0:PPS1:VERSIONMAJOR.LOW")
#! Record("PLC:UND0:PPS1:VERSIONMINORDES",2160,3147,0,1,"PLC:UND0:PPS1:VERSIONMINORDES")
#! Field("PLC:UND0:PPS1:VERSIONMINORDES.FLNK",16777215,1,"PLC:UND0:PPS1:VERSIONMINORDES.FLNK")
#! Link("PLC:UND0:PPS1:VERSIONMINORDES.FLNK","PLC:UND0:PPS1:VERSIONMINORCALCHI")
#! Field("PLC:UND0:PPS1:VERSIONMINORDES.VAL",16777215,1,"PLC:UND0:PPS1:VERSIONMINORDES.VAL")
#! Record("PLC:UND0:PPS1:VERSIONMINORCALCLO",2480,3322,0,1,"PLC:UND0:PPS1:VERSIONMINORCALCLO")
#! Field("PLC:UND0:PPS1:VERSIONMINORCALCLO.INPA",16777215,0,"PLC:UND0:PPS1:VERSIONMINORCALCLO.INPA")
#! Link("PLC:UND0:PPS1:VERSIONMINORCALCLO.INPA","PLC:UND0:PPS1:VERSIONMINORDES.VAL")
#! Field("PLC:UND0:PPS1:VERSIONMINORCALCLO.OUT",16777215,1,"PLC:UND0:PPS1:VERSIONMINORCALCLO.OUT")
#! Link("PLC:UND0:PPS1:VERSIONMINORCALCLO.OUT","PLC:UND0:PPS1:VERSIONMINOR.LOW")
#! Record("PLC:UND0:PPS1:VERSIONMINORCALCHI",2440,3087,0,0,"PLC:UND0:PPS1:VERSIONMINORCALCHI")
#! Field("PLC:UND0:PPS1:VERSIONMINORCALCHI.FLNK",16777215,1,"PLC:UND0:PPS1:VERSIONMINORCALCHI.FLNK")
#! Link("PLC:UND0:PPS1:VERSIONMINORCALCHI.FLNK","PLC:UND0:PPS1:VERSIONMINORCALCLO")
#! Field("PLC:UND0:PPS1:VERSIONMINORCALCHI.INPA",16777215,0,"PLC:UND0:PPS1:VERSIONMINORCALCHI.INPA")
#! Link("PLC:UND0:PPS1:VERSIONMINORCALCHI.INPA","PLC:UND0:PPS1:VERSIONMINORDES.VAL")
#! Field("PLC:UND0:PPS1:VERSIONMINORCALCHI.OUT",16777215,1,"PLC:UND0:PPS1:VERSIONMINORCALCHI.OUT")
#! Link("PLC:UND0:PPS1:VERSIONMINORCALCHI.OUT","PLC:UND0:PPS1:VERSIONMINOR.HIGH")
#! Record("PLC:UND0:PPS1:VERSIONREVDES",2180,3547,0,1,"PLC:UND0:PPS1:VERSIONREVDES")
#! Field("PLC:UND0:PPS1:VERSIONREVDES.FLNK",16777215,1,"PLC:UND0:PPS1:VERSIONREVDES.FLNK")
#! Link("PLC:UND0:PPS1:VERSIONREVDES.FLNK","PLC:UND0:PPS1:VERSIONREVCALCHI")
#! Field("PLC:UND0:PPS1:VERSIONREVDES.VAL",16777215,1,"PLC:UND0:PPS1:VERSIONREVDES.VAL")
#! Record("PLC:UND0:PPS1:VERSIONREVCALCHI",2460,3487,0,0,"PLC:UND0:PPS1:VERSIONREVCALCHI")
#! Field("PLC:UND0:PPS1:VERSIONREVCALCHI.FLNK",16777215,1,"PLC:UND0:PPS1:VERSIONREVCALCHI.FLNK")
#! Link("PLC:UND0:PPS1:VERSIONREVCALCHI.FLNK","PLC:UND0:PPS1:VERSIONREVCALCLO")
#! Field("PLC:UND0:PPS1:VERSIONREVCALCHI.INPA",16777215,0,"PLC:UND0:PPS1:VERSIONREVCALCHI.INPA")
#! Link("PLC:UND0:PPS1:VERSIONREVCALCHI.INPA","PLC:UND0:PPS1:VERSIONREVDES.VAL")
#! Field("PLC:UND0:PPS1:VERSIONREVCALCHI.OUT",16777215,1,"PLC:UND0:PPS1:VERSIONREVCALCHI.OUT")
#! Link("PLC:UND0:PPS1:VERSIONREVCALCHI.OUT","PLC:UND0:PPS1:VERSIONREV.HIGH")
#! Record("PLC:UND0:PPS1:VERSIONREVCALCLO",2500,3722,0,1,"PLC:UND0:PPS1:VERSIONREVCALCLO")
#! Field("PLC:UND0:PPS1:VERSIONREVCALCLO.INPA",16777215,0,"PLC:UND0:PPS1:VERSIONREVCALCLO.INPA")
#! Link("PLC:UND0:PPS1:VERSIONREVCALCLO.INPA","PLC:UND0:PPS1:VERSIONREVDES.VAL")
#! Field("PLC:UND0:PPS1:VERSIONREVCALCLO.OUT",16777215,1,"PLC:UND0:PPS1:VERSIONREVCALCLO.OUT")
#! Link("PLC:UND0:PPS1:VERSIONREVCALCLO.OUT","PLC:UND0:PPS1:VERSIONREV.LOW")
#! Record("PLC:UND0:PPS1:HEARTBEATCALC",600,187,0,0,"PLC:UND0:PPS1:HEARTBEATCALC")
#! Field("PLC:UND0:PPS1:HEARTBEATCALC.INPA",16777215,0,"PLC:UND0:PPS1:HEARTBEATCALC.INPA")
#! Link("PLC:UND0:PPS1:HEARTBEATCALC.INPA","PLC:UND0:PPS1:HEARTBEATRAW.VAL")
#! Field("PLC:UND0:PPS1:HEARTBEATCALC.VAL",16777215,0,"PLC:UND0:PPS1:HEARTBEATCALC.VAL")
#! Field("PLC:UND0:PPS1:HEARTBEATCALC.INPB",16777215,0,"PLC:UND0:PPS1:HEARTBEATCALC.INPB")
#! Link("PLC:UND0:PPS1:HEARTBEATCALC.INPB","PLC:UND0:PPS1:HEARTBEATCALC.VAL")
#! Field("PLC:UND0:PPS1:HEARTBEATCALC.FLNK",16777215,1,"PLC:UND0:PPS1:HEARTBEATCALC.FLNK")
#! Link("PLC:UND0:PPS1:HEARTBEATCALC.FLNK","PLC:UND0:PPS1:HEARTBEATERR")
#! Field("PLC:UND0:PPS1:HEARTBEATCALC.A",16777215,1,"PLC:UND0:PPS1:HEARTBEATCALC.A")
#! Field("PLC:UND0:PPS1:HEARTBEATCALC.B",16777215,1,"PLC:UND0:PPS1:HEARTBEATCALC.B")
#! Record("PLC:UND0:PPS1:HEARTBEATOK",1600,299,0,0,"PLC:UND0:PPS1:HEARTBEATOK")
#! Field("PLC:UND0:PPS1:HEARTBEATOK.INP",16777215,0,"PLC:UND0:PPS1:HEARTBEATOK.INP")
#! Link("PLC:UND0:PPS1:HEARTBEATOK.INP","PLC:UND0:PPS1:HEARTBEATERR.VAL")
#! Field("PLC:UND0:PPS1:HEARTBEATOK.FLNK",16777215,0,"PLC:UND0:PPS1:HEARTBEATOK.FLNK")
#! Link("PLC:UND0:PPS1:HEARTBEATOK.FLNK","PLC:UND0:PPS1:HEARTBEATE01")
#! Record("PLC:UND0:PPS1:HEARTBEATERR",900,267,0,0,"PLC:UND0:PPS1:HEARTBEATERR")
#! Field("PLC:UND0:PPS1:HEARTBEATERR.INPA",16777215,0,"PLC:UND0:PPS1:HEARTBEATERR.INPA")
#! Link("PLC:UND0:PPS1:HEARTBEATERR.INPA","PLC:UND0:PPS1:HEARTBEATCALC.A")
#! Field("PLC:UND0:PPS1:HEARTBEATERR.INPB",16777215,0,"PLC:UND0:PPS1:HEARTBEATERR.INPB")
#! Link("PLC:UND0:PPS1:HEARTBEATERR.INPB","PLC:UND0:PPS1:HEARTBEATCALC.B")
#! Field("PLC:UND0:PPS1:HEARTBEATERR.FLNK",16777215,1,"PLC:UND0:PPS1:HEARTBEATERR.FLNK")
#! Link("PLC:UND0:PPS1:HEARTBEATERR.FLNK","PLC:UND0:PPS1:HEARTBEATOK")
#! Field("PLC:UND0:PPS1:HEARTBEATERR.VAL",16777215,1,"PLC:UND0:PPS1:HEARTBEATERR.VAL")
#! Record("PLC:UND0:PPS1:HEARTBEATECT",1740,1160,0,0,"PLC:UND0:PPS1:HEARTBEATECT")
#! Field("PLC:UND0:PPS1:HEARTBEATECT.INPA",16777215,0,"PLC:UND0:PPS1:HEARTBEATECT.INPA")
#! Link("PLC:UND0:PPS1:HEARTBEATECT.INPA","PLC:UND0:PPS1:HEARTBEATECT/INPA")
#! Field("PLC:UND0:PPS1:HEARTBEATECT.INPB",16777215,0,"PLC:UND0:PPS1:HEARTBEATECT.INPB")
#! Link("PLC:UND0:PPS1:HEARTBEATECT.INPB","PLC:UND0:PPS1:HEARTBEATECT/INPB")
#! Field("PLC:UND0:PPS1:HEARTBEATECT.INPC",16777215,0,"PLC:UND0:PPS1:HEARTBEATECT.INPC")
#! Link("PLC:UND0:PPS1:HEARTBEATECT.INPC","PLC:UND0:PPS1:HEARTBEATECT/INPC")
#! Field("PLC:UND0:PPS1:HEARTBEATECT.INPD",16777215,0,"PLC:UND0:PPS1:HEARTBEATECT.INPD")
#! Link("PLC:UND0:PPS1:HEARTBEATECT.INPD","PLC:UND0:PPS1:HEARTBEATECT/INPD")
#! Field("PLC:UND0:PPS1:HEARTBEATECT.INPE",16777215,0,"PLC:UND0:PPS1:HEARTBEATECT.INPE")
#! Link("PLC:UND0:PPS1:HEARTBEATECT.INPE","PLC:UND0:PPS1:HEARTBEATECT/INPE")
#! Field("PLC:UND0:PPS1:HEARTBEATECT.INPF",16777215,0,"PLC:UND0:PPS1:HEARTBEATECT.INPF")
#! Link("PLC:UND0:PPS1:HEARTBEATECT.INPF","PLC:UND0:PPS1:HEARTBEATECT/INPF")
#! Field("PLC:UND0:PPS1:HEARTBEATECT.INPG",16777215,0,"PLC:UND0:PPS1:HEARTBEATECT.INPG")
#! Link("PLC:UND0:PPS1:HEARTBEATECT.INPG","PLC:UND0:PPS1:HEARTBEATECT/INPG")
#! Field("PLC:UND0:PPS1:HEARTBEATECT.INPH",16777215,0,"PLC:UND0:PPS1:HEARTBEATECT.INPH")
#! Link("PLC:UND0:PPS1:HEARTBEATECT.INPH","PLC:UND0:PPS1:HEARTBEATECT/INPH")
#! Field("PLC:UND0:PPS1:HEARTBEATECT.INPI",16777215,0,"PLC:UND0:PPS1:HEARTBEATECT.INPI")
#! Link("PLC:UND0:PPS1:HEARTBEATECT.INPI","PLC:UND0:PPS1:HEARTBEATECT/INPI")
#! Field("PLC:UND0:PPS1:HEARTBEATECT.INPJ",16777215,0,"PLC:UND0:PPS1:HEARTBEATECT.INPJ")
#! Link("PLC:UND0:PPS1:HEARTBEATECT.INPJ","PLC:UND0:PPS1:HEARTBEATECT/INPJ")
#! Field("PLC:UND0:PPS1:HEARTBEATECT.FLNK",16777215,1,"PLC:UND0:PPS1:HEARTBEATECT.FLNK")
#! Link("PLC:UND0:PPS1:HEARTBEATECT.FLNK","PLC:UND0:PPS1:HEARTBEATSUM")
#! Field("PLC:UND0:PPS1:HEARTBEATECT.SEVR",16777215,1,"PLC:UND0:PPS1:HEARTBEATECT.SEVR")
#! Connector("PLC:UND0:PPS1:HEARTBEATECT/INPJ","PLC:UND0:PPS1:HEARTBEATE10.VAL",1600,2130,16777215,"",0)
#! Connector("PLC:UND0:PPS1:HEARTBEATECT/INPI","PLC:UND0:PPS1:HEARTBEATE09.VAL",1560,2020,16777215,"",0)
#! Connector("PLC:UND0:PPS1:HEARTBEATECT/INPH","PLC:UND0:PPS1:HEARTBEATE08.VAL",1520,1910,16777215,"",0)
#! Connector("PLC:UND0:PPS1:HEARTBEATECT/INPG","PLC:UND0:PPS1:HEARTBEATE07.VAL",1480,1790,16777215,"",0)
#! Connector("PLC:UND0:PPS1:HEARTBEATECT/INPF","PLC:UND0:PPS1:HEARTBEATE06.VAL",1280,1670,16777215,"",0)
#! Connector("PLC:UND0:PPS1:HEARTBEATECT/INPE","PLC:UND0:PPS1:HEARTBEATE05.VAL",1320,1550,16777215,"",0)
#! Connector("PLC:UND0:PPS1:HEARTBEATECT/INPD","PLC:UND0:PPS1:HEARTBEATE04.VAL",1360,1430,16777215,"",0)
#! Connector("PLC:UND0:PPS1:HEARTBEATECT/INPC","PLC:UND0:PPS1:HEARTBEATE03.VAL",1400,1310,16777215,"",0)
#! Connector("PLC:UND0:PPS1:HEARTBEATECT/INPB","PLC:UND0:PPS1:HEARTBEATE02.VAL",1440,1190,16777215,"",0)
#! Connector("PLC:UND0:PPS1:HEARTBEATECT/INPA","PLC:UND0:PPS1:HEARTBEATE01.VAL",1480,1070,16777215,"",0)
#! Record("PLC:UND0:PPS1:HEARTBEATE09",1060,2227,0,1,"PLC:UND0:PPS1:HEARTBEATE09")
#! Field("PLC:UND0:PPS1:HEARTBEATE09.INPA",16777215,0,"PLC:UND0:PPS1:HEARTBEATE09.INPA")
#! Link("PLC:UND0:PPS1:HEARTBEATE09.INPA","PLC:UND0:PPS1:HEARTBEATE08.B")
#! Field("PLC:UND0:PPS1:HEARTBEATE09.VAL",16777215,1,"PLC:UND0:PPS1:HEARTBEATE09.VAL")
#! Field("PLC:UND0:PPS1:HEARTBEATE09.FLNK",16777215,1,"PLC:UND0:PPS1:HEARTBEATE09.FLNK")
#! Link("PLC:UND0:PPS1:HEARTBEATE09.FLNK","PLC:UND0:PPS1:HEARTBEATE10")
#! Field("PLC:UND0:PPS1:HEARTBEATE09.INPB",16777215,0,"PLC:UND0:PPS1:HEARTBEATE09.INPB")
#! Link("PLC:UND0:PPS1:HEARTBEATE09.INPB","PLC:UND0:PPS1:HEARTBEATE09.VAL")
#! Field("PLC:UND0:PPS1:HEARTBEATE09.B",16777215,0,"PLC:UND0:PPS1:HEARTBEATE09.B")
#! Record("PLC:UND0:PPS1:HEARTBEATE08",1040,2007,0,1,"PLC:UND0:PPS1:HEARTBEATE08")
#! Field("PLC:UND0:PPS1:HEARTBEATE08.FLNK",16777215,1,"PLC:UND0:PPS1:HEARTBEATE08.FLNK")
#! Link("PLC:UND0:PPS1:HEARTBEATE08.FLNK","PLC:UND0:PPS1:HEARTBEATE09")
#! Field("PLC:UND0:PPS1:HEARTBEATE08.INPA",16777215,0,"PLC:UND0:PPS1:HEARTBEATE08.INPA")
#! Link("PLC:UND0:PPS1:HEARTBEATE08.INPA","PLC:UND0:PPS1:HEARTBEATE07.B")
#! Field("PLC:UND0:PPS1:HEARTBEATE08.VAL",16777215,1,"PLC:UND0:PPS1:HEARTBEATE08.VAL")
#! Field("PLC:UND0:PPS1:HEARTBEATE08.INPB",16777215,0,"PLC:UND0:PPS1:HEARTBEATE08.INPB")
#! Link("PLC:UND0:PPS1:HEARTBEATE08.INPB","PLC:UND0:PPS1:HEARTBEATE08.VAL")
#! Field("PLC:UND0:PPS1:HEARTBEATE08.B",16777215,0,"PLC:UND0:PPS1:HEARTBEATE08.B")
#! Record("PLC:UND0:PPS1:HEARTBEATE07",1020,1787,0,1,"PLC:UND0:PPS1:HEARTBEATE07")
#! Field("PLC:UND0:PPS1:HEARTBEATE07.FLNK",16777215,1,"PLC:UND0:PPS1:HEARTBEATE07.FLNK")
#! Link("PLC:UND0:PPS1:HEARTBEATE07.FLNK","PLC:UND0:PPS1:HEARTBEATE08")
#! Field("PLC:UND0:PPS1:HEARTBEATE07.INPA",16777215,0,"PLC:UND0:PPS1:HEARTBEATE07.INPA")
#! Link("PLC:UND0:PPS1:HEARTBEATE07.INPA","PLC:UND0:PPS1:HEARTBEATE06.B")
#! Field("PLC:UND0:PPS1:HEARTBEATE07.VAL",16777215,1,"PLC:UND0:PPS1:HEARTBEATE07.VAL")
#! Field("PLC:UND0:PPS1:HEARTBEATE07.INPB",16777215,0,"PLC:UND0:PPS1:HEARTBEATE07.INPB")
#! Link("PLC:UND0:PPS1:HEARTBEATE07.INPB","PLC:UND0:PPS1:HEARTBEATE07.VAL")
#! Field("PLC:UND0:PPS1:HEARTBEATE07.B",16777215,0,"PLC:UND0:PPS1:HEARTBEATE07.B")
#! Record("PLC:UND0:PPS1:HEARTBEATE06",1020,1567,0,1,"PLC:UND0:PPS1:HEARTBEATE06")
#! Field("PLC:UND0:PPS1:HEARTBEATE06.FLNK",16777215,1,"PLC:UND0:PPS1:HEARTBEATE06.FLNK")
#! Link("PLC:UND0:PPS1:HEARTBEATE06.FLNK","PLC:UND0:PPS1:HEARTBEATE05/FLNK")
#! Field("PLC:UND0:PPS1:HEARTBEATE06.INPA",16777215,0,"PLC:UND0:PPS1:HEARTBEATE06.INPA")
#! Link("PLC:UND0:PPS1:HEARTBEATE06.INPA","PLC:UND0:PPS1:HEARTBEATE05.B")
#! Field("PLC:UND0:PPS1:HEARTBEATE06.VAL",16777215,1,"PLC:UND0:PPS1:HEARTBEATE06.VAL")
#! Field("PLC:UND0:PPS1:HEARTBEATE06.INPB",16777215,0,"PLC:UND0:PPS1:HEARTBEATE06.INPB")
#! Link("PLC:UND0:PPS1:HEARTBEATE06.INPB","PLC:UND0:PPS1:HEARTBEATE06.VAL")
#! Field("PLC:UND0:PPS1:HEARTBEATE06.B",16777215,0,"PLC:UND0:PPS1:HEARTBEATE06.B")
#! Connector("PLC:UND0:PPS1:HEARTBEATE05/FLNK","PLC:UND0:PPS1:HEARTBEATE07",1260,1766,16777215,"",0)
#! Record("PLC:UND0:PPS1:HEARTBEATE05",1000,1347,0,1,"PLC:UND0:PPS1:HEARTBEATE05")
#! Field("PLC:UND0:PPS1:HEARTBEATE05.FLNK",16777215,1,"PLC:UND0:PPS1:HEARTBEATE05.FLNK")
#! Link("PLC:UND0:PPS1:HEARTBEATE05.FLNK","PLC:UND0:PPS1:HEARTBEATE06")
#! Field("PLC:UND0:PPS1:HEARTBEATE05.INPA",16777215,0,"PLC:UND0:PPS1:HEARTBEATE05.INPA")
#! Link("PLC:UND0:PPS1:HEARTBEATE05.INPA","PLC:UND0:PPS1:HEARTBEATE04.B")
#! Field("PLC:UND0:PPS1:HEARTBEATE05.VAL",16777215,1,"PLC:UND0:PPS1:HEARTBEATE05.VAL")
#! Field("PLC:UND0:PPS1:HEARTBEATE05.INPB",16777215,0,"PLC:UND0:PPS1:HEARTBEATE05.INPB")
#! Link("PLC:UND0:PPS1:HEARTBEATE05.INPB","PLC:UND0:PPS1:HEARTBEATE05.VAL")
#! Field("PLC:UND0:PPS1:HEARTBEATE05.B",16777215,0,"PLC:UND0:PPS1:HEARTBEATE05.B")
#! Record("PLC:UND0:PPS1:HEARTBEATE04",980,1127,0,1,"PLC:UND0:PPS1:HEARTBEATE04")
#! Field("PLC:UND0:PPS1:HEARTBEATE04.FLNK",16777215,1,"PLC:UND0:PPS1:HEARTBEATE04.FLNK")
#! Link("PLC:UND0:PPS1:HEARTBEATE04.FLNK","PLC:UND0:PPS1:HEARTBEATE05")
#! Field("PLC:UND0:PPS1:HEARTBEATE04.INPA",16777215,0,"PLC:UND0:PPS1:HEARTBEATE04.INPA")
#! Link("PLC:UND0:PPS1:HEARTBEATE04.INPA","PLC:UND0:PPS1:HEARTBEATE03.B")
#! Field("PLC:UND0:PPS1:HEARTBEATE04.VAL",16777215,1,"PLC:UND0:PPS1:HEARTBEATE04.VAL")
#! Field("PLC:UND0:PPS1:HEARTBEATE04.INPB",16777215,0,"PLC:UND0:PPS1:HEARTBEATE04.INPB")
#! Link("PLC:UND0:PPS1:HEARTBEATE04.INPB","PLC:UND0:PPS1:HEARTBEATE04.VAL")
#! Field("PLC:UND0:PPS1:HEARTBEATE04.B",16777215,0,"PLC:UND0:PPS1:HEARTBEATE04.B")
#! Record("PLC:UND0:PPS1:HEARTBEATE03",960,907,0,1,"PLC:UND0:PPS1:HEARTBEATE03")
#! Field("PLC:UND0:PPS1:HEARTBEATE03.FLNK",16777215,1,"PLC:UND0:PPS1:HEARTBEATE03.FLNK")
#! Link("PLC:UND0:PPS1:HEARTBEATE03.FLNK","PLC:UND0:PPS1:HEARTBEATE04")
#! Field("PLC:UND0:PPS1:HEARTBEATE03.INPA",16777215,0,"PLC:UND0:PPS1:HEARTBEATE03.INPA")
#! Link("PLC:UND0:PPS1:HEARTBEATE03.INPA","PLC:UND0:PPS1:HEARTBEATE02.B")
#! Field("PLC:UND0:PPS1:HEARTBEATE03.VAL",16777215,1,"PLC:UND0:PPS1:HEARTBEATE03.VAL")
#! Field("PLC:UND0:PPS1:HEARTBEATE03.INPB",16777215,0,"PLC:UND0:PPS1:HEARTBEATE03.INPB")
#! Link("PLC:UND0:PPS1:HEARTBEATE03.INPB","PLC:UND0:PPS1:HEARTBEATE03.VAL")
#! Field("PLC:UND0:PPS1:HEARTBEATE03.B",16777215,0,"PLC:UND0:PPS1:HEARTBEATE03.B")
#! Record("PLC:UND0:PPS1:HEARTBEATE02",940,687,0,1,"PLC:UND0:PPS1:HEARTBEATE02")
#! Field("PLC:UND0:PPS1:HEARTBEATE02.FLNK",16777215,1,"PLC:UND0:PPS1:HEARTBEATE02.FLNK")
#! Link("PLC:UND0:PPS1:HEARTBEATE02.FLNK","PLC:UND0:PPS1:HEARTBEATE03")
#! Field("PLC:UND0:PPS1:HEARTBEATE02.INPA",16777215,0,"PLC:UND0:PPS1:HEARTBEATE02.INPA")
#! Link("PLC:UND0:PPS1:HEARTBEATE02.INPA","PLC:UND0:PPS1:HEARTBEATE01.B")
#! Field("PLC:UND0:PPS1:HEARTBEATE02.VAL",16777215,1,"PLC:UND0:PPS1:HEARTBEATE02.VAL")
#! Field("PLC:UND0:PPS1:HEARTBEATE02.INPB",16777215,0,"PLC:UND0:PPS1:HEARTBEATE02.INPB")
#! Link("PLC:UND0:PPS1:HEARTBEATE02.INPB","PLC:UND0:PPS1:HEARTBEATE02.VAL")
#! Field("PLC:UND0:PPS1:HEARTBEATE02.B",16777215,0,"PLC:UND0:PPS1:HEARTBEATE02.B")
#! Record("PLC:UND0:PPS1:HEARTBEATE01",900,467,0,1,"PLC:UND0:PPS1:HEARTBEATE01")
#! Field("PLC:UND0:PPS1:HEARTBEATE01.INPA",16777215,0,"PLC:UND0:PPS1:HEARTBEATE01.INPA")
#! Link("PLC:UND0:PPS1:HEARTBEATE01.INPA","PLC:UND0:PPS1:HEARTBEATERR.VAL")
#! Field("PLC:UND0:PPS1:HEARTBEATE01.FLNK",16777215,1,"PLC:UND0:PPS1:HEARTBEATE01.FLNK")
#! Link("PLC:UND0:PPS1:HEARTBEATE01.FLNK","PLC:UND0:PPS1:HEARTBEATE02")
#! Field("PLC:UND0:PPS1:HEARTBEATE01.VAL",16777215,1,"PLC:UND0:PPS1:HEARTBEATE01.VAL")
#! Field("PLC:UND0:PPS1:HEARTBEATE01.INPB",16777215,0,"PLC:UND0:PPS1:HEARTBEATE01.INPB")
#! Link("PLC:UND0:PPS1:HEARTBEATE01.INPB","PLC:UND0:PPS1:HEARTBEATE01.VAL")
#! Field("PLC:UND0:PPS1:HEARTBEATE01.B",16777215,0,"PLC:UND0:PPS1:HEARTBEATE01.B")
#! Record("PLC:UND0:PPS1:HEARTBEATCLC",3300,1847,0,0,"PLC:UND0:PPS1:HEARTBEATCLC")
#! Field("PLC:UND0:PPS1:HEARTBEATCLC.INPA",16777215,0,"PLC:UND0:PPS1:HEARTBEATCLC.INPA")
#! Link("PLC:UND0:PPS1:HEARTBEATCLC.INPA","PLC:UND0:PPS1:HEARTBEATECT.SEVR")
#! Field("PLC:UND0:PPS1:HEARTBEATCLC.VAL",16777215,1,"PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:HEARTBEATSUM",2080,1690,0,0,"PLC:UND0:PPS1:HEARTBEATSUM")
#! Field("PLC:UND0:PPS1:HEARTBEATSUM.INP",16777215,0,"PLC:UND0:PPS1:HEARTBEATSUM.INP")
#! Link("PLC:UND0:PPS1:HEARTBEATSUM.INP","PLC:UND0:PPS1:HEARTBEATECT.SEVR")
#! Field("PLC:UND0:PPS1:HEARTBEATSUM.FLNK",16777215,1,"PLC:UND0:PPS1:HEARTBEATSUM.FLNK")
#! Link("PLC:UND0:PPS1:HEARTBEATSUM.FLNK","PLC:UND0:PPS1:HEARTBEATCLC")
#! Field("PLC:UND0:PPS1:HEARTBEATSUM.VAL",16777215,0,"PLC:UND0:PPS1:HEARTBEATSUM.VAL")
#! Record("PLC:UND0:PPS1:UPTIMEDAYRAW",4280,1587,0,0,"PLC:UND0:PPS1:UPTIMEDAYRAW")
#! Field("PLC:UND0:PPS1:UPTIMEDAYRAW.FLNK",16777215,1,"PLC:UND0:PPS1:UPTIMEDAYRAW.FLNK")
#! Link("PLC:UND0:PPS1:UPTIMEDAYRAW.FLNK","PLC:UND0:PPS1:UPTIMEDAY")
#! Field("PLC:UND0:PPS1:UPTIMEDAYRAW.VAL",16777215,1,"PLC:UND0:PPS1:UPTIMEDAYRAW.VAL")
#! Record("PLC:UND0:PPS1:UPTIMEDAY",4560,1622,0,0,"PLC:UND0:PPS1:UPTIMEDAY")
#! Field("PLC:UND0:PPS1:UPTIMEDAY.INPA",16777215,0,"PLC:UND0:PPS1:UPTIMEDAY.INPA")
#! Link("PLC:UND0:PPS1:UPTIMEDAY.INPA","PLC:UND0:PPS1:UPTIMEDAYRAW.VAL")
#! Field("PLC:UND0:PPS1:UPTIMEDAY.INPB",16777215,0,"PLC:UND0:PPS1:UPTIMEDAY.INPB")
#! Link("PLC:UND0:PPS1:UPTIMEDAY.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:TODYEARRAW",4220,487,0,0,"PLC:UND0:PPS1:TODYEARRAW")
#! Field("PLC:UND0:PPS1:TODYEARRAW.FLNK",16777215,1,"PLC:UND0:PPS1:TODYEARRAW.FLNK")
#! Link("PLC:UND0:PPS1:TODYEARRAW.FLNK","PLC:UND0:PPS1:TODYEAR")
#! Field("PLC:UND0:PPS1:TODYEARRAW.VAL",16777215,1,"PLC:UND0:PPS1:TODYEARRAW.VAL")
#! Record("PLC:UND0:PPS1:TODDAYRAW",4220,847,0,0,"PLC:UND0:PPS1:TODDAYRAW")
#! Field("PLC:UND0:PPS1:TODDAYRAW.FLNK",16777215,1,"PLC:UND0:PPS1:TODDAYRAW.FLNK")
#! Link("PLC:UND0:PPS1:TODDAYRAW.FLNK","PLC:UND0:PPS1:TODDAY")
#! Field("PLC:UND0:PPS1:TODDAYRAW.VAL",16777215,1,"PLC:UND0:PPS1:TODDAYRAW.VAL")
#! Record("PLC:UND0:PPS1:TODMONTHRAW",4220,667,0,0,"PLC:UND0:PPS1:TODMONTHRAW")
#! Field("PLC:UND0:PPS1:TODMONTHRAW.FLNK",16777215,1,"PLC:UND0:PPS1:TODMONTHRAW.FLNK")
#! Link("PLC:UND0:PPS1:TODMONTHRAW.FLNK","PLC:UND0:PPS1:TODMONTH")
#! Field("PLC:UND0:PPS1:TODMONTHRAW.VAL",16777215,1,"PLC:UND0:PPS1:TODMONTHRAW.VAL")
#! Record("PLC:UND0:PPS1:TODHOURRAW",4220,1027,0,0,"PLC:UND0:PPS1:TODHOURRAW")
#! Field("PLC:UND0:PPS1:TODHOURRAW.FLNK",16777215,1,"PLC:UND0:PPS1:TODHOURRAW.FLNK")
#! Link("PLC:UND0:PPS1:TODHOURRAW.FLNK","PLC:UND0:PPS1:TODHOUR")
#! Field("PLC:UND0:PPS1:TODHOURRAW.VAL",16777215,1,"PLC:UND0:PPS1:TODHOURRAW.VAL")
#! Record("PLC:UND0:PPS1:TODMINUTERAW",4220,1207,0,0,"PLC:UND0:PPS1:TODMINUTERAW")
#! Field("PLC:UND0:PPS1:TODMINUTERAW.FLNK",16777215,1,"PLC:UND0:PPS1:TODMINUTERAW.FLNK")
#! Link("PLC:UND0:PPS1:TODMINUTERAW.FLNK","PLC:UND0:PPS1:TODMINUTE")
#! Field("PLC:UND0:PPS1:TODMINUTERAW.VAL",16777215,1,"PLC:UND0:PPS1:TODMINUTERAW.VAL")
#! Record("PLC:UND0:PPS1:TODSECONDRAW",4220,1374,0,0,"PLC:UND0:PPS1:TODSECONDRAW")
#! Field("PLC:UND0:PPS1:TODSECONDRAW.FLNK",16777215,1,"PLC:UND0:PPS1:TODSECONDRAW.FLNK")
#! Link("PLC:UND0:PPS1:TODSECONDRAW.FLNK","PLC:UND0:PPS1:TODSECOND")
#! Field("PLC:UND0:PPS1:TODSECONDRAW.VAL",16777215,1,"PLC:UND0:PPS1:TODSECONDRAW.VAL")
#! Record("PLC:UND0:PPS1:TODYEAR",4520,522,0,0,"PLC:UND0:PPS1:TODYEAR")
#! Field("PLC:UND0:PPS1:TODYEAR.INPA",16777215,0,"PLC:UND0:PPS1:TODYEAR.INPA")
#! Link("PLC:UND0:PPS1:TODYEAR.INPA","PLC:UND0:PPS1:TODYEARRAW.VAL")
#! Field("PLC:UND0:PPS1:TODYEAR.INPB",16777215,0,"PLC:UND0:PPS1:TODYEAR.INPB")
#! Link("PLC:UND0:PPS1:TODYEAR.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:TODMONTH",4520,702,0,0,"PLC:UND0:PPS1:TODMONTH")
#! Field("PLC:UND0:PPS1:TODMONTH.INPA",16777215,0,"PLC:UND0:PPS1:TODMONTH.INPA")
#! Link("PLC:UND0:PPS1:TODMONTH.INPA","PLC:UND0:PPS1:TODMONTHRAW.VAL")
#! Field("PLC:UND0:PPS1:TODMONTH.INPB",16777215,0,"PLC:UND0:PPS1:TODMONTH.INPB")
#! Link("PLC:UND0:PPS1:TODMONTH.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:TODDAY",4520,882,0,0,"PLC:UND0:PPS1:TODDAY")
#! Field("PLC:UND0:PPS1:TODDAY.INPA",16777215,0,"PLC:UND0:PPS1:TODDAY.INPA")
#! Link("PLC:UND0:PPS1:TODDAY.INPA","PLC:UND0:PPS1:TODDAYRAW.VAL")
#! Field("PLC:UND0:PPS1:TODDAY.INPB",16777215,0,"PLC:UND0:PPS1:TODDAY.INPB")
#! Link("PLC:UND0:PPS1:TODDAY.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:TODHOUR",4520,1062,0,0,"PLC:UND0:PPS1:TODHOUR")
#! Field("PLC:UND0:PPS1:TODHOUR.INPA",16777215,0,"PLC:UND0:PPS1:TODHOUR.INPA")
#! Link("PLC:UND0:PPS1:TODHOUR.INPA","PLC:UND0:PPS1:TODHOURRAW.VAL")
#! Field("PLC:UND0:PPS1:TODHOUR.INPB",16777215,0,"PLC:UND0:PPS1:TODHOUR.INPB")
#! Link("PLC:UND0:PPS1:TODHOUR.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:TODMINUTE",4520,1242,0,0,"PLC:UND0:PPS1:TODMINUTE")
#! Field("PLC:UND0:PPS1:TODMINUTE.INPA",16777215,0,"PLC:UND0:PPS1:TODMINUTE.INPA")
#! Link("PLC:UND0:PPS1:TODMINUTE.INPA","PLC:UND0:PPS1:TODMINUTERAW.VAL")
#! Field("PLC:UND0:PPS1:TODMINUTE.INPB",16777215,0,"PLC:UND0:PPS1:TODMINUTE.INPB")
#! Link("PLC:UND0:PPS1:TODMINUTE.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:TODSECOND",4520,1422,0,0,"PLC:UND0:PPS1:TODSECOND")
#! Field("PLC:UND0:PPS1:TODSECOND.INPA",16777215,0,"PLC:UND0:PPS1:TODSECOND.INPA")
#! Link("PLC:UND0:PPS1:TODSECOND.INPA","PLC:UND0:PPS1:TODSECONDRAW.VAL")
#! Field("PLC:UND0:PPS1:TODSECOND.INPB",16777215,0,"PLC:UND0:PPS1:TODSECOND.INPB")
#! Link("PLC:UND0:PPS1:TODSECOND.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:VERSIONMAJORRAW",2740,2874,0,1,"PLC:UND0:PPS1:VERSIONMAJORRAW")
#! Field("PLC:UND0:PPS1:VERSIONMAJORRAW.VAL",16777215,1,"PLC:UND0:PPS1:VERSIONMAJORRAW.VAL")
#! Field("PLC:UND0:PPS1:VERSIONMAJORRAW.FLNK",16777215,1,"PLC:UND0:PPS1:VERSIONMAJORRAW.FLNK")
#! Link("PLC:UND0:PPS1:VERSIONMAJORRAW.FLNK","PLC:UND0:PPS1:VERSIONMAJOR")
#! Record("PLC:UND0:PPS1:VERSIONMINORRAW",2760,3287,0,1,"PLC:UND0:PPS1:VERSIONMINORRAW")
#! Field("PLC:UND0:PPS1:VERSIONMINORRAW.VAL",16777215,1,"PLC:UND0:PPS1:VERSIONMINORRAW.VAL")
#! Field("PLC:UND0:PPS1:VERSIONMINORRAW.FLNK",16777215,1,"PLC:UND0:PPS1:VERSIONMINORRAW.FLNK")
#! Link("PLC:UND0:PPS1:VERSIONMINORRAW.FLNK","PLC:UND0:PPS1:VERSIONMINOR")
#! Record("PLC:UND0:PPS1:VERSIONMAJOR",3040,2834,0,0,"PLC:UND0:PPS1:VERSIONMAJOR")
#! Field("PLC:UND0:PPS1:VERSIONMAJOR.INPA",16777215,0,"PLC:UND0:PPS1:VERSIONMAJOR.INPA")
#! Link("PLC:UND0:PPS1:VERSIONMAJOR.INPA","PLC:UND0:PPS1:VERSIONMAJORRAW.VAL")
#! Field("PLC:UND0:PPS1:VERSIONMAJOR.HIGH",16777215,0,"PLC:UND0:PPS1:VERSIONMAJOR.HIGH")
#! Field("PLC:UND0:PPS1:VERSIONMAJOR.LOW",16777215,0,"PLC:UND0:PPS1:VERSIONMAJOR.LOW")
#! Field("PLC:UND0:PPS1:VERSIONMAJOR.INPB",16777215,1,"PLC:UND0:PPS1:VERSIONMAJOR.INPB")
#! Link("PLC:UND0:PPS1:VERSIONMAJOR.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Field("PLC:UND0:PPS1:VERSIONMAJOR.VAL",16777215,0,"PLC:UND0:PPS1:VERSIONMAJOR.VAL")
#! Record("PLC:UND0:PPS1:VERSIONMINOR",3060,3194,0,0,"PLC:UND0:PPS1:VERSIONMINOR")
#! Field("PLC:UND0:PPS1:VERSIONMINOR.HIGH",16777215,0,"PLC:UND0:PPS1:VERSIONMINOR.HIGH")
#! Field("PLC:UND0:PPS1:VERSIONMINOR.INPA",16777215,0,"PLC:UND0:PPS1:VERSIONMINOR.INPA")
#! Link("PLC:UND0:PPS1:VERSIONMINOR.INPA","PLC:UND0:PPS1:VERSIONMINORRAW.VAL")
#! Field("PLC:UND0:PPS1:VERSIONMINOR.LOW",16777215,0,"PLC:UND0:PPS1:VERSIONMINOR.LOW")
#! Field("PLC:UND0:PPS1:VERSIONMINOR.INPB",16777215,1,"PLC:UND0:PPS1:VERSIONMINOR.INPB")
#! Link("PLC:UND0:PPS1:VERSIONMINOR.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Field("PLC:UND0:PPS1:VERSIONMINOR.VAL",16777215,0,"PLC:UND0:PPS1:VERSIONMINOR.VAL")
#! Record("PLC:UND0:PPS1:VERSIONREVRAW",2780,3687,0,1,"PLC:UND0:PPS1:VERSIONREVRAW")
#! Field("PLC:UND0:PPS1:VERSIONREVRAW.FLNK",16777215,1,"PLC:UND0:PPS1:VERSIONREVRAW.FLNK")
#! Link("PLC:UND0:PPS1:VERSIONREVRAW.FLNK","PLC:UND0:PPS1:VERSIONREV")
#! Field("PLC:UND0:PPS1:VERSIONREVRAW.VAL",16777215,1,"PLC:UND0:PPS1:VERSIONREVRAW.VAL")
#! Record("PLC:UND0:PPS1:VERSIONREV",3060,3594,0,0,"PLC:UND0:PPS1:VERSIONREV")
#! Field("PLC:UND0:PPS1:VERSIONREV.HIGH",16777215,0,"PLC:UND0:PPS1:VERSIONREV.HIGH")
#! Field("PLC:UND0:PPS1:VERSIONREV.LOW",16777215,0,"PLC:UND0:PPS1:VERSIONREV.LOW")
#! Field("PLC:UND0:PPS1:VERSIONREV.INPA",16777215,0,"PLC:UND0:PPS1:VERSIONREV.INPA")
#! Link("PLC:UND0:PPS1:VERSIONREV.INPA","PLC:UND0:PPS1:VERSIONREVRAW.VAL")
#! Field("PLC:UND0:PPS1:VERSIONREV.INPB",16777215,1,"PLC:UND0:PPS1:VERSIONREV.INPB")
#! Link("PLC:UND0:PPS1:VERSIONREV.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Field("PLC:UND0:PPS1:VERSIONREV.VAL",16777215,0,"PLC:UND0:PPS1:VERSIONREV.VAL")
#! Record("PLC:UND0:PPS1:SERIALNUMBERRAW",1960,3787,0,1,"PLC:UND0:PPS1:SERIALNUMBERRAW")
#! Field("PLC:UND0:PPS1:SERIALNUMBERRAW.FLNK",16777215,1,"PLC:UND0:PPS1:SERIALNUMBERRAW.FLNK")
#! Link("PLC:UND0:PPS1:SERIALNUMBERRAW.FLNK","PLC:UND0:PPS1:SERIALNUMBER")
#! Field("PLC:UND0:PPS1:SERIALNUMBERRAW.VAL",16777215,0,"PLC:UND0:PPS1:SERIALNUMBERRAW.VAL")
#! Record("PLC:UND0:PPS1:SERIALNUMBER",2220,3822,0,0,"PLC:UND0:PPS1:SERIALNUMBER")
#! Field("PLC:UND0:PPS1:SERIALNUMBER.INPA",16777215,0,"PLC:UND0:PPS1:SERIALNUMBER.INPA")
#! Link("PLC:UND0:PPS1:SERIALNUMBER.INPA","PLC:UND0:PPS1:SERIALNUMBERRAW.VAL")
#! Field("PLC:UND0:PPS1:SERIALNUMBER.INPB",16777215,1,"PLC:UND0:PPS1:SERIALNUMBER.INPB")
#! Link("PLC:UND0:PPS1:SERIALNUMBER.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:COMMLINK",340,43,0,0,"PLC:UND0:PPS1:COMMLINK")
#! Field("PLC:UND0:PPS1:COMMLINK.INP",16777215,0,"PLC:UND0:PPS1:COMMLINK.INP")
#! Link("PLC:UND0:PPS1:COMMLINK.INP","PLC:UND0:PPS1:HEARTBEATRAW.SEVR")
#! Field("PLC:UND0:PPS1:COMMLINK.FLNK",16777215,1,"PLC:UND0:PPS1:COMMLINK.FLNK")
#! Link("PLC:UND0:PPS1:COMMLINK.FLNK","PLC:UND0:PPS1:HEARTBEATCALC")
#! Record("PLC:UND0:PPS1:HEARTBEATE10",1100,2447,0,1,"PLC:UND0:PPS1:HEARTBEATE10")
#! Field("PLC:UND0:PPS1:HEARTBEATE10.VAL",16777215,1,"PLC:UND0:PPS1:HEARTBEATE10.VAL")
#! Field("PLC:UND0:PPS1:HEARTBEATE10.INPB",16777215,0,"PLC:UND0:PPS1:HEARTBEATE10.INPB")
#! Link("PLC:UND0:PPS1:HEARTBEATE10.INPB","PLC:UND0:PPS1:HEARTBEATE10.VAL")
#! Field("PLC:UND0:PPS1:HEARTBEATE10.FLNK",16777215,1,"PLC:UND0:PPS1:HEARTBEATE10.FLNK")
#! Link("PLC:UND0:PPS1:HEARTBEATE10.FLNK","PLC:UND0:PPS1:HEARTBEATECT")
#! Field("PLC:UND0:PPS1:HEARTBEATE10.INPA",16777215,0,"PLC:UND0:PPS1:HEARTBEATE10.INPA")
#! Link("PLC:UND0:PPS1:HEARTBEATE10.INPA","PLC:UND0:PPS1:HEARTBEATE09.B")
#! Record("PLC:UND0:PPS1:DOCPREFIXRAW",880,2867,0,1,"PLC:UND0:PPS1:DOCPREFIXRAW")
#! Field("PLC:UND0:PPS1:DOCPREFIXRAW.FLNK",16777215,1,"PLC:UND0:PPS1:DOCPREFIXRAW.FLNK")
#! Link("PLC:UND0:PPS1:DOCPREFIXRAW.FLNK","PLC:UND0:PPS1:DOCPREFIXCALC")
#! Field("PLC:UND0:PPS1:DOCPREFIXRAW.VAL",16777215,1,"PLC:UND0:PPS1:DOCPREFIXRAW.VAL")
#! Record("PLC:UND0:PPS1:DOCPREFIXCALC",1160,2887,0,0,"PLC:UND0:PPS1:DOCPREFIXCALC")
#! Field("PLC:UND0:PPS1:DOCPREFIXCALC.INPA",16777215,0,"PLC:UND0:PPS1:DOCPREFIXCALC.INPA")
#! Link("PLC:UND0:PPS1:DOCPREFIXCALC.INPA","PLC:UND0:PPS1:DOCPREFIXRAW.VAL")
#! Field("PLC:UND0:PPS1:DOCPREFIXCALC.FLNK",16777215,1,"PLC:UND0:PPS1:DOCPREFIXCALC.FLNK")
#! Link("PLC:UND0:PPS1:DOCPREFIXCALC.FLNK","PLC:UND0:PPS1:DOCPREFIX")
#! Field("PLC:UND0:PPS1:DOCPREFIXCALC.VAL",16777215,1,"PLC:UND0:PPS1:DOCPREFIXCALC.VAL")
#! Field("PLC:UND0:PPS1:DOCPREFIXCALC.INPB",16777215,1,"PLC:UND0:PPS1:DOCPREFIXCALC.INPB")
#! Link("PLC:UND0:PPS1:DOCPREFIXCALC.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:DOCPREFIX",1460,2630,0,0,"PLC:UND0:PPS1:DOCPREFIX")
#! Field("PLC:UND0:PPS1:DOCPREFIX.INP",16777215,0,"PLC:UND0:PPS1:DOCPREFIX.INP")
#! Link("PLC:UND0:PPS1:DOCPREFIX.INP","PLC:UND0:PPS1:DOCPREFIXCALC.VAL")
#! Record("PLC:UND0:PPS1:DOCSERIESRAW",880,3087,0,1,"PLC:UND0:PPS1:DOCSERIESRAW")
#! Field("PLC:UND0:PPS1:DOCSERIESRAW.FLNK",16777215,1,"PLC:UND0:PPS1:DOCSERIESRAW.FLNK")
#! Link("PLC:UND0:PPS1:DOCSERIESRAW.FLNK","PLC:UND0:PPS1:DOCSERIES")
#! Field("PLC:UND0:PPS1:DOCSERIESRAW.VAL",16777215,1,"PLC:UND0:PPS1:DOCSERIESRAW.VAL")
#! Record("PLC:UND0:PPS1:DOCSERIES",1160,3122,0,0,"PLC:UND0:PPS1:DOCSERIES")
#! Field("PLC:UND0:PPS1:DOCSERIES.INPA",16777215,0,"PLC:UND0:PPS1:DOCSERIES.INPA")
#! Link("PLC:UND0:PPS1:DOCSERIES.INPA","PLC:UND0:PPS1:DOCSERIESRAW.VAL")
#! Field("PLC:UND0:PPS1:DOCSERIES.INPB",16777215,1,"PLC:UND0:PPS1:DOCSERIES.INPB")
#! Link("PLC:UND0:PPS1:DOCSERIES.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:DOCBASERAW",878,3307,0,1,"PLC:UND0:PPS1:DOCBASERAW")
#! Field("PLC:UND0:PPS1:DOCBASERAW.FLNK",16777215,1,"PLC:UND0:PPS1:DOCBASERAW.FLNK")
#! Link("PLC:UND0:PPS1:DOCBASERAW.FLNK","PLC:UND0:PPS1:DOCBASE")
#! Field("PLC:UND0:PPS1:DOCBASERAW.VAL",16777215,1,"PLC:UND0:PPS1:DOCBASERAW.VAL")
#! Record("PLC:UND0:PPS1:DOCBASE",1160,3342,0,0,"PLC:UND0:PPS1:DOCBASE")
#! Field("PLC:UND0:PPS1:DOCBASE.INPA",16777215,0,"PLC:UND0:PPS1:DOCBASE.INPA")
#! Link("PLC:UND0:PPS1:DOCBASE.INPA","PLC:UND0:PPS1:DOCBASERAW.VAL")
#! Field("PLC:UND0:PPS1:DOCBASE.INPB",16777215,1,"PLC:UND0:PPS1:DOCBASE.INPB")
#! Link("PLC:UND0:PPS1:DOCBASE.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:DOCSUFFIXRAW",878,3567,0,1,"PLC:UND0:PPS1:DOCSUFFIXRAW")
#! Field("PLC:UND0:PPS1:DOCSUFFIXRAW.FLNK",16777215,1,"PLC:UND0:PPS1:DOCSUFFIXRAW.FLNK")
#! Link("PLC:UND0:PPS1:DOCSUFFIXRAW.FLNK","PLC:UND0:PPS1:DOCSUFFIX")
#! Field("PLC:UND0:PPS1:DOCSUFFIXRAW.VAL",16777215,1,"PLC:UND0:PPS1:DOCSUFFIXRAW.VAL")
#! Record("PLC:UND0:PPS1:DOCSUFFIX",1160,3602,0,0,"PLC:UND0:PPS1:DOCSUFFIX")
#! Field("PLC:UND0:PPS1:DOCSUFFIX.INPA",16777215,0,"PLC:UND0:PPS1:DOCSUFFIX.INPA")
#! Link("PLC:UND0:PPS1:DOCSUFFIX.INPA","PLC:UND0:PPS1:DOCSUFFIXRAW.VAL")
#! Field("PLC:UND0:PPS1:DOCSUFFIX.INPB",16777215,1,"PLC:UND0:PPS1:DOCSUFFIX.INPB")
#! Link("PLC:UND0:PPS1:DOCSUFFIX.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:DOCREVRAW",874,3787,0,1,"PLC:UND0:PPS1:DOCREVRAW")
#! Field("PLC:UND0:PPS1:DOCREVRAW.FLNK",16777215,1,"PLC:UND0:PPS1:DOCREVRAW.FLNK")
#! Link("PLC:UND0:PPS1:DOCREVRAW.FLNK","PLC:UND0:PPS1:DOCREV")
#! Field("PLC:UND0:PPS1:DOCREVRAW.VAL",16777215,1,"PLC:UND0:PPS1:DOCREVRAW.VAL")
#! Record("PLC:UND0:PPS1:DOCREV",1154,3822,0,0,"PLC:UND0:PPS1:DOCREV")
#! Field("PLC:UND0:PPS1:DOCREV.INPA",16777215,0,"PLC:UND0:PPS1:DOCREV.INPA")
#! Link("PLC:UND0:PPS1:DOCREV.INPA","PLC:UND0:PPS1:DOCREVRAW.VAL")
#! Field("PLC:UND0:PPS1:DOCREV.INPB",16777215,1,"PLC:UND0:PPS1:DOCREV.INPB")
#! Link("PLC:UND0:PPS1:DOCREV.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:SUBSYSTEM",3320,2816,0,1,"PLC:UND0:PPS1:SUBSYSTEM")
#! Record("PLC:UND0:PPS1:PLCADMINVMAJRAW",2720,2087,0,1,"PLC:UND0:PPS1:PLCADMINVMAJRAW")
#! Field("PLC:UND0:PPS1:PLCADMINVMAJRAW.FLNK",16777215,1,"PLC:UND0:PPS1:PLCADMINVMAJRAW.FLNK")
#! Link("PLC:UND0:PPS1:PLCADMINVMAJRAW.FLNK","PLC:UND0:PPS1:PLCADMINVMAJ")
#! Field("PLC:UND0:PPS1:PLCADMINVMAJRAW.VAL",16777215,1,"PLC:UND0:PPS1:PLCADMINVMAJRAW.VAL")
#! Record("PLC:UND0:PPS1:PLCADMINVMAJ",3020,2050,0,0,"PLC:UND0:PPS1:PLCADMINVMAJ")
#! Field("PLC:UND0:PPS1:PLCADMINVMAJ.INPA",16777215,0,"PLC:UND0:PPS1:PLCADMINVMAJ.INPA")
#! Link("PLC:UND0:PPS1:PLCADMINVMAJ.INPA","PLC:UND0:PPS1:PLCADMINVMAJRAW.VAL")
#! Field("PLC:UND0:PPS1:PLCADMINVMAJ.INPB",16777215,1,"PLC:UND0:PPS1:PLCADMINVMAJ.INPB")
#! Link("PLC:UND0:PPS1:PLCADMINVMAJ.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:PLCADMINVMINRAW",2720,2327,0,1,"PLC:UND0:PPS1:PLCADMINVMINRAW")
#! Field("PLC:UND0:PPS1:PLCADMINVMINRAW.FLNK",16777215,1,"PLC:UND0:PPS1:PLCADMINVMINRAW.FLNK")
#! Link("PLC:UND0:PPS1:PLCADMINVMINRAW.FLNK","PLC:UND0:PPS1:PLCADMINVMIN")
#! Field("PLC:UND0:PPS1:PLCADMINVMINRAW.VAL",16777215,1,"PLC:UND0:PPS1:PLCADMINVMINRAW.VAL")
#! Record("PLC:UND0:PPS1:PLCADMINVMIN",3020,2290,0,0,"PLC:UND0:PPS1:PLCADMINVMIN")
#! Field("PLC:UND0:PPS1:PLCADMINVMIN.INPA",16777215,0,"PLC:UND0:PPS1:PLCADMINVMIN.INPA")
#! Link("PLC:UND0:PPS1:PLCADMINVMIN.INPA","PLC:UND0:PPS1:PLCADMINVMINRAW.VAL")
#! Field("PLC:UND0:PPS1:PLCADMINVMIN.INPB",16777215,1,"PLC:UND0:PPS1:PLCADMINVMIN.INPB")
#! Link("PLC:UND0:PPS1:PLCADMINVMIN.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:PLCADMINVREVRAW",2720,2567,0,1,"PLC:UND0:PPS1:PLCADMINVREVRAW")
#! Field("PLC:UND0:PPS1:PLCADMINVREVRAW.FLNK",16777215,1,"PLC:UND0:PPS1:PLCADMINVREVRAW.FLNK")
#! Link("PLC:UND0:PPS1:PLCADMINVREVRAW.FLNK","PLC:UND0:PPS1:PLCADMINVREV")
#! Field("PLC:UND0:PPS1:PLCADMINVREVRAW.VAL",16777215,1,"PLC:UND0:PPS1:PLCADMINVREVRAW.VAL")
#! Record("PLC:UND0:PPS1:PLCADMINVREV",3020,2530,0,0,"PLC:UND0:PPS1:PLCADMINVREV")
#! Field("PLC:UND0:PPS1:PLCADMINVREV.INPA",16777215,0,"PLC:UND0:PPS1:PLCADMINVREV.INPA")
#! Link("PLC:UND0:PPS1:PLCADMINVREV.INPA","PLC:UND0:PPS1:PLCADMINVREVRAW.VAL")
#! Field("PLC:UND0:PPS1:PLCADMINVREV.INPB",16777215,1,"PLC:UND0:PPS1:PLCADMINVREV.INPB")
#! Link("PLC:UND0:PPS1:PLCADMINVREV.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:PROGPLCATMAXRAW",2700,727,0,0,"PLC:UND0:PPS1:PROGPLCATMAXRAW")
#! Field("PLC:UND0:PPS1:PROGPLCATMAXRAW.FLNK",16777215,1,"PLC:UND0:PPS1:PROGPLCATMAXRAW.FLNK")
#! Link("PLC:UND0:PPS1:PROGPLCATMAXRAW.FLNK","PLC:UND0:PPS1:PROGPLCATMAX")
#! Field("PLC:UND0:PPS1:PROGPLCATMAXRAW.VAL",16777215,1,"PLC:UND0:PPS1:PROGPLCATMAXRAW.VAL")
#! Record("PLC:UND0:PPS1:PROGPLCATLSTRAW",2700,567,0,0,"PLC:UND0:PPS1:PROGPLCATLSTRAW")
#! Field("PLC:UND0:PPS1:PROGPLCATLSTRAW.FLNK",16777215,1,"PLC:UND0:PPS1:PROGPLCATLSTRAW.FLNK")
#! Link("PLC:UND0:PPS1:PROGPLCATLSTRAW.FLNK","PLC:UND0:PPS1:PROGPLCATLST")
#! Field("PLC:UND0:PPS1:PROGPLCATLSTRAW.VAL",16777215,1,"PLC:UND0:PPS1:PROGPLCATLSTRAW.VAL")
#! Record("PLC:UND0:PPS1:PROGPLCATLST",3000,602,0,0,"PLC:UND0:PPS1:PROGPLCATLST")
#! Field("PLC:UND0:PPS1:PROGPLCATLST.INPA",16777215,0,"PLC:UND0:PPS1:PROGPLCATLST.INPA")
#! Link("PLC:UND0:PPS1:PROGPLCATLST.INPA","PLC:UND0:PPS1:PROGPLCATLSTRAW.VAL")
#! Field("PLC:UND0:PPS1:PROGPLCATLST.INPB",16777215,1,"PLC:UND0:PPS1:PROGPLCATLST.INPB")
#! Link("PLC:UND0:PPS1:PROGPLCATLST.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:PROGPLCATMAX",3000,762,0,0,"PLC:UND0:PPS1:PROGPLCATMAX")
#! Field("PLC:UND0:PPS1:PROGPLCATMAX.INPA",16777215,0,"PLC:UND0:PPS1:PROGPLCATMAX.INPA")
#! Link("PLC:UND0:PPS1:PROGPLCATMAX.INPA","PLC:UND0:PPS1:PROGPLCATMAXRAW.VAL")
#! Field("PLC:UND0:PPS1:PROGPLCATMAX.INPB",16777215,1,"PLC:UND0:PPS1:PROGPLCATMAX.INPB")
#! Link("PLC:UND0:PPS1:PROGPLCATMAX.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:PLCADMINTAG",2120,876,0,1,"PLC:UND0:PPS1:PLCADMINTAG")
#! Record("PLC:UND0:PPS1:TASKMAINTLSTRAW",2700,247,0,0,"PLC:UND0:PPS1:TASKMAINTLSTRAW")
#! Field("PLC:UND0:PPS1:TASKMAINTLSTRAW.FLNK",16777215,1,"PLC:UND0:PPS1:TASKMAINTLSTRAW.FLNK")
#! Link("PLC:UND0:PPS1:TASKMAINTLSTRAW.FLNK","PLC:UND0:PPS1:TASKMAINTLST")
#! Field("PLC:UND0:PPS1:TASKMAINTLSTRAW.VAL",16777215,1,"PLC:UND0:PPS1:TASKMAINTLSTRAW.VAL")
#! Record("PLC:UND0:PPS1:TASKMAINTLST",3000,282,0,0,"PLC:UND0:PPS1:TASKMAINTLST")
#! Field("PLC:UND0:PPS1:TASKMAINTLST.INPA",16777215,0,"PLC:UND0:PPS1:TASKMAINTLST.INPA")
#! Link("PLC:UND0:PPS1:TASKMAINTLST.INPA","PLC:UND0:PPS1:TASKMAINTLSTRAW.VAL")
#! Field("PLC:UND0:PPS1:TASKMAINTLST.INPB",16777215,1,"PLC:UND0:PPS1:TASKMAINTLST.INPB")
#! Link("PLC:UND0:PPS1:TASKMAINTLST.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:TASKMAINTMAXRAW",2700,407,0,0,"PLC:UND0:PPS1:TASKMAINTMAXRAW")
#! Field("PLC:UND0:PPS1:TASKMAINTMAXRAW.FLNK",16777215,1,"PLC:UND0:PPS1:TASKMAINTMAXRAW.FLNK")
#! Link("PLC:UND0:PPS1:TASKMAINTMAXRAW.FLNK","PLC:UND0:PPS1:TASKMAINTMAX")
#! Field("PLC:UND0:PPS1:TASKMAINTMAXRAW.VAL",16777215,1,"PLC:UND0:PPS1:TASKMAINTMAXRAW.VAL")
#! Record("PLC:UND0:PPS1:TASKMAINTMAX",3000,442,0,0,"PLC:UND0:PPS1:TASKMAINTMAX")
#! Field("PLC:UND0:PPS1:TASKMAINTMAX.INPA",16777215,0,"PLC:UND0:PPS1:TASKMAINTMAX.INPA")
#! Link("PLC:UND0:PPS1:TASKMAINTMAX.INPA","PLC:UND0:PPS1:TASKMAINTMAXRAW.VAL")
#! Field("PLC:UND0:PPS1:TASKMAINTMAX.INPB",16777215,1,"PLC:UND0:PPS1:TASKMAINTMAX.INPB")
#! Link("PLC:UND0:PPS1:TASKMAINTMAX.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:PROG1TLSTRAW",2700,887,0,0,"PLC:UND0:PPS1:PROG1TLSTRAW")
#! Field("PLC:UND0:PPS1:PROG1TLSTRAW.FLNK",16777215,1,"PLC:UND0:PPS1:PROG1TLSTRAW.FLNK")
#! Link("PLC:UND0:PPS1:PROG1TLSTRAW.FLNK","PLC:UND0:PPS1:PROG1TLST")
#! Field("PLC:UND0:PPS1:PROG1TLSTRAW.VAL",16777215,1,"PLC:UND0:PPS1:PROG1TLSTRAW.VAL")
#! Record("PLC:UND0:PPS1:PROG1TMAXRAW",2700,1047,0,0,"PLC:UND0:PPS1:PROG1TMAXRAW")
#! Field("PLC:UND0:PPS1:PROG1TMAXRAW.FLNK",16777215,1,"PLC:UND0:PPS1:PROG1TMAXRAW.FLNK")
#! Link("PLC:UND0:PPS1:PROG1TMAXRAW.FLNK","PLC:UND0:PPS1:PROG1TMAX")
#! Field("PLC:UND0:PPS1:PROG1TMAXRAW.VAL",16777215,1,"PLC:UND0:PPS1:PROG1TMAXRAW.VAL")
#! Record("PLC:UND0:PPS1:PROG1TLST",3000,922,0,0,"PLC:UND0:PPS1:PROG1TLST")
#! Field("PLC:UND0:PPS1:PROG1TLST.INPA",16777215,0,"PLC:UND0:PPS1:PROG1TLST.INPA")
#! Link("PLC:UND0:PPS1:PROG1TLST.INPA","PLC:UND0:PPS1:PROG1TLSTRAW.VAL")
#! Field("PLC:UND0:PPS1:PROG1TLST.INPB",16777215,1,"PLC:UND0:PPS1:PROG1TLST.INPB")
#! Link("PLC:UND0:PPS1:PROG1TLST.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:PROG1TMAX",3000,1082,0,0,"PLC:UND0:PPS1:PROG1TMAX")
#! Field("PLC:UND0:PPS1:PROG1TMAX.INPA",16777215,0,"PLC:UND0:PPS1:PROG1TMAX.INPA")
#! Link("PLC:UND0:PPS1:PROG1TMAX.INPA","PLC:UND0:PPS1:PROG1TMAXRAW.VAL")
#! Field("PLC:UND0:PPS1:PROG1TMAX.INPB",16777215,1,"PLC:UND0:PPS1:PROG1TMAX.INPB")
#! Link("PLC:UND0:PPS1:PROG1TMAX.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:PROG2TLSTRAW",2700,1207,0,0,"PLC:UND0:PPS1:PROG2TLSTRAW")
#! Field("PLC:UND0:PPS1:PROG2TLSTRAW.FLNK",16777215,1,"PLC:UND0:PPS1:PROG2TLSTRAW.FLNK")
#! Link("PLC:UND0:PPS1:PROG2TLSTRAW.FLNK","PLC:UND0:PPS1:PROG2TLST")
#! Field("PLC:UND0:PPS1:PROG2TLSTRAW.VAL",16777215,1,"PLC:UND0:PPS1:PROG2TLSTRAW.VAL")
#! Record("PLC:UND0:PPS1:PROG2TMAXRAW",2700,1367,0,0,"PLC:UND0:PPS1:PROG2TMAXRAW")
#! Field("PLC:UND0:PPS1:PROG2TMAXRAW.FLNK",16777215,1,"PLC:UND0:PPS1:PROG2TMAXRAW.FLNK")
#! Link("PLC:UND0:PPS1:PROG2TMAXRAW.FLNK","PLC:UND0:PPS1:PROG2TMAX")
#! Field("PLC:UND0:PPS1:PROG2TMAXRAW.VAL",16777215,1,"PLC:UND0:PPS1:PROG2TMAXRAW.VAL")
#! Record("PLC:UND0:PPS1:PROG2TLST",3000,1242,0,0,"PLC:UND0:PPS1:PROG2TLST")
#! Field("PLC:UND0:PPS1:PROG2TLST.INPA",16777215,0,"PLC:UND0:PPS1:PROG2TLST.INPA")
#! Link("PLC:UND0:PPS1:PROG2TLST.INPA","PLC:UND0:PPS1:PROG2TLSTRAW.VAL")
#! Field("PLC:UND0:PPS1:PROG2TLST.INPB",16777215,1,"PLC:UND0:PPS1:PROG2TLST.INPB")
#! Link("PLC:UND0:PPS1:PROG2TLST.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:PROG2TMAX",3000,1402,0,0,"PLC:UND0:PPS1:PROG2TMAX")
#! Field("PLC:UND0:PPS1:PROG2TMAX.INPA",16777215,0,"PLC:UND0:PPS1:PROG2TMAX.INPA")
#! Link("PLC:UND0:PPS1:PROG2TMAX.INPA","PLC:UND0:PPS1:PROG2TMAXRAW.VAL")
#! Field("PLC:UND0:PPS1:PROG2TMAX.INPB",16777215,1,"PLC:UND0:PPS1:PROG2TMAX.INPB")
#! Link("PLC:UND0:PPS1:PROG2TMAX.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:PROG3TLSTRAW",2700,1527,0,0,"PLC:UND0:PPS1:PROG3TLSTRAW")
#! Field("PLC:UND0:PPS1:PROG3TLSTRAW.FLNK",16777215,1,"PLC:UND0:PPS1:PROG3TLSTRAW.FLNK")
#! Link("PLC:UND0:PPS1:PROG3TLSTRAW.FLNK","PLC:UND0:PPS1:PROG3TLST")
#! Field("PLC:UND0:PPS1:PROG3TLSTRAW.VAL",16777215,1,"PLC:UND0:PPS1:PROG3TLSTRAW.VAL")
#! Record("PLC:UND0:PPS1:PROG3TMAXRAW",2700,1687,0,0,"PLC:UND0:PPS1:PROG3TMAXRAW")
#! Field("PLC:UND0:PPS1:PROG3TMAXRAW.FLNK",16777215,1,"PLC:UND0:PPS1:PROG3TMAXRAW.FLNK")
#! Link("PLC:UND0:PPS1:PROG3TMAXRAW.FLNK","PLC:UND0:PPS1:PROG3TMAX")
#! Field("PLC:UND0:PPS1:PROG3TMAXRAW.VAL",16777215,1,"PLC:UND0:PPS1:PROG3TMAXRAW.VAL")
#! Record("PLC:UND0:PPS1:PROG3TMAX",3000,1722,0,0,"PLC:UND0:PPS1:PROG3TMAX")
#! Field("PLC:UND0:PPS1:PROG3TMAX.INPA",16777215,0,"PLC:UND0:PPS1:PROG3TMAX.INPA")
#! Link("PLC:UND0:PPS1:PROG3TMAX.INPA","PLC:UND0:PPS1:PROG3TMAXRAW.VAL")
#! Field("PLC:UND0:PPS1:PROG3TMAX.INPB",16777215,1,"PLC:UND0:PPS1:PROG3TMAX.INPB")
#! Link("PLC:UND0:PPS1:PROG3TMAX.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:PROG3TLST",3000,1562,0,0,"PLC:UND0:PPS1:PROG3TLST")
#! Field("PLC:UND0:PPS1:PROG3TLST.INPA",16777215,0,"PLC:UND0:PPS1:PROG3TLST.INPA")
#! Link("PLC:UND0:PPS1:PROG3TLST.INPA","PLC:UND0:PPS1:PROG3TLSTRAW.VAL")
#! Field("PLC:UND0:PPS1:PROG3TLST.INPB",16777215,1,"PLC:UND0:PPS1:PROG3TLST.INPB")
#! Link("PLC:UND0:PPS1:PROG3TLST.INPB","PLC:UND0:PPS1:HEARTBEATCLC.VAL")
#! Record("PLC:UND0:PPS1:STATSUMY",1600,4643,0,1,"PLC:UND0:PPS1:STATSUMY")
#! Field("PLC:UND0:PPS1:STATSUMY.INPB",16777215,1,"PLC:UND0:PPS1:STATSUMY.INPB")
#! Link("PLC:UND0:PPS1:STATSUMY.INPB","PLC:UND0:PPS1:HEARTBEATSUM.VAL")
#! Field("PLC:UND0:PPS1:STATSUMY.INPC",16777215,1,"PLC:UND0:PPS1:STATSUMY.INPC")
#! Link("PLC:UND0:PPS1:STATSUMY.INPC","PLC:UND0:PPS1:FAULTSTATUS.VAL")
#! Field("PLC:UND0:PPS1:STATSUMY.INPD",16777215,1,"PLC:UND0:PPS1:STATSUMY.INPD")
#! Link("PLC:UND0:PPS1:STATSUMY.INPD","PLC:UND0:PPS1:KEYSTATUS.VAL")
#! Field("PLC:UND0:PPS1:STATSUMY.INPE",16777215,1,"PLC:UND0:PPS1:STATSUMY.INPE")
#! Link("PLC:UND0:PPS1:STATSUMY.INPE","PLC:UND0:PPS1:DEVICESTATUS.VAL")
#! Field("PLC:UND0:PPS1:STATSUMY.INPF",16777215,1,"PLC:UND0:PPS1:STATSUMY.INPF")
#! Link("PLC:UND0:PPS1:STATSUMY.INPF","PLC:UND0:PPS1:VERSIONMAJOR.VAL")
#! Field("PLC:UND0:PPS1:STATSUMY.INPG",16777215,1,"PLC:UND0:PPS1:STATSUMY.INPG")
#! Link("PLC:UND0:PPS1:STATSUMY.INPG","PLC:UND0:PPS1:VERSIONMINOR.VAL")
#! Field("PLC:UND0:PPS1:STATSUMY.INPH",16777215,1,"PLC:UND0:PPS1:STATSUMY.INPH")
#! Link("PLC:UND0:PPS1:STATSUMY.INPH","PLC:UND0:PPS1:VERSIONREV.VAL")
#! Field("PLC:UND0:PPS1:STATSUMY.SEVR",16777215,0,"PLC:UND0:PPS1:STATSUMY.SEVR")
#! Field("PLC:UND0:PPS1:STATSUMY.INPA",16777215,0,"PLC:UND0:PPS1:STATSUMY.INPA")
#! Link("PLC:UND0:PPS1:STATSUMY.INPA","PLC:UND0:PPS1:STATSUMY.SEVR")
# -*- shell-script -*-
# AI records that read statistical information from EtherIP
# driver/device
#
# IOC:  prefix to records
# PLC:  PLC to use
# TAG:  queried tag (leads to PLC's ScanList)

record(ai, "PLC:UND0:PPS1:PLC_ERRORS")
{
	field(SCAN, ".5 second")
	field(DTYP, "EtherIP")
	field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01 PLC_ERRORS")
	field(EGUF, "5")
	field(EGU, "Errors")
	field(HOPR, "5")
	field(LOPR, "0")
}


record(ai, "PLC:UND0:PPS1:PLC_TASK_SLOW")
{
	field(SCAN, ".5 second")
	field(DTYP, "EtherIP")
	field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01 PLC_TASK_SLOW")
	field(EGUF, "5")
	field(EGU, "Holdups")
	field(HOPR, "5")
	field(LOPR, "0")
}

record(ai, "PLC:UND0:PPS1:LIST_TICKS")
{
	field(SCAN, ".5 second")
	field(DTYP, "EtherIP")
	field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01 LIST_TICKS")
	field(EGUF, "5")
	field(EGU, "vx ticks")
	field(HOPR, "5")
	field(LOPR, "0")
}

record(ai, "PLC:UND0:PPS1:LIST_SCAN_TIME")
{
	field(SCAN, ".5 second")
	field(DTYP, "EtherIP")
	field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01 LIST_SCAN_TIME")
	field(EGUF, "1")
	field(EGU, "s")
	field(HOPR, "1")
	field(LOPR, "0")
	field(PREC, "5")
}

record(ai, "PLC:UND0:PPS1:LIST_MIN_SCAN_TIME")
{
	field(SCAN, ".5 second")
	field(DTYP, "EtherIP")
	field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01 LIST_MIN_SCAN_TIME")
	field(EGUF, "1")
	field(EGU, "s")
	field(HOPR, "1")
	field(LOPR, "0")
	field(PREC, "5")
}

record(ai, "PLC:UND0:PPS1:LIST_MAX_SCAN_TIME")
{
	field(SCAN, ".5 second")
	field(DTYP, "EtherIP")
	field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01 LIST_MAX_SCAN_TIME")
	field(EGUF, "1")
	field(EGU, "s")
	field(HOPR, "1")
	field(LOPR, "0")
	field(PREC, "5")
}

record(ai, "PLC:UND0:PPS1:TAG_TRANSFER_TIME")
{
	field(SCAN, ".5 second")
	field(DTYP, "EtherIP")
	field(INP, "@PLC:UND0:PPS1 PLCADMIN_PLC_LTU0_PP01 TAG_TRANSFER_TIME")
	field(EGUF, "1000000000")
	field(EGU, "s")
	field(HOPR, "1")
	field(LOPR, "0")
	field(PREC, "5")
}