record(asyn,"$(BL)GAMMAASYNCONTROL") { field(DTYP, "asynRecordDevice") field(PORT, "$(PORT)") } record(calcout, "$(BL)GAMMAACT") { field(DESC, "gamma dose rate") field(DTYP, "stream") # SDIS is for alarm propogation only #field(SDIS, "$(BL)GammaCheckIO CP MS") field(OUT, "@gamma6032.proto read($(BL)) $(PORT)") field(SCAN, "I/O Intr") # .A is filled in by gamma6032.proto #field(INPB, "$(BL)GammaDoseStatus NPP MS") field(CALC, "A<8388608 ? 0.01*A : 0.01*(8388608-A)") field(EGU, "mrem/hour") field(PREC, "2") field(FLNK, "$(BL)GAMMAFANOUT") info(autosaveFields, "ADEL MDEL HIHI HHSV HIGH HSV LOW LSV LOLO LLSV") } record(fanout, "$(BL)GAMMAFANOUT") { field(DESC, "gamma fanout") field(SCAN, "Passive") field(LNK1, "$(BL)GAMMATOTALDOSE") field(LNK2, "$(BL)GAMMADAILYDOSE") } record(calc, "$(BL)GAMMATOTALDOSE") { field(DESC, "gamma total dose") field(INPA, "$(BL)GAMMATOTALDOSE NPP MS") field(INPB, "$(BL)GAMMAACT NPP MS") field(CALC, "(B<(-.09))||(B>1001)?A:A+(B/3600.)") field(EGU, "mR") field(PREC, "2") info(autosaveFields_pass0, "VAL") } record(calc, "$(BL)GAMMADAILYDOSE") { field(DESC, "gamma daily dose") field(INPA, "$(BL)GAMMADAILYDOSE NPP MS") field(INPB, "$(BL)GAMMAACT NPP MS") field(INPC, "$(IOC):SUBRESETCOUNT NPP") field(CALC, "(C!=0)?0:((B<(-.09))||(B>1001)?A:A+(B/3600.))") field(EGU, "mR") field(PREC, "2") info(autosaveFields_pass0, "VAL") }