record(asyn,"SIOC:B34:PP03:ASYN")
{
    field(DTYP,"asynRecordDevice")
    field(PORT,"PLC_RD")
    field(ADDR,"0")
    field(OMAX,"0")
    field(IMAX,"0")
}

#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi7") {
  field(DESC, "Port PLC_RD bit 7")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 7, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:00:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi7Valid") {
  field(INPA, "PLC:B34:PP02:Bi7.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:00:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:00:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi7 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi7Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:00:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:00:A0o") {
  field(DESC, "Bi7 --> A0.o0 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb7",20,19,0,0,"PLC:B34:PP02:PLC_RDb7")
#! Field("PLC:B34:PP02:PLC_RDb7.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb7.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb7.FLNK","PLC:B34:PP02:00:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb7.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb7.VAL")
#! Record("PLC:B34:PP02:00:A0o_calc",260,18,0,1,"PLC:B34:PP02:00:A0o_calc")
#! Field("PLC:B34:PP02:00:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:00:A0o_calc.INPA")
#! Link("PLC:B34:PP02:00:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb7.VAL")
#! Field("PLC:B34:PP02:00:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:00:A0o_calc.INPB")
#! Field("PLC:B34:PP02:00:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:00:A0o_calc.OUT")
#! Link("PLC:B34:PP02:00:A0o_calc.OUT","PLC:B34:PP02:00:A0o.VAL")
#! Record("PLC:B34:PP02:00:A0o",500,20,0,0,"PLC:B34:PP02:00:A0o")
#! Field("PLC:B34:PP02:00:A0o.VAL",16777215,1,"PLC:B34:PP02:00:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi6") {
  field(DESC, "Port PLC_RD bit 6")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 6, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:01:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi6Valid") {
  field(INPA, "PLC:B34:PP02:Bi6.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:01:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:01:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi6 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi6Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:01:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:01:A0o") {
  field(DESC, "Bi6 --> A0.o1 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb6",20,19,0,0,"PLC:B34:PP02:PLC_RDb6")
#! Field("PLC:B34:PP02:PLC_RDb6.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb6.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb6.FLNK","PLC:B34:PP02:01:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb6.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb6.VAL")
#! Record("PLC:B34:PP02:01:A0o_calc",260,18,0,1,"PLC:B34:PP02:01:A0o_calc")
#! Field("PLC:B34:PP02:01:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:01:A0o_calc.INPA")
#! Link("PLC:B34:PP02:01:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb6.VAL")
#! Field("PLC:B34:PP02:01:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:01:A0o_calc.INPB")
#! Field("PLC:B34:PP02:01:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:01:A0o_calc.OUT")
#! Link("PLC:B34:PP02:01:A0o_calc.OUT","PLC:B34:PP02:01:A0o.VAL")
#! Record("PLC:B34:PP02:01:A0o",500,20,0,0,"PLC:B34:PP02:01:A0o")
#! Field("PLC:B34:PP02:01:A0o.VAL",16777215,1,"PLC:B34:PP02:01:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi5") {
  field(DESC, "Port PLC_RD bit 5")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 5, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:02:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi5Valid") {
  field(INPA, "PLC:B34:PP02:Bi5.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:02:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:02:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi5 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi5Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:02:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:02:A0o") {
  field(DESC, "Bi5 --> A0.o2 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb5",20,19,0,0,"PLC:B34:PP02:PLC_RDb5")
#! Field("PLC:B34:PP02:PLC_RDb5.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb5.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb5.FLNK","PLC:B34:PP02:02:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb5.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb5.VAL")
#! Record("PLC:B34:PP02:02:A0o_calc",260,18,0,1,"PLC:B34:PP02:02:A0o_calc")
#! Field("PLC:B34:PP02:02:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:02:A0o_calc.INPA")
#! Link("PLC:B34:PP02:02:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb5.VAL")
#! Field("PLC:B34:PP02:02:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:02:A0o_calc.INPB")
#! Field("PLC:B34:PP02:02:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:02:A0o_calc.OUT")
#! Link("PLC:B34:PP02:02:A0o_calc.OUT","PLC:B34:PP02:02:A0o.VAL")
#! Record("PLC:B34:PP02:02:A0o",500,20,0,0,"PLC:B34:PP02:02:A0o")
#! Field("PLC:B34:PP02:02:A0o.VAL",16777215,1,"PLC:B34:PP02:02:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi4") {
  field(DESC, "Port PLC_RD bit 4")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 4, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:03:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi4Valid") {
  field(INPA, "PLC:B34:PP02:Bi4.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:03:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:03:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi4 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi4Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:03:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:03:A0o") {
  field(DESC, "Bi4 --> A0.o3 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb4",20,19,0,0,"PLC:B34:PP02:PLC_RDb4")
#! Field("PLC:B34:PP02:PLC_RDb4.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb4.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb4.FLNK","PLC:B34:PP02:03:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb4.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb4.VAL")
#! Record("PLC:B34:PP02:03:A0o_calc",260,18,0,1,"PLC:B34:PP02:03:A0o_calc")
#! Field("PLC:B34:PP02:03:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:03:A0o_calc.INPA")
#! Link("PLC:B34:PP02:03:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb4.VAL")
#! Field("PLC:B34:PP02:03:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:03:A0o_calc.INPB")
#! Field("PLC:B34:PP02:03:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:03:A0o_calc.OUT")
#! Link("PLC:B34:PP02:03:A0o_calc.OUT","PLC:B34:PP02:03:A0o.VAL")
#! Record("PLC:B34:PP02:03:A0o",500,20,0,0,"PLC:B34:PP02:03:A0o")
#! Field("PLC:B34:PP02:03:A0o.VAL",16777215,1,"PLC:B34:PP02:03:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi3") {
  field(DESC, "Port PLC_RD bit 3")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 3, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:04:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi3Valid") {
  field(INPA, "PLC:B34:PP02:Bi3.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:04:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:04:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi3 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi3Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:04:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:04:A0o") {
  field(DESC, "Bi3 --> A0.o4 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb3",20,19,0,0,"PLC:B34:PP02:PLC_RDb3")
#! Field("PLC:B34:PP02:PLC_RDb3.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb3.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb3.FLNK","PLC:B34:PP02:04:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb3.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb3.VAL")
#! Record("PLC:B34:PP02:04:A0o_calc",260,18,0,1,"PLC:B34:PP02:04:A0o_calc")
#! Field("PLC:B34:PP02:04:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:04:A0o_calc.INPA")
#! Link("PLC:B34:PP02:04:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb3.VAL")
#! Field("PLC:B34:PP02:04:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:04:A0o_calc.INPB")
#! Field("PLC:B34:PP02:04:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:04:A0o_calc.OUT")
#! Link("PLC:B34:PP02:04:A0o_calc.OUT","PLC:B34:PP02:04:A0o.VAL")
#! Record("PLC:B34:PP02:04:A0o",500,20,0,0,"PLC:B34:PP02:04:A0o")
#! Field("PLC:B34:PP02:04:A0o.VAL",16777215,1,"PLC:B34:PP02:04:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi2") {
  field(DESC, "Port PLC_RD bit 2")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 2, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:05:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi2Valid") {
  field(INPA, "PLC:B34:PP02:Bi2.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:05:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:05:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi2 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi2Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:05:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:05:A0o") {
  field(DESC, "Bi2 --> A0.o5 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb2",20,19,0,0,"PLC:B34:PP02:PLC_RDb2")
#! Field("PLC:B34:PP02:PLC_RDb2.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb2.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb2.FLNK","PLC:B34:PP02:05:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb2.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb2.VAL")
#! Record("PLC:B34:PP02:05:A0o_calc",260,18,0,1,"PLC:B34:PP02:05:A0o_calc")
#! Field("PLC:B34:PP02:05:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:05:A0o_calc.INPA")
#! Link("PLC:B34:PP02:05:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb2.VAL")
#! Field("PLC:B34:PP02:05:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:05:A0o_calc.INPB")
#! Field("PLC:B34:PP02:05:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:05:A0o_calc.OUT")
#! Link("PLC:B34:PP02:05:A0o_calc.OUT","PLC:B34:PP02:05:A0o.VAL")
#! Record("PLC:B34:PP02:05:A0o",500,20,0,0,"PLC:B34:PP02:05:A0o")
#! Field("PLC:B34:PP02:05:A0o.VAL",16777215,1,"PLC:B34:PP02:05:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi1") {
  field(DESC, "Port PLC_RD bit 1")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 1, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:06:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi1Valid") {
  field(INPA, "PLC:B34:PP02:Bi1.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:06:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:06:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi1 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi1Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:06:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:06:A0o") {
  field(DESC, "Bi1 --> A0.o6 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb1",20,19,0,0,"PLC:B34:PP02:PLC_RDb1")
#! Field("PLC:B34:PP02:PLC_RDb1.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb1.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb1.FLNK","PLC:B34:PP02:06:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb1.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb1.VAL")
#! Record("PLC:B34:PP02:06:A0o_calc",260,18,0,1,"PLC:B34:PP02:06:A0o_calc")
#! Field("PLC:B34:PP02:06:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:06:A0o_calc.INPA")
#! Link("PLC:B34:PP02:06:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb1.VAL")
#! Field("PLC:B34:PP02:06:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:06:A0o_calc.INPB")
#! Field("PLC:B34:PP02:06:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:06:A0o_calc.OUT")
#! Link("PLC:B34:PP02:06:A0o_calc.OUT","PLC:B34:PP02:06:A0o.VAL")
#! Record("PLC:B34:PP02:06:A0o",500,20,0,0,"PLC:B34:PP02:06:A0o")
#! Field("PLC:B34:PP02:06:A0o.VAL",16777215,1,"PLC:B34:PP02:06:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi0") {
  field(DESC, "Port PLC_RD bit 0")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 0, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:07:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi0Valid") {
  field(INPA, "PLC:B34:PP02:Bi0.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:07:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:07:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi0 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi0Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:07:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:07:A0o") {
  field(DESC, "Bi0 --> A0.o7 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb0",20,19,0,0,"PLC:B34:PP02:PLC_RDb0")
#! Field("PLC:B34:PP02:PLC_RDb0.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb0.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb0.FLNK","PLC:B34:PP02:07:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb0.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb0.VAL")
#! Record("PLC:B34:PP02:07:A0o_calc",260,18,0,1,"PLC:B34:PP02:07:A0o_calc")
#! Field("PLC:B34:PP02:07:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:07:A0o_calc.INPA")
#! Link("PLC:B34:PP02:07:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb0.VAL")
#! Field("PLC:B34:PP02:07:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:07:A0o_calc.INPB")
#! Field("PLC:B34:PP02:07:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:07:A0o_calc.OUT")
#! Link("PLC:B34:PP02:07:A0o_calc.OUT","PLC:B34:PP02:07:A0o.VAL")
#! Record("PLC:B34:PP02:07:A0o",500,20,0,0,"PLC:B34:PP02:07:A0o")
#! Field("PLC:B34:PP02:07:A0o.VAL",16777215,1,"PLC:B34:PP02:07:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi15") {
  field(DESC, "Port PLC_RD bit 15")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 15, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:08:AOo_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi15Valid") {
  field(INPA, "PLC:B34:PP02:Bi15.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:08:AOo_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:08:AOo_calc") {
  field(INPA, "PLC:B34:PP02:Bi15 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi15Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:08:AOo PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:08:AOo") {
  field(DESC, "Bi15 --> A0.o8 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb15",20,19,0,0,"PLC:B34:PP02:PLC_RDb15")
#! Field("PLC:B34:PP02:PLC_RDb15.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb15.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb15.FLNK","PLC:B34:PP02:08:AOo_calc")
#! Field("PLC:B34:PP02:PLC_RDb15.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb15.VAL")
#! Record("PLC:B34:PP02:08:AOo_calc",260,18,0,1,"PLC:B34:PP02:08:AOo_calc")
#! Field("PLC:B34:PP02:08:AOo_calc.INPA",16777215,0,"PLC:B34:PP02:08:AOo_calc.INPA")
#! Link("PLC:B34:PP02:08:AOo_calc.INPA","PLC:B34:PP02:PLC_RDb15.VAL")
#! Field("PLC:B34:PP02:08:AOo_calc.INPB",16777215,1,"PLC:B34:PP02:08:AOo_calc.INPB")
#! Field("PLC:B34:PP02:08:AOo_calc.OUT",16777215,1,"PLC:B34:PP02:08:AOo_calc.OUT")
#! Link("PLC:B34:PP02:08:AOo_calc.OUT","PLC:B34:PP02:08:AOo.VAL")
#! Record("PLC:B34:PP02:08:AOo",500,20,0,0,"PLC:B34:PP02:08:AOo")
#! Field("PLC:B34:PP02:08:AOo.VAL",16777215,1,"PLC:B34:PP02:08:AOo.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi14") {
  field(DESC, "Port PLC_RD bit 14")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 14, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:09:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi14Valid") {
  field(INPA, "PLC:B34:PP02:Bi14.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:09:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:09:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi14 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi14Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:09:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:09:A0o") {
  field(DESC, "Bi14 --> A0.o9 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb14",20,19,0,0,"PLC:B34:PP02:PLC_RDb14")
#! Field("PLC:B34:PP02:PLC_RDb14.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb14.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb14.FLNK","PLC:B34:PP02:09:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb14.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb14.VAL")
#! Record("PLC:B34:PP02:09:A0o_calc",260,18,0,1,"PLC:B34:PP02:09:A0o_calc")
#! Field("PLC:B34:PP02:09:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:09:A0o_calc.INPA")
#! Link("PLC:B34:PP02:09:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb14.VAL")
#! Field("PLC:B34:PP02:09:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:09:A0o_calc.INPB")
#! Field("PLC:B34:PP02:09:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:09:A0o_calc.OUT")
#! Link("PLC:B34:PP02:09:A0o_calc.OUT","PLC:B34:PP02:09:A0o.VAL")
#! Record("PLC:B34:PP02:09:A0o",500,20,0,0,"PLC:B34:PP02:09:A0o")
#! Field("PLC:B34:PP02:09:A0o.VAL",16777215,1,"PLC:B34:PP02:09:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi13") {
  field(DESC, "Port PLC_RD bit 13")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 13, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:10:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi13Valid") {
  field(INPA, "PLC:B34:PP02:Bi13.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:10:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:10:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi13 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi13Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:10:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:10:A0o") {
  field(DESC, "Bi13 --> A0.o10 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb13",20,19,0,0,"PLC:B34:PP02:PLC_RDb13")
#! Field("PLC:B34:PP02:PLC_RDb13.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb13.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb13.FLNK","PLC:B34:PP02:10:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb13.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb13.VAL")
#! Record("PLC:B34:PP02:10:A0o_calc",260,18,0,1,"PLC:B34:PP02:10:A0o_calc")
#! Field("PLC:B34:PP02:10:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:10:A0o_calc.INPA")
#! Link("PLC:B34:PP02:10:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb13.VAL")
#! Field("PLC:B34:PP02:10:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:10:A0o_calc.INPB")
#! Field("PLC:B34:PP02:10:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:10:A0o_calc.OUT")
#! Link("PLC:B34:PP02:10:A0o_calc.OUT","PLC:B34:PP02:10:A0o.VAL")
#! Record("PLC:B34:PP02:10:A0o",500,20,0,0,"PLC:B34:PP02:10:A0o")
#! Field("PLC:B34:PP02:10:A0o.VAL",16777215,1,"PLC:B34:PP02:10:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi12") {
  field(DESC, "Port PLC_RD bit 12")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 12, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:11:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi12Valid") {
  field(INPA, "PLC:B34:PP02:Bi12.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:11:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:11:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi12 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi12Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:11:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:11:A0o") {
  field(DESC, "Bi12 --> A0.o11 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb12",20,19,0,0,"PLC:B34:PP02:PLC_RDb12")
#! Field("PLC:B34:PP02:PLC_RDb12.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb12.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb12.FLNK","PLC:B34:PP02:11:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb12.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb12.VAL")
#! Record("PLC:B34:PP02:11:A0o_calc",260,18,0,1,"PLC:B34:PP02:11:A0o_calc")
#! Field("PLC:B34:PP02:11:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:11:A0o_calc.INPA")
#! Link("PLC:B34:PP02:11:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb12.VAL")
#! Field("PLC:B34:PP02:11:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:11:A0o_calc.INPB")
#! Field("PLC:B34:PP02:11:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:11:A0o_calc.OUT")
#! Link("PLC:B34:PP02:11:A0o_calc.OUT","PLC:B34:PP02:11:A0o.VAL")
#! Record("PLC:B34:PP02:11:A0o",500,20,0,0,"PLC:B34:PP02:11:A0o")
#! Field("PLC:B34:PP02:11:A0o.VAL",16777215,1,"PLC:B34:PP02:11:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi11") {
  field(DESC, "Port PLC_RD bit 11")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 11, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:12:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi11Valid") {
  field(INPA, "PLC:B34:PP02:Bi11.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:12:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:12:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi11 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi11Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:12:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:12:A0o") {
  field(DESC, "Bi11 --> A0.o12 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb11",20,19,0,0,"PLC:B34:PP02:PLC_RDb11")
#! Field("PLC:B34:PP02:PLC_RDb11.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb11.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb11.FLNK","PLC:B34:PP02:12:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb11.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb11.VAL")
#! Record("PLC:B34:PP02:12:A0o_calc",260,18,0,1,"PLC:B34:PP02:12:A0o_calc")
#! Field("PLC:B34:PP02:12:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:12:A0o_calc.INPA")
#! Link("PLC:B34:PP02:12:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb11.VAL")
#! Field("PLC:B34:PP02:12:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:12:A0o_calc.INPB")
#! Field("PLC:B34:PP02:12:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:12:A0o_calc.OUT")
#! Link("PLC:B34:PP02:12:A0o_calc.OUT","PLC:B34:PP02:12:A0o.VAL")
#! Record("PLC:B34:PP02:12:A0o",500,20,0,0,"PLC:B34:PP02:12:A0o")
#! Field("PLC:B34:PP02:12:A0o.VAL",16777215,1,"PLC:B34:PP02:12:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi10") {
  field(DESC, "Port PLC_RD bit 10")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 10, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:13:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi10Valid") {
  field(INPA, "PLC:B34:PP02:Bi10.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:13:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:13:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi10 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi10Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:13:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:13:A0o") {
  field(DESC, "Bi10 --> A0.o13 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb10",20,19,0,0,"PLC:B34:PP02:PLC_RDb10")
#! Field("PLC:B34:PP02:PLC_RDb10.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb10.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb10.FLNK","PLC:B34:PP02:13:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb10.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb10.VAL")
#! Record("PLC:B34:PP02:13:A0o_calc",260,18,0,1,"PLC:B34:PP02:13:A0o_calc")
#! Field("PLC:B34:PP02:13:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:13:A0o_calc.INPA")
#! Link("PLC:B34:PP02:13:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb10.VAL")
#! Field("PLC:B34:PP02:13:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:13:A0o_calc.INPB")
#! Field("PLC:B34:PP02:13:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:13:A0o_calc.OUT")
#! Link("PLC:B34:PP02:13:A0o_calc.OUT","PLC:B34:PP02:13:A0o.VAL")
#! Record("PLC:B34:PP02:13:A0o",500,20,0,0,"PLC:B34:PP02:13:A0o")
#! Field("PLC:B34:PP02:13:A0o.VAL",16777215,1,"PLC:B34:PP02:13:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi9") {
  field(DESC, "Port PLC_RD bit 9")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 9, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:14:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi9Valid") {
  field(INPA, "PLC:B34:PP02:Bi9.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:14:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:14:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi9 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi9Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:14:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:14:A0o") {
  field(DESC, "Bi9  --> A0.o14 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb9",20,19,0,0,"PLC:B34:PP02:PLC_RDb9")
#! Field("PLC:B34:PP02:PLC_RDb9.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb9.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb9.FLNK","PLC:B34:PP02:14:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb9.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb9.VAL")
#! Record("PLC:B34:PP02:14:A0o_calc",260,18,0,1,"PLC:B34:PP02:14:A0o_calc")
#! Field("PLC:B34:PP02:14:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:14:A0o_calc.INPA")
#! Link("PLC:B34:PP02:14:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb9.VAL")
#! Field("PLC:B34:PP02:14:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:14:A0o_calc.INPB")
#! Field("PLC:B34:PP02:14:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:14:A0o_calc.OUT")
#! Link("PLC:B34:PP02:14:A0o_calc.OUT","PLC:B34:PP02:14:A0o.VAL")
#! Record("PLC:B34:PP02:14:A0o",500,20,0,0,"PLC:B34:PP02:14:A0o")
#! Field("PLC:B34:PP02:14:A0o.VAL",16777215,1,"PLC:B34:PP02:14:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi8") {
  field(DESC, "Port PLC_RD bit 8")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 8, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:15:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi8Valid") {
  field(INPA, "PLC:B34:PP02:Bi8.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:15:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:15:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi8 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi8Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:15:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:15:A0o") {
  field(DESC, "Bi8  --> A0.o15 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb8",20,19,0,0,"PLC:B34:PP02:PLC_RDb8")
#! Field("PLC:B34:PP02:PLC_RDb8.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb8.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb8.FLNK","PLC:B34:PP02:15:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb8.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb8.VAL")
#! Record("PLC:B34:PP02:15:A0o_calc",260,18,0,1,"PLC:B34:PP02:15:A0o_calc")
#! Field("PLC:B34:PP02:15:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:15:A0o_calc.INPA")
#! Link("PLC:B34:PP02:15:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb8.VAL")
#! Field("PLC:B34:PP02:15:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:15:A0o_calc.INPB")
#! Field("PLC:B34:PP02:15:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:15:A0o_calc.OUT")
#! Link("PLC:B34:PP02:15:A0o_calc.OUT","PLC:B34:PP02:15:A0o.VAL")
#! Record("PLC:B34:PP02:15:A0o",500,20,0,0,"PLC:B34:PP02:15:A0o")
#! Field("PLC:B34:PP02:15:A0o.VAL",16777215,1,"PLC:B34:PP02:15:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi23") {
  field(DESC, "Port PLC_RD bit 23")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 23, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:16:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi23Valid") {
  field(INPA, "PLC:B34:PP02:Bi23.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:16:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:16:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi23 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi23Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:16:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:16:A0o") {
  field(DESC, "Bi23 --> A0.o16 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb23",20,19,0,0,"PLC:B34:PP02:PLC_RDb23")
#! Field("PLC:B34:PP02:PLC_RDb23.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb23.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb23.FLNK","PLC:B34:PP02:16:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb23.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb23.VAL")
#! Record("PLC:B34:PP02:16:A0o_calc",260,18,0,1,"PLC:B34:PP02:16:A0o_calc")
#! Field("PLC:B34:PP02:16:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:16:A0o_calc.INPA")
#! Link("PLC:B34:PP02:16:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb23.VAL")
#! Field("PLC:B34:PP02:16:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:16:A0o_calc.INPB")
#! Field("PLC:B34:PP02:16:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:16:A0o_calc.OUT")
#! Link("PLC:B34:PP02:16:A0o_calc.OUT","PLC:B34:PP02:16:A0o.VAL")
#! Record("PLC:B34:PP02:16:A0o",500,20,0,0,"PLC:B34:PP02:16:A0o")
#! Field("PLC:B34:PP02:16:A0o.VAL",16777215,1,"PLC:B34:PP02:16:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi22") {
  field(DESC, "Port PLC_RD bit 22")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 22, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:17:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi22Valid") {
  field(INPA, "PLC:B34:PP02:Bi22.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:17:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:17:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi22 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi22Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:17:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:17:A0o") {
  field(DESC, "Bi22 --> A0.o17 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb22",20,19,0,0,"PLC:B34:PP02:PLC_RDb22")
#! Field("PLC:B34:PP02:PLC_RDb22.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb22.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb22.FLNK","PLC:B34:PP02:17:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb22.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb22.VAL")
#! Record("PLC:B34:PP02:17:A0o_calc",260,18,0,1,"PLC:B34:PP02:17:A0o_calc")
#! Field("PLC:B34:PP02:17:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:17:A0o_calc.INPA")
#! Link("PLC:B34:PP02:17:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb22.VAL")
#! Field("PLC:B34:PP02:17:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:17:A0o_calc.INPB")
#! Field("PLC:B34:PP02:17:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:17:A0o_calc.OUT")
#! Link("PLC:B34:PP02:17:A0o_calc.OUT","PLC:B34:PP02:17:A0o.VAL")
#! Record("PLC:B34:PP02:17:A0o",500,20,0,0,"PLC:B34:PP02:17:A0o")
#! Field("PLC:B34:PP02:17:A0o.VAL",16777215,1,"PLC:B34:PP02:17:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi21") {
  field(DESC, "Port PLC_RD bit 21")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 21, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:18:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi21Valid") {
  field(INPA, "PLC:B34:PP02:Bi21.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:18:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:18:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi21 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi21Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:18:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:18:A0o") {
  field(DESC, "Bi21 --> A0.o18 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb21",20,19,0,0,"PLC:B34:PP02:PLC_RDb21")
#! Field("PLC:B34:PP02:PLC_RDb21.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb21.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb21.FLNK","PLC:B34:PP02:18:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb21.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb21.VAL")
#! Record("PLC:B34:PP02:18:A0o_calc",260,18,0,1,"PLC:B34:PP02:18:A0o_calc")
#! Field("PLC:B34:PP02:18:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:18:A0o_calc.INPA")
#! Link("PLC:B34:PP02:18:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb21.VAL")
#! Field("PLC:B34:PP02:18:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:18:A0o_calc.INPB")
#! Field("PLC:B34:PP02:18:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:18:A0o_calc.OUT")
#! Link("PLC:B34:PP02:18:A0o_calc.OUT","PLC:B34:PP02:18:A0o.VAL")
#! Record("PLC:B34:PP02:18:A0o",500,20,0,0,"PLC:B34:PP02:18:A0o")
#! Field("PLC:B34:PP02:18:A0o.VAL",16777215,1,"PLC:B34:PP02:18:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi20") {
  field(DESC, "Port PLC_RD bit 20")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 20, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:19:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi20Valid") {
  field(INPA, "PLC:B34:PP02:Bi20.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:19:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:19:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi20 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi20Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:19:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:19:A0o") {
  field(DESC, "Bi20 --> A0.o19 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb20",20,19,0,0,"PLC:B34:PP02:PLC_RDb20")
#! Field("PLC:B34:PP02:PLC_RDb20.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb20.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb20.FLNK","PLC:B34:PP02:19:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb20.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb20.VAL")
#! Record("PLC:B34:PP02:19:A0o_calc",260,18,0,1,"PLC:B34:PP02:19:A0o_calc")
#! Field("PLC:B34:PP02:19:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:19:A0o_calc.INPA")
#! Link("PLC:B34:PP02:19:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb20.VAL")
#! Field("PLC:B34:PP02:19:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:19:A0o_calc.INPB")
#! Field("PLC:B34:PP02:19:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:19:A0o_calc.OUT")
#! Link("PLC:B34:PP02:19:A0o_calc.OUT","PLC:B34:PP02:19:A0o.VAL")
#! Record("PLC:B34:PP02:19:A0o",500,20,0,0,"PLC:B34:PP02:19:A0o")
#! Field("PLC:B34:PP02:19:A0o.VAL",16777215,1,"PLC:B34:PP02:19:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi19") {
  field(DESC, "Port PLC_RD bit 19")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 19, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:20:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi19Valid") {
  field(INPA, "PLC:B34:PP02:Bi19.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:20:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:20:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi19 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi19Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:20:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:20:A0o") {
  field(DESC, "Bi19 --> A0.o20 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb19",20,19,0,0,"PLC:B34:PP02:PLC_RDb19")
#! Field("PLC:B34:PP02:PLC_RDb19.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb19.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb19.FLNK","PLC:B34:PP02:20:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb19.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb19.VAL")
#! Record("PLC:B34:PP02:20:A0o_calc",260,18,0,1,"PLC:B34:PP02:20:A0o_calc")
#! Field("PLC:B34:PP02:20:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:20:A0o_calc.INPA")
#! Link("PLC:B34:PP02:20:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb19.VAL")
#! Field("PLC:B34:PP02:20:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:20:A0o_calc.INPB")
#! Field("PLC:B34:PP02:20:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:20:A0o_calc.OUT")
#! Link("PLC:B34:PP02:20:A0o_calc.OUT","PLC:B34:PP02:20:A0o.VAL")
#! Record("PLC:B34:PP02:20:A0o",500,20,0,0,"PLC:B34:PP02:20:A0o")
#! Field("PLC:B34:PP02:20:A0o.VAL",16777215,1,"PLC:B34:PP02:20:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi18") {
  field(DESC, "Port PLC_RD bit 18")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 18, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:21:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi18Valid") {
  field(INPA, "PLC:B34:PP02:Bi18.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:21:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:21:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi18 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi18Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:21:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:21:A0o") {
  field(DESC, "Bi18 --> A0.o21 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb18",20,19,0,0,"PLC:B34:PP02:PLC_RDb18")
#! Field("PLC:B34:PP02:PLC_RDb18.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb18.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb18.FLNK","PLC:B34:PP02:21:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb18.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb18.VAL")
#! Record("PLC:B34:PP02:21:A0o_calc",260,18,0,1,"PLC:B34:PP02:21:A0o_calc")
#! Field("PLC:B34:PP02:21:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:21:A0o_calc.INPA")
#! Link("PLC:B34:PP02:21:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb18.VAL")
#! Field("PLC:B34:PP02:21:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:21:A0o_calc.INPB")
#! Field("PLC:B34:PP02:21:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:21:A0o_calc.OUT")
#! Link("PLC:B34:PP02:21:A0o_calc.OUT","PLC:B34:PP02:21:A0o.VAL")
#! Record("PLC:B34:PP02:21:A0o",500,20,0,0,"PLC:B34:PP02:21:A0o")
#! Field("PLC:B34:PP02:21:A0o.VAL",16777215,1,"PLC:B34:PP02:21:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi17") {
  field(DESC, "Port PLC_RD bit 17")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 17, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:22:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi17Valid") {
  field(INPA, "PLC:B34:PP02:Bi17.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:22:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:22:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi17 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi17Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:22:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:22:A0o") {
  field(DESC, "Bi17 --> A0.o22 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb17",20,19,0,0,"PLC:B34:PP02:PLC_RDb17")
#! Field("PLC:B34:PP02:PLC_RDb17.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb17.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb17.FLNK","PLC:B34:PP02:22:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb17.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb17.VAL")
#! Record("PLC:B34:PP02:22:A0o_calc",260,18,0,1,"PLC:B34:PP02:22:A0o_calc")
#! Field("PLC:B34:PP02:22:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:22:A0o_calc.INPA")
#! Link("PLC:B34:PP02:22:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb17.VAL")
#! Field("PLC:B34:PP02:22:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:22:A0o_calc.INPB")
#! Field("PLC:B34:PP02:22:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:22:A0o_calc.OUT")
#! Link("PLC:B34:PP02:22:A0o_calc.OUT","PLC:B34:PP02:22:A0o.VAL")
#! Record("PLC:B34:PP02:22:A0o",500,20,0,0,"PLC:B34:PP02:22:A0o")
#! Field("PLC:B34:PP02:22:A0o.VAL",16777215,1,"PLC:B34:PP02:22:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi16") {
  field(DESC, "Port PLC_RD bit 16")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 16, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:23:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi16Valid") {
  field(INPA, "PLC:B34:PP02:Bi16.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:23:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:23:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi16 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi16Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:23:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:23:A0o") {
  field(DESC, "Bi16 --> A0.o23 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb16",20,19,0,0,"PLC:B34:PP02:PLC_RDb16")
#! Field("PLC:B34:PP02:PLC_RDb16.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb16.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb16.FLNK","PLC:B34:PP02:23:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb16.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb16.VAL")
#! Record("PLC:B34:PP02:23:A0o_calc",260,18,0,1,"PLC:B34:PP02:23:A0o_calc")
#! Field("PLC:B34:PP02:23:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:23:A0o_calc.INPA")
#! Link("PLC:B34:PP02:23:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb16.VAL")
#! Field("PLC:B34:PP02:23:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:23:A0o_calc.INPB")
#! Field("PLC:B34:PP02:23:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:23:A0o_calc.OUT")
#! Link("PLC:B34:PP02:23:A0o_calc.OUT","PLC:B34:PP02:23:A0o.VAL")
#! Record("PLC:B34:PP02:23:A0o",500,20,0,0,"PLC:B34:PP02:23:A0o")
#! Field("PLC:B34:PP02:23:A0o.VAL",16777215,1,"PLC:B34:PP02:23:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi95") {
  field(DESC, "Port PLC_RD bit 95")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 95, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:64:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi95Valid") {
  field(INPA, "PLC:B34:PP02:Bi95.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:64:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:64:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi95 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi95Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:64:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:64:A0o") {
  field(DESC, "Bi95 --> A0.o64 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb95",20,19,0,0,"PLC:B34:PP02:PLC_RDb95")
#! Field("PLC:B34:PP02:PLC_RDb95.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb95.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb95.FLNK","PLC:B34:PP02:64:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb95.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb95.VAL")
#! Record("PLC:B34:PP02:64:A0o_calc",260,18,0,1,"PLC:B34:PP02:64:A0o_calc")
#! Field("PLC:B34:PP02:64:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:64:A0o_calc.INPA")
#! Link("PLC:B34:PP02:64:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb95.VAL")
#! Field("PLC:B34:PP02:64:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:64:A0o_calc.INPB")
#! Field("PLC:B34:PP02:64:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:64:A0o_calc.OUT")
#! Link("PLC:B34:PP02:64:A0o_calc.OUT","PLC:B34:PP02:64:A0o.VAL")
#! Record("PLC:B34:PP02:64:A0o",500,20,0,0,"PLC:B34:PP02:64:A0o")
#! Field("PLC:B34:PP02:64:A0o.VAL",16777215,1,"PLC:B34:PP02:64:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi94") {
  field(DESC, "Port PLC_RD bit 94")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 94, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:65:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi94Valid") {
  field(INPA, "PLC:B34:PP02:Bi94.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:65:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:65:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi94 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi94Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:65:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:65:A0o") {
  field(DESC, "Bi94 --> A0.o65 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb94",20,19,0,0,"PLC:B34:PP02:PLC_RDb94")
#! Field("PLC:B34:PP02:PLC_RDb94.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb94.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb94.FLNK","PLC:B34:PP02:65:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb94.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb94.VAL")
#! Record("PLC:B34:PP02:65:A0o_calc",260,18,0,1,"PLC:B34:PP02:65:A0o_calc")
#! Field("PLC:B34:PP02:65:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:65:A0o_calc.INPA")
#! Link("PLC:B34:PP02:65:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb94.VAL")
#! Field("PLC:B34:PP02:65:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:65:A0o_calc.INPB")
#! Field("PLC:B34:PP02:65:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:65:A0o_calc.OUT")
#! Link("PLC:B34:PP02:65:A0o_calc.OUT","PLC:B34:PP02:65:A0o.VAL")
#! Record("PLC:B34:PP02:65:A0o",500,20,0,0,"PLC:B34:PP02:65:A0o")
#! Field("PLC:B34:PP02:65:A0o.VAL",16777215,1,"PLC:B34:PP02:65:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi93") {
  field(DESC, "Port PLC_RD bit 93")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 93, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:66:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi93Valid") {
  field(INPA, "PLC:B34:PP02:Bi93.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:66:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:66:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi93 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi93Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:66:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:66:A0o") {
  field(DESC, "Bi93 --> A0.o66 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb93",20,19,0,0,"PLC:B34:PP02:PLC_RDb93")
#! Field("PLC:B34:PP02:PLC_RDb93.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb93.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb93.FLNK","PLC:B34:PP02:66:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb93.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb93.VAL")
#! Record("PLC:B34:PP02:66:A0o_calc",260,18,0,1,"PLC:B34:PP02:66:A0o_calc")
#! Field("PLC:B34:PP02:66:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:66:A0o_calc.INPA")
#! Link("PLC:B34:PP02:66:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb93.VAL")
#! Field("PLC:B34:PP02:66:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:66:A0o_calc.INPB")
#! Field("PLC:B34:PP02:66:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:66:A0o_calc.OUT")
#! Link("PLC:B34:PP02:66:A0o_calc.OUT","PLC:B34:PP02:66:A0o.VAL")
#! Record("PLC:B34:PP02:66:A0o",500,20,0,0,"PLC:B34:PP02:66:A0o")
#! Field("PLC:B34:PP02:66:A0o.VAL",16777215,1,"PLC:B34:PP02:66:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi92") {
  field(DESC, "Port PLC_RD bit 92")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 92, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:67:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi92Valid") {
  field(INPA, "PLC:B34:PP02:Bi92.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:67:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:67:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi92 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi92Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:67:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:67:A0o") {
  field(DESC, "Bi92 --> A0.o67 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb92",20,19,0,0,"PLC:B34:PP02:PLC_RDb92")
#! Field("PLC:B34:PP02:PLC_RDb92.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb92.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb92.FLNK","PLC:B34:PP02:67:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb92.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb92.VAL")
#! Record("PLC:B34:PP02:67:A0o_calc",260,18,0,1,"PLC:B34:PP02:67:A0o_calc")
#! Field("PLC:B34:PP02:67:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:67:A0o_calc.INPA")
#! Link("PLC:B34:PP02:67:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb92.VAL")
#! Field("PLC:B34:PP02:67:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:67:A0o_calc.INPB")
#! Field("PLC:B34:PP02:67:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:67:A0o_calc.OUT")
#! Link("PLC:B34:PP02:67:A0o_calc.OUT","PLC:B34:PP02:67:A0o.VAL")
#! Record("PLC:B34:PP02:67:A0o",500,20,0,0,"PLC:B34:PP02:67:A0o")
#! Field("PLC:B34:PP02:67:A0o.VAL",16777215,1,"PLC:B34:PP02:67:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi91") {
  field(DESC, "Port PLC_RD bit 91")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 91, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:68:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi91Valid") {
  field(INPA, "PLC:B34:PP02:Bi91.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:68:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:68:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi91 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi91Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:68:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:68:A0o") {
  field(DESC, "Bi91 --> A0.o68 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb91",20,19,0,0,"PLC:B34:PP02:PLC_RDb91")
#! Field("PLC:B34:PP02:PLC_RDb91.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb91.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb91.FLNK","PLC:B34:PP02:68:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb91.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb91.VAL")
#! Record("PLC:B34:PP02:68:A0o_calc",260,18,0,1,"PLC:B34:PP02:68:A0o_calc")
#! Field("PLC:B34:PP02:68:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:68:A0o_calc.INPA")
#! Link("PLC:B34:PP02:68:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb91.VAL")
#! Field("PLC:B34:PP02:68:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:68:A0o_calc.INPB")
#! Field("PLC:B34:PP02:68:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:68:A0o_calc.OUT")
#! Link("PLC:B34:PP02:68:A0o_calc.OUT","PLC:B34:PP02:68:A0o.VAL")
#! Record("PLC:B34:PP02:68:A0o",500,20,0,0,"PLC:B34:PP02:68:A0o")
#! Field("PLC:B34:PP02:68:A0o.VAL",16777215,1,"PLC:B34:PP02:68:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi90") {
  field(DESC, "Port PLC_RD bit 90")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 90, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:69:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi90Valid") {
  field(INPA, "PLC:B34:PP02:Bi90.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:69:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:69:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi90 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi90Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:69:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:69:A0o") {
  field(DESC, "Bi90 --> A0.o69 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb90",20,19,0,0,"PLC:B34:PP02:PLC_RDb90")
#! Field("PLC:B34:PP02:PLC_RDb90.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb90.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb90.FLNK","PLC:B34:PP02:69:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb90.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb90.VAL")
#! Record("PLC:B34:PP02:69:A0o_calc",260,18,0,1,"PLC:B34:PP02:69:A0o_calc")
#! Field("PLC:B34:PP02:69:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:69:A0o_calc.INPA")
#! Link("PLC:B34:PP02:69:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb90.VAL")
#! Field("PLC:B34:PP02:69:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:69:A0o_calc.INPB")
#! Field("PLC:B34:PP02:69:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:69:A0o_calc.OUT")
#! Link("PLC:B34:PP02:69:A0o_calc.OUT","PLC:B34:PP02:69:A0o.VAL")
#! Record("PLC:B34:PP02:69:A0o",500,20,0,0,"PLC:B34:PP02:69:A0o")
#! Field("PLC:B34:PP02:69:A0o.VAL",16777215,1,"PLC:B34:PP02:69:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi89") {
  field(DESC, "Port PLC_RD bit 89")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 89, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:70:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi89Valid") {
  field(INPA, "PLC:B34:PP02:Bi89.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:70:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:70:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi89 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi89Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:70:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:70:A0o") {
  field(DESC, "Bi89 --> A0.o70 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb89",20,19,0,0,"PLC:B34:PP02:PLC_RDb89")
#! Field("PLC:B34:PP02:PLC_RDb89.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb89.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb89.FLNK","PLC:B34:PP02:70:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb89.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb89.VAL")
#! Record("PLC:B34:PP02:70:A0o_calc",260,18,0,1,"PLC:B34:PP02:70:A0o_calc")
#! Field("PLC:B34:PP02:70:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:70:A0o_calc.INPA")
#! Link("PLC:B34:PP02:70:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb89.VAL")
#! Field("PLC:B34:PP02:70:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:70:A0o_calc.INPB")
#! Field("PLC:B34:PP02:70:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:70:A0o_calc.OUT")
#! Link("PLC:B34:PP02:70:A0o_calc.OUT","PLC:B34:PP02:70:A0o.VAL")
#! Record("PLC:B34:PP02:70:A0o",500,20,0,0,"PLC:B34:PP02:70:A0o")
#! Field("PLC:B34:PP02:70:A0o.VAL",16777215,1,"PLC:B34:PP02:70:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi88") {
  field(DESC, "Port PLC_RD bit 88")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 88, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:71:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi88Valid") {
  field(INPA, "PLC:B34:PP02:Bi88.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:71:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:71:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi88 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi88Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:71:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:71:A0o") {
  field(DESC, "Bi88 --> A0.o71 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb88",20,19,0,0,"PLC:B34:PP02:PLC_RDb88")
#! Field("PLC:B34:PP02:PLC_RDb88.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb88.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb88.FLNK","PLC:B34:PP02:71:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb88.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb88.VAL")
#! Record("PLC:B34:PP02:71:A0o_calc",260,18,0,1,"PLC:B34:PP02:71:A0o_calc")
#! Field("PLC:B34:PP02:71:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:71:A0o_calc.INPA")
#! Link("PLC:B34:PP02:71:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb88.VAL")
#! Field("PLC:B34:PP02:71:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:71:A0o_calc.INPB")
#! Field("PLC:B34:PP02:71:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:71:A0o_calc.OUT")
#! Link("PLC:B34:PP02:71:A0o_calc.OUT","PLC:B34:PP02:71:A0o.VAL")
#! Record("PLC:B34:PP02:71:A0o",500,20,0,0,"PLC:B34:PP02:71:A0o")
#! Field("PLC:B34:PP02:71:A0o.VAL",16777215,1,"PLC:B34:PP02:71:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi103") {
  field(DESC, "Port PLC_RD bit 103")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 103, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:72:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi103Valid") {
  field(INPA, "PLC:B34:PP02:Bi103.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:72:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:72:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi103 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi103Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:72:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:72:A0o") {
  field(DESC, "Bi103 --> A0.o72 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb103",20,19,0,0,"PLC:B34:PP02:PLC_RDb103")
#! Field("PLC:B34:PP02:PLC_RDb103.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb103.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb103.FLNK","PLC:B34:PP02:72:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb103.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb103.VAL")
#! Record("PLC:B34:PP02:72:A0o_calc",260,18,0,1,"PLC:B34:PP02:72:A0o_calc")
#! Field("PLC:B34:PP02:72:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:72:A0o_calc.INPA")
#! Link("PLC:B34:PP02:72:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb103.VAL")
#! Field("PLC:B34:PP02:72:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:72:A0o_calc.INPB")
#! Field("PLC:B34:PP02:72:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:72:A0o_calc.OUT")
#! Link("PLC:B34:PP02:72:A0o_calc.OUT","PLC:B34:PP02:72:A0o.VAL")
#! Record("PLC:B34:PP02:72:A0o",500,20,0,0,"PLC:B34:PP02:72:A0o")
#! Field("PLC:B34:PP02:72:A0o.VAL",16777215,1,"PLC:B34:PP02:72:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi102") {
  field(DESC, "Port PLC_RD bit 102")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 102, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:73:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi102Valid") {
  field(INPA, "PLC:B34:PP02:Bi102.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:73:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:73:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi102 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi102Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:73:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:73:A0o") {
  field(DESC, "Bi102 --> A0.o73 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb102",20,19,0,0,"PLC:B34:PP02:PLC_RDb102")
#! Field("PLC:B34:PP02:PLC_RDb102.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb102.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb102.FLNK","PLC:B34:PP02:73:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb102.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb102.VAL")
#! Record("PLC:B34:PP02:73:A0o_calc",260,18,0,1,"PLC:B34:PP02:73:A0o_calc")
#! Field("PLC:B34:PP02:73:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:73:A0o_calc.INPA")
#! Link("PLC:B34:PP02:73:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb102.VAL")
#! Field("PLC:B34:PP02:73:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:73:A0o_calc.INPB")
#! Field("PLC:B34:PP02:73:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:73:A0o_calc.OUT")
#! Link("PLC:B34:PP02:73:A0o_calc.OUT","PLC:B34:PP02:73:A0o.VAL")
#! Record("PLC:B34:PP02:73:A0o",500,20,0,0,"PLC:B34:PP02:73:A0o")
#! Field("PLC:B34:PP02:73:A0o.VAL",16777215,1,"PLC:B34:PP02:73:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi101") {
  field(DESC, "Port PLC_RD bit 101")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 101, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:74:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi101Valid") {
  field(INPA, "PLC:B34:PP02:Bi101.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:74:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:74:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi101 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi101Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:74:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:74:A0o") {
  field(DESC, "Bi101 --> A0.o74 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb101",20,19,0,0,"PLC:B34:PP02:PLC_RDb101")
#! Field("PLC:B34:PP02:PLC_RDb101.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb101.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb101.FLNK","PLC:B34:PP02:74:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb101.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb101.VAL")
#! Record("PLC:B34:PP02:74:A0o_calc",260,18,0,1,"PLC:B34:PP02:74:A0o_calc")
#! Field("PLC:B34:PP02:74:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:74:A0o_calc.INPA")
#! Link("PLC:B34:PP02:74:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb101.VAL")
#! Field("PLC:B34:PP02:74:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:74:A0o_calc.INPB")
#! Field("PLC:B34:PP02:74:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:74:A0o_calc.OUT")
#! Link("PLC:B34:PP02:74:A0o_calc.OUT","PLC:B34:PP02:74:A0o.VAL")
#! Record("PLC:B34:PP02:74:A0o",500,20,0,0,"PLC:B34:PP02:74:A0o")
#! Field("PLC:B34:PP02:74:A0o.VAL",16777215,1,"PLC:B34:PP02:74:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi100") {
  field(DESC, "Port PLC_RD bit 100")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 100, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:75:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi100Valid") {
  field(INPA, "PLC:B34:PP02:Bi100.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:75:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:75:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi100 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi100Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:75:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:75:A0o") {
  field(DESC, "Bi100 --> A0.o75 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb100",20,19,0,0,"PLC:B34:PP02:PLC_RDb100")
#! Field("PLC:B34:PP02:PLC_RDb100.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb100.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb100.FLNK","PLC:B34:PP02:75:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb100.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb100.VAL")
#! Record("PLC:B34:PP02:75:A0o_calc",260,18,0,1,"PLC:B34:PP02:75:A0o_calc")
#! Field("PLC:B34:PP02:75:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:75:A0o_calc.INPA")
#! Link("PLC:B34:PP02:75:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb100.VAL")
#! Field("PLC:B34:PP02:75:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:75:A0o_calc.INPB")
#! Field("PLC:B34:PP02:75:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:75:A0o_calc.OUT")
#! Link("PLC:B34:PP02:75:A0o_calc.OUT","PLC:B34:PP02:75:A0o.VAL")
#! Record("PLC:B34:PP02:75:A0o",500,20,0,0,"PLC:B34:PP02:75:A0o")
#! Field("PLC:B34:PP02:75:A0o.VAL",16777215,1,"PLC:B34:PP02:75:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi99") {
  field(DESC, "Port PLC_RD bit 99")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 99, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:76:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi99Valid") {
  field(INPA, "PLC:B34:PP02:Bi99.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:76:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:76:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi99 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi99Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:76:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:76:A0o") {
  field(DESC, "Bi99  --> A0.o76 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb99",20,19,0,0,"PLC:B34:PP02:PLC_RDb99")
#! Field("PLC:B34:PP02:PLC_RDb99.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb99.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb99.FLNK","PLC:B34:PP02:76:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb99.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb99.VAL")
#! Record("PLC:B34:PP02:76:A0o_calc",260,18,0,1,"PLC:B34:PP02:76:A0o_calc")
#! Field("PLC:B34:PP02:76:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:76:A0o_calc.INPA")
#! Link("PLC:B34:PP02:76:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb99.VAL")
#! Field("PLC:B34:PP02:76:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:76:A0o_calc.INPB")
#! Field("PLC:B34:PP02:76:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:76:A0o_calc.OUT")
#! Link("PLC:B34:PP02:76:A0o_calc.OUT","PLC:B34:PP02:76:A0o.VAL")
#! Record("PLC:B34:PP02:76:A0o",500,20,0,0,"PLC:B34:PP02:76:A0o")
#! Field("PLC:B34:PP02:76:A0o.VAL",16777215,1,"PLC:B34:PP02:76:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi98") {
  field(DESC, "Port PLC_RD bit 98")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 98, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:77:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi98Valid") {
  field(INPA, "PLC:B34:PP02:Bi98.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:77:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:77:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi98 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi98Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:77:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:77:A0o") {
  field(DESC, "Bi98  --> A0.o77 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb98",20,19,0,0,"PLC:B34:PP02:PLC_RDb98")
#! Field("PLC:B34:PP02:PLC_RDb98.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb98.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb98.FLNK","PLC:B34:PP02:77:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb98.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb98.VAL")
#! Record("PLC:B34:PP02:77:A0o_calc",260,18,0,1,"PLC:B34:PP02:77:A0o_calc")
#! Field("PLC:B34:PP02:77:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:77:A0o_calc.INPA")
#! Link("PLC:B34:PP02:77:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb98.VAL")
#! Field("PLC:B34:PP02:77:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:77:A0o_calc.INPB")
#! Field("PLC:B34:PP02:77:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:77:A0o_calc.OUT")
#! Link("PLC:B34:PP02:77:A0o_calc.OUT","PLC:B34:PP02:77:A0o.VAL")
#! Record("PLC:B34:PP02:77:A0o",500,20,0,0,"PLC:B34:PP02:77:A0o")
#! Field("PLC:B34:PP02:77:A0o.VAL",16777215,1,"PLC:B34:PP02:77:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi97") {
  field(DESC, "Port PLC_RD bit 97")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 97, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:78:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi97Valid") {
  field(INPA, "PLC:B34:PP02:Bi97.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:78:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:78:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi97 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi97Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:78:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:78:A0o") {
  field(DESC, "Bi97  --> A0.o78 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb97",20,19,0,0,"PLC:B34:PP02:PLC_RDb97")
#! Field("PLC:B34:PP02:PLC_RDb97.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb97.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb97.FLNK","PLC:B34:PP02:78:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb97.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb97.VAL")
#! Record("PLC:B34:PP02:78:A0o_calc",260,18,0,1,"PLC:B34:PP02:78:A0o_calc")
#! Field("PLC:B34:PP02:78:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:78:A0o_calc.INPA")
#! Link("PLC:B34:PP02:78:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb97.VAL")
#! Field("PLC:B34:PP02:78:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:78:A0o_calc.INPB")
#! Field("PLC:B34:PP02:78:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:78:A0o_calc.OUT")
#! Link("PLC:B34:PP02:78:A0o_calc.OUT","PLC:B34:PP02:78:A0o.VAL")
#! Record("PLC:B34:PP02:78:A0o",500,20,0,0,"PLC:B34:PP02:78:A0o")
#! Field("PLC:B34:PP02:78:A0o.VAL",16777215,1,"PLC:B34:PP02:78:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi96") {
  field(DESC, "Port PLC_RD bit 96")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 96, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:79:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi96Valid") {
  field(INPA, "PLC:B34:PP02:Bi96.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:79:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:79:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi96 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi96Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:79:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:79:A0o") {
  field(DESC, "Bi96  --> A0.o79 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb96",20,19,0,0,"PLC:B34:PP02:PLC_RDb96")
#! Field("PLC:B34:PP02:PLC_RDb96.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb96.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb96.FLNK","PLC:B34:PP02:79:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb96.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb96.VAL")
#! Record("PLC:B34:PP02:79:A0o_calc",260,18,0,1,"PLC:B34:PP02:79:A0o_calc")
#! Field("PLC:B34:PP02:79:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:79:A0o_calc.INPA")
#! Link("PLC:B34:PP02:79:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb96.VAL")
#! Field("PLC:B34:PP02:79:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:79:A0o_calc.INPB")
#! Field("PLC:B34:PP02:79:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:79:A0o_calc.OUT")
#! Link("PLC:B34:PP02:79:A0o_calc.OUT","PLC:B34:PP02:79:A0o.VAL")
#! Record("PLC:B34:PP02:79:A0o",500,20,0,0,"PLC:B34:PP02:79:A0o")
#! Field("PLC:B34:PP02:79:A0o.VAL",16777215,1,"PLC:B34:PP02:79:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi111") {
  field(DESC, "Port PLC_RD bit 111")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 111, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:80:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi111Valid") {
  field(INPA, "PLC:B34:PP02:Bi111.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:80:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:80:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi111 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi111Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:80:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:80:A0o") {
  field(DESC, "Bi111 --> A0.o80 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb111",20,19,0,0,"PLC:B34:PP02:PLC_RDb111")
#! Field("PLC:B34:PP02:PLC_RDb111.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb111.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb111.FLNK","PLC:B34:PP02:80:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb111.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb111.VAL")
#! Record("PLC:B34:PP02:80:A0o_calc",260,18,0,1,"PLC:B34:PP02:80:A0o_calc")
#! Field("PLC:B34:PP02:80:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:80:A0o_calc.INPA")
#! Link("PLC:B34:PP02:80:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb111.VAL")
#! Field("PLC:B34:PP02:80:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:80:A0o_calc.INPB")
#! Field("PLC:B34:PP02:80:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:80:A0o_calc.OUT")
#! Link("PLC:B34:PP02:80:A0o_calc.OUT","PLC:B34:PP02:80:A0o.VAL")
#! Record("PLC:B34:PP02:80:A0o",500,20,0,0,"PLC:B34:PP02:80:A0o")
#! Field("PLC:B34:PP02:80:A0o.VAL",16777215,1,"PLC:B34:PP02:80:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi110") {
  field(DESC, "Port PLC_RD bit 110")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 110, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:81:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi110Valid") {
  field(INPA, "PLC:B34:PP02:Bi110.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:81:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:81:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi110 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi110Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:81:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:81:A0o") {
  field(DESC, "Bi110 --> A0.o81 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb110",20,19,0,0,"PLC:B34:PP02:PLC_RDb110")
#! Field("PLC:B34:PP02:PLC_RDb110.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb110.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb110.FLNK","PLC:B34:PP02:81:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb110.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb110.VAL")
#! Record("PLC:B34:PP02:81:A0o_calc",260,18,0,1,"PLC:B34:PP02:81:A0o_calc")
#! Field("PLC:B34:PP02:81:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:81:A0o_calc.INPA")
#! Link("PLC:B34:PP02:81:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb110.VAL")
#! Field("PLC:B34:PP02:81:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:81:A0o_calc.INPB")
#! Field("PLC:B34:PP02:81:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:81:A0o_calc.OUT")
#! Link("PLC:B34:PP02:81:A0o_calc.OUT","PLC:B34:PP02:81:A0o.VAL")
#! Record("PLC:B34:PP02:81:A0o",500,20,0,0,"PLC:B34:PP02:81:A0o")
#! Field("PLC:B34:PP02:81:A0o.VAL",16777215,1,"PLC:B34:PP02:81:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi109") {
  field(DESC, "Port PLC_RD bit 109")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 109, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:82:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi109Valid") {
  field(INPA, "PLC:B34:PP02:Bi109.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:82:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:82:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi109 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi109Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:82:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:82:A0o") {
  field(DESC, "Bi109 --> A0.o82 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb109",20,19,0,0,"PLC:B34:PP02:PLC_RDb109")
#! Field("PLC:B34:PP02:PLC_RDb109.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb109.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb109.FLNK","PLC:B34:PP02:82:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb109.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb109.VAL")
#! Record("PLC:B34:PP02:82:A0o_calc",260,18,0,1,"PLC:B34:PP02:82:A0o_calc")
#! Field("PLC:B34:PP02:82:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:82:A0o_calc.INPA")
#! Link("PLC:B34:PP02:82:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb109.VAL")
#! Field("PLC:B34:PP02:82:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:82:A0o_calc.INPB")
#! Field("PLC:B34:PP02:82:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:82:A0o_calc.OUT")
#! Link("PLC:B34:PP02:82:A0o_calc.OUT","PLC:B34:PP02:82:A0o.VAL")
#! Record("PLC:B34:PP02:82:A0o",500,20,0,0,"PLC:B34:PP02:82:A0o")
#! Field("PLC:B34:PP02:82:A0o.VAL",16777215,1,"PLC:B34:PP02:82:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi108") {
  field(DESC, "Port PLC_RD bit 108")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 108, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:83:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi108Valid") {
  field(INPA, "PLC:B34:PP02:Bi108.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:83:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:83:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi108 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi108Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:83:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:83:A0o") {
  field(DESC, "Bi108 --> A0.o83 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb108",20,19,0,0,"PLC:B34:PP02:PLC_RDb108")
#! Field("PLC:B34:PP02:PLC_RDb108.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb108.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb108.FLNK","PLC:B34:PP02:83:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb108.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb108.VAL")
#! Record("PLC:B34:PP02:83:A0o_calc",260,18,0,1,"PLC:B34:PP02:83:A0o_calc")
#! Field("PLC:B34:PP02:83:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:83:A0o_calc.INPA")
#! Link("PLC:B34:PP02:83:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb108.VAL")
#! Field("PLC:B34:PP02:83:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:83:A0o_calc.INPB")
#! Field("PLC:B34:PP02:83:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:83:A0o_calc.OUT")
#! Link("PLC:B34:PP02:83:A0o_calc.OUT","PLC:B34:PP02:83:A0o.VAL")
#! Record("PLC:B34:PP02:83:A0o",500,20,0,0,"PLC:B34:PP02:83:A0o")
#! Field("PLC:B34:PP02:83:A0o.VAL",16777215,1,"PLC:B34:PP02:83:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi107") {
  field(DESC, "Port PLC_RD bit 107")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 107, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:84:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi107Valid") {
  field(INPA, "PLC:B34:PP02:Bi107.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:84:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:84:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi107 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi107Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:84:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:84:A0o") {
  field(DESC, "Bi107 --> A0.o84 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb107",20,19,0,0,"PLC:B34:PP02:PLC_RDb107")
#! Field("PLC:B34:PP02:PLC_RDb107.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb107.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb107.FLNK","PLC:B34:PP02:84:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb107.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb107.VAL")
#! Record("PLC:B34:PP02:84:A0o_calc",260,18,0,1,"PLC:B34:PP02:84:A0o_calc")
#! Field("PLC:B34:PP02:84:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:84:A0o_calc.INPA")
#! Link("PLC:B34:PP02:84:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb107.VAL")
#! Field("PLC:B34:PP02:84:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:84:A0o_calc.INPB")
#! Field("PLC:B34:PP02:84:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:84:A0o_calc.OUT")
#! Link("PLC:B34:PP02:84:A0o_calc.OUT","PLC:B34:PP02:84:A0o.VAL")
#! Record("PLC:B34:PP02:84:A0o",500,20,0,0,"PLC:B34:PP02:84:A0o")
#! Field("PLC:B34:PP02:84:A0o.VAL",16777215,1,"PLC:B34:PP02:84:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi106") {
  field(DESC, "Port PLC_RD bit 106")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 106, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:85:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi106Valid") {
  field(INPA, "PLC:B34:PP02:Bi106.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:85:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:85:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi106 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi106Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:85:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:85:A0o") {
  field(DESC, "Bi106 --> A0.o85 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb106",20,19,0,0,"PLC:B34:PP02:PLC_RDb106")
#! Field("PLC:B34:PP02:PLC_RDb106.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb106.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb106.FLNK","PLC:B34:PP02:85:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb106.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb106.VAL")
#! Record("PLC:B34:PP02:85:A0o_calc",260,18,0,1,"PLC:B34:PP02:85:A0o_calc")
#! Field("PLC:B34:PP02:85:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:85:A0o_calc.INPA")
#! Link("PLC:B34:PP02:85:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb106.VAL")
#! Field("PLC:B34:PP02:85:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:85:A0o_calc.INPB")
#! Field("PLC:B34:PP02:85:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:85:A0o_calc.OUT")
#! Link("PLC:B34:PP02:85:A0o_calc.OUT","PLC:B34:PP02:85:A0o.VAL")
#! Record("PLC:B34:PP02:85:A0o",500,20,0,0,"PLC:B34:PP02:85:A0o")
#! Field("PLC:B34:PP02:85:A0o.VAL",16777215,1,"PLC:B34:PP02:85:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi105") {
  field(DESC, "Port PLC_RD bit 105")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 105, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:86:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi105Valid") {
  field(INPA, "PLC:B34:PP02:Bi105.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:86:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:86:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi105 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi105Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:86:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:86:A0o") {
  field(DESC, "Bi105 --> A0.o86 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb105",20,19,0,0,"PLC:B34:PP02:PLC_RDb105")
#! Field("PLC:B34:PP02:PLC_RDb105.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb105.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb105.FLNK","PLC:B34:PP02:86:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb105.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb105.VAL")
#! Record("PLC:B34:PP02:86:A0o_calc",260,18,0,1,"PLC:B34:PP02:86:A0o_calc")
#! Field("PLC:B34:PP02:86:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:86:A0o_calc.INPA")
#! Link("PLC:B34:PP02:86:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb105.VAL")
#! Field("PLC:B34:PP02:86:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:86:A0o_calc.INPB")
#! Field("PLC:B34:PP02:86:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:86:A0o_calc.OUT")
#! Link("PLC:B34:PP02:86:A0o_calc.OUT","PLC:B34:PP02:86:A0o.VAL")
#! Record("PLC:B34:PP02:86:A0o",500,20,0,0,"PLC:B34:PP02:86:A0o")
#! Field("PLC:B34:PP02:86:A0o.VAL",16777215,1,"PLC:B34:PP02:86:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi104") {
  field(DESC, "Port PLC_RD bit 104")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 104, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:87:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi104Valid") {
  field(INPA, "PLC:B34:PP02:Bi104.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:87:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:87:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi104 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi104Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:87:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:87:A0o") {
  field(DESC, "Bi104 --> A0.o87 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb104",20,19,0,0,"PLC:B34:PP02:PLC_RDb104")
#! Field("PLC:B34:PP02:PLC_RDb104.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb104.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb104.FLNK","PLC:B34:PP02:87:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb104.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb104.VAL")
#! Record("PLC:B34:PP02:87:A0o_calc",260,18,0,1,"PLC:B34:PP02:87:A0o_calc")
#! Field("PLC:B34:PP02:87:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:87:A0o_calc.INPA")
#! Link("PLC:B34:PP02:87:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb104.VAL")
#! Field("PLC:B34:PP02:87:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:87:A0o_calc.INPB")
#! Field("PLC:B34:PP02:87:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:87:A0o_calc.OUT")
#! Link("PLC:B34:PP02:87:A0o_calc.OUT","PLC:B34:PP02:87:A0o.VAL")
#! Record("PLC:B34:PP02:87:A0o",500,20,0,0,"PLC:B34:PP02:87:A0o")
#! Field("PLC:B34:PP02:87:A0o.VAL",16777215,1,"PLC:B34:PP02:87:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi119") {
  field(DESC, "Port PLC_RD bit 119")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 119, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:88:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi119Valid") {
  field(INPA, "PLC:B34:PP02:Bi119.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:88:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:88:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi119 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi119Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:88:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:88:A0o") {
  field(DESC, "Bi119 --> A0.o88 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb119",20,19,0,0,"PLC:B34:PP02:PLC_RDb119")
#! Field("PLC:B34:PP02:PLC_RDb119.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb119.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb119.FLNK","PLC:B34:PP02:88:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb119.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb119.VAL")
#! Record("PLC:B34:PP02:88:A0o_calc",260,18,0,1,"PLC:B34:PP02:88:A0o_calc")
#! Field("PLC:B34:PP02:88:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:88:A0o_calc.INPA")
#! Link("PLC:B34:PP02:88:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb119.VAL")
#! Field("PLC:B34:PP02:88:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:88:A0o_calc.INPB")
#! Field("PLC:B34:PP02:88:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:88:A0o_calc.OUT")
#! Link("PLC:B34:PP02:88:A0o_calc.OUT","PLC:B34:PP02:88:A0o.VAL")
#! Record("PLC:B34:PP02:88:A0o",500,20,0,0,"PLC:B34:PP02:88:A0o")
#! Field("PLC:B34:PP02:88:A0o.VAL",16777215,1,"PLC:B34:PP02:88:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi118") {
  field(DESC, "Port PLC_RD bit 118")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 118, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:89:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi118Valid") {
  field(INPA, "PLC:B34:PP02:Bi118.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:89:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:89:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi118 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi118Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:89:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:89:A0o") {
  field(DESC, "Bi118 --> A0.o89 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb118",20,19,0,0,"PLC:B34:PP02:PLC_RDb118")
#! Field("PLC:B34:PP02:PLC_RDb118.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb118.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb118.FLNK","PLC:B34:PP02:89:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb118.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb118.VAL")
#! Record("PLC:B34:PP02:89:A0o_calc",260,18,0,1,"PLC:B34:PP02:89:A0o_calc")
#! Field("PLC:B34:PP02:89:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:89:A0o_calc.INPA")
#! Link("PLC:B34:PP02:89:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb118.VAL")
#! Field("PLC:B34:PP02:89:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:89:A0o_calc.INPB")
#! Field("PLC:B34:PP02:89:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:89:A0o_calc.OUT")
#! Link("PLC:B34:PP02:89:A0o_calc.OUT","PLC:B34:PP02:89:A0o.VAL")
#! Record("PLC:B34:PP02:89:A0o",500,20,0,0,"PLC:B34:PP02:89:A0o")
#! Field("PLC:B34:PP02:89:A0o.VAL",16777215,1,"PLC:B34:PP02:89:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi117") {
  field(DESC, "Port PLC_RD bit 117")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 117, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:90:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi117Valid") {
  field(INPA, "PLC:B34:PP02:Bi117.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:90:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:90:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi117 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi117Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:90:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:90:A0o") {
  field(DESC, "Bi117 --> A0.o90 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb117",20,19,0,0,"PLC:B34:PP02:PLC_RDb117")
#! Field("PLC:B34:PP02:PLC_RDb117.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb117.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb117.FLNK","PLC:B34:PP02:90:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb117.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb117.VAL")
#! Record("PLC:B34:PP02:90:A0o_calc",260,18,0,1,"PLC:B34:PP02:90:A0o_calc")
#! Field("PLC:B34:PP02:90:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:90:A0o_calc.INPA")
#! Link("PLC:B34:PP02:90:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb117.VAL")
#! Field("PLC:B34:PP02:90:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:90:A0o_calc.INPB")
#! Field("PLC:B34:PP02:90:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:90:A0o_calc.OUT")
#! Link("PLC:B34:PP02:90:A0o_calc.OUT","PLC:B34:PP02:90:A0o.VAL")
#! Record("PLC:B34:PP02:90:A0o",500,20,0,0,"PLC:B34:PP02:90:A0o")
#! Field("PLC:B34:PP02:90:A0o.VAL",16777215,1,"PLC:B34:PP02:90:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi116") {
  field(DESC, "Port PLC_RD bit 116")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 116, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:91:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi116Valid") {
  field(INPA, "PLC:B34:PP02:Bi116.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:91:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:91:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi116 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi116Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:91:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:91:A0o") {
  field(DESC, "B116i --> A0.o91 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb116",20,19,0,0,"PLC:B34:PP02:PLC_RDb116")
#! Field("PLC:B34:PP02:PLC_RDb116.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb116.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb116.FLNK","PLC:B34:PP02:91:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb116.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb116.VAL")
#! Record("PLC:B34:PP02:91:A0o_calc",260,18,0,1,"PLC:B34:PP02:91:A0o_calc")
#! Field("PLC:B34:PP02:91:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:91:A0o_calc.INPA")
#! Link("PLC:B34:PP02:91:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb116.VAL")
#! Field("PLC:B34:PP02:91:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:91:A0o_calc.INPB")
#! Field("PLC:B34:PP02:91:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:91:A0o_calc.OUT")
#! Link("PLC:B34:PP02:91:A0o_calc.OUT","PLC:B34:PP02:91:A0o.VAL")
#! Record("PLC:B34:PP02:91:A0o",500,20,0,0,"PLC:B34:PP02:91:A0o")
#! Field("PLC:B34:PP02:91:A0o.VAL",16777215,1,"PLC:B34:PP02:91:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi115") {
  field(DESC, "Port PLC_RD bit 115")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 115, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:92:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi115Valid") {
  field(INPA, "PLC:B34:PP02:Bi115.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:92:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:92:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi115 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi115Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:92:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:92:A0o") {
  field(DESC, "Bi115 --> A0.o92 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb115",20,19,0,0,"PLC:B34:PP02:PLC_RDb115")
#! Field("PLC:B34:PP02:PLC_RDb115.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb115.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb115.FLNK","PLC:B34:PP02:92:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb115.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb115.VAL")
#! Record("PLC:B34:PP02:92:A0o_calc",260,18,0,1,"PLC:B34:PP02:92:A0o_calc")
#! Field("PLC:B34:PP02:92:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:92:A0o_calc.INPA")
#! Link("PLC:B34:PP02:92:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb115.VAL")
#! Field("PLC:B34:PP02:92:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:92:A0o_calc.INPB")
#! Field("PLC:B34:PP02:92:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:92:A0o_calc.OUT")
#! Link("PLC:B34:PP02:92:A0o_calc.OUT","PLC:B34:PP02:92:A0o.VAL")
#! Record("PLC:B34:PP02:92:A0o",500,20,0,0,"PLC:B34:PP02:92:A0o")
#! Field("PLC:B34:PP02:92:A0o.VAL",16777215,1,"PLC:B34:PP02:92:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi114") {
  field(DESC, "Port PLC_RD bit 114")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 114, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:93:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi114Valid") {
  field(INPA, "PLC:B34:PP02:Bi114.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:93:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:93:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi114 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi114Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:93:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:93:A0o") {
  field(DESC, "Bi114 --> A0.o93 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb114",20,19,0,0,"PLC:B34:PP02:PLC_RDb114")
#! Field("PLC:B34:PP02:PLC_RDb114.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb114.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb114.FLNK","PLC:B34:PP02:93:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb114.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb114.VAL")
#! Record("PLC:B34:PP02:93:A0o_calc",260,18,0,1,"PLC:B34:PP02:93:A0o_calc")
#! Field("PLC:B34:PP02:93:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:93:A0o_calc.INPA")
#! Link("PLC:B34:PP02:93:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb114.VAL")
#! Field("PLC:B34:PP02:93:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:93:A0o_calc.INPB")
#! Field("PLC:B34:PP02:93:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:93:A0o_calc.OUT")
#! Link("PLC:B34:PP02:93:A0o_calc.OUT","PLC:B34:PP02:93:A0o.VAL")
#! Record("PLC:B34:PP02:93:A0o",500,20,0,0,"PLC:B34:PP02:93:A0o")
#! Field("PLC:B34:PP02:93:A0o.VAL",16777215,1,"PLC:B34:PP02:93:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi113") {
  field(DESC, "Port PLC_RD bit 113")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 113, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:94:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi113Valid") {
  field(INPA, "PLC:B34:PP02:Bi113.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:94:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:94:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi113 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi113Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:94:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:94:A0o") {
  field(DESC, "Bi113 --> A0.o94 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb113",20,19,0,0,"PLC:B34:PP02:PLC_RDb113")
#! Field("PLC:B34:PP02:PLC_RDb113.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb113.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb113.FLNK","PLC:B34:PP02:94:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb113.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb113.VAL")
#! Record("PLC:B34:PP02:94:A0o_calc",260,18,0,1,"PLC:B34:PP02:94:A0o_calc")
#! Field("PLC:B34:PP02:94:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:94:A0o_calc.INPA")
#! Link("PLC:B34:PP02:94:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb113.VAL")
#! Field("PLC:B34:PP02:94:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:94:A0o_calc.INPB")
#! Field("PLC:B34:PP02:94:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:94:A0o_calc.OUT")
#! Link("PLC:B34:PP02:94:A0o_calc.OUT","PLC:B34:PP02:94:A0o.VAL")
#! Record("PLC:B34:PP02:94:A0o",500,20,0,0,"PLC:B34:PP02:94:A0o")
#! Field("PLC:B34:PP02:94:A0o.VAL",16777215,1,"PLC:B34:PP02:94:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi112") {
  field(DESC, "Port PLC_RD bit 112")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 112, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:95:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi112Valid") {
  field(INPA, "PLC:B34:PP02:Bi112.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:95:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:95:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi112 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi112Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:95:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:95:A0o") {
  field(DESC, "Bi112 --> A0.o95 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb112",20,19,0,0,"PLC:B34:PP02:PLC_RDb112")
#! Field("PLC:B34:PP02:PLC_RDb112.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb112.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb112.FLNK","PLC:B34:PP02:95:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb112.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb112.VAL")
#! Record("PLC:B34:PP02:95:A0o_calc",260,18,0,1,"PLC:B34:PP02:95:A0o_calc")
#! Field("PLC:B34:PP02:95:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:95:A0o_calc.INPA")
#! Link("PLC:B34:PP02:95:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb112.VAL")
#! Field("PLC:B34:PP02:95:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:95:A0o_calc.INPB")
#! Field("PLC:B34:PP02:95:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:95:A0o_calc.OUT")
#! Link("PLC:B34:PP02:95:A0o_calc.OUT","PLC:B34:PP02:95:A0o.VAL")
#! Record("PLC:B34:PP02:95:A0o",500,20,0,0,"PLC:B34:PP02:95:A0o")
#! Field("PLC:B34:PP02:95:A0o.VAL",16777215,1,"PLC:B34:PP02:95:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi127") {
  field(DESC, "Port PLC_RD bit 127")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 127, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:96:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi127Valid") {
  field(INPA, "PLC:B34:PP02:Bi127.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:96:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:96:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi127 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi127Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:96:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:96:A0o") {
  field(DESC, "Bi127 --> A0.o96 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb127",20,19,0,0,"PLC:B34:PP02:PLC_RDb127")
#! Field("PLC:B34:PP02:PLC_RDb127.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb127.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb127.FLNK","PLC:B34:PP02:96:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb127.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb127.VAL")
#! Record("PLC:B34:PP02:96:A0o_calc",260,18,0,1,"PLC:B34:PP02:96:A0o_calc")
#! Field("PLC:B34:PP02:96:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:96:A0o_calc.INPA")
#! Link("PLC:B34:PP02:96:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb127.VAL")
#! Field("PLC:B34:PP02:96:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:96:A0o_calc.INPB")
#! Field("PLC:B34:PP02:96:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:96:A0o_calc.OUT")
#! Link("PLC:B34:PP02:96:A0o_calc.OUT","PLC:B34:PP02:96:A0o.VAL")
#! Record("PLC:B34:PP02:96:A0o",500,20,0,0,"PLC:B34:PP02:96:A0o")
#! Field("PLC:B34:PP02:96:A0o.VAL",16777215,1,"PLC:B34:PP02:96:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi126") {
  field(DESC, "Port PLC_RD bit 126")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 126, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:97:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi126Valid") {
  field(INPA, "PLC:B34:PP02:Bi126.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:97:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:97:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi126 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi126Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:97:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:97:A0o") {
  field(DESC, "Bi126 --> A0.o97 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb126",20,19,0,0,"PLC:B34:PP02:PLC_RDb126")
#! Field("PLC:B34:PP02:PLC_RDb126.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb126.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb126.FLNK","PLC:B34:PP02:97:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb126.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb126.VAL")
#! Record("PLC:B34:PP02:97:A0o_calc",260,18,0,1,"PLC:B34:PP02:97:A0o_calc")
#! Field("PLC:B34:PP02:97:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:97:A0o_calc.INPA")
#! Link("PLC:B34:PP02:97:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb126.VAL")
#! Field("PLC:B34:PP02:97:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:97:A0o_calc.INPB")
#! Field("PLC:B34:PP02:97:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:97:A0o_calc.OUT")
#! Link("PLC:B34:PP02:97:A0o_calc.OUT","PLC:B34:PP02:97:A0o.VAL")
#! Record("PLC:B34:PP02:97:A0o",500,20,0,0,"PLC:B34:PP02:97:A0o")
#! Field("PLC:B34:PP02:97:A0o.VAL",16777215,1,"PLC:B34:PP02:97:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi125") {
  field(DESC, "Port PLC_RD bit 125")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 125, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:98:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi125Valid") {
  field(INPA, "PLC:B34:PP02:Bi125.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:98:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:98:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi125 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi125Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:98:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:98:A0o") {
  field(DESC, "Bi125 --> A0.o98 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb125",20,19,0,0,"PLC:B34:PP02:PLC_RDb125")
#! Field("PLC:B34:PP02:PLC_RDb125.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb125.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb125.FLNK","PLC:B34:PP02:98:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb125.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb125.VAL")
#! Record("PLC:B34:PP02:98:A0o_calc",260,18,0,1,"PLC:B34:PP02:98:A0o_calc")
#! Field("PLC:B34:PP02:98:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:98:A0o_calc.INPA")
#! Link("PLC:B34:PP02:98:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb125.VAL")
#! Field("PLC:B34:PP02:98:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:98:A0o_calc.INPB")
#! Field("PLC:B34:PP02:98:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:98:A0o_calc.OUT")
#! Link("PLC:B34:PP02:98:A0o_calc.OUT","PLC:B34:PP02:98:A0o.VAL")
#! Record("PLC:B34:PP02:98:A0o",500,20,0,0,"PLC:B34:PP02:98:A0o")
#! Field("PLC:B34:PP02:98:A0o.VAL",16777215,1,"PLC:B34:PP02:98:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi124") {
  field(DESC, "Port PLC_RD bit 124")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 124, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:99:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi124Valid") {
  field(INPA, "PLC:B34:PP02:Bi124.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:99:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:99:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi124 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi124Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:99:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:99:A0o") {
  field(DESC, "Bi124 --> A0.o99 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb124",20,19,0,0,"PLC:B34:PP02:PLC_RDb124")
#! Field("PLC:B34:PP02:PLC_RDb124.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb124.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb124.FLNK","PLC:B34:PP02:99:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb124.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb124.VAL")
#! Record("PLC:B34:PP02:99:A0o_calc",260,18,0,1,"PLC:B34:PP02:99:A0o_calc")
#! Field("PLC:B34:PP02:99:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:99:A0o_calc.INPA")
#! Link("PLC:B34:PP02:99:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb124.VAL")
#! Field("PLC:B34:PP02:99:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:99:A0o_calc.INPB")
#! Field("PLC:B34:PP02:99:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:99:A0o_calc.OUT")
#! Link("PLC:B34:PP02:99:A0o_calc.OUT","PLC:B34:PP02:99:A0o.VAL")
#! Record("PLC:B34:PP02:99:A0o",500,20,0,0,"PLC:B34:PP02:99:A0o")
#! Field("PLC:B34:PP02:99:A0o.VAL",16777215,1,"PLC:B34:PP02:99:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi123") {
  field(DESC, "Port PLC_RD bit 123")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 123, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:100:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi123Valid") {
  field(INPA, "PLC:B34:PP02:Bi123.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:100:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:100:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi123 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi123Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:100:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:100:A0o") {
  field(DESC, "Bi123 --> A0.o100 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb123",20,19,0,0,"PLC:B34:PP02:PLC_RDb123")
#! Field("PLC:B34:PP02:PLC_RDb123.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb123.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb123.FLNK","PLC:B34:PP02:100:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb123.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb123.VAL")
#! Record("PLC:B34:PP02:100:A0o_calc",260,18,0,1,"PLC:B34:PP02:100:A0o_calc")
#! Field("PLC:B34:PP02:100:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:100:A0o_calc.INPA")
#! Link("PLC:B34:PP02:100:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb123.VAL")
#! Field("PLC:B34:PP02:100:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:100:A0o_calc.INPB")
#! Field("PLC:B34:PP02:100:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:100:A0o_calc.OUT")
#! Link("PLC:B34:PP02:100:A0o_calc.OUT","PLC:B34:PP02:100:A0o.VAL")
#! Record("PLC:B34:PP02:100:A0o",500,20,0,0,"PLC:B34:PP02:100:A0o")
#! Field("PLC:B34:PP02:100:A0o.VAL",16777215,1,"PLC:B34:PP02:100:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi122") {
  field(DESC, "Port PLC_RD bit 122")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 122, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:101:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi122Valid") {
  field(INPA, "PLC:B34:PP02:Bi122.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:101:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:101:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi122 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi122Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:101:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:101:A0o") {
  field(DESC, "Bi122 --> A0.o101 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb122",20,19,0,0,"PLC:B34:PP02:PLC_RDb122")
#! Field("PLC:B34:PP02:PLC_RDb122.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb122.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb122.FLNK","PLC:B34:PP02:101:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb122.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb122.VAL")
#! Record("PLC:B34:PP02:101:A0o_calc",260,18,0,1,"PLC:B34:PP02:101:A0o_calc")
#! Field("PLC:B34:PP02:101:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:101:A0o_calc.INPA")
#! Link("PLC:B34:PP02:101:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb122.VAL")
#! Field("PLC:B34:PP02:101:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:101:A0o_calc.INPB")
#! Field("PLC:B34:PP02:101:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:101:A0o_calc.OUT")
#! Link("PLC:B34:PP02:101:A0o_calc.OUT","PLC:B34:PP02:101:A0o.VAL")
#! Record("PLC:B34:PP02:101:A0o",500,20,0,0,"PLC:B34:PP02:101:A0o")
#! Field("PLC:B34:PP02:101:A0o.VAL",16777215,1,"PLC:B34:PP02:101:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi121") {
  field(DESC, "Port PLC_RD bit 121")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 121, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:102:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi121Valid") {
  field(INPA, "PLC:B34:PP02:Bi121.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:102:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:102:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi121 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi121Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:102:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:102:A0o") {
  field(DESC, "Bi121 --> A0.o102 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb121",20,19,0,0,"PLC:B34:PP02:PLC_RDb121")
#! Field("PLC:B34:PP02:PLC_RDb121.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb121.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb121.FLNK","PLC:B34:PP02:102:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb121.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb121.VAL")
#! Record("PLC:B34:PP02:102:A0o_calc",260,18,0,1,"PLC:B34:PP02:102:A0o_calc")
#! Field("PLC:B34:PP02:102:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:102:A0o_calc.INPA")
#! Link("PLC:B34:PP02:102:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb121.VAL")
#! Field("PLC:B34:PP02:102:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:102:A0o_calc.INPB")
#! Field("PLC:B34:PP02:102:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:102:A0o_calc.OUT")
#! Link("PLC:B34:PP02:102:A0o_calc.OUT","PLC:B34:PP02:102:A0o.VAL")
#! Record("PLC:B34:PP02:102:A0o",500,20,0,0,"PLC:B34:PP02:102:A0o")
#! Field("PLC:B34:PP02:102:A0o.VAL",16777215,1,"PLC:B34:PP02:102:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi120") {
  field(DESC, "Port PLC_RD bit 120")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 120, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:103:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi120Valid") {
  field(INPA, "PLC:B34:PP02:Bi120.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:103:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:103:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi120 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi120Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:103:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:103:A0o") {
  field(DESC, "Bi120 --> A0.o103 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb120",20,19,0,0,"PLC:B34:PP02:PLC_RDb120")
#! Field("PLC:B34:PP02:PLC_RDb120.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb120.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb120.FLNK","PLC:B34:PP02:103:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb120.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb120.VAL")
#! Record("PLC:B34:PP02:103:A0o_calc",260,18,0,1,"PLC:B34:PP02:103:A0o_calc")
#! Field("PLC:B34:PP02:103:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:103:A0o_calc.INPA")
#! Link("PLC:B34:PP02:103:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb120.VAL")
#! Field("PLC:B34:PP02:103:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:103:A0o_calc.INPB")
#! Field("PLC:B34:PP02:103:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:103:A0o_calc.OUT")
#! Link("PLC:B34:PP02:103:A0o_calc.OUT","PLC:B34:PP02:103:A0o.VAL")
#! Record("PLC:B34:PP02:103:A0o",500,20,0,0,"PLC:B34:PP02:103:A0o")
#! Field("PLC:B34:PP02:103:A0o.VAL",16777215,1,"PLC:B34:PP02:103:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi135") {
  field(DESC, "Port PLC_RD bit 135")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 135, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:104:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi135Valid") {
  field(INPA, "PLC:B34:PP02:Bi135.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:104:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:104:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi135 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi135Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:104:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:104:A0o") {
  field(DESC, "Bi135 --> A0.o104 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb135",20,19,0,0,"PLC:B34:PP02:PLC_RDb135")
#! Field("PLC:B34:PP02:PLC_RDb135.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb135.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb135.FLNK","PLC:B34:PP02:104:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb135.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb135.VAL")
#! Record("PLC:B34:PP02:104:A0o_calc",260,18,0,1,"PLC:B34:PP02:104:A0o_calc")
#! Field("PLC:B34:PP02:104:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:104:A0o_calc.INPA")
#! Link("PLC:B34:PP02:104:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb135.VAL")
#! Field("PLC:B34:PP02:104:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:104:A0o_calc.INPB")
#! Field("PLC:B34:PP02:104:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:104:A0o_calc.OUT")
#! Link("PLC:B34:PP02:104:A0o_calc.OUT","PLC:B34:PP02:104:A0o.VAL")
#! Record("PLC:B34:PP02:104:A0o",500,20,0,0,"PLC:B34:PP02:104:A0o")
#! Field("PLC:B34:PP02:104:A0o.VAL",16777215,1,"PLC:B34:PP02:104:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi134") {
  field(DESC, "Port PLC_RD bit 134")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 134, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:105:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi134Valid") {
  field(INPA, "PLC:B34:PP02:Bi134.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:105:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:105:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi134 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi134Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:105:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:105:A0o") {
  field(DESC, "Bi134 --> A0.o105 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb134",20,19,0,0,"PLC:B34:PP02:PLC_RDb134")
#! Field("PLC:B34:PP02:PLC_RDb134.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb134.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb134.FLNK","PLC:B34:PP02:105:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb134.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb134.VAL")
#! Record("PLC:B34:PP02:105:A0o_calc",260,18,0,1,"PLC:B34:PP02:105:A0o_calc")
#! Field("PLC:B34:PP02:105:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:105:A0o_calc.INPA")
#! Link("PLC:B34:PP02:105:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb134.VAL")
#! Field("PLC:B34:PP02:105:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:105:A0o_calc.INPB")
#! Field("PLC:B34:PP02:105:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:105:A0o_calc.OUT")
#! Link("PLC:B34:PP02:105:A0o_calc.OUT","PLC:B34:PP02:105:A0o.VAL")
#! Record("PLC:B34:PP02:105:A0o",500,20,0,0,"PLC:B34:PP02:105:A0o")
#! Field("PLC:B34:PP02:105:A0o.VAL",16777215,1,"PLC:B34:PP02:105:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi133") {
  field(DESC, "Port PLC_RD bit 133")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 133, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:106:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi133Valid") {
  field(INPA, "PLC:B34:PP02:Bi133.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:106:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:106:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi133 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi133Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:106:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:106:A0o") {
  field(DESC, "Bi133 --> A0.o106 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb133",20,19,0,0,"PLC:B34:PP02:PLC_RDb133")
#! Field("PLC:B34:PP02:PLC_RDb133.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb133.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb133.FLNK","PLC:B34:PP02:106:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb133.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb133.VAL")
#! Record("PLC:B34:PP02:106:A0o_calc",260,18,0,1,"PLC:B34:PP02:106:A0o_calc")
#! Field("PLC:B34:PP02:106:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:106:A0o_calc.INPA")
#! Link("PLC:B34:PP02:106:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb133.VAL")
#! Field("PLC:B34:PP02:106:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:106:A0o_calc.INPB")
#! Field("PLC:B34:PP02:106:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:106:A0o_calc.OUT")
#! Link("PLC:B34:PP02:106:A0o_calc.OUT","PLC:B34:PP02:106:A0o.VAL")
#! Record("PLC:B34:PP02:106:A0o",500,20,0,0,"PLC:B34:PP02:106:A0o")
#! Field("PLC:B34:PP02:106:A0o.VAL",16777215,1,"PLC:B34:PP02:106:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi132") {
  field(DESC, "Port PLC_RD bit 132")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 132, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:107:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi132Valid") {
  field(INPA, "PLC:B34:PP02:Bi132.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:107:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:107:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi132 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi132Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:107:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:107:A0o") {
  field(DESC, "Bi132 --> A0.o107 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb132",20,19,0,0,"PLC:B34:PP02:PLC_RDb132")
#! Field("PLC:B34:PP02:PLC_RDb132.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb132.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb132.FLNK","PLC:B34:PP02:107:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb132.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb132.VAL")
#! Record("PLC:B34:PP02:107:A0o_calc",260,18,0,1,"PLC:B34:PP02:107:A0o_calc")
#! Field("PLC:B34:PP02:107:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:107:A0o_calc.INPA")
#! Link("PLC:B34:PP02:107:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb132.VAL")
#! Field("PLC:B34:PP02:107:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:107:A0o_calc.INPB")
#! Field("PLC:B34:PP02:107:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:107:A0o_calc.OUT")
#! Link("PLC:B34:PP02:107:A0o_calc.OUT","PLC:B34:PP02:107:A0o.VAL")
#! Record("PLC:B34:PP02:107:A0o",500,20,0,0,"PLC:B34:PP02:107:A0o")
#! Field("PLC:B34:PP02:107:A0o.VAL",16777215,1,"PLC:B34:PP02:107:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi131") {
  field(DESC, "Port PLC_RD bit 131")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 131, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:108:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi131Valid") {
  field(INPA, "PLC:B34:PP02:Bi131.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:108:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:108:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi131 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi131Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:108:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:108:A0o") {
  field(DESC, "Bi131 --> A0.o108 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb131",20,19,0,0,"PLC:B34:PP02:PLC_RDb131")
#! Field("PLC:B34:PP02:PLC_RDb131.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb131.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb131.FLNK","PLC:B34:PP02:108:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb131.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb131.VAL")
#! Record("PLC:B34:PP02:108:A0o_calc",260,18,0,1,"PLC:B34:PP02:108:A0o_calc")
#! Field("PLC:B34:PP02:108:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:108:A0o_calc.INPA")
#! Link("PLC:B34:PP02:108:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb131.VAL")
#! Field("PLC:B34:PP02:108:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:108:A0o_calc.INPB")
#! Field("PLC:B34:PP02:108:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:108:A0o_calc.OUT")
#! Link("PLC:B34:PP02:108:A0o_calc.OUT","PLC:B34:PP02:108:A0o.VAL")
#! Record("PLC:B34:PP02:108:A0o",500,20,0,0,"PLC:B34:PP02:108:A0o")
#! Field("PLC:B34:PP02:108:A0o.VAL",16777215,1,"PLC:B34:PP02:108:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi130") {
  field(DESC, "Port PLC_RD bit 130")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 130, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:109:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi130Valid") {
  field(INPA, "PLC:B34:PP02:Bi130.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:109:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:109:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi130 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi130Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:109:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:109:A0o") {
  field(DESC, "Bi130 --> A0.o109 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb130",20,19,0,0,"PLC:B34:PP02:PLC_RDb130")
#! Field("PLC:B34:PP02:PLC_RDb130.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb130.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb130.FLNK","PLC:B34:PP02:109:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb130.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb130.VAL")
#! Record("PLC:B34:PP02:109:A0o_calc",260,18,0,1,"PLC:B34:PP02:109:A0o_calc")
#! Field("PLC:B34:PP02:109:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:109:A0o_calc.INPA")
#! Link("PLC:B34:PP02:109:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb130.VAL")
#! Field("PLC:B34:PP02:109:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:109:A0o_calc.INPB")
#! Field("PLC:B34:PP02:109:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:109:A0o_calc.OUT")
#! Link("PLC:B34:PP02:109:A0o_calc.OUT","PLC:B34:PP02:109:A0o.VAL")
#! Record("PLC:B34:PP02:109:A0o",500,20,0,0,"PLC:B34:PP02:109:A0o")
#! Field("PLC:B34:PP02:109:A0o.VAL",16777215,1,"PLC:B34:PP02:109:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi129") {
  field(DESC, "Port PLC_RD bit 129")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 129, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:110:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi129Valid") {
  field(INPA, "PLC:B34:PP02:Bi129.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:110:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:110:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi129 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi129Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:110:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:110:A0o") {
  field(DESC, "Bi129 --> A0.o110 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb129",20,19,0,0,"PLC:B34:PP02:PLC_RDb129")
#! Field("PLC:B34:PP02:PLC_RDb129.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb129.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb129.FLNK","PLC:B34:PP02:110:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb129.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb129.VAL")
#! Record("PLC:B34:PP02:110:A0o_calc",260,18,0,1,"PLC:B34:PP02:110:A0o_calc")
#! Field("PLC:B34:PP02:110:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:110:A0o_calc.INPA")
#! Link("PLC:B34:PP02:110:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb129.VAL")
#! Field("PLC:B34:PP02:110:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:110:A0o_calc.INPB")
#! Field("PLC:B34:PP02:110:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:110:A0o_calc.OUT")
#! Link("PLC:B34:PP02:110:A0o_calc.OUT","PLC:B34:PP02:110:A0o.VAL")
#! Record("PLC:B34:PP02:110:A0o",500,20,0,0,"PLC:B34:PP02:110:A0o")
#! Field("PLC:B34:PP02:110:A0o.VAL",16777215,1,"PLC:B34:PP02:110:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi128") {
  field(DESC, "Port PLC_RD bit 128")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 128, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:111:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi128Valid") {
  field(INPA, "PLC:B34:PP02:Bi128.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:111:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:111:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi128 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi128Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:111:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:111:A0o") {
  field(DESC, "Bi128 --> A0.o111 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb128",20,19,0,0,"PLC:B34:PP02:PLC_RDb128")
#! Field("PLC:B34:PP02:PLC_RDb128.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb128.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb128.FLNK","PLC:B34:PP02:111:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb128.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb128.VAL")
#! Record("PLC:B34:PP02:111:A0o_calc",260,18,0,1,"PLC:B34:PP02:111:A0o_calc")
#! Field("PLC:B34:PP02:111:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:111:A0o_calc.INPA")
#! Link("PLC:B34:PP02:111:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb128.VAL")
#! Field("PLC:B34:PP02:111:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:111:A0o_calc.INPB")
#! Field("PLC:B34:PP02:111:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:111:A0o_calc.OUT")
#! Link("PLC:B34:PP02:111:A0o_calc.OUT","PLC:B34:PP02:111:A0o.VAL")
#! Record("PLC:B34:PP02:111:A0o",500,20,0,0,"PLC:B34:PP02:111:A0o")
#! Field("PLC:B34:PP02:111:A0o.VAL",16777215,1,"PLC:B34:PP02:111:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi143") {
  field(DESC, "Port PLC_RD bit 143")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 143, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:112:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi143Valid") {
  field(INPA, "PLC:B34:PP02:Bi143.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:112:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:112:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi143 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi143Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:112:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:112:A0o") {
  field(DESC, "Bi143 --> A0.o112 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb143",20,19,0,0,"PLC:B34:PP02:PLC_RDb143")
#! Field("PLC:B34:PP02:PLC_RDb143.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb143.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb143.FLNK","PLC:B34:PP02:112:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb143.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb143.VAL")
#! Record("PLC:B34:PP02:112:A0o_calc",260,18,0,1,"PLC:B34:PP02:112:A0o_calc")
#! Field("PLC:B34:PP02:112:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:112:A0o_calc.INPA")
#! Link("PLC:B34:PP02:112:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb143.VAL")
#! Field("PLC:B34:PP02:112:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:112:A0o_calc.INPB")
#! Field("PLC:B34:PP02:112:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:112:A0o_calc.OUT")
#! Link("PLC:B34:PP02:112:A0o_calc.OUT","PLC:B34:PP02:112:A0o.VAL")
#! Record("PLC:B34:PP02:112:A0o",500,20,0,0,"PLC:B34:PP02:112:A0o")
#! Field("PLC:B34:PP02:112:A0o.VAL",16777215,1,"PLC:B34:PP02:112:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi142") {
  field(DESC, "Port PLC_RD bit 142")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 142, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:113:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi142Valid") {
  field(INPA, "PLC:B34:PP02:Bi142.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:113:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:113:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi142 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi142Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:113:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:113:A0o") {
  field(DESC, "Bi142 --> A0.o113 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb142",20,19,0,0,"PLC:B34:PP02:PLC_RDb142")
#! Field("PLC:B34:PP02:PLC_RDb142.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb142.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb142.FLNK","PLC:B34:PP02:113:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb142.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb142.VAL")
#! Record("PLC:B34:PP02:113:A0o_calc",260,18,0,1,"PLC:B34:PP02:113:A0o_calc")
#! Field("PLC:B34:PP02:113:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:113:A0o_calc.INPA")
#! Link("PLC:B34:PP02:113:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb142.VAL")
#! Field("PLC:B34:PP02:113:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:113:A0o_calc.INPB")
#! Field("PLC:B34:PP02:113:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:113:A0o_calc.OUT")
#! Link("PLC:B34:PP02:113:A0o_calc.OUT","PLC:B34:PP02:113:A0o.VAL")
#! Record("PLC:B34:PP02:113:A0o",500,20,0,0,"PLC:B34:PP02:113:A0o")
#! Field("PLC:B34:PP02:113:A0o.VAL",16777215,1,"PLC:B34:PP02:113:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi141") {
  field(DESC, "Port PLC_RD bit 141")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 141, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:114:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi141Valid") {
  field(INPA, "PLC:B34:PP02:Bi141.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:114:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:114:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi141 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi141Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:114:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:114:A0o") {
  field(DESC, "Bi141 --> A0.o114 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb141",20,19,0,0,"PLC:B34:PP02:PLC_RDb141")
#! Field("PLC:B34:PP02:PLC_RDb141.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb141.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb141.FLNK","PLC:B34:PP02:114:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb141.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb141.VAL")
#! Record("PLC:B34:PP02:114:A0o_calc",260,18,0,1,"PLC:B34:PP02:114:A0o_calc")
#! Field("PLC:B34:PP02:114:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:114:A0o_calc.INPA")
#! Link("PLC:B34:PP02:114:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb141.VAL")
#! Field("PLC:B34:PP02:114:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:114:A0o_calc.INPB")
#! Field("PLC:B34:PP02:114:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:114:A0o_calc.OUT")
#! Link("PLC:B34:PP02:114:A0o_calc.OUT","PLC:B34:PP02:114:A0o.VAL")
#! Record("PLC:B34:PP02:114:A0o",500,20,0,0,"PLC:B34:PP02:114:A0o")
#! Field("PLC:B34:PP02:114:A0o.VAL",16777215,1,"PLC:B34:PP02:114:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi140") {
  field(DESC, "Port PLC_RD bit 140")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 140, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:115:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi140Valid") {
  field(INPA, "PLC:B34:PP02:Bi140.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:115:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:115:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi140 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi140Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:115:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:115:A0o") {
  field(DESC, "Bi140 --> A0.o115 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb140",20,19,0,0,"PLC:B34:PP02:PLC_RDb140")
#! Field("PLC:B34:PP02:PLC_RDb140.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb140.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb140.FLNK","PLC:B34:PP02:115:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb140.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb140.VAL")
#! Record("PLC:B34:PP02:115:A0o_calc",260,18,0,1,"PLC:B34:PP02:115:A0o_calc")
#! Field("PLC:B34:PP02:115:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:115:A0o_calc.INPA")
#! Link("PLC:B34:PP02:115:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb140.VAL")
#! Field("PLC:B34:PP02:115:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:115:A0o_calc.INPB")
#! Field("PLC:B34:PP02:115:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:115:A0o_calc.OUT")
#! Link("PLC:B34:PP02:115:A0o_calc.OUT","PLC:B34:PP02:115:A0o.VAL")
#! Record("PLC:B34:PP02:115:A0o",500,20,0,0,"PLC:B34:PP02:115:A0o")
#! Field("PLC:B34:PP02:115:A0o.VAL",16777215,1,"PLC:B34:PP02:115:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi139") {
  field(DESC, "Port PLC_RD bit 139")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 139, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:116:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi139Valid") {
  field(INPA, "PLC:B34:PP02:Bi139.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:116:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:116:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi139 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi139Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:116:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:116:A0o") {
  field(DESC, "Bi139 --> A0.o116 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb139",20,19,0,0,"PLC:B34:PP02:PLC_RDb139")
#! Field("PLC:B34:PP02:PLC_RDb139.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb139.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb139.FLNK","PLC:B34:PP02:116:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb139.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb139.VAL")
#! Record("PLC:B34:PP02:116:A0o_calc",260,18,0,1,"PLC:B34:PP02:116:A0o_calc")
#! Field("PLC:B34:PP02:116:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:116:A0o_calc.INPA")
#! Link("PLC:B34:PP02:116:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb139.VAL")
#! Field("PLC:B34:PP02:116:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:116:A0o_calc.INPB")
#! Field("PLC:B34:PP02:116:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:116:A0o_calc.OUT")
#! Link("PLC:B34:PP02:116:A0o_calc.OUT","PLC:B34:PP02:116:A0o.VAL")
#! Record("PLC:B34:PP02:116:A0o",500,20,0,0,"PLC:B34:PP02:116:A0o")
#! Field("PLC:B34:PP02:116:A0o.VAL",16777215,1,"PLC:B34:PP02:116:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi138") {
  field(DESC, "Port PLC_RD bit 138")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 138, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:117:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi138Valid") {
  field(INPA, "PLC:B34:PP02:Bi138.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:117:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:117:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi138 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi138Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:117:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:117:A0o") {
  field(DESC, "Bi138 --> A0.o117 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb138",20,19,0,0,"PLC:B34:PP02:PLC_RDb138")
#! Field("PLC:B34:PP02:PLC_RDb138.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb138.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb138.FLNK","PLC:B34:PP02:117:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb138.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb138.VAL")
#! Record("PLC:B34:PP02:117:A0o_calc",260,18,0,1,"PLC:B34:PP02:117:A0o_calc")
#! Field("PLC:B34:PP02:117:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:117:A0o_calc.INPA")
#! Link("PLC:B34:PP02:117:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb138.VAL")
#! Field("PLC:B34:PP02:117:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:117:A0o_calc.INPB")
#! Field("PLC:B34:PP02:117:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:117:A0o_calc.OUT")
#! Link("PLC:B34:PP02:117:A0o_calc.OUT","PLC:B34:PP02:117:A0o.VAL")
#! Record("PLC:B34:PP02:117:A0o",500,20,0,0,"PLC:B34:PP02:117:A0o")
#! Field("PLC:B34:PP02:117:A0o.VAL",16777215,1,"PLC:B34:PP02:117:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi137") {
  field(DESC, "Port PLC_RD bit 137")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 137, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:118:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi137Valid") {
  field(INPA, "PLC:B34:PP02:Bi137.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:118:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:118:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi137 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi137Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:118:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:118:A0o") {
  field(DESC, "Bi137 --> A0.o118 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb137",20,19,0,0,"PLC:B34:PP02:PLC_RDb137")
#! Field("PLC:B34:PP02:PLC_RDb137.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb137.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb137.FLNK","PLC:B34:PP02:118:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb137.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb137.VAL")
#! Record("PLC:B34:PP02:118:A0o_calc",260,18,0,1,"PLC:B34:PP02:118:A0o_calc")
#! Field("PLC:B34:PP02:118:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:118:A0o_calc.INPA")
#! Link("PLC:B34:PP02:118:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb137.VAL")
#! Field("PLC:B34:PP02:118:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:118:A0o_calc.INPB")
#! Field("PLC:B34:PP02:118:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:118:A0o_calc.OUT")
#! Link("PLC:B34:PP02:118:A0o_calc.OUT","PLC:B34:PP02:118:A0o.VAL")
#! Record("PLC:B34:PP02:118:A0o",500,20,0,0,"PLC:B34:PP02:118:A0o")
#! Field("PLC:B34:PP02:118:A0o.VAL",16777215,1,"PLC:B34:PP02:118:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi136") {
  field(DESC, "Port PLC_RD bit 136")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 136, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:119:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi136Valid") {
  field(INPA, "PLC:B34:PP02:Bi136.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:119:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:119:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi136 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi136Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:119:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:119:A0o") {
  field(DESC, "Bi136 --> A0.o119 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb136",20,19,0,0,"PLC:B34:PP02:PLC_RDb136")
#! Field("PLC:B34:PP02:PLC_RDb136.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb136.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb136.FLNK","PLC:B34:PP02:119:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb136.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb136.VAL")
#! Record("PLC:B34:PP02:119:A0o_calc",260,18,0,1,"PLC:B34:PP02:119:A0o_calc")
#! Field("PLC:B34:PP02:119:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:119:A0o_calc.INPA")
#! Link("PLC:B34:PP02:119:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb136.VAL")
#! Field("PLC:B34:PP02:119:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:119:A0o_calc.INPB")
#! Field("PLC:B34:PP02:119:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:119:A0o_calc.OUT")
#! Link("PLC:B34:PP02:119:A0o_calc.OUT","PLC:B34:PP02:119:A0o.VAL")
#! Record("PLC:B34:PP02:119:A0o",500,20,0,0,"PLC:B34:PP02:119:A0o")
#! Field("PLC:B34:PP02:119:A0o.VAL",16777215,1,"PLC:B34:PP02:119:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi151") {
  field(DESC, "Port PLC_RD bit 151")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 151, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:120:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi151Valid") {
  field(INPA, "PLC:B34:PP02:Bi151.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:120:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:120:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi151 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi151Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:120:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:120:A0o") {
  field(DESC, "Bi151 --> A0.o112 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb151",20,19,0,0,"PLC:B34:PP02:PLC_RDb151")
#! Field("PLC:B34:PP02:PLC_RDb151.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb151.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb151.FLNK","PLC:B34:PP02:120:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb151.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb151.VAL")
#! Record("PLC:B34:PP02:120:A0o_calc",260,18,0,1,"PLC:B34:PP02:120:A0o_calc")
#! Field("PLC:B34:PP02:120:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:120:A0o_calc.INPA")
#! Link("PLC:B34:PP02:120:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb151.VAL")
#! Field("PLC:B34:PP02:120:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:120:A0o_calc.INPB")
#! Field("PLC:B34:PP02:120:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:120:A0o_calc.OUT")
#! Link("PLC:B34:PP02:120:A0o_calc.OUT","PLC:B34:PP02:120:A0o.VAL")
#! Record("PLC:B34:PP02:120:A0o",500,20,0,0,"PLC:B34:PP02:120:A0o")
#! Field("PLC:B34:PP02:120:A0o.VAL",16777215,1,"PLC:B34:PP02:120:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi150") {
  field(DESC, "Port PLC_RD bit 150")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 150, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:121:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi150Valid") {
  field(INPA, "PLC:B34:PP02:Bi150.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:121:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:121:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi150 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi150Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:121:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:121:A0o") {
  field(DESC, "Bi150 --> A0.o113 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb150",20,19,0,0,"PLC:B34:PP02:PLC_RDb150")
#! Field("PLC:B34:PP02:PLC_RDb150.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb150.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb150.FLNK","PLC:B34:PP02:121:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb150.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb150.VAL")
#! Record("PLC:B34:PP02:121:A0o_calc",260,18,0,1,"PLC:B34:PP02:121:A0o_calc")
#! Field("PLC:B34:PP02:121:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:121:A0o_calc.INPA")
#! Link("PLC:B34:PP02:121:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb150.VAL")
#! Field("PLC:B34:PP02:121:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:121:A0o_calc.INPB")
#! Field("PLC:B34:PP02:121:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:121:A0o_calc.OUT")
#! Link("PLC:B34:PP02:121:A0o_calc.OUT","PLC:B34:PP02:121:A0o.VAL")
#! Record("PLC:B34:PP02:121:A0o",500,20,0,0,"PLC:B34:PP02:121:A0o")
#! Field("PLC:B34:PP02:121:A0o.VAL",16777215,1,"PLC:B34:PP02:121:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi149") {
  field(DESC, "Port PLC_RD bit 149")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 149, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:122:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi149Valid") {
  field(INPA, "PLC:B34:PP02:Bi149.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:122:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:122:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi149 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi149Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:122:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:122:A0o") {
  field(DESC, "Bi149 --> A0.o114 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb149",20,19,0,0,"PLC:B34:PP02:PLC_RDb149")
#! Field("PLC:B34:PP02:PLC_RDb149.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb149.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb149.FLNK","PLC:B34:PP02:122:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb149.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb149.VAL")
#! Record("PLC:B34:PP02:122:A0o_calc",260,18,0,1,"PLC:B34:PP02:122:A0o_calc")
#! Field("PLC:B34:PP02:122:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:122:A0o_calc.INPA")
#! Link("PLC:B34:PP02:122:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb149.VAL")
#! Field("PLC:B34:PP02:122:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:122:A0o_calc.INPB")
#! Field("PLC:B34:PP02:122:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:122:A0o_calc.OUT")
#! Link("PLC:B34:PP02:122:A0o_calc.OUT","PLC:B34:PP02:122:A0o.VAL")
#! Record("PLC:B34:PP02:122:A0o",500,20,0,0,"PLC:B34:PP02:122:A0o")
#! Field("PLC:B34:PP02:122:A0o.VAL",16777215,1,"PLC:B34:PP02:122:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi148") {
  field(DESC, "Port PLC_RD bit 148")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 148, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:123:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi148Valid") {
  field(INPA, "PLC:B34:PP02:Bi148.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:123:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:123:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi148 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi148Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:123:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:123:A0o") {
  field(DESC, "Bi148 --> A0.o115 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb148",20,19,0,0,"PLC:B34:PP02:PLC_RDb148")
#! Field("PLC:B34:PP02:PLC_RDb148.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb148.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb148.FLNK","PLC:B34:PP02:123:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb148.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb148.VAL")
#! Record("PLC:B34:PP02:123:A0o_calc",260,18,0,1,"PLC:B34:PP02:123:A0o_calc")
#! Field("PLC:B34:PP02:123:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:123:A0o_calc.INPA")
#! Link("PLC:B34:PP02:123:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb148.VAL")
#! Field("PLC:B34:PP02:123:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:123:A0o_calc.INPB")
#! Field("PLC:B34:PP02:123:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:123:A0o_calc.OUT")
#! Link("PLC:B34:PP02:123:A0o_calc.OUT","PLC:B34:PP02:123:A0o.VAL")
#! Record("PLC:B34:PP02:123:A0o",500,20,0,0,"PLC:B34:PP02:123:A0o")
#! Field("PLC:B34:PP02:123:A0o.VAL",16777215,1,"PLC:B34:PP02:123:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi147") {
  field(DESC, "Port PLC_RD bit 147")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 147, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:124:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi147Valid") {
  field(INPA, "PLC:B34:PP02:Bi147.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:124:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:124:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi147 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi147Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:124:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:124:A0o") {
  field(DESC, "Bi147 --> A0.o116 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb147",20,19,0,0,"PLC:B34:PP02:PLC_RDb147")
#! Field("PLC:B34:PP02:PLC_RDb147.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb147.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb147.FLNK","PLC:B34:PP02:124:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb147.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb147.VAL")
#! Record("PLC:B34:PP02:124:A0o_calc",260,18,0,1,"PLC:B34:PP02:124:A0o_calc")
#! Field("PLC:B34:PP02:124:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:124:A0o_calc.INPA")
#! Link("PLC:B34:PP02:124:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb147.VAL")
#! Field("PLC:B34:PP02:124:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:124:A0o_calc.INPB")
#! Field("PLC:B34:PP02:124:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:124:A0o_calc.OUT")
#! Link("PLC:B34:PP02:124:A0o_calc.OUT","PLC:B34:PP02:124:A0o.VAL")
#! Record("PLC:B34:PP02:124:A0o",500,20,0,0,"PLC:B34:PP02:124:A0o")
#! Field("PLC:B34:PP02:124:A0o.VAL",16777215,1,"PLC:B34:PP02:124:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi146") {
  field(DESC, "Port PLC_RD bit 146")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 146, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:125:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi146Valid") {
  field(INPA, "PLC:B34:PP02:Bi146.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:125:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:125:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi146 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi146Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:125:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:125:A0o") {
  field(DESC, "Bi146 --> A0.o117 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb146",20,19,0,0,"PLC:B34:PP02:PLC_RDb146")
#! Field("PLC:B34:PP02:PLC_RDb146.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb146.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb146.FLNK","PLC:B34:PP02:125:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb146.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb146.VAL")
#! Record("PLC:B34:PP02:125:A0o_calc",260,18,0,1,"PLC:B34:PP02:125:A0o_calc")
#! Field("PLC:B34:PP02:125:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:125:A0o_calc.INPA")
#! Link("PLC:B34:PP02:125:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb146.VAL")
#! Field("PLC:B34:PP02:125:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:125:A0o_calc.INPB")
#! Field("PLC:B34:PP02:125:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:125:A0o_calc.OUT")
#! Link("PLC:B34:PP02:125:A0o_calc.OUT","PLC:B34:PP02:125:A0o.VAL")
#! Record("PLC:B34:PP02:125:A0o",500,20,0,0,"PLC:B34:PP02:125:A0o")
#! Field("PLC:B34:PP02:125:A0o.VAL",16777215,1,"PLC:B34:PP02:125:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi145") {
  field(DESC, "Port PLC_RD bit 145")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 145, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:126:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi145Valid") {
  field(INPA, "PLC:B34:PP02:Bi145.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:126:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:126:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi145 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi145Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:126:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:126:A0o") {
  field(DESC, "Bi145 --> A0.o118 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb145",20,19,0,0,"PLC:B34:PP02:PLC_RDb145")
#! Field("PLC:B34:PP02:PLC_RDb145.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb145.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb145.FLNK","PLC:B34:PP02:126:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb145.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb145.VAL")
#! Record("PLC:B34:PP02:126:A0o_calc",260,18,0,1,"PLC:B34:PP02:126:A0o_calc")
#! Field("PLC:B34:PP02:126:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:126:A0o_calc.INPA")
#! Link("PLC:B34:PP02:126:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb145.VAL")
#! Field("PLC:B34:PP02:126:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:126:A0o_calc.INPB")
#! Field("PLC:B34:PP02:126:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:126:A0o_calc.OUT")
#! Link("PLC:B34:PP02:126:A0o_calc.OUT","PLC:B34:PP02:126:A0o.VAL")
#! Record("PLC:B34:PP02:126:A0o",500,20,0,0,"PLC:B34:PP02:126:A0o")
#! Field("PLC:B34:PP02:126:A0o.VAL",16777215,1,"PLC:B34:PP02:126:A0o.VAL")
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND



record(bi, "PLC:B34:PP02:Bi144") {
  field(DESC, "Port PLC_RD bit 144")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_RD, 144, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(FLNK, "PLC:B34:PP02:127:A0o_calc PP NMS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:Bi144Valid") {
  field(INPA, "PLC:B34:PP02:Bi144.SEVR NPP NMS")
  field(CALC, "A=3?VAL+1:0")
#Go invalid if input is invalid for 3 seconds
  field(HIHI, 9)
  field(HHSV, "INVALID")
  field(OUT, "PLC:B34:PP02:127:A0o_calc.C PP MSI")
  field(SCAN, "1 second")
  field(ASG,  "Internal")
  field(OOPT, "On Change")
}

record(calcout, "PLC:B34:PP02:127:A0o_calc") {
  field(INPA, "PLC:B34:PP02:Bi144 NPP NMS")
  field(INPB, "PLC:B34:PP02:TABLE_9_SEG_1 CP NMS")
# Input C is for setting invalid severity, not used otherwise
  field(INPC, "PLC:B34:PP02:Bi144Valid NPP MSI")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:127:A0o PP MS")
  field(ASG,  "Internal")
}

record(bi, "PLC:B34:PP02:127:A0o") {
  field(DESC, "Bi144 --> A0.o119 Status")
  field(ZNAM, "Off")
  field(ONAM, "On")
  field(ZSV, "NO_ALARM")
  field(OSV, "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

#! Further lines contain data used by VisualDCT
#! View(0,0,1.0)
#! Record("PLC:B34:PP02:PLC_RDb144",20,19,0,0,"PLC:B34:PP02:PLC_RDb144")
#! Field("PLC:B34:PP02:PLC_RDb144.FLNK",16777215,1,"PLC:B34:PP02:PLC_RDb144.FLNK")
#! Link("PLC:B34:PP02:PLC_RDb144.FLNK","PLC:B34:PP02:127:A0o_calc")
#! Field("PLC:B34:PP02:PLC_RDb144.VAL",16777215,0,"PLC:B34:PP02:PLC_RDb144.VAL")
#! Record("PLC:B34:PP02:127:A0o_calc",260,18,0,1,"PLC:B34:PP02:127:A0o_calc")
#! Field("PLC:B34:PP02:127:A0o_calc.INPA",16777215,0,"PLC:B34:PP02:127:A0o_calc.INPA")
#! Link("PLC:B34:PP02:127:A0o_calc.INPA","PLC:B34:PP02:PLC_RDb144.VAL")
#! Field("PLC:B34:PP02:127:A0o_calc.INPB",16777215,1,"PLC:B34:PP02:127:A0o_calc.INPB")
#! Field("PLC:B34:PP02:127:A0o_calc.OUT",16777215,1,"PLC:B34:PP02:127:A0o_calc.OUT")
#! Link("PLC:B34:PP02:127:A0o_calc.OUT","PLC:B34:PP02:127:A0o.VAL")
#! Record("PLC:B34:PP02:127:A0o",500,20,0,0,"PLC:B34:PP02:127:A0o")
#! Field("PLC:B34:PP02:127:A0o.VAL",16777215,1,"PLC:B34:PP02:127:A0o.VAL")
record(bo, "PLC:B34:PP02:00:A0i") {
  field(DESC, "Bi --> A0.i0 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 7, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:01:A0i") {
  field(DESC, "Bi --> A0.i1 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 6, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:02:A0i") {
  field(DESC, "Bi --> A0.i2 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 5, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:03:A0i") {
  field(DESC, "Bi --> A0.i3 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 4, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:04:A0i") {
  field(DESC, "Bi --> A0.i4 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 3, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:05:A0i") {
  field(DESC, "Bi --> A0.i5 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 2, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:06:A0i") {
  field(DESC, "Bi --> A0.i6 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 1, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:07:A0i") {
  field(DESC, "Bi --> A0.i7 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 0, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:08:AOi") {
  field(DESC, "Bi --> A0.i8 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 15, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:09:A0i") {
  field(DESC, "Bi --> A0.i9 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 14, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:10:A0i") {
  field(DESC, "Bi --> A0.i10 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 13, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:11:A0i") {
  field(DESC, "Bi --> A0.i11 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 12, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:12:A0i") {
  field(DESC, "Bi --> A0.i12 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 11, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:13:A0i") {
  field(DESC, "Bi --> A0.i13 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 10, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:14:A0i") {
  field(DESC, "Bi --> A0.i14 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 9, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:15:A0i") {
  field(DESC, "Bi --> A0.i15 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 8, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:16:A0i") {
  field(DESC, "Bi --> A0.i16 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 23, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:17:A0i") {
  field(DESC, "Bi --> A0.i17 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 22, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:18:A0i") {
  field(DESC, "Bi --> A0.i18 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 21, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:19:A0i") {
  field(DESC, "Bi --> A0.i19 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 20, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:20:A0i") {
  field(DESC, "Bi --> A0.i20 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 19, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:21:A0i") {
  field(DESC, "Bi --> A0.i21 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 18, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:22:A0i") {
  field(DESC, "Bi --> A0.i22 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 17, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:23:A0i") {
  field(DESC, "Bi --> A0.i23 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 16, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:64:A0i") {
  field(DESC, "Bi --> A0.i64 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 95, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:65:A0i") {
  field(DESC, "Bi --> A0.i65 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 94, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:66:A0i") {
  field(DESC, "Bi --> A0.i66 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 93, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:67:A0i") {
  field(DESC, "Bi --> A0.i67 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 92, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:68:A0i") {
  field(DESC, "Bi --> A0.i68 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 91, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:69:A0i") {
  field(DESC, "Bi --> A0.i69 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 90, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:70:A0i") {
  field(DESC, "Bi --> A0.i70 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 89, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:71:A0i") {
  field(DESC, "Bi --> A0.i71 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 88, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:72:A0i") {
  field(DESC, "Bi --> A0.i72 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 103, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:73:A0i") {
  field(DESC, "Bi --> A0.i73 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 102, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:74:A0i") {
  field(DESC, "Bi --> A0.i74 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 101, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:75:A0i") {
  field(DESC, "Bi --> A0.i75 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 100, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:76:A0i") {
  field(DESC, "Bi --> A0.i76 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 99, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:77:A0i") {
  field(DESC, "Bi --> A0.i77 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 98, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:78:A0i") {
  field(DESC, "Bi --> A0.i78 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 97, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:79:A0i") {
  field(DESC, "Bi --> A0.i79 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 96, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:80:A0i") {
  field(DESC, "Bi --> A0.i80 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 111, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:81:A0i") {
  field(DESC, "Bi --> A0.i81 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 110, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:82:A0i") {
  field(DESC, "Bi --> A0.i82 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 109, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:83:A0i") {
  field(DESC, "Bi --> A0.i83 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 108, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:84:A0i") {
  field(DESC, "Bi --> A0.i84 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 107, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:85:A0i") {
  field(DESC, "Bi --> A0.i85 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 106, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:86:A0i") {
  field(DESC, "Bi --> A0.i86 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 105, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:87:A0i") {
  field(DESC, "Bi --> A0.i87 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 104, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:88:A0i") {
  field(DESC, "Bi --> A0.i88 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 119, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:89:A0i") {
  field(DESC, "Bi --> A0.i89 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 118, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:90:A0i") {
  field(DESC, "Bi --> A0.i90 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 117, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:91:A0i") {
  field(DESC, "Bi --> A0.i91 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 116, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:92:A0i") {
  field(DESC, "Bi --> A0.i92 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 115, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:93:A0i") {
  field(DESC, "Bi --> A0.i93 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 114, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:94:A0i") {
  field(DESC, "Bi --> A0.i94 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 113, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:95:A0i") {
  field(DESC, "Bi --> A0.i95 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 112, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:96:A0i") {
  field(DESC, "Bi --> A0.i96 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 127, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:97:A0i") {
  field(DESC, "Bi --> A0.i97 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 126, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:98:A0i") {
  field(DESC, "Bi --> A0.i98 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 125, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:99:A0i") {
  field(DESC, "Bi --> A0.i99 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 124, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:100:A0i") {
  field(DESC, "Bi --> A0.i100 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 123, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:101:A0i") {
  field(DESC, "Bi --> A0.i101 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 122, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:102:A0i") {
  field(DESC, "Bi --> A0.i102 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 121, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:103:A0i") {
  field(DESC, "Bi --> A0.i103 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 120, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:104:A0i") {
  field(DESC, "Bi --> A0.i104 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 135, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:105:A0i") {
  field(DESC, "Bi --> A0.i105 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 134, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:106:A0i") {
  field(DESC, "Bi --> A0.i106 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 133, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:107:A0i") {
  field(DESC, "Bi --> A0.i107 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 132, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:108:A0i") {
  field(DESC, "Bi --> A0.i108 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 131, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:109:A0i") {
  field(DESC, "Bi --> A0.i109 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 130, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:110:A0i") {
  field(DESC, "Bi --> A0.i110 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 129, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:111:A0i") {
  field(DESC, "Bi --> A0.i111 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 128, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:112:A0i") {
  field(DESC, "Bi --> A0.i112 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 143, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:113:A0i") {
  field(DESC, "Bi --> A0.i113 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 142, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:114:A0i") {
  field(DESC, "Bi --> A0.i114 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 141, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:115:A0i") {
  field(DESC, "Bi --> A0.i115 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 140, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:116:A0i") {
  field(DESC, "Bi --> A0.i116 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 139, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:117:A0i") {
  field(DESC, "Bi --> A0.i117 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 138, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:118:A0i") {
  field(DESC, "Bi --> A0.i118 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 137, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:119:A0i") {
  field(DESC, "Bi --> A0.i119 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 136, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:120:A0i") {
  field(DESC, "Bi --> A0.i120 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 151, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:121:A0i") {
  field(DESC, "Bi --> A0.i121 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 150, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:122:A0i") {
  field(DESC, "Bi --> A0.i122 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 149, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:123:A0i") {
  field(DESC, "Bi --> A0.i123 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 148, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:124:A0i") {
  field(DESC, "Bi --> A0.i125 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 147, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:125:A0i") {
  field(DESC, "Bi --> A0.i126 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 146, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:126:A0i") {
  field(DESC, "Bi --> A0.i127 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 145, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

record(bo, "PLC:B34:PP02:127:A0i") {
  field(DESC, "Bi --> A0.i128 Status")
  field(DTYP, "asynUInt32Digital")
  field(OUT,  "@asynMask(PLC_WT, 144, 1, 1)")
  field(ZNAM, "Off")
  field(ONAM, "On")
   field(ASG,  "MCC")
}

#==============================================================================
#
# Abs:  PILZ PNOZ PLC interface for accessing the right table/segment
#
# Name: pilz-plc-request.template
#
# Facility: LCLS Personnel Protection Controls
#
# Auth: 11-Dec-2018, Garth Brown   (GWBROWN)
# Rev : dd-mmm-yyyy, Reviewer's Name  (USERNAME)
#
# To specify which registers to read/write, you need to set the table and
# segment (see PNOZ docs). This set of PVs keeps them set to the correct values
# for reading either virtual I/O points or program stats such as project checksum.
# The PNOZ PLC also has occasional communications dropouts, where the PLC stops
# responding and the TCP connection must be reset. This happens more frequently
# the more communication there is with the PLC.
# While the vendor offers a PNOZ model with integrated Ethernet port which
# allows readback at different modbus addresses instead of needing to set
# table/segment, that interface also allows remote access to secure registers
# and PLC programming. For safety, that type of remote access is not allowed in
# our system. All of their products that don't allow remote access beyond our
# safety specs also require table/segment setting to choose which registers to
# read/write.
#
#-----------------------------------------------------------------------------
#  Mod:
#
#==============================================================================
#

record(longout, "PLC:B34:PP02:REQ_TABLE") {
	field(DESC, "Table to read/write")
	field(VAL, "9")
	field(OUT, "PLC:B34:PP02:REQ_TABLE_OUT PP")
	field(HOPR, "128")
	field(LOPR, "0")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}

# All the data we're interested in is: Tables 1 and 9, segment 1
# We only need table 1 once for check sums that don't change, so
# read it for a short time during startup, then switch to table 9.
record(calcout, "PLC:B34:PP02:TABLE_CYCLER")
{
	field( OUT, "PLC:B34:PP02:REQ_TABLE PP")
	field( CALC, "A:=(A+1)%3600;A=20?1:9")
	field( INPA, "0")
	field( SCAN, ".5 second")
}

record(calcout, "PLC:B34:PP02:SEG_CYCLER")
{
	field( OUT, "PLC:B34:PP02:REQ_SEG PP")
	field( CALC, "1")
	field( INPA, "0")
	field( SCAN, ".5 second")
}

# Records for disabling PVs when their reqest table isn't active
record(calc, "PLC:B34:PP02:TABLE_9_SEG_1")
{
	field( INPA, "PLC:B34:PP02:REQ_TABLE CP")
	field( INPB, "PLC:B34:PP02:REQ_SEG CP")
	field( INPC, "PLC:B34:PP02:REQ_TABLE_IN CP")
	field( INPD, "PLC:B34:PP02:REQ_SEG_IN CP")
	field(CALC, "A=9 & B=1 & C=9 & D=1")
}

record(calc, "PLC:B34:PP02:TABLE_1_SEG_1")
{
	field( INPA, "PLC:B34:PP02:REQ_TABLE CP")
	field( INPB, "PLC:B34:PP02:REQ_SEG CP")
	field( INPC, "PLC:B34:PP02:REQ_TABLE_IN CP")
	field( INPD, "PLC:B34:PP02:REQ_SEG_IN CP")
	field(CALC, "A=1 & B=1 & C=1 & D=1")
}

# The target PVs don't use the data, but this has 8 forward links,
# the number we need, while the fanout record only has 6.
record(dfanout, "PLC:B34:PP02:REQ_TABLE_OUT") {
	field(OUTA, "PLC:B34:PP02:REQ_TABLE_BIT0_CALC.A PP")
	field(OUTB, "PLC:B34:PP02:REQ_TABLE_BIT1_CALC.A PP")
	field(OUTC, "PLC:B34:PP02:REQ_TABLE_BIT2_CALC.A PP")
	field(OUTD, "PLC:B34:PP02:REQ_TABLE_BIT3_CALC.A PP")
	field(OUTE, "PLC:B34:PP02:REQ_TABLE_BIT4_CALC.A PP")
	field(OUTF, "PLC:B34:PP02:REQ_TABLE_BIT5_CALC.A PP")
	field(OUTG, "PLC:B34:PP02:REQ_TABLE_BIT6_CALC.A PP")
	field(OUTH, "PLC:B34:PP02:REQ_TABLE_BIT7_CALC.A PP")
	field(SDIS, "PLC:B34:PP02:REQ_TABLE_IN.PACT")
}

# The simpler approach of writing to the table/segment every few seconds caused
# TCP dropouts to happen several times an hour, compared to every day or two
# when we only ever read/wrote table 9 segment 1. These calcout records reduce
# the dropouts to around 5 a day by only writing the bits that need to change.

record(calcout, "PLC:B34:PP02:REQ_TABLE_BIT0_CALC") {
	field(INPA, "PLC:B34:PP02:REQ_TABLE_OUT")
	field(INPB, "PLC:B34:PP02:TABLE_BIT0 MS")
	field(INPC, "PLC:B34:PP02:REQ_TABLE_BIT0 MS")
	field(CALC, "(B#C)||(B#(A&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "A&1")
	field(OUT, "PLC:B34:PP02:REQ_TABLE_BIT0 PP")
}

record(calcout, "PLC:B34:PP02:REQ_TABLE_BIT1_CALC") {
	field(INPA, "PLC:B34:PP02:REQ_TABLE_OUT")
	field(INPB, "PLC:B34:PP02:TABLE_BIT1 MS")
	field(INPC, "PLC:B34:PP02:REQ_TABLE_BIT1 MS")
	field(CALC, "(B#C)||(B#((A>>1)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>1)&1")
	field(OUT, "PLC:B34:PP02:REQ_TABLE_BIT1 PP")
}

record(calcout, "PLC:B34:PP02:REQ_TABLE_BIT2_CALC") {
	field(INPA, "PLC:B34:PP02:REQ_TABLE_OUT")
	field(INPB, "PLC:B34:PP02:TABLE_BIT2 MS")
	field(INPC, "PLC:B34:PP02:REQ_TABLE_BIT2 MS")
	field(CALC, "(B#C)||(B#((A>>2)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>2)&1")
	field(OUT, "PLC:B34:PP02:REQ_TABLE_BIT2 PP")
}

record(calcout, "PLC:B34:PP02:REQ_TABLE_BIT3_CALC") {
	field(INPA, "PLC:B34:PP02:REQ_TABLE_OUT")
	field(INPB, "PLC:B34:PP02:TABLE_BIT3 MS")
	field(INPC, "PLC:B34:PP02:REQ_TABLE_BIT3 MS")
	field(CALC, "(B#C)||(B#((A>>3)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>3)&1")
	field(OUT, "PLC:B34:PP02:REQ_TABLE_BIT3 PP")
}

record(calcout, "PLC:B34:PP02:REQ_TABLE_BIT4_CALC") {
	field(INPA, "PLC:B34:PP02:REQ_TABLE_OUT")
	field(INPB, "PLC:B34:PP02:TABLE_BIT4 MS")
	field(INPC, "PLC:B34:PP02:REQ_TABLE_BIT4 MS")
	field(CALC, "(B#C)||(B#((A>>4)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>4)&1")
	field(OUT, "PLC:B34:PP02:REQ_TABLE_BIT4 PP")
}

record(calcout, "PLC:B34:PP02:REQ_TABLE_BIT5_CALC") {
	field(INPA, "PLC:B34:PP02:REQ_TABLE_OUT")
	field(INPB, "PLC:B34:PP02:TABLE_BIT5 MS")
	field(INPC, "PLC:B34:PP02:REQ_TABLE_BIT5 MS")
	field(CALC, "(B#C)||(B#((A>>5)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>5)&1")
	field(OUT, "PLC:B34:PP02:REQ_TABLE_BIT5 PP")
}

record(calcout, "PLC:B34:PP02:REQ_TABLE_BIT6_CALC") {
	field(INPA, "PLC:B34:PP02:REQ_TABLE_OUT")
	field(INPB, "PLC:B34:PP02:TABLE_BIT6 MS")
	field(INPC, "PLC:B34:PP02:REQ_TABLE_BIT6 MS")
	field(CALC, "(B#C)||(B#((A>>6)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>6)&1")
	field(OUT, "PLC:B34:PP02:REQ_TABLE_BIT6 PP")
}

record(calcout, "PLC:B34:PP02:REQ_TABLE_BIT7_CALC") {
	field(INPA, "PLC:B34:PP02:REQ_TABLE_OUT")
	field(INPB, "PLC:B34:PP02:TABLE_BIT7 MS")
	field(INPC, "PLC:B34:PP02:REQ_TABLE_BIT7 MS")
	field(CALC, "(B#C)||(B#((A>>7)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>7)&1")
	field(OUT, "PLC:B34:PP02:REQ_TABLE_BIT7 PP")
}


record(calcout, "PLC:B34:PP02:REQ_TABLE_IN") {
	field(DESC, "Table readback")
	field(INPA, "PLC:B34:PP02:TABLE_BIT0 CP MS")
	field(INPB, "PLC:B34:PP02:TABLE_BIT1 CP MS")
	field(INPC, "PLC:B34:PP02:TABLE_BIT2 CP MS")
	field(INPD, "PLC:B34:PP02:TABLE_BIT3 CP MS")
	field(INPE, "PLC:B34:PP02:TABLE_BIT4 CP MS")
	field(INPF, "PLC:B34:PP02:TABLE_BIT5 CP MS")
	field(INPG, "PLC:B34:PP02:TABLE_BIT6 CP MS")
	field(INPH, "PLC:B34:PP02:TABLE_BIT7 CP MS")
	field(CALC, "A+B*2+C*4+D*8+E*16+F*32+G*64+H*128")
	field(OUT, "PLC:B34:PP02:REQ_TABLE PP MS")
	#field(SDIS, "PLC:B34:PP02:REQ_TABLE_OUT.PACT")
}


record(longout, "PLC:B34:PP02:REQ_SEG") {
	field(DESC, "Segment to read/write")
	field(VAL, "1")
	field(OUT, "PLC:B34:PP02:REQ_SEG_OUT PP")
	field(HOPR, "128")
	field(LOPR, "0")
	field(PINI, "YES")
	info(autosaveFields, "VAL")
}

# The target PVs don't use the data, but this has 8 forward links,
# the number we need, while the fanout record only has 6.
record(dfanout, "PLC:B34:PP02:REQ_SEG_OUT") {
	field(OUTA, "PLC:B34:PP02:REQ_SEG_BIT0_CALC.A PP")
	field(OUTB, "PLC:B34:PP02:REQ_SEG_BIT1_CALC.A PP")
	field(OUTC, "PLC:B34:PP02:REQ_SEG_BIT2_CALC.A PP")
	field(OUTD, "PLC:B34:PP02:REQ_SEG_BIT3_CALC.A PP")
	field(OUTE, "PLC:B34:PP02:REQ_SEG_BIT4_CALC.A PP")
	field(OUTF, "PLC:B34:PP02:REQ_SEG_BIT5_CALC.A PP")
	field(OUTG, "PLC:B34:PP02:REQ_SEG_BIT6_CALC.A PP")
	field(OUTH, "PLC:B34:PP02:REQ_SEG_BIT7_CALC.A PP")
	field(SDIS, "PLC:B34:PP02:REQ_SEG_IN.PACT")
}

record(calcout, "PLC:B34:PP02:REQ_SEG_BIT0_CALC") {
	field(INPA, "PLC:B34:PP02:REQ_SEG_OUT")
	field(INPB, "PLC:B34:PP02:SEG_BIT0 CP MS")
	field(CALC, "(B#C)||(B#(A&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "A&1")
	field(OUT, "PLC:B34:PP02:REQ_SEG_BIT0 PP")
}

record(calcout, "PLC:B34:PP02:REQ_SEG_BIT1_CALC") {
	field(INPA, "PLC:B34:PP02:REQ_SEG_OUT")
	field(INPB, "PLC:B34:PP02:SEG_BIT1 MS")
	field(INPC, "PLC:B34:PP02:REQ_SEG_BIT1 MS")
	field(CALC, "(B#C)||(B#((A>>1)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>1)&1")
	field(OUT, "PLC:B34:PP02:REQ_SEG_BIT1 PP")
}

record(calcout, "PLC:B34:PP02:REQ_SEG_BIT2_CALC") {
	field(INPA, "PLC:B34:PP02:REQ_SEG_OUT")
	field(INPB, "PLC:B34:PP02:SEG_BIT2 MS")
	field(INPC, "PLC:B34:PP02:REQ_SEG_BIT2 MS")
	field(CALC, "(B#C)||(B#((A>>2)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>2)&1")
	field(OUT, "PLC:B34:PP02:REQ_SEG_BIT2 PP")
}

record(calcout, "PLC:B34:PP02:REQ_SEG_BIT3_CALC") {
	field(INPA, "PLC:B34:PP02:REQ_SEG_OUT")
	field(INPB, "PLC:B34:PP02:SEG_BIT3 MS")
	field(INPC, "PLC:B34:PP02:REQ_SEG_BIT3 MS")
	field(CALC, "(B#C)||(B#((A>>3)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>3)&1")
	field(OUT, "PLC:B34:PP02:REQ_SEG_BIT3 PP")
}

record(calcout, "PLC:B34:PP02:REQ_SEG_BIT4_CALC") {
	field(INPA, "PLC:B34:PP02:REQ_SEG_OUT")
	field(INPB, "PLC:B34:PP02:SEG_BIT4 MS")
	field(INPC, "PLC:B34:PP02:REQ_SEG_BIT4 MS")
	field(CALC, "(B#C)||(B#((A>>4)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>4)&1")
	field(OUT, "PLC:B34:PP02:REQ_SEG_BIT4 PP")
}

record(calcout, "PLC:B34:PP02:REQ_SEG_BIT5_CALC") {
	field(INPA, "PLC:B34:PP02:REQ_SEG_OUT")
	field(INPB, "PLC:B34:PP02:SEG_BIT5 MS")
	field(INPC, "PLC:B34:PP02:REQ_SEG_BIT5 MS")
	field(CALC, "(B#C)||(B#((A>>5)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>5)&1")
	field(OUT, "PLC:B34:PP02:REQ_SEG_BIT5 PP")
}

record(calcout, "PLC:B34:PP02:REQ_SEG_BIT6_CALC") {
	field(INPA, "PLC:B34:PP02:REQ_SEG_OUT")
	field(INPB, "PLC:B34:PP02:SEG_BIT6 MS")
	field(INPC, "PLC:B34:PP02:REQ_SEG_BIT6 MS")
	field(CALC, "(B#C)||(B#((A>>6)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>6)&1")
	field(OUT, "PLC:B34:PP02:REQ_SEG_BIT6 PP")
}

record(calcout, "PLC:B34:PP02:REQ_SEG_BIT7_CALC") {
	field(INPA, "PLC:B34:PP02:REQ_SEG_OUT")
	field(INPB, "PLC:B34:PP02:SEG_BIT7 MS")
	field(INPC, "PLC:B34:PP02:REQ_SEG_BIT7 MS")
	field(CALC, "(B#C)||(B#((A>>7)&1))")
	field(DOPT, "Use OCAL")
	field(OOPT, "When Non-zero")
	field(OCAL, "(A>>7)&1")
	field(OUT, "PLC:B34:PP02:REQ_SEG_BIT7 PP")
}

record(calcout, "PLC:B34:PP02:REQ_SEG_IN") {
	field(DESC, "Segment readback")
	field(INPA, "PLC:B34:PP02:SEG_BIT0 CP MS")
	field(INPB, "PLC:B34:PP02:SEG_BIT1 CP MS")
	field(INPC, "PLC:B34:PP02:SEG_BIT2 CP MS")
	field(INPD, "PLC:B34:PP02:SEG_BIT3 CP MS")
	field(INPE, "PLC:B34:PP02:SEG_BIT4 CP MS")
	field(INPF, "PLC:B34:PP02:SEG_BIT5 CP MS")
	field(INPG, "PLC:B34:PP02:SEG_BIT6 CP MS")
	field(INPH, "PLC:B34:PP02:SEG_BIT7 CP MS")
	field(CALC, "A+B*2+C*4+D*8+E*16+F*32+G*64+H*128")
	field(OUT, "PLC:B34:PP02:REQ_SEG PP MS")
	field(SDIS, "PLC:B34:PP02:REQ_SEG_OUT.PACT")
}

record(bi, "PLC:B34:PP02:LED_X1") {
	field(DESC, "PPS-X1_LED")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(PLC_RD, 24, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "MAJOR")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:B34:PP02:LED_X2") {
	field(DESC, "PPS-X2_LED")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(PLC_RD, 25, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "MAJOR")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:B34:PP02:PWLED") {
	field(DESC, "PLC-Power_LED_A")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(PLC_RD, 26, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "MAJOR")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:B34:PP02:RUNLED") {
	field(DESC, "PLC-Run_LED_A")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(PLC_RD, 27, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "MAJOR")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:B34:PP02:DIAGLED") {
	field(DESC, "PLC-Diag_LED_A")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(PLC_RD, 28, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:B34:PP02:FAULTLED") {
	field(DESC, "PLC-Fault_LED_A")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(PLC_RD, 29, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:B34:PP02:IFAULTLED") {
	field(DESC, "PLC-IFault_LED_A")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(PLC_RD, 30, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:B34:PP02:OFAULTLED") {
	field(DESC, "PLC-OFault_LED_A")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(PLC_RD, 31, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "MAJOR")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:B34:PP02:TABLE_BIT7") {
	field(DESC, "Table Read bit 7")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(PLC_RD, 32, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:B34:PP02:TABLE_BIT6") {
	field(DESC, "Table Read bit 6")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(PLC_RD, 33, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:B34:PP02:TABLE_BIT5") {
	field(DESC, "Table Read bit 5")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(PLC_RD, 34, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:B34:PP02:TABLE_BIT4") {
	field(DESC, "Table Read bit 4")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(PLC_RD, 35, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:B34:PP02:TABLE_BIT3") {
	field(DESC, "Table Read bit 3")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(PLC_RD, 36, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:B34:PP02:TABLE_BIT2") {
	field(DESC, "Table Read bit 2")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(PLC_RD, 37, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:B34:PP02:TABLE_BIT1") {
	field(DESC, "Table Read bit 1")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(PLC_RD, 38, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:B34:PP02:TABLE_BIT0") {
	field(DESC, "Table Read bit 0")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(PLC_RD, 39, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:B34:PP02:SEG_BIT7") {
	field(DESC, "Segment Read bit 7")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(PLC_RD, 40, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:B34:PP02:SEG_BIT6") {
	field(DESC, "Segment Read bit 6")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(PLC_RD, 41, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:B34:PP02:SEG_BIT5") {
	field(DESC, "Segment Read bit 5")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(PLC_RD, 42, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:B34:PP02:SEG_BIT4") {
	field(DESC, "Segment Read bit 4")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(PLC_RD, 43, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:B34:PP02:SEG_BIT3") {
	field(DESC, "Segment Read bit 3")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(PLC_RD, 44, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:B34:PP02:SEG_BIT2") {
	field(DESC, "Segment Read bit 2")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(PLC_RD, 45, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:B34:PP02:SEG_BIT1") {
	field(DESC, "Segment Read bit 1")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(PLC_RD, 46, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}

record(bi, "PLC:B34:PP02:SEG_BIT0") {
	field(DESC, "Segment Read bit 0")
	field(SCAN, "I/O Intr")
	field(DTYP, "asynUInt32Digital")
	field(INP,  "@asynMask(PLC_RD, 47, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
	field(ZSV,  "NO_ALARM")
	field(OSV,  "NO_ALARM")
  info(autosaveFields_pass0, "SEVR")
}


record(bo, "PLC:B34:PP02:REQ_TABLE_BIT7") {
	field(DESC, "Table Request bit 7")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(PLC_WT, 32, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:B34:PP02:REQ_TABLE_BIT6") {
	field(DESC, "Table Request bit 6")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(PLC_WT, 33, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:B34:PP02:REQ_TABLE_BIT5") {
	field(DESC, "Table Request bit 5")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(PLC_WT, 34, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:B34:PP02:REQ_TABLE_BIT4") {
	field(DESC, "Table Request bit 4")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(PLC_WT, 35, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:B34:PP02:REQ_TABLE_BIT3") {
	field(DESC, "Table Request bit 3")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(PLC_WT, 36, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:B34:PP02:REQ_TABLE_BIT2") {
	field(DESC, "Table Request bit 2")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(PLC_WT, 37, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:B34:PP02:REQ_TABLE_BIT1") {
	field(DESC, "Table Request bit 1")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(PLC_WT, 38, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:B34:PP02:REQ_TABLE_BIT0") {
	field(DESC, "Table Request bit 0")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(PLC_WT, 39, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:B34:PP02:REQ_SEG_BIT7") {
	field(DESC, "Segment Request bit 7")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(PLC_WT, 40, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:B34:PP02:REQ_SEG_BIT6") {
	field(DESC, "Segment Request bit 6")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(PLC_WT, 41, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:B34:PP02:REQ_SEG_BIT5") {
	field(DESC, "Segment Request bit 5")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(PLC_WT, 42, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:B34:PP02:REQ_SEG_BIT4") {
	field(DESC, "Segment Request bit 4")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(PLC_WT, 43, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:B34:PP02:REQ_SEG_BIT3") {
	field(DESC, "Segment Request bit 3")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(PLC_WT, 44, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:B34:PP02:REQ_SEG_BIT2") {
	field(DESC, "Segment Request bit 2")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(PLC_WT, 45, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:B34:PP02:REQ_SEG_BIT1") {
	field(DESC, "Segment Request bit 1")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(PLC_WT, 46, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}

record(bo, "PLC:B34:PP02:REQ_SEG_BIT0") {
	field(DESC, "Segment Request bit 0")
	field(DTYP, "asynUInt32Digital")
	field(OUT,  "@asynMask(PLC_WT, 47, 1, 1)")
	field(ZNAM, "Off")
	field(ONAM, "On")
}
#! Generated by VisualDCT v2.7.0
#! DBDSTART
#! DBDEND


record(longin, "PLC:B34:PP02:w0") {
  field(DESC, "Checksum")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_CHECKSUM, 0, 0xFFFF, 1)")
  field(ASG,  "Internal")
}

record(longin, "PLC:B34:PP02:w1") {
  field(DESC, "Checksum")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_CHECKSUM, 1, 0xFFFF, 1)")
  field(ASG,  "Internal")
}

record(longin, "PLC:B34:PP02:w2") {
  field(DESC, "Active Table and Segment")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_CHECKSUM, 2, 0xFFFF, 1)")
  field(FLNK, "PLC:B34:PP02:CHECKSUM_SDIS PP MS")
  field(ASG,  "Internal")
}

record(calc, "PLC:B34:PP02:CHECKSUM_SDIS") {
  field(INPA, "PLC:B34:PP02:w2 NPP MS")
  field(CALC, "A = 0X0101")
}

record(longin, "PLC:B34:PP02:w3") {
  field(DESC, "Checksum")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_CHECKSUM, 3, 0xFFFF, 1)")
  field(FLNK, "PLC:B34:PP02:CHECKSUM_SAFE PP MS")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:CHECKSUM_SAFE_calc") {
  field(INPA, "PLC:B34:PP02:w3 PP MS")
  field(INPB, "PLC:B34:PP02:CHECKSUM_SDIS PP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:CHECKSUM_SAFE PP MS")
  field(ASG,  "Internal")
}

record(longin, "PLC:B34:PP02:CHECKSUM_SAFE") {
  field(DESC, "Check Sum Safe")
  field(FLNK, "PLC:B34:PP02:CHECKSUM_SAFE_calc PP MS")
  info(autosaveFields_pass0, "VAL")
}

record(longin, "PLC:B34:PP02:w4") {
  field(DESC, "Checksum")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_CHECKSUM, 4, 0xFFFF, 1)")
  field(FLNK, "PLC:B34:PP02:PROJ_CHECKSUM_calc")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:PROJ_CHECKSUM_calc") {
  field(INPA, "PLC:B34:PP02:w4 NPP MS")
  field(INPB, "PLC:B34:PP02:CHECKSUM_SDIS NPP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:PROJ_CHECKSUM PP MS")
  field(ASG,  "Internal")
}

record(longin, "PLC:B34:PP02:PROJ_CHECKSUM") {
  field(DESC, "Total Project Check Sum")
  info(autosaveFields_pass0, "VAL")
}

record(longin, "PLC:B34:PP02:w5") {
  field(DESC, "Checksum")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_CHECKSUM, 5, 0xFFFF, 1)")
  field(FLNK, "PLC:B34:PP02:DAY_MONTH_calc")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:DAY_MONTH_calc") {
  field(INPA, "PLC:B34:PP02:w5 NPP MS")
  field(INPB, "PLC:B34:PP02:CHECKSUM_SDIS NPP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:DAY_MONTH PP MS")
  field(ASG,  "Internal")
}

record(longin, "PLC:B34:PP02:DAY_MONTH") {
  field(DESC, "Raw day and month")
  field(ASG,  "Internal")
}

record(calc, "PLC:B34:PP02:PROJ_MONTH") {
  field(DESC, "Project creation day")
  field(INPA, "PLC:B34:PP02:DAY_MONTH CP MS")
  field(CALC, "A & 0xFF")
  info(autosaveFields_pass0, "VAL")
}

record(calc, "PLC:B34:PP02:PROJ_DAY") {
  field(DESC, "Project creation month")
  field(INPA, "PLC:B34:PP02:DAY_MONTH CP MS")
  field(CALC, "A >> 8")
  info(autosaveFields_pass0, "VAL")
}

record(longin, "PLC:B34:PP02:w6") {
  field(DESC, "Checksum word 6")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_CHECKSUM, 6, 0xFFFF, 1)")
  field(FLNK, "PLC:B34:PP02:PROJ_YEAR_calc")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:PROJ_YEAR_calc") {
  field(INPA, "PLC:B34:PP02:w6 NPP MS")
  field(INPB, "PLC:B34:PP02:CHECKSUM_SDIS NPP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:PROJ_YEAR PP MS")
  field(ASG,  "Internal")
}

record(longin, "PLC:B34:PP02:PROJ_YEAR") {
  field(DESC, "Project creation year.")
  info(autosaveFields_pass0, "VAL")
}

record(longin, "PLC:B34:PP02:w7") {
  field(DESC, "Checksum word 7")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_CHECKSUM, 7, 0xFFFF, 1)")
  field(FLNK, "PLC:B34:PP02:OP_HRS_MSB_calc")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:OP_HRS_MSB_calc") {
  field(INPA, "PLC:B34:PP02:w7 NPP MS")
  field(INPB, "PLC:B34:PP02:CHECKSUM_SDIS NPP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:OP_HRS_MSB PP MS")
  field(ASG,  "Internal")
}

record(longin, "PLC:B34:PP02:OP_HRS_MSB") {
  field(DESC, "Operation hours upper byte")
  field(ASG,  "Internal")
}

record(longin, "PLC:B34:PP02:w8") {
  field(DESC, "Checksum word 8")
  field(SCAN, "I/O Intr")
  field(DTYP, "asynUInt32Digital")
  field(INP, "@asynMask(PLC_CHECKSUM, 8, 0xFFFF, 1)")
  field(FLNK, "PLC:B34:PP02:OP_HRS_LSB_calc")
  field(ASG,  "Internal")
}

record(calcout, "PLC:B34:PP02:OP_HRS_LSB_calc") {
  field(INPA, "PLC:B34:PP02:w8 NPP MS")
  field(INPB, "PLC:B34:PP02:CHECKSUM_SDIS NPP MS")
  field(CALC, "B")
  field(OCAL, "A")
  field(DOPT, "Use OCAL")
  field(OOPT, "When Non-zero")
  field(OUT, "PLC:B34:PP02:OP_HRS_LSB PP MS")
  field(ASG,  "Internal")
}

record(longin, "PLC:B34:PP02:OP_HRS_LSB") {
  field(DESC, "Operation hours lower byte")
  field(ASG,  "Internal")
}

record(calc, "PLC:B34:PP02:OP_HOURS") {
  field(INPA, "PLC:B34:PP02:OP_HRS_MSB CP MS")
  field(INPB, "PLC:B34:PP02:OP_HRS_LSB CP MS")
  field(CALC, "(A << 8)+(B>>8)")
  info(autosaveFields_pass0, "VAL")
}

record(mbbi, "PLC:B34:PP02:BASE_MODEL") {
  field(DTYP, "Raw Soft Channel")
  field(NOBT, "8")
  field(INP, "PLC:B34:PP02:OP_HRS_LSB CP MS")
  field(ZRVL, "0x00")
  field(ONVL, "0x02")
  field(TWVL, "0x04")
  field(THVL, "0x03")
  field(FRVL, "0x20")
  field(FVVL, "0x22")
  field(SXVL, "0x24")
  field(SVVL, "0x23")
  field(EIVL, "0x50")
  field(NIVL, "0x51")
  field(TEVL, "0x52")
  field(ZRST, "PNOZ m1p")
  field(ONST, "PNOZ m0p")
  field(TWST, "PNOZ m2p")
  field(THST, "PNOZ m3p")
  field(FRST, "PNOZ m1p ETH")
  field(FVST, "PNOZ m0p ETH")
  field(SXST, "PNOZ m2p ETH")
  field(SVST, "PNOZ m3p ETH")
  field(EIST, "PNOZ mm0p")
  field(NIST, "PNOZ mm0.1p")
  field(TEST, "PNOZ mm0.2p")
}

# End of file