record(asyn,"SIOC:B34:PP02:ASYN") { field(DTYP,"asynRecordDevice") field(PORT,"30BSY_B") field(ADDR,"0") field(OMAX,"0") field(IMAX,"0") } #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi7") { field(DESC, "Port 30BSY_RDA bit 7") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 7, 1, 1)") field(ZNAM, "Not_Enabled") field(ONAM, "Enabled") field(FLNK, "PPS:SYSE:1:HW_ENABLE_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi7Valid") { field(INPA, "PLC:BSY0:PP09:Bi7.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:HW_ENABLE_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:HW_ENABLE_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi7 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi7Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:HW_ENABLE_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:HW_ENABLE_A") { field(DESC, "HW Enabled A") field(ZNAM, "Not_Enabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb7",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb7") #! Field("PLC:BSY0:PP09:30BSY_RDAb7.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb7.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb7.FLNK","PPS:SYSE:1:HW_ENABLE_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb7.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb7.VAL") #! Record("PPS:SYSE:1:HW_ENABLE_A_calc",260,18,0,1,"PPS:SYSE:1:HW_ENABLE_A_calc") #! Field("PPS:SYSE:1:HW_ENABLE_A_calc.INPA",16777215,0,"PPS:SYSE:1:HW_ENABLE_A_calc.INPA") #! Link("PPS:SYSE:1:HW_ENABLE_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb7.VAL") #! Field("PPS:SYSE:1:HW_ENABLE_A_calc.INPB",16777215,1,"PPS:SYSE:1:HW_ENABLE_A_calc.INPB") #! Field("PPS:SYSE:1:HW_ENABLE_A_calc.OUT",16777215,1,"PPS:SYSE:1:HW_ENABLE_A_calc.OUT") #! Link("PPS:SYSE:1:HW_ENABLE_A_calc.OUT","PPS:SYSE:1:HW_ENABLE_A.VAL") #! Record("PPS:SYSE:1:HW_ENABLE_A",500,20,0,0,"PPS:SYSE:1:HW_ENABLE_A") #! Field("PPS:SYSE:1:HW_ENABLE_A.VAL",16777215,1,"PPS:SYSE:1:HW_ENABLE_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi6") { field(DESC, "Port 30BSY_RDA bit 6") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 6, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(FLNK, "PPS:SYSE:1:CROSS_INTLK_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi6Valid") { field(INPA, "PLC:BSY0:PP09:Bi6.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:CROSS_INTLK_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:CROSS_INTLK_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi6 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi6Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:CROSS_INTLK_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:CROSS_INTLK_A") { field(DESC, "Secure Complete from Other Chain") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb6",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb6") #! Field("PLC:BSY0:PP09:30BSY_RDAb6.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb6.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb6.FLNK","PPS:SYSE:1:CROSS_INTLK_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb6.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb6.VAL") #! Record("PPS:SYSE:1:CROSS_INTLK_A_calc",260,18,0,1,"PPS:SYSE:1:CROSS_INTLK_A_calc") #! Field("PPS:SYSE:1:CROSS_INTLK_A_calc.INPA",16777215,0,"PPS:SYSE:1:CROSS_INTLK_A_calc.INPA") #! Link("PPS:SYSE:1:CROSS_INTLK_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb6.VAL") #! Field("PPS:SYSE:1:CROSS_INTLK_A_calc.INPB",16777215,1,"PPS:SYSE:1:CROSS_INTLK_A_calc.INPB") #! Field("PPS:SYSE:1:CROSS_INTLK_A_calc.OUT",16777215,1,"PPS:SYSE:1:CROSS_INTLK_A_calc.OUT") #! Link("PPS:SYSE:1:CROSS_INTLK_A_calc.OUT","PPS:SYSE:1:CROSS_INTLK_A.VAL") #! Record("PPS:SYSE:1:CROSS_INTLK_A",500,20,0,0,"PPS:SYSE:1:CROSS_INTLK_A") #! Field("PPS:SYSE:1:CROSS_INTLK_A.VAL",16777215,1,"PPS:SYSE:1:CROSS_INTLK_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi5") { field(DESC, "Port 30BSY_RDA bit 5") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 5, 1, 1)") field(ZNAM, "Fault") field(ONAM, "Ok") field(FLNK, "PPS:SYSE:1:BLM_INP_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi5Valid") { field(INPA, "PLC:BSY0:PP09:Bi5.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:BLM_INP_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:BLM_INP_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi5 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi5Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:BLM_INP_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:BLM_INP_A") { field(DESC, "BCS_BLM_Input_A") field(ZNAM, "Fault") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb5",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb5") #! Field("PLC:BSY0:PP09:30BSY_RDAb5.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb5.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb5.FLNK","PPS:SYSE:1:BLM_INP_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb5.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb5.VAL") #! Record("PPS:SYSE:1:BLM_INP_A_calc",260,18,0,1,"PPS:SYSE:1:BLM_INP_A_calc") #! Field("PPS:SYSE:1:BLM_INP_A_calc.INPA",16777215,0,"PPS:SYSE:1:BLM_INP_A_calc.INPA") #! Link("PPS:SYSE:1:BLM_INP_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb5.VAL") #! Field("PPS:SYSE:1:BLM_INP_A_calc.INPB",16777215,1,"PPS:SYSE:1:BLM_INP_A_calc.INPB") #! Field("PPS:SYSE:1:BLM_INP_A_calc.OUT",16777215,1,"PPS:SYSE:1:BLM_INP_A_calc.OUT") #! Link("PPS:SYSE:1:BLM_INP_A_calc.OUT","PPS:SYSE:1:BLM_INP_A.VAL") #! Record("PPS:SYSE:1:BLM_INP_A",500,20,0,0,"PPS:SYSE:1:BLM_INP_A") #! Field("PPS:SYSE:1:BLM_INP_A.VAL",16777215,1,"PPS:SYSE:1:BLM_INP_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi3") { field(DESC, "Port 30BSY_RDA bit 3") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 3, 1, 1)") field(ZNAM, "Fault") field(ONAM, "Ok") field(FLNK, "PPS:LI30:1:SECURE_INP_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi3Valid") { field(INPA, "PLC:BSY0:PP09:Bi3.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:LI30:1:SECURE_INP_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:LI30:1:SECURE_INP_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi3 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi3Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:LI30:1:SECURE_INP_A PP MS") field(ASG, "Internal") } record(bi, "PPS:LI30:1:SECURE_INP_A") { field(DESC, "S30_Secure_Input_A") field(ZNAM, "Fault") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb3",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb3") #! Field("PLC:BSY0:PP09:30BSY_RDAb3.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb3.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb3.FLNK","PPS:LI30:1:SECURE_INP_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb3.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb3.VAL") #! Record("PPS:LI30:1:SECURE_INP_A_calc",260,18,0,1,"PPS:LI30:1:SECURE_INP_A_calc") #! Field("PPS:LI30:1:SECURE_INP_A_calc.INPA",16777215,0,"PPS:LI30:1:SECURE_INP_A_calc.INPA") #! Link("PPS:LI30:1:SECURE_INP_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb3.VAL") #! Field("PPS:LI30:1:SECURE_INP_A_calc.INPB",16777215,1,"PPS:LI30:1:SECURE_INP_A_calc.INPB") #! Field("PPS:LI30:1:SECURE_INP_A_calc.OUT",16777215,1,"PPS:LI30:1:SECURE_INP_A_calc.OUT") #! Link("PPS:LI30:1:SECURE_INP_A_calc.OUT","PPS:LI30:1:SECURE_INP_A.VAL") #! Record("PPS:LI30:1:SECURE_INP_A",500,20,0,0,"PPS:LI30:1:SECURE_INP_A") #! Field("PPS:LI30:1:SECURE_INP_A.VAL",16777215,1,"PPS:LI30:1:SECURE_INP_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi2") { field(DESC, "Port 30BSY_RDA bit 2") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 2, 1, 1)") field(ZNAM, "Fault") field(ONAM, "Ok") field(FLNK, "PPS:BSY0:1:SECURE_INP_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi2Valid") { field(INPA, "PLC:BSY0:PP09:Bi2.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:BSY0:1:SECURE_INP_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:BSY0:1:SECURE_INP_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi2 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi2Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:BSY0:1:SECURE_INP_A PP MS") field(ASG, "Internal") } record(bi, "PPS:BSY0:1:SECURE_INP_A") { field(DESC, "BSY_Secure_Input_A") field(ZNAM, "Fault") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb2",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb2") #! Field("PLC:BSY0:PP09:30BSY_RDAb2.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb2.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb2.FLNK","PPS:BSY0:1:SECURE_INP_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb2.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb2.VAL") #! Record("PPS:BSY0:1:SECURE_INP_A_calc",260,18,0,1,"PPS:BSY0:1:SECURE_INP_A_calc") #! Field("PPS:BSY0:1:SECURE_INP_A_calc.INPA",16777215,0,"PPS:BSY0:1:SECURE_INP_A_calc.INPA") #! Link("PPS:BSY0:1:SECURE_INP_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb2.VAL") #! Field("PPS:BSY0:1:SECURE_INP_A_calc.INPB",16777215,1,"PPS:BSY0:1:SECURE_INP_A_calc.INPB") #! Field("PPS:BSY0:1:SECURE_INP_A_calc.OUT",16777215,1,"PPS:BSY0:1:SECURE_INP_A_calc.OUT") #! Link("PPS:BSY0:1:SECURE_INP_A_calc.OUT","PPS:BSY0:1:SECURE_INP_A.VAL") #! Record("PPS:BSY0:1:SECURE_INP_A",500,20,0,0,"PPS:BSY0:1:SECURE_INP_A") #! Field("PPS:BSY0:1:SECURE_INP_A.VAL",16777215,1,"PPS:BSY0:1:SECURE_INP_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi1") { field(DESC, "Port 30BSY_RDA bit 1") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 1, 1, 1)") field(ZNAM, "Fault") field(ONAM, "Ok") field(FLNK, "PPS:ESA0:1:RADREADY_INP_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi1Valid") { field(INPA, "PLC:BSY0:PP09:Bi1.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:ESA0:1:RADREADY_INP_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:ESA0:1:RADREADY_INP_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi1 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi1Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:ESA0:1:RADREADY_INP_A PP MS") field(ASG, "Internal") } record(bi, "PPS:ESA0:1:RADREADY_INP_A") { field(DESC, "ESA_Rad_Ready_Input_A") field(ZNAM, "Fault") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb1",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb1") #! Field("PLC:BSY0:PP09:30BSY_RDAb1.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb1.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb1.FLNK","PPS:ESA0:1:RADREADY_INP_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb1.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb1.VAL") #! Record("PPS:ESA0:1:RADREADY_INP_A_calc",260,18,0,1,"PPS:ESA0:1:RADREADY_INP_A_calc") #! Field("PPS:ESA0:1:RADREADY_INP_A_calc.INPA",16777215,0,"PPS:ESA0:1:RADREADY_INP_A_calc.INPA") #! Link("PPS:ESA0:1:RADREADY_INP_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb1.VAL") #! Field("PPS:ESA0:1:RADREADY_INP_A_calc.INPB",16777215,1,"PPS:ESA0:1:RADREADY_INP_A_calc.INPB") #! Field("PPS:ESA0:1:RADREADY_INP_A_calc.OUT",16777215,1,"PPS:ESA0:1:RADREADY_INP_A_calc.OUT") #! Link("PPS:ESA0:1:RADREADY_INP_A_calc.OUT","PPS:ESA0:1:RADREADY_INP_A.VAL") #! Record("PPS:ESA0:1:RADREADY_INP_A",500,20,0,0,"PPS:ESA0:1:RADREADY_INP_A") #! Field("PPS:ESA0:1:RADREADY_INP_A.VAL",16777215,1,"PPS:ESA0:1:RADREADY_INP_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi0") { field(DESC, "Port 30BSY_RDA bit 0") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 0, 1, 1)") field(ZNAM, "Fault") field(ONAM, "Ok") field(FLNK, "BTM:BSY0:1:SUM_OK_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi0Valid") { field(INPA, "PLC:BSY0:PP09:Bi0.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "BTM:BSY0:1:SUM_OK_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "BTM:BSY0:1:SUM_OK_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi0 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi0Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "BTM:BSY0:1:SUM_OK_A PP MS") field(ASG, "Internal") } record(bi, "BTM:BSY0:1:SUM_OK_A") { field(DESC, "BTM_Sum_OK_Input_A") field(ZNAM, "Fault") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb0",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb0") #! Field("PLC:BSY0:PP09:30BSY_RDAb0.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb0.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb0.FLNK","BTM:BSY0:1:SUM_OK_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb0.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb0.VAL") #! Record("BTM:BSY0:1:SUM_OK_A_calc",260,18,0,1,"BTM:BSY0:1:SUM_OK_A_calc") #! Field("BTM:BSY0:1:SUM_OK_A_calc.INPA",16777215,0,"BTM:BSY0:1:SUM_OK_A_calc.INPA") #! Link("BTM:BSY0:1:SUM_OK_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb0.VAL") #! Field("BTM:BSY0:1:SUM_OK_A_calc.INPB",16777215,1,"BTM:BSY0:1:SUM_OK_A_calc.INPB") #! Field("BTM:BSY0:1:SUM_OK_A_calc.OUT",16777215,1,"BTM:BSY0:1:SUM_OK_A_calc.OUT") #! Link("BTM:BSY0:1:SUM_OK_A_calc.OUT","BTM:BSY0:1:SUM_OK_A.VAL") #! Record("BTM:BSY0:1:SUM_OK_A",500,20,0,0,"BTM:BSY0:1:SUM_OK_A") #! Field("BTM:BSY0:1:SUM_OK_A.VAL",16777215,1,"BTM:BSY0:1:SUM_OK_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi15") { field(DESC, "Port 30BSY_RDA bit 15") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 15, 1, 1)") field(ZNAM, "Fault") field(ONAM, "Ok") field(FLNK, "BSOC:SYSE:1:GROUPC_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi15Valid") { field(INPA, "PLC:BSY0:PP09:Bi15.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "BSOC:SYSE:1:GROUPC_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "BSOC:SYSE:1:GROUPC_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi15 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi15Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "BSOC:SYSE:1:GROUPC_A PP MS") field(ASG, "Internal") } record(bi, "BSOC:SYSE:1:GROUPC_A") { field(DESC, "BSOIC_GrpC_OK_Input_A") field(ZNAM, "Fault") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb15",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb15") #! Field("PLC:BSY0:PP09:30BSY_RDAb15.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb15.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb15.FLNK","BSOC:SYSE:1:GROUPC_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb15.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb15.VAL") #! Record("BSOC:SYSE:1:GROUPC_A_calc",260,18,0,1,"BSOC:SYSE:1:GROUPC_A_calc") #! Field("BSOC:SYSE:1:GROUPC_A_calc.INPA",16777215,0,"BSOC:SYSE:1:GROUPC_A_calc.INPA") #! Link("BSOC:SYSE:1:GROUPC_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb15.VAL") #! Field("BSOC:SYSE:1:GROUPC_A_calc.INPB",16777215,1,"BSOC:SYSE:1:GROUPC_A_calc.INPB") #! Field("BSOC:SYSE:1:GROUPC_A_calc.OUT",16777215,1,"BSOC:SYSE:1:GROUPC_A_calc.OUT") #! Link("BSOC:SYSE:1:GROUPC_A_calc.OUT","BSOC:SYSE:1:GROUPC_A.VAL") #! Record("BSOC:SYSE:1:GROUPC_A",500,20,0,0,"BSOC:SYSE:1:GROUPC_A") #! Field("BSOC:SYSE:1:GROUPC_A.VAL",16777215,1,"BSOC:SYSE:1:GROUPC_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi14") { field(DESC, "Port 30BSY_RDA bit 14") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 14, 1, 1)") field(ZNAM, "Fault") field(ONAM, "Ok") field(FLNK, "PPS:UND0:1:SECURE_INP_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi14Valid") { field(INPA, "PLC:BSY0:PP09:Bi14.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:UND0:1:SECURE_INP_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:UND0:1:SECURE_INP_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi14 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi14Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:UND0:1:SECURE_INP_A PP MS") field(ASG, "Internal") } record(bi, "PPS:UND0:1:SECURE_INP_A") { field(DESC, "LCLS_Secure_Input_A") field(ZNAM, "Fault") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb14",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb14") #! Field("PLC:BSY0:PP09:30BSY_RDAb14.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb14.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb14.FLNK","PPS:UND0:1:SECURE_INP_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb14.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb14.VAL") #! Record("PPS:UND0:1:SECURE_INP_A_calc",260,18,0,1,"PPS:UND0:1:SECURE_INP_A_calc") #! Field("PPS:UND0:1:SECURE_INP_A_calc.INPA",16777215,0,"PPS:UND0:1:SECURE_INP_A_calc.INPA") #! Link("PPS:UND0:1:SECURE_INP_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb14.VAL") #! Field("PPS:UND0:1:SECURE_INP_A_calc.INPB",16777215,1,"PPS:UND0:1:SECURE_INP_A_calc.INPB") #! Field("PPS:UND0:1:SECURE_INP_A_calc.OUT",16777215,1,"PPS:UND0:1:SECURE_INP_A_calc.OUT") #! Link("PPS:UND0:1:SECURE_INP_A_calc.OUT","PPS:UND0:1:SECURE_INP_A.VAL") #! Record("PPS:UND0:1:SECURE_INP_A",500,20,0,0,"PPS:UND0:1:SECURE_INP_A") #! Field("PPS:UND0:1:SECURE_INP_A.VAL",16777215,1,"PPS:UND0:1:SECURE_INP_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi13") { field(DESC, "Port 30BSY_RDA bit 13") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 13, 1, 1)") field(ZNAM, "Not_Enabled") field(ONAM, "Enabled") field(FLNK, "PPS:SYSE:1:30BSY:LOCAL_ENABLE_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi13Valid") { field(INPA, "PLC:BSY0:PP09:Bi13.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:LOCAL_ENABLE_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:LOCAL_ENABLE_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi13 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi13Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:LOCAL_ENABLE_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:LOCAL_ENABLE_A") { field(DESC, "Local_Beam_Enable_Keysw_A") field(ZNAM, "Not_Enabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb13",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb13") #! Field("PLC:BSY0:PP09:30BSY_RDAb13.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb13.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb13.FLNK","PPS:SYSE:1:30BSY:LOCAL_ENABLE_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb13.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb13.VAL") #! Record("PPS:SYSE:1:30BSY:LOCAL_ENABLE_A_calc",260,18,0,1,"PPS:SYSE:1:30BSY:LOCAL_ENABLE_A_calc") #! Field("PPS:SYSE:1:30BSY:LOCAL_ENABLE_A_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:LOCAL_ENABLE_A_calc.INPA") #! Link("PPS:SYSE:1:30BSY:LOCAL_ENABLE_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb13.VAL") #! Field("PPS:SYSE:1:30BSY:LOCAL_ENABLE_A_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:LOCAL_ENABLE_A_calc.INPB") #! Field("PPS:SYSE:1:30BSY:LOCAL_ENABLE_A_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:LOCAL_ENABLE_A_calc.OUT") #! Link("PPS:SYSE:1:30BSY:LOCAL_ENABLE_A_calc.OUT","PPS:SYSE:1:30BSY:LOCAL_ENABLE_A.VAL") #! Record("PPS:SYSE:1:30BSY:LOCAL_ENABLE_A",500,20,0,0,"PPS:SYSE:1:30BSY:LOCAL_ENABLE_A") #! Field("PPS:SYSE:1:30BSY:LOCAL_ENABLE_A.VAL",16777215,1,"PPS:SYSE:1:30BSY:LOCAL_ENABLE_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi12") { field(DESC, "Port 30BSY_RDA bit 12") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 12, 1, 1)") field(ZNAM, "Not_Lowered") field(ONAM, "Lowered") field(FLNK, "PPS:LTU0:1:BCS_TRP_LOW_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi12Valid") { field(INPA, "PLC:BSY0:PP09:Bi12.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:LTU0:1:BCS_TRP_LOW_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:LTU0:1:BCS_TRP_LOW_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi12 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi12Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:LTU0:1:BCS_TRP_LOW_A PP MS") field(ASG, "Internal") } record(bi, "PPS:LTU0:1:BCS_TRP_LOW_A") { field(DESC, "BCS_BTH_Trips_Low_Inp_A") field(ZNAM, "Not_Lowered") field(ONAM, "Lowered") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb12",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb12") #! Field("PLC:BSY0:PP09:30BSY_RDAb12.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb12.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb12.FLNK","PPS:LTU0:1:BCS_TRP_LOW_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb12.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb12.VAL") #! Record("PPS:LTU0:1:BCS_TRP_LOW_A_calc",260,18,0,1,"PPS:LTU0:1:BCS_TRP_LOW_A_calc") #! Field("PPS:LTU0:1:BCS_TRP_LOW_A_calc.INPA",16777215,0,"PPS:LTU0:1:BCS_TRP_LOW_A_calc.INPA") #! Link("PPS:LTU0:1:BCS_TRP_LOW_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb12.VAL") #! Field("PPS:LTU0:1:BCS_TRP_LOW_A_calc.INPB",16777215,1,"PPS:LTU0:1:BCS_TRP_LOW_A_calc.INPB") #! Field("PPS:LTU0:1:BCS_TRP_LOW_A_calc.OUT",16777215,1,"PPS:LTU0:1:BCS_TRP_LOW_A_calc.OUT") #! Link("PPS:LTU0:1:BCS_TRP_LOW_A_calc.OUT","PPS:LTU0:1:BCS_TRP_LOW_A.VAL") #! Record("PPS:LTU0:1:BCS_TRP_LOW_A",500,20,0,0,"PPS:LTU0:1:BCS_TRP_LOW_A") #! Field("PPS:LTU0:1:BCS_TRP_LOW_A.VAL",16777215,1,"PPS:LTU0:1:BCS_TRP_LOW_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi10") { field(DESC, "Port 30BSY_RDA bit 10") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 10, 1, 1)") field(ZNAM, "Not_Enabled") field(ONAM, "Enabled") field(FLNK, "PPS:SYSE:1:30BSY:ACR_ENABLE_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi10Valid") { field(INPA, "PLC:BSY0:PP09:Bi10.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:ACR_ENABLE_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:ACR_ENABLE_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi10 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi10Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:ACR_ENABLE_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:ACR_ENABLE_A") { field(DESC, "ACR_Beam_Enable_Keysw_A") field(ZNAM, "Not_Enabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb10",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb10") #! Field("PLC:BSY0:PP09:30BSY_RDAb10.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb10.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb10.FLNK","PPS:SYSE:1:30BSY:ACR_ENABLE_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb10.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb10.VAL") #! Record("PPS:SYSE:1:30BSY:ACR_ENABLE_A_calc",260,18,0,1,"PPS:SYSE:1:30BSY:ACR_ENABLE_A_calc") #! Field("PPS:SYSE:1:30BSY:ACR_ENABLE_A_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:ACR_ENABLE_A_calc.INPA") #! Link("PPS:SYSE:1:30BSY:ACR_ENABLE_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb10.VAL") #! Field("PPS:SYSE:1:30BSY:ACR_ENABLE_A_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:ACR_ENABLE_A_calc.INPB") #! Field("PPS:SYSE:1:30BSY:ACR_ENABLE_A_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:ACR_ENABLE_A_calc.OUT") #! Link("PPS:SYSE:1:30BSY:ACR_ENABLE_A_calc.OUT","PPS:SYSE:1:30BSY:ACR_ENABLE_A.VAL") #! Record("PPS:SYSE:1:30BSY:ACR_ENABLE_A",500,20,0,0,"PPS:SYSE:1:30BSY:ACR_ENABLE_A") #! Field("PPS:SYSE:1:30BSY:ACR_ENABLE_A.VAL",16777215,1,"PPS:SYSE:1:30BSY:ACR_ENABLE_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi9") { field(DESC, "Port 30BSY_RDA bit 9") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 9, 1, 1)") field(ZNAM, "NOT_OFF") field(ONAM, "OFF") field(FLNK, "PPS:LI28:1:HXR:KICKSEP_OFF_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi9Valid") { field(INPA, "PLC:BSY0:PP09:Bi9.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:LI28:1:HXR:KICKSEP_OFF_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:LI28:1:HXR:KICKSEP_OFF_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi9 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi9Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:LI28:1:HXR:KICKSEP_OFF_A PP MS") field(ASG, "Internal") } record(bi, "PPS:LI28:1:HXR:KICKSEP_OFF_A") { field(DESC, "HXR_KickSept_Off_Inp_A") field(ZNAM, "NOT_OFF") field(ONAM, "OFF") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb9",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb9") #! Field("PLC:BSY0:PP09:30BSY_RDAb9.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb9.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb9.FLNK","PPS:LI28:1:HXR:KICKSEP_OFF_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb9.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb9.VAL") #! Record("PPS:LI28:1:HXR:KICKSEP_OFF_A_calc",260,18,0,1,"PPS:LI28:1:HXR:KICKSEP_OFF_A_calc") #! Field("PPS:LI28:1:HXR:KICKSEP_OFF_A_calc.INPA",16777215,0,"PPS:LI28:1:HXR:KICKSEP_OFF_A_calc.INPA") #! Link("PPS:LI28:1:HXR:KICKSEP_OFF_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb9.VAL") #! Field("PPS:LI28:1:HXR:KICKSEP_OFF_A_calc.INPB",16777215,1,"PPS:LI28:1:HXR:KICKSEP_OFF_A_calc.INPB") #! Field("PPS:LI28:1:HXR:KICKSEP_OFF_A_calc.OUT",16777215,1,"PPS:LI28:1:HXR:KICKSEP_OFF_A_calc.OUT") #! Link("PPS:LI28:1:HXR:KICKSEP_OFF_A_calc.OUT","PPS:LI28:1:HXR:KICKSEP_OFF_A.VAL") #! Record("PPS:LI28:1:HXR:KICKSEP_OFF_A",500,20,0,0,"PPS:LI28:1:HXR:KICKSEP_OFF_A") #! Field("PPS:LI28:1:HXR:KICKSEP_OFF_A.VAL",16777215,1,"PPS:LI28:1:HXR:KICKSEP_OFF_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi8") { field(DESC, "Port 30BSY_RDA bit 8") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 8, 1, 1)") field(ZNAM, "NOT_OK") field(ONAM, "OK") field(FLNK, "PPS:LI28:1:HXR:KICK_COND_OK_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi8Valid") { field(INPA, "PLC:BSY0:PP09:Bi8.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:LI28:1:HXR:KICK_COND_OK_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:LI28:1:HXR:KICK_COND_OK_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi8 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi8Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:LI28:1:HXR:KICK_COND_OK_A PP MS") field(ASG, "Internal") } record(bi, "PPS:LI28:1:HXR:KICK_COND_OK_A") { field(DESC, "HXR_Kick_OK_A") field(ZNAM, "NOT_OK") field(ONAM, "OK") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb8",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb8") #! Field("PLC:BSY0:PP09:30BSY_RDAb8.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb8.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb8.FLNK","PPS:LI28:1:HXR:KICK_COND_OK_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb8.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb8.VAL") #! Record("PPS:LI28:1:HXR:KICK_COND_OK_A_calc",260,18,0,1,"PPS:LI28:1:HXR:KICK_COND_OK_A_calc") #! Field("PPS:LI28:1:HXR:KICK_COND_OK_A_calc.INPA",16777215,0,"PPS:LI28:1:HXR:KICK_COND_OK_A_calc.INPA") #! Link("PPS:LI28:1:HXR:KICK_COND_OK_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb8.VAL") #! Field("PPS:LI28:1:HXR:KICK_COND_OK_A_calc.INPB",16777215,1,"PPS:LI28:1:HXR:KICK_COND_OK_A_calc.INPB") #! Field("PPS:LI28:1:HXR:KICK_COND_OK_A_calc.OUT",16777215,1,"PPS:LI28:1:HXR:KICK_COND_OK_A_calc.OUT") #! Link("PPS:LI28:1:HXR:KICK_COND_OK_A_calc.OUT","PPS:LI28:1:HXR:KICK_COND_OK_A.VAL") #! Record("PPS:LI28:1:HXR:KICK_COND_OK_A",500,20,0,0,"PPS:LI28:1:HXR:KICK_COND_OK_A") #! Field("PPS:LI28:1:HXR:KICK_COND_OK_A.VAL",16777215,1,"PPS:LI28:1:HXR:KICK_COND_OK_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi23") { field(DESC, "Port 30BSY_RDA bit 23") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 23, 1, 1)") field(ZNAM, "NOT_OFF") field(ONAM, "OFF") field(FLNK, "PPS:LI30:1:SXR:KICKSEP_OFF_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi23Valid") { field(INPA, "PLC:BSY0:PP09:Bi23.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:LI30:1:SXR:KICKSEP_OFF_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:LI30:1:SXR:KICKSEP_OFF_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi23 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi23Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:LI30:1:SXR:KICKSEP_OFF_A PP MS") field(ASG, "Internal") } record(bi, "PPS:LI30:1:SXR:KICKSEP_OFF_A") { field(DESC, "SXR_KickSept_Off_Inp_A") field(ZNAM, "NOT_OFF") field(ONAM, "OFF") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb23",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb23") #! Field("PLC:BSY0:PP09:30BSY_RDAb23.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb23.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb23.FLNK","PPS:LI30:1:SXR:KICKSEP_OFF_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb23.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb23.VAL") #! Record("PPS:LI30:1:SXR:KICKSEP_OFF_A_calc",260,18,0,1,"PPS:LI30:1:SXR:KICKSEP_OFF_A_calc") #! Field("PPS:LI30:1:SXR:KICKSEP_OFF_A_calc.INPA",16777215,0,"PPS:LI30:1:SXR:KICKSEP_OFF_A_calc.INPA") #! Link("PPS:LI30:1:SXR:KICKSEP_OFF_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb23.VAL") #! Field("PPS:LI30:1:SXR:KICKSEP_OFF_A_calc.INPB",16777215,1,"PPS:LI30:1:SXR:KICKSEP_OFF_A_calc.INPB") #! Field("PPS:LI30:1:SXR:KICKSEP_OFF_A_calc.OUT",16777215,1,"PPS:LI30:1:SXR:KICKSEP_OFF_A_calc.OUT") #! Link("PPS:LI30:1:SXR:KICKSEP_OFF_A_calc.OUT","PPS:LI30:1:SXR:KICKSEP_OFF_A.VAL") #! Record("PPS:LI30:1:SXR:KICKSEP_OFF_A",500,20,0,0,"PPS:LI30:1:SXR:KICKSEP_OFF_A") #! Field("PPS:LI30:1:SXR:KICKSEP_OFF_A.VAL",16777215,1,"PPS:LI30:1:SXR:KICKSEP_OFF_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi22") { field(DESC, "Port 30BSY_RDA bit 22") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 22, 1, 1)") field(ZNAM, "NOT_OK") field(ONAM, "OK") field(FLNK, "PPS:LI30:1:SXR:KICK_COND_OK_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi22Valid") { field(INPA, "PLC:BSY0:PP09:Bi22.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:LI30:1:SXR:KICK_COND_OK_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:LI30:1:SXR:KICK_COND_OK_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi22 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi22Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:LI30:1:SXR:KICK_COND_OK_A PP MS") field(ASG, "Internal") } record(bi, "PPS:LI30:1:SXR:KICK_COND_OK_A") { field(DESC, "SXR_Kick_OK_A") field(ZNAM, "NOT_OK") field(ONAM, "OK") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb22",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb22") #! Field("PLC:BSY0:PP09:30BSY_RDAb22.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb22.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb22.FLNK","PPS:LI30:1:SXR:KICK_COND_OK_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb22.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb22.VAL") #! Record("PPS:LI30:1:SXR:KICK_COND_OK_A_calc",260,18,0,1,"PPS:LI30:1:SXR:KICK_COND_OK_A_calc") #! Field("PPS:LI30:1:SXR:KICK_COND_OK_A_calc.INPA",16777215,0,"PPS:LI30:1:SXR:KICK_COND_OK_A_calc.INPA") #! Link("PPS:LI30:1:SXR:KICK_COND_OK_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb22.VAL") #! Field("PPS:LI30:1:SXR:KICK_COND_OK_A_calc.INPB",16777215,1,"PPS:LI30:1:SXR:KICK_COND_OK_A_calc.INPB") #! Field("PPS:LI30:1:SXR:KICK_COND_OK_A_calc.OUT",16777215,1,"PPS:LI30:1:SXR:KICK_COND_OK_A_calc.OUT") #! Link("PPS:LI30:1:SXR:KICK_COND_OK_A_calc.OUT","PPS:LI30:1:SXR:KICK_COND_OK_A.VAL") #! Record("PPS:LI30:1:SXR:KICK_COND_OK_A",500,20,0,0,"PPS:LI30:1:SXR:KICK_COND_OK_A") #! Field("PPS:LI30:1:SXR:KICK_COND_OK_A.VAL",16777215,1,"PPS:LI30:1:SXR:KICK_COND_OK_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi21") { field(DESC, "Port 30BSY_RDA bit 21") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 21, 1, 1)") field(ZNAM, "NOT_IN") field(ONAM, "IN") field(FLNK, "STPR:BSYH:1:30BSY:STD2_IN_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi21Valid") { field(INPA, "PLC:BSY0:PP09:Bi21.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "STPR:BSYH:1:30BSY:STD2_IN_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "STPR:BSYH:1:30BSY:STD2_IN_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi21 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi21Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "STPR:BSYH:1:30BSY:STD2_IN_A PP MS") field(ASG, "Internal") } record(bi, "STPR:BSYH:1:30BSY:STD2_IN_A") { field(DESC, "STD2_Set_In_30BSY_Inp_A") field(ZNAM, "NOT_IN") field(ONAM, "IN") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb21",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb21") #! Field("PLC:BSY0:PP09:30BSY_RDAb21.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb21.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb21.FLNK","STPR:BSYH:1:30BSY:STD2_IN_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb21.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb21.VAL") #! Record("STPR:BSYH:1:30BSY:STD2_IN_A_calc",260,18,0,1,"STPR:BSYH:1:30BSY:STD2_IN_A_calc") #! Field("STPR:BSYH:1:30BSY:STD2_IN_A_calc.INPA",16777215,0,"STPR:BSYH:1:30BSY:STD2_IN_A_calc.INPA") #! Link("STPR:BSYH:1:30BSY:STD2_IN_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb21.VAL") #! Field("STPR:BSYH:1:30BSY:STD2_IN_A_calc.INPB",16777215,1,"STPR:BSYH:1:30BSY:STD2_IN_A_calc.INPB") #! Field("STPR:BSYH:1:30BSY:STD2_IN_A_calc.OUT",16777215,1,"STPR:BSYH:1:30BSY:STD2_IN_A_calc.OUT") #! Link("STPR:BSYH:1:30BSY:STD2_IN_A_calc.OUT","STPR:BSYH:1:30BSY:STD2_IN_A.VAL") #! Record("STPR:BSYH:1:30BSY:STD2_IN_A",500,20,0,0,"STPR:BSYH:1:30BSY:STD2_IN_A") #! Field("STPR:BSYH:1:30BSY:STD2_IN_A.VAL",16777215,1,"STPR:BSYH:1:30BSY:STD2_IN_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi20") { field(DESC, "Port 30BSY_RDA bit 20") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 20, 1, 1)") field(ZNAM, "NOT_OUT") field(ONAM, "OUT") field(FLNK, "STPR:BSYH:1:30BSY:STD2_OUT_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi20Valid") { field(INPA, "PLC:BSY0:PP09:Bi20.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "STPR:BSYH:1:30BSY:STD2_OUT_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "STPR:BSYH:1:30BSY:STD2_OUT_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi20 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi20Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "STPR:BSYH:1:30BSY:STD2_OUT_A PP MS") field(ASG, "Internal") } record(bi, "STPR:BSYH:1:30BSY:STD2_OUT_A") { field(DESC, "STD2_Set_Out_30BSY_Inp_A") field(ZNAM, "NOT_OUT") field(ONAM, "OUT") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb20",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb20") #! Field("PLC:BSY0:PP09:30BSY_RDAb20.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb20.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb20.FLNK","STPR:BSYH:1:30BSY:STD2_OUT_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb20.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb20.VAL") #! Record("STPR:BSYH:1:30BSY:STD2_OUT_A_calc",260,18,0,1,"STPR:BSYH:1:30BSY:STD2_OUT_A_calc") #! Field("STPR:BSYH:1:30BSY:STD2_OUT_A_calc.INPA",16777215,0,"STPR:BSYH:1:30BSY:STD2_OUT_A_calc.INPA") #! Link("STPR:BSYH:1:30BSY:STD2_OUT_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb20.VAL") #! Field("STPR:BSYH:1:30BSY:STD2_OUT_A_calc.INPB",16777215,1,"STPR:BSYH:1:30BSY:STD2_OUT_A_calc.INPB") #! Field("STPR:BSYH:1:30BSY:STD2_OUT_A_calc.OUT",16777215,1,"STPR:BSYH:1:30BSY:STD2_OUT_A_calc.OUT") #! Link("STPR:BSYH:1:30BSY:STD2_OUT_A_calc.OUT","STPR:BSYH:1:30BSY:STD2_OUT_A.VAL") #! Record("STPR:BSYH:1:30BSY:STD2_OUT_A",500,20,0,0,"STPR:BSYH:1:30BSY:STD2_OUT_A") #! Field("STPR:BSYH:1:30BSY:STD2_OUT_A.VAL",16777215,1,"STPR:BSYH:1:30BSY:STD2_OUT_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi19") { field(DESC, "Port 30BSY_RDA bit 19") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 19, 1, 1)") field(ZNAM, "NOT_IN") field(ONAM, "IN") field(FLNK, "STPR:BSYS:1:ST34_IN_SUM_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi19Valid") { field(INPA, "PLC:BSY0:PP09:Bi19.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "STPR:BSYS:1:ST34_IN_SUM_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "STPR:BSYS:1:ST34_IN_SUM_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi19 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi19Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "STPR:BSYS:1:ST34_IN_SUM_A PP MS") field(ASG, "Internal") } record(bi, "STPR:BSYS:1:ST34_IN_SUM_A") { field(DESC, "ST34_Set_In_Inp_A") field(ZNAM, "NOT_IN") field(ONAM, "IN") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb19",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb19") #! Field("PLC:BSY0:PP09:30BSY_RDAb19.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb19.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb19.FLNK","STPR:BSYS:1:ST34_IN_SUM_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb19.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb19.VAL") #! Record("STPR:BSYS:1:ST34_IN_SUM_A_calc",260,18,0,1,"STPR:BSYS:1:ST34_IN_SUM_A_calc") #! Field("STPR:BSYS:1:ST34_IN_SUM_A_calc.INPA",16777215,0,"STPR:BSYS:1:ST34_IN_SUM_A_calc.INPA") #! Link("STPR:BSYS:1:ST34_IN_SUM_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb19.VAL") #! Field("STPR:BSYS:1:ST34_IN_SUM_A_calc.INPB",16777215,1,"STPR:BSYS:1:ST34_IN_SUM_A_calc.INPB") #! Field("STPR:BSYS:1:ST34_IN_SUM_A_calc.OUT",16777215,1,"STPR:BSYS:1:ST34_IN_SUM_A_calc.OUT") #! Link("STPR:BSYS:1:ST34_IN_SUM_A_calc.OUT","STPR:BSYS:1:ST34_IN_SUM_A.VAL") #! Record("STPR:BSYS:1:ST34_IN_SUM_A",500,20,0,0,"STPR:BSYS:1:ST34_IN_SUM_A") #! Field("STPR:BSYS:1:ST34_IN_SUM_A.VAL",16777215,1,"STPR:BSYS:1:ST34_IN_SUM_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi18") { field(DESC, "Port 30BSY_RDA bit 18") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 18, 1, 1)") field(ZNAM, "NOT_OUT") field(ONAM, "OUT") field(FLNK, "STPR:BSYS:1:ST34_OUT_SUM_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi18Valid") { field(INPA, "PLC:BSY0:PP09:Bi18.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "STPR:BSYS:1:ST34_OUT_SUM_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "STPR:BSYS:1:ST34_OUT_SUM_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi18 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi18Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "STPR:BSYS:1:ST34_OUT_SUM_A PP MS") field(ASG, "Internal") } record(bi, "STPR:BSYS:1:ST34_OUT_SUM_A") { field(DESC, "ST34_Set_Out_Inp_A") field(ZNAM, "NOT_OUT") field(ONAM, "OUT") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb18",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb18") #! Field("PLC:BSY0:PP09:30BSY_RDAb18.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb18.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb18.FLNK","STPR:BSYS:1:ST34_OUT_SUM_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb18.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb18.VAL") #! Record("STPR:BSYS:1:ST34_OUT_SUM_A_calc",260,18,0,1,"STPR:BSYS:1:ST34_OUT_SUM_A_calc") #! Field("STPR:BSYS:1:ST34_OUT_SUM_A_calc.INPA",16777215,0,"STPR:BSYS:1:ST34_OUT_SUM_A_calc.INPA") #! Link("STPR:BSYS:1:ST34_OUT_SUM_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb18.VAL") #! Field("STPR:BSYS:1:ST34_OUT_SUM_A_calc.INPB",16777215,1,"STPR:BSYS:1:ST34_OUT_SUM_A_calc.INPB") #! Field("STPR:BSYS:1:ST34_OUT_SUM_A_calc.OUT",16777215,1,"STPR:BSYS:1:ST34_OUT_SUM_A_calc.OUT") #! Link("STPR:BSYS:1:ST34_OUT_SUM_A_calc.OUT","STPR:BSYS:1:ST34_OUT_SUM_A.VAL") #! Record("STPR:BSYS:1:ST34_OUT_SUM_A",500,20,0,0,"STPR:BSYS:1:ST34_OUT_SUM_A") #! Field("STPR:BSYS:1:ST34_OUT_SUM_A.VAL",16777215,1,"STPR:BSYS:1:ST34_OUT_SUM_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi17") { field(DESC, "Port 30BSY_RDA bit 17") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 17, 1, 1)") field(ZNAM, "NOT_IN") field(ONAM, "IN") field(FLNK, "STPR:CLTS:585:IN_INP_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi17Valid") { field(INPA, "PLC:BSY0:PP09:Bi17.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "STPR:CLTS:585:IN_INP_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "STPR:CLTS:585:IN_INP_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi17 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi17Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "STPR:CLTS:585:IN_INP_A PP MS") field(ASG, "Internal") } record(bi, "STPR:CLTS:585:IN_INP_A") { field(DESC, "STCLTS_In_A") field(ZNAM, "NOT_IN") field(ONAM, "IN") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb17",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb17") #! Field("PLC:BSY0:PP09:30BSY_RDAb17.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb17.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb17.FLNK","STPR:CLTS:585:IN_INP_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb17.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb17.VAL") #! Record("STPR:CLTS:585:IN_INP_A_calc",260,18,0,1,"STPR:CLTS:585:IN_INP_A_calc") #! Field("STPR:CLTS:585:IN_INP_A_calc.INPA",16777215,0,"STPR:CLTS:585:IN_INP_A_calc.INPA") #! Link("STPR:CLTS:585:IN_INP_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb17.VAL") #! Field("STPR:CLTS:585:IN_INP_A_calc.INPB",16777215,1,"STPR:CLTS:585:IN_INP_A_calc.INPB") #! Field("STPR:CLTS:585:IN_INP_A_calc.OUT",16777215,1,"STPR:CLTS:585:IN_INP_A_calc.OUT") #! Link("STPR:CLTS:585:IN_INP_A_calc.OUT","STPR:CLTS:585:IN_INP_A.VAL") #! Record("STPR:CLTS:585:IN_INP_A",500,20,0,0,"STPR:CLTS:585:IN_INP_A") #! Field("STPR:CLTS:585:IN_INP_A.VAL",16777215,1,"STPR:CLTS:585:IN_INP_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi16") { field(DESC, "Port 30BSY_RDA bit 16") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 16, 1, 1)") field(ZNAM, "NOT_OUT") field(ONAM, "OUT") field(FLNK, "STPR:CLTS:585:OUT_INP_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi16Valid") { field(INPA, "PLC:BSY0:PP09:Bi16.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "STPR:CLTS:585:OUT_INP_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "STPR:CLTS:585:OUT_INP_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi16 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi16Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "STPR:CLTS:585:OUT_INP_A PP MS") field(ASG, "Internal") } record(bi, "STPR:CLTS:585:OUT_INP_A") { field(DESC, "STCLTS_Out_A") field(ZNAM, "NOT_OUT") field(ONAM, "OUT") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb16",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb16") #! Field("PLC:BSY0:PP09:30BSY_RDAb16.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb16.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb16.FLNK","STPR:CLTS:585:OUT_INP_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb16.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb16.VAL") #! Record("STPR:CLTS:585:OUT_INP_A_calc",260,18,0,1,"STPR:CLTS:585:OUT_INP_A_calc") #! Field("STPR:CLTS:585:OUT_INP_A_calc.INPA",16777215,0,"STPR:CLTS:585:OUT_INP_A_calc.INPA") #! Link("STPR:CLTS:585:OUT_INP_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb16.VAL") #! Field("STPR:CLTS:585:OUT_INP_A_calc.INPB",16777215,1,"STPR:CLTS:585:OUT_INP_A_calc.INPB") #! Field("STPR:CLTS:585:OUT_INP_A_calc.OUT",16777215,1,"STPR:CLTS:585:OUT_INP_A_calc.OUT") #! Link("STPR:CLTS:585:OUT_INP_A_calc.OUT","STPR:CLTS:585:OUT_INP_A.VAL") #! Record("STPR:CLTS:585:OUT_INP_A",500,20,0,0,"STPR:CLTS:585:OUT_INP_A") #! Field("STPR:CLTS:585:OUT_INP_A.VAL",16777215,1,"STPR:CLTS:585:OUT_INP_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi95") { field(DESC, "Port 30BSY_RDA bit 95") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 95, 1, 1)") field(ZNAM, "NOT_OFF") field(ONAM, "OFF") field(FLNK, "PPS:CLTS:1:KICK_OFF_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi95Valid") { field(INPA, "PLC:BSY0:PP09:Bi95.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:CLTS:1:KICK_OFF_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:CLTS:1:KICK_OFF_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi95 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi95Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:CLTS:1:KICK_OFF_A PP MS") field(ASG, "Internal") } record(bi, "PPS:CLTS:1:KICK_OFF_A") { field(DESC, "CLTS_Kicker_OFF_A") field(ZNAM, "NOT_OFF") field(ONAM, "OFF") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb95",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb95") #! Field("PLC:BSY0:PP09:30BSY_RDAb95.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb95.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb95.FLNK","PPS:CLTS:1:KICK_OFF_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb95.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb95.VAL") #! Record("PPS:CLTS:1:KICK_OFF_A_calc",260,18,0,1,"PPS:CLTS:1:KICK_OFF_A_calc") #! Field("PPS:CLTS:1:KICK_OFF_A_calc.INPA",16777215,0,"PPS:CLTS:1:KICK_OFF_A_calc.INPA") #! Link("PPS:CLTS:1:KICK_OFF_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb95.VAL") #! Field("PPS:CLTS:1:KICK_OFF_A_calc.INPB",16777215,1,"PPS:CLTS:1:KICK_OFF_A_calc.INPB") #! Field("PPS:CLTS:1:KICK_OFF_A_calc.OUT",16777215,1,"PPS:CLTS:1:KICK_OFF_A_calc.OUT") #! Link("PPS:CLTS:1:KICK_OFF_A_calc.OUT","PPS:CLTS:1:KICK_OFF_A.VAL") #! Record("PPS:CLTS:1:KICK_OFF_A",500,20,0,0,"PPS:CLTS:1:KICK_OFF_A") #! Field("PPS:CLTS:1:KICK_OFF_A.VAL",16777215,1,"PPS:CLTS:1:KICK_OFF_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi94") { field(DESC, "Port 30BSY_RDA bit 94") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 94, 1, 1)") field(ZNAM, "NOT_OFF") field(ONAM, "OFF") field(FLNK, "PPS:CLTS:1:DCBEND_OFF_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi94Valid") { field(INPA, "PLC:BSY0:PP09:Bi94.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:CLTS:1:DCBEND_OFF_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:CLTS:1:DCBEND_OFF_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi94 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi94Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:CLTS:1:DCBEND_OFF_A PP MS") field(ASG, "Internal") } record(bi, "PPS:CLTS:1:DCBEND_OFF_A") { field(DESC, "CLTS_DC_Bend_OFF_A") field(ZNAM, "NOT_OFF") field(ONAM, "OFF") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb94",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb94") #! Field("PLC:BSY0:PP09:30BSY_RDAb94.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb94.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb94.FLNK","PPS:CLTS:1:DCBEND_OFF_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb94.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb94.VAL") #! Record("PPS:CLTS:1:DCBEND_OFF_A_calc",260,18,0,1,"PPS:CLTS:1:DCBEND_OFF_A_calc") #! Field("PPS:CLTS:1:DCBEND_OFF_A_calc.INPA",16777215,0,"PPS:CLTS:1:DCBEND_OFF_A_calc.INPA") #! Link("PPS:CLTS:1:DCBEND_OFF_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb94.VAL") #! Field("PPS:CLTS:1:DCBEND_OFF_A_calc.INPB",16777215,1,"PPS:CLTS:1:DCBEND_OFF_A_calc.INPB") #! Field("PPS:CLTS:1:DCBEND_OFF_A_calc.OUT",16777215,1,"PPS:CLTS:1:DCBEND_OFF_A_calc.OUT") #! Link("PPS:CLTS:1:DCBEND_OFF_A_calc.OUT","PPS:CLTS:1:DCBEND_OFF_A.VAL") #! Record("PPS:CLTS:1:DCBEND_OFF_A",500,20,0,0,"PPS:CLTS:1:DCBEND_OFF_A") #! Field("PPS:CLTS:1:DCBEND_OFF_A.VAL",16777215,1,"PPS:CLTS:1:DCBEND_OFF_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi92") { field(DESC, "Port 30BSY_RDA bit 92") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 92, 1, 1)") field(ZNAM, "NOT_OFF") field(ONAM, "OFF") field(FLNK, "PPS:BSYS:1:MERGE_OFF_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi92Valid") { field(INPA, "PLC:BSY0:PP09:Bi92.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:BSYS:1:MERGE_OFF_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:BSYS:1:MERGE_OFF_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi92 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi92Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:BSYS:1:MERGE_OFF_A PP MS") field(ASG, "Internal") } record(bi, "PPS:BSYS:1:MERGE_OFF_A") { field(DESC, "SXR_Merge_Dipole_OFF_A") field(ZNAM, "NOT_OFF") field(ONAM, "OFF") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb92",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb92") #! Field("PLC:BSY0:PP09:30BSY_RDAb92.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb92.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb92.FLNK","PPS:BSYS:1:MERGE_OFF_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb92.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb92.VAL") #! Record("PPS:BSYS:1:MERGE_OFF_A_calc",260,18,0,1,"PPS:BSYS:1:MERGE_OFF_A_calc") #! Field("PPS:BSYS:1:MERGE_OFF_A_calc.INPA",16777215,0,"PPS:BSYS:1:MERGE_OFF_A_calc.INPA") #! Link("PPS:BSYS:1:MERGE_OFF_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb92.VAL") #! Field("PPS:BSYS:1:MERGE_OFF_A_calc.INPB",16777215,1,"PPS:BSYS:1:MERGE_OFF_A_calc.INPB") #! Field("PPS:BSYS:1:MERGE_OFF_A_calc.OUT",16777215,1,"PPS:BSYS:1:MERGE_OFF_A_calc.OUT") #! Link("PPS:BSYS:1:MERGE_OFF_A_calc.OUT","PPS:BSYS:1:MERGE_OFF_A.VAL") #! Record("PPS:BSYS:1:MERGE_OFF_A",500,20,0,0,"PPS:BSYS:1:MERGE_OFF_A") #! Field("PPS:BSYS:1:MERGE_OFF_A.VAL",16777215,1,"PPS:BSYS:1:MERGE_OFF_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi90") { field(DESC, "Port 30BSY_RDA bit 90") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 90, 1, 1)") field(ZNAM, "OFF") field(ONAM, "ON") field(FLNK, "PPS:CLTS:1:DCBEND_ON_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi90Valid") { field(INPA, "PLC:BSY0:PP09:Bi90.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:CLTS:1:DCBEND_ON_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:CLTS:1:DCBEND_ON_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi90 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi90Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:CLTS:1:DCBEND_ON_A PP MS") field(ASG, "Internal") } record(bi, "PPS:CLTS:1:DCBEND_ON_A") { field(DESC, "CLTS_DC_Bend_On_A") field(ZNAM, "OFF") field(ONAM, "ON") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb90",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb90") #! Field("PLC:BSY0:PP09:30BSY_RDAb90.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb90.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb90.FLNK","PPS:CLTS:1:DCBEND_ON_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb90.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb90.VAL") #! Record("PPS:CLTS:1:DCBEND_ON_A_calc",260,18,0,1,"PPS:CLTS:1:DCBEND_ON_A_calc") #! Field("PPS:CLTS:1:DCBEND_ON_A_calc.INPA",16777215,0,"PPS:CLTS:1:DCBEND_ON_A_calc.INPA") #! Link("PPS:CLTS:1:DCBEND_ON_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb90.VAL") #! Field("PPS:CLTS:1:DCBEND_ON_A_calc.INPB",16777215,1,"PPS:CLTS:1:DCBEND_ON_A_calc.INPB") #! Field("PPS:CLTS:1:DCBEND_ON_A_calc.OUT",16777215,1,"PPS:CLTS:1:DCBEND_ON_A_calc.OUT") #! Link("PPS:CLTS:1:DCBEND_ON_A_calc.OUT","PPS:CLTS:1:DCBEND_ON_A.VAL") #! Record("PPS:CLTS:1:DCBEND_ON_A",500,20,0,0,"PPS:CLTS:1:DCBEND_ON_A") #! Field("PPS:CLTS:1:DCBEND_ON_A.VAL",16777215,1,"PPS:CLTS:1:DCBEND_ON_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi89") { field(DESC, "Port 30BSY_RDA bit 89") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 89, 1, 1)") field(ZNAM, "OFF") field(ONAM, "ON") field(FLNK, "PPS:CLTS:1:SEP_ON_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi89Valid") { field(INPA, "PLC:BSY0:PP09:Bi89.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:CLTS:1:SEP_ON_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:CLTS:1:SEP_ON_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi89 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi89Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:CLTS:1:SEP_ON_A PP MS") field(ASG, "Internal") } record(bi, "PPS:CLTS:1:SEP_ON_A") { field(DESC, "CLTS_Septum_On_A") field(ZNAM, "OFF") field(ONAM, "ON") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb89",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb89") #! Field("PLC:BSY0:PP09:30BSY_RDAb89.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb89.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb89.FLNK","PPS:CLTS:1:SEP_ON_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb89.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb89.VAL") #! Record("PPS:CLTS:1:SEP_ON_A_calc",260,18,0,1,"PPS:CLTS:1:SEP_ON_A_calc") #! Field("PPS:CLTS:1:SEP_ON_A_calc.INPA",16777215,0,"PPS:CLTS:1:SEP_ON_A_calc.INPA") #! Link("PPS:CLTS:1:SEP_ON_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb89.VAL") #! Field("PPS:CLTS:1:SEP_ON_A_calc.INPB",16777215,1,"PPS:CLTS:1:SEP_ON_A_calc.INPB") #! Field("PPS:CLTS:1:SEP_ON_A_calc.OUT",16777215,1,"PPS:CLTS:1:SEP_ON_A_calc.OUT") #! Link("PPS:CLTS:1:SEP_ON_A_calc.OUT","PPS:CLTS:1:SEP_ON_A.VAL") #! Record("PPS:CLTS:1:SEP_ON_A",500,20,0,0,"PPS:CLTS:1:SEP_ON_A") #! Field("PPS:CLTS:1:SEP_ON_A.VAL",16777215,1,"PPS:CLTS:1:SEP_ON_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi88") { field(DESC, "Port 30BSY_RDA bit 88") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 88, 1, 1)") field(ZNAM, "OFF") field(ONAM, "ON") field(FLNK, "PPS:BSYS:1:MERGE_ON_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi88Valid") { field(INPA, "PLC:BSY0:PP09:Bi88.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:BSYS:1:MERGE_ON_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:BSYS:1:MERGE_ON_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi88 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi88Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:BSYS:1:MERGE_ON_A PP MS") field(ASG, "Internal") } record(bi, "PPS:BSYS:1:MERGE_ON_A") { field(DESC, "SXR_Merge_Dipole_On_A") field(ZNAM, "OFF") field(ONAM, "ON") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb88",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb88") #! Field("PLC:BSY0:PP09:30BSY_RDAb88.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb88.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb88.FLNK","PPS:BSYS:1:MERGE_ON_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb88.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb88.VAL") #! Record("PPS:BSYS:1:MERGE_ON_A_calc",260,18,0,1,"PPS:BSYS:1:MERGE_ON_A_calc") #! Field("PPS:BSYS:1:MERGE_ON_A_calc.INPA",16777215,0,"PPS:BSYS:1:MERGE_ON_A_calc.INPA") #! Link("PPS:BSYS:1:MERGE_ON_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb88.VAL") #! Field("PPS:BSYS:1:MERGE_ON_A_calc.INPB",16777215,1,"PPS:BSYS:1:MERGE_ON_A_calc.INPB") #! Field("PPS:BSYS:1:MERGE_ON_A_calc.OUT",16777215,1,"PPS:BSYS:1:MERGE_ON_A_calc.OUT") #! Link("PPS:BSYS:1:MERGE_ON_A_calc.OUT","PPS:BSYS:1:MERGE_ON_A.VAL") #! Record("PPS:BSYS:1:MERGE_ON_A",500,20,0,0,"PPS:BSYS:1:MERGE_ON_A") #! Field("PPS:BSYS:1:MERGE_ON_A.VAL",16777215,1,"PPS:BSYS:1:MERGE_ON_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi103") { field(DESC, "Port 30BSY_RDA bit 103") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 103, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(FLNK, "PPS:SYSE:1:30BSY:INTLK_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi103Valid") { field(INPA, "PLC:BSY0:PP09:Bi103.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:INTLK_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:INTLK_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi103 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi103Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:INTLK_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:INTLK_A") { field(DESC, "30-BSY interlock A (spare)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb103",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb103") #! Field("PLC:BSY0:PP09:30BSY_RDAb103.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb103.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb103.FLNK","PPS:SYSE:1:30BSY:INTLK_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb103.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb103.VAL") #! Record("PPS:SYSE:1:30BSY:INTLK_A_calc",260,18,0,1,"PPS:SYSE:1:30BSY:INTLK_A_calc") #! Field("PPS:SYSE:1:30BSY:INTLK_A_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:INTLK_A_calc.INPA") #! Link("PPS:SYSE:1:30BSY:INTLK_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb103.VAL") #! Field("PPS:SYSE:1:30BSY:INTLK_A_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:INTLK_A_calc.INPB") #! Field("PPS:SYSE:1:30BSY:INTLK_A_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:INTLK_A_calc.OUT") #! Link("PPS:SYSE:1:30BSY:INTLK_A_calc.OUT","PPS:SYSE:1:30BSY:INTLK_A.VAL") #! Record("PPS:SYSE:1:30BSY:INTLK_A",500,20,0,0,"PPS:SYSE:1:30BSY:INTLK_A") #! Field("PPS:SYSE:1:30BSY:INTLK_A.VAL",16777215,1,"PPS:SYSE:1:30BSY:INTLK_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi102") { field(DESC, "Port 30BSY_RDA bit 102") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 102, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(FLNK, "PPS:SYSE:1:CU:INTLK_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi102Valid") { field(INPA, "PLC:BSY0:PP09:Bi102.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:CU:INTLK_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:CU:INTLK_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi102 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi102Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:CU:INTLK_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:CU:INTLK_A") { field(DESC, "Cu beam interlock A (spare)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb102",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb102") #! Field("PLC:BSY0:PP09:30BSY_RDAb102.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb102.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb102.FLNK","PPS:SYSE:1:CU:INTLK_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb102.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb102.VAL") #! Record("PPS:SYSE:1:CU:INTLK_A_calc",260,18,0,1,"PPS:SYSE:1:CU:INTLK_A_calc") #! Field("PPS:SYSE:1:CU:INTLK_A_calc.INPA",16777215,0,"PPS:SYSE:1:CU:INTLK_A_calc.INPA") #! Link("PPS:SYSE:1:CU:INTLK_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb102.VAL") #! Field("PPS:SYSE:1:CU:INTLK_A_calc.INPB",16777215,1,"PPS:SYSE:1:CU:INTLK_A_calc.INPB") #! Field("PPS:SYSE:1:CU:INTLK_A_calc.OUT",16777215,1,"PPS:SYSE:1:CU:INTLK_A_calc.OUT") #! Link("PPS:SYSE:1:CU:INTLK_A_calc.OUT","PPS:SYSE:1:CU:INTLK_A.VAL") #! Record("PPS:SYSE:1:CU:INTLK_A",500,20,0,0,"PPS:SYSE:1:CU:INTLK_A") #! Field("PPS:SYSE:1:CU:INTLK_A.VAL",16777215,1,"PPS:SYSE:1:CU:INTLK_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi101") { field(DESC, "Port 30BSY_RDA bit 101") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 101, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(FLNK, "PPS:SYSE:1:SC:INTLK_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi101Valid") { field(INPA, "PLC:BSY0:PP09:Bi101.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:SC:INTLK_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:SC:INTLK_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi101 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi101Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:SC:INTLK_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:SC:INTLK_A") { field(DESC, "SC beam interlock A (spare)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb101",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb101") #! Field("PLC:BSY0:PP09:30BSY_RDAb101.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb101.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb101.FLNK","PPS:SYSE:1:SC:INTLK_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb101.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb101.VAL") #! Record("PPS:SYSE:1:SC:INTLK_A_calc",260,18,0,1,"PPS:SYSE:1:SC:INTLK_A_calc") #! Field("PPS:SYSE:1:SC:INTLK_A_calc.INPA",16777215,0,"PPS:SYSE:1:SC:INTLK_A_calc.INPA") #! Link("PPS:SYSE:1:SC:INTLK_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb101.VAL") #! Field("PPS:SYSE:1:SC:INTLK_A_calc.INPB",16777215,1,"PPS:SYSE:1:SC:INTLK_A_calc.INPB") #! Field("PPS:SYSE:1:SC:INTLK_A_calc.OUT",16777215,1,"PPS:SYSE:1:SC:INTLK_A_calc.OUT") #! Link("PPS:SYSE:1:SC:INTLK_A_calc.OUT","PPS:SYSE:1:SC:INTLK_A.VAL") #! Record("PPS:SYSE:1:SC:INTLK_A",500,20,0,0,"PPS:SYSE:1:SC:INTLK_A") #! Field("PPS:SYSE:1:SC:INTLK_A.VAL",16777215,1,"PPS:SYSE:1:SC:INTLK_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi100") { field(DESC, "Port 30BSY_RDA bit 100") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 100, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(FLNK, "PPS:SYSE:1:BTH_ACCESS_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi100Valid") { field(INPA, "PLC:BSY0:PP09:Bi100.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:BTH_ACCESS_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:BTH_ACCESS_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi100 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi100Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:BTH_ACCESS_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:BTH_ACCESS_A") { field(DESC, "BTH Access cond. A (spare)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb100",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb100") #! Field("PLC:BSY0:PP09:30BSY_RDAb100.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb100.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb100.FLNK","PPS:SYSE:1:BTH_ACCESS_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb100.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb100.VAL") #! Record("PPS:SYSE:1:BTH_ACCESS_A_calc",260,18,0,1,"PPS:SYSE:1:BTH_ACCESS_A_calc") #! Field("PPS:SYSE:1:BTH_ACCESS_A_calc.INPA",16777215,0,"PPS:SYSE:1:BTH_ACCESS_A_calc.INPA") #! Link("PPS:SYSE:1:BTH_ACCESS_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb100.VAL") #! Field("PPS:SYSE:1:BTH_ACCESS_A_calc.INPB",16777215,1,"PPS:SYSE:1:BTH_ACCESS_A_calc.INPB") #! Field("PPS:SYSE:1:BTH_ACCESS_A_calc.OUT",16777215,1,"PPS:SYSE:1:BTH_ACCESS_A_calc.OUT") #! Link("PPS:SYSE:1:BTH_ACCESS_A_calc.OUT","PPS:SYSE:1:BTH_ACCESS_A.VAL") #! Record("PPS:SYSE:1:BTH_ACCESS_A",500,20,0,0,"PPS:SYSE:1:BTH_ACCESS_A") #! Field("PPS:SYSE:1:BTH_ACCESS_A.VAL",16777215,1,"PPS:SYSE:1:BTH_ACCESS_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi99") { field(DESC, "Port 30BSY_RDA bit 99") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 99, 1, 1)") field(ZNAM, "Test") field(ONAM, "Normal") field(FLNK, "PPS:SYSE:1:30BSY:CROSS_CHECK_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi99Valid") { field(INPA, "PLC:BSY0:PP09:Bi99.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:CROSS_CHECK_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:CROSS_CHECK_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi99 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi99Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:CROSS_CHECK_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:CROSS_CHECK_A") { field(DESC, "Cross_Check_Keysw_in_Normal_A") field(ZNAM, "Test") field(ONAM, "Normal") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb99",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb99") #! Field("PLC:BSY0:PP09:30BSY_RDAb99.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb99.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb99.FLNK","PPS:SYSE:1:30BSY:CROSS_CHECK_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb99.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb99.VAL") #! Record("PPS:SYSE:1:30BSY:CROSS_CHECK_A_calc",260,18,0,1,"PPS:SYSE:1:30BSY:CROSS_CHECK_A_calc") #! Field("PPS:SYSE:1:30BSY:CROSS_CHECK_A_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:CROSS_CHECK_A_calc.INPA") #! Link("PPS:SYSE:1:30BSY:CROSS_CHECK_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb99.VAL") #! Field("PPS:SYSE:1:30BSY:CROSS_CHECK_A_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:CROSS_CHECK_A_calc.INPB") #! Field("PPS:SYSE:1:30BSY:CROSS_CHECK_A_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:CROSS_CHECK_A_calc.OUT") #! Link("PPS:SYSE:1:30BSY:CROSS_CHECK_A_calc.OUT","PPS:SYSE:1:30BSY:CROSS_CHECK_A.VAL") #! Record("PPS:SYSE:1:30BSY:CROSS_CHECK_A",500,20,0,0,"PPS:SYSE:1:30BSY:CROSS_CHECK_A") #! Field("PPS:SYSE:1:30BSY:CROSS_CHECK_A.VAL",16777215,1,"PPS:SYSE:1:30BSY:CROSS_CHECK_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi98") { field(DESC, "Port 30BSY_RDA bit 98") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 98, 1, 1)") field(ZNAM, "Fault") field(ONAM, "Ok") field(FLNK, "PPS:SYSE:1:30BSY:HRTBT_INP_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi98Valid") { field(INPA, "PLC:BSY0:PP09:Bi98.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:HRTBT_INP_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:HRTBT_INP_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi98 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi98Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:HRTBT_INP_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:HRTBT_INP_A") { field(DESC, "Heartbeat IN (other chn.) A") field(ZNAM, "Fault") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb98",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb98") #! Field("PLC:BSY0:PP09:30BSY_RDAb98.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb98.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb98.FLNK","PPS:SYSE:1:30BSY:HRTBT_INP_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb98.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb98.VAL") #! Record("PPS:SYSE:1:30BSY:HRTBT_INP_A_calc",260,18,0,1,"PPS:SYSE:1:30BSY:HRTBT_INP_A_calc") #! Field("PPS:SYSE:1:30BSY:HRTBT_INP_A_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:HRTBT_INP_A_calc.INPA") #! Link("PPS:SYSE:1:30BSY:HRTBT_INP_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb98.VAL") #! Field("PPS:SYSE:1:30BSY:HRTBT_INP_A_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:HRTBT_INP_A_calc.INPB") #! Field("PPS:SYSE:1:30BSY:HRTBT_INP_A_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:HRTBT_INP_A_calc.OUT") #! Link("PPS:SYSE:1:30BSY:HRTBT_INP_A_calc.OUT","PPS:SYSE:1:30BSY:HRTBT_INP_A.VAL") #! Record("PPS:SYSE:1:30BSY:HRTBT_INP_A",500,20,0,0,"PPS:SYSE:1:30BSY:HRTBT_INP_A") #! Field("PPS:SYSE:1:30BSY:HRTBT_INP_A.VAL",16777215,1,"PPS:SYSE:1:30BSY:HRTBT_INP_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi97") { field(DESC, "Port 30BSY_RDA bit 97") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 97, 1, 1)") field(ZNAM, "NOT_READY") field(ONAM, "READY") field(FLNK, "PPS:SYSE:1:BEAM_ON_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi97Valid") { field(INPA, "PLC:BSY0:PP09:Bi97.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:BEAM_ON_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:BEAM_ON_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi97 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi97Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:BEAM_ON_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:BEAM_ON_A") { field(DESC, "Linac E. Global in Ready for Beam") field(ZNAM, "NOT_READY") field(ONAM, "READY") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb97",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb97") #! Field("PLC:BSY0:PP09:30BSY_RDAb97.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb97.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb97.FLNK","PPS:SYSE:1:BEAM_ON_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb97.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb97.VAL") #! Record("PPS:SYSE:1:BEAM_ON_A_calc",260,18,0,1,"PPS:SYSE:1:BEAM_ON_A_calc") #! Field("PPS:SYSE:1:BEAM_ON_A_calc.INPA",16777215,0,"PPS:SYSE:1:BEAM_ON_A_calc.INPA") #! Link("PPS:SYSE:1:BEAM_ON_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb97.VAL") #! Field("PPS:SYSE:1:BEAM_ON_A_calc.INPB",16777215,1,"PPS:SYSE:1:BEAM_ON_A_calc.INPB") #! Field("PPS:SYSE:1:BEAM_ON_A_calc.OUT",16777215,1,"PPS:SYSE:1:BEAM_ON_A_calc.OUT") #! Link("PPS:SYSE:1:BEAM_ON_A_calc.OUT","PPS:SYSE:1:BEAM_ON_A.VAL") #! Record("PPS:SYSE:1:BEAM_ON_A",500,20,0,0,"PPS:SYSE:1:BEAM_ON_A") #! Field("PPS:SYSE:1:BEAM_ON_A.VAL",16777215,1,"PPS:SYSE:1:BEAM_ON_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi111") { field(DESC, "Port 30BSY_RDA bit 111") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 111, 1, 1)") field(ZNAM, "Not_Reset") field(ONAM, "Reset") field(FLNK, "PPS:SYSE:1:HW_RESET_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi111Valid") { field(INPA, "PLC:BSY0:PP09:Bi111.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:HW_RESET_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:HW_RESET_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi111 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi111Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:HW_RESET_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:HW_RESET_A") { field(DESC, "HW Reset A") field(ZNAM, "Not_Reset") field(ONAM, "Reset") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb111",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb111") #! Field("PLC:BSY0:PP09:30BSY_RDAb111.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb111.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb111.FLNK","PPS:SYSE:1:HW_RESET_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb111.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb111.VAL") #! Record("PPS:SYSE:1:HW_RESET_A_calc",260,18,0,1,"PPS:SYSE:1:HW_RESET_A_calc") #! Field("PPS:SYSE:1:HW_RESET_A_calc.INPA",16777215,0,"PPS:SYSE:1:HW_RESET_A_calc.INPA") #! Link("PPS:SYSE:1:HW_RESET_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb111.VAL") #! Field("PPS:SYSE:1:HW_RESET_A_calc.INPB",16777215,1,"PPS:SYSE:1:HW_RESET_A_calc.INPB") #! Field("PPS:SYSE:1:HW_RESET_A_calc.OUT",16777215,1,"PPS:SYSE:1:HW_RESET_A_calc.OUT") #! Link("PPS:SYSE:1:HW_RESET_A_calc.OUT","PPS:SYSE:1:HW_RESET_A.VAL") #! Record("PPS:SYSE:1:HW_RESET_A",500,20,0,0,"PPS:SYSE:1:HW_RESET_A") #! Field("PPS:SYSE:1:HW_RESET_A.VAL",16777215,1,"PPS:SYSE:1:HW_RESET_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi110") { field(DESC, "Port 30BSY_RDA bit 110") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 110, 1, 1)") field(ZNAM, "Not_Secure") field(ONAM, "Secure") field(FLNK, "PPS:SYSE:1:RSY_SECURE_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi110Valid") { field(INPA, "PLC:BSY0:PP09:Bi110.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:RSY_SECURE_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:RSY_SECURE_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi110 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi110Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:RSY_SECURE_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:RSY_SECURE_A") { field(DESC, "RSY Secure A") field(ZNAM, "Not_Secure") field(ONAM, "Secure") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb110",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb110") #! Field("PLC:BSY0:PP09:30BSY_RDAb110.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb110.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb110.FLNK","PPS:SYSE:1:RSY_SECURE_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb110.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb110.VAL") #! Record("PPS:SYSE:1:RSY_SECURE_A_calc",260,18,0,1,"PPS:SYSE:1:RSY_SECURE_A_calc") #! Field("PPS:SYSE:1:RSY_SECURE_A_calc.INPA",16777215,0,"PPS:SYSE:1:RSY_SECURE_A_calc.INPA") #! Link("PPS:SYSE:1:RSY_SECURE_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb110.VAL") #! Field("PPS:SYSE:1:RSY_SECURE_A_calc.INPB",16777215,1,"PPS:SYSE:1:RSY_SECURE_A_calc.INPB") #! Field("PPS:SYSE:1:RSY_SECURE_A_calc.OUT",16777215,1,"PPS:SYSE:1:RSY_SECURE_A_calc.OUT") #! Link("PPS:SYSE:1:RSY_SECURE_A_calc.OUT","PPS:SYSE:1:RSY_SECURE_A.VAL") #! Record("PPS:SYSE:1:RSY_SECURE_A",500,20,0,0,"PPS:SYSE:1:RSY_SECURE_A") #! Field("PPS:SYSE:1:RSY_SECURE_A.VAL",16777215,1,"PPS:SYSE:1:RSY_SECURE_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi109") { field(DESC, "Port 30BSY_RDA bit 109") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 109, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(FLNK, "PPS:SYSE:1:SPARE_4_i6_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi109Valid") { field(INPA, "PLC:BSY0:PP09:Bi109.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:SPARE_4_i6_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:SPARE_4_i6_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi109 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi109Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:SPARE_4_i6_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:SPARE_4_i6_A") { field(DESC, "Spare 4.i6 A") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb109",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb109") #! Field("PLC:BSY0:PP09:30BSY_RDAb109.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb109.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb109.FLNK","PPS:SYSE:1:SPARE_4_i6_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb109.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb109.VAL") #! Record("PPS:SYSE:1:SPARE_4_i6_A_calc",260,18,0,1,"PPS:SYSE:1:SPARE_4_i6_A_calc") #! Field("PPS:SYSE:1:SPARE_4_i6_A_calc.INPA",16777215,0,"PPS:SYSE:1:SPARE_4_i6_A_calc.INPA") #! Link("PPS:SYSE:1:SPARE_4_i6_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb109.VAL") #! Field("PPS:SYSE:1:SPARE_4_i6_A_calc.INPB",16777215,1,"PPS:SYSE:1:SPARE_4_i6_A_calc.INPB") #! Field("PPS:SYSE:1:SPARE_4_i6_A_calc.OUT",16777215,1,"PPS:SYSE:1:SPARE_4_i6_A_calc.OUT") #! Link("PPS:SYSE:1:SPARE_4_i6_A_calc.OUT","PPS:SYSE:1:SPARE_4_i6_A.VAL") #! Record("PPS:SYSE:1:SPARE_4_i6_A",500,20,0,0,"PPS:SYSE:1:SPARE_4_i6_A") #! Field("PPS:SYSE:1:SPARE_4_i6_A.VAL",16777215,1,"PPS:SYSE:1:SPARE_4_i6_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi108") { field(DESC, "Port 30BSY_RDA bit 108") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 108, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(FLNK, "PPS:SYSE:1:SPARE_4_i7_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi108Valid") { field(INPA, "PLC:BSY0:PP09:Bi108.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:SPARE_4_i7_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:SPARE_4_i7_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi108 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi108Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:SPARE_4_i7_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:SPARE_4_i7_A") { field(DESC, "Spare 4.i7 A") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb108",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb108") #! Field("PLC:BSY0:PP09:30BSY_RDAb108.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb108.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb108.FLNK","PPS:SYSE:1:SPARE_4_i7_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb108.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb108.VAL") #! Record("PPS:SYSE:1:SPARE_4_i7_A_calc",260,18,0,1,"PPS:SYSE:1:SPARE_4_i7_A_calc") #! Field("PPS:SYSE:1:SPARE_4_i7_A_calc.INPA",16777215,0,"PPS:SYSE:1:SPARE_4_i7_A_calc.INPA") #! Link("PPS:SYSE:1:SPARE_4_i7_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb108.VAL") #! Field("PPS:SYSE:1:SPARE_4_i7_A_calc.INPB",16777215,1,"PPS:SYSE:1:SPARE_4_i7_A_calc.INPB") #! Field("PPS:SYSE:1:SPARE_4_i7_A_calc.OUT",16777215,1,"PPS:SYSE:1:SPARE_4_i7_A_calc.OUT") #! Link("PPS:SYSE:1:SPARE_4_i7_A_calc.OUT","PPS:SYSE:1:SPARE_4_i7_A.VAL") #! Record("PPS:SYSE:1:SPARE_4_i7_A",500,20,0,0,"PPS:SYSE:1:SPARE_4_i7_A") #! Field("PPS:SYSE:1:SPARE_4_i7_A.VAL",16777215,1,"PPS:SYSE:1:SPARE_4_i7_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi107") { field(DESC, "Port 30BSY_RDA bit 107") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 107, 1, 1)") field(ZNAM, "Not_Secure") field(ONAM, "Secure") field(FLNK, "PPS:SYSE:2:30BSY:SECURE_COM_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi107Valid") { field(INPA, "PLC:BSY0:PP09:Bi107.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:2:30BSY:SECURE_COM_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:2:30BSY:SECURE_COM_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi107 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi107Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:2:30BSY:SECURE_COM_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:2:30BSY:SECURE_COM_A") { field(DESC, "30-BSY Sec. Comp. (test mode)") field(ZNAM, "Not_Secure") field(ONAM, "Secure") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb107",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb107") #! Field("PLC:BSY0:PP09:30BSY_RDAb107.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb107.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb107.FLNK","PPS:SYSE:2:30BSY:SECURE_COM_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb107.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb107.VAL") #! Record("PPS:SYSE:2:30BSY:SECURE_COM_A_calc",260,18,0,1,"PPS:SYSE:2:30BSY:SECURE_COM_A_calc") #! Field("PPS:SYSE:2:30BSY:SECURE_COM_A_calc.INPA",16777215,0,"PPS:SYSE:2:30BSY:SECURE_COM_A_calc.INPA") #! Link("PPS:SYSE:2:30BSY:SECURE_COM_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb107.VAL") #! Field("PPS:SYSE:2:30BSY:SECURE_COM_A_calc.INPB",16777215,1,"PPS:SYSE:2:30BSY:SECURE_COM_A_calc.INPB") #! Field("PPS:SYSE:2:30BSY:SECURE_COM_A_calc.OUT",16777215,1,"PPS:SYSE:2:30BSY:SECURE_COM_A_calc.OUT") #! Link("PPS:SYSE:2:30BSY:SECURE_COM_A_calc.OUT","PPS:SYSE:2:30BSY:SECURE_COM_A.VAL") #! Record("PPS:SYSE:2:30BSY:SECURE_COM_A",500,20,0,0,"PPS:SYSE:2:30BSY:SECURE_COM_A") #! Field("PPS:SYSE:2:30BSY:SECURE_COM_A.VAL",16777215,1,"PPS:SYSE:2:30BSY:SECURE_COM_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi106") { field(DESC, "Port 30BSY_RDA bit 106") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 106, 1, 1)") field(ZNAM, "Not_Secure") field(ONAM, "Secure") field(FLNK, "PPS:SYSE:3:30BSY:SECURE_COM_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi106Valid") { field(INPA, "PLC:BSY0:PP09:Bi106.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:3:30BSY:SECURE_COM_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:3:30BSY:SECURE_COM_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi106 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi106Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:3:30BSY:SECURE_COM_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:3:30BSY:SECURE_COM_A") { field(DESC, "30-BSY Sec. Comp. (other ch.)") field(ZNAM, "Not_Secure") field(ONAM, "Secure") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb106",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb106") #! Field("PLC:BSY0:PP09:30BSY_RDAb106.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb106.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb106.FLNK","PPS:SYSE:3:30BSY:SECURE_COM_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb106.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb106.VAL") #! Record("PPS:SYSE:3:30BSY:SECURE_COM_A_calc",260,18,0,1,"PPS:SYSE:3:30BSY:SECURE_COM_A_calc") #! Field("PPS:SYSE:3:30BSY:SECURE_COM_A_calc.INPA",16777215,0,"PPS:SYSE:3:30BSY:SECURE_COM_A_calc.INPA") #! Link("PPS:SYSE:3:30BSY:SECURE_COM_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb106.VAL") #! Field("PPS:SYSE:3:30BSY:SECURE_COM_A_calc.INPB",16777215,1,"PPS:SYSE:3:30BSY:SECURE_COM_A_calc.INPB") #! Field("PPS:SYSE:3:30BSY:SECURE_COM_A_calc.OUT",16777215,1,"PPS:SYSE:3:30BSY:SECURE_COM_A_calc.OUT") #! Link("PPS:SYSE:3:30BSY:SECURE_COM_A_calc.OUT","PPS:SYSE:3:30BSY:SECURE_COM_A.VAL") #! Record("PPS:SYSE:3:30BSY:SECURE_COM_A",500,20,0,0,"PPS:SYSE:3:30BSY:SECURE_COM_A") #! Field("PPS:SYSE:3:30BSY:SECURE_COM_A.VAL",16777215,1,"PPS:SYSE:3:30BSY:SECURE_COM_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi105") { field(DESC, "Port 30BSY_RDA bit 105") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 105, 1, 1)") field(ZNAM, "Fault") field(ONAM, "Ok") field(FLNK, "PPS:SYSE:1:30BSY:HWALRMWARN_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi105Valid") { field(INPA, "PLC:BSY0:PP09:Bi105.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:HWALRMWARN_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:HWALRMWARN_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi105 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi105Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:HWALRMWARN_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:HWALRMWARN_A") { field(DESC, "HW_Alarm_Warning_A") field(ZNAM, "Fault") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb105",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb105") #! Field("PLC:BSY0:PP09:30BSY_RDAb105.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb105.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb105.FLNK","PPS:SYSE:1:30BSY:HWALRMWARN_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb105.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb105.VAL") #! Record("PPS:SYSE:1:30BSY:HWALRMWARN_A_calc",260,18,0,1,"PPS:SYSE:1:30BSY:HWALRMWARN_A_calc") #! Field("PPS:SYSE:1:30BSY:HWALRMWARN_A_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:HWALRMWARN_A_calc.INPA") #! Link("PPS:SYSE:1:30BSY:HWALRMWARN_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb105.VAL") #! Field("PPS:SYSE:1:30BSY:HWALRMWARN_A_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:HWALRMWARN_A_calc.INPB") #! Field("PPS:SYSE:1:30BSY:HWALRMWARN_A_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:HWALRMWARN_A_calc.OUT") #! Link("PPS:SYSE:1:30BSY:HWALRMWARN_A_calc.OUT","PPS:SYSE:1:30BSY:HWALRMWARN_A.VAL") #! Record("PPS:SYSE:1:30BSY:HWALRMWARN_A",500,20,0,0,"PPS:SYSE:1:30BSY:HWALRMWARN_A") #! Field("PPS:SYSE:1:30BSY:HWALRMWARN_A.VAL",16777215,1,"PPS:SYSE:1:30BSY:HWALRMWARN_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi104") { field(DESC, "Port 30BSY_RDA bit 104") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 104, 1, 1)") field(ZNAM, "Fault") field(ONAM, "Ok") field(FLNK, "PPS:SYSE:1:30BSY:HRTBT_OUTP_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi104Valid") { field(INPA, "PLC:BSY0:PP09:Bi104.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:HRTBT_OUTP_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:HRTBT_OUTP_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi104 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi104Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:HRTBT_OUTP_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:HRTBT_OUTP_A") { field(DESC, "PLC_Heartbeat_Output_A") field(ZNAM, "Fault") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb104",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb104") #! Field("PLC:BSY0:PP09:30BSY_RDAb104.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb104.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb104.FLNK","PPS:SYSE:1:30BSY:HRTBT_OUTP_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb104.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb104.VAL") #! Record("PPS:SYSE:1:30BSY:HRTBT_OUTP_A_calc",260,18,0,1,"PPS:SYSE:1:30BSY:HRTBT_OUTP_A_calc") #! Field("PPS:SYSE:1:30BSY:HRTBT_OUTP_A_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:HRTBT_OUTP_A_calc.INPA") #! Link("PPS:SYSE:1:30BSY:HRTBT_OUTP_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb104.VAL") #! Field("PPS:SYSE:1:30BSY:HRTBT_OUTP_A_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:HRTBT_OUTP_A_calc.INPB") #! Field("PPS:SYSE:1:30BSY:HRTBT_OUTP_A_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:HRTBT_OUTP_A_calc.OUT") #! Link("PPS:SYSE:1:30BSY:HRTBT_OUTP_A_calc.OUT","PPS:SYSE:1:30BSY:HRTBT_OUTP_A.VAL") #! Record("PPS:SYSE:1:30BSY:HRTBT_OUTP_A",500,20,0,0,"PPS:SYSE:1:30BSY:HRTBT_OUTP_A") #! Field("PPS:SYSE:1:30BSY:HRTBT_OUTP_A.VAL",16777215,1,"PPS:SYSE:1:30BSY:HRTBT_OUTP_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi119") { field(DESC, "Port 30BSY_RDA bit 119") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 119, 1, 1)") field(ZNAM, "Fault") field(ONAM, "Ok") field(FLNK, "PPS:SYSE:1:30BSY:BCS_FAULT_TRG_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi119Valid") { field(INPA, "PLC:BSY0:PP09:Bi119.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:BCS_FAULT_TRG_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:BCS_FAULT_TRG_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi119 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi119Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:BCS_FAULT_TRG_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:BCS_FAULT_TRG_A") { field(DESC, "BCS_Fault_Trigger_Output_A") field(ZNAM, "Fault") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb119",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb119") #! Field("PLC:BSY0:PP09:30BSY_RDAb119.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb119.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb119.FLNK","PPS:SYSE:1:30BSY:BCS_FAULT_TRG_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb119.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb119.VAL") #! Record("PPS:SYSE:1:30BSY:BCS_FAULT_TRG_A_calc",260,18,0,1,"PPS:SYSE:1:30BSY:BCS_FAULT_TRG_A_calc") #! Field("PPS:SYSE:1:30BSY:BCS_FAULT_TRG_A_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:BCS_FAULT_TRG_A_calc.INPA") #! Link("PPS:SYSE:1:30BSY:BCS_FAULT_TRG_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb119.VAL") #! Field("PPS:SYSE:1:30BSY:BCS_FAULT_TRG_A_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:BCS_FAULT_TRG_A_calc.INPB") #! Field("PPS:SYSE:1:30BSY:BCS_FAULT_TRG_A_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:BCS_FAULT_TRG_A_calc.OUT") #! Link("PPS:SYSE:1:30BSY:BCS_FAULT_TRG_A_calc.OUT","PPS:SYSE:1:30BSY:BCS_FAULT_TRG_A.VAL") #! Record("PPS:SYSE:1:30BSY:BCS_FAULT_TRG_A",500,20,0,0,"PPS:SYSE:1:30BSY:BCS_FAULT_TRG_A") #! Field("PPS:SYSE:1:30BSY:BCS_FAULT_TRG_A.VAL",16777215,1,"PPS:SYSE:1:30BSY:BCS_FAULT_TRG_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi117") { field(DESC, "Port 30BSY_RDA bit 117") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 117, 1, 1)") field(ZNAM, "Not_Complete") field(ONAM, "Complete") field(FLNK, "PPS:SYSE:1:30BSY:SECURE_COM_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi117Valid") { field(INPA, "PLC:BSY0:PP09:Bi117.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:SECURE_COM_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:SECURE_COM_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi117 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi117Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:SECURE_COM_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:SECURE_COM_A") { field(DESC, "30BSY_Secure_Complete_A") field(ZNAM, "Not_Complete") field(ONAM, "Complete") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb117",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb117") #! Field("PLC:BSY0:PP09:30BSY_RDAb117.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb117.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb117.FLNK","PPS:SYSE:1:30BSY:SECURE_COM_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb117.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb117.VAL") #! Record("PPS:SYSE:1:30BSY:SECURE_COM_A_calc",260,18,0,1,"PPS:SYSE:1:30BSY:SECURE_COM_A_calc") #! Field("PPS:SYSE:1:30BSY:SECURE_COM_A_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:SECURE_COM_A_calc.INPA") #! Link("PPS:SYSE:1:30BSY:SECURE_COM_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb117.VAL") #! Field("PPS:SYSE:1:30BSY:SECURE_COM_A_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:SECURE_COM_A_calc.INPB") #! Field("PPS:SYSE:1:30BSY:SECURE_COM_A_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:SECURE_COM_A_calc.OUT") #! Link("PPS:SYSE:1:30BSY:SECURE_COM_A_calc.OUT","PPS:SYSE:1:30BSY:SECURE_COM_A.VAL") #! Record("PPS:SYSE:1:30BSY:SECURE_COM_A",500,20,0,0,"PPS:SYSE:1:30BSY:SECURE_COM_A") #! Field("PPS:SYSE:1:30BSY:SECURE_COM_A.VAL",16777215,1,"PPS:SYSE:1:30BSY:SECURE_COM_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi116") { field(DESC, "Port 30BSY_RDA bit 116") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 116, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:SYSE:1:30BSY:SECURE_LTH_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi116Valid") { field(INPA, "PLC:BSY0:PP09:Bi116.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:SECURE_LTH_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:SECURE_LTH_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi116 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi116Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:SECURE_LTH_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:SECURE_LTH_A") { field(DESC, "30BSY_Secure_Latched_A") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb116",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb116") #! Field("PLC:BSY0:PP09:30BSY_RDAb116.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb116.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb116.FLNK","PPS:SYSE:1:30BSY:SECURE_LTH_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb116.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb116.VAL") #! Record("PPS:SYSE:1:30BSY:SECURE_LTH_A_calc",260,18,0,1,"PPS:SYSE:1:30BSY:SECURE_LTH_A_calc") #! Field("PPS:SYSE:1:30BSY:SECURE_LTH_A_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:SECURE_LTH_A_calc.INPA") #! Link("PPS:SYSE:1:30BSY:SECURE_LTH_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb116.VAL") #! Field("PPS:SYSE:1:30BSY:SECURE_LTH_A_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:SECURE_LTH_A_calc.INPB") #! Field("PPS:SYSE:1:30BSY:SECURE_LTH_A_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:SECURE_LTH_A_calc.OUT") #! Link("PPS:SYSE:1:30BSY:SECURE_LTH_A_calc.OUT","PPS:SYSE:1:30BSY:SECURE_LTH_A.VAL") #! Record("PPS:SYSE:1:30BSY:SECURE_LTH_A",500,20,0,0,"PPS:SYSE:1:30BSY:SECURE_LTH_A") #! Field("PPS:SYSE:1:30BSY:SECURE_LTH_A.VAL",16777215,1,"PPS:SYSE:1:30BSY:SECURE_LTH_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi115") { field(DESC, "Port 30BSY_RDA bit 115") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 115, 1, 1)") field(ZNAM, "Not Ok") field(ONAM, "Ok") field(FLNK, "PPS:LTU0:1:ACCPERMIT_OUT_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi115Valid") { field(INPA, "PLC:BSY0:PP09:Bi115.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:LTU0:1:ACCPERMIT_OUT_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:LTU0:1:ACCPERMIT_OUT_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi115 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi115Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:LTU0:1:ACCPERMIT_OUT_A PP MS") field(ASG, "Internal") } record(bi, "PPS:LTU0:1:ACCPERMIT_OUT_A") { field(DESC, "BTH_UND_Access_Permit_Out_A") field(ZNAM, "Not Ok") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb115",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb115") #! Field("PLC:BSY0:PP09:30BSY_RDAb115.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb115.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb115.FLNK","PPS:LTU0:1:ACCPERMIT_OUT_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb115.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb115.VAL") #! Record("PPS:LTU0:1:ACCPERMIT_OUT_A_calc",260,18,0,1,"PPS:LTU0:1:ACCPERMIT_OUT_A_calc") #! Field("PPS:LTU0:1:ACCPERMIT_OUT_A_calc.INPA",16777215,0,"PPS:LTU0:1:ACCPERMIT_OUT_A_calc.INPA") #! Link("PPS:LTU0:1:ACCPERMIT_OUT_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb115.VAL") #! Field("PPS:LTU0:1:ACCPERMIT_OUT_A_calc.INPB",16777215,1,"PPS:LTU0:1:ACCPERMIT_OUT_A_calc.INPB") #! Field("PPS:LTU0:1:ACCPERMIT_OUT_A_calc.OUT",16777215,1,"PPS:LTU0:1:ACCPERMIT_OUT_A_calc.OUT") #! Link("PPS:LTU0:1:ACCPERMIT_OUT_A_calc.OUT","PPS:LTU0:1:ACCPERMIT_OUT_A.VAL") #! Record("PPS:LTU0:1:ACCPERMIT_OUT_A",500,20,0,0,"PPS:LTU0:1:ACCPERMIT_OUT_A") #! Field("PPS:LTU0:1:ACCPERMIT_OUT_A.VAL",16777215,1,"PPS:LTU0:1:ACCPERMIT_OUT_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi114") { field(DESC, "Port 30BSY_RDA bit 114") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 114, 1, 1)") field(ZNAM, "Not Ok") field(ONAM, "Ok") field(FLNK, "PPS:LTU0:2:ACCPERMIT_OUT_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi114Valid") { field(INPA, "PLC:BSY0:PP09:Bi114.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:LTU0:2:ACCPERMIT_OUT_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:LTU0:2:ACCPERMIT_OUT_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi114 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi114Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:LTU0:2:ACCPERMIT_OUT_A PP MS") field(ASG, "Internal") } record(bi, "PPS:LTU0:2:ACCPERMIT_OUT_A") { field(DESC, "RSY_Access_Permit_Out_A") field(ZNAM, "Not Ok") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb114",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb114") #! Field("PLC:BSY0:PP09:30BSY_RDAb114.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb114.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb114.FLNK","PPS:LTU0:2:ACCPERMIT_OUT_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb114.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb114.VAL") #! Record("PPS:LTU0:2:ACCPERMIT_OUT_A_calc",260,18,0,1,"PPS:LTU0:2:ACCPERMIT_OUT_A_calc") #! Field("PPS:LTU0:2:ACCPERMIT_OUT_A_calc.INPA",16777215,0,"PPS:LTU0:2:ACCPERMIT_OUT_A_calc.INPA") #! Link("PPS:LTU0:2:ACCPERMIT_OUT_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb114.VAL") #! Field("PPS:LTU0:2:ACCPERMIT_OUT_A_calc.INPB",16777215,1,"PPS:LTU0:2:ACCPERMIT_OUT_A_calc.INPB") #! Field("PPS:LTU0:2:ACCPERMIT_OUT_A_calc.OUT",16777215,1,"PPS:LTU0:2:ACCPERMIT_OUT_A_calc.OUT") #! Link("PPS:LTU0:2:ACCPERMIT_OUT_A_calc.OUT","PPS:LTU0:2:ACCPERMIT_OUT_A.VAL") #! Record("PPS:LTU0:2:ACCPERMIT_OUT_A",500,20,0,0,"PPS:LTU0:2:ACCPERMIT_OUT_A") #! Field("PPS:LTU0:2:ACCPERMIT_OUT_A.VAL",16777215,1,"PPS:LTU0:2:ACCPERMIT_OUT_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi113") { field(DESC, "Port 30BSY_RDA bit 113") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 113, 1, 1)") field(ZNAM, "Not_Escalated") field(ONAM, "Escalated") field(FLNK, "PPS:SYSE:1:BSOIC_ESC_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi113Valid") { field(INPA, "PLC:BSY0:PP09:Bi113.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:BSOIC_ESC_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:BSOIC_ESC_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi113 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi113Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:BSOIC_ESC_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:BSOIC_ESC_A") { field(DESC, "BSOIC escalation A") field(ZNAM, "Not_Escalated") field(ONAM, "Escalated") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb113",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb113") #! Field("PLC:BSY0:PP09:30BSY_RDAb113.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb113.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb113.FLNK","PPS:SYSE:1:BSOIC_ESC_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb113.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb113.VAL") #! Record("PPS:SYSE:1:BSOIC_ESC_A_calc",260,18,0,1,"PPS:SYSE:1:BSOIC_ESC_A_calc") #! Field("PPS:SYSE:1:BSOIC_ESC_A_calc.INPA",16777215,0,"PPS:SYSE:1:BSOIC_ESC_A_calc.INPA") #! Link("PPS:SYSE:1:BSOIC_ESC_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb113.VAL") #! Field("PPS:SYSE:1:BSOIC_ESC_A_calc.INPB",16777215,1,"PPS:SYSE:1:BSOIC_ESC_A_calc.INPB") #! Field("PPS:SYSE:1:BSOIC_ESC_A_calc.OUT",16777215,1,"PPS:SYSE:1:BSOIC_ESC_A_calc.OUT") #! Link("PPS:SYSE:1:BSOIC_ESC_A_calc.OUT","PPS:SYSE:1:BSOIC_ESC_A.VAL") #! Record("PPS:SYSE:1:BSOIC_ESC_A",500,20,0,0,"PPS:SYSE:1:BSOIC_ESC_A") #! Field("PPS:SYSE:1:BSOIC_ESC_A.VAL",16777215,1,"PPS:SYSE:1:BSOIC_ESC_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi112") { field(DESC, "Port 30BSY_RDA bit 112") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 112, 1, 1)") field(ZNAM, "Not_Complete") field(ONAM, "Complete") field(FLNK, "PPS:SYSE:1:GLOBAL:BEAMCOND_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi112Valid") { field(INPA, "PLC:BSY0:PP09:Bi112.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:GLOBAL:BEAMCOND_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:GLOBAL:BEAMCOND_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi112 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi112Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:GLOBAL:BEAMCOND_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:GLOBAL:BEAMCOND_A") { field(DESC, "Global_Beam_Conditions_A") field(ZNAM, "Not_Complete") field(ONAM, "Complete") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb112",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb112") #! Field("PLC:BSY0:PP09:30BSY_RDAb112.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb112.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb112.FLNK","PPS:SYSE:1:GLOBAL:BEAMCOND_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb112.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb112.VAL") #! Record("PPS:SYSE:1:GLOBAL:BEAMCOND_A_calc",260,18,0,1,"PPS:SYSE:1:GLOBAL:BEAMCOND_A_calc") #! Field("PPS:SYSE:1:GLOBAL:BEAMCOND_A_calc.INPA",16777215,0,"PPS:SYSE:1:GLOBAL:BEAMCOND_A_calc.INPA") #! Link("PPS:SYSE:1:GLOBAL:BEAMCOND_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb112.VAL") #! Field("PPS:SYSE:1:GLOBAL:BEAMCOND_A_calc.INPB",16777215,1,"PPS:SYSE:1:GLOBAL:BEAMCOND_A_calc.INPB") #! Field("PPS:SYSE:1:GLOBAL:BEAMCOND_A_calc.OUT",16777215,1,"PPS:SYSE:1:GLOBAL:BEAMCOND_A_calc.OUT") #! Link("PPS:SYSE:1:GLOBAL:BEAMCOND_A_calc.OUT","PPS:SYSE:1:GLOBAL:BEAMCOND_A.VAL") #! Record("PPS:SYSE:1:GLOBAL:BEAMCOND_A",500,20,0,0,"PPS:SYSE:1:GLOBAL:BEAMCOND_A") #! Field("PPS:SYSE:1:GLOBAL:BEAMCOND_A.VAL",16777215,1,"PPS:SYSE:1:GLOBAL:BEAMCOND_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi127") { field(DESC, "Port 30BSY_RDA bit 127") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 127, 1, 1)") field(ZNAM, "Not_Complete") field(ONAM, "Complete") field(FLNK, "PPS:SYSE:1:CU:BEAMCOND_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi127Valid") { field(INPA, "PLC:BSY0:PP09:Bi127.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:CU:BEAMCOND_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:CU:BEAMCOND_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi127 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi127Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:CU:BEAMCOND_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:CU:BEAMCOND_A") { field(DESC, "Cu_Beam_Conditions_A") field(ZNAM, "Not_Complete") field(ONAM, "Complete") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb127",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb127") #! Field("PLC:BSY0:PP09:30BSY_RDAb127.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb127.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb127.FLNK","PPS:SYSE:1:CU:BEAMCOND_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb127.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb127.VAL") #! Record("PPS:SYSE:1:CU:BEAMCOND_A_calc",260,18,0,1,"PPS:SYSE:1:CU:BEAMCOND_A_calc") #! Field("PPS:SYSE:1:CU:BEAMCOND_A_calc.INPA",16777215,0,"PPS:SYSE:1:CU:BEAMCOND_A_calc.INPA") #! Link("PPS:SYSE:1:CU:BEAMCOND_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb127.VAL") #! Field("PPS:SYSE:1:CU:BEAMCOND_A_calc.INPB",16777215,1,"PPS:SYSE:1:CU:BEAMCOND_A_calc.INPB") #! Field("PPS:SYSE:1:CU:BEAMCOND_A_calc.OUT",16777215,1,"PPS:SYSE:1:CU:BEAMCOND_A_calc.OUT") #! Link("PPS:SYSE:1:CU:BEAMCOND_A_calc.OUT","PPS:SYSE:1:CU:BEAMCOND_A.VAL") #! Record("PPS:SYSE:1:CU:BEAMCOND_A",500,20,0,0,"PPS:SYSE:1:CU:BEAMCOND_A") #! Field("PPS:SYSE:1:CU:BEAMCOND_A.VAL",16777215,1,"PPS:SYSE:1:CU:BEAMCOND_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi126") { field(DESC, "Port 30BSY_RDA bit 126") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 126, 1, 1)") field(ZNAM, "Not_Complete") field(ONAM, "Complete") field(FLNK, "PPS:SYSE:1:SC:BEAMCOND_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi126Valid") { field(INPA, "PLC:BSY0:PP09:Bi126.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:SC:BEAMCOND_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:SC:BEAMCOND_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi126 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi126Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:SC:BEAMCOND_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:SC:BEAMCOND_A") { field(DESC, "SC_Beam_Conditions_A") field(ZNAM, "Not_Complete") field(ONAM, "Complete") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb126",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb126") #! Field("PLC:BSY0:PP09:30BSY_RDAb126.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb126.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb126.FLNK","PPS:SYSE:1:SC:BEAMCOND_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb126.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb126.VAL") #! Record("PPS:SYSE:1:SC:BEAMCOND_A_calc",260,18,0,1,"PPS:SYSE:1:SC:BEAMCOND_A_calc") #! Field("PPS:SYSE:1:SC:BEAMCOND_A_calc.INPA",16777215,0,"PPS:SYSE:1:SC:BEAMCOND_A_calc.INPA") #! Link("PPS:SYSE:1:SC:BEAMCOND_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb126.VAL") #! Field("PPS:SYSE:1:SC:BEAMCOND_A_calc.INPB",16777215,1,"PPS:SYSE:1:SC:BEAMCOND_A_calc.INPB") #! Field("PPS:SYSE:1:SC:BEAMCOND_A_calc.OUT",16777215,1,"PPS:SYSE:1:SC:BEAMCOND_A_calc.OUT") #! Link("PPS:SYSE:1:SC:BEAMCOND_A_calc.OUT","PPS:SYSE:1:SC:BEAMCOND_A.VAL") #! Record("PPS:SYSE:1:SC:BEAMCOND_A",500,20,0,0,"PPS:SYSE:1:SC:BEAMCOND_A") #! Field("PPS:SYSE:1:SC:BEAMCOND_A.VAL",16777215,1,"PPS:SYSE:1:SC:BEAMCOND_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi123") { field(DESC, "Port 30BSY_RDA bit 123") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 123, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:SYSE:1:BLM_INP_LTH_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi123Valid") { field(INPA, "PLC:BSY0:PP09:Bi123.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:BLM_INP_LTH_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:BLM_INP_LTH_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi123 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi123Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:BLM_INP_LTH_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:BLM_INP_LTH_A") { field(DESC, "BCS_BLM_Input_Lat_A") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb123",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb123") #! Field("PLC:BSY0:PP09:30BSY_RDAb123.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb123.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb123.FLNK","PPS:SYSE:1:BLM_INP_LTH_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb123.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb123.VAL") #! Record("PPS:SYSE:1:BLM_INP_LTH_A_calc",260,18,0,1,"PPS:SYSE:1:BLM_INP_LTH_A_calc") #! Field("PPS:SYSE:1:BLM_INP_LTH_A_calc.INPA",16777215,0,"PPS:SYSE:1:BLM_INP_LTH_A_calc.INPA") #! Link("PPS:SYSE:1:BLM_INP_LTH_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb123.VAL") #! Field("PPS:SYSE:1:BLM_INP_LTH_A_calc.INPB",16777215,1,"PPS:SYSE:1:BLM_INP_LTH_A_calc.INPB") #! Field("PPS:SYSE:1:BLM_INP_LTH_A_calc.OUT",16777215,1,"PPS:SYSE:1:BLM_INP_LTH_A_calc.OUT") #! Link("PPS:SYSE:1:BLM_INP_LTH_A_calc.OUT","PPS:SYSE:1:BLM_INP_LTH_A.VAL") #! Record("PPS:SYSE:1:BLM_INP_LTH_A",500,20,0,0,"PPS:SYSE:1:BLM_INP_LTH_A") #! Field("PPS:SYSE:1:BLM_INP_LTH_A.VAL",16777215,1,"PPS:SYSE:1:BLM_INP_LTH_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi121") { field(DESC, "Port 30BSY_RDA bit 121") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 121, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:LI30:1:SECURE_INP_LTH_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi121Valid") { field(INPA, "PLC:BSY0:PP09:Bi121.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:LI30:1:SECURE_INP_LTH_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:LI30:1:SECURE_INP_LTH_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi121 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi121Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:LI30:1:SECURE_INP_LTH_A PP MS") field(ASG, "Internal") } record(bi, "PPS:LI30:1:SECURE_INP_LTH_A") { field(DESC, "S30_Secure_Input_A") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb121",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb121") #! Field("PLC:BSY0:PP09:30BSY_RDAb121.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb121.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb121.FLNK","PPS:LI30:1:SECURE_INP_LTH_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb121.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb121.VAL") #! Record("PPS:LI30:1:SECURE_INP_LTH_A_calc",260,18,0,1,"PPS:LI30:1:SECURE_INP_LTH_A_calc") #! Field("PPS:LI30:1:SECURE_INP_LTH_A_calc.INPA",16777215,0,"PPS:LI30:1:SECURE_INP_LTH_A_calc.INPA") #! Link("PPS:LI30:1:SECURE_INP_LTH_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb121.VAL") #! Field("PPS:LI30:1:SECURE_INP_LTH_A_calc.INPB",16777215,1,"PPS:LI30:1:SECURE_INP_LTH_A_calc.INPB") #! Field("PPS:LI30:1:SECURE_INP_LTH_A_calc.OUT",16777215,1,"PPS:LI30:1:SECURE_INP_LTH_A_calc.OUT") #! Link("PPS:LI30:1:SECURE_INP_LTH_A_calc.OUT","PPS:LI30:1:SECURE_INP_LTH_A.VAL") #! Record("PPS:LI30:1:SECURE_INP_LTH_A",500,20,0,0,"PPS:LI30:1:SECURE_INP_LTH_A") #! Field("PPS:LI30:1:SECURE_INP_LTH_A.VAL",16777215,1,"PPS:LI30:1:SECURE_INP_LTH_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi120") { field(DESC, "Port 30BSY_RDA bit 120") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 120, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:BSY0:1:SECURE_INP_LTH_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi120Valid") { field(INPA, "PLC:BSY0:PP09:Bi120.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:BSY0:1:SECURE_INP_LTH_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:BSY0:1:SECURE_INP_LTH_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi120 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi120Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:BSY0:1:SECURE_INP_LTH_A PP MS") field(ASG, "Internal") } record(bi, "PPS:BSY0:1:SECURE_INP_LTH_A") { field(DESC, "BSY_Secure_Input_A") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb120",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb120") #! Field("PLC:BSY0:PP09:30BSY_RDAb120.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb120.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb120.FLNK","PPS:BSY0:1:SECURE_INP_LTH_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb120.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb120.VAL") #! Record("PPS:BSY0:1:SECURE_INP_LTH_A_calc",260,18,0,1,"PPS:BSY0:1:SECURE_INP_LTH_A_calc") #! Field("PPS:BSY0:1:SECURE_INP_LTH_A_calc.INPA",16777215,0,"PPS:BSY0:1:SECURE_INP_LTH_A_calc.INPA") #! Link("PPS:BSY0:1:SECURE_INP_LTH_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb120.VAL") #! Field("PPS:BSY0:1:SECURE_INP_LTH_A_calc.INPB",16777215,1,"PPS:BSY0:1:SECURE_INP_LTH_A_calc.INPB") #! Field("PPS:BSY0:1:SECURE_INP_LTH_A_calc.OUT",16777215,1,"PPS:BSY0:1:SECURE_INP_LTH_A_calc.OUT") #! Link("PPS:BSY0:1:SECURE_INP_LTH_A_calc.OUT","PPS:BSY0:1:SECURE_INP_LTH_A.VAL") #! Record("PPS:BSY0:1:SECURE_INP_LTH_A",500,20,0,0,"PPS:BSY0:1:SECURE_INP_LTH_A") #! Field("PPS:BSY0:1:SECURE_INP_LTH_A.VAL",16777215,1,"PPS:BSY0:1:SECURE_INP_LTH_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi135") { field(DESC, "Port 30BSY_RDA bit 135") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 135, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:ESA0:1:RADREADY_INP_LTH_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi135Valid") { field(INPA, "PLC:BSY0:PP09:Bi135.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:ESA0:1:RADREADY_INP_LTH_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:ESA0:1:RADREADY_INP_LTH_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi135 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi135Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:ESA0:1:RADREADY_INP_LTH_A PP MS") field(ASG, "Internal") } record(bi, "PPS:ESA0:1:RADREADY_INP_LTH_A") { field(DESC, "ESA_Rad_Ready_Input_A") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb135",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb135") #! Field("PLC:BSY0:PP09:30BSY_RDAb135.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb135.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb135.FLNK","PPS:ESA0:1:RADREADY_INP_LTH_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb135.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb135.VAL") #! Record("PPS:ESA0:1:RADREADY_INP_LTH_A_calc",260,18,0,1,"PPS:ESA0:1:RADREADY_INP_LTH_A_calc") #! Field("PPS:ESA0:1:RADREADY_INP_LTH_A_calc.INPA",16777215,0,"PPS:ESA0:1:RADREADY_INP_LTH_A_calc.INPA") #! Link("PPS:ESA0:1:RADREADY_INP_LTH_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb135.VAL") #! Field("PPS:ESA0:1:RADREADY_INP_LTH_A_calc.INPB",16777215,1,"PPS:ESA0:1:RADREADY_INP_LTH_A_calc.INPB") #! Field("PPS:ESA0:1:RADREADY_INP_LTH_A_calc.OUT",16777215,1,"PPS:ESA0:1:RADREADY_INP_LTH_A_calc.OUT") #! Link("PPS:ESA0:1:RADREADY_INP_LTH_A_calc.OUT","PPS:ESA0:1:RADREADY_INP_LTH_A.VAL") #! Record("PPS:ESA0:1:RADREADY_INP_LTH_A",500,20,0,0,"PPS:ESA0:1:RADREADY_INP_LTH_A") #! Field("PPS:ESA0:1:RADREADY_INP_LTH_A.VAL",16777215,1,"PPS:ESA0:1:RADREADY_INP_LTH_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi134") { field(DESC, "Port 30BSY_RDA bit 134") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 134, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "BTM:BSY0:1:SUM_OK_LTH_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi134Valid") { field(INPA, "PLC:BSY0:PP09:Bi134.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "BTM:BSY0:1:SUM_OK_LTH_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "BTM:BSY0:1:SUM_OK_LTH_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi134 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi134Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "BTM:BSY0:1:SUM_OK_LTH_A PP MS") field(ASG, "Internal") } record(bi, "BTM:BSY0:1:SUM_OK_LTH_A") { field(DESC, "BTM_Sum_OK_Input_A") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb134",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb134") #! Field("PLC:BSY0:PP09:30BSY_RDAb134.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb134.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb134.FLNK","BTM:BSY0:1:SUM_OK_LTH_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb134.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb134.VAL") #! Record("BTM:BSY0:1:SUM_OK_LTH_A_calc",260,18,0,1,"BTM:BSY0:1:SUM_OK_LTH_A_calc") #! Field("BTM:BSY0:1:SUM_OK_LTH_A_calc.INPA",16777215,0,"BTM:BSY0:1:SUM_OK_LTH_A_calc.INPA") #! Link("BTM:BSY0:1:SUM_OK_LTH_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb134.VAL") #! Field("BTM:BSY0:1:SUM_OK_LTH_A_calc.INPB",16777215,1,"BTM:BSY0:1:SUM_OK_LTH_A_calc.INPB") #! Field("BTM:BSY0:1:SUM_OK_LTH_A_calc.OUT",16777215,1,"BTM:BSY0:1:SUM_OK_LTH_A_calc.OUT") #! Link("BTM:BSY0:1:SUM_OK_LTH_A_calc.OUT","BTM:BSY0:1:SUM_OK_LTH_A.VAL") #! Record("BTM:BSY0:1:SUM_OK_LTH_A",500,20,0,0,"BTM:BSY0:1:SUM_OK_LTH_A") #! Field("BTM:BSY0:1:SUM_OK_LTH_A.VAL",16777215,1,"BTM:BSY0:1:SUM_OK_LTH_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi133") { field(DESC, "Port 30BSY_RDA bit 133") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 133, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "BSOC:SYSE:1:GROUPC_LTH_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi133Valid") { field(INPA, "PLC:BSY0:PP09:Bi133.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "BSOC:SYSE:1:GROUPC_LTH_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "BSOC:SYSE:1:GROUPC_LTH_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi133 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi133Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "BSOC:SYSE:1:GROUPC_LTH_A PP MS") field(ASG, "Internal") } record(bi, "BSOC:SYSE:1:GROUPC_LTH_A") { field(DESC, "BSOIC_GrpC_OK_Input_A") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb133",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb133") #! Field("PLC:BSY0:PP09:30BSY_RDAb133.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb133.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb133.FLNK","BSOC:SYSE:1:GROUPC_LTH_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb133.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb133.VAL") #! Record("BSOC:SYSE:1:GROUPC_LTH_A_calc",260,18,0,1,"BSOC:SYSE:1:GROUPC_LTH_A_calc") #! Field("BSOC:SYSE:1:GROUPC_LTH_A_calc.INPA",16777215,0,"BSOC:SYSE:1:GROUPC_LTH_A_calc.INPA") #! Link("BSOC:SYSE:1:GROUPC_LTH_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb133.VAL") #! Field("BSOC:SYSE:1:GROUPC_LTH_A_calc.INPB",16777215,1,"BSOC:SYSE:1:GROUPC_LTH_A_calc.INPB") #! Field("BSOC:SYSE:1:GROUPC_LTH_A_calc.OUT",16777215,1,"BSOC:SYSE:1:GROUPC_LTH_A_calc.OUT") #! Link("BSOC:SYSE:1:GROUPC_LTH_A_calc.OUT","BSOC:SYSE:1:GROUPC_LTH_A.VAL") #! Record("BSOC:SYSE:1:GROUPC_LTH_A",500,20,0,0,"BSOC:SYSE:1:GROUPC_LTH_A") #! Field("BSOC:SYSE:1:GROUPC_LTH_A.VAL",16777215,1,"BSOC:SYSE:1:GROUPC_LTH_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi132") { field(DESC, "Port 30BSY_RDA bit 132") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 132, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:UND0:1:SECURE_INP_LTH_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi132Valid") { field(INPA, "PLC:BSY0:PP09:Bi132.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:UND0:1:SECURE_INP_LTH_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:UND0:1:SECURE_INP_LTH_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi132 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi132Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:UND0:1:SECURE_INP_LTH_A PP MS") field(ASG, "Internal") } record(bi, "PPS:UND0:1:SECURE_INP_LTH_A") { field(DESC, "LCLS_Secure_Input_A") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb132",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb132") #! Field("PLC:BSY0:PP09:30BSY_RDAb132.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb132.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb132.FLNK","PPS:UND0:1:SECURE_INP_LTH_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb132.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb132.VAL") #! Record("PPS:UND0:1:SECURE_INP_LTH_A_calc",260,18,0,1,"PPS:UND0:1:SECURE_INP_LTH_A_calc") #! Field("PPS:UND0:1:SECURE_INP_LTH_A_calc.INPA",16777215,0,"PPS:UND0:1:SECURE_INP_LTH_A_calc.INPA") #! Link("PPS:UND0:1:SECURE_INP_LTH_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb132.VAL") #! Field("PPS:UND0:1:SECURE_INP_LTH_A_calc.INPB",16777215,1,"PPS:UND0:1:SECURE_INP_LTH_A_calc.INPB") #! Field("PPS:UND0:1:SECURE_INP_LTH_A_calc.OUT",16777215,1,"PPS:UND0:1:SECURE_INP_LTH_A_calc.OUT") #! Link("PPS:UND0:1:SECURE_INP_LTH_A_calc.OUT","PPS:UND0:1:SECURE_INP_LTH_A.VAL") #! Record("PPS:UND0:1:SECURE_INP_LTH_A",500,20,0,0,"PPS:UND0:1:SECURE_INP_LTH_A") #! Field("PPS:UND0:1:SECURE_INP_LTH_A.VAL",16777215,1,"PPS:UND0:1:SECURE_INP_LTH_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi131") { field(DESC, "Port 30BSY_RDA bit 131") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 131, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi131Valid") { field(INPA, "PLC:BSY0:PP09:Bi131.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi131 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi131Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_A") { field(DESC, "Local_Beam_Enable_Keysw_A") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb131",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb131") #! Field("PLC:BSY0:PP09:30BSY_RDAb131.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb131.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb131.FLNK","PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb131.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb131.VAL") #! Record("PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_A_calc",260,18,0,1,"PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_A_calc") #! Field("PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_A_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_A_calc.INPA") #! Link("PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb131.VAL") #! Field("PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_A_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_A_calc.INPB") #! Field("PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_A_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_A_calc.OUT") #! Link("PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_A_calc.OUT","PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_A.VAL") #! Record("PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_A",500,20,0,0,"PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_A") #! Field("PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_A.VAL",16777215,1,"PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi130") { field(DESC, "Port 30BSY_RDA bit 130") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 130, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:SYSE:1:BSOIC_ESC_LTH_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi130Valid") { field(INPA, "PLC:BSY0:PP09:Bi130.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:BSOIC_ESC_LTH_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:BSOIC_ESC_LTH_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi130 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi130Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:BSOIC_ESC_LTH_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:BSOIC_ESC_LTH_A") { field(DESC, "BSOIC escalation Lat A") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb130",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb130") #! Field("PLC:BSY0:PP09:30BSY_RDAb130.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb130.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb130.FLNK","PPS:SYSE:1:BSOIC_ESC_LTH_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb130.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb130.VAL") #! Record("PPS:SYSE:1:BSOIC_ESC_LTH_A_calc",260,18,0,1,"PPS:SYSE:1:BSOIC_ESC_LTH_A_calc") #! Field("PPS:SYSE:1:BSOIC_ESC_LTH_A_calc.INPA",16777215,0,"PPS:SYSE:1:BSOIC_ESC_LTH_A_calc.INPA") #! Link("PPS:SYSE:1:BSOIC_ESC_LTH_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb130.VAL") #! Field("PPS:SYSE:1:BSOIC_ESC_LTH_A_calc.INPB",16777215,1,"PPS:SYSE:1:BSOIC_ESC_LTH_A_calc.INPB") #! Field("PPS:SYSE:1:BSOIC_ESC_LTH_A_calc.OUT",16777215,1,"PPS:SYSE:1:BSOIC_ESC_LTH_A_calc.OUT") #! Link("PPS:SYSE:1:BSOIC_ESC_LTH_A_calc.OUT","PPS:SYSE:1:BSOIC_ESC_LTH_A.VAL") #! Record("PPS:SYSE:1:BSOIC_ESC_LTH_A",500,20,0,0,"PPS:SYSE:1:BSOIC_ESC_LTH_A") #! Field("PPS:SYSE:1:BSOIC_ESC_LTH_A.VAL",16777215,1,"PPS:SYSE:1:BSOIC_ESC_LTH_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi129") { field(DESC, "Port 30BSY_RDA bit 129") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 129, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:SYSE:1:BCS_FAULT_LTH_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi129Valid") { field(INPA, "PLC:BSY0:PP09:Bi129.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:BCS_FAULT_LTH_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:BCS_FAULT_LTH_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi129 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi129Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:BCS_FAULT_LTH_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:BCS_FAULT_LTH_A") { field(DESC, "BCS BEAM ON Fault A") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb129",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb129") #! Field("PLC:BSY0:PP09:30BSY_RDAb129.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb129.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb129.FLNK","PPS:SYSE:1:BCS_FAULT_LTH_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb129.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb129.VAL") #! Record("PPS:SYSE:1:BCS_FAULT_LTH_A_calc",260,18,0,1,"PPS:SYSE:1:BCS_FAULT_LTH_A_calc") #! Field("PPS:SYSE:1:BCS_FAULT_LTH_A_calc.INPA",16777215,0,"PPS:SYSE:1:BCS_FAULT_LTH_A_calc.INPA") #! Link("PPS:SYSE:1:BCS_FAULT_LTH_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb129.VAL") #! Field("PPS:SYSE:1:BCS_FAULT_LTH_A_calc.INPB",16777215,1,"PPS:SYSE:1:BCS_FAULT_LTH_A_calc.INPB") #! Field("PPS:SYSE:1:BCS_FAULT_LTH_A_calc.OUT",16777215,1,"PPS:SYSE:1:BCS_FAULT_LTH_A_calc.OUT") #! Link("PPS:SYSE:1:BCS_FAULT_LTH_A_calc.OUT","PPS:SYSE:1:BCS_FAULT_LTH_A.VAL") #! Record("PPS:SYSE:1:BCS_FAULT_LTH_A",500,20,0,0,"PPS:SYSE:1:BCS_FAULT_LTH_A") #! Field("PPS:SYSE:1:BCS_FAULT_LTH_A.VAL",16777215,1,"PPS:SYSE:1:BCS_FAULT_LTH_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi128") { field(DESC, "Port 30BSY_RDA bit 128") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 128, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi128Valid") { field(INPA, "PLC:BSY0:PP09:Bi128.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi128 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi128Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_A") { field(DESC, "ACR_Beam_Enable_Keysw_A") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb128",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb128") #! Field("PLC:BSY0:PP09:30BSY_RDAb128.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb128.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb128.FLNK","PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb128.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb128.VAL") #! Record("PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_A_calc",260,18,0,1,"PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_A_calc") #! Field("PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_A_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_A_calc.INPA") #! Link("PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb128.VAL") #! Field("PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_A_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_A_calc.INPB") #! Field("PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_A_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_A_calc.OUT") #! Link("PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_A_calc.OUT","PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_A.VAL") #! Record("PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_A",500,20,0,0,"PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_A") #! Field("PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_A.VAL",16777215,1,"PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi143") { field(DESC, "Port 30BSY_RDA bit 143") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 143, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:SYSE:1:30BSY:INTLK_LTH_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi143Valid") { field(INPA, "PLC:BSY0:PP09:Bi143.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:INTLK_LTH_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:INTLK_LTH_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi143 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi143Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:INTLK_LTH_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:INTLK_LTH_A") { field(DESC, "30-BSY Glbl. intlk (spare) A") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb143",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb143") #! Field("PLC:BSY0:PP09:30BSY_RDAb143.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb143.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb143.FLNK","PPS:SYSE:1:30BSY:INTLK_LTH_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb143.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb143.VAL") #! Record("PPS:SYSE:1:30BSY:INTLK_LTH_A_calc",260,18,0,1,"PPS:SYSE:1:30BSY:INTLK_LTH_A_calc") #! Field("PPS:SYSE:1:30BSY:INTLK_LTH_A_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:INTLK_LTH_A_calc.INPA") #! Link("PPS:SYSE:1:30BSY:INTLK_LTH_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb143.VAL") #! Field("PPS:SYSE:1:30BSY:INTLK_LTH_A_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:INTLK_LTH_A_calc.INPB") #! Field("PPS:SYSE:1:30BSY:INTLK_LTH_A_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:INTLK_LTH_A_calc.OUT") #! Link("PPS:SYSE:1:30BSY:INTLK_LTH_A_calc.OUT","PPS:SYSE:1:30BSY:INTLK_LTH_A.VAL") #! Record("PPS:SYSE:1:30BSY:INTLK_LTH_A",500,20,0,0,"PPS:SYSE:1:30BSY:INTLK_LTH_A") #! Field("PPS:SYSE:1:30BSY:INTLK_LTH_A.VAL",16777215,1,"PPS:SYSE:1:30BSY:INTLK_LTH_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi142") { field(DESC, "Port 30BSY_RDA bit 142") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 142, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:SYSE:1:CU:BEAMOK_LTH_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi142Valid") { field(INPA, "PLC:BSY0:PP09:Bi142.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:CU:BEAMOK_LTH_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:CU:BEAMOK_LTH_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi142 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi142Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:CU:BEAMOK_LTH_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:CU:BEAMOK_LTH_A") { field(DESC, "Cu beam config OK (spare) A") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb142",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb142") #! Field("PLC:BSY0:PP09:30BSY_RDAb142.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb142.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb142.FLNK","PPS:SYSE:1:CU:BEAMOK_LTH_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb142.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb142.VAL") #! Record("PPS:SYSE:1:CU:BEAMOK_LTH_A_calc",260,18,0,1,"PPS:SYSE:1:CU:BEAMOK_LTH_A_calc") #! Field("PPS:SYSE:1:CU:BEAMOK_LTH_A_calc.INPA",16777215,0,"PPS:SYSE:1:CU:BEAMOK_LTH_A_calc.INPA") #! Link("PPS:SYSE:1:CU:BEAMOK_LTH_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb142.VAL") #! Field("PPS:SYSE:1:CU:BEAMOK_LTH_A_calc.INPB",16777215,1,"PPS:SYSE:1:CU:BEAMOK_LTH_A_calc.INPB") #! Field("PPS:SYSE:1:CU:BEAMOK_LTH_A_calc.OUT",16777215,1,"PPS:SYSE:1:CU:BEAMOK_LTH_A_calc.OUT") #! Link("PPS:SYSE:1:CU:BEAMOK_LTH_A_calc.OUT","PPS:SYSE:1:CU:BEAMOK_LTH_A.VAL") #! Record("PPS:SYSE:1:CU:BEAMOK_LTH_A",500,20,0,0,"PPS:SYSE:1:CU:BEAMOK_LTH_A") #! Field("PPS:SYSE:1:CU:BEAMOK_LTH_A.VAL",16777215,1,"PPS:SYSE:1:CU:BEAMOK_LTH_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi141") { field(DESC, "Port 30BSY_RDA bit 141") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 141, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:SYSE:1:SC:BEAMOK_LTH_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi141Valid") { field(INPA, "PLC:BSY0:PP09:Bi141.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:SC:BEAMOK_LTH_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:SC:BEAMOK_LTH_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi141 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi141Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:SC:BEAMOK_LTH_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:SC:BEAMOK_LTH_A") { field(DESC, "SC beam config OK (spare) A") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb141",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb141") #! Field("PLC:BSY0:PP09:30BSY_RDAb141.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb141.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb141.FLNK","PPS:SYSE:1:SC:BEAMOK_LTH_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb141.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb141.VAL") #! Record("PPS:SYSE:1:SC:BEAMOK_LTH_A_calc",260,18,0,1,"PPS:SYSE:1:SC:BEAMOK_LTH_A_calc") #! Field("PPS:SYSE:1:SC:BEAMOK_LTH_A_calc.INPA",16777215,0,"PPS:SYSE:1:SC:BEAMOK_LTH_A_calc.INPA") #! Link("PPS:SYSE:1:SC:BEAMOK_LTH_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb141.VAL") #! Field("PPS:SYSE:1:SC:BEAMOK_LTH_A_calc.INPB",16777215,1,"PPS:SYSE:1:SC:BEAMOK_LTH_A_calc.INPB") #! Field("PPS:SYSE:1:SC:BEAMOK_LTH_A_calc.OUT",16777215,1,"PPS:SYSE:1:SC:BEAMOK_LTH_A_calc.OUT") #! Link("PPS:SYSE:1:SC:BEAMOK_LTH_A_calc.OUT","PPS:SYSE:1:SC:BEAMOK_LTH_A.VAL") #! Record("PPS:SYSE:1:SC:BEAMOK_LTH_A",500,20,0,0,"PPS:SYSE:1:SC:BEAMOK_LTH_A") #! Field("PPS:SYSE:1:SC:BEAMOK_LTH_A.VAL",16777215,1,"PPS:SYSE:1:SC:BEAMOK_LTH_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi139") { field(DESC, "Port 30BSY_RDA bit 139") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 139, 1, 1)") field(ZNAM, "Not_Ok") field(ONAM, "Ok") field(FLNK, "PPS:SYSE:1:30BSY:HRTBT_OK_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi139Valid") { field(INPA, "PLC:BSY0:PP09:Bi139.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:HRTBT_OK_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:HRTBT_OK_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi139 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi139Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:HRTBT_OK_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:HRTBT_OK_A") { field(DESC, "Heartbeat OK A") field(ZNAM, "Not_Ok") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb139",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb139") #! Field("PLC:BSY0:PP09:30BSY_RDAb139.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb139.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb139.FLNK","PPS:SYSE:1:30BSY:HRTBT_OK_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb139.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb139.VAL") #! Record("PPS:SYSE:1:30BSY:HRTBT_OK_A_calc",260,18,0,1,"PPS:SYSE:1:30BSY:HRTBT_OK_A_calc") #! Field("PPS:SYSE:1:30BSY:HRTBT_OK_A_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:HRTBT_OK_A_calc.INPA") #! Link("PPS:SYSE:1:30BSY:HRTBT_OK_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb139.VAL") #! Field("PPS:SYSE:1:30BSY:HRTBT_OK_A_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:HRTBT_OK_A_calc.INPB") #! Field("PPS:SYSE:1:30BSY:HRTBT_OK_A_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:HRTBT_OK_A_calc.OUT") #! Link("PPS:SYSE:1:30BSY:HRTBT_OK_A_calc.OUT","PPS:SYSE:1:30BSY:HRTBT_OK_A.VAL") #! Record("PPS:SYSE:1:30BSY:HRTBT_OK_A",500,20,0,0,"PPS:SYSE:1:30BSY:HRTBT_OK_A") #! Field("PPS:SYSE:1:30BSY:HRTBT_OK_A.VAL",16777215,1,"PPS:SYSE:1:30BSY:HRTBT_OK_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi138") { field(DESC, "Port 30BSY_RDA bit 138") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 138, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "STPR:SYSE:1:INSERT_FAILED_LTH_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi138Valid") { field(INPA, "PLC:BSY0:PP09:Bi138.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "STPR:SYSE:1:INSERT_FAILED_LTH_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "STPR:SYSE:1:INSERT_FAILED_LTH_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi138 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi138Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "STPR:SYSE:1:INSERT_FAILED_LTH_A PP MS") field(ASG, "Internal") } record(bi, "STPR:SYSE:1:INSERT_FAILED_LTH_A") { field(DESC, "Stopper_Insert_Failed_A") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb138",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb138") #! Field("PLC:BSY0:PP09:30BSY_RDAb138.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb138.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb138.FLNK","STPR:SYSE:1:INSERT_FAILED_LTH_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb138.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb138.VAL") #! Record("STPR:SYSE:1:INSERT_FAILED_LTH_A_calc",260,18,0,1,"STPR:SYSE:1:INSERT_FAILED_LTH_A_calc") #! Field("STPR:SYSE:1:INSERT_FAILED_LTH_A_calc.INPA",16777215,0,"STPR:SYSE:1:INSERT_FAILED_LTH_A_calc.INPA") #! Link("STPR:SYSE:1:INSERT_FAILED_LTH_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb138.VAL") #! Field("STPR:SYSE:1:INSERT_FAILED_LTH_A_calc.INPB",16777215,1,"STPR:SYSE:1:INSERT_FAILED_LTH_A_calc.INPB") #! Field("STPR:SYSE:1:INSERT_FAILED_LTH_A_calc.OUT",16777215,1,"STPR:SYSE:1:INSERT_FAILED_LTH_A_calc.OUT") #! Link("STPR:SYSE:1:INSERT_FAILED_LTH_A_calc.OUT","STPR:SYSE:1:INSERT_FAILED_LTH_A.VAL") #! Record("STPR:SYSE:1:INSERT_FAILED_LTH_A",500,20,0,0,"STPR:SYSE:1:INSERT_FAILED_LTH_A") #! Field("STPR:SYSE:1:INSERT_FAILED_LTH_A.VAL",16777215,1,"STPR:SYSE:1:INSERT_FAILED_LTH_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi137") { field(DESC, "Port 30BSY_RDA bit 137") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 137, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:SYSE:1:30BSY:HRTBT_OK_LTH_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi137Valid") { field(INPA, "PLC:BSY0:PP09:Bi137.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:HRTBT_OK_LTH_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:HRTBT_OK_LTH_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi137 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi137Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:HRTBT_OK_LTH_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:HRTBT_OK_LTH_A") { field(DESC, "Heartbeat OK Latched A") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb137",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb137") #! Field("PLC:BSY0:PP09:30BSY_RDAb137.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb137.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb137.FLNK","PPS:SYSE:1:30BSY:HRTBT_OK_LTH_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb137.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb137.VAL") #! Record("PPS:SYSE:1:30BSY:HRTBT_OK_LTH_A_calc",260,18,0,1,"PPS:SYSE:1:30BSY:HRTBT_OK_LTH_A_calc") #! Field("PPS:SYSE:1:30BSY:HRTBT_OK_LTH_A_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:HRTBT_OK_LTH_A_calc.INPA") #! Link("PPS:SYSE:1:30BSY:HRTBT_OK_LTH_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb137.VAL") #! Field("PPS:SYSE:1:30BSY:HRTBT_OK_LTH_A_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:HRTBT_OK_LTH_A_calc.INPB") #! Field("PPS:SYSE:1:30BSY:HRTBT_OK_LTH_A_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:HRTBT_OK_LTH_A_calc.OUT") #! Link("PPS:SYSE:1:30BSY:HRTBT_OK_LTH_A_calc.OUT","PPS:SYSE:1:30BSY:HRTBT_OK_LTH_A.VAL") #! Record("PPS:SYSE:1:30BSY:HRTBT_OK_LTH_A",500,20,0,0,"PPS:SYSE:1:30BSY:HRTBT_OK_LTH_A") #! Field("PPS:SYSE:1:30BSY:HRTBT_OK_LTH_A.VAL",16777215,1,"PPS:SYSE:1:30BSY:HRTBT_OK_LTH_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi136") { field(DESC, "Port 30BSY_RDA bit 136") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 136, 1, 1)") field(ZNAM, "Not_Cleared") field(ONAM, "Cleared") field(FLNK, "PPS:SYSE:1:CU:HXR_CLEAR_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi136Valid") { field(INPA, "PLC:BSY0:PP09:Bi136.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:CU:HXR_CLEAR_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:CU:HXR_CLEAR_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi136 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi136Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:CU:HXR_CLEAR_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:CU:HXR_CLEAR_A") { field(DESC, "Cu line cleared to HXR A") field(ZNAM, "Not_Cleared") field(ONAM, "Cleared") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb136",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb136") #! Field("PLC:BSY0:PP09:30BSY_RDAb136.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb136.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb136.FLNK","PPS:SYSE:1:CU:HXR_CLEAR_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb136.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb136.VAL") #! Record("PPS:SYSE:1:CU:HXR_CLEAR_A_calc",260,18,0,1,"PPS:SYSE:1:CU:HXR_CLEAR_A_calc") #! Field("PPS:SYSE:1:CU:HXR_CLEAR_A_calc.INPA",16777215,0,"PPS:SYSE:1:CU:HXR_CLEAR_A_calc.INPA") #! Link("PPS:SYSE:1:CU:HXR_CLEAR_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb136.VAL") #! Field("PPS:SYSE:1:CU:HXR_CLEAR_A_calc.INPB",16777215,1,"PPS:SYSE:1:CU:HXR_CLEAR_A_calc.INPB") #! Field("PPS:SYSE:1:CU:HXR_CLEAR_A_calc.OUT",16777215,1,"PPS:SYSE:1:CU:HXR_CLEAR_A_calc.OUT") #! Link("PPS:SYSE:1:CU:HXR_CLEAR_A_calc.OUT","PPS:SYSE:1:CU:HXR_CLEAR_A.VAL") #! Record("PPS:SYSE:1:CU:HXR_CLEAR_A",500,20,0,0,"PPS:SYSE:1:CU:HXR_CLEAR_A") #! Field("PPS:SYSE:1:CU:HXR_CLEAR_A.VAL",16777215,1,"PPS:SYSE:1:CU:HXR_CLEAR_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi151") { field(DESC, "Port 30BSY_RDA bit 151") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 151, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:SYSE:1:CU:HXR_CLEAR_LTH_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi151Valid") { field(INPA, "PLC:BSY0:PP09:Bi151.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:CU:HXR_CLEAR_LTH_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:CU:HXR_CLEAR_LTH_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi151 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi151Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:CU:HXR_CLEAR_LTH_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:CU:HXR_CLEAR_LTH_A") { field(DESC, "Cu line cleared to HXR Lat A") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb151",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb151") #! Field("PLC:BSY0:PP09:30BSY_RDAb151.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb151.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb151.FLNK","PPS:SYSE:1:CU:HXR_CLEAR_LTH_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb151.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb151.VAL") #! Record("PPS:SYSE:1:CU:HXR_CLEAR_LTH_A_calc",260,18,0,1,"PPS:SYSE:1:CU:HXR_CLEAR_LTH_A_calc") #! Field("PPS:SYSE:1:CU:HXR_CLEAR_LTH_A_calc.INPA",16777215,0,"PPS:SYSE:1:CU:HXR_CLEAR_LTH_A_calc.INPA") #! Link("PPS:SYSE:1:CU:HXR_CLEAR_LTH_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb151.VAL") #! Field("PPS:SYSE:1:CU:HXR_CLEAR_LTH_A_calc.INPB",16777215,1,"PPS:SYSE:1:CU:HXR_CLEAR_LTH_A_calc.INPB") #! Field("PPS:SYSE:1:CU:HXR_CLEAR_LTH_A_calc.OUT",16777215,1,"PPS:SYSE:1:CU:HXR_CLEAR_LTH_A_calc.OUT") #! Link("PPS:SYSE:1:CU:HXR_CLEAR_LTH_A_calc.OUT","PPS:SYSE:1:CU:HXR_CLEAR_LTH_A.VAL") #! Record("PPS:SYSE:1:CU:HXR_CLEAR_LTH_A",500,20,0,0,"PPS:SYSE:1:CU:HXR_CLEAR_LTH_A") #! Field("PPS:SYSE:1:CU:HXR_CLEAR_LTH_A.VAL",16777215,1,"PPS:SYSE:1:CU:HXR_CLEAR_LTH_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi150") { field(DESC, "Port 30BSY_RDA bit 150") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 150, 1, 1)") field(ZNAM, "Not_Cleared") field(ONAM, "Cleared") field(FLNK, "PPS:SYSE:1:CU:SXR_CLEAR_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi150Valid") { field(INPA, "PLC:BSY0:PP09:Bi150.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:CU:SXR_CLEAR_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:CU:SXR_CLEAR_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi150 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi150Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:CU:SXR_CLEAR_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:CU:SXR_CLEAR_A") { field(DESC, "Cu line cleared to SXR A") field(ZNAM, "Not_Cleared") field(ONAM, "Cleared") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb150",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb150") #! Field("PLC:BSY0:PP09:30BSY_RDAb150.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb150.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb150.FLNK","PPS:SYSE:1:CU:SXR_CLEAR_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb150.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb150.VAL") #! Record("PPS:SYSE:1:CU:SXR_CLEAR_A_calc",260,18,0,1,"PPS:SYSE:1:CU:SXR_CLEAR_A_calc") #! Field("PPS:SYSE:1:CU:SXR_CLEAR_A_calc.INPA",16777215,0,"PPS:SYSE:1:CU:SXR_CLEAR_A_calc.INPA") #! Link("PPS:SYSE:1:CU:SXR_CLEAR_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb150.VAL") #! Field("PPS:SYSE:1:CU:SXR_CLEAR_A_calc.INPB",16777215,1,"PPS:SYSE:1:CU:SXR_CLEAR_A_calc.INPB") #! Field("PPS:SYSE:1:CU:SXR_CLEAR_A_calc.OUT",16777215,1,"PPS:SYSE:1:CU:SXR_CLEAR_A_calc.OUT") #! Link("PPS:SYSE:1:CU:SXR_CLEAR_A_calc.OUT","PPS:SYSE:1:CU:SXR_CLEAR_A.VAL") #! Record("PPS:SYSE:1:CU:SXR_CLEAR_A",500,20,0,0,"PPS:SYSE:1:CU:SXR_CLEAR_A") #! Field("PPS:SYSE:1:CU:SXR_CLEAR_A.VAL",16777215,1,"PPS:SYSE:1:CU:SXR_CLEAR_A.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP09:Bi149") { field(DESC, "Port 30BSY_RDA bit 149") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 149, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:SYSE:1:CU:SXR_CLEAR_LTH_A_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:Bi149Valid") { field(INPA, "PLC:BSY0:PP09:Bi149.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:CU:SXR_CLEAR_LTH_A_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:CU:SXR_CLEAR_LTH_A_calc") { field(INPA, "PLC:BSY0:PP09:Bi149 NPP NMS") field(INPB, "PLC:BSY0:PP09:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP09:Bi149Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:CU:SXR_CLEAR_LTH_A PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:CU:SXR_CLEAR_LTH_A") { field(DESC, "Cu line cleared to SXR Lat A") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP09:30BSY_RDAb149",20,19,0,0,"PLC:BSY0:PP09:30BSY_RDAb149") #! Field("PLC:BSY0:PP09:30BSY_RDAb149.FLNK",16777215,1,"PLC:BSY0:PP09:30BSY_RDAb149.FLNK") #! Link("PLC:BSY0:PP09:30BSY_RDAb149.FLNK","PPS:SYSE:1:CU:SXR_CLEAR_LTH_A_calc") #! Field("PLC:BSY0:PP09:30BSY_RDAb149.VAL",16777215,0,"PLC:BSY0:PP09:30BSY_RDAb149.VAL") #! Record("PPS:SYSE:1:CU:SXR_CLEAR_LTH_A_calc",260,18,0,1,"PPS:SYSE:1:CU:SXR_CLEAR_LTH_A_calc") #! Field("PPS:SYSE:1:CU:SXR_CLEAR_LTH_A_calc.INPA",16777215,0,"PPS:SYSE:1:CU:SXR_CLEAR_LTH_A_calc.INPA") #! Link("PPS:SYSE:1:CU:SXR_CLEAR_LTH_A_calc.INPA","PLC:BSY0:PP09:30BSY_RDAb149.VAL") #! Field("PPS:SYSE:1:CU:SXR_CLEAR_LTH_A_calc.INPB",16777215,1,"PPS:SYSE:1:CU:SXR_CLEAR_LTH_A_calc.INPB") #! Field("PPS:SYSE:1:CU:SXR_CLEAR_LTH_A_calc.OUT",16777215,1,"PPS:SYSE:1:CU:SXR_CLEAR_LTH_A_calc.OUT") #! Link("PPS:SYSE:1:CU:SXR_CLEAR_LTH_A_calc.OUT","PPS:SYSE:1:CU:SXR_CLEAR_LTH_A.VAL") #! Record("PPS:SYSE:1:CU:SXR_CLEAR_LTH_A",500,20,0,0,"PPS:SYSE:1:CU:SXR_CLEAR_LTH_A") #! Field("PPS:SYSE:1:CU:SXR_CLEAR_LTH_A.VAL",16777215,1,"PPS:SYSE:1:CU:SXR_CLEAR_LTH_A.VAL") record(bo, "PPS:SYSE:1:30BSY:RESET_INTLK_A") { field(DESC, "PPS_Interlock_Reset_A") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTA, 7, 1, 1)") field(ZNAM, "Off") field(ONAM, "Reset") field(ASG, "MCC") } record(bo, "PPS:SYSE:1:30BSY:PAUSEHB_A") { field(DESC, "PPS_Pause_Heartbeat_A") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTA, 6, 1, 1)") field(ZNAM, "Off") field(ONAM, "Reset") field(ASG, "MCC") } #============================================================================== # # Abs: PILZ PNOZ PLC interface for accessing the right table/segment # # Name: pilz-plc-request.template # # Facility: LCLS Personnel Protection Controls # # Auth: 11-Dec-2018, Garth Brown (GWBROWN) # Rev : dd-mmm-yyyy, Reviewer's Name (USERNAME) # # To specify which registers to read/write, you need to set the table and # segment (see PNOZ docs). This set of PVs keeps them set to the correct values # for reading either virtual I/O points or program stats such as project checksum. # The PNOZ PLC also has occasional communications dropouts, where the PLC stops # responding and the TCP connection must be reset. This happens more frequently # the more communication there is with the PLC. # While the vendor offers a PNOZ model with integrated Ethernet port which # allows readback at different modbus addresses instead of needing to set # table/segment, that interface also allows remote access to secure registers # and PLC programming. For safety, that type of remote access is not allowed in # our system. All of their products that don't allow remote access beyond our # safety specs also require table/segment setting to choose which registers to # read/write. # #----------------------------------------------------------------------------- # Mod: # #============================================================================== # record(longout, "PLC:BSY0:PP09:REQ_TABLE") { field(DESC, "Table to read/write") field(VAL, "9") field(OUT, "PLC:BSY0:PP09:REQ_TABLE_OUT PP") field(HOPR, "128") field(LOPR, "0") field(PINI, "YES") info(autosaveFields, "VAL") } # All the data we're interested in is: Tables 1 and 9, segment 1 # We only need table 1 once for check sums that don't change, so # read it for a short time during startup, then switch to table 9. record(calcout, "PLC:BSY0:PP09:TABLE_CYCLER") { field( OUT, "PLC:BSY0:PP09:REQ_TABLE PP") field( CALC, "A:=(A+1)%3600;A=20?1:9") field( INPA, "0") field( SCAN, ".5 second") } record(calcout, "PLC:BSY0:PP09:SEG_CYCLER") { field( OUT, "PLC:BSY0:PP09:REQ_SEG PP") field( CALC, "1") field( INPA, "0") field( SCAN, ".5 second") } # Records for disabling PVs when their reqest table isn't active record(calc, "PLC:BSY0:PP09:TABLE_9_SEG_1") { field( INPA, "PLC:BSY0:PP09:REQ_TABLE CP") field( INPB, "PLC:BSY0:PP09:REQ_SEG CP") field( INPC, "PLC:BSY0:PP09:REQ_TABLE_IN CP") field( INPD, "PLC:BSY0:PP09:REQ_SEG_IN CP") field(CALC, "A=9 & B=1 & C=9 & D=1") } record(calc, "PLC:BSY0:PP09:TABLE_1_SEG_1") { field( INPA, "PLC:BSY0:PP09:REQ_TABLE CP") field( INPB, "PLC:BSY0:PP09:REQ_SEG CP") field( INPC, "PLC:BSY0:PP09:REQ_TABLE_IN CP") field( INPD, "PLC:BSY0:PP09:REQ_SEG_IN CP") field(CALC, "A=1 & B=1 & C=1 & D=1") } # The target PVs don't use the data, but this has 8 forward links, # the number we need, while the fanout record only has 6. record(dfanout, "PLC:BSY0:PP09:REQ_TABLE_OUT") { field(OUTA, "PLC:BSY0:PP09:REQ_TABLE_BIT0_CALC.A PP") field(OUTB, "PLC:BSY0:PP09:REQ_TABLE_BIT1_CALC.A PP") field(OUTC, "PLC:BSY0:PP09:REQ_TABLE_BIT2_CALC.A PP") field(OUTD, "PLC:BSY0:PP09:REQ_TABLE_BIT3_CALC.A PP") field(OUTE, "PLC:BSY0:PP09:REQ_TABLE_BIT4_CALC.A PP") field(OUTF, "PLC:BSY0:PP09:REQ_TABLE_BIT5_CALC.A PP") field(OUTG, "PLC:BSY0:PP09:REQ_TABLE_BIT6_CALC.A PP") field(OUTH, "PLC:BSY0:PP09:REQ_TABLE_BIT7_CALC.A PP") field(SDIS, "PLC:BSY0:PP09:REQ_TABLE_IN.PACT") } # The simpler approach of writing to the table/segment every few seconds caused # TCP dropouts to happen several times an hour, compared to every day or two # when we only ever read/wrote table 9 segment 1. These calcout records reduce # the dropouts to around 5 a day by only writing the bits that need to change. record(calcout, "PLC:BSY0:PP09:REQ_TABLE_BIT0_CALC") { field(INPA, "PLC:BSY0:PP09:REQ_TABLE_OUT") field(INPB, "PLC:BSY0:PP09:TABLE_BIT0 MS") field(INPC, "PLC:BSY0:PP09:REQ_TABLE_BIT0 MS") field(CALC, "(B#C)||(B#(A&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "A&1") field(OUT, "PLC:BSY0:PP09:REQ_TABLE_BIT0 PP") } record(calcout, "PLC:BSY0:PP09:REQ_TABLE_BIT1_CALC") { field(INPA, "PLC:BSY0:PP09:REQ_TABLE_OUT") field(INPB, "PLC:BSY0:PP09:TABLE_BIT1 MS") field(INPC, "PLC:BSY0:PP09:REQ_TABLE_BIT1 MS") field(CALC, "(B#C)||(B#((A>>1)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>1)&1") field(OUT, "PLC:BSY0:PP09:REQ_TABLE_BIT1 PP") } record(calcout, "PLC:BSY0:PP09:REQ_TABLE_BIT2_CALC") { field(INPA, "PLC:BSY0:PP09:REQ_TABLE_OUT") field(INPB, "PLC:BSY0:PP09:TABLE_BIT2 MS") field(INPC, "PLC:BSY0:PP09:REQ_TABLE_BIT2 MS") field(CALC, "(B#C)||(B#((A>>2)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>2)&1") field(OUT, "PLC:BSY0:PP09:REQ_TABLE_BIT2 PP") } record(calcout, "PLC:BSY0:PP09:REQ_TABLE_BIT3_CALC") { field(INPA, "PLC:BSY0:PP09:REQ_TABLE_OUT") field(INPB, "PLC:BSY0:PP09:TABLE_BIT3 MS") field(INPC, "PLC:BSY0:PP09:REQ_TABLE_BIT3 MS") field(CALC, "(B#C)||(B#((A>>3)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>3)&1") field(OUT, "PLC:BSY0:PP09:REQ_TABLE_BIT3 PP") } record(calcout, "PLC:BSY0:PP09:REQ_TABLE_BIT4_CALC") { field(INPA, "PLC:BSY0:PP09:REQ_TABLE_OUT") field(INPB, "PLC:BSY0:PP09:TABLE_BIT4 MS") field(INPC, "PLC:BSY0:PP09:REQ_TABLE_BIT4 MS") field(CALC, "(B#C)||(B#((A>>4)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>4)&1") field(OUT, "PLC:BSY0:PP09:REQ_TABLE_BIT4 PP") } record(calcout, "PLC:BSY0:PP09:REQ_TABLE_BIT5_CALC") { field(INPA, "PLC:BSY0:PP09:REQ_TABLE_OUT") field(INPB, "PLC:BSY0:PP09:TABLE_BIT5 MS") field(INPC, "PLC:BSY0:PP09:REQ_TABLE_BIT5 MS") field(CALC, "(B#C)||(B#((A>>5)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>5)&1") field(OUT, "PLC:BSY0:PP09:REQ_TABLE_BIT5 PP") } record(calcout, "PLC:BSY0:PP09:REQ_TABLE_BIT6_CALC") { field(INPA, "PLC:BSY0:PP09:REQ_TABLE_OUT") field(INPB, "PLC:BSY0:PP09:TABLE_BIT6 MS") field(INPC, "PLC:BSY0:PP09:REQ_TABLE_BIT6 MS") field(CALC, "(B#C)||(B#((A>>6)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>6)&1") field(OUT, "PLC:BSY0:PP09:REQ_TABLE_BIT6 PP") } record(calcout, "PLC:BSY0:PP09:REQ_TABLE_BIT7_CALC") { field(INPA, "PLC:BSY0:PP09:REQ_TABLE_OUT") field(INPB, "PLC:BSY0:PP09:TABLE_BIT7 MS") field(INPC, "PLC:BSY0:PP09:REQ_TABLE_BIT7 MS") field(CALC, "(B#C)||(B#((A>>7)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>7)&1") field(OUT, "PLC:BSY0:PP09:REQ_TABLE_BIT7 PP") } record(calcout, "PLC:BSY0:PP09:REQ_TABLE_IN") { field(DESC, "Table readback") field(INPA, "PLC:BSY0:PP09:TABLE_BIT0 CP MS") field(INPB, "PLC:BSY0:PP09:TABLE_BIT1 CP MS") field(INPC, "PLC:BSY0:PP09:TABLE_BIT2 CP MS") field(INPD, "PLC:BSY0:PP09:TABLE_BIT3 CP MS") field(INPE, "PLC:BSY0:PP09:TABLE_BIT4 CP MS") field(INPF, "PLC:BSY0:PP09:TABLE_BIT5 CP MS") field(INPG, "PLC:BSY0:PP09:TABLE_BIT6 CP MS") field(INPH, "PLC:BSY0:PP09:TABLE_BIT7 CP MS") field(CALC, "A+B*2+C*4+D*8+E*16+F*32+G*64+H*128") field(OUT, "PLC:BSY0:PP09:REQ_TABLE PP MS") #field(SDIS, "PLC:BSY0:PP09:REQ_TABLE_OUT.PACT") } record(longout, "PLC:BSY0:PP09:REQ_SEG") { field(DESC, "Segment to read/write") field(VAL, "1") field(OUT, "PLC:BSY0:PP09:REQ_SEG_OUT PP") field(HOPR, "128") field(LOPR, "0") field(PINI, "YES") info(autosaveFields, "VAL") } # The target PVs don't use the data, but this has 8 forward links, # the number we need, while the fanout record only has 6. record(dfanout, "PLC:BSY0:PP09:REQ_SEG_OUT") { field(OUTA, "PLC:BSY0:PP09:REQ_SEG_BIT0_CALC.A PP") field(OUTB, "PLC:BSY0:PP09:REQ_SEG_BIT1_CALC.A PP") field(OUTC, "PLC:BSY0:PP09:REQ_SEG_BIT2_CALC.A PP") field(OUTD, "PLC:BSY0:PP09:REQ_SEG_BIT3_CALC.A PP") field(OUTE, "PLC:BSY0:PP09:REQ_SEG_BIT4_CALC.A PP") field(OUTF, "PLC:BSY0:PP09:REQ_SEG_BIT5_CALC.A PP") field(OUTG, "PLC:BSY0:PP09:REQ_SEG_BIT6_CALC.A PP") field(OUTH, "PLC:BSY0:PP09:REQ_SEG_BIT7_CALC.A PP") field(SDIS, "PLC:BSY0:PP09:REQ_SEG_IN.PACT") } record(calcout, "PLC:BSY0:PP09:REQ_SEG_BIT0_CALC") { field(INPA, "PLC:BSY0:PP09:REQ_SEG_OUT") field(INPB, "PLC:BSY0:PP09:SEG_BIT0 CP MS") field(CALC, "(B#C)||(B#(A&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "A&1") field(OUT, "PLC:BSY0:PP09:REQ_SEG_BIT0 PP") } record(calcout, "PLC:BSY0:PP09:REQ_SEG_BIT1_CALC") { field(INPA, "PLC:BSY0:PP09:REQ_SEG_OUT") field(INPB, "PLC:BSY0:PP09:SEG_BIT1 MS") field(INPC, "PLC:BSY0:PP09:REQ_SEG_BIT1 MS") field(CALC, "(B#C)||(B#((A>>1)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>1)&1") field(OUT, "PLC:BSY0:PP09:REQ_SEG_BIT1 PP") } record(calcout, "PLC:BSY0:PP09:REQ_SEG_BIT2_CALC") { field(INPA, "PLC:BSY0:PP09:REQ_SEG_OUT") field(INPB, "PLC:BSY0:PP09:SEG_BIT2 MS") field(INPC, "PLC:BSY0:PP09:REQ_SEG_BIT2 MS") field(CALC, "(B#C)||(B#((A>>2)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>2)&1") field(OUT, "PLC:BSY0:PP09:REQ_SEG_BIT2 PP") } record(calcout, "PLC:BSY0:PP09:REQ_SEG_BIT3_CALC") { field(INPA, "PLC:BSY0:PP09:REQ_SEG_OUT") field(INPB, "PLC:BSY0:PP09:SEG_BIT3 MS") field(INPC, "PLC:BSY0:PP09:REQ_SEG_BIT3 MS") field(CALC, "(B#C)||(B#((A>>3)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>3)&1") field(OUT, "PLC:BSY0:PP09:REQ_SEG_BIT3 PP") } record(calcout, "PLC:BSY0:PP09:REQ_SEG_BIT4_CALC") { field(INPA, "PLC:BSY0:PP09:REQ_SEG_OUT") field(INPB, "PLC:BSY0:PP09:SEG_BIT4 MS") field(INPC, "PLC:BSY0:PP09:REQ_SEG_BIT4 MS") field(CALC, "(B#C)||(B#((A>>4)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>4)&1") field(OUT, "PLC:BSY0:PP09:REQ_SEG_BIT4 PP") } record(calcout, "PLC:BSY0:PP09:REQ_SEG_BIT5_CALC") { field(INPA, "PLC:BSY0:PP09:REQ_SEG_OUT") field(INPB, "PLC:BSY0:PP09:SEG_BIT5 MS") field(INPC, "PLC:BSY0:PP09:REQ_SEG_BIT5 MS") field(CALC, "(B#C)||(B#((A>>5)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>5)&1") field(OUT, "PLC:BSY0:PP09:REQ_SEG_BIT5 PP") } record(calcout, "PLC:BSY0:PP09:REQ_SEG_BIT6_CALC") { field(INPA, "PLC:BSY0:PP09:REQ_SEG_OUT") field(INPB, "PLC:BSY0:PP09:SEG_BIT6 MS") field(INPC, "PLC:BSY0:PP09:REQ_SEG_BIT6 MS") field(CALC, "(B#C)||(B#((A>>6)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>6)&1") field(OUT, "PLC:BSY0:PP09:REQ_SEG_BIT6 PP") } record(calcout, "PLC:BSY0:PP09:REQ_SEG_BIT7_CALC") { field(INPA, "PLC:BSY0:PP09:REQ_SEG_OUT") field(INPB, "PLC:BSY0:PP09:SEG_BIT7 MS") field(INPC, "PLC:BSY0:PP09:REQ_SEG_BIT7 MS") field(CALC, "(B#C)||(B#((A>>7)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>7)&1") field(OUT, "PLC:BSY0:PP09:REQ_SEG_BIT7 PP") } record(calcout, "PLC:BSY0:PP09:REQ_SEG_IN") { field(DESC, "Segment readback") field(INPA, "PLC:BSY0:PP09:SEG_BIT0 CP MS") field(INPB, "PLC:BSY0:PP09:SEG_BIT1 CP MS") field(INPC, "PLC:BSY0:PP09:SEG_BIT2 CP MS") field(INPD, "PLC:BSY0:PP09:SEG_BIT3 CP MS") field(INPE, "PLC:BSY0:PP09:SEG_BIT4 CP MS") field(INPF, "PLC:BSY0:PP09:SEG_BIT5 CP MS") field(INPG, "PLC:BSY0:PP09:SEG_BIT6 CP MS") field(INPH, "PLC:BSY0:PP09:SEG_BIT7 CP MS") field(CALC, "A+B*2+C*4+D*8+E*16+F*32+G*64+H*128") field(OUT, "PLC:BSY0:PP09:REQ_SEG PP MS") field(SDIS, "PLC:BSY0:PP09:REQ_SEG_OUT.PACT") } record(bi, "PLC:BSY0:PP09:LED_X1") { field(DESC, "PPS-X1_LED") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 24, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP09:LED_X2") { field(DESC, "PPS-X2_LED") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 25, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP09:PWLED") { field(DESC, "PLC-Power_LED_A") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 26, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP09:RUNLED") { field(DESC, "PLC-Run_LED_A") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 27, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP09:DIAGLED") { field(DESC, "PLC-Diag_LED_A") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 28, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP09:FAULTLED") { field(DESC, "PLC-Fault_LED_A") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 29, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP09:IFAULTLED") { field(DESC, "PLC-IFault_LED_A") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 30, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP09:OFAULTLED") { field(DESC, "PLC-OFault_LED_A") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 31, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP09:TABLE_BIT7") { field(DESC, "Table Read bit 7") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 32, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP09:TABLE_BIT6") { field(DESC, "Table Read bit 6") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 33, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP09:TABLE_BIT5") { field(DESC, "Table Read bit 5") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 34, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP09:TABLE_BIT4") { field(DESC, "Table Read bit 4") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 35, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP09:TABLE_BIT3") { field(DESC, "Table Read bit 3") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 36, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP09:TABLE_BIT2") { field(DESC, "Table Read bit 2") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 37, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP09:TABLE_BIT1") { field(DESC, "Table Read bit 1") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 38, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP09:TABLE_BIT0") { field(DESC, "Table Read bit 0") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 39, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP09:SEG_BIT7") { field(DESC, "Segment Read bit 7") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 40, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP09:SEG_BIT6") { field(DESC, "Segment Read bit 6") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 41, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP09:SEG_BIT5") { field(DESC, "Segment Read bit 5") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 42, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP09:SEG_BIT4") { field(DESC, "Segment Read bit 4") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 43, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP09:SEG_BIT3") { field(DESC, "Segment Read bit 3") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 44, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP09:SEG_BIT2") { field(DESC, "Segment Read bit 2") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 45, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP09:SEG_BIT1") { field(DESC, "Segment Read bit 1") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 46, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP09:SEG_BIT0") { field(DESC, "Segment Read bit 0") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDA, 47, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bo, "PLC:BSY0:PP09:REQ_TABLE_BIT7") { field(DESC, "Table Request bit 7") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTA, 32, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP09:REQ_TABLE_BIT6") { field(DESC, "Table Request bit 6") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTA, 33, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP09:REQ_TABLE_BIT5") { field(DESC, "Table Request bit 5") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTA, 34, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP09:REQ_TABLE_BIT4") { field(DESC, "Table Request bit 4") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTA, 35, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP09:REQ_TABLE_BIT3") { field(DESC, "Table Request bit 3") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTA, 36, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP09:REQ_TABLE_BIT2") { field(DESC, "Table Request bit 2") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTA, 37, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP09:REQ_TABLE_BIT1") { field(DESC, "Table Request bit 1") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTA, 38, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP09:REQ_TABLE_BIT0") { field(DESC, "Table Request bit 0") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTA, 39, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP09:REQ_SEG_BIT7") { field(DESC, "Segment Request bit 7") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTA, 40, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP09:REQ_SEG_BIT6") { field(DESC, "Segment Request bit 6") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTA, 41, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP09:REQ_SEG_BIT5") { field(DESC, "Segment Request bit 5") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTA, 42, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP09:REQ_SEG_BIT4") { field(DESC, "Segment Request bit 4") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTA, 43, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP09:REQ_SEG_BIT3") { field(DESC, "Segment Request bit 3") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTA, 44, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP09:REQ_SEG_BIT2") { field(DESC, "Segment Request bit 2") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTA, 45, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP09:REQ_SEG_BIT1") { field(DESC, "Segment Request bit 1") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTA, 46, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP09:REQ_SEG_BIT0") { field(DESC, "Segment Request bit 0") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTA, 47, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(longin, "PLC:BSY0:PP09:w0") { field(DESC, "S30 BSY CHA Checksum") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_WDA, 0, 0xFFFF, 1)") field(ASG, "Internal") } record(longin, "PLC:BSY0:PP09:w1") { field(DESC, "S30 BSY CHA Checksum") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_WDA, 1, 0xFFFF, 1)") field(ASG, "Internal") } record(longin, "PLC:BSY0:PP09:w2") { field(DESC, "Active Table and Segment") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_WDA, 2, 0xFFFF, 1)") field(FLNK, "PLC:BSY0:PP09:CHECKSUM_SDIS PP MS") field(ASG, "Internal") } record(calc, "PLC:BSY0:PP09:CHECKSUM_SDIS") { field(INPA, "PLC:BSY0:PP09:w2 NPP MS") field(CALC, "A = 0X0101") } record(longin, "PLC:BSY0:PP09:w3") { field(DESC, "S30 BSY CHA Checksum") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_WDA, 3, 0xFFFF, 1)") field(FLNK, "PLC:BSY0:PP09:CHECKSUM_SAFE PP MS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:CHECKSUM_SAFE_calc") { field(INPA, "PLC:BSY0:PP09:w3 PP MS") field(INPB, "PLC:BSY0:PP09:CHECKSUM_SDIS PP MS") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PLC:BSY0:PP09:CHECKSUM_SAFE PP MS") field(ASG, "Internal") } record(longin, "PLC:BSY0:PP09:CHECKSUM_SAFE") { field(DESC, "Check Sum Safe") field(FLNK, "PLC:BSY0:PP09:CHECKSUM_SAFE_calc PP MS") info(autosaveFields_pass0, "VAL") } record(longin, "PLC:BSY0:PP09:w4") { field(DESC, "S30 BSY CHA Checksum") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_WDA, 4, 0xFFFF, 1)") field(FLNK, "PLC:BSY0:PP09:PROJ_CHECKSUM_calc") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:PROJ_CHECKSUM_calc") { field(INPA, "PLC:BSY0:PP09:w4 NPP MS") field(INPB, "PLC:BSY0:PP09:CHECKSUM_SDIS NPP MS") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PLC:BSY0:PP09:PROJ_CHECKSUM PP MS") field(ASG, "Internal") } record(longin, "PLC:BSY0:PP09:PROJ_CHECKSUM") { field(DESC, "Total Project Check Sum") info(autosaveFields_pass0, "VAL") } record(longin, "PLC:BSY0:PP09:w5") { field(DESC, "S30 BSY CHA Checksum") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_WDA, 5, 0xFFFF, 1)") field(FLNK, "PLC:BSY0:PP09:DAY_MONTH_calc") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:DAY_MONTH_calc") { field(INPA, "PLC:BSY0:PP09:w5 NPP MS") field(INPB, "PLC:BSY0:PP09:CHECKSUM_SDIS NPP MS") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PLC:BSY0:PP09:DAY_MONTH PP MS") field(ASG, "Internal") } record(longin, "PLC:BSY0:PP09:DAY_MONTH") { field(DESC, "Raw day and month") field(ASG, "Internal") } record(calc, "PLC:BSY0:PP09:PROJ_MONTH") { field(DESC, "Project creation day") field(INPA, "PLC:BSY0:PP09:DAY_MONTH CP MS") field(CALC, "A & 0xFF") info(autosaveFields_pass0, "VAL") } record(calc, "PLC:BSY0:PP09:PROJ_DAY") { field(DESC, "Project creation month") field(INPA, "PLC:BSY0:PP09:DAY_MONTH CP MS") field(CALC, "A >> 8") info(autosaveFields_pass0, "VAL") } record(longin, "PLC:BSY0:PP09:w6") { field(DESC, "Checksum word 6") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_WDA, 6, 0xFFFF, 1)") field(FLNK, "PLC:BSY0:PP09:PROJ_YEAR_calc") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:PROJ_YEAR_calc") { field(INPA, "PLC:BSY0:PP09:w6 NPP MS") field(INPB, "PLC:BSY0:PP09:CHECKSUM_SDIS NPP MS") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PLC:BSY0:PP09:PROJ_YEAR PP MS") field(ASG, "Internal") } record(longin, "PLC:BSY0:PP09:PROJ_YEAR") { field(DESC, "Project creation year.") info(autosaveFields_pass0, "VAL") } record(longin, "PLC:BSY0:PP09:w7") { field(DESC, "Checksum word 7") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_WDA, 7, 0xFFFF, 1)") field(FLNK, "PLC:BSY0:PP09:OP_HRS_MSB_calc") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:OP_HRS_MSB_calc") { field(INPA, "PLC:BSY0:PP09:w7 NPP MS") field(INPB, "PLC:BSY0:PP09:CHECKSUM_SDIS NPP MS") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PLC:BSY0:PP09:OP_HRS_MSB PP MS") field(ASG, "Internal") } record(longin, "PLC:BSY0:PP09:OP_HRS_MSB") { field(DESC, "Operation hours upper byte") field(ASG, "Internal") } record(longin, "PLC:BSY0:PP09:w8") { field(DESC, "Checksum word 8") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_WDA, 8, 0xFFFF, 1)") field(FLNK, "PLC:BSY0:PP09:OP_HRS_LSB_calc") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP09:OP_HRS_LSB_calc") { field(INPA, "PLC:BSY0:PP09:w8 NPP MS") field(INPB, "PLC:BSY0:PP09:CHECKSUM_SDIS NPP MS") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PLC:BSY0:PP09:OP_HRS_LSB PP MS") field(ASG, "Internal") } record(longin, "PLC:BSY0:PP09:OP_HRS_LSB") { field(DESC, "Operation hours lower byte") field(ASG, "Internal") } record(calc, "PLC:BSY0:PP09:OP_HOURS") { field(INPA, "PLC:BSY0:PP09:OP_HRS_MSB CP MS") field(INPB, "PLC:BSY0:PP09:OP_HRS_LSB CP MS") field(CALC, "(A << 8)+(B>>8)") info(autosaveFields_pass0, "VAL") } record(mbbi, "PLC:BSY0:PP09:BASE_MODEL") { field(DTYP, "Raw Soft Channel") field(NOBT, "8") field(INP, "PLC:BSY0:PP09:OP_HRS_LSB CP MS") field(ZRVL, "0x00") field(ONVL, "0x02") field(TWVL, "0x04") field(THVL, "0x03") field(FRVL, "0x20") field(FVVL, "0x22") field(SXVL, "0x24") field(SVVL, "0x23") field(EIVL, "0x50") field(NIVL, "0x51") field(TEVL, "0x52") field(ZRST, "PNOZ m1p") field(ONST, "PNOZ m0p") field(TWST, "PNOZ m2p") field(THST, "PNOZ m3p") field(FRST, "PNOZ m1p ETH") field(FVST, "PNOZ m0p ETH") field(SXST, "PNOZ m2p ETH") field(SVST, "PNOZ m3p ETH") field(EIST, "PNOZ mm0p") field(NIST, "PNOZ mm0.1p") field(TEST, "PNOZ mm0.2p") } # End of file # Template for I/O statistics record(bo,"PLC:BSY0:PP09:RDHistEnable") { field(DTYP,"asynUInt32Digital") field(OUT,"@asynMask(30BSY_RDA 0 0xFFFF)ENABLE_HISTOGRAM") field(ZNAM,"Disable") field(ONAM,"Enable") } record(bo, "PLC:BSY0:PP09:RDStatistics") { field(SCAN, "10 second") field(FLNK, "PLC:BSY0:PP09:RDHist.PROC") } record(waveform,"PLC:BSY0:PP09:RDHist") { field(DTYP,"asynInt32ArrayIn") field(INP,"@asyn(30BSY_RDA 0)READ_HISTOGRAM") field(FTVL,"LONG") field(NELM,"200") # This number should match driver field(FLNK,"PLC:BSY0:PP09:RDHistTimeAxis.PROC") } record(waveform,"PLC:BSY0:PP09:RDHistTimeAxis") { field(DTYP,"asynInt32ArrayIn") field(INP,"@asyn(30BSY_RDA 0)HISTOGRAM_TIME_AXIS") field(FTVL,"LONG") field(NELM,"200") # This number should match driver field(FLNK,"PLC:BSY0:PP09:RDReadOK.PROC") } record(longout,"PLC:BSY0:PP09:RDMsPerBin") { field(DTYP,"asynInt32") field(OUT,"@asyn(30BSY_RDA 0)HISTOGRAM_BIN_TIME") field(DRVL,"0") field(VAL,"1") field(PINI,"1") } record(longin,"PLC:BSY0:PP09:RDReadOK") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_RDA 0)READ_OK") field(FLNK,"PLC:BSY0:PP09:RDWriteOK.PROC") } record(longin,"PLC:BSY0:PP09:RDWriteOK") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_RDA 0)WRITE_OK") field(FLNK,"PLC:BSY0:PP09:RDIOErrors.PROC") } record(longin,"PLC:BSY0:PP09:RDIOErrors") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_RDA 0)IO_ERRORS") field(FLNK,"PLC:BSY0:PP09:RDLastIOTime.PROC") } record(longin,"PLC:BSY0:PP09:RDLastIOTime") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_RDA 0)LAST_IO_TIME") field(FLNK,"PLC:BSY0:PP09:RDMaxIOTime.PROC") } record(longin,"PLC:BSY0:PP09:RDMaxIOTime") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_RDA 0)MAX_IO_TIME") } # Template for I/O statistics record(bo,"PLC:BSY0:PP09:WRTHistEnable") { field(DTYP,"asynUInt32Digital") field(OUT,"@asynMask(30BSY_WRTA 0 0xFFFF)ENABLE_HISTOGRAM") field(ZNAM,"Disable") field(ONAM,"Enable") } record(bo, "PLC:BSY0:PP09:WRTStatistics") { field(SCAN, "10 second") field(FLNK, "PLC:BSY0:PP09:WRTHist.PROC") } record(waveform,"PLC:BSY0:PP09:WRTHist") { field(DTYP,"asynInt32ArrayIn") field(INP,"@asyn(30BSY_WRTA 0)READ_HISTOGRAM") field(FTVL,"LONG") field(NELM,"200") # This number should match driver field(FLNK,"PLC:BSY0:PP09:WRTHistTimeAxis.PROC") } record(waveform,"PLC:BSY0:PP09:WRTHistTimeAxis") { field(DTYP,"asynInt32ArrayIn") field(INP,"@asyn(30BSY_WRTA 0)HISTOGRAM_TIME_AXIS") field(FTVL,"LONG") field(NELM,"200") # This number should match driver field(FLNK,"PLC:BSY0:PP09:WRTReadOK.PROC") } record(longout,"PLC:BSY0:PP09:WRTMsPerBin") { field(DTYP,"asynInt32") field(OUT,"@asyn(30BSY_WRTA 0)HISTOGRAM_BIN_TIME") field(DRVL,"0") field(VAL,"1") field(PINI,"1") } record(longin,"PLC:BSY0:PP09:WRTReadOK") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_WRTA 0)READ_OK") field(FLNK,"PLC:BSY0:PP09:WRTWriteOK.PROC") } record(longin,"PLC:BSY0:PP09:WRTWriteOK") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_WRTA 0)WRITE_OK") field(FLNK,"PLC:BSY0:PP09:WRTIOErrors.PROC") } record(longin,"PLC:BSY0:PP09:WRTIOErrors") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_WRTA 0)IO_ERRORS") field(FLNK,"PLC:BSY0:PP09:WRTLastIOTime.PROC") } record(longin,"PLC:BSY0:PP09:WRTLastIOTime") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_WRTA 0)LAST_IO_TIME") field(FLNK,"PLC:BSY0:PP09:WRTMaxIOTime.PROC") } record(longin,"PLC:BSY0:PP09:WRTMaxIOTime") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_WRTA 0)MAX_IO_TIME") } # Template for I/O statistics record(bo,"PLC:BSY0:PP09:WDHistEnable") { field(DTYP,"asynUInt32Digital") field(OUT,"@asynMask(30BSY_WDA 0 0xFFFF)ENABLE_HISTOGRAM") field(ZNAM,"Disable") field(ONAM,"Enable") } record(bo, "PLC:BSY0:PP09:WDStatistics") { field(SCAN, "10 second") field(FLNK, "PLC:BSY0:PP09:WDHist.PROC") } record(waveform,"PLC:BSY0:PP09:WDHist") { field(DTYP,"asynInt32ArrayIn") field(INP,"@asyn(30BSY_WDA 0)READ_HISTOGRAM") field(FTVL,"LONG") field(NELM,"200") # This number should match driver field(FLNK,"PLC:BSY0:PP09:WDHistTimeAxis.PROC") } record(waveform,"PLC:BSY0:PP09:WDHistTimeAxis") { field(DTYP,"asynInt32ArrayIn") field(INP,"@asyn(30BSY_WDA 0)HISTOGRAM_TIME_AXIS") field(FTVL,"LONG") field(NELM,"200") # This number should match driver field(FLNK,"PLC:BSY0:PP09:WDReadOK.PROC") } record(longout,"PLC:BSY0:PP09:WDMsPerBin") { field(DTYP,"asynInt32") field(OUT,"@asyn(30BSY_WDA 0)HISTOGRAM_BIN_TIME") field(DRVL,"0") field(VAL,"1") field(PINI,"1") } record(longin,"PLC:BSY0:PP09:WDReadOK") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_WDA 0)READ_OK") field(FLNK,"PLC:BSY0:PP09:WDWriteOK.PROC") } record(longin,"PLC:BSY0:PP09:WDWriteOK") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_WDA 0)WRITE_OK") field(FLNK,"PLC:BSY0:PP09:WDIOErrors.PROC") } record(longin,"PLC:BSY0:PP09:WDIOErrors") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_WDA 0)IO_ERRORS") field(FLNK,"PLC:BSY0:PP09:WDLastIOTime.PROC") } record(longin,"PLC:BSY0:PP09:WDLastIOTime") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_WDA 0)LAST_IO_TIME") field(FLNK,"PLC:BSY0:PP09:WDMaxIOTime.PROC") } record(longin,"PLC:BSY0:PP09:WDMaxIOTime") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_WDA 0)MAX_IO_TIME") } #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi7") { field(DESC, "Port 30BSY_RDB bit 7") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 7, 1, 1)") field(ZNAM, "Not_Enabled") field(ONAM, "Enabled") field(FLNK, "PPS:SYSE:1:HW_ENABLE_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi7Valid") { field(INPA, "PLC:BSY0:PP10:Bi7.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:HW_ENABLE_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:HW_ENABLE_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi7 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi7Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:HW_ENABLE_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:HW_ENABLE_B") { field(DESC, "HW Enabled B") field(ZNAM, "Not_Enabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb7",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb7") #! Field("PLC:BSY0:PP10:30BSY_RDBb7.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb7.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb7.FLNK","PPS:SYSE:1:HW_ENABLE_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb7.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb7.VAL") #! Record("PPS:SYSE:1:HW_ENABLE_B_calc",260,18,0,1,"PPS:SYSE:1:HW_ENABLE_B_calc") #! Field("PPS:SYSE:1:HW_ENABLE_B_calc.INPA",16777215,0,"PPS:SYSE:1:HW_ENABLE_B_calc.INPA") #! Link("PPS:SYSE:1:HW_ENABLE_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb7.VAL") #! Field("PPS:SYSE:1:HW_ENABLE_B_calc.INPB",16777215,1,"PPS:SYSE:1:HW_ENABLE_B_calc.INPB") #! Field("PPS:SYSE:1:HW_ENABLE_B_calc.OUT",16777215,1,"PPS:SYSE:1:HW_ENABLE_B_calc.OUT") #! Link("PPS:SYSE:1:HW_ENABLE_B_calc.OUT","PPS:SYSE:1:HW_ENABLE_B.VAL") #! Record("PPS:SYSE:1:HW_ENABLE_B",500,20,0,0,"PPS:SYSE:1:HW_ENABLE_B") #! Field("PPS:SYSE:1:HW_ENABLE_B.VAL",16777215,1,"PPS:SYSE:1:HW_ENABLE_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi6") { field(DESC, "Port 30BSY_RDB bit 6") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 6, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(FLNK, "PPS:SYSE:1:CROSS_INTLK_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi6Valid") { field(INPA, "PLC:BSY0:PP10:Bi6.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:CROSS_INTLK_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:CROSS_INTLK_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi6 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi6Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:CROSS_INTLK_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:CROSS_INTLK_B") { field(DESC, "Secure Complete from Other Chain") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb6",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb6") #! Field("PLC:BSY0:PP10:30BSY_RDBb6.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb6.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb6.FLNK","PPS:SYSE:1:CROSS_INTLK_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb6.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb6.VAL") #! Record("PPS:SYSE:1:CROSS_INTLK_B_calc",260,18,0,1,"PPS:SYSE:1:CROSS_INTLK_B_calc") #! Field("PPS:SYSE:1:CROSS_INTLK_B_calc.INPA",16777215,0,"PPS:SYSE:1:CROSS_INTLK_B_calc.INPA") #! Link("PPS:SYSE:1:CROSS_INTLK_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb6.VAL") #! Field("PPS:SYSE:1:CROSS_INTLK_B_calc.INPB",16777215,1,"PPS:SYSE:1:CROSS_INTLK_B_calc.INPB") #! Field("PPS:SYSE:1:CROSS_INTLK_B_calc.OUT",16777215,1,"PPS:SYSE:1:CROSS_INTLK_B_calc.OUT") #! Link("PPS:SYSE:1:CROSS_INTLK_B_calc.OUT","PPS:SYSE:1:CROSS_INTLK_B.VAL") #! Record("PPS:SYSE:1:CROSS_INTLK_B",500,20,0,0,"PPS:SYSE:1:CROSS_INTLK_B") #! Field("PPS:SYSE:1:CROSS_INTLK_B.VAL",16777215,1,"PPS:SYSE:1:CROSS_INTLK_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi5") { field(DESC, "Port 30BSY_RDB bit 5") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 5, 1, 1)") field(ZNAM, "Fault") field(ONAM, "Ok") field(FLNK, "PPS:SYSE:1:BLM_INP_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi5Valid") { field(INPA, "PLC:BSY0:PP10:Bi5.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:BLM_INP_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:BLM_INP_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi5 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi5Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:BLM_INP_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:BLM_INP_B") { field(DESC, "BCS_BLM_Input_B") field(ZNAM, "Fault") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb5",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb5") #! Field("PLC:BSY0:PP10:30BSY_RDBb5.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb5.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb5.FLNK","PPS:SYSE:1:BLM_INP_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb5.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb5.VAL") #! Record("PPS:SYSE:1:BLM_INP_B_calc",260,18,0,1,"PPS:SYSE:1:BLM_INP_B_calc") #! Field("PPS:SYSE:1:BLM_INP_B_calc.INPA",16777215,0,"PPS:SYSE:1:BLM_INP_B_calc.INPA") #! Link("PPS:SYSE:1:BLM_INP_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb5.VAL") #! Field("PPS:SYSE:1:BLM_INP_B_calc.INPB",16777215,1,"PPS:SYSE:1:BLM_INP_B_calc.INPB") #! Field("PPS:SYSE:1:BLM_INP_B_calc.OUT",16777215,1,"PPS:SYSE:1:BLM_INP_B_calc.OUT") #! Link("PPS:SYSE:1:BLM_INP_B_calc.OUT","PPS:SYSE:1:BLM_INP_B.VAL") #! Record("PPS:SYSE:1:BLM_INP_B",500,20,0,0,"PPS:SYSE:1:BLM_INP_B") #! Field("PPS:SYSE:1:BLM_INP_B.VAL",16777215,1,"PPS:SYSE:1:BLM_INP_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi3") { field(DESC, "Port 30BSY_RDB bit 3") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 3, 1, 1)") field(ZNAM, "Fault") field(ONAM, "Ok") field(FLNK, "PPS:LI30:1:SECURE_INP_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi3Valid") { field(INPA, "PLC:BSY0:PP10:Bi3.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:LI30:1:SECURE_INP_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:LI30:1:SECURE_INP_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi3 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi3Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:LI30:1:SECURE_INP_B PP MS") field(ASG, "Internal") } record(bi, "PPS:LI30:1:SECURE_INP_B") { field(DESC, "S30_Secure_Input_B") field(ZNAM, "Fault") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb3",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb3") #! Field("PLC:BSY0:PP10:30BSY_RDBb3.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb3.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb3.FLNK","PPS:LI30:1:SECURE_INP_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb3.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb3.VAL") #! Record("PPS:LI30:1:SECURE_INP_B_calc",260,18,0,1,"PPS:LI30:1:SECURE_INP_B_calc") #! Field("PPS:LI30:1:SECURE_INP_B_calc.INPA",16777215,0,"PPS:LI30:1:SECURE_INP_B_calc.INPA") #! Link("PPS:LI30:1:SECURE_INP_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb3.VAL") #! Field("PPS:LI30:1:SECURE_INP_B_calc.INPB",16777215,1,"PPS:LI30:1:SECURE_INP_B_calc.INPB") #! Field("PPS:LI30:1:SECURE_INP_B_calc.OUT",16777215,1,"PPS:LI30:1:SECURE_INP_B_calc.OUT") #! Link("PPS:LI30:1:SECURE_INP_B_calc.OUT","PPS:LI30:1:SECURE_INP_B.VAL") #! Record("PPS:LI30:1:SECURE_INP_B",500,20,0,0,"PPS:LI30:1:SECURE_INP_B") #! Field("PPS:LI30:1:SECURE_INP_B.VAL",16777215,1,"PPS:LI30:1:SECURE_INP_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi2") { field(DESC, "Port 30BSY_RDB bit 2") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 2, 1, 1)") field(ZNAM, "Fault") field(ONAM, "Ok") field(FLNK, "PPS:BSY0:1:SECURE_INP_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi2Valid") { field(INPA, "PLC:BSY0:PP10:Bi2.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:BSY0:1:SECURE_INP_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:BSY0:1:SECURE_INP_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi2 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi2Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:BSY0:1:SECURE_INP_B PP MS") field(ASG, "Internal") } record(bi, "PPS:BSY0:1:SECURE_INP_B") { field(DESC, "BSY_Secure_Input_B") field(ZNAM, "Fault") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb2",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb2") #! Field("PLC:BSY0:PP10:30BSY_RDBb2.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb2.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb2.FLNK","PPS:BSY0:1:SECURE_INP_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb2.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb2.VAL") #! Record("PPS:BSY0:1:SECURE_INP_B_calc",260,18,0,1,"PPS:BSY0:1:SECURE_INP_B_calc") #! Field("PPS:BSY0:1:SECURE_INP_B_calc.INPA",16777215,0,"PPS:BSY0:1:SECURE_INP_B_calc.INPA") #! Link("PPS:BSY0:1:SECURE_INP_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb2.VAL") #! Field("PPS:BSY0:1:SECURE_INP_B_calc.INPB",16777215,1,"PPS:BSY0:1:SECURE_INP_B_calc.INPB") #! Field("PPS:BSY0:1:SECURE_INP_B_calc.OUT",16777215,1,"PPS:BSY0:1:SECURE_INP_B_calc.OUT") #! Link("PPS:BSY0:1:SECURE_INP_B_calc.OUT","PPS:BSY0:1:SECURE_INP_B.VAL") #! Record("PPS:BSY0:1:SECURE_INP_B",500,20,0,0,"PPS:BSY0:1:SECURE_INP_B") #! Field("PPS:BSY0:1:SECURE_INP_B.VAL",16777215,1,"PPS:BSY0:1:SECURE_INP_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi1") { field(DESC, "Port 30BSY_RDB bit 1") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 1, 1, 1)") field(ZNAM, "Fault") field(ONAM, "Ok") field(FLNK, "PPS:ESA0:1:RADREADY_INP_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi1Valid") { field(INPA, "PLC:BSY0:PP10:Bi1.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:ESA0:1:RADREADY_INP_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:ESA0:1:RADREADY_INP_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi1 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi1Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:ESA0:1:RADREADY_INP_B PP MS") field(ASG, "Internal") } record(bi, "PPS:ESA0:1:RADREADY_INP_B") { field(DESC, "ESA_Rad_Ready_Input_B") field(ZNAM, "Fault") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb1",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb1") #! Field("PLC:BSY0:PP10:30BSY_RDBb1.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb1.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb1.FLNK","PPS:ESA0:1:RADREADY_INP_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb1.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb1.VAL") #! Record("PPS:ESA0:1:RADREADY_INP_B_calc",260,18,0,1,"PPS:ESA0:1:RADREADY_INP_B_calc") #! Field("PPS:ESA0:1:RADREADY_INP_B_calc.INPA",16777215,0,"PPS:ESA0:1:RADREADY_INP_B_calc.INPA") #! Link("PPS:ESA0:1:RADREADY_INP_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb1.VAL") #! Field("PPS:ESA0:1:RADREADY_INP_B_calc.INPB",16777215,1,"PPS:ESA0:1:RADREADY_INP_B_calc.INPB") #! Field("PPS:ESA0:1:RADREADY_INP_B_calc.OUT",16777215,1,"PPS:ESA0:1:RADREADY_INP_B_calc.OUT") #! Link("PPS:ESA0:1:RADREADY_INP_B_calc.OUT","PPS:ESA0:1:RADREADY_INP_B.VAL") #! Record("PPS:ESA0:1:RADREADY_INP_B",500,20,0,0,"PPS:ESA0:1:RADREADY_INP_B") #! Field("PPS:ESA0:1:RADREADY_INP_B.VAL",16777215,1,"PPS:ESA0:1:RADREADY_INP_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi0") { field(DESC, "Port 30BSY_RDB bit 0") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 0, 1, 1)") field(ZNAM, "Fault") field(ONAM, "Ok") field(FLNK, "BTM:BSY0:1:SUM_OK_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi0Valid") { field(INPA, "PLC:BSY0:PP10:Bi0.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "BTM:BSY0:1:SUM_OK_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "BTM:BSY0:1:SUM_OK_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi0 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi0Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "BTM:BSY0:1:SUM_OK_B PP MS") field(ASG, "Internal") } record(bi, "BTM:BSY0:1:SUM_OK_B") { field(DESC, "BTM_Sum_OK_Input_B") field(ZNAM, "Fault") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb0",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb0") #! Field("PLC:BSY0:PP10:30BSY_RDBb0.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb0.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb0.FLNK","BTM:BSY0:1:SUM_OK_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb0.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb0.VAL") #! Record("BTM:BSY0:1:SUM_OK_B_calc",260,18,0,1,"BTM:BSY0:1:SUM_OK_B_calc") #! Field("BTM:BSY0:1:SUM_OK_B_calc.INPA",16777215,0,"BTM:BSY0:1:SUM_OK_B_calc.INPA") #! Link("BTM:BSY0:1:SUM_OK_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb0.VAL") #! Field("BTM:BSY0:1:SUM_OK_B_calc.INPB",16777215,1,"BTM:BSY0:1:SUM_OK_B_calc.INPB") #! Field("BTM:BSY0:1:SUM_OK_B_calc.OUT",16777215,1,"BTM:BSY0:1:SUM_OK_B_calc.OUT") #! Link("BTM:BSY0:1:SUM_OK_B_calc.OUT","BTM:BSY0:1:SUM_OK_B.VAL") #! Record("BTM:BSY0:1:SUM_OK_B",500,20,0,0,"BTM:BSY0:1:SUM_OK_B") #! Field("BTM:BSY0:1:SUM_OK_B.VAL",16777215,1,"BTM:BSY0:1:SUM_OK_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi15") { field(DESC, "Port 30BSY_RDB bit 15") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 15, 1, 1)") field(ZNAM, "Fault") field(ONAM, "Ok") field(FLNK, "BSOC:SYSE:1:GROUPC_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi15Valid") { field(INPA, "PLC:BSY0:PP10:Bi15.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "BSOC:SYSE:1:GROUPC_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "BSOC:SYSE:1:GROUPC_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi15 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi15Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "BSOC:SYSE:1:GROUPC_B PP MS") field(ASG, "Internal") } record(bi, "BSOC:SYSE:1:GROUPC_B") { field(DESC, "BSOIC_GrpC_OK_Input_B") field(ZNAM, "Fault") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb15",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb15") #! Field("PLC:BSY0:PP10:30BSY_RDBb15.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb15.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb15.FLNK","BSOC:SYSE:1:GROUPC_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb15.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb15.VAL") #! Record("BSOC:SYSE:1:GROUPC_B_calc",260,18,0,1,"BSOC:SYSE:1:GROUPC_B_calc") #! Field("BSOC:SYSE:1:GROUPC_B_calc.INPA",16777215,0,"BSOC:SYSE:1:GROUPC_B_calc.INPA") #! Link("BSOC:SYSE:1:GROUPC_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb15.VAL") #! Field("BSOC:SYSE:1:GROUPC_B_calc.INPB",16777215,1,"BSOC:SYSE:1:GROUPC_B_calc.INPB") #! Field("BSOC:SYSE:1:GROUPC_B_calc.OUT",16777215,1,"BSOC:SYSE:1:GROUPC_B_calc.OUT") #! Link("BSOC:SYSE:1:GROUPC_B_calc.OUT","BSOC:SYSE:1:GROUPC_B.VAL") #! Record("BSOC:SYSE:1:GROUPC_B",500,20,0,0,"BSOC:SYSE:1:GROUPC_B") #! Field("BSOC:SYSE:1:GROUPC_B.VAL",16777215,1,"BSOC:SYSE:1:GROUPC_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi14") { field(DESC, "Port 30BSY_RDB bit 14") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 14, 1, 1)") field(ZNAM, "Fault") field(ONAM, "Ok") field(FLNK, "PPS:UND0:1:SECURE_INP_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi14Valid") { field(INPA, "PLC:BSY0:PP10:Bi14.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:UND0:1:SECURE_INP_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:UND0:1:SECURE_INP_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi14 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi14Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:UND0:1:SECURE_INP_B PP MS") field(ASG, "Internal") } record(bi, "PPS:UND0:1:SECURE_INP_B") { field(DESC, "LCLS_Secure_Input_B") field(ZNAM, "Fault") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb14",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb14") #! Field("PLC:BSY0:PP10:30BSY_RDBb14.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb14.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb14.FLNK","PPS:UND0:1:SECURE_INP_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb14.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb14.VAL") #! Record("PPS:UND0:1:SECURE_INP_B_calc",260,18,0,1,"PPS:UND0:1:SECURE_INP_B_calc") #! Field("PPS:UND0:1:SECURE_INP_B_calc.INPA",16777215,0,"PPS:UND0:1:SECURE_INP_B_calc.INPA") #! Link("PPS:UND0:1:SECURE_INP_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb14.VAL") #! Field("PPS:UND0:1:SECURE_INP_B_calc.INPB",16777215,1,"PPS:UND0:1:SECURE_INP_B_calc.INPB") #! Field("PPS:UND0:1:SECURE_INP_B_calc.OUT",16777215,1,"PPS:UND0:1:SECURE_INP_B_calc.OUT") #! Link("PPS:UND0:1:SECURE_INP_B_calc.OUT","PPS:UND0:1:SECURE_INP_B.VAL") #! Record("PPS:UND0:1:SECURE_INP_B",500,20,0,0,"PPS:UND0:1:SECURE_INP_B") #! Field("PPS:UND0:1:SECURE_INP_B.VAL",16777215,1,"PPS:UND0:1:SECURE_INP_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi13") { field(DESC, "Port 30BSY_RDB bit 13") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 13, 1, 1)") field(ZNAM, "Not_Enabled") field(ONAM, "Enabled") field(FLNK, "PPS:SYSE:1:30BSY:LOCAL_ENABLE_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi13Valid") { field(INPA, "PLC:BSY0:PP10:Bi13.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:LOCAL_ENABLE_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:LOCAL_ENABLE_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi13 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi13Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:LOCAL_ENABLE_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:LOCAL_ENABLE_B") { field(DESC, "Local_Beam_Enable_Keysw_B") field(ZNAM, "Not_Enabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb13",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb13") #! Field("PLC:BSY0:PP10:30BSY_RDBb13.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb13.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb13.FLNK","PPS:SYSE:1:30BSY:LOCAL_ENABLE_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb13.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb13.VAL") #! Record("PPS:SYSE:1:30BSY:LOCAL_ENABLE_B_calc",260,18,0,1,"PPS:SYSE:1:30BSY:LOCAL_ENABLE_B_calc") #! Field("PPS:SYSE:1:30BSY:LOCAL_ENABLE_B_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:LOCAL_ENABLE_B_calc.INPA") #! Link("PPS:SYSE:1:30BSY:LOCAL_ENABLE_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb13.VAL") #! Field("PPS:SYSE:1:30BSY:LOCAL_ENABLE_B_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:LOCAL_ENABLE_B_calc.INPB") #! Field("PPS:SYSE:1:30BSY:LOCAL_ENABLE_B_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:LOCAL_ENABLE_B_calc.OUT") #! Link("PPS:SYSE:1:30BSY:LOCAL_ENABLE_B_calc.OUT","PPS:SYSE:1:30BSY:LOCAL_ENABLE_B.VAL") #! Record("PPS:SYSE:1:30BSY:LOCAL_ENABLE_B",500,20,0,0,"PPS:SYSE:1:30BSY:LOCAL_ENABLE_B") #! Field("PPS:SYSE:1:30BSY:LOCAL_ENABLE_B.VAL",16777215,1,"PPS:SYSE:1:30BSY:LOCAL_ENABLE_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi12") { field(DESC, "Port 30BSY_RDB bit 12") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 12, 1, 1)") field(ZNAM, "Not_Lowered") field(ONAM, "Lowered") field(FLNK, "PPS:LTU0:1:BCS_TRP_LOW_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi12Valid") { field(INPA, "PLC:BSY0:PP10:Bi12.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:LTU0:1:BCS_TRP_LOW_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:LTU0:1:BCS_TRP_LOW_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi12 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi12Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:LTU0:1:BCS_TRP_LOW_B PP MS") field(ASG, "Internal") } record(bi, "PPS:LTU0:1:BCS_TRP_LOW_B") { field(DESC, "BCS_BTH_Trips_Low_Inp_B") field(ZNAM, "Not_Lowered") field(ONAM, "Lowered") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb12",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb12") #! Field("PLC:BSY0:PP10:30BSY_RDBb12.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb12.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb12.FLNK","PPS:LTU0:1:BCS_TRP_LOW_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb12.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb12.VAL") #! Record("PPS:LTU0:1:BCS_TRP_LOW_B_calc",260,18,0,1,"PPS:LTU0:1:BCS_TRP_LOW_B_calc") #! Field("PPS:LTU0:1:BCS_TRP_LOW_B_calc.INPA",16777215,0,"PPS:LTU0:1:BCS_TRP_LOW_B_calc.INPA") #! Link("PPS:LTU0:1:BCS_TRP_LOW_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb12.VAL") #! Field("PPS:LTU0:1:BCS_TRP_LOW_B_calc.INPB",16777215,1,"PPS:LTU0:1:BCS_TRP_LOW_B_calc.INPB") #! Field("PPS:LTU0:1:BCS_TRP_LOW_B_calc.OUT",16777215,1,"PPS:LTU0:1:BCS_TRP_LOW_B_calc.OUT") #! Link("PPS:LTU0:1:BCS_TRP_LOW_B_calc.OUT","PPS:LTU0:1:BCS_TRP_LOW_B.VAL") #! Record("PPS:LTU0:1:BCS_TRP_LOW_B",500,20,0,0,"PPS:LTU0:1:BCS_TRP_LOW_B") #! Field("PPS:LTU0:1:BCS_TRP_LOW_B.VAL",16777215,1,"PPS:LTU0:1:BCS_TRP_LOW_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi10") { field(DESC, "Port 30BSY_RDB bit 10") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 10, 1, 1)") field(ZNAM, "Not_Enabled") field(ONAM, "Enabled") field(FLNK, "PPS:SYSE:1:30BSY:ACR_ENABLE_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi10Valid") { field(INPA, "PLC:BSY0:PP10:Bi10.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:ACR_ENABLE_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:ACR_ENABLE_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi10 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi10Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:ACR_ENABLE_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:ACR_ENABLE_B") { field(DESC, "ACR_Beam_Enable_Keysw_B") field(ZNAM, "Not_Enabled") field(ONAM, "Enabled") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb10",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb10") #! Field("PLC:BSY0:PP10:30BSY_RDBb10.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb10.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb10.FLNK","PPS:SYSE:1:30BSY:ACR_ENABLE_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb10.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb10.VAL") #! Record("PPS:SYSE:1:30BSY:ACR_ENABLE_B_calc",260,18,0,1,"PPS:SYSE:1:30BSY:ACR_ENABLE_B_calc") #! Field("PPS:SYSE:1:30BSY:ACR_ENABLE_B_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:ACR_ENABLE_B_calc.INPA") #! Link("PPS:SYSE:1:30BSY:ACR_ENABLE_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb10.VAL") #! Field("PPS:SYSE:1:30BSY:ACR_ENABLE_B_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:ACR_ENABLE_B_calc.INPB") #! Field("PPS:SYSE:1:30BSY:ACR_ENABLE_B_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:ACR_ENABLE_B_calc.OUT") #! Link("PPS:SYSE:1:30BSY:ACR_ENABLE_B_calc.OUT","PPS:SYSE:1:30BSY:ACR_ENABLE_B.VAL") #! Record("PPS:SYSE:1:30BSY:ACR_ENABLE_B",500,20,0,0,"PPS:SYSE:1:30BSY:ACR_ENABLE_B") #! Field("PPS:SYSE:1:30BSY:ACR_ENABLE_B.VAL",16777215,1,"PPS:SYSE:1:30BSY:ACR_ENABLE_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi9") { field(DESC, "Port 30BSY_RDB bit 9") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 9, 1, 1)") field(ZNAM, "NOT_OFF") field(ONAM, "OFF") field(FLNK, "PPS:LI28:1:HXR:KICKSEP_OFF_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi9Valid") { field(INPA, "PLC:BSY0:PP10:Bi9.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:LI28:1:HXR:KICKSEP_OFF_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:LI28:1:HXR:KICKSEP_OFF_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi9 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi9Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:LI28:1:HXR:KICKSEP_OFF_B PP MS") field(ASG, "Internal") } record(bi, "PPS:LI28:1:HXR:KICKSEP_OFF_B") { field(DESC, "HXR_KickSept_Off_Inp_B") field(ZNAM, "NOT_OFF") field(ONAM, "OFF") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb9",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb9") #! Field("PLC:BSY0:PP10:30BSY_RDBb9.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb9.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb9.FLNK","PPS:LI28:1:HXR:KICKSEP_OFF_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb9.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb9.VAL") #! Record("PPS:LI28:1:HXR:KICKSEP_OFF_B_calc",260,18,0,1,"PPS:LI28:1:HXR:KICKSEP_OFF_B_calc") #! Field("PPS:LI28:1:HXR:KICKSEP_OFF_B_calc.INPA",16777215,0,"PPS:LI28:1:HXR:KICKSEP_OFF_B_calc.INPA") #! Link("PPS:LI28:1:HXR:KICKSEP_OFF_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb9.VAL") #! Field("PPS:LI28:1:HXR:KICKSEP_OFF_B_calc.INPB",16777215,1,"PPS:LI28:1:HXR:KICKSEP_OFF_B_calc.INPB") #! Field("PPS:LI28:1:HXR:KICKSEP_OFF_B_calc.OUT",16777215,1,"PPS:LI28:1:HXR:KICKSEP_OFF_B_calc.OUT") #! Link("PPS:LI28:1:HXR:KICKSEP_OFF_B_calc.OUT","PPS:LI28:1:HXR:KICKSEP_OFF_B.VAL") #! Record("PPS:LI28:1:HXR:KICKSEP_OFF_B",500,20,0,0,"PPS:LI28:1:HXR:KICKSEP_OFF_B") #! Field("PPS:LI28:1:HXR:KICKSEP_OFF_B.VAL",16777215,1,"PPS:LI28:1:HXR:KICKSEP_OFF_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi8") { field(DESC, "Port 30BSY_RDB bit 8") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 8, 1, 1)") field(ZNAM, "NOT_OK") field(ONAM, "OK") field(FLNK, "PPS:LI28:1:HXR:KICK_COND_OK_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi8Valid") { field(INPA, "PLC:BSY0:PP10:Bi8.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:LI28:1:HXR:KICK_COND_OK_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:LI28:1:HXR:KICK_COND_OK_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi8 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi8Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:LI28:1:HXR:KICK_COND_OK_B PP MS") field(ASG, "Internal") } record(bi, "PPS:LI28:1:HXR:KICK_COND_OK_B") { field(DESC, "HXR_Kick_OK_B") field(ZNAM, "NOT_OK") field(ONAM, "OK") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb8",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb8") #! Field("PLC:BSY0:PP10:30BSY_RDBb8.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb8.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb8.FLNK","PPS:LI28:1:HXR:KICK_COND_OK_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb8.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb8.VAL") #! Record("PPS:LI28:1:HXR:KICK_COND_OK_B_calc",260,18,0,1,"PPS:LI28:1:HXR:KICK_COND_OK_B_calc") #! Field("PPS:LI28:1:HXR:KICK_COND_OK_B_calc.INPA",16777215,0,"PPS:LI28:1:HXR:KICK_COND_OK_B_calc.INPA") #! Link("PPS:LI28:1:HXR:KICK_COND_OK_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb8.VAL") #! Field("PPS:LI28:1:HXR:KICK_COND_OK_B_calc.INPB",16777215,1,"PPS:LI28:1:HXR:KICK_COND_OK_B_calc.INPB") #! Field("PPS:LI28:1:HXR:KICK_COND_OK_B_calc.OUT",16777215,1,"PPS:LI28:1:HXR:KICK_COND_OK_B_calc.OUT") #! Link("PPS:LI28:1:HXR:KICK_COND_OK_B_calc.OUT","PPS:LI28:1:HXR:KICK_COND_OK_B.VAL") #! Record("PPS:LI28:1:HXR:KICK_COND_OK_B",500,20,0,0,"PPS:LI28:1:HXR:KICK_COND_OK_B") #! Field("PPS:LI28:1:HXR:KICK_COND_OK_B.VAL",16777215,1,"PPS:LI28:1:HXR:KICK_COND_OK_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi23") { field(DESC, "Port 30BSY_RDB bit 23") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 23, 1, 1)") field(ZNAM, "NOT_OFF") field(ONAM, "OFF") field(FLNK, "PPS:LI30:1:SXR:KICKSEP_OFF_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi23Valid") { field(INPA, "PLC:BSY0:PP10:Bi23.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:LI30:1:SXR:KICKSEP_OFF_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:LI30:1:SXR:KICKSEP_OFF_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi23 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi23Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:LI30:1:SXR:KICKSEP_OFF_B PP MS") field(ASG, "Internal") } record(bi, "PPS:LI30:1:SXR:KICKSEP_OFF_B") { field(DESC, "SXR_KickSept_Off_Inp_B") field(ZNAM, "NOT_OFF") field(ONAM, "OFF") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb23",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb23") #! Field("PLC:BSY0:PP10:30BSY_RDBb23.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb23.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb23.FLNK","PPS:LI30:1:SXR:KICKSEP_OFF_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb23.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb23.VAL") #! Record("PPS:LI30:1:SXR:KICKSEP_OFF_B_calc",260,18,0,1,"PPS:LI30:1:SXR:KICKSEP_OFF_B_calc") #! Field("PPS:LI30:1:SXR:KICKSEP_OFF_B_calc.INPA",16777215,0,"PPS:LI30:1:SXR:KICKSEP_OFF_B_calc.INPA") #! Link("PPS:LI30:1:SXR:KICKSEP_OFF_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb23.VAL") #! Field("PPS:LI30:1:SXR:KICKSEP_OFF_B_calc.INPB",16777215,1,"PPS:LI30:1:SXR:KICKSEP_OFF_B_calc.INPB") #! Field("PPS:LI30:1:SXR:KICKSEP_OFF_B_calc.OUT",16777215,1,"PPS:LI30:1:SXR:KICKSEP_OFF_B_calc.OUT") #! Link("PPS:LI30:1:SXR:KICKSEP_OFF_B_calc.OUT","PPS:LI30:1:SXR:KICKSEP_OFF_B.VAL") #! Record("PPS:LI30:1:SXR:KICKSEP_OFF_B",500,20,0,0,"PPS:LI30:1:SXR:KICKSEP_OFF_B") #! Field("PPS:LI30:1:SXR:KICKSEP_OFF_B.VAL",16777215,1,"PPS:LI30:1:SXR:KICKSEP_OFF_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi22") { field(DESC, "Port 30BSY_RDB bit 22") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 22, 1, 1)") field(ZNAM, "NOT_OK") field(ONAM, "OK") field(FLNK, "PPS:LI30:1:SXR:KICK_COND_OK_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi22Valid") { field(INPA, "PLC:BSY0:PP10:Bi22.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:LI30:1:SXR:KICK_COND_OK_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:LI30:1:SXR:KICK_COND_OK_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi22 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi22Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:LI30:1:SXR:KICK_COND_OK_B PP MS") field(ASG, "Internal") } record(bi, "PPS:LI30:1:SXR:KICK_COND_OK_B") { field(DESC, "SXR_Kick_OK_B") field(ZNAM, "NOT_OK") field(ONAM, "OK") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb22",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb22") #! Field("PLC:BSY0:PP10:30BSY_RDBb22.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb22.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb22.FLNK","PPS:LI30:1:SXR:KICK_COND_OK_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb22.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb22.VAL") #! Record("PPS:LI30:1:SXR:KICK_COND_OK_B_calc",260,18,0,1,"PPS:LI30:1:SXR:KICK_COND_OK_B_calc") #! Field("PPS:LI30:1:SXR:KICK_COND_OK_B_calc.INPA",16777215,0,"PPS:LI30:1:SXR:KICK_COND_OK_B_calc.INPA") #! Link("PPS:LI30:1:SXR:KICK_COND_OK_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb22.VAL") #! Field("PPS:LI30:1:SXR:KICK_COND_OK_B_calc.INPB",16777215,1,"PPS:LI30:1:SXR:KICK_COND_OK_B_calc.INPB") #! Field("PPS:LI30:1:SXR:KICK_COND_OK_B_calc.OUT",16777215,1,"PPS:LI30:1:SXR:KICK_COND_OK_B_calc.OUT") #! Link("PPS:LI30:1:SXR:KICK_COND_OK_B_calc.OUT","PPS:LI30:1:SXR:KICK_COND_OK_B.VAL") #! Record("PPS:LI30:1:SXR:KICK_COND_OK_B",500,20,0,0,"PPS:LI30:1:SXR:KICK_COND_OK_B") #! Field("PPS:LI30:1:SXR:KICK_COND_OK_B.VAL",16777215,1,"PPS:LI30:1:SXR:KICK_COND_OK_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi21") { field(DESC, "Port 30BSY_RDB bit 21") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 21, 1, 1)") field(ZNAM, "NOT_IN") field(ONAM, "IN") field(FLNK, "STPR:BSYH:1:30BSY:STD2_IN_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi21Valid") { field(INPA, "PLC:BSY0:PP10:Bi21.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "STPR:BSYH:1:30BSY:STD2_IN_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "STPR:BSYH:1:30BSY:STD2_IN_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi21 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi21Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "STPR:BSYH:1:30BSY:STD2_IN_B PP MS") field(ASG, "Internal") } record(bi, "STPR:BSYH:1:30BSY:STD2_IN_B") { field(DESC, "STD2_Set_In_30BSY_Inp_B") field(ZNAM, "NOT_IN") field(ONAM, "IN") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb21",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb21") #! Field("PLC:BSY0:PP10:30BSY_RDBb21.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb21.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb21.FLNK","STPR:BSYH:1:30BSY:STD2_IN_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb21.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb21.VAL") #! Record("STPR:BSYH:1:30BSY:STD2_IN_B_calc",260,18,0,1,"STPR:BSYH:1:30BSY:STD2_IN_B_calc") #! Field("STPR:BSYH:1:30BSY:STD2_IN_B_calc.INPA",16777215,0,"STPR:BSYH:1:30BSY:STD2_IN_B_calc.INPA") #! Link("STPR:BSYH:1:30BSY:STD2_IN_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb21.VAL") #! Field("STPR:BSYH:1:30BSY:STD2_IN_B_calc.INPB",16777215,1,"STPR:BSYH:1:30BSY:STD2_IN_B_calc.INPB") #! Field("STPR:BSYH:1:30BSY:STD2_IN_B_calc.OUT",16777215,1,"STPR:BSYH:1:30BSY:STD2_IN_B_calc.OUT") #! Link("STPR:BSYH:1:30BSY:STD2_IN_B_calc.OUT","STPR:BSYH:1:30BSY:STD2_IN_B.VAL") #! Record("STPR:BSYH:1:30BSY:STD2_IN_B",500,20,0,0,"STPR:BSYH:1:30BSY:STD2_IN_B") #! Field("STPR:BSYH:1:30BSY:STD2_IN_B.VAL",16777215,1,"STPR:BSYH:1:30BSY:STD2_IN_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi20") { field(DESC, "Port 30BSY_RDB bit 20") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 20, 1, 1)") field(ZNAM, "NOT_OUT") field(ONAM, "OUT") field(FLNK, "STPR:BSYH:1:30BSY:STD2_OUT_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi20Valid") { field(INPA, "PLC:BSY0:PP10:Bi20.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "STPR:BSYH:1:30BSY:STD2_OUT_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "STPR:BSYH:1:30BSY:STD2_OUT_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi20 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi20Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "STPR:BSYH:1:30BSY:STD2_OUT_B PP MS") field(ASG, "Internal") } record(bi, "STPR:BSYH:1:30BSY:STD2_OUT_B") { field(DESC, "STD2_Set_Out_30BSY_Inp_B") field(ZNAM, "NOT_OUT") field(ONAM, "OUT") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb20",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb20") #! Field("PLC:BSY0:PP10:30BSY_RDBb20.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb20.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb20.FLNK","STPR:BSYH:1:30BSY:STD2_OUT_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb20.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb20.VAL") #! Record("STPR:BSYH:1:30BSY:STD2_OUT_B_calc",260,18,0,1,"STPR:BSYH:1:30BSY:STD2_OUT_B_calc") #! Field("STPR:BSYH:1:30BSY:STD2_OUT_B_calc.INPA",16777215,0,"STPR:BSYH:1:30BSY:STD2_OUT_B_calc.INPA") #! Link("STPR:BSYH:1:30BSY:STD2_OUT_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb20.VAL") #! Field("STPR:BSYH:1:30BSY:STD2_OUT_B_calc.INPB",16777215,1,"STPR:BSYH:1:30BSY:STD2_OUT_B_calc.INPB") #! Field("STPR:BSYH:1:30BSY:STD2_OUT_B_calc.OUT",16777215,1,"STPR:BSYH:1:30BSY:STD2_OUT_B_calc.OUT") #! Link("STPR:BSYH:1:30BSY:STD2_OUT_B_calc.OUT","STPR:BSYH:1:30BSY:STD2_OUT_B.VAL") #! Record("STPR:BSYH:1:30BSY:STD2_OUT_B",500,20,0,0,"STPR:BSYH:1:30BSY:STD2_OUT_B") #! Field("STPR:BSYH:1:30BSY:STD2_OUT_B.VAL",16777215,1,"STPR:BSYH:1:30BSY:STD2_OUT_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi19") { field(DESC, "Port 30BSY_RDB bit 19") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 19, 1, 1)") field(ZNAM, "NOT_IN") field(ONAM, "IN") field(FLNK, "STPR:BSYS:1:ST34_IN_SUM_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi19Valid") { field(INPA, "PLC:BSY0:PP10:Bi19.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "STPR:BSYS:1:ST34_IN_SUM_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "STPR:BSYS:1:ST34_IN_SUM_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi19 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi19Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "STPR:BSYS:1:ST34_IN_SUM_B PP MS") field(ASG, "Internal") } record(bi, "STPR:BSYS:1:ST34_IN_SUM_B") { field(DESC, "ST34_Set_In_Inp_B") field(ZNAM, "NOT_IN") field(ONAM, "IN") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb19",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb19") #! Field("PLC:BSY0:PP10:30BSY_RDBb19.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb19.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb19.FLNK","STPR:BSYS:1:ST34_IN_SUM_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb19.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb19.VAL") #! Record("STPR:BSYS:1:ST34_IN_SUM_B_calc",260,18,0,1,"STPR:BSYS:1:ST34_IN_SUM_B_calc") #! Field("STPR:BSYS:1:ST34_IN_SUM_B_calc.INPA",16777215,0,"STPR:BSYS:1:ST34_IN_SUM_B_calc.INPA") #! Link("STPR:BSYS:1:ST34_IN_SUM_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb19.VAL") #! Field("STPR:BSYS:1:ST34_IN_SUM_B_calc.INPB",16777215,1,"STPR:BSYS:1:ST34_IN_SUM_B_calc.INPB") #! Field("STPR:BSYS:1:ST34_IN_SUM_B_calc.OUT",16777215,1,"STPR:BSYS:1:ST34_IN_SUM_B_calc.OUT") #! Link("STPR:BSYS:1:ST34_IN_SUM_B_calc.OUT","STPR:BSYS:1:ST34_IN_SUM_B.VAL") #! Record("STPR:BSYS:1:ST34_IN_SUM_B",500,20,0,0,"STPR:BSYS:1:ST34_IN_SUM_B") #! Field("STPR:BSYS:1:ST34_IN_SUM_B.VAL",16777215,1,"STPR:BSYS:1:ST34_IN_SUM_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi18") { field(DESC, "Port 30BSY_RDB bit 18") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 18, 1, 1)") field(ZNAM, "NOT_OUT") field(ONAM, "OUT") field(FLNK, "STPR:BSYS:1:ST34_OUT_SUM_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi18Valid") { field(INPA, "PLC:BSY0:PP10:Bi18.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "STPR:BSYS:1:ST34_OUT_SUM_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "STPR:BSYS:1:ST34_OUT_SUM_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi18 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi18Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "STPR:BSYS:1:ST34_OUT_SUM_B PP MS") field(ASG, "Internal") } record(bi, "STPR:BSYS:1:ST34_OUT_SUM_B") { field(DESC, "ST34_Set_Out_Inp_B") field(ZNAM, "NOT_OUT") field(ONAM, "OUT") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb18",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb18") #! Field("PLC:BSY0:PP10:30BSY_RDBb18.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb18.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb18.FLNK","STPR:BSYS:1:ST34_OUT_SUM_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb18.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb18.VAL") #! Record("STPR:BSYS:1:ST34_OUT_SUM_B_calc",260,18,0,1,"STPR:BSYS:1:ST34_OUT_SUM_B_calc") #! Field("STPR:BSYS:1:ST34_OUT_SUM_B_calc.INPA",16777215,0,"STPR:BSYS:1:ST34_OUT_SUM_B_calc.INPA") #! Link("STPR:BSYS:1:ST34_OUT_SUM_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb18.VAL") #! Field("STPR:BSYS:1:ST34_OUT_SUM_B_calc.INPB",16777215,1,"STPR:BSYS:1:ST34_OUT_SUM_B_calc.INPB") #! Field("STPR:BSYS:1:ST34_OUT_SUM_B_calc.OUT",16777215,1,"STPR:BSYS:1:ST34_OUT_SUM_B_calc.OUT") #! Link("STPR:BSYS:1:ST34_OUT_SUM_B_calc.OUT","STPR:BSYS:1:ST34_OUT_SUM_B.VAL") #! Record("STPR:BSYS:1:ST34_OUT_SUM_B",500,20,0,0,"STPR:BSYS:1:ST34_OUT_SUM_B") #! Field("STPR:BSYS:1:ST34_OUT_SUM_B.VAL",16777215,1,"STPR:BSYS:1:ST34_OUT_SUM_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi17") { field(DESC, "Port 30BSY_RDB bit 17") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 17, 1, 1)") field(ZNAM, "NOT_IN") field(ONAM, "IN") field(FLNK, "STPR:CLTS:585:IN_INP_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi17Valid") { field(INPA, "PLC:BSY0:PP10:Bi17.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "STPR:CLTS:585:IN_INP_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "STPR:CLTS:585:IN_INP_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi17 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi17Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "STPR:CLTS:585:IN_INP_B PP MS") field(ASG, "Internal") } record(bi, "STPR:CLTS:585:IN_INP_B") { field(DESC, "STCLTS_In_B") field(ZNAM, "NOT_IN") field(ONAM, "IN") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb17",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb17") #! Field("PLC:BSY0:PP10:30BSY_RDBb17.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb17.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb17.FLNK","STPR:CLTS:585:IN_INP_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb17.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb17.VAL") #! Record("STPR:CLTS:585:IN_INP_B_calc",260,18,0,1,"STPR:CLTS:585:IN_INP_B_calc") #! Field("STPR:CLTS:585:IN_INP_B_calc.INPA",16777215,0,"STPR:CLTS:585:IN_INP_B_calc.INPA") #! Link("STPR:CLTS:585:IN_INP_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb17.VAL") #! Field("STPR:CLTS:585:IN_INP_B_calc.INPB",16777215,1,"STPR:CLTS:585:IN_INP_B_calc.INPB") #! Field("STPR:CLTS:585:IN_INP_B_calc.OUT",16777215,1,"STPR:CLTS:585:IN_INP_B_calc.OUT") #! Link("STPR:CLTS:585:IN_INP_B_calc.OUT","STPR:CLTS:585:IN_INP_B.VAL") #! Record("STPR:CLTS:585:IN_INP_B",500,20,0,0,"STPR:CLTS:585:IN_INP_B") #! Field("STPR:CLTS:585:IN_INP_B.VAL",16777215,1,"STPR:CLTS:585:IN_INP_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi16") { field(DESC, "Port 30BSY_RDB bit 16") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 16, 1, 1)") field(ZNAM, "NOT_OUT") field(ONAM, "OUT") field(FLNK, "STPR:CLTS:585:OUT_INP_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi16Valid") { field(INPA, "PLC:BSY0:PP10:Bi16.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "STPR:CLTS:585:OUT_INP_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "STPR:CLTS:585:OUT_INP_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi16 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi16Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "STPR:CLTS:585:OUT_INP_B PP MS") field(ASG, "Internal") } record(bi, "STPR:CLTS:585:OUT_INP_B") { field(DESC, "STCLTS_Out_B") field(ZNAM, "NOT_OUT") field(ONAM, "OUT") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb16",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb16") #! Field("PLC:BSY0:PP10:30BSY_RDBb16.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb16.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb16.FLNK","STPR:CLTS:585:OUT_INP_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb16.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb16.VAL") #! Record("STPR:CLTS:585:OUT_INP_B_calc",260,18,0,1,"STPR:CLTS:585:OUT_INP_B_calc") #! Field("STPR:CLTS:585:OUT_INP_B_calc.INPA",16777215,0,"STPR:CLTS:585:OUT_INP_B_calc.INPA") #! Link("STPR:CLTS:585:OUT_INP_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb16.VAL") #! Field("STPR:CLTS:585:OUT_INP_B_calc.INPB",16777215,1,"STPR:CLTS:585:OUT_INP_B_calc.INPB") #! Field("STPR:CLTS:585:OUT_INP_B_calc.OUT",16777215,1,"STPR:CLTS:585:OUT_INP_B_calc.OUT") #! Link("STPR:CLTS:585:OUT_INP_B_calc.OUT","STPR:CLTS:585:OUT_INP_B.VAL") #! Record("STPR:CLTS:585:OUT_INP_B",500,20,0,0,"STPR:CLTS:585:OUT_INP_B") #! Field("STPR:CLTS:585:OUT_INP_B.VAL",16777215,1,"STPR:CLTS:585:OUT_INP_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi95") { field(DESC, "Port 30BSY_RDB bit 95") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 95, 1, 1)") field(ZNAM, "NOT_OFF") field(ONAM, "OFF") field(FLNK, "PPS:CLTS:1:KICK_OFF_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi95Valid") { field(INPA, "PLC:BSY0:PP10:Bi95.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:CLTS:1:KICK_OFF_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:CLTS:1:KICK_OFF_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi95 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi95Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:CLTS:1:KICK_OFF_B PP MS") field(ASG, "Internal") } record(bi, "PPS:CLTS:1:KICK_OFF_B") { field(DESC, "CLTS_Kicker_OFF_B") field(ZNAM, "NOT_OFF") field(ONAM, "OFF") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb95",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb95") #! Field("PLC:BSY0:PP10:30BSY_RDBb95.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb95.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb95.FLNK","PPS:CLTS:1:KICK_OFF_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb95.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb95.VAL") #! Record("PPS:CLTS:1:KICK_OFF_B_calc",260,18,0,1,"PPS:CLTS:1:KICK_OFF_B_calc") #! Field("PPS:CLTS:1:KICK_OFF_B_calc.INPA",16777215,0,"PPS:CLTS:1:KICK_OFF_B_calc.INPA") #! Link("PPS:CLTS:1:KICK_OFF_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb95.VAL") #! Field("PPS:CLTS:1:KICK_OFF_B_calc.INPB",16777215,1,"PPS:CLTS:1:KICK_OFF_B_calc.INPB") #! Field("PPS:CLTS:1:KICK_OFF_B_calc.OUT",16777215,1,"PPS:CLTS:1:KICK_OFF_B_calc.OUT") #! Link("PPS:CLTS:1:KICK_OFF_B_calc.OUT","PPS:CLTS:1:KICK_OFF_B.VAL") #! Record("PPS:CLTS:1:KICK_OFF_B",500,20,0,0,"PPS:CLTS:1:KICK_OFF_B") #! Field("PPS:CLTS:1:KICK_OFF_B.VAL",16777215,1,"PPS:CLTS:1:KICK_OFF_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi94") { field(DESC, "Port 30BSY_RDB bit 94") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 94, 1, 1)") field(ZNAM, "NOT_OFF") field(ONAM, "OFF") field(FLNK, "PPS:CLTS:1:DCBEND_OFF_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi94Valid") { field(INPA, "PLC:BSY0:PP10:Bi94.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:CLTS:1:DCBEND_OFF_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:CLTS:1:DCBEND_OFF_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi94 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi94Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:CLTS:1:DCBEND_OFF_B PP MS") field(ASG, "Internal") } record(bi, "PPS:CLTS:1:DCBEND_OFF_B") { field(DESC, "CLTS_DC_Bend_OFF_B") field(ZNAM, "NOT_OFF") field(ONAM, "OFF") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb94",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb94") #! Field("PLC:BSY0:PP10:30BSY_RDBb94.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb94.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb94.FLNK","PPS:CLTS:1:DCBEND_OFF_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb94.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb94.VAL") #! Record("PPS:CLTS:1:DCBEND_OFF_B_calc",260,18,0,1,"PPS:CLTS:1:DCBEND_OFF_B_calc") #! Field("PPS:CLTS:1:DCBEND_OFF_B_calc.INPA",16777215,0,"PPS:CLTS:1:DCBEND_OFF_B_calc.INPA") #! Link("PPS:CLTS:1:DCBEND_OFF_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb94.VAL") #! Field("PPS:CLTS:1:DCBEND_OFF_B_calc.INPB",16777215,1,"PPS:CLTS:1:DCBEND_OFF_B_calc.INPB") #! Field("PPS:CLTS:1:DCBEND_OFF_B_calc.OUT",16777215,1,"PPS:CLTS:1:DCBEND_OFF_B_calc.OUT") #! Link("PPS:CLTS:1:DCBEND_OFF_B_calc.OUT","PPS:CLTS:1:DCBEND_OFF_B.VAL") #! Record("PPS:CLTS:1:DCBEND_OFF_B",500,20,0,0,"PPS:CLTS:1:DCBEND_OFF_B") #! Field("PPS:CLTS:1:DCBEND_OFF_B.VAL",16777215,1,"PPS:CLTS:1:DCBEND_OFF_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi92") { field(DESC, "Port 30BSY_RDB bit 92") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 92, 1, 1)") field(ZNAM, "NOT_OFF") field(ONAM, "OFF") field(FLNK, "PPS:BSYS:1:MERGE_OFF_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi92Valid") { field(INPA, "PLC:BSY0:PP10:Bi92.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:BSYS:1:MERGE_OFF_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:BSYS:1:MERGE_OFF_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi92 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi92Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:BSYS:1:MERGE_OFF_B PP MS") field(ASG, "Internal") } record(bi, "PPS:BSYS:1:MERGE_OFF_B") { field(DESC, "SXR_Merge_Dipole_OFF_B") field(ZNAM, "NOT_OFF") field(ONAM, "OFF") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb92",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb92") #! Field("PLC:BSY0:PP10:30BSY_RDBb92.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb92.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb92.FLNK","PPS:BSYS:1:MERGE_OFF_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb92.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb92.VAL") #! Record("PPS:BSYS:1:MERGE_OFF_B_calc",260,18,0,1,"PPS:BSYS:1:MERGE_OFF_B_calc") #! Field("PPS:BSYS:1:MERGE_OFF_B_calc.INPA",16777215,0,"PPS:BSYS:1:MERGE_OFF_B_calc.INPA") #! Link("PPS:BSYS:1:MERGE_OFF_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb92.VAL") #! Field("PPS:BSYS:1:MERGE_OFF_B_calc.INPB",16777215,1,"PPS:BSYS:1:MERGE_OFF_B_calc.INPB") #! Field("PPS:BSYS:1:MERGE_OFF_B_calc.OUT",16777215,1,"PPS:BSYS:1:MERGE_OFF_B_calc.OUT") #! Link("PPS:BSYS:1:MERGE_OFF_B_calc.OUT","PPS:BSYS:1:MERGE_OFF_B.VAL") #! Record("PPS:BSYS:1:MERGE_OFF_B",500,20,0,0,"PPS:BSYS:1:MERGE_OFF_B") #! Field("PPS:BSYS:1:MERGE_OFF_B.VAL",16777215,1,"PPS:BSYS:1:MERGE_OFF_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi90") { field(DESC, "Port 30BSY_RDB bit 90") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 90, 1, 1)") field(ZNAM, "OFF") field(ONAM, "ON") field(FLNK, "PPS:CLTS:1:DCBEND_ON_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi90Valid") { field(INPA, "PLC:BSY0:PP10:Bi90.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:CLTS:1:DCBEND_ON_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:CLTS:1:DCBEND_ON_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi90 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi90Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:CLTS:1:DCBEND_ON_B PP MS") field(ASG, "Internal") } record(bi, "PPS:CLTS:1:DCBEND_ON_B") { field(DESC, "CLTS_DC_Bend_On_B") field(ZNAM, "OFF") field(ONAM, "ON") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb90",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb90") #! Field("PLC:BSY0:PP10:30BSY_RDBb90.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb90.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb90.FLNK","PPS:CLTS:1:DCBEND_ON_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb90.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb90.VAL") #! Record("PPS:CLTS:1:DCBEND_ON_B_calc",260,18,0,1,"PPS:CLTS:1:DCBEND_ON_B_calc") #! Field("PPS:CLTS:1:DCBEND_ON_B_calc.INPA",16777215,0,"PPS:CLTS:1:DCBEND_ON_B_calc.INPA") #! Link("PPS:CLTS:1:DCBEND_ON_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb90.VAL") #! Field("PPS:CLTS:1:DCBEND_ON_B_calc.INPB",16777215,1,"PPS:CLTS:1:DCBEND_ON_B_calc.INPB") #! Field("PPS:CLTS:1:DCBEND_ON_B_calc.OUT",16777215,1,"PPS:CLTS:1:DCBEND_ON_B_calc.OUT") #! Link("PPS:CLTS:1:DCBEND_ON_B_calc.OUT","PPS:CLTS:1:DCBEND_ON_B.VAL") #! Record("PPS:CLTS:1:DCBEND_ON_B",500,20,0,0,"PPS:CLTS:1:DCBEND_ON_B") #! Field("PPS:CLTS:1:DCBEND_ON_B.VAL",16777215,1,"PPS:CLTS:1:DCBEND_ON_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi89") { field(DESC, "Port 30BSY_RDB bit 89") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 89, 1, 1)") field(ZNAM, "OFF") field(ONAM, "ON") field(FLNK, "PPS:CLTS:1:SEP_ON_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi89Valid") { field(INPA, "PLC:BSY0:PP10:Bi89.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:CLTS:1:SEP_ON_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:CLTS:1:SEP_ON_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi89 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi89Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:CLTS:1:SEP_ON_B PP MS") field(ASG, "Internal") } record(bi, "PPS:CLTS:1:SEP_ON_B") { field(DESC, "CLTS_Septum_On_B") field(ZNAM, "OFF") field(ONAM, "ON") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb89",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb89") #! Field("PLC:BSY0:PP10:30BSY_RDBb89.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb89.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb89.FLNK","PPS:CLTS:1:SEP_ON_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb89.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb89.VAL") #! Record("PPS:CLTS:1:SEP_ON_B_calc",260,18,0,1,"PPS:CLTS:1:SEP_ON_B_calc") #! Field("PPS:CLTS:1:SEP_ON_B_calc.INPA",16777215,0,"PPS:CLTS:1:SEP_ON_B_calc.INPA") #! Link("PPS:CLTS:1:SEP_ON_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb89.VAL") #! Field("PPS:CLTS:1:SEP_ON_B_calc.INPB",16777215,1,"PPS:CLTS:1:SEP_ON_B_calc.INPB") #! Field("PPS:CLTS:1:SEP_ON_B_calc.OUT",16777215,1,"PPS:CLTS:1:SEP_ON_B_calc.OUT") #! Link("PPS:CLTS:1:SEP_ON_B_calc.OUT","PPS:CLTS:1:SEP_ON_B.VAL") #! Record("PPS:CLTS:1:SEP_ON_B",500,20,0,0,"PPS:CLTS:1:SEP_ON_B") #! Field("PPS:CLTS:1:SEP_ON_B.VAL",16777215,1,"PPS:CLTS:1:SEP_ON_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi88") { field(DESC, "Port 30BSY_RDB bit 88") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 88, 1, 1)") field(ZNAM, "OFF") field(ONAM, "ON") field(FLNK, "PPS:BSYS:1:MERGE_ON_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi88Valid") { field(INPA, "PLC:BSY0:PP10:Bi88.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:BSYS:1:MERGE_ON_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:BSYS:1:MERGE_ON_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi88 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi88Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:BSYS:1:MERGE_ON_B PP MS") field(ASG, "Internal") } record(bi, "PPS:BSYS:1:MERGE_ON_B") { field(DESC, "SXR_Merge_Dipole_On_B") field(ZNAM, "OFF") field(ONAM, "ON") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb88",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb88") #! Field("PLC:BSY0:PP10:30BSY_RDBb88.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb88.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb88.FLNK","PPS:BSYS:1:MERGE_ON_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb88.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb88.VAL") #! Record("PPS:BSYS:1:MERGE_ON_B_calc",260,18,0,1,"PPS:BSYS:1:MERGE_ON_B_calc") #! Field("PPS:BSYS:1:MERGE_ON_B_calc.INPA",16777215,0,"PPS:BSYS:1:MERGE_ON_B_calc.INPA") #! Link("PPS:BSYS:1:MERGE_ON_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb88.VAL") #! Field("PPS:BSYS:1:MERGE_ON_B_calc.INPB",16777215,1,"PPS:BSYS:1:MERGE_ON_B_calc.INPB") #! Field("PPS:BSYS:1:MERGE_ON_B_calc.OUT",16777215,1,"PPS:BSYS:1:MERGE_ON_B_calc.OUT") #! Link("PPS:BSYS:1:MERGE_ON_B_calc.OUT","PPS:BSYS:1:MERGE_ON_B.VAL") #! Record("PPS:BSYS:1:MERGE_ON_B",500,20,0,0,"PPS:BSYS:1:MERGE_ON_B") #! Field("PPS:BSYS:1:MERGE_ON_B.VAL",16777215,1,"PPS:BSYS:1:MERGE_ON_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi103") { field(DESC, "Port 30BSY_RDB bit 103") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 103, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(FLNK, "PPS:SYSE:1:30BSY:INTLK_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi103Valid") { field(INPA, "PLC:BSY0:PP10:Bi103.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:INTLK_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:INTLK_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi103 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi103Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:INTLK_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:INTLK_B") { field(DESC, "30-BSY interlock A (spare)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb103",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb103") #! Field("PLC:BSY0:PP10:30BSY_RDBb103.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb103.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb103.FLNK","PPS:SYSE:1:30BSY:INTLK_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb103.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb103.VAL") #! Record("PPS:SYSE:1:30BSY:INTLK_B_calc",260,18,0,1,"PPS:SYSE:1:30BSY:INTLK_B_calc") #! Field("PPS:SYSE:1:30BSY:INTLK_B_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:INTLK_B_calc.INPA") #! Link("PPS:SYSE:1:30BSY:INTLK_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb103.VAL") #! Field("PPS:SYSE:1:30BSY:INTLK_B_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:INTLK_B_calc.INPB") #! Field("PPS:SYSE:1:30BSY:INTLK_B_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:INTLK_B_calc.OUT") #! Link("PPS:SYSE:1:30BSY:INTLK_B_calc.OUT","PPS:SYSE:1:30BSY:INTLK_B.VAL") #! Record("PPS:SYSE:1:30BSY:INTLK_B",500,20,0,0,"PPS:SYSE:1:30BSY:INTLK_B") #! Field("PPS:SYSE:1:30BSY:INTLK_B.VAL",16777215,1,"PPS:SYSE:1:30BSY:INTLK_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi102") { field(DESC, "Port 30BSY_RDB bit 102") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 102, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(FLNK, "PPS:SYSE:1:CU:INTLK_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi102Valid") { field(INPA, "PLC:BSY0:PP10:Bi102.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:CU:INTLK_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:CU:INTLK_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi102 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi102Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:CU:INTLK_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:CU:INTLK_B") { field(DESC, "Cu beam interlock A (spare)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb102",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb102") #! Field("PLC:BSY0:PP10:30BSY_RDBb102.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb102.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb102.FLNK","PPS:SYSE:1:CU:INTLK_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb102.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb102.VAL") #! Record("PPS:SYSE:1:CU:INTLK_B_calc",260,18,0,1,"PPS:SYSE:1:CU:INTLK_B_calc") #! Field("PPS:SYSE:1:CU:INTLK_B_calc.INPA",16777215,0,"PPS:SYSE:1:CU:INTLK_B_calc.INPA") #! Link("PPS:SYSE:1:CU:INTLK_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb102.VAL") #! Field("PPS:SYSE:1:CU:INTLK_B_calc.INPB",16777215,1,"PPS:SYSE:1:CU:INTLK_B_calc.INPB") #! Field("PPS:SYSE:1:CU:INTLK_B_calc.OUT",16777215,1,"PPS:SYSE:1:CU:INTLK_B_calc.OUT") #! Link("PPS:SYSE:1:CU:INTLK_B_calc.OUT","PPS:SYSE:1:CU:INTLK_B.VAL") #! Record("PPS:SYSE:1:CU:INTLK_B",500,20,0,0,"PPS:SYSE:1:CU:INTLK_B") #! Field("PPS:SYSE:1:CU:INTLK_B.VAL",16777215,1,"PPS:SYSE:1:CU:INTLK_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi101") { field(DESC, "Port 30BSY_RDB bit 101") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 101, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(FLNK, "PPS:SYSE:1:SC:INTLK_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi101Valid") { field(INPA, "PLC:BSY0:PP10:Bi101.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:SC:INTLK_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:SC:INTLK_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi101 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi101Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:SC:INTLK_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:SC:INTLK_B") { field(DESC, "SC beam interlock A (spare)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb101",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb101") #! Field("PLC:BSY0:PP10:30BSY_RDBb101.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb101.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb101.FLNK","PPS:SYSE:1:SC:INTLK_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb101.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb101.VAL") #! Record("PPS:SYSE:1:SC:INTLK_B_calc",260,18,0,1,"PPS:SYSE:1:SC:INTLK_B_calc") #! Field("PPS:SYSE:1:SC:INTLK_B_calc.INPA",16777215,0,"PPS:SYSE:1:SC:INTLK_B_calc.INPA") #! Link("PPS:SYSE:1:SC:INTLK_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb101.VAL") #! Field("PPS:SYSE:1:SC:INTLK_B_calc.INPB",16777215,1,"PPS:SYSE:1:SC:INTLK_B_calc.INPB") #! Field("PPS:SYSE:1:SC:INTLK_B_calc.OUT",16777215,1,"PPS:SYSE:1:SC:INTLK_B_calc.OUT") #! Link("PPS:SYSE:1:SC:INTLK_B_calc.OUT","PPS:SYSE:1:SC:INTLK_B.VAL") #! Record("PPS:SYSE:1:SC:INTLK_B",500,20,0,0,"PPS:SYSE:1:SC:INTLK_B") #! Field("PPS:SYSE:1:SC:INTLK_B.VAL",16777215,1,"PPS:SYSE:1:SC:INTLK_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi100") { field(DESC, "Port 30BSY_RDB bit 100") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 100, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(FLNK, "PPS:SYSE:1:BTH_ACCESS_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi100Valid") { field(INPA, "PLC:BSY0:PP10:Bi100.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:BTH_ACCESS_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:BTH_ACCESS_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi100 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi100Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:BTH_ACCESS_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:BTH_ACCESS_B") { field(DESC, "BTH Access cond. A (spare)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb100",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb100") #! Field("PLC:BSY0:PP10:30BSY_RDBb100.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb100.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb100.FLNK","PPS:SYSE:1:BTH_ACCESS_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb100.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb100.VAL") #! Record("PPS:SYSE:1:BTH_ACCESS_B_calc",260,18,0,1,"PPS:SYSE:1:BTH_ACCESS_B_calc") #! Field("PPS:SYSE:1:BTH_ACCESS_B_calc.INPA",16777215,0,"PPS:SYSE:1:BTH_ACCESS_B_calc.INPA") #! Link("PPS:SYSE:1:BTH_ACCESS_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb100.VAL") #! Field("PPS:SYSE:1:BTH_ACCESS_B_calc.INPB",16777215,1,"PPS:SYSE:1:BTH_ACCESS_B_calc.INPB") #! Field("PPS:SYSE:1:BTH_ACCESS_B_calc.OUT",16777215,1,"PPS:SYSE:1:BTH_ACCESS_B_calc.OUT") #! Link("PPS:SYSE:1:BTH_ACCESS_B_calc.OUT","PPS:SYSE:1:BTH_ACCESS_B.VAL") #! Record("PPS:SYSE:1:BTH_ACCESS_B",500,20,0,0,"PPS:SYSE:1:BTH_ACCESS_B") #! Field("PPS:SYSE:1:BTH_ACCESS_B.VAL",16777215,1,"PPS:SYSE:1:BTH_ACCESS_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi99") { field(DESC, "Port 30BSY_RDB bit 99") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 99, 1, 1)") field(ZNAM, "Test") field(ONAM, "Normal") field(FLNK, "PPS:SYSE:1:30BSY:CROSS_CHECK_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi99Valid") { field(INPA, "PLC:BSY0:PP10:Bi99.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:CROSS_CHECK_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:CROSS_CHECK_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi99 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi99Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:CROSS_CHECK_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:CROSS_CHECK_B") { field(DESC, "Cross_Check_Keysw_in_Normal_B") field(ZNAM, "Test") field(ONAM, "Normal") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb99",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb99") #! Field("PLC:BSY0:PP10:30BSY_RDBb99.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb99.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb99.FLNK","PPS:SYSE:1:30BSY:CROSS_CHECK_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb99.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb99.VAL") #! Record("PPS:SYSE:1:30BSY:CROSS_CHECK_B_calc",260,18,0,1,"PPS:SYSE:1:30BSY:CROSS_CHECK_B_calc") #! Field("PPS:SYSE:1:30BSY:CROSS_CHECK_B_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:CROSS_CHECK_B_calc.INPA") #! Link("PPS:SYSE:1:30BSY:CROSS_CHECK_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb99.VAL") #! Field("PPS:SYSE:1:30BSY:CROSS_CHECK_B_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:CROSS_CHECK_B_calc.INPB") #! Field("PPS:SYSE:1:30BSY:CROSS_CHECK_B_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:CROSS_CHECK_B_calc.OUT") #! Link("PPS:SYSE:1:30BSY:CROSS_CHECK_B_calc.OUT","PPS:SYSE:1:30BSY:CROSS_CHECK_B.VAL") #! Record("PPS:SYSE:1:30BSY:CROSS_CHECK_B",500,20,0,0,"PPS:SYSE:1:30BSY:CROSS_CHECK_B") #! Field("PPS:SYSE:1:30BSY:CROSS_CHECK_B.VAL",16777215,1,"PPS:SYSE:1:30BSY:CROSS_CHECK_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi98") { field(DESC, "Port 30BSY_RDB bit 98") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 98, 1, 1)") field(ZNAM, "Fault") field(ONAM, "Ok") field(FLNK, "PPS:SYSE:1:30BSY:HRTBT_INP_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi98Valid") { field(INPA, "PLC:BSY0:PP10:Bi98.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:HRTBT_INP_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:HRTBT_INP_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi98 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi98Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:HRTBT_INP_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:HRTBT_INP_B") { field(DESC, "Heartbeat IN (other chn.) B") field(ZNAM, "Fault") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb98",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb98") #! Field("PLC:BSY0:PP10:30BSY_RDBb98.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb98.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb98.FLNK","PPS:SYSE:1:30BSY:HRTBT_INP_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb98.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb98.VAL") #! Record("PPS:SYSE:1:30BSY:HRTBT_INP_B_calc",260,18,0,1,"PPS:SYSE:1:30BSY:HRTBT_INP_B_calc") #! Field("PPS:SYSE:1:30BSY:HRTBT_INP_B_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:HRTBT_INP_B_calc.INPA") #! Link("PPS:SYSE:1:30BSY:HRTBT_INP_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb98.VAL") #! Field("PPS:SYSE:1:30BSY:HRTBT_INP_B_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:HRTBT_INP_B_calc.INPB") #! Field("PPS:SYSE:1:30BSY:HRTBT_INP_B_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:HRTBT_INP_B_calc.OUT") #! Link("PPS:SYSE:1:30BSY:HRTBT_INP_B_calc.OUT","PPS:SYSE:1:30BSY:HRTBT_INP_B.VAL") #! Record("PPS:SYSE:1:30BSY:HRTBT_INP_B",500,20,0,0,"PPS:SYSE:1:30BSY:HRTBT_INP_B") #! Field("PPS:SYSE:1:30BSY:HRTBT_INP_B.VAL",16777215,1,"PPS:SYSE:1:30BSY:HRTBT_INP_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi97") { field(DESC, "Port 30BSY_RDB bit 97") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 97, 1, 1)") field(ZNAM, "NOT_READY") field(ONAM, "READY") field(FLNK, "PPS:SYSE:1:BEAM_ON_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi97Valid") { field(INPA, "PLC:BSY0:PP10:Bi97.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:BEAM_ON_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:BEAM_ON_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi97 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi97Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:BEAM_ON_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:BEAM_ON_B") { field(DESC, "Linac E. Global in Ready for Beam") field(ZNAM, "NOT_READY") field(ONAM, "READY") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb97",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb97") #! Field("PLC:BSY0:PP10:30BSY_RDBb97.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb97.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb97.FLNK","PPS:SYSE:1:BEAM_ON_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb97.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb97.VAL") #! Record("PPS:SYSE:1:BEAM_ON_B_calc",260,18,0,1,"PPS:SYSE:1:BEAM_ON_B_calc") #! Field("PPS:SYSE:1:BEAM_ON_B_calc.INPA",16777215,0,"PPS:SYSE:1:BEAM_ON_B_calc.INPA") #! Link("PPS:SYSE:1:BEAM_ON_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb97.VAL") #! Field("PPS:SYSE:1:BEAM_ON_B_calc.INPB",16777215,1,"PPS:SYSE:1:BEAM_ON_B_calc.INPB") #! Field("PPS:SYSE:1:BEAM_ON_B_calc.OUT",16777215,1,"PPS:SYSE:1:BEAM_ON_B_calc.OUT") #! Link("PPS:SYSE:1:BEAM_ON_B_calc.OUT","PPS:SYSE:1:BEAM_ON_B.VAL") #! Record("PPS:SYSE:1:BEAM_ON_B",500,20,0,0,"PPS:SYSE:1:BEAM_ON_B") #! Field("PPS:SYSE:1:BEAM_ON_B.VAL",16777215,1,"PPS:SYSE:1:BEAM_ON_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi111") { field(DESC, "Port 30BSY_RDB bit 111") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 111, 1, 1)") field(ZNAM, "Not_Reset") field(ONAM, "Reset") field(FLNK, "PPS:SYSE:1:HW_RESET_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi111Valid") { field(INPA, "PLC:BSY0:PP10:Bi111.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:HW_RESET_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:HW_RESET_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi111 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi111Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:HW_RESET_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:HW_RESET_B") { field(DESC, "HW Reset B") field(ZNAM, "Not_Reset") field(ONAM, "Reset") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb111",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb111") #! Field("PLC:BSY0:PP10:30BSY_RDBb111.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb111.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb111.FLNK","PPS:SYSE:1:HW_RESET_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb111.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb111.VAL") #! Record("PPS:SYSE:1:HW_RESET_B_calc",260,18,0,1,"PPS:SYSE:1:HW_RESET_B_calc") #! Field("PPS:SYSE:1:HW_RESET_B_calc.INPA",16777215,0,"PPS:SYSE:1:HW_RESET_B_calc.INPA") #! Link("PPS:SYSE:1:HW_RESET_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb111.VAL") #! Field("PPS:SYSE:1:HW_RESET_B_calc.INPB",16777215,1,"PPS:SYSE:1:HW_RESET_B_calc.INPB") #! Field("PPS:SYSE:1:HW_RESET_B_calc.OUT",16777215,1,"PPS:SYSE:1:HW_RESET_B_calc.OUT") #! Link("PPS:SYSE:1:HW_RESET_B_calc.OUT","PPS:SYSE:1:HW_RESET_B.VAL") #! Record("PPS:SYSE:1:HW_RESET_B",500,20,0,0,"PPS:SYSE:1:HW_RESET_B") #! Field("PPS:SYSE:1:HW_RESET_B.VAL",16777215,1,"PPS:SYSE:1:HW_RESET_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi110") { field(DESC, "Port 30BSY_RDB bit 110") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 110, 1, 1)") field(ZNAM, "Not_Secure") field(ONAM, "Secure") field(FLNK, "PPS:SYSE:1:RSY_SECURE_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi110Valid") { field(INPA, "PLC:BSY0:PP10:Bi110.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:RSY_SECURE_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:RSY_SECURE_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi110 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi110Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:RSY_SECURE_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:RSY_SECURE_B") { field(DESC, "RSY Secure B") field(ZNAM, "Not_Secure") field(ONAM, "Secure") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb110",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb110") #! Field("PLC:BSY0:PP10:30BSY_RDBb110.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb110.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb110.FLNK","PPS:SYSE:1:RSY_SECURE_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb110.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb110.VAL") #! Record("PPS:SYSE:1:RSY_SECURE_B_calc",260,18,0,1,"PPS:SYSE:1:RSY_SECURE_B_calc") #! Field("PPS:SYSE:1:RSY_SECURE_B_calc.INPA",16777215,0,"PPS:SYSE:1:RSY_SECURE_B_calc.INPA") #! Link("PPS:SYSE:1:RSY_SECURE_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb110.VAL") #! Field("PPS:SYSE:1:RSY_SECURE_B_calc.INPB",16777215,1,"PPS:SYSE:1:RSY_SECURE_B_calc.INPB") #! Field("PPS:SYSE:1:RSY_SECURE_B_calc.OUT",16777215,1,"PPS:SYSE:1:RSY_SECURE_B_calc.OUT") #! Link("PPS:SYSE:1:RSY_SECURE_B_calc.OUT","PPS:SYSE:1:RSY_SECURE_B.VAL") #! Record("PPS:SYSE:1:RSY_SECURE_B",500,20,0,0,"PPS:SYSE:1:RSY_SECURE_B") #! Field("PPS:SYSE:1:RSY_SECURE_B.VAL",16777215,1,"PPS:SYSE:1:RSY_SECURE_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi109") { field(DESC, "Port 30BSY_RDB bit 109") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 109, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(FLNK, "PPS:SYSE:1:SPARE_4_i6_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi109Valid") { field(INPA, "PLC:BSY0:PP10:Bi109.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:SPARE_4_i6_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:SPARE_4_i6_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi109 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi109Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:SPARE_4_i6_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:SPARE_4_i6_B") { field(DESC, "Spare 4.i6 B") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb109",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb109") #! Field("PLC:BSY0:PP10:30BSY_RDBb109.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb109.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb109.FLNK","PPS:SYSE:1:SPARE_4_i6_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb109.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb109.VAL") #! Record("PPS:SYSE:1:SPARE_4_i6_B_calc",260,18,0,1,"PPS:SYSE:1:SPARE_4_i6_B_calc") #! Field("PPS:SYSE:1:SPARE_4_i6_B_calc.INPA",16777215,0,"PPS:SYSE:1:SPARE_4_i6_B_calc.INPA") #! Link("PPS:SYSE:1:SPARE_4_i6_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb109.VAL") #! Field("PPS:SYSE:1:SPARE_4_i6_B_calc.INPB",16777215,1,"PPS:SYSE:1:SPARE_4_i6_B_calc.INPB") #! Field("PPS:SYSE:1:SPARE_4_i6_B_calc.OUT",16777215,1,"PPS:SYSE:1:SPARE_4_i6_B_calc.OUT") #! Link("PPS:SYSE:1:SPARE_4_i6_B_calc.OUT","PPS:SYSE:1:SPARE_4_i6_B.VAL") #! Record("PPS:SYSE:1:SPARE_4_i6_B",500,20,0,0,"PPS:SYSE:1:SPARE_4_i6_B") #! Field("PPS:SYSE:1:SPARE_4_i6_B.VAL",16777215,1,"PPS:SYSE:1:SPARE_4_i6_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi108") { field(DESC, "Port 30BSY_RDB bit 108") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 108, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(FLNK, "PPS:SYSE:1:SPARE_4_i7_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi108Valid") { field(INPA, "PLC:BSY0:PP10:Bi108.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:SPARE_4_i7_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:SPARE_4_i7_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi108 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi108Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:SPARE_4_i7_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:SPARE_4_i7_B") { field(DESC, "Spare 4.i7 B") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb108",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb108") #! Field("PLC:BSY0:PP10:30BSY_RDBb108.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb108.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb108.FLNK","PPS:SYSE:1:SPARE_4_i7_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb108.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb108.VAL") #! Record("PPS:SYSE:1:SPARE_4_i7_B_calc",260,18,0,1,"PPS:SYSE:1:SPARE_4_i7_B_calc") #! Field("PPS:SYSE:1:SPARE_4_i7_B_calc.INPA",16777215,0,"PPS:SYSE:1:SPARE_4_i7_B_calc.INPA") #! Link("PPS:SYSE:1:SPARE_4_i7_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb108.VAL") #! Field("PPS:SYSE:1:SPARE_4_i7_B_calc.INPB",16777215,1,"PPS:SYSE:1:SPARE_4_i7_B_calc.INPB") #! Field("PPS:SYSE:1:SPARE_4_i7_B_calc.OUT",16777215,1,"PPS:SYSE:1:SPARE_4_i7_B_calc.OUT") #! Link("PPS:SYSE:1:SPARE_4_i7_B_calc.OUT","PPS:SYSE:1:SPARE_4_i7_B.VAL") #! Record("PPS:SYSE:1:SPARE_4_i7_B",500,20,0,0,"PPS:SYSE:1:SPARE_4_i7_B") #! Field("PPS:SYSE:1:SPARE_4_i7_B.VAL",16777215,1,"PPS:SYSE:1:SPARE_4_i7_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi107") { field(DESC, "Port 30BSY_RDB bit 107") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 107, 1, 1)") field(ZNAM, "Not_Secure") field(ONAM, "Secure") field(FLNK, "PPS:SYSE:2:30BSY:SECURE_COM_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi107Valid") { field(INPA, "PLC:BSY0:PP10:Bi107.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:2:30BSY:SECURE_COM_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:2:30BSY:SECURE_COM_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi107 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi107Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:2:30BSY:SECURE_COM_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:2:30BSY:SECURE_COM_B") { field(DESC, "30-BSY Sec. Comp. (test mode)") field(ZNAM, "Not_Secure") field(ONAM, "Secure") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb107",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb107") #! Field("PLC:BSY0:PP10:30BSY_RDBb107.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb107.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb107.FLNK","PPS:SYSE:2:30BSY:SECURE_COM_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb107.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb107.VAL") #! Record("PPS:SYSE:2:30BSY:SECURE_COM_B_calc",260,18,0,1,"PPS:SYSE:2:30BSY:SECURE_COM_B_calc") #! Field("PPS:SYSE:2:30BSY:SECURE_COM_B_calc.INPA",16777215,0,"PPS:SYSE:2:30BSY:SECURE_COM_B_calc.INPA") #! Link("PPS:SYSE:2:30BSY:SECURE_COM_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb107.VAL") #! Field("PPS:SYSE:2:30BSY:SECURE_COM_B_calc.INPB",16777215,1,"PPS:SYSE:2:30BSY:SECURE_COM_B_calc.INPB") #! Field("PPS:SYSE:2:30BSY:SECURE_COM_B_calc.OUT",16777215,1,"PPS:SYSE:2:30BSY:SECURE_COM_B_calc.OUT") #! Link("PPS:SYSE:2:30BSY:SECURE_COM_B_calc.OUT","PPS:SYSE:2:30BSY:SECURE_COM_B.VAL") #! Record("PPS:SYSE:2:30BSY:SECURE_COM_B",500,20,0,0,"PPS:SYSE:2:30BSY:SECURE_COM_B") #! Field("PPS:SYSE:2:30BSY:SECURE_COM_B.VAL",16777215,1,"PPS:SYSE:2:30BSY:SECURE_COM_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi106") { field(DESC, "Port 30BSY_RDB bit 106") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 106, 1, 1)") field(ZNAM, "Not_Secure") field(ONAM, "Secure") field(FLNK, "PPS:SYSE:3:30BSY:SECURE_COM_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi106Valid") { field(INPA, "PLC:BSY0:PP10:Bi106.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:3:30BSY:SECURE_COM_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:3:30BSY:SECURE_COM_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi106 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi106Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:3:30BSY:SECURE_COM_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:3:30BSY:SECURE_COM_B") { field(DESC, "30-BSY Sec. Comp. (other ch.)") field(ZNAM, "Not_Secure") field(ONAM, "Secure") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb106",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb106") #! Field("PLC:BSY0:PP10:30BSY_RDBb106.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb106.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb106.FLNK","PPS:SYSE:3:30BSY:SECURE_COM_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb106.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb106.VAL") #! Record("PPS:SYSE:3:30BSY:SECURE_COM_B_calc",260,18,0,1,"PPS:SYSE:3:30BSY:SECURE_COM_B_calc") #! Field("PPS:SYSE:3:30BSY:SECURE_COM_B_calc.INPA",16777215,0,"PPS:SYSE:3:30BSY:SECURE_COM_B_calc.INPA") #! Link("PPS:SYSE:3:30BSY:SECURE_COM_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb106.VAL") #! Field("PPS:SYSE:3:30BSY:SECURE_COM_B_calc.INPB",16777215,1,"PPS:SYSE:3:30BSY:SECURE_COM_B_calc.INPB") #! Field("PPS:SYSE:3:30BSY:SECURE_COM_B_calc.OUT",16777215,1,"PPS:SYSE:3:30BSY:SECURE_COM_B_calc.OUT") #! Link("PPS:SYSE:3:30BSY:SECURE_COM_B_calc.OUT","PPS:SYSE:3:30BSY:SECURE_COM_B.VAL") #! Record("PPS:SYSE:3:30BSY:SECURE_COM_B",500,20,0,0,"PPS:SYSE:3:30BSY:SECURE_COM_B") #! Field("PPS:SYSE:3:30BSY:SECURE_COM_B.VAL",16777215,1,"PPS:SYSE:3:30BSY:SECURE_COM_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi105") { field(DESC, "Port 30BSY_RDB bit 105") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 105, 1, 1)") field(ZNAM, "Fault") field(ONAM, "Ok") field(FLNK, "PPS:SYSE:1:30BSY:HWALRMWARN_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi105Valid") { field(INPA, "PLC:BSY0:PP10:Bi105.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:HWALRMWARN_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:HWALRMWARN_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi105 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi105Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:HWALRMWARN_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:HWALRMWARN_B") { field(DESC, "HW_Alarm_Warning_B") field(ZNAM, "Fault") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb105",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb105") #! Field("PLC:BSY0:PP10:30BSY_RDBb105.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb105.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb105.FLNK","PPS:SYSE:1:30BSY:HWALRMWARN_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb105.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb105.VAL") #! Record("PPS:SYSE:1:30BSY:HWALRMWARN_B_calc",260,18,0,1,"PPS:SYSE:1:30BSY:HWALRMWARN_B_calc") #! Field("PPS:SYSE:1:30BSY:HWALRMWARN_B_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:HWALRMWARN_B_calc.INPA") #! Link("PPS:SYSE:1:30BSY:HWALRMWARN_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb105.VAL") #! Field("PPS:SYSE:1:30BSY:HWALRMWARN_B_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:HWALRMWARN_B_calc.INPB") #! Field("PPS:SYSE:1:30BSY:HWALRMWARN_B_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:HWALRMWARN_B_calc.OUT") #! Link("PPS:SYSE:1:30BSY:HWALRMWARN_B_calc.OUT","PPS:SYSE:1:30BSY:HWALRMWARN_B.VAL") #! Record("PPS:SYSE:1:30BSY:HWALRMWARN_B",500,20,0,0,"PPS:SYSE:1:30BSY:HWALRMWARN_B") #! Field("PPS:SYSE:1:30BSY:HWALRMWARN_B.VAL",16777215,1,"PPS:SYSE:1:30BSY:HWALRMWARN_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi104") { field(DESC, "Port 30BSY_RDB bit 104") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 104, 1, 1)") field(ZNAM, "Fault") field(ONAM, "Ok") field(FLNK, "PPS:SYSE:1:30BSY:HRTBT_OUTP_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi104Valid") { field(INPA, "PLC:BSY0:PP10:Bi104.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:HRTBT_OUTP_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:HRTBT_OUTP_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi104 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi104Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:HRTBT_OUTP_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:HRTBT_OUTP_B") { field(DESC, "PLC_Heartbeat_Output_B") field(ZNAM, "Fault") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb104",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb104") #! Field("PLC:BSY0:PP10:30BSY_RDBb104.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb104.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb104.FLNK","PPS:SYSE:1:30BSY:HRTBT_OUTP_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb104.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb104.VAL") #! Record("PPS:SYSE:1:30BSY:HRTBT_OUTP_B_calc",260,18,0,1,"PPS:SYSE:1:30BSY:HRTBT_OUTP_B_calc") #! Field("PPS:SYSE:1:30BSY:HRTBT_OUTP_B_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:HRTBT_OUTP_B_calc.INPA") #! Link("PPS:SYSE:1:30BSY:HRTBT_OUTP_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb104.VAL") #! Field("PPS:SYSE:1:30BSY:HRTBT_OUTP_B_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:HRTBT_OUTP_B_calc.INPB") #! Field("PPS:SYSE:1:30BSY:HRTBT_OUTP_B_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:HRTBT_OUTP_B_calc.OUT") #! Link("PPS:SYSE:1:30BSY:HRTBT_OUTP_B_calc.OUT","PPS:SYSE:1:30BSY:HRTBT_OUTP_B.VAL") #! Record("PPS:SYSE:1:30BSY:HRTBT_OUTP_B",500,20,0,0,"PPS:SYSE:1:30BSY:HRTBT_OUTP_B") #! Field("PPS:SYSE:1:30BSY:HRTBT_OUTP_B.VAL",16777215,1,"PPS:SYSE:1:30BSY:HRTBT_OUTP_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi119") { field(DESC, "Port 30BSY_RDB bit 119") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 119, 1, 1)") field(ZNAM, "Fault") field(ONAM, "Ok") field(FLNK, "PPS:SYSE:1:30BSY:BCS_FAULT_TRG_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi119Valid") { field(INPA, "PLC:BSY0:PP10:Bi119.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:BCS_FAULT_TRG_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:BCS_FAULT_TRG_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi119 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi119Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:BCS_FAULT_TRG_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:BCS_FAULT_TRG_B") { field(DESC, "BCS_Fault_Trigger_Output_B") field(ZNAM, "Fault") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb119",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb119") #! Field("PLC:BSY0:PP10:30BSY_RDBb119.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb119.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb119.FLNK","PPS:SYSE:1:30BSY:BCS_FAULT_TRG_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb119.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb119.VAL") #! Record("PPS:SYSE:1:30BSY:BCS_FAULT_TRG_B_calc",260,18,0,1,"PPS:SYSE:1:30BSY:BCS_FAULT_TRG_B_calc") #! Field("PPS:SYSE:1:30BSY:BCS_FAULT_TRG_B_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:BCS_FAULT_TRG_B_calc.INPA") #! Link("PPS:SYSE:1:30BSY:BCS_FAULT_TRG_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb119.VAL") #! Field("PPS:SYSE:1:30BSY:BCS_FAULT_TRG_B_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:BCS_FAULT_TRG_B_calc.INPB") #! Field("PPS:SYSE:1:30BSY:BCS_FAULT_TRG_B_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:BCS_FAULT_TRG_B_calc.OUT") #! Link("PPS:SYSE:1:30BSY:BCS_FAULT_TRG_B_calc.OUT","PPS:SYSE:1:30BSY:BCS_FAULT_TRG_B.VAL") #! Record("PPS:SYSE:1:30BSY:BCS_FAULT_TRG_B",500,20,0,0,"PPS:SYSE:1:30BSY:BCS_FAULT_TRG_B") #! Field("PPS:SYSE:1:30BSY:BCS_FAULT_TRG_B.VAL",16777215,1,"PPS:SYSE:1:30BSY:BCS_FAULT_TRG_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi117") { field(DESC, "Port 30BSY_RDB bit 117") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 117, 1, 1)") field(ZNAM, "Not_Complete") field(ONAM, "Complete") field(FLNK, "PPS:SYSE:1:30BSY:SECURE_COM_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi117Valid") { field(INPA, "PLC:BSY0:PP10:Bi117.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:SECURE_COM_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:SECURE_COM_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi117 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi117Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:SECURE_COM_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:SECURE_COM_B") { field(DESC, "30BSY_Secure_Complete_B") field(ZNAM, "Not_Complete") field(ONAM, "Complete") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb117",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb117") #! Field("PLC:BSY0:PP10:30BSY_RDBb117.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb117.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb117.FLNK","PPS:SYSE:1:30BSY:SECURE_COM_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb117.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb117.VAL") #! Record("PPS:SYSE:1:30BSY:SECURE_COM_B_calc",260,18,0,1,"PPS:SYSE:1:30BSY:SECURE_COM_B_calc") #! Field("PPS:SYSE:1:30BSY:SECURE_COM_B_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:SECURE_COM_B_calc.INPA") #! Link("PPS:SYSE:1:30BSY:SECURE_COM_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb117.VAL") #! Field("PPS:SYSE:1:30BSY:SECURE_COM_B_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:SECURE_COM_B_calc.INPB") #! Field("PPS:SYSE:1:30BSY:SECURE_COM_B_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:SECURE_COM_B_calc.OUT") #! Link("PPS:SYSE:1:30BSY:SECURE_COM_B_calc.OUT","PPS:SYSE:1:30BSY:SECURE_COM_B.VAL") #! Record("PPS:SYSE:1:30BSY:SECURE_COM_B",500,20,0,0,"PPS:SYSE:1:30BSY:SECURE_COM_B") #! Field("PPS:SYSE:1:30BSY:SECURE_COM_B.VAL",16777215,1,"PPS:SYSE:1:30BSY:SECURE_COM_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi116") { field(DESC, "Port 30BSY_RDB bit 116") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 116, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:SYSE:1:30BSY:SECURE_LTH_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi116Valid") { field(INPA, "PLC:BSY0:PP10:Bi116.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:SECURE_LTH_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:SECURE_LTH_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi116 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi116Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:SECURE_LTH_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:SECURE_LTH_B") { field(DESC, "30BSY_Secure_Latched_B") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb116",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb116") #! Field("PLC:BSY0:PP10:30BSY_RDBb116.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb116.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb116.FLNK","PPS:SYSE:1:30BSY:SECURE_LTH_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb116.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb116.VAL") #! Record("PPS:SYSE:1:30BSY:SECURE_LTH_B_calc",260,18,0,1,"PPS:SYSE:1:30BSY:SECURE_LTH_B_calc") #! Field("PPS:SYSE:1:30BSY:SECURE_LTH_B_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:SECURE_LTH_B_calc.INPA") #! Link("PPS:SYSE:1:30BSY:SECURE_LTH_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb116.VAL") #! Field("PPS:SYSE:1:30BSY:SECURE_LTH_B_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:SECURE_LTH_B_calc.INPB") #! Field("PPS:SYSE:1:30BSY:SECURE_LTH_B_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:SECURE_LTH_B_calc.OUT") #! Link("PPS:SYSE:1:30BSY:SECURE_LTH_B_calc.OUT","PPS:SYSE:1:30BSY:SECURE_LTH_B.VAL") #! Record("PPS:SYSE:1:30BSY:SECURE_LTH_B",500,20,0,0,"PPS:SYSE:1:30BSY:SECURE_LTH_B") #! Field("PPS:SYSE:1:30BSY:SECURE_LTH_B.VAL",16777215,1,"PPS:SYSE:1:30BSY:SECURE_LTH_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi115") { field(DESC, "Port 30BSY_RDB bit 115") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 115, 1, 1)") field(ZNAM, "Not Ok") field(ONAM, "Ok") field(FLNK, "PPS:LTU0:1:ACCPERMIT_OUT_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi115Valid") { field(INPA, "PLC:BSY0:PP10:Bi115.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:LTU0:1:ACCPERMIT_OUT_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:LTU0:1:ACCPERMIT_OUT_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi115 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi115Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:LTU0:1:ACCPERMIT_OUT_B PP MS") field(ASG, "Internal") } record(bi, "PPS:LTU0:1:ACCPERMIT_OUT_B") { field(DESC, "BTH_UND_Access_Permit_Out_B") field(ZNAM, "Not Ok") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb115",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb115") #! Field("PLC:BSY0:PP10:30BSY_RDBb115.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb115.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb115.FLNK","PPS:LTU0:1:ACCPERMIT_OUT_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb115.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb115.VAL") #! Record("PPS:LTU0:1:ACCPERMIT_OUT_B_calc",260,18,0,1,"PPS:LTU0:1:ACCPERMIT_OUT_B_calc") #! Field("PPS:LTU0:1:ACCPERMIT_OUT_B_calc.INPA",16777215,0,"PPS:LTU0:1:ACCPERMIT_OUT_B_calc.INPA") #! Link("PPS:LTU0:1:ACCPERMIT_OUT_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb115.VAL") #! Field("PPS:LTU0:1:ACCPERMIT_OUT_B_calc.INPB",16777215,1,"PPS:LTU0:1:ACCPERMIT_OUT_B_calc.INPB") #! Field("PPS:LTU0:1:ACCPERMIT_OUT_B_calc.OUT",16777215,1,"PPS:LTU0:1:ACCPERMIT_OUT_B_calc.OUT") #! Link("PPS:LTU0:1:ACCPERMIT_OUT_B_calc.OUT","PPS:LTU0:1:ACCPERMIT_OUT_B.VAL") #! Record("PPS:LTU0:1:ACCPERMIT_OUT_B",500,20,0,0,"PPS:LTU0:1:ACCPERMIT_OUT_B") #! Field("PPS:LTU0:1:ACCPERMIT_OUT_B.VAL",16777215,1,"PPS:LTU0:1:ACCPERMIT_OUT_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi114") { field(DESC, "Port 30BSY_RDB bit 114") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 114, 1, 1)") field(ZNAM, "Not Ok") field(ONAM, "Ok") field(FLNK, "PPS:LTU0:2:ACCPERMIT_OUT_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi114Valid") { field(INPA, "PLC:BSY0:PP10:Bi114.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:LTU0:2:ACCPERMIT_OUT_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:LTU0:2:ACCPERMIT_OUT_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi114 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi114Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:LTU0:2:ACCPERMIT_OUT_B PP MS") field(ASG, "Internal") } record(bi, "PPS:LTU0:2:ACCPERMIT_OUT_B") { field(DESC, "RSY_Access_Permit_Out_B") field(ZNAM, "Not Ok") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb114",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb114") #! Field("PLC:BSY0:PP10:30BSY_RDBb114.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb114.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb114.FLNK","PPS:LTU0:2:ACCPERMIT_OUT_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb114.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb114.VAL") #! Record("PPS:LTU0:2:ACCPERMIT_OUT_B_calc",260,18,0,1,"PPS:LTU0:2:ACCPERMIT_OUT_B_calc") #! Field("PPS:LTU0:2:ACCPERMIT_OUT_B_calc.INPA",16777215,0,"PPS:LTU0:2:ACCPERMIT_OUT_B_calc.INPA") #! Link("PPS:LTU0:2:ACCPERMIT_OUT_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb114.VAL") #! Field("PPS:LTU0:2:ACCPERMIT_OUT_B_calc.INPB",16777215,1,"PPS:LTU0:2:ACCPERMIT_OUT_B_calc.INPB") #! Field("PPS:LTU0:2:ACCPERMIT_OUT_B_calc.OUT",16777215,1,"PPS:LTU0:2:ACCPERMIT_OUT_B_calc.OUT") #! Link("PPS:LTU0:2:ACCPERMIT_OUT_B_calc.OUT","PPS:LTU0:2:ACCPERMIT_OUT_B.VAL") #! Record("PPS:LTU0:2:ACCPERMIT_OUT_B",500,20,0,0,"PPS:LTU0:2:ACCPERMIT_OUT_B") #! Field("PPS:LTU0:2:ACCPERMIT_OUT_B.VAL",16777215,1,"PPS:LTU0:2:ACCPERMIT_OUT_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi113") { field(DESC, "Port 30BSY_RDB bit 113") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 113, 1, 1)") field(ZNAM, "Not_Escalated") field(ONAM, "Escalated") field(FLNK, "PPS:SYSE:1:BSOIC_ESC_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi113Valid") { field(INPA, "PLC:BSY0:PP10:Bi113.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:BSOIC_ESC_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:BSOIC_ESC_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi113 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi113Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:BSOIC_ESC_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:BSOIC_ESC_B") { field(DESC, "BSOIC escalation B") field(ZNAM, "Not_Escalated") field(ONAM, "Escalated") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb113",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb113") #! Field("PLC:BSY0:PP10:30BSY_RDBb113.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb113.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb113.FLNK","PPS:SYSE:1:BSOIC_ESC_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb113.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb113.VAL") #! Record("PPS:SYSE:1:BSOIC_ESC_B_calc",260,18,0,1,"PPS:SYSE:1:BSOIC_ESC_B_calc") #! Field("PPS:SYSE:1:BSOIC_ESC_B_calc.INPA",16777215,0,"PPS:SYSE:1:BSOIC_ESC_B_calc.INPA") #! Link("PPS:SYSE:1:BSOIC_ESC_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb113.VAL") #! Field("PPS:SYSE:1:BSOIC_ESC_B_calc.INPB",16777215,1,"PPS:SYSE:1:BSOIC_ESC_B_calc.INPB") #! Field("PPS:SYSE:1:BSOIC_ESC_B_calc.OUT",16777215,1,"PPS:SYSE:1:BSOIC_ESC_B_calc.OUT") #! Link("PPS:SYSE:1:BSOIC_ESC_B_calc.OUT","PPS:SYSE:1:BSOIC_ESC_B.VAL") #! Record("PPS:SYSE:1:BSOIC_ESC_B",500,20,0,0,"PPS:SYSE:1:BSOIC_ESC_B") #! Field("PPS:SYSE:1:BSOIC_ESC_B.VAL",16777215,1,"PPS:SYSE:1:BSOIC_ESC_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi112") { field(DESC, "Port 30BSY_RDB bit 112") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 112, 1, 1)") field(ZNAM, "Not_Complete") field(ONAM, "Complete") field(FLNK, "PPS:SYSE:1:GLOBAL:BEAMCOND_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi112Valid") { field(INPA, "PLC:BSY0:PP10:Bi112.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:GLOBAL:BEAMCOND_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:GLOBAL:BEAMCOND_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi112 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi112Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:GLOBAL:BEAMCOND_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:GLOBAL:BEAMCOND_B") { field(DESC, "Global_Beam_Conditions_B") field(ZNAM, "Not_Complete") field(ONAM, "Complete") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb112",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb112") #! Field("PLC:BSY0:PP10:30BSY_RDBb112.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb112.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb112.FLNK","PPS:SYSE:1:GLOBAL:BEAMCOND_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb112.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb112.VAL") #! Record("PPS:SYSE:1:GLOBAL:BEAMCOND_B_calc",260,18,0,1,"PPS:SYSE:1:GLOBAL:BEAMCOND_B_calc") #! Field("PPS:SYSE:1:GLOBAL:BEAMCOND_B_calc.INPA",16777215,0,"PPS:SYSE:1:GLOBAL:BEAMCOND_B_calc.INPA") #! Link("PPS:SYSE:1:GLOBAL:BEAMCOND_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb112.VAL") #! Field("PPS:SYSE:1:GLOBAL:BEAMCOND_B_calc.INPB",16777215,1,"PPS:SYSE:1:GLOBAL:BEAMCOND_B_calc.INPB") #! Field("PPS:SYSE:1:GLOBAL:BEAMCOND_B_calc.OUT",16777215,1,"PPS:SYSE:1:GLOBAL:BEAMCOND_B_calc.OUT") #! Link("PPS:SYSE:1:GLOBAL:BEAMCOND_B_calc.OUT","PPS:SYSE:1:GLOBAL:BEAMCOND_B.VAL") #! Record("PPS:SYSE:1:GLOBAL:BEAMCOND_B",500,20,0,0,"PPS:SYSE:1:GLOBAL:BEAMCOND_B") #! Field("PPS:SYSE:1:GLOBAL:BEAMCOND_B.VAL",16777215,1,"PPS:SYSE:1:GLOBAL:BEAMCOND_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi127") { field(DESC, "Port 30BSY_RDB bit 127") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 127, 1, 1)") field(ZNAM, "Not_Complete") field(ONAM, "Complete") field(FLNK, "PPS:SYSE:1:CU:BEAMCOND_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi127Valid") { field(INPA, "PLC:BSY0:PP10:Bi127.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:CU:BEAMCOND_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:CU:BEAMCOND_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi127 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi127Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:CU:BEAMCOND_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:CU:BEAMCOND_B") { field(DESC, "Cu_Beam_Conditions_B") field(ZNAM, "Not_Complete") field(ONAM, "Complete") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb127",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb127") #! Field("PLC:BSY0:PP10:30BSY_RDBb127.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb127.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb127.FLNK","PPS:SYSE:1:CU:BEAMCOND_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb127.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb127.VAL") #! Record("PPS:SYSE:1:CU:BEAMCOND_B_calc",260,18,0,1,"PPS:SYSE:1:CU:BEAMCOND_B_calc") #! Field("PPS:SYSE:1:CU:BEAMCOND_B_calc.INPA",16777215,0,"PPS:SYSE:1:CU:BEAMCOND_B_calc.INPA") #! Link("PPS:SYSE:1:CU:BEAMCOND_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb127.VAL") #! Field("PPS:SYSE:1:CU:BEAMCOND_B_calc.INPB",16777215,1,"PPS:SYSE:1:CU:BEAMCOND_B_calc.INPB") #! Field("PPS:SYSE:1:CU:BEAMCOND_B_calc.OUT",16777215,1,"PPS:SYSE:1:CU:BEAMCOND_B_calc.OUT") #! Link("PPS:SYSE:1:CU:BEAMCOND_B_calc.OUT","PPS:SYSE:1:CU:BEAMCOND_B.VAL") #! Record("PPS:SYSE:1:CU:BEAMCOND_B",500,20,0,0,"PPS:SYSE:1:CU:BEAMCOND_B") #! Field("PPS:SYSE:1:CU:BEAMCOND_B.VAL",16777215,1,"PPS:SYSE:1:CU:BEAMCOND_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi126") { field(DESC, "Port 30BSY_RDB bit 126") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 126, 1, 1)") field(ZNAM, "Not_Complete") field(ONAM, "Complete") field(FLNK, "PPS:SYSE:1:SC:BEAMCOND_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi126Valid") { field(INPA, "PLC:BSY0:PP10:Bi126.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:SC:BEAMCOND_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:SC:BEAMCOND_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi126 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi126Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:SC:BEAMCOND_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:SC:BEAMCOND_B") { field(DESC, "SC_Beam_Conditions_B") field(ZNAM, "Not_Complete") field(ONAM, "Complete") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb126",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb126") #! Field("PLC:BSY0:PP10:30BSY_RDBb126.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb126.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb126.FLNK","PPS:SYSE:1:SC:BEAMCOND_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb126.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb126.VAL") #! Record("PPS:SYSE:1:SC:BEAMCOND_B_calc",260,18,0,1,"PPS:SYSE:1:SC:BEAMCOND_B_calc") #! Field("PPS:SYSE:1:SC:BEAMCOND_B_calc.INPA",16777215,0,"PPS:SYSE:1:SC:BEAMCOND_B_calc.INPA") #! Link("PPS:SYSE:1:SC:BEAMCOND_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb126.VAL") #! Field("PPS:SYSE:1:SC:BEAMCOND_B_calc.INPB",16777215,1,"PPS:SYSE:1:SC:BEAMCOND_B_calc.INPB") #! Field("PPS:SYSE:1:SC:BEAMCOND_B_calc.OUT",16777215,1,"PPS:SYSE:1:SC:BEAMCOND_B_calc.OUT") #! Link("PPS:SYSE:1:SC:BEAMCOND_B_calc.OUT","PPS:SYSE:1:SC:BEAMCOND_B.VAL") #! Record("PPS:SYSE:1:SC:BEAMCOND_B",500,20,0,0,"PPS:SYSE:1:SC:BEAMCOND_B") #! Field("PPS:SYSE:1:SC:BEAMCOND_B.VAL",16777215,1,"PPS:SYSE:1:SC:BEAMCOND_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi123") { field(DESC, "Port 30BSY_RDB bit 123") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 123, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:SYSE:1:BLM_INP_LTH_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi123Valid") { field(INPA, "PLC:BSY0:PP10:Bi123.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:BLM_INP_LTH_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:BLM_INP_LTH_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi123 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi123Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:BLM_INP_LTH_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:BLM_INP_LTH_B") { field(DESC, "BCS_BLM_Input_Lat_B") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb123",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb123") #! Field("PLC:BSY0:PP10:30BSY_RDBb123.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb123.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb123.FLNK","PPS:SYSE:1:BLM_INP_LTH_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb123.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb123.VAL") #! Record("PPS:SYSE:1:BLM_INP_LTH_B_calc",260,18,0,1,"PPS:SYSE:1:BLM_INP_LTH_B_calc") #! Field("PPS:SYSE:1:BLM_INP_LTH_B_calc.INPA",16777215,0,"PPS:SYSE:1:BLM_INP_LTH_B_calc.INPA") #! Link("PPS:SYSE:1:BLM_INP_LTH_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb123.VAL") #! Field("PPS:SYSE:1:BLM_INP_LTH_B_calc.INPB",16777215,1,"PPS:SYSE:1:BLM_INP_LTH_B_calc.INPB") #! Field("PPS:SYSE:1:BLM_INP_LTH_B_calc.OUT",16777215,1,"PPS:SYSE:1:BLM_INP_LTH_B_calc.OUT") #! Link("PPS:SYSE:1:BLM_INP_LTH_B_calc.OUT","PPS:SYSE:1:BLM_INP_LTH_B.VAL") #! Record("PPS:SYSE:1:BLM_INP_LTH_B",500,20,0,0,"PPS:SYSE:1:BLM_INP_LTH_B") #! Field("PPS:SYSE:1:BLM_INP_LTH_B.VAL",16777215,1,"PPS:SYSE:1:BLM_INP_LTH_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi121") { field(DESC, "Port 30BSY_RDB bit 121") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 121, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:LI30:1:SECURE_INP_LTH_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi121Valid") { field(INPA, "PLC:BSY0:PP10:Bi121.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:LI30:1:SECURE_INP_LTH_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:LI30:1:SECURE_INP_LTH_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi121 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi121Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:LI30:1:SECURE_INP_LTH_B PP MS") field(ASG, "Internal") } record(bi, "PPS:LI30:1:SECURE_INP_LTH_B") { field(DESC, "S30_Secure_Input_B") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb121",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb121") #! Field("PLC:BSY0:PP10:30BSY_RDBb121.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb121.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb121.FLNK","PPS:LI30:1:SECURE_INP_LTH_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb121.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb121.VAL") #! Record("PPS:LI30:1:SECURE_INP_LTH_B_calc",260,18,0,1,"PPS:LI30:1:SECURE_INP_LTH_B_calc") #! Field("PPS:LI30:1:SECURE_INP_LTH_B_calc.INPA",16777215,0,"PPS:LI30:1:SECURE_INP_LTH_B_calc.INPA") #! Link("PPS:LI30:1:SECURE_INP_LTH_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb121.VAL") #! Field("PPS:LI30:1:SECURE_INP_LTH_B_calc.INPB",16777215,1,"PPS:LI30:1:SECURE_INP_LTH_B_calc.INPB") #! Field("PPS:LI30:1:SECURE_INP_LTH_B_calc.OUT",16777215,1,"PPS:LI30:1:SECURE_INP_LTH_B_calc.OUT") #! Link("PPS:LI30:1:SECURE_INP_LTH_B_calc.OUT","PPS:LI30:1:SECURE_INP_LTH_B.VAL") #! Record("PPS:LI30:1:SECURE_INP_LTH_B",500,20,0,0,"PPS:LI30:1:SECURE_INP_LTH_B") #! Field("PPS:LI30:1:SECURE_INP_LTH_B.VAL",16777215,1,"PPS:LI30:1:SECURE_INP_LTH_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi120") { field(DESC, "Port 30BSY_RDB bit 120") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 120, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:BSY0:1:SECURE_INP_LTH_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi120Valid") { field(INPA, "PLC:BSY0:PP10:Bi120.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:BSY0:1:SECURE_INP_LTH_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:BSY0:1:SECURE_INP_LTH_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi120 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi120Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:BSY0:1:SECURE_INP_LTH_B PP MS") field(ASG, "Internal") } record(bi, "PPS:BSY0:1:SECURE_INP_LTH_B") { field(DESC, "BSY_Secure_Input_B") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb120",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb120") #! Field("PLC:BSY0:PP10:30BSY_RDBb120.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb120.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb120.FLNK","PPS:BSY0:1:SECURE_INP_LTH_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb120.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb120.VAL") #! Record("PPS:BSY0:1:SECURE_INP_LTH_B_calc",260,18,0,1,"PPS:BSY0:1:SECURE_INP_LTH_B_calc") #! Field("PPS:BSY0:1:SECURE_INP_LTH_B_calc.INPA",16777215,0,"PPS:BSY0:1:SECURE_INP_LTH_B_calc.INPA") #! Link("PPS:BSY0:1:SECURE_INP_LTH_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb120.VAL") #! Field("PPS:BSY0:1:SECURE_INP_LTH_B_calc.INPB",16777215,1,"PPS:BSY0:1:SECURE_INP_LTH_B_calc.INPB") #! Field("PPS:BSY0:1:SECURE_INP_LTH_B_calc.OUT",16777215,1,"PPS:BSY0:1:SECURE_INP_LTH_B_calc.OUT") #! Link("PPS:BSY0:1:SECURE_INP_LTH_B_calc.OUT","PPS:BSY0:1:SECURE_INP_LTH_B.VAL") #! Record("PPS:BSY0:1:SECURE_INP_LTH_B",500,20,0,0,"PPS:BSY0:1:SECURE_INP_LTH_B") #! Field("PPS:BSY0:1:SECURE_INP_LTH_B.VAL",16777215,1,"PPS:BSY0:1:SECURE_INP_LTH_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi135") { field(DESC, "Port 30BSY_RDB bit 135") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 135, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:ESA0:1:RADREADY_INP_LTH_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi135Valid") { field(INPA, "PLC:BSY0:PP10:Bi135.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:ESA0:1:RADREADY_INP_LTH_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:ESA0:1:RADREADY_INP_LTH_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi135 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi135Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:ESA0:1:RADREADY_INP_LTH_B PP MS") field(ASG, "Internal") } record(bi, "PPS:ESA0:1:RADREADY_INP_LTH_B") { field(DESC, "ESA_Rad_Ready_Input_B") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb135",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb135") #! Field("PLC:BSY0:PP10:30BSY_RDBb135.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb135.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb135.FLNK","PPS:ESA0:1:RADREADY_INP_LTH_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb135.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb135.VAL") #! Record("PPS:ESA0:1:RADREADY_INP_LTH_B_calc",260,18,0,1,"PPS:ESA0:1:RADREADY_INP_LTH_B_calc") #! Field("PPS:ESA0:1:RADREADY_INP_LTH_B_calc.INPA",16777215,0,"PPS:ESA0:1:RADREADY_INP_LTH_B_calc.INPA") #! Link("PPS:ESA0:1:RADREADY_INP_LTH_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb135.VAL") #! Field("PPS:ESA0:1:RADREADY_INP_LTH_B_calc.INPB",16777215,1,"PPS:ESA0:1:RADREADY_INP_LTH_B_calc.INPB") #! Field("PPS:ESA0:1:RADREADY_INP_LTH_B_calc.OUT",16777215,1,"PPS:ESA0:1:RADREADY_INP_LTH_B_calc.OUT") #! Link("PPS:ESA0:1:RADREADY_INP_LTH_B_calc.OUT","PPS:ESA0:1:RADREADY_INP_LTH_B.VAL") #! Record("PPS:ESA0:1:RADREADY_INP_LTH_B",500,20,0,0,"PPS:ESA0:1:RADREADY_INP_LTH_B") #! Field("PPS:ESA0:1:RADREADY_INP_LTH_B.VAL",16777215,1,"PPS:ESA0:1:RADREADY_INP_LTH_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi134") { field(DESC, "Port 30BSY_RDB bit 134") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 134, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "BTM:BSY0:1:SUM_OK_LTH_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi134Valid") { field(INPA, "PLC:BSY0:PP10:Bi134.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "BTM:BSY0:1:SUM_OK_LTH_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "BTM:BSY0:1:SUM_OK_LTH_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi134 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi134Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "BTM:BSY0:1:SUM_OK_LTH_B PP MS") field(ASG, "Internal") } record(bi, "BTM:BSY0:1:SUM_OK_LTH_B") { field(DESC, "BTM_Sum_OK_Input_B") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb134",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb134") #! Field("PLC:BSY0:PP10:30BSY_RDBb134.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb134.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb134.FLNK","BTM:BSY0:1:SUM_OK_LTH_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb134.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb134.VAL") #! Record("BTM:BSY0:1:SUM_OK_LTH_B_calc",260,18,0,1,"BTM:BSY0:1:SUM_OK_LTH_B_calc") #! Field("BTM:BSY0:1:SUM_OK_LTH_B_calc.INPA",16777215,0,"BTM:BSY0:1:SUM_OK_LTH_B_calc.INPA") #! Link("BTM:BSY0:1:SUM_OK_LTH_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb134.VAL") #! Field("BTM:BSY0:1:SUM_OK_LTH_B_calc.INPB",16777215,1,"BTM:BSY0:1:SUM_OK_LTH_B_calc.INPB") #! Field("BTM:BSY0:1:SUM_OK_LTH_B_calc.OUT",16777215,1,"BTM:BSY0:1:SUM_OK_LTH_B_calc.OUT") #! Link("BTM:BSY0:1:SUM_OK_LTH_B_calc.OUT","BTM:BSY0:1:SUM_OK_LTH_B.VAL") #! Record("BTM:BSY0:1:SUM_OK_LTH_B",500,20,0,0,"BTM:BSY0:1:SUM_OK_LTH_B") #! Field("BTM:BSY0:1:SUM_OK_LTH_B.VAL",16777215,1,"BTM:BSY0:1:SUM_OK_LTH_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi133") { field(DESC, "Port 30BSY_RDB bit 133") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 133, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "BSOC:SYSE:1:GROUPC_LTH_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi133Valid") { field(INPA, "PLC:BSY0:PP10:Bi133.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "BSOC:SYSE:1:GROUPC_LTH_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "BSOC:SYSE:1:GROUPC_LTH_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi133 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi133Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "BSOC:SYSE:1:GROUPC_LTH_B PP MS") field(ASG, "Internal") } record(bi, "BSOC:SYSE:1:GROUPC_LTH_B") { field(DESC, "BSOIC_GrpC_OK_Input_B") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb133",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb133") #! Field("PLC:BSY0:PP10:30BSY_RDBb133.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb133.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb133.FLNK","BSOC:SYSE:1:GROUPC_LTH_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb133.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb133.VAL") #! Record("BSOC:SYSE:1:GROUPC_LTH_B_calc",260,18,0,1,"BSOC:SYSE:1:GROUPC_LTH_B_calc") #! Field("BSOC:SYSE:1:GROUPC_LTH_B_calc.INPA",16777215,0,"BSOC:SYSE:1:GROUPC_LTH_B_calc.INPA") #! Link("BSOC:SYSE:1:GROUPC_LTH_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb133.VAL") #! Field("BSOC:SYSE:1:GROUPC_LTH_B_calc.INPB",16777215,1,"BSOC:SYSE:1:GROUPC_LTH_B_calc.INPB") #! Field("BSOC:SYSE:1:GROUPC_LTH_B_calc.OUT",16777215,1,"BSOC:SYSE:1:GROUPC_LTH_B_calc.OUT") #! Link("BSOC:SYSE:1:GROUPC_LTH_B_calc.OUT","BSOC:SYSE:1:GROUPC_LTH_B.VAL") #! Record("BSOC:SYSE:1:GROUPC_LTH_B",500,20,0,0,"BSOC:SYSE:1:GROUPC_LTH_B") #! Field("BSOC:SYSE:1:GROUPC_LTH_B.VAL",16777215,1,"BSOC:SYSE:1:GROUPC_LTH_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi132") { field(DESC, "Port 30BSY_RDB bit 132") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 132, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:UND0:1:SECURE_INP_LTH_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi132Valid") { field(INPA, "PLC:BSY0:PP10:Bi132.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:UND0:1:SECURE_INP_LTH_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:UND0:1:SECURE_INP_LTH_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi132 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi132Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:UND0:1:SECURE_INP_LTH_B PP MS") field(ASG, "Internal") } record(bi, "PPS:UND0:1:SECURE_INP_LTH_B") { field(DESC, "LCLS_Secure_Input_B") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb132",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb132") #! Field("PLC:BSY0:PP10:30BSY_RDBb132.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb132.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb132.FLNK","PPS:UND0:1:SECURE_INP_LTH_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb132.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb132.VAL") #! Record("PPS:UND0:1:SECURE_INP_LTH_B_calc",260,18,0,1,"PPS:UND0:1:SECURE_INP_LTH_B_calc") #! Field("PPS:UND0:1:SECURE_INP_LTH_B_calc.INPA",16777215,0,"PPS:UND0:1:SECURE_INP_LTH_B_calc.INPA") #! Link("PPS:UND0:1:SECURE_INP_LTH_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb132.VAL") #! Field("PPS:UND0:1:SECURE_INP_LTH_B_calc.INPB",16777215,1,"PPS:UND0:1:SECURE_INP_LTH_B_calc.INPB") #! Field("PPS:UND0:1:SECURE_INP_LTH_B_calc.OUT",16777215,1,"PPS:UND0:1:SECURE_INP_LTH_B_calc.OUT") #! Link("PPS:UND0:1:SECURE_INP_LTH_B_calc.OUT","PPS:UND0:1:SECURE_INP_LTH_B.VAL") #! Record("PPS:UND0:1:SECURE_INP_LTH_B",500,20,0,0,"PPS:UND0:1:SECURE_INP_LTH_B") #! Field("PPS:UND0:1:SECURE_INP_LTH_B.VAL",16777215,1,"PPS:UND0:1:SECURE_INP_LTH_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi131") { field(DESC, "Port 30BSY_RDB bit 131") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 131, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi131Valid") { field(INPA, "PLC:BSY0:PP10:Bi131.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi131 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi131Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_B") { field(DESC, "Local_Beam_Enable_Keysw_B") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb131",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb131") #! Field("PLC:BSY0:PP10:30BSY_RDBb131.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb131.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb131.FLNK","PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb131.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb131.VAL") #! Record("PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_B_calc",260,18,0,1,"PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_B_calc") #! Field("PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_B_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_B_calc.INPA") #! Link("PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb131.VAL") #! Field("PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_B_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_B_calc.INPB") #! Field("PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_B_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_B_calc.OUT") #! Link("PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_B_calc.OUT","PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_B.VAL") #! Record("PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_B",500,20,0,0,"PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_B") #! Field("PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_B.VAL",16777215,1,"PPS:SYSE:1:30BSY:LOCAL_ENABLE_LTH_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi130") { field(DESC, "Port 30BSY_RDB bit 130") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 130, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:SYSE:1:BSOIC_ESC_LTH_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi130Valid") { field(INPA, "PLC:BSY0:PP10:Bi130.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:BSOIC_ESC_LTH_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:BSOIC_ESC_LTH_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi130 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi130Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:BSOIC_ESC_LTH_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:BSOIC_ESC_LTH_B") { field(DESC, "BSOIC escalation Lat B") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb130",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb130") #! Field("PLC:BSY0:PP10:30BSY_RDBb130.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb130.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb130.FLNK","PPS:SYSE:1:BSOIC_ESC_LTH_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb130.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb130.VAL") #! Record("PPS:SYSE:1:BSOIC_ESC_LTH_B_calc",260,18,0,1,"PPS:SYSE:1:BSOIC_ESC_LTH_B_calc") #! Field("PPS:SYSE:1:BSOIC_ESC_LTH_B_calc.INPA",16777215,0,"PPS:SYSE:1:BSOIC_ESC_LTH_B_calc.INPA") #! Link("PPS:SYSE:1:BSOIC_ESC_LTH_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb130.VAL") #! Field("PPS:SYSE:1:BSOIC_ESC_LTH_B_calc.INPB",16777215,1,"PPS:SYSE:1:BSOIC_ESC_LTH_B_calc.INPB") #! Field("PPS:SYSE:1:BSOIC_ESC_LTH_B_calc.OUT",16777215,1,"PPS:SYSE:1:BSOIC_ESC_LTH_B_calc.OUT") #! Link("PPS:SYSE:1:BSOIC_ESC_LTH_B_calc.OUT","PPS:SYSE:1:BSOIC_ESC_LTH_B.VAL") #! Record("PPS:SYSE:1:BSOIC_ESC_LTH_B",500,20,0,0,"PPS:SYSE:1:BSOIC_ESC_LTH_B") #! Field("PPS:SYSE:1:BSOIC_ESC_LTH_B.VAL",16777215,1,"PPS:SYSE:1:BSOIC_ESC_LTH_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi129") { field(DESC, "Port 30BSY_RDB bit 129") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 129, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:SYSE:1:BCS_FAULT_LTH_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi129Valid") { field(INPA, "PLC:BSY0:PP10:Bi129.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:BCS_FAULT_LTH_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:BCS_FAULT_LTH_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi129 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi129Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:BCS_FAULT_LTH_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:BCS_FAULT_LTH_B") { field(DESC, "BCS BEAM ON Fault B") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb129",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb129") #! Field("PLC:BSY0:PP10:30BSY_RDBb129.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb129.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb129.FLNK","PPS:SYSE:1:BCS_FAULT_LTH_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb129.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb129.VAL") #! Record("PPS:SYSE:1:BCS_FAULT_LTH_B_calc",260,18,0,1,"PPS:SYSE:1:BCS_FAULT_LTH_B_calc") #! Field("PPS:SYSE:1:BCS_FAULT_LTH_B_calc.INPA",16777215,0,"PPS:SYSE:1:BCS_FAULT_LTH_B_calc.INPA") #! Link("PPS:SYSE:1:BCS_FAULT_LTH_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb129.VAL") #! Field("PPS:SYSE:1:BCS_FAULT_LTH_B_calc.INPB",16777215,1,"PPS:SYSE:1:BCS_FAULT_LTH_B_calc.INPB") #! Field("PPS:SYSE:1:BCS_FAULT_LTH_B_calc.OUT",16777215,1,"PPS:SYSE:1:BCS_FAULT_LTH_B_calc.OUT") #! Link("PPS:SYSE:1:BCS_FAULT_LTH_B_calc.OUT","PPS:SYSE:1:BCS_FAULT_LTH_B.VAL") #! Record("PPS:SYSE:1:BCS_FAULT_LTH_B",500,20,0,0,"PPS:SYSE:1:BCS_FAULT_LTH_B") #! Field("PPS:SYSE:1:BCS_FAULT_LTH_B.VAL",16777215,1,"PPS:SYSE:1:BCS_FAULT_LTH_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi128") { field(DESC, "Port 30BSY_RDB bit 128") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 128, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi128Valid") { field(INPA, "PLC:BSY0:PP10:Bi128.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi128 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi128Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_B") { field(DESC, "ACR_Beam_Enable_Keysw_B") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb128",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb128") #! Field("PLC:BSY0:PP10:30BSY_RDBb128.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb128.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb128.FLNK","PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb128.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb128.VAL") #! Record("PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_B_calc",260,18,0,1,"PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_B_calc") #! Field("PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_B_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_B_calc.INPA") #! Link("PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb128.VAL") #! Field("PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_B_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_B_calc.INPB") #! Field("PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_B_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_B_calc.OUT") #! Link("PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_B_calc.OUT","PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_B.VAL") #! Record("PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_B",500,20,0,0,"PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_B") #! Field("PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_B.VAL",16777215,1,"PPS:SYSE:1:30BSY:ACR_ENABLE_LTH_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi143") { field(DESC, "Port 30BSY_RDB bit 143") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 143, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:SYSE:1:30BSY:INTLK_LTH_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi143Valid") { field(INPA, "PLC:BSY0:PP10:Bi143.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:INTLK_LTH_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:INTLK_LTH_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi143 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi143Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:INTLK_LTH_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:INTLK_LTH_B") { field(DESC, "30-BSY Glbl. intlk (spare) B") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb143",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb143") #! Field("PLC:BSY0:PP10:30BSY_RDBb143.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb143.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb143.FLNK","PPS:SYSE:1:30BSY:INTLK_LTH_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb143.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb143.VAL") #! Record("PPS:SYSE:1:30BSY:INTLK_LTH_B_calc",260,18,0,1,"PPS:SYSE:1:30BSY:INTLK_LTH_B_calc") #! Field("PPS:SYSE:1:30BSY:INTLK_LTH_B_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:INTLK_LTH_B_calc.INPA") #! Link("PPS:SYSE:1:30BSY:INTLK_LTH_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb143.VAL") #! Field("PPS:SYSE:1:30BSY:INTLK_LTH_B_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:INTLK_LTH_B_calc.INPB") #! Field("PPS:SYSE:1:30BSY:INTLK_LTH_B_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:INTLK_LTH_B_calc.OUT") #! Link("PPS:SYSE:1:30BSY:INTLK_LTH_B_calc.OUT","PPS:SYSE:1:30BSY:INTLK_LTH_B.VAL") #! Record("PPS:SYSE:1:30BSY:INTLK_LTH_B",500,20,0,0,"PPS:SYSE:1:30BSY:INTLK_LTH_B") #! Field("PPS:SYSE:1:30BSY:INTLK_LTH_B.VAL",16777215,1,"PPS:SYSE:1:30BSY:INTLK_LTH_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi142") { field(DESC, "Port 30BSY_RDB bit 142") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 142, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:SYSE:1:CU:BEAMOK_LTH_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi142Valid") { field(INPA, "PLC:BSY0:PP10:Bi142.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:CU:BEAMOK_LTH_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:CU:BEAMOK_LTH_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi142 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi142Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:CU:BEAMOK_LTH_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:CU:BEAMOK_LTH_B") { field(DESC, "Cu beam config OK (spare) B") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb142",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb142") #! Field("PLC:BSY0:PP10:30BSY_RDBb142.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb142.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb142.FLNK","PPS:SYSE:1:CU:BEAMOK_LTH_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb142.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb142.VAL") #! Record("PPS:SYSE:1:CU:BEAMOK_LTH_B_calc",260,18,0,1,"PPS:SYSE:1:CU:BEAMOK_LTH_B_calc") #! Field("PPS:SYSE:1:CU:BEAMOK_LTH_B_calc.INPA",16777215,0,"PPS:SYSE:1:CU:BEAMOK_LTH_B_calc.INPA") #! Link("PPS:SYSE:1:CU:BEAMOK_LTH_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb142.VAL") #! Field("PPS:SYSE:1:CU:BEAMOK_LTH_B_calc.INPB",16777215,1,"PPS:SYSE:1:CU:BEAMOK_LTH_B_calc.INPB") #! Field("PPS:SYSE:1:CU:BEAMOK_LTH_B_calc.OUT",16777215,1,"PPS:SYSE:1:CU:BEAMOK_LTH_B_calc.OUT") #! Link("PPS:SYSE:1:CU:BEAMOK_LTH_B_calc.OUT","PPS:SYSE:1:CU:BEAMOK_LTH_B.VAL") #! Record("PPS:SYSE:1:CU:BEAMOK_LTH_B",500,20,0,0,"PPS:SYSE:1:CU:BEAMOK_LTH_B") #! Field("PPS:SYSE:1:CU:BEAMOK_LTH_B.VAL",16777215,1,"PPS:SYSE:1:CU:BEAMOK_LTH_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi141") { field(DESC, "Port 30BSY_RDB bit 141") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 141, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:SYSE:1:SC:BEAMOK_LTH_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi141Valid") { field(INPA, "PLC:BSY0:PP10:Bi141.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:SC:BEAMOK_LTH_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:SC:BEAMOK_LTH_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi141 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi141Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:SC:BEAMOK_LTH_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:SC:BEAMOK_LTH_B") { field(DESC, "SC beam config OK (spare) B") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb141",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb141") #! Field("PLC:BSY0:PP10:30BSY_RDBb141.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb141.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb141.FLNK","PPS:SYSE:1:SC:BEAMOK_LTH_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb141.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb141.VAL") #! Record("PPS:SYSE:1:SC:BEAMOK_LTH_B_calc",260,18,0,1,"PPS:SYSE:1:SC:BEAMOK_LTH_B_calc") #! Field("PPS:SYSE:1:SC:BEAMOK_LTH_B_calc.INPA",16777215,0,"PPS:SYSE:1:SC:BEAMOK_LTH_B_calc.INPA") #! Link("PPS:SYSE:1:SC:BEAMOK_LTH_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb141.VAL") #! Field("PPS:SYSE:1:SC:BEAMOK_LTH_B_calc.INPB",16777215,1,"PPS:SYSE:1:SC:BEAMOK_LTH_B_calc.INPB") #! Field("PPS:SYSE:1:SC:BEAMOK_LTH_B_calc.OUT",16777215,1,"PPS:SYSE:1:SC:BEAMOK_LTH_B_calc.OUT") #! Link("PPS:SYSE:1:SC:BEAMOK_LTH_B_calc.OUT","PPS:SYSE:1:SC:BEAMOK_LTH_B.VAL") #! Record("PPS:SYSE:1:SC:BEAMOK_LTH_B",500,20,0,0,"PPS:SYSE:1:SC:BEAMOK_LTH_B") #! Field("PPS:SYSE:1:SC:BEAMOK_LTH_B.VAL",16777215,1,"PPS:SYSE:1:SC:BEAMOK_LTH_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi139") { field(DESC, "Port 30BSY_RDB bit 139") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 139, 1, 1)") field(ZNAM, "Not_Ok") field(ONAM, "Ok") field(FLNK, "PPS:SYSE:1:30BSY:HRTBT_OK_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi139Valid") { field(INPA, "PLC:BSY0:PP10:Bi139.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:HRTBT_OK_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:HRTBT_OK_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi139 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi139Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:HRTBT_OK_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:HRTBT_OK_B") { field(DESC, "Heartbeat OK B") field(ZNAM, "Not_Ok") field(ONAM, "Ok") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb139",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb139") #! Field("PLC:BSY0:PP10:30BSY_RDBb139.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb139.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb139.FLNK","PPS:SYSE:1:30BSY:HRTBT_OK_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb139.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb139.VAL") #! Record("PPS:SYSE:1:30BSY:HRTBT_OK_B_calc",260,18,0,1,"PPS:SYSE:1:30BSY:HRTBT_OK_B_calc") #! Field("PPS:SYSE:1:30BSY:HRTBT_OK_B_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:HRTBT_OK_B_calc.INPA") #! Link("PPS:SYSE:1:30BSY:HRTBT_OK_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb139.VAL") #! Field("PPS:SYSE:1:30BSY:HRTBT_OK_B_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:HRTBT_OK_B_calc.INPB") #! Field("PPS:SYSE:1:30BSY:HRTBT_OK_B_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:HRTBT_OK_B_calc.OUT") #! Link("PPS:SYSE:1:30BSY:HRTBT_OK_B_calc.OUT","PPS:SYSE:1:30BSY:HRTBT_OK_B.VAL") #! Record("PPS:SYSE:1:30BSY:HRTBT_OK_B",500,20,0,0,"PPS:SYSE:1:30BSY:HRTBT_OK_B") #! Field("PPS:SYSE:1:30BSY:HRTBT_OK_B.VAL",16777215,1,"PPS:SYSE:1:30BSY:HRTBT_OK_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi138") { field(DESC, "Port 30BSY_RDB bit 138") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 138, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "STPR:SYSE:1:INSERT_FAILED_LTH_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi138Valid") { field(INPA, "PLC:BSY0:PP10:Bi138.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "STPR:SYSE:1:INSERT_FAILED_LTH_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "STPR:SYSE:1:INSERT_FAILED_LTH_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi138 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi138Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "STPR:SYSE:1:INSERT_FAILED_LTH_B PP MS") field(ASG, "Internal") } record(bi, "STPR:SYSE:1:INSERT_FAILED_LTH_B") { field(DESC, "Stopper_Insert_Failed_B") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb138",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb138") #! Field("PLC:BSY0:PP10:30BSY_RDBb138.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb138.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb138.FLNK","STPR:SYSE:1:INSERT_FAILED_LTH_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb138.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb138.VAL") #! Record("STPR:SYSE:1:INSERT_FAILED_LTH_B_calc",260,18,0,1,"STPR:SYSE:1:INSERT_FAILED_LTH_B_calc") #! Field("STPR:SYSE:1:INSERT_FAILED_LTH_B_calc.INPA",16777215,0,"STPR:SYSE:1:INSERT_FAILED_LTH_B_calc.INPA") #! Link("STPR:SYSE:1:INSERT_FAILED_LTH_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb138.VAL") #! Field("STPR:SYSE:1:INSERT_FAILED_LTH_B_calc.INPB",16777215,1,"STPR:SYSE:1:INSERT_FAILED_LTH_B_calc.INPB") #! Field("STPR:SYSE:1:INSERT_FAILED_LTH_B_calc.OUT",16777215,1,"STPR:SYSE:1:INSERT_FAILED_LTH_B_calc.OUT") #! Link("STPR:SYSE:1:INSERT_FAILED_LTH_B_calc.OUT","STPR:SYSE:1:INSERT_FAILED_LTH_B.VAL") #! Record("STPR:SYSE:1:INSERT_FAILED_LTH_B",500,20,0,0,"STPR:SYSE:1:INSERT_FAILED_LTH_B") #! Field("STPR:SYSE:1:INSERT_FAILED_LTH_B.VAL",16777215,1,"STPR:SYSE:1:INSERT_FAILED_LTH_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi137") { field(DESC, "Port 30BSY_RDB bit 137") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 137, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:SYSE:1:30BSY:HRTBT_OK_LTH_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi137Valid") { field(INPA, "PLC:BSY0:PP10:Bi137.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:30BSY:HRTBT_OK_LTH_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:30BSY:HRTBT_OK_LTH_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi137 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi137Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:30BSY:HRTBT_OK_LTH_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:30BSY:HRTBT_OK_LTH_B") { field(DESC, "Heartbeat OK Latched B") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb137",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb137") #! Field("PLC:BSY0:PP10:30BSY_RDBb137.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb137.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb137.FLNK","PPS:SYSE:1:30BSY:HRTBT_OK_LTH_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb137.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb137.VAL") #! Record("PPS:SYSE:1:30BSY:HRTBT_OK_LTH_B_calc",260,18,0,1,"PPS:SYSE:1:30BSY:HRTBT_OK_LTH_B_calc") #! Field("PPS:SYSE:1:30BSY:HRTBT_OK_LTH_B_calc.INPA",16777215,0,"PPS:SYSE:1:30BSY:HRTBT_OK_LTH_B_calc.INPA") #! Link("PPS:SYSE:1:30BSY:HRTBT_OK_LTH_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb137.VAL") #! Field("PPS:SYSE:1:30BSY:HRTBT_OK_LTH_B_calc.INPB",16777215,1,"PPS:SYSE:1:30BSY:HRTBT_OK_LTH_B_calc.INPB") #! Field("PPS:SYSE:1:30BSY:HRTBT_OK_LTH_B_calc.OUT",16777215,1,"PPS:SYSE:1:30BSY:HRTBT_OK_LTH_B_calc.OUT") #! Link("PPS:SYSE:1:30BSY:HRTBT_OK_LTH_B_calc.OUT","PPS:SYSE:1:30BSY:HRTBT_OK_LTH_B.VAL") #! Record("PPS:SYSE:1:30BSY:HRTBT_OK_LTH_B",500,20,0,0,"PPS:SYSE:1:30BSY:HRTBT_OK_LTH_B") #! Field("PPS:SYSE:1:30BSY:HRTBT_OK_LTH_B.VAL",16777215,1,"PPS:SYSE:1:30BSY:HRTBT_OK_LTH_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi136") { field(DESC, "Port 30BSY_RDB bit 136") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 136, 1, 1)") field(ZNAM, "Not_Cleared") field(ONAM, "Cleared") field(FLNK, "PPS:SYSE:1:CU:HXR_CLEAR_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi136Valid") { field(INPA, "PLC:BSY0:PP10:Bi136.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:CU:HXR_CLEAR_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:CU:HXR_CLEAR_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi136 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi136Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:CU:HXR_CLEAR_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:CU:HXR_CLEAR_B") { field(DESC, "Cu line cleared to HXR B") field(ZNAM, "Not_Cleared") field(ONAM, "Cleared") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb136",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb136") #! Field("PLC:BSY0:PP10:30BSY_RDBb136.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb136.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb136.FLNK","PPS:SYSE:1:CU:HXR_CLEAR_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb136.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb136.VAL") #! Record("PPS:SYSE:1:CU:HXR_CLEAR_B_calc",260,18,0,1,"PPS:SYSE:1:CU:HXR_CLEAR_B_calc") #! Field("PPS:SYSE:1:CU:HXR_CLEAR_B_calc.INPA",16777215,0,"PPS:SYSE:1:CU:HXR_CLEAR_B_calc.INPA") #! Link("PPS:SYSE:1:CU:HXR_CLEAR_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb136.VAL") #! Field("PPS:SYSE:1:CU:HXR_CLEAR_B_calc.INPB",16777215,1,"PPS:SYSE:1:CU:HXR_CLEAR_B_calc.INPB") #! Field("PPS:SYSE:1:CU:HXR_CLEAR_B_calc.OUT",16777215,1,"PPS:SYSE:1:CU:HXR_CLEAR_B_calc.OUT") #! Link("PPS:SYSE:1:CU:HXR_CLEAR_B_calc.OUT","PPS:SYSE:1:CU:HXR_CLEAR_B.VAL") #! Record("PPS:SYSE:1:CU:HXR_CLEAR_B",500,20,0,0,"PPS:SYSE:1:CU:HXR_CLEAR_B") #! Field("PPS:SYSE:1:CU:HXR_CLEAR_B.VAL",16777215,1,"PPS:SYSE:1:CU:HXR_CLEAR_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi151") { field(DESC, "Port 30BSY_RDB bit 151") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 151, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:SYSE:1:CU:HXR_CLEAR_LTH_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi151Valid") { field(INPA, "PLC:BSY0:PP10:Bi151.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:CU:HXR_CLEAR_LTH_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:CU:HXR_CLEAR_LTH_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi151 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi151Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:CU:HXR_CLEAR_LTH_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:CU:HXR_CLEAR_LTH_B") { field(DESC, "Cu line cleared to HXR Lat B") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb151",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb151") #! Field("PLC:BSY0:PP10:30BSY_RDBb151.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb151.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb151.FLNK","PPS:SYSE:1:CU:HXR_CLEAR_LTH_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb151.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb151.VAL") #! Record("PPS:SYSE:1:CU:HXR_CLEAR_LTH_B_calc",260,18,0,1,"PPS:SYSE:1:CU:HXR_CLEAR_LTH_B_calc") #! Field("PPS:SYSE:1:CU:HXR_CLEAR_LTH_B_calc.INPA",16777215,0,"PPS:SYSE:1:CU:HXR_CLEAR_LTH_B_calc.INPA") #! Link("PPS:SYSE:1:CU:HXR_CLEAR_LTH_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb151.VAL") #! Field("PPS:SYSE:1:CU:HXR_CLEAR_LTH_B_calc.INPB",16777215,1,"PPS:SYSE:1:CU:HXR_CLEAR_LTH_B_calc.INPB") #! Field("PPS:SYSE:1:CU:HXR_CLEAR_LTH_B_calc.OUT",16777215,1,"PPS:SYSE:1:CU:HXR_CLEAR_LTH_B_calc.OUT") #! Link("PPS:SYSE:1:CU:HXR_CLEAR_LTH_B_calc.OUT","PPS:SYSE:1:CU:HXR_CLEAR_LTH_B.VAL") #! Record("PPS:SYSE:1:CU:HXR_CLEAR_LTH_B",500,20,0,0,"PPS:SYSE:1:CU:HXR_CLEAR_LTH_B") #! Field("PPS:SYSE:1:CU:HXR_CLEAR_LTH_B.VAL",16777215,1,"PPS:SYSE:1:CU:HXR_CLEAR_LTH_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi150") { field(DESC, "Port 30BSY_RDB bit 150") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 150, 1, 1)") field(ZNAM, "Not_Cleared") field(ONAM, "Cleared") field(FLNK, "PPS:SYSE:1:CU:SXR_CLEAR_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi150Valid") { field(INPA, "PLC:BSY0:PP10:Bi150.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:CU:SXR_CLEAR_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:CU:SXR_CLEAR_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi150 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi150Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:CU:SXR_CLEAR_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:CU:SXR_CLEAR_B") { field(DESC, "Cu line cleared to SXR B") field(ZNAM, "Not_Cleared") field(ONAM, "Cleared") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb150",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb150") #! Field("PLC:BSY0:PP10:30BSY_RDBb150.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb150.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb150.FLNK","PPS:SYSE:1:CU:SXR_CLEAR_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb150.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb150.VAL") #! Record("PPS:SYSE:1:CU:SXR_CLEAR_B_calc",260,18,0,1,"PPS:SYSE:1:CU:SXR_CLEAR_B_calc") #! Field("PPS:SYSE:1:CU:SXR_CLEAR_B_calc.INPA",16777215,0,"PPS:SYSE:1:CU:SXR_CLEAR_B_calc.INPA") #! Link("PPS:SYSE:1:CU:SXR_CLEAR_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb150.VAL") #! Field("PPS:SYSE:1:CU:SXR_CLEAR_B_calc.INPB",16777215,1,"PPS:SYSE:1:CU:SXR_CLEAR_B_calc.INPB") #! Field("PPS:SYSE:1:CU:SXR_CLEAR_B_calc.OUT",16777215,1,"PPS:SYSE:1:CU:SXR_CLEAR_B_calc.OUT") #! Link("PPS:SYSE:1:CU:SXR_CLEAR_B_calc.OUT","PPS:SYSE:1:CU:SXR_CLEAR_B.VAL") #! Record("PPS:SYSE:1:CU:SXR_CLEAR_B",500,20,0,0,"PPS:SYSE:1:CU:SXR_CLEAR_B") #! Field("PPS:SYSE:1:CU:SXR_CLEAR_B.VAL",16777215,1,"PPS:SYSE:1:CU:SXR_CLEAR_B.VAL") #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bi, "PLC:BSY0:PP10:Bi149") { field(DESC, "Port 30BSY_RDB bit 149") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 149, 1, 1)") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(FLNK, "PPS:SYSE:1:CU:SXR_CLEAR_LTH_B_calc PP NMS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:Bi149Valid") { field(INPA, "PLC:BSY0:PP10:Bi149.SEVR NPP NMS") field(CALC, "A=3?VAL+1:0") #Go invalid if input is invalid for 3 seconds field(HIHI, 9) field(HHSV, "INVALID") field(OUT, "PPS:SYSE:1:CU:SXR_CLEAR_LTH_B_calc.C PP MSI") field(SCAN, "1 second") field(ASG, "Internal") field(OOPT, "On Change") } record(calcout, "PPS:SYSE:1:CU:SXR_CLEAR_LTH_B_calc") { field(INPA, "PLC:BSY0:PP10:Bi149 NPP NMS") field(INPB, "PLC:BSY0:PP10:TABLE_9_SEG_1 CP NMS") # Input C is for setting invalid severity, not used otherwise field(INPC, "PLC:BSY0:PP10:Bi149Valid NPP MSI") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PPS:SYSE:1:CU:SXR_CLEAR_LTH_B PP MS") field(ASG, "Internal") } record(bi, "PPS:SYSE:1:CU:SXR_CLEAR_LTH_B") { field(DESC, "Cu line cleared to SXR Lat B") field(ZNAM, "Not_Latched") field(ONAM, "Latched") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } #! Further lines contain data used by VisualDCT #! View(0,0,1.0) #! Record("PLC:BSY0:PP10:30BSY_RDBb149",20,19,0,0,"PLC:BSY0:PP10:30BSY_RDBb149") #! Field("PLC:BSY0:PP10:30BSY_RDBb149.FLNK",16777215,1,"PLC:BSY0:PP10:30BSY_RDBb149.FLNK") #! Link("PLC:BSY0:PP10:30BSY_RDBb149.FLNK","PPS:SYSE:1:CU:SXR_CLEAR_LTH_B_calc") #! Field("PLC:BSY0:PP10:30BSY_RDBb149.VAL",16777215,0,"PLC:BSY0:PP10:30BSY_RDBb149.VAL") #! Record("PPS:SYSE:1:CU:SXR_CLEAR_LTH_B_calc",260,18,0,1,"PPS:SYSE:1:CU:SXR_CLEAR_LTH_B_calc") #! Field("PPS:SYSE:1:CU:SXR_CLEAR_LTH_B_calc.INPA",16777215,0,"PPS:SYSE:1:CU:SXR_CLEAR_LTH_B_calc.INPA") #! Link("PPS:SYSE:1:CU:SXR_CLEAR_LTH_B_calc.INPA","PLC:BSY0:PP10:30BSY_RDBb149.VAL") #! Field("PPS:SYSE:1:CU:SXR_CLEAR_LTH_B_calc.INPB",16777215,1,"PPS:SYSE:1:CU:SXR_CLEAR_LTH_B_calc.INPB") #! Field("PPS:SYSE:1:CU:SXR_CLEAR_LTH_B_calc.OUT",16777215,1,"PPS:SYSE:1:CU:SXR_CLEAR_LTH_B_calc.OUT") #! Link("PPS:SYSE:1:CU:SXR_CLEAR_LTH_B_calc.OUT","PPS:SYSE:1:CU:SXR_CLEAR_LTH_B.VAL") #! Record("PPS:SYSE:1:CU:SXR_CLEAR_LTH_B",500,20,0,0,"PPS:SYSE:1:CU:SXR_CLEAR_LTH_B") #! Field("PPS:SYSE:1:CU:SXR_CLEAR_LTH_B.VAL",16777215,1,"PPS:SYSE:1:CU:SXR_CLEAR_LTH_B.VAL") record(bo, "PPS:SYSE:1:30BSY:RESET_INTLK_B") { field(DESC, "PPS_Interlock_Reset_B") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTB, 7, 1, 1)") field(ZNAM, "Off") field(ONAM, "Reset") field(ASG, "MCC") } record(bo, "PPS:SYSE:1:30BSY:PAUSEHB_B") { field(DESC, "PPS_Pause_Heartbeat_B") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTB, 6, 1, 1)") field(ZNAM, "Off") field(ONAM, "Reset") field(ASG, "MCC") } #============================================================================== # # Abs: PILZ PNOZ PLC interface for accessing the right table/segment # # Name: pilz-plc-request.template # # Facility: LCLS Personnel Protection Controls # # Auth: 11-Dec-2018, Garth Brown (GWBROWN) # Rev : dd-mmm-yyyy, Reviewer's Name (USERNAME) # # To specify which registers to read/write, you need to set the table and # segment (see PNOZ docs). This set of PVs keeps them set to the correct values # for reading either virtual I/O points or program stats such as project checksum. # The PNOZ PLC also has occasional communications dropouts, where the PLC stops # responding and the TCP connection must be reset. This happens more frequently # the more communication there is with the PLC. # While the vendor offers a PNOZ model with integrated Ethernet port which # allows readback at different modbus addresses instead of needing to set # table/segment, that interface also allows remote access to secure registers # and PLC programming. For safety, that type of remote access is not allowed in # our system. All of their products that don't allow remote access beyond our # safety specs also require table/segment setting to choose which registers to # read/write. # #----------------------------------------------------------------------------- # Mod: # #============================================================================== # record(longout, "PLC:BSY0:PP10:REQ_TABLE") { field(DESC, "Table to read/write") field(VAL, "9") field(OUT, "PLC:BSY0:PP10:REQ_TABLE_OUT PP") field(HOPR, "128") field(LOPR, "0") field(PINI, "YES") info(autosaveFields, "VAL") } # All the data we're interested in is: Tables 1 and 9, segment 1 # We only need table 1 once for check sums that don't change, so # read it for a short time during startup, then switch to table 9. record(calcout, "PLC:BSY0:PP10:TABLE_CYCLER") { field( OUT, "PLC:BSY0:PP10:REQ_TABLE PP") field( CALC, "A:=(A+1)%3600;A=20?1:9") field( INPA, "0") field( SCAN, ".5 second") } record(calcout, "PLC:BSY0:PP10:SEG_CYCLER") { field( OUT, "PLC:BSY0:PP10:REQ_SEG PP") field( CALC, "1") field( INPA, "0") field( SCAN, ".5 second") } # Records for disabling PVs when their reqest table isn't active record(calc, "PLC:BSY0:PP10:TABLE_9_SEG_1") { field( INPA, "PLC:BSY0:PP10:REQ_TABLE CP") field( INPB, "PLC:BSY0:PP10:REQ_SEG CP") field( INPC, "PLC:BSY0:PP10:REQ_TABLE_IN CP") field( INPD, "PLC:BSY0:PP10:REQ_SEG_IN CP") field(CALC, "A=9 & B=1 & C=9 & D=1") } record(calc, "PLC:BSY0:PP10:TABLE_1_SEG_1") { field( INPA, "PLC:BSY0:PP10:REQ_TABLE CP") field( INPB, "PLC:BSY0:PP10:REQ_SEG CP") field( INPC, "PLC:BSY0:PP10:REQ_TABLE_IN CP") field( INPD, "PLC:BSY0:PP10:REQ_SEG_IN CP") field(CALC, "A=1 & B=1 & C=1 & D=1") } # The target PVs don't use the data, but this has 8 forward links, # the number we need, while the fanout record only has 6. record(dfanout, "PLC:BSY0:PP10:REQ_TABLE_OUT") { field(OUTA, "PLC:BSY0:PP10:REQ_TABLE_BIT0_CALC.A PP") field(OUTB, "PLC:BSY0:PP10:REQ_TABLE_BIT1_CALC.A PP") field(OUTC, "PLC:BSY0:PP10:REQ_TABLE_BIT2_CALC.A PP") field(OUTD, "PLC:BSY0:PP10:REQ_TABLE_BIT3_CALC.A PP") field(OUTE, "PLC:BSY0:PP10:REQ_TABLE_BIT4_CALC.A PP") field(OUTF, "PLC:BSY0:PP10:REQ_TABLE_BIT5_CALC.A PP") field(OUTG, "PLC:BSY0:PP10:REQ_TABLE_BIT6_CALC.A PP") field(OUTH, "PLC:BSY0:PP10:REQ_TABLE_BIT7_CALC.A PP") field(SDIS, "PLC:BSY0:PP10:REQ_TABLE_IN.PACT") } # The simpler approach of writing to the table/segment every few seconds caused # TCP dropouts to happen several times an hour, compared to every day or two # when we only ever read/wrote table 9 segment 1. These calcout records reduce # the dropouts to around 5 a day by only writing the bits that need to change. record(calcout, "PLC:BSY0:PP10:REQ_TABLE_BIT0_CALC") { field(INPA, "PLC:BSY0:PP10:REQ_TABLE_OUT") field(INPB, "PLC:BSY0:PP10:TABLE_BIT0 MS") field(INPC, "PLC:BSY0:PP10:REQ_TABLE_BIT0 MS") field(CALC, "(B#C)||(B#(A&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "A&1") field(OUT, "PLC:BSY0:PP10:REQ_TABLE_BIT0 PP") } record(calcout, "PLC:BSY0:PP10:REQ_TABLE_BIT1_CALC") { field(INPA, "PLC:BSY0:PP10:REQ_TABLE_OUT") field(INPB, "PLC:BSY0:PP10:TABLE_BIT1 MS") field(INPC, "PLC:BSY0:PP10:REQ_TABLE_BIT1 MS") field(CALC, "(B#C)||(B#((A>>1)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>1)&1") field(OUT, "PLC:BSY0:PP10:REQ_TABLE_BIT1 PP") } record(calcout, "PLC:BSY0:PP10:REQ_TABLE_BIT2_CALC") { field(INPA, "PLC:BSY0:PP10:REQ_TABLE_OUT") field(INPB, "PLC:BSY0:PP10:TABLE_BIT2 MS") field(INPC, "PLC:BSY0:PP10:REQ_TABLE_BIT2 MS") field(CALC, "(B#C)||(B#((A>>2)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>2)&1") field(OUT, "PLC:BSY0:PP10:REQ_TABLE_BIT2 PP") } record(calcout, "PLC:BSY0:PP10:REQ_TABLE_BIT3_CALC") { field(INPA, "PLC:BSY0:PP10:REQ_TABLE_OUT") field(INPB, "PLC:BSY0:PP10:TABLE_BIT3 MS") field(INPC, "PLC:BSY0:PP10:REQ_TABLE_BIT3 MS") field(CALC, "(B#C)||(B#((A>>3)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>3)&1") field(OUT, "PLC:BSY0:PP10:REQ_TABLE_BIT3 PP") } record(calcout, "PLC:BSY0:PP10:REQ_TABLE_BIT4_CALC") { field(INPA, "PLC:BSY0:PP10:REQ_TABLE_OUT") field(INPB, "PLC:BSY0:PP10:TABLE_BIT4 MS") field(INPC, "PLC:BSY0:PP10:REQ_TABLE_BIT4 MS") field(CALC, "(B#C)||(B#((A>>4)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>4)&1") field(OUT, "PLC:BSY0:PP10:REQ_TABLE_BIT4 PP") } record(calcout, "PLC:BSY0:PP10:REQ_TABLE_BIT5_CALC") { field(INPA, "PLC:BSY0:PP10:REQ_TABLE_OUT") field(INPB, "PLC:BSY0:PP10:TABLE_BIT5 MS") field(INPC, "PLC:BSY0:PP10:REQ_TABLE_BIT5 MS") field(CALC, "(B#C)||(B#((A>>5)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>5)&1") field(OUT, "PLC:BSY0:PP10:REQ_TABLE_BIT5 PP") } record(calcout, "PLC:BSY0:PP10:REQ_TABLE_BIT6_CALC") { field(INPA, "PLC:BSY0:PP10:REQ_TABLE_OUT") field(INPB, "PLC:BSY0:PP10:TABLE_BIT6 MS") field(INPC, "PLC:BSY0:PP10:REQ_TABLE_BIT6 MS") field(CALC, "(B#C)||(B#((A>>6)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>6)&1") field(OUT, "PLC:BSY0:PP10:REQ_TABLE_BIT6 PP") } record(calcout, "PLC:BSY0:PP10:REQ_TABLE_BIT7_CALC") { field(INPA, "PLC:BSY0:PP10:REQ_TABLE_OUT") field(INPB, "PLC:BSY0:PP10:TABLE_BIT7 MS") field(INPC, "PLC:BSY0:PP10:REQ_TABLE_BIT7 MS") field(CALC, "(B#C)||(B#((A>>7)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>7)&1") field(OUT, "PLC:BSY0:PP10:REQ_TABLE_BIT7 PP") } record(calcout, "PLC:BSY0:PP10:REQ_TABLE_IN") { field(DESC, "Table readback") field(INPA, "PLC:BSY0:PP10:TABLE_BIT0 CP MS") field(INPB, "PLC:BSY0:PP10:TABLE_BIT1 CP MS") field(INPC, "PLC:BSY0:PP10:TABLE_BIT2 CP MS") field(INPD, "PLC:BSY0:PP10:TABLE_BIT3 CP MS") field(INPE, "PLC:BSY0:PP10:TABLE_BIT4 CP MS") field(INPF, "PLC:BSY0:PP10:TABLE_BIT5 CP MS") field(INPG, "PLC:BSY0:PP10:TABLE_BIT6 CP MS") field(INPH, "PLC:BSY0:PP10:TABLE_BIT7 CP MS") field(CALC, "A+B*2+C*4+D*8+E*16+F*32+G*64+H*128") field(OUT, "PLC:BSY0:PP10:REQ_TABLE PP MS") #field(SDIS, "PLC:BSY0:PP10:REQ_TABLE_OUT.PACT") } record(longout, "PLC:BSY0:PP10:REQ_SEG") { field(DESC, "Segment to read/write") field(VAL, "1") field(OUT, "PLC:BSY0:PP10:REQ_SEG_OUT PP") field(HOPR, "128") field(LOPR, "0") field(PINI, "YES") info(autosaveFields, "VAL") } # The target PVs don't use the data, but this has 8 forward links, # the number we need, while the fanout record only has 6. record(dfanout, "PLC:BSY0:PP10:REQ_SEG_OUT") { field(OUTA, "PLC:BSY0:PP10:REQ_SEG_BIT0_CALC.A PP") field(OUTB, "PLC:BSY0:PP10:REQ_SEG_BIT1_CALC.A PP") field(OUTC, "PLC:BSY0:PP10:REQ_SEG_BIT2_CALC.A PP") field(OUTD, "PLC:BSY0:PP10:REQ_SEG_BIT3_CALC.A PP") field(OUTE, "PLC:BSY0:PP10:REQ_SEG_BIT4_CALC.A PP") field(OUTF, "PLC:BSY0:PP10:REQ_SEG_BIT5_CALC.A PP") field(OUTG, "PLC:BSY0:PP10:REQ_SEG_BIT6_CALC.A PP") field(OUTH, "PLC:BSY0:PP10:REQ_SEG_BIT7_CALC.A PP") field(SDIS, "PLC:BSY0:PP10:REQ_SEG_IN.PACT") } record(calcout, "PLC:BSY0:PP10:REQ_SEG_BIT0_CALC") { field(INPA, "PLC:BSY0:PP10:REQ_SEG_OUT") field(INPB, "PLC:BSY0:PP10:SEG_BIT0 CP MS") field(CALC, "(B#C)||(B#(A&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "A&1") field(OUT, "PLC:BSY0:PP10:REQ_SEG_BIT0 PP") } record(calcout, "PLC:BSY0:PP10:REQ_SEG_BIT1_CALC") { field(INPA, "PLC:BSY0:PP10:REQ_SEG_OUT") field(INPB, "PLC:BSY0:PP10:SEG_BIT1 MS") field(INPC, "PLC:BSY0:PP10:REQ_SEG_BIT1 MS") field(CALC, "(B#C)||(B#((A>>1)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>1)&1") field(OUT, "PLC:BSY0:PP10:REQ_SEG_BIT1 PP") } record(calcout, "PLC:BSY0:PP10:REQ_SEG_BIT2_CALC") { field(INPA, "PLC:BSY0:PP10:REQ_SEG_OUT") field(INPB, "PLC:BSY0:PP10:SEG_BIT2 MS") field(INPC, "PLC:BSY0:PP10:REQ_SEG_BIT2 MS") field(CALC, "(B#C)||(B#((A>>2)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>2)&1") field(OUT, "PLC:BSY0:PP10:REQ_SEG_BIT2 PP") } record(calcout, "PLC:BSY0:PP10:REQ_SEG_BIT3_CALC") { field(INPA, "PLC:BSY0:PP10:REQ_SEG_OUT") field(INPB, "PLC:BSY0:PP10:SEG_BIT3 MS") field(INPC, "PLC:BSY0:PP10:REQ_SEG_BIT3 MS") field(CALC, "(B#C)||(B#((A>>3)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>3)&1") field(OUT, "PLC:BSY0:PP10:REQ_SEG_BIT3 PP") } record(calcout, "PLC:BSY0:PP10:REQ_SEG_BIT4_CALC") { field(INPA, "PLC:BSY0:PP10:REQ_SEG_OUT") field(INPB, "PLC:BSY0:PP10:SEG_BIT4 MS") field(INPC, "PLC:BSY0:PP10:REQ_SEG_BIT4 MS") field(CALC, "(B#C)||(B#((A>>4)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>4)&1") field(OUT, "PLC:BSY0:PP10:REQ_SEG_BIT4 PP") } record(calcout, "PLC:BSY0:PP10:REQ_SEG_BIT5_CALC") { field(INPA, "PLC:BSY0:PP10:REQ_SEG_OUT") field(INPB, "PLC:BSY0:PP10:SEG_BIT5 MS") field(INPC, "PLC:BSY0:PP10:REQ_SEG_BIT5 MS") field(CALC, "(B#C)||(B#((A>>5)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>5)&1") field(OUT, "PLC:BSY0:PP10:REQ_SEG_BIT5 PP") } record(calcout, "PLC:BSY0:PP10:REQ_SEG_BIT6_CALC") { field(INPA, "PLC:BSY0:PP10:REQ_SEG_OUT") field(INPB, "PLC:BSY0:PP10:SEG_BIT6 MS") field(INPC, "PLC:BSY0:PP10:REQ_SEG_BIT6 MS") field(CALC, "(B#C)||(B#((A>>6)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>6)&1") field(OUT, "PLC:BSY0:PP10:REQ_SEG_BIT6 PP") } record(calcout, "PLC:BSY0:PP10:REQ_SEG_BIT7_CALC") { field(INPA, "PLC:BSY0:PP10:REQ_SEG_OUT") field(INPB, "PLC:BSY0:PP10:SEG_BIT7 MS") field(INPC, "PLC:BSY0:PP10:REQ_SEG_BIT7 MS") field(CALC, "(B#C)||(B#((A>>7)&1))") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OCAL, "(A>>7)&1") field(OUT, "PLC:BSY0:PP10:REQ_SEG_BIT7 PP") } record(calcout, "PLC:BSY0:PP10:REQ_SEG_IN") { field(DESC, "Segment readback") field(INPA, "PLC:BSY0:PP10:SEG_BIT0 CP MS") field(INPB, "PLC:BSY0:PP10:SEG_BIT1 CP MS") field(INPC, "PLC:BSY0:PP10:SEG_BIT2 CP MS") field(INPD, "PLC:BSY0:PP10:SEG_BIT3 CP MS") field(INPE, "PLC:BSY0:PP10:SEG_BIT4 CP MS") field(INPF, "PLC:BSY0:PP10:SEG_BIT5 CP MS") field(INPG, "PLC:BSY0:PP10:SEG_BIT6 CP MS") field(INPH, "PLC:BSY0:PP10:SEG_BIT7 CP MS") field(CALC, "A+B*2+C*4+D*8+E*16+F*32+G*64+H*128") field(OUT, "PLC:BSY0:PP10:REQ_SEG PP MS") field(SDIS, "PLC:BSY0:PP10:REQ_SEG_OUT.PACT") } record(bi, "PLC:BSY0:PP10:LED_X1") { field(DESC, "PPS-X1_LED") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 24, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP10:LED_X2") { field(DESC, "PPS-X2_LED") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 25, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP10:PWLED") { field(DESC, "PLC-Power_LED_A") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 26, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP10:RUNLED") { field(DESC, "PLC-Run_LED_A") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 27, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "MAJOR") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP10:DIAGLED") { field(DESC, "PLC-Diag_LED_A") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 28, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP10:FAULTLED") { field(DESC, "PLC-Fault_LED_A") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 29, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP10:IFAULTLED") { field(DESC, "PLC-IFault_LED_A") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 30, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP10:OFAULTLED") { field(DESC, "PLC-OFault_LED_A") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 31, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP10:TABLE_BIT7") { field(DESC, "Table Read bit 7") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 32, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP10:TABLE_BIT6") { field(DESC, "Table Read bit 6") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 33, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP10:TABLE_BIT5") { field(DESC, "Table Read bit 5") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 34, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP10:TABLE_BIT4") { field(DESC, "Table Read bit 4") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 35, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP10:TABLE_BIT3") { field(DESC, "Table Read bit 3") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 36, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP10:TABLE_BIT2") { field(DESC, "Table Read bit 2") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 37, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP10:TABLE_BIT1") { field(DESC, "Table Read bit 1") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 38, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP10:TABLE_BIT0") { field(DESC, "Table Read bit 0") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 39, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP10:SEG_BIT7") { field(DESC, "Segment Read bit 7") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 40, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP10:SEG_BIT6") { field(DESC, "Segment Read bit 6") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 41, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP10:SEG_BIT5") { field(DESC, "Segment Read bit 5") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 42, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP10:SEG_BIT4") { field(DESC, "Segment Read bit 4") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 43, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP10:SEG_BIT3") { field(DESC, "Segment Read bit 3") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 44, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP10:SEG_BIT2") { field(DESC, "Segment Read bit 2") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 45, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP10:SEG_BIT1") { field(DESC, "Segment Read bit 1") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 46, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bi, "PLC:BSY0:PP10:SEG_BIT0") { field(DESC, "Segment Read bit 0") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_RDB, 47, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") info(autosaveFields_pass0, "SEVR") } record(bo, "PLC:BSY0:PP10:REQ_TABLE_BIT7") { field(DESC, "Table Request bit 7") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTB, 32, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP10:REQ_TABLE_BIT6") { field(DESC, "Table Request bit 6") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTB, 33, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP10:REQ_TABLE_BIT5") { field(DESC, "Table Request bit 5") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTB, 34, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP10:REQ_TABLE_BIT4") { field(DESC, "Table Request bit 4") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTB, 35, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP10:REQ_TABLE_BIT3") { field(DESC, "Table Request bit 3") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTB, 36, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP10:REQ_TABLE_BIT2") { field(DESC, "Table Request bit 2") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTB, 37, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP10:REQ_TABLE_BIT1") { field(DESC, "Table Request bit 1") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTB, 38, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP10:REQ_TABLE_BIT0") { field(DESC, "Table Request bit 0") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTB, 39, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP10:REQ_SEG_BIT7") { field(DESC, "Segment Request bit 7") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTB, 40, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP10:REQ_SEG_BIT6") { field(DESC, "Segment Request bit 6") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTB, 41, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP10:REQ_SEG_BIT5") { field(DESC, "Segment Request bit 5") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTB, 42, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP10:REQ_SEG_BIT4") { field(DESC, "Segment Request bit 4") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTB, 43, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP10:REQ_SEG_BIT3") { field(DESC, "Segment Request bit 3") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTB, 44, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP10:REQ_SEG_BIT2") { field(DESC, "Segment Request bit 2") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTB, 45, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP10:REQ_SEG_BIT1") { field(DESC, "Segment Request bit 1") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTB, 46, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } record(bo, "PLC:BSY0:PP10:REQ_SEG_BIT0") { field(DESC, "Segment Request bit 0") field(DTYP, "asynUInt32Digital") field(OUT, "@asynMask(30BSY_WRTB, 47, 1, 1)") field(ZNAM, "Off") field(ONAM, "On") } #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(longin, "PLC:BSY0:PP10:w0") { field(DESC, "S30 BSY CHB Checksum") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_WDB, 0, 0xFFFF, 1)") field(ASG, "Internal") } record(longin, "PLC:BSY0:PP10:w1") { field(DESC, "S30 BSY CHB Checksum") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_WDB, 1, 0xFFFF, 1)") field(ASG, "Internal") } record(longin, "PLC:BSY0:PP10:w2") { field(DESC, "Active Table and Segment") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_WDB, 2, 0xFFFF, 1)") field(FLNK, "PLC:BSY0:PP10:CHECKSUM_SDIS PP MS") field(ASG, "Internal") } record(calc, "PLC:BSY0:PP10:CHECKSUM_SDIS") { field(INPA, "PLC:BSY0:PP10:w2 NPP MS") field(CALC, "A = 0X0101") } record(longin, "PLC:BSY0:PP10:w3") { field(DESC, "S30 BSY CHB Checksum") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_WDB, 3, 0xFFFF, 1)") field(FLNK, "PLC:BSY0:PP10:CHECKSUM_SAFE PP MS") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:CHECKSUM_SAFE_calc") { field(INPA, "PLC:BSY0:PP10:w3 PP MS") field(INPB, "PLC:BSY0:PP10:CHECKSUM_SDIS PP MS") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PLC:BSY0:PP10:CHECKSUM_SAFE PP MS") field(ASG, "Internal") } record(longin, "PLC:BSY0:PP10:CHECKSUM_SAFE") { field(DESC, "Check Sum Safe") field(FLNK, "PLC:BSY0:PP10:CHECKSUM_SAFE_calc PP MS") info(autosaveFields_pass0, "VAL") } record(longin, "PLC:BSY0:PP10:w4") { field(DESC, "S30 BSY CHB Checksum") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_WDB, 4, 0xFFFF, 1)") field(FLNK, "PLC:BSY0:PP10:PROJ_CHECKSUM_calc") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:PROJ_CHECKSUM_calc") { field(INPA, "PLC:BSY0:PP10:w4 NPP MS") field(INPB, "PLC:BSY0:PP10:CHECKSUM_SDIS NPP MS") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PLC:BSY0:PP10:PROJ_CHECKSUM PP MS") field(ASG, "Internal") } record(longin, "PLC:BSY0:PP10:PROJ_CHECKSUM") { field(DESC, "Total Project Check Sum") info(autosaveFields_pass0, "VAL") } record(longin, "PLC:BSY0:PP10:w5") { field(DESC, "S30 BSY CHB Checksum") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_WDB, 5, 0xFFFF, 1)") field(FLNK, "PLC:BSY0:PP10:DAY_MONTH_calc") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:DAY_MONTH_calc") { field(INPA, "PLC:BSY0:PP10:w5 NPP MS") field(INPB, "PLC:BSY0:PP10:CHECKSUM_SDIS NPP MS") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PLC:BSY0:PP10:DAY_MONTH PP MS") field(ASG, "Internal") } record(longin, "PLC:BSY0:PP10:DAY_MONTH") { field(DESC, "Raw day and month") field(ASG, "Internal") } record(calc, "PLC:BSY0:PP10:PROJ_MONTH") { field(DESC, "Project creation day") field(INPA, "PLC:BSY0:PP10:DAY_MONTH CP MS") field(CALC, "A & 0xFF") info(autosaveFields_pass0, "VAL") } record(calc, "PLC:BSY0:PP10:PROJ_DAY") { field(DESC, "Project creation month") field(INPA, "PLC:BSY0:PP10:DAY_MONTH CP MS") field(CALC, "A >> 8") info(autosaveFields_pass0, "VAL") } record(longin, "PLC:BSY0:PP10:w6") { field(DESC, "Checksum word 6") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_WDB, 6, 0xFFFF, 1)") field(FLNK, "PLC:BSY0:PP10:PROJ_YEAR_calc") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:PROJ_YEAR_calc") { field(INPA, "PLC:BSY0:PP10:w6 NPP MS") field(INPB, "PLC:BSY0:PP10:CHECKSUM_SDIS NPP MS") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PLC:BSY0:PP10:PROJ_YEAR PP MS") field(ASG, "Internal") } record(longin, "PLC:BSY0:PP10:PROJ_YEAR") { field(DESC, "Project creation year.") info(autosaveFields_pass0, "VAL") } record(longin, "PLC:BSY0:PP10:w7") { field(DESC, "Checksum word 7") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_WDB, 7, 0xFFFF, 1)") field(FLNK, "PLC:BSY0:PP10:OP_HRS_MSB_calc") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:OP_HRS_MSB_calc") { field(INPA, "PLC:BSY0:PP10:w7 NPP MS") field(INPB, "PLC:BSY0:PP10:CHECKSUM_SDIS NPP MS") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PLC:BSY0:PP10:OP_HRS_MSB PP MS") field(ASG, "Internal") } record(longin, "PLC:BSY0:PP10:OP_HRS_MSB") { field(DESC, "Operation hours upper byte") field(ASG, "Internal") } record(longin, "PLC:BSY0:PP10:w8") { field(DESC, "Checksum word 8") field(SCAN, "I/O Intr") field(DTYP, "asynUInt32Digital") field(INP, "@asynMask(30BSY_WDB, 8, 0xFFFF, 1)") field(FLNK, "PLC:BSY0:PP10:OP_HRS_LSB_calc") field(ASG, "Internal") } record(calcout, "PLC:BSY0:PP10:OP_HRS_LSB_calc") { field(INPA, "PLC:BSY0:PP10:w8 NPP MS") field(INPB, "PLC:BSY0:PP10:CHECKSUM_SDIS NPP MS") field(CALC, "B") field(OCAL, "A") field(DOPT, "Use OCAL") field(OOPT, "When Non-zero") field(OUT, "PLC:BSY0:PP10:OP_HRS_LSB PP MS") field(ASG, "Internal") } record(longin, "PLC:BSY0:PP10:OP_HRS_LSB") { field(DESC, "Operation hours lower byte") field(ASG, "Internal") } record(calc, "PLC:BSY0:PP10:OP_HOURS") { field(INPA, "PLC:BSY0:PP10:OP_HRS_MSB CP MS") field(INPB, "PLC:BSY0:PP10:OP_HRS_LSB CP MS") field(CALC, "(A << 8)+(B>>8)") info(autosaveFields_pass0, "VAL") } record(mbbi, "PLC:BSY0:PP10:BASE_MODEL") { field(DTYP, "Raw Soft Channel") field(NOBT, "8") field(INP, "PLC:BSY0:PP10:OP_HRS_LSB CP MS") field(ZRVL, "0x00") field(ONVL, "0x02") field(TWVL, "0x04") field(THVL, "0x03") field(FRVL, "0x20") field(FVVL, "0x22") field(SXVL, "0x24") field(SVVL, "0x23") field(EIVL, "0x50") field(NIVL, "0x51") field(TEVL, "0x52") field(ZRST, "PNOZ m1p") field(ONST, "PNOZ m0p") field(TWST, "PNOZ m2p") field(THST, "PNOZ m3p") field(FRST, "PNOZ m1p ETH") field(FVST, "PNOZ m0p ETH") field(SXST, "PNOZ m2p ETH") field(SVST, "PNOZ m3p ETH") field(EIST, "PNOZ mm0p") field(NIST, "PNOZ mm0.1p") field(TEST, "PNOZ mm0.2p") } # End of file # Template for I/O statistics record(bo,"PLC:BSY0:PP10:RDHistEnable") { field(DTYP,"asynUInt32Digital") field(OUT,"@asynMask(30BSY_RDB 0 0xFFFF)ENABLE_HISTOGRAM") field(ZNAM,"Disable") field(ONAM,"Enable") } record(bo, "PLC:BSY0:PP10:RDStatistics") { field(SCAN, "10 second") field(FLNK, "PLC:BSY0:PP10:RDHist.PROC") } record(waveform,"PLC:BSY0:PP10:RDHist") { field(DTYP,"asynInt32ArrayIn") field(INP,"@asyn(30BSY_RDB 0)READ_HISTOGRAM") field(FTVL,"LONG") field(NELM,"200") # This number should match driver field(FLNK,"PLC:BSY0:PP10:RDHistTimeAxis.PROC") } record(waveform,"PLC:BSY0:PP10:RDHistTimeAxis") { field(DTYP,"asynInt32ArrayIn") field(INP,"@asyn(30BSY_RDB 0)HISTOGRAM_TIME_AXIS") field(FTVL,"LONG") field(NELM,"200") # This number should match driver field(FLNK,"PLC:BSY0:PP10:RDReadOK.PROC") } record(longout,"PLC:BSY0:PP10:RDMsPerBin") { field(DTYP,"asynInt32") field(OUT,"@asyn(30BSY_RDB 0)HISTOGRAM_BIN_TIME") field(DRVL,"0") field(VAL,"1") field(PINI,"1") } record(longin,"PLC:BSY0:PP10:RDReadOK") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_RDB 0)READ_OK") field(FLNK,"PLC:BSY0:PP10:RDWriteOK.PROC") } record(longin,"PLC:BSY0:PP10:RDWriteOK") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_RDB 0)WRITE_OK") field(FLNK,"PLC:BSY0:PP10:RDIOErrors.PROC") } record(longin,"PLC:BSY0:PP10:RDIOErrors") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_RDB 0)IO_ERRORS") field(FLNK,"PLC:BSY0:PP10:RDLastIOTime.PROC") } record(longin,"PLC:BSY0:PP10:RDLastIOTime") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_RDB 0)LAST_IO_TIME") field(FLNK,"PLC:BSY0:PP10:RDMaxIOTime.PROC") } record(longin,"PLC:BSY0:PP10:RDMaxIOTime") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_RDB 0)MAX_IO_TIME") } # Template for I/O statistics record(bo,"PLC:BSY0:PP10:WRTHistEnable") { field(DTYP,"asynUInt32Digital") field(OUT,"@asynMask(30BSY_WRTB 0 0xFFFF)ENABLE_HISTOGRAM") field(ZNAM,"Disable") field(ONAM,"Enable") } record(bo, "PLC:BSY0:PP10:WRTStatistics") { field(SCAN, "10 second") field(FLNK, "PLC:BSY0:PP10:WRTHist.PROC") } record(waveform,"PLC:BSY0:PP10:WRTHist") { field(DTYP,"asynInt32ArrayIn") field(INP,"@asyn(30BSY_WRTB 0)READ_HISTOGRAM") field(FTVL,"LONG") field(NELM,"200") # This number should match driver field(FLNK,"PLC:BSY0:PP10:WRTHistTimeAxis.PROC") } record(waveform,"PLC:BSY0:PP10:WRTHistTimeAxis") { field(DTYP,"asynInt32ArrayIn") field(INP,"@asyn(30BSY_WRTB 0)HISTOGRAM_TIME_AXIS") field(FTVL,"LONG") field(NELM,"200") # This number should match driver field(FLNK,"PLC:BSY0:PP10:WRTReadOK.PROC") } record(longout,"PLC:BSY0:PP10:WRTMsPerBin") { field(DTYP,"asynInt32") field(OUT,"@asyn(30BSY_WRTB 0)HISTOGRAM_BIN_TIME") field(DRVL,"0") field(VAL,"1") field(PINI,"1") } record(longin,"PLC:BSY0:PP10:WRTReadOK") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_WRTB 0)READ_OK") field(FLNK,"PLC:BSY0:PP10:WRTWriteOK.PROC") } record(longin,"PLC:BSY0:PP10:WRTWriteOK") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_WRTB 0)WRITE_OK") field(FLNK,"PLC:BSY0:PP10:WRTIOErrors.PROC") } record(longin,"PLC:BSY0:PP10:WRTIOErrors") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_WRTB 0)IO_ERRORS") field(FLNK,"PLC:BSY0:PP10:WRTLastIOTime.PROC") } record(longin,"PLC:BSY0:PP10:WRTLastIOTime") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_WRTB 0)LAST_IO_TIME") field(FLNK,"PLC:BSY0:PP10:WRTMaxIOTime.PROC") } record(longin,"PLC:BSY0:PP10:WRTMaxIOTime") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_WRTB 0)MAX_IO_TIME") } # Template for I/O statistics record(bo,"PLC:BSY0:PP10:WDHistEnable") { field(DTYP,"asynUInt32Digital") field(OUT,"@asynMask(30BSY_WDB 0 0xFFFF)ENABLE_HISTOGRAM") field(ZNAM,"Disable") field(ONAM,"Enable") } record(bo, "PLC:BSY0:PP10:WDStatistics") { field(SCAN, "10 second") field(FLNK, "PLC:BSY0:PP10:WDHist.PROC") } record(waveform,"PLC:BSY0:PP10:WDHist") { field(DTYP,"asynInt32ArrayIn") field(INP,"@asyn(30BSY_WDB 0)READ_HISTOGRAM") field(FTVL,"LONG") field(NELM,"200") # This number should match driver field(FLNK,"PLC:BSY0:PP10:WDHistTimeAxis.PROC") } record(waveform,"PLC:BSY0:PP10:WDHistTimeAxis") { field(DTYP,"asynInt32ArrayIn") field(INP,"@asyn(30BSY_WDB 0)HISTOGRAM_TIME_AXIS") field(FTVL,"LONG") field(NELM,"200") # This number should match driver field(FLNK,"PLC:BSY0:PP10:WDReadOK.PROC") } record(longout,"PLC:BSY0:PP10:WDMsPerBin") { field(DTYP,"asynInt32") field(OUT,"@asyn(30BSY_WDB 0)HISTOGRAM_BIN_TIME") field(DRVL,"0") field(VAL,"1") field(PINI,"1") } record(longin,"PLC:BSY0:PP10:WDReadOK") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_WDB 0)READ_OK") field(FLNK,"PLC:BSY0:PP10:WDWriteOK.PROC") } record(longin,"PLC:BSY0:PP10:WDWriteOK") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_WDB 0)WRITE_OK") field(FLNK,"PLC:BSY0:PP10:WDIOErrors.PROC") } record(longin,"PLC:BSY0:PP10:WDIOErrors") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_WDB 0)IO_ERRORS") field(FLNK,"PLC:BSY0:PP10:WDLastIOTime.PROC") } record(longin,"PLC:BSY0:PP10:WDLastIOTime") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_WDB 0)LAST_IO_TIME") field(FLNK,"PLC:BSY0:PP10:WDMaxIOTime.PROC") } record(longin,"PLC:BSY0:PP10:WDMaxIOTime") { field(DTYP,"asynInt32") field(INP,"@asyn(30BSY_WDB 0)MAX_IO_TIME") } record(bo, "PPS:SYSE:1:30BSY:RESET_INTLK") { field(DESC, "30BSY Intlk Reset") field(ZNAM, "Off") field(ONAM, "Reset") field(ZSV, "NO_ALARM") field(OSV, "NO_ALARM") field(FLNK, "PPS:SYSE:1:30BSY:RESET_INTLK_DFO") field(ASG, "MCC") } record(dfanout, "PPS:SYSE:1:30BSY:RESET_INTLK_DFO") { field(DESC, "30BSY Intlk Reset dfanout") field(DOL, "PPS:SYSE:1:30BSY:RESET_INTLK") field(OMSL, "closed_loop") field(OUTA, "PPS:SYSE:1:30BSY:RESET_INTLK_A PP") field(OUTB, "PPS:SYSE:1:30BSY:RESET_INTLK_B PP") field(OUTC, " PP") field(ASG, "MCC") }