MpsConfiguration-R2-225 Config 2025-02-04-b ------------- Remove XPP Beamline In position input Logic 2025-02-04-b ------------- Remove unused ignore logic associated with XPP Beamline In position MpsConfiguration-R2-224 Config 2025-02-04-a ------------- Work for LCLS-II-HE: * Remove XPP inputs * Remove RFBSX14 and RFBSX15 Logic 2025-02-04-a ------------- Remove logic associated with RFBSX14, RFBSX15, and XPP MpsConfiguration-R2-223 Logic 2025-01-17-a ------------- * Fix typo for 10 new HE BLMS (CBLM:UNDS:1610 through 2510) both OK and NOT OK state rate limited to 0 Hz MpsConfiguration-R2-222 Config 2025-01-14-b ------------- * Change autorecoverable flag for all UNDS BPMs and BLMs Logic 2025-01-14-b ------------- * Fix UNDS BPMs 14-25 to look at X and Y instead of X twice. MpsConfiguration-R2-221 Config 2025-01-14-a ------------- * Add CBLM:UNDS:1610 through 2510 * Add RFBSX14 through RFBSX25 * Add OUT switch for CBXFEL station F Logic 2025-01-14-a ------------- * Add logic for I0 and I1 LOSS of CBLM:UNDS:1610 through 2510 * Add logic for RFBSX14 through RFBSX25 * Add logic for station F CBXFEL. Requires it to be OUT MpsConfiguration-R2-220 Update all versions of the scripts to be the same as version1-0-12 for python3 compliance MpsConfiguration-R2-219 Config 2024-08-19-a ------------- * Switch IN/OUT channels of OTR2 and OTR3 Logic 2024-08-19-a ------------- * No changes to logic MpsConfiguration-R2-218 Config 2024-08-13-b ------------- * Add SXR UNDS BPMs for LCLS-II-HE Cell 22 and 23 Logic 2024-08-13-c ------------- Add logic for RFBSX22 and RFBSX23 MpsConfiguration-R2-217 Logic 2024-08-13-b ------------- Add Ignore Condition "STCLTS Is In" for: SIOC BSYS MP01 HEARTBEAT SIOC BSYS MP02 HEARTBEAT SIOC BSYS MP03 HEARTBEAT SIOC BSYS MP04 HEARTBEAT MpsConfiguration-R2-216 Config 2024-08-13-a ------------- No Changes Logic 2024-08-13-a ------------- * Modify SXR Facility Mode to be ignored when STCLTS Is In MpsConfiguration-R2-215 Config 2024-01-30-a ------------- * Remove WIGG:LTUS:726:US_IN * Remove WIGG:LTUS:726:US_OUT * Remove WIGG:LTUS:726:DS_IN * Remove WIGG:LTUS:726:DS_OUT Logic 2024-01-30-a ------------- * Remove logic for UMXL2H upstream and downstream positions MpsConfiguration-R2-214 Config 2023-12-17-a ------------- * Remap YAGS:IN20:921, OTRS:IN20:571, OTRS:IN20:711, OTRS:IN20:465, and OTRS:IN20:471 for injector profile monitor upgrade Logic 2023-12-17-a ------------- * No Changes to logic. MpsConfiguration-R2-213 Config 2023-08-23-a ------------- * Did not make any config changes Logic 2023-08-23-a ------------- * Add "Ignore when SXR in SC Mode" to BRCUSDC Current and BKRCUS Current logic tables MpsConfiguration-R2-212 Config 2023-07-31-a ------------- * No new configuration changes Logic 2023-07-31-a ------------- * Apply HXR SC Mode and SXR SC Mode ignore conditions to many pieces of logic. See attached json files for complete list. MpsConfiguration-R2-211 Config 2023-07-30-a ------------- * Add HXR and SXR FACMODE PV inputs to LN195 (CLTS ATCA Link Node) Logic 2023-07-30-a ------------- * Add logic that stops GUNH/S if UNDH/X is in SC mode * Add ignore logic for beamlines being in SC mode MpsConfiguration-R2-209 Config 2023-07-28-b ------------- * Move BPMS_UNDS_2590 from LN 195 to LN 203 Logic 2023-07-28-b ------------- * Move BPMS:UNDS:2590 Orbit Interlock from LN 195 to LN 203 MpsConfiguration-R2-208 Config 2023-07-28-a ------------- * Remove STCLTS Temperature input - the RTD is not installed Logic 2023-07-28-a ------------- * Remove STCLTS Logic - there is no temperature sensor MpsConfiguration-R2-207 Config 2022-11-10-a ------------- Add: * YAGPSI OUT, P1, P2 to LN 134 (rename OUT and IN to OUT_LMTSW and P1_LMTSW) * OTRDL18 OUT, P1, P2 to LN 205 * VVMG UNDH 1338 to LN 139 (CBXFEL) * VVMG UNDH 1343 to LN 139 (CBXFEL) * VVMG UNDH 2138 to LN 139 (CBXFEL) * VVMG UNDH 2143 to LN 139 (CBXFEL) Logic 2022-11-10-a ------------- Add: * YAGPSI and OTRDL18 PAL Logic (3 position actuator and 5 "broken" states) * Vac OPEN/NOT_OPEN logig for 4 CBXFEL valves listed above MpsConfiguration-R2-206 Config 2022-07-25-a ------------- * Move BSY PPS stopper inputs from mode switching HPS link nodes to Link Node 25 in B005 Logic 2022-07-25-a ------------- * Logic remains the same MpsConfiguration-R2-205 Config 2022-07-18-a ------------- Add 3 signals to Link Node 25 for HX2: S1 CH1 = HXRC:B969:1:ROOM_LEL S1 CH2 = HXRC:B969:1:RCBR_LEL S1 CH3 = HXRC:B969:1:TIMER Logic 2022-07-18-a ------------- Add logic for HX2 inputs. Must be true or beam trips off. MpsConfiguration-R2-204 Logic 2022-06-27-a ------------- * Rename logic for YAGS:LI21:995 to YAGS:IN20:995 MpsConfiguration-R2-203 Logic 2022-06-24-a ------------- * "Remove" (set all mitigation to 120 Hz) log per D. Zhu area physicist for: 1. XPP SB2 VGC 02 Gate Valve Position 2. XPP SB2 VGC 03 Gate Valve Position 3. XPP SB2 VGC 04 Gate Valve Position MpsConfiguration-R2-202 Config 2022-04-21-a ------------- * Move SH2 OUT switch to LN40 card 5 channel 7 Logic 2022-04-21-a ------------- * No logic changes MpsConfiguration-R2-201 Logic 2022-04-07-b ------------- * Change TDUNDB In to 10 Hz limit MpsConfiguration-R2-200 Config 2022-04-07-a ------------- * Add PEPPEX Zone plate (MOVR:UNDS:5013) IN_LMTSW to LN 213 card 3 ch 2 (Ch 25) * Add PEPPEX Zone plate (MOVR:UNDS:5013) OUT_LMTSW to LN 213 card 3 ch 3 (Ch 26) Logic 2022-04-07-a ------------- * Add PEPPEX Zone Plate mover logic * Make TDUNDB IN = 30 Hz rate limit MpsConfiguration-R2-199 Config 2022-03-16-a ------------- * Add VVMG UNDS 4998 to LN 213 card 3 channel 1 Logic 2022-03-16-a ------------- * Add logic for VVMG UNDS 4998 MpsConfiguration-R2-198 Logic 2022-01-13-b ------------- BLMH47 logic pointed to wrong database entry. It pointed to BLMH27. Fixed it MpsConfiguration-R2-197 Config 2022-01-13-a ------------- * Add LN 147 (CBXFEL) * CBLM:UNDH:4775 I0 and I1 * BPMS:UNDH:4790 X and Y * SIOC:UNDH:MP11:HEARTBEAT Logic 2022-01-13-a ------------- * Add Logic for CBXFEL: * CBLM:UNDH:4775 Single Shot and 500 ms * BPMS:UNDH:4790 Position * SIOC:UNDH:MP11:HEARTBEAT Watchdog MpsConfiguration-R2-196 Logic 2021-11-16-a ------------- * Fix SXRSS Mode Logic Code -> if{} if{} changed to if{} else if{} MpsConfiguration-R2-195 Logic 2021-09-23-a ------------- * TDUNDB mitigated to 10 Hz MpsConfiguration-R2-194 Logic 2021-09-21-b ------------- * Update SXRSS Mode to include SLIT mode * Chance SXRSS Watchdog logic to affect BYKIKS instead of Hard Line mitigation devices MpsConfiguration-R2-193 Config 2021-09-21-a ------------- * Fxi channel mapping of inputs from SXRSS MpsSupport Logic 2021-09-21-a ------------- * No logic changes MpsConfiguration-R2-192 Config 2021-09-20-c ------------- No Config Change Logic 2021-09-20-c ------------- Add in SXRSS Mode MpsConfiguration-R2-191 Config 2021-09-20-b ------------- * Fix SXR Guardian and CBLM channels from HXR Link Nodes to SXR Link Nodes Logic 2021-09-20-b ------------- * Logic for SXR Guardian and CBLM watchdog faults MpsConfiguration-R2-190 Config 2021-09-20-a ------------- * Remove PICM_ESA0_1_HV signal - it is flakey physically and no logic behind it Logic 2021-09-20-a ------------- * New logic for the configuration MpsConfiguration-R2-189 Config 2021-09-19-a ------------- * Remove all CBLM Alive faults and replace with 2 summary faults - actual watchdog is handled in MpsSupport now * Remove all CBLM RMON faults and replace with 2 summary faults - actual math is handled in MpsSupport now * Revive SXRSS inputs and logic and update for new beamline * Add 8 additional inputs to LN 216 for PCDS Logic 2021-09-19-a ------------- * Replace CBLM ALIVE and RMON faults with summary faults * Add back SXRSS logic * Add logic for 2 CRIX fast faults from LN 216 MpsConfiguration-R2-188 Logic 2021-06-29-b ------------- * Same as previous but 30 Hz TDUNDB MpsConfiguration-R2-187 Config 2021-06-29-a ------------- * No config changes Logic 2021-06-29-a ------------- * Fix misconfiguration so that RIX vacuum fast fault points to RIX Vacuum input instead of RIX motion input MpsConfiguration-R2-186 Logic 2021-04-30-b ------------- * Change TDUNDB In to 10 Hz rate limit MpsConfiguration-R2-185 Config 2021-04-30-a ------------- * Move BPMS_1990_Y input to different link node * Add input to LN195 for IN20 laser heater power PV reading Logic 2021-04-30-a ------------- * No new logic yet. IN20 Power Meter will come later MpsConfiguration-R2-184 Logic 2021-04-27-b ------------- * Remove logic for BLM/PIC Watchdoe Downstream of TDUND. No PIC / BLM link nodes exist downstream of TDUND anymore. MpsConfiguration-R2-183 Logic 2021-04-27-a ------------- * RFBHX35 and RFBHX36 * Add all UNDH HXR ignore devices which were missing for these 2 pieces of logic * VVMG UNDH 1498, 1798,2838, and 2844 * Remove GUNH mitigation from these 4 truth tables to make these valves consistent with all other VVMG in UNDH area * SLSXS1 Position * Change state 0 to Broken and state 3 to Moving. This is opposite of other "profile monitor"-like devices, but the in-vacuum switches of these slits works slightly differently. Also, the interface box between the in-vacuum switches and the MPS requires AC power. If AC power is lost, both switches go to "0", so the state should read Broken. It is also verified that in the "Moving" state, both switches read high. MpsConfiguration-R2-182 Logic 2021-04-26-a ------------- * Fix bug from previous version where HXRSS Modes were 1, 2, 3 instead of 0, 1, 2. Do not use previous version. MpsConfiguration-R2-181 Config 2021-04-24-a ------------- Readd inputs for HXRSS with correct UNDH and position (girder 28) names: * VVMG UNDH 2838 * VVMG UNDH 2844 * Crystal In encoder position * crystal out limit switch * crystal valid state * BEND DMPH 400 BRANGE * BEND UNDH 2810 ON/OFF and INTOL Logic 2021-04-24-a ------------- Add 6 pieces of logic for HXRSS: 1. VVMG UNDH 2838 Position 2. VVMG UNDH 2844 Position 3. HXRSS Mode (code) 4. HXRSS Crystal Position 5. HXRSS Cryatal Encoder Valid State 6. HXRSS Magnet ON/OFF MpsConfiguration-R2-180 MpsConfiguration-R2-179 Logic 2021-03-25-b ------------- * ALternate logic with TDUNDB Position limited to 30 Hz. MpsConfiguration-R2-178 Config 2021-03-25-a ------------- Remove inputs from LN125 and LN196 - these are SC only and do not need to be part of LCLS1 Logic 2021-03-25-a ------------- Remove logic for inputs from LN125 and LN196 MpsConfiguration-R2-177 Config 2021-03-23-a ------------- Move soft inputs around to better handle LCLS2 Logic 2021-03-23-a ------------- No new logic - just same logic with new input channels MpsConfiguration-R2-176 Config 2021-03-18-a ------------- * Add HXR HOMS Fast Fault to link node 145 card 3 channel 4 per PCDS Logic 2021-03-18-a ------------- * Add logic for XRT HOMS Fast Fault 1, fault at BYKIK MpsConfiguration-R2-175 Logic 2021-03-02-b ------------- TDUNDB IN Position limit SXR to 10 Hz MpsConfiguration-R2-174 Config 2021-03-02-a ------------- Add VVMG LTUS 505 to link node 205 Logic 2021-03-02-a ------------- Activate logic for VVMG LTUS 505 and VVMG LTUS 656 MpsConfiguration-R2-173 Logic 2021-02-24-b ------------- Change TDUNDB IN logic to reduce rate to 30 Hz instead of 10. MpsConfiguration-R2-172 Config 2021-02-24-a ------------- * Add MR1K1 Is Out signal in photon area Logic 2021-02-24-a ------------- * Change RIX logic to use new MR1K1 OUT ignore logic * Applies to RIX Vacuum, MC, and Optics Faults MpsConfiguration-R2-171 Logic 2021-01-27-b ------------- TDUNDB IN mitigates BYKIKS to 10 Hz MpsConfiguration-R2-170 Logic 2021-01-27-a ------------- Change TDUNDB to mitigate at BYKIKS to 30 Hz. MpsConfiguration-R2-169 Config 2021-01-11-a ------------- * Add link processor inputs for SXR and HXR wire scanner mode Logic 2021-01-11-a ------------- * Add logic to monitor power on TDUNDB when it is IN * Add 2 logic tables to handle 10 Hz vs 30 Hz at TDUNDB IN depending on Wire Scanner mode setting MpsConfiguration-R2-168 Config 2020-12-11-a ------------- * Add inputs OUT / IN for: SXRSS M1 SXRSS M2 SXRSS M3 SXRSS SLIT SXRSS BOD10 SXRSS BOD12 into SXR ATCA link nodes * Move TDUND Flow Switch input from LN34 to LN141 * General cleanup and deletion of devices that are no longer in system Logic 2020-12-11-a ------------- * Add temporary logic for all SXRSS insertable devices so that beam is inhibited if device is not OUT. Keep this until system is commissioned MpsConfiguration-R2-167 Config 2020-12-10-a ------------- * Add SW inputs for BPMS UNDH 1305, 1390, 1490, 1690, 1790, and 1890 * Change name of VVMG UNDH 1698 to VVMG UNDH 1798 Logic 2020-12-10-a ------------- * Add standard RFBHX logic for RFBHX12, 13, 14, 16, 17, and 18 * Re-enable logic for VVMG UNDH 1498 and VVMG UNDH 1798 MpsConfiguration-R2-166 Logic 2020-12-01-b ------------- TDUNDB Position limits to 10 Hz MpsConfiguration-R2-165 Config 2020-12-01-a ------------- * Change name of MPLN_FEES_1_RIXOPTFASTFLT to MPLN_FEES_1_RIXVACFASTFLT * Change name of MPLN_FEES_2_RIXOPTFASTFLT to MPLN_FEES_1_RIXOPTFASTFLT Logic 2020-12-01-a ------------- * Add logic for MPLN_FEES_1_RIXVACFASTFLT MPLN_FEES_1_RIXOPTFASTFLT MPLN_FEES_1_RIXMCFASTFLT MpsConfiguration-R2-164 MpsConfiguration-R2-163 Logic 2020-11-30-b ------------- TDUNDB Position IN = 30 Hz rate limit at BYKIKS MpsConfiguration-R2-162 Logic 2020-11-30-a ------------- Change name of ignore logic ST1K4 to ST3K4 per PCDS. MpsConfiguration-R2-161 MpsConfiguration-R2-160 Logic 2020-11-12-b ------------- TDUNDB in at 10 Hz MpsConfiguration-R2-159 Config 2020-11-12-a ------------- * New device names for FEES stopper IN positions which will be used for Ignore Devices ST1K4, MR1K1, and ST1K2 Logic 2020-11-12-a ------------- * Add ignore devices ST1K4 Is In, MR1K1 Is In, ST1K2 Is In * ST1K4 IN MR1K1 IN ST1K2 IN TMO Fast Shutter Fault 2 (Vacuum FFO 4) RIX Motion Fast Fault 1 (no-fault) RIX Motion Fast Fault 2 (no-fault) TMO Vacuum Fast Fault 2 TMO Vacuum Fast Fault 1 RIX Vacuum Fast Fault 1 (no-fault) TMO Motion Fast Fault 1 TMO Vacuum Fast Fault 2 TMO Motion Fast Fault 2 TMO Motion Fast Fault 1 TMO Motion Fast Fault 2 TMO Fast Shutter Fault 1 (Vacuum FFO 3) TMO Fast Shutter Fault 2 (Vacuum FFO 4) MpsConfiguration-R2-158 Logic 2020-11-09-b ------------- * TDUNDB Position In limit SXR to 30 Hz MpsConfiguration-R2-157 Config 2020-11-09-a ------------- * Remove IOC_UNDH)BP02_MPSSTAT * Remove GDET_FEE1_CAL_OK * Remove HYDRECM1, 2, HTEXCH2 per T. Smith. Logic 2020-11-09-a ------------- Logic associated with removed inputs is also deletec. MpsConfiguration-R2-156 Logic 2020-10-26-b ------------- * Change TDUNDB Position IN logic to rate limit SXR to 10 Hz MpsConfiguration-R2-155 Config 2020-10-26-a ------------- * Add faults for RFBHX19 and RFBHX20 * Rename VVPG_UNDH_1998 to VVPG_UNDH_2098 Logic 2020-10-26-a ------------- * Add logic for RFBHX19 and RFBHX20 * Change name of VVPG UNDH 1998 to VVPG UNDH 2098 and set to active MpsConfiguration-R2-154 Logic 2020-10-23-a ------------- * Change logic to allow 30 Hz to TDUNDB MpsConfiguration-R2-153 Config 2020-10-16-a ------------- * Change name of VVPG:UNDH:2198 to VVPG:UNDH:2298 * Add RFBHX15, 22, and 23 X and Y inputs for HXR BPM orbit faults Logic 2020-10-16-a ------------- * Add logic for VVPM:UNDH:2298 * Add logic for RFBHX15, 22, and 23 * Change verbiage of HXR and SXR Arbiter faults to PMPS Rate Limit MpsConfiguration-R2-152 Logic 2020-10-08-a ------------- * Add logic for TMO Fast Shutter Fault 1 and 2 MpsConfiguration-R2-151 Logic 2020-10-06-b ------------- * TDUNGB In to 10 Hz MpsConfiguration-R2-150 Config 2020-10-06-a ------------- * Change BX31 and BX31B to BYD and BYDB (BEND DMPH/S 400) Logic 2020-10-06-a ------------- * Logic for changes to magnet names * TDUNDB at 30 Hz MpsConfiguration-R2-149 Logic 2020-10-03-b ------------- * TDUNDB Position 10 Hz when TDUNDB Is In MpsConfiguration-R2-148 Config 2020-10-03-a ------------- * Add VVPG DMPS 355 Vacuum Valve for XLEAP-S * Add RFBHX18 X and Y PV inputs for girder 18 Logic 2020-10-03-a ------------- * Add logic for new devices * Change TDUNDB Position to 30 Hz when TDUNDB Is In * Change PIC Raw CHarge Thresholds: LTUH 420, 452, 480, 722 to mitigate only at BYKIK MpsConfiguration-R2-147 Config 2020-09-23-a ------------- No config changes Logic 2020-09-23-a ------------- * Add ignore logic to BKRCUS Current and BRCUSDC Current such that they are ignored when the other is on MpsConfiguration-R2-146 Logic 2020-09-08-d ------------- * No logic for MPS / Timing agreement * TDUNDB 10 Hz MpsConfiguration-R2-145 Logic 2020-09-08-c ------------- * TDUNDB Position 30 Hz * No logic that matters for Timing / Mps Ageement MpsConfiguration-R2-144 Logic 2020-09-08-b ------------- * Include EVG / MPS agree logic, TDUNDB Position 30 Hz limit MpsConfiguration-R2-143 Config 2020-09-08-a ------------- No changes - new LP version Logic 2020-09-08-a ------------- No Changes - new LP version MpsConfiguration-R2-142 Config 2020-09-06-a ------------- * Add Latching LP fault to check that no BC1 beam comes out when BRCUSDC is ON LP_BC_MODE_BC1 * Add Latching LP fault to check timing and MPS destinations agree LP_DESTINATION_MATCH Logic 2020-09-06-a ------------- * Add logic to fault beam if either condition in config is met. MpsConfiguration-R2-141 Config 2020-09-03-a ------------- * remove RFBSX51 and RFBHX51 orbit inputs * Add xleap in / out inputs * Add 2vacuum valves for SXRSS * Add SXRSS and HXRSS chincane on / off inputs Logic 2020-09-03-a ------------- * Add logic for vac valves * add logic for xleap positions MpsConfiguration-R2-140 Logic 2020-08-28-b ------------- * TDUNDB Position to 10 Hz MpsConfiguration-R2-139 Logic 2020-08-28-a ------------- * Move RFBHX35 and RFBHX36 from SXR logic to HXR logic - copy mistake problem. * Remove gun mitigation for TDUND and TDUNDB positions * TDUNDB Position 30 Hz limit MpsConfiguration-R2-138 Logic 2020-08-24-b ------------- * Remove GMD and XGMD until PMPS is ready * TDUNDB to 10 Hz MpsConfiguration-R2-137 Logic 2020-08-24-a ------------- * Remove GMD and XGMD logic until PMPS is ready * TDUND Position 30 Hz MpsConfiguration-R2-136 Logic 2020-08-22-b ------------- *TDUNDB Position regulates to 10 Hz MpsConfiguration-R2-135 Logic 2020-08-22-a ------------- * Remove "Destination SXR / Destination HXR" Ignore logig from all undulator BLM faults * TDUNDB Position rate limits to 30 Hz MpsConfiguration-R2-134 Logic 2020-08-19-b ------------- * New mitigation strategy where everything downstream of fast abort kickers aborts only at kickers * TDUNDB Position regulates to 10 Hz at BYKIKS MpsConfiguration-R2-133 Config 2020-08-19-a ------------- * Rearrange some RF BPM input channels per add_devices.json * Add TREF and TDES inputs for each kicker (BYKIK, BYKIKS, BKRCUS) Logic 2020-08-19-a ------------- * Change Mitigation Strategy so that everything downstream of fast abort kicker aborts only at fast abort kicker * TDUNDB Position regulates to 30 Hz at BYKIKS * Add necessary logic based on BPM inputs that were removed and re-added at new channels * Add TDES and TREF faults for all three kickers to monitor timing MpsConfiguration-R2-132 Logic 2020-08-07-c ------------- * Move TDUNDB head to 10 Hz limit. MpsConfiguration-R2-131 Config 2020-08-07-b ------------- Set all Magnet current faults to latching Logic 2020-08-07-b ------------- Set TDUNDB to 30 Hz at BYKIKS MpsConfiguration-R2-130 Logic 2020-08-07-a ------------- * Fix RFBPM SXR faults 16, 19, 51 for real. * move the head for TDUNDB Position to 10 Hz from 30 Hz MpsConfiguration-R2-129 Logic 2020-08-06-b ------------- * Change TDUNDB to 30 Hz rate limit. MpsConfiguration-R2-128 Config 2020-08-06-a ------------- NoNo config changes. Logic 2020-08-06-a ------------- Add logic for CLTS magnets BKRCUS, BLRCUS, BRCUSDC, BRCUS1 currents. Change BYKIK logic to look like BYKIKS logic - no more in link processor MpsConfiguration-R2-127 Config 2020-08-05-a ------------- Add VVPG:CLTS:685:POSITION to LN27 Card 1 Channel 8 Logic 2020-08-05-a ------------- Add logic for VVPG CLTS 685 POSITION STATE MpsConfiguration-R2-126 Config 2020-07-31-c ------------- Ran out of disk space the first time. trying again Logic 2020-07-31-c ------------- ran out of disk space the first time. trying again. MpsConfiguration-R2-125 Config 2020-07-31-b ------------- Remove CXI:DG4:VGC:01 Gast Valve open and closed Logic 2020-07-31-b ------------- Remove CXI DG4 VGC Gate Valve Position MpsConfiguration-R2-124 Config 2020-07-31-a ------------- * remove BPM SXR watchdogs * Add BPM SXR orbit SW inputs * Rename some badly named FEES inputs. Logic 2020-07-31-a ------------- * Add logic for SXR BPM orbit * Rename some badly named FEE logic MpsConfiguration-R2-123 Logic 2020-07-25-b ------------- Remove BLMS48 Threshold I0 HXR fault missed in previous version MpsConfiguration-R2-122 Config 2020-07-25-a ------------- No config changes Logic 2020-07-25-a ------------- * Fix SH2 PPS Stopper Logic so no rate limit when In * Remove BLMS HXR faults - not needed MpsConfiguration-R2-121 Config 2020-07-24-a ------------- * Remove BPM heartbeat watchdogs * Add PVs for X and Y UND orbits in LN 127, 129, 130 Logic 2020-07-24-a ------------- * Add logic for Soft BPM orbit faults * Change name of ignore logic for ST1 to ST1L0 * Add logic fo SH2 Position * Change name of FEE summary faults to make it more clear * Remove BLMH SXR faults MpsConfiguration-R2-120 Logic 2020-07-09-d ------------- Try one more time to figure out how to do CVS. This is hopefully for real sending 30 hx past BYKIK when TDUND is in MpsConfiguration-R2-121 Logic 2020-07-09-c ------------- Ignore 2020-07-09-b. This one changes TDUND to 30 Hz allowed past BYKIK Logic 2020-07-09-b ------------- Allow 30 Hz past BYKIK MpsConfiguration-R2-119 Config 2020-07-09-a ------------- Change BLRCUS PIC (PICM:CLTS:280) LOSSL and LOSSH faults to be latching Logic 2020-07-09-a ------------- Change ignore conditions for BCS PIC in DMP (DMP997 and DMP998) to not be ignored when split beam stoppers are in. These devices are common to HXR and SXR. MpsConfiguration-R2-118 Config 2020-07-02-a ------------- Change BPMS_UNDH_2190_ORBIT to a latching fault Logic 2020-07-02-a ------------- No logic changes MpsConfiguration-R2-117 Config 2020-06-30-a ------------- Move BPM 2190 to card 5 channel 5 Remove VVPG DMPH/S 424 - this is handled by PCDS Logic 2020-06-30-a ------------- Move BPM 2190 to card 5 channel 5 Remove VVPG DMPH/S 424 - this is handled by PCDS MpsConfiguration-R2-116 Config 2020-06-29-a ------------- Release a version for TDUND proper mitigation after releasing the 30 Hz version Logic 2020-06-29-a ------------- Release a version for TDUND proper mitigation after releasing the 30 Hz version MpsConfiguration-R2-115 Config 2020-06-27-b ------------- This is a temporary version that allows beam to TDUND past BYKIK of 30 Hz for low charge commissioning only. Logic 2020-06-27-b ------------- This is a temporary version that allows beam to TDUND past BYKIK of 30 Hz for low charge commissioning only. MpsConfiguration-R2-114 Config 2020-06-27-a ------------- No config changes Logic 2020-06-27-a ------------- Change TDUND Position to mitigate 10 Hz from BYKIK only, not the gun because of the gun / mps dropouts. MpsConfiguration-R2-113 Config 2020-06-26-b ------------- Change TDUND Position to be 10 Hz rate limit at gun HXR and BYKIK Logic 2020-06-26-b ------------- Change TDUND Position to be 10 Hz rate limit at gun HXR and BYKIK MpsConfiguration-R2-112 Config 2020-06-26-a ------------- No config changes. This is a version that temporarily allows operations to send 30 Hz to TDUND. It is only to be used for commissioning, and only with strict administrative controls on the charge. Logic 2020-06-26-a ------------- No config changes. This is a version that temporarily allows operations to send 30 Hz to TDUND with logic "TDUND Position". It is only to be used for commissioning, and only with strict administrative controls on the charge. MpsConfiguration-R2-111 Config 2020-06-20-a ------------- Fix up config and logic for beam to TDUND: * Remove SIOC:LTUH:MP01, MP02, and MP04 heartbeats. Not needed for LCLS1 MPS * Move dechirper THz mirror from LN134 to LN132. Logic 2020-06-20-a ------------- Fix up config and logic for beam to TDUND: * Change the name of VVPG LTUH 102 to VVPG LTUH 100 MpsConfiguration-R2-110 Config 2020-06-14-a ------------- Move SIOC BSYS MP01, MP02, and MP03 from LN203 (doesn't exist) to correct LN 199. Logic 2020-06-14-a ------------- * Fix logic for all SBST Ready - input was off by one for all logic tables i.e Sub Booster 21 logic looked at input from SBST22 * Add logic for sioc bsys mp01, mp02, mp03 watchdogs now that they are in correct link nodes * remove logic for slit 10/30 and hydrogen recombiner as they no longer exist MpsConfiguration-R2-109 Config 2020-06-09-a ------------- No Changes to Config Logic 2020-06-09-a ------------- Fix mechanical shutter bootstrapping problem. When the shutter was removed, the shutter position logic tried to put it back in again. The shutter needs to be not affected by its position logic. only linac permits and bykik permits are affected. MpsConfiguration-R2-108 Config 2020-06-08-a ------------- No Changed to Config Logic 2020-06-08-a ------------- Fix truth table for Gun RF Peak Power Fault which is reversed - 0 is good and 1 is bad. MpsConfiguration-R2-107 Config 2020-06-01-a ------------- Correct Channel assignments for HXR Fast Fault (x2) and HXR Spare in LN 145 Add SXR FEE inputs per PCDS input sheet to LN 216 Logic 2020-06-01-a ------------- Add logic associated with SXR FEE inputs in LN216 Add logic back for HXR FEE fast faults (x2) in LN145 MpsConfiguration-R2-106 Config 2020-05-22-b ------------- * Remove BYKIK_WD LP EPICS Input * Change BEND:DMP1 to BEND:DMPH for 4 EPICS PV LP Faults Logic 2020-05-22-b ------------- * Remove BYKIK_WD LP EPICS Input * Change BEND:DMP1 to BEND:DMPH for 4 EPICS PV LP Faults MpsConfiguration-R2-105 Config 2020-05-22-a ------------- SIOC:LTUH:MP03:HEARTBEAT, MP04m MP05, and MP06 were mistakenly added to the wrong link nodes. MP03 and MP04 are now in LN132 card 2 ch 9 and 10, and MP05 MP06 are added to LN134 card 2 ch 9 and 10. Logic 2020-05-22-a ------------- Modify logic to support LTUH MP03, MP04, MP05, and MP06 now being at the correct input channels in configuration. MpsConfiguration-R2-104 Config 2020-05-21-a ------------- Change EPICS PV Inputs of type QUAD:LTU1 to QUAD:LTUH. Change associated device name as well Logic 2020-05-21-a ------------- Change EPICS PV Inputs of type QUAD:LTU1 to QUAD:LTUH. Change associated device name as well MpsConfiguration-R2-103 Config 2020-05-04-a ------------- Add LP faults LP_BYKIK_OK and LP_BYKIKS_OK Make both faults latching Logic 2020-05-04-a ------------- Add Logic entries for LP_BYKIK_OK and LP_BYKIKS_OK Add truth table for BYKIK Current that is associated with LP_BYKIK_OK, but no truth table added yet for BYKIKS Current. MpsConfiguration-R2-102 Config 2020-04-30-a ------------- * Add Inputs for UND BPM Orbits * Add Inputs for MPS and BPM Heartbeat watchdogs * Add Inputs for CBLM alive watchdog * Add Inputs for CBLM HV status * All added inputs are set to latch when faulted Logic 2020-04-30-a ------------- * Add Logic to support new inputs. All inputs are single input. All either are 120 Hz or 0 Hz permits. MpsConfiguration-R2-101 Config 2020-03-24-a ------------- Remove: SXR_GMD_VGC_01_OPN_DI_POSITION SXR_GMD_VGC_01_CLS_DI_POSITION Logic 2020-03-24-a ------------- Logic associated with these inputs is gone: SXR_GMD_VGC_01_OPN_DI_POSITION SXR_GMD_VGC_01_CLS_DI_POSITION MpsConfiguration-R2-100 Config 2020-03-23-b ------------- The mps_config_gui, for whatever reason, set the autorecoverable flag to true for each new device that was added to the database. For most inputs, this is fine. For the undulator beam loss monitors, these faults need to latch. A script in version1-0-12 interacts with the database and sets these CBLM faults to not autorecover. Logic 2020-03-23-b ------------- No new logic. MpsConfiguration-R2-99 Config 2020-03-23-a ------------- No new configuration. Logic changes for ATCA link node inputs in PCDS. Logic 2020-03-23-a ------------- Add locig for HXR Arbiter and HXR PCDS Fast Faults. MpsConfiguration-R2-98 Config 2020-03-20-b ------------- For LN145, FEEH. Remove placeholder signals and put in correct signals from Alex Wallace / PCDS. Logic to come in next MpsConfiguration version Logic 2020-03-20-b ------------- No new logic in this version. New logic to support FEEH configuration in next version MpsConfiguration-R2-97 Config 2020-03-20-a ------------- No new config. Just keeping in sync with logic. This release should complete the pcds changes for legacy link nodes. Logic 2020-03-20-a ------------- Add Logic for XPP_SB2_VGC_04_OPN_DI and new PPS stoppers ST1L0 and ST1L1 MpsConfiguration-R2-96 Config 2020-03-19-b ------------- Incremental change for PCDS. Remove Stoppers from LN38. LN38 is now completely gone. Logic 2020-03-19-b ------------- Incremental Change for LCDS. Move Stopper SH1 Is In input 0 to STPR_FEE1_ST1_IN_POSITION using logic editor. MpsConfiguration-R2-95 Config 2020-03-19-a ------------- Incremental Change - Remove PCDS Devices from LN38 and LN39 per Alex Wallace. Remove Ignore Logic no longer used. Logic 2020-03-19-a ------------- Incremental Change - Remove PCDS Devices from LN38 and LN39 per Alex Wallace. Remove Ignore Logic no longer used. MpsConfiguration-R2-94 Config 2020-03-18-a ------------- There was a bug beginning with version 2020-01-27-a that corrupted the database. This release captures everything that was done in 2020-01-27-a, 2020-03-12-a, and 2020-02-26-a. The database is not corrputed. Logic 2020-03-18-a ------------- There was a bug beginning with version 2020-01-27-a that corrupted the database. This release captures everything that was done in 2020-01-27-a, 2020-03-12-a, and 2020-02-26-a. The database is not corrputed. MpsConfiguration-R2-93 Config 2020-03-12-a ------------- Add XTCAV Manual (Pneumatic) Valve VVPG:DMPH:355 to Link Node 141 Add Dechirper THz Mirror In/Out switches to LN 134 Logic 2020-03-12-a ------------- Add HXR Vac logic for XTCAV Manual (Pneumatic) Valve VVPG:DMPH:355 to Link Node 141 Add HXR Stopper logic for Dechirper THz Mirror In/Out switches to LN 134 MpsConfiguration-R2-92 Config 2020-02-26-a ------------- Remove VVPG_LTUH_999_POSITION: STPR_BSYS_891_TEMP: STPR_BSYS_897_TEMP: VVMG_LTUS_505_POSITION: Logic 2020-02-26-a ------------- Make inactive: "VVFS SLTH 130 POSITION" 0 "VVPG SLTH 115 POSITION" 0 "VVPG SLTH 291 POSITION" 0 "VVPG UNDH 1998 POSITION" 0 "VVPG UNDH 2198 POSITION" 0 VVMG UNDH 1498 POSITION" 0 VVMG UNDH 1698 POSITION" 0 VVMG UNDH 2838 POSITION" 0 "VVMG UNDH 2843 POSITION" 0 "VVFS SLTS 130 POSITION" 0 VVPG SLTS 115 POSITION" 0 VVPG SLTS 581 POSITION" 0 VVMG LTUS 656 POSITION" 0 Devices to be installed during upcomming PAMMs Change STCLTS In limit from 10 Hz to 120 Hz Change MCC E-stop button to fault ALL mitigation devices MpsConfiguration-R2-91 Config 2020-01-27-a ------------- No changes to configuration. Tag this to keep consistency Logic 2020-01-27-a ------------- *Change linac logic to make BYKIKS mirror behavior for BYKIK. *Change some HXR device logic, especially downstream PICs, to mirror new HXR behavior - kill at Gun HXR and not trip the shutter so delivery can still happen to SXR *Set PCAP1-4 collimator thresholds and flowswitch to inactive *See attached text files for complete list of what was done. MpsConfiguration-R2-90 Config 2020-01-03-b ------------- Add PICM:CLTS:280 at BLRCUS to LN42 Logic 2020-01-03-b ------------- Add logic for PICM:CLTS:280 at BLRCUS MpsConfiguration-R2-89 Config 2020-01-03-a ------------- Remove DUMP_LTU1_970_TDUND_IN and DUMP_LTU1_970_TDUND_OUT as these inputs, associated with TDUND, are now into a new LCLS2 link node and are no londer needed. Logic 2020-01-03-a ------------- Add much new logic associated with the new link nodes and the new LCLS2 SXR and HXR beamlines. Please see the json patch files for a list of all the pieces of logic that were added. This will serve as the foundation of the system checkout that will be conducted prior to operation. MpsConfiguration-R2-88 Config 2020-01-02-h ------------- No config changes, but skip ahead a few letters to get congif back in sync with algorithm Logic 2020-01-02-h ------------- Add ignore devices needed for new SXR beamline Change input for existing ignore devices TDUND and D2 Logic 2020-01-02-g ------------- Still trying to fix issue where database gets corrupted after using logic editor to set pieces of logic to inactive. What has been done here is a new script in version1-0-11 called mpslogicsetactive.py is used to set the active state of logic to 0 writing to the db directly. Hopefully this fixes the problem. Logic 2020-01-02-f ------------- Still having trouble deactivating 2 pieces of logic. Base of this version is 2020-01-02-c Config 2020-01-02-e ------------- There was an error in the logic sql database for version 2020-01-02-d. This version uses 2020-01-02-c as input in an attempt to fix the problem Logic 2020-01-02-e ------------- There was an error in the logic sql database for version 2020-01-02-d. This version uses 2020-01-02-c as input in an attempt to fix the problem MpsConfiguration-R2-87 Config 2020-01-02-d ------------- No Config Changes Logic 2020-01-02-d ------------- Deactivate logic that is temporarily not needed per LCLS2 upgrade. These logic will come back once devices are re-established. MpsConfiguration-R2-86 Config 2020-01-02-c ------------- Rename devices that are to stay after the addition of new LCLS2 beamlines Logic 2020-01-02-c ------------- Logic changes associated with renaming certain devices that remain after LCLS2 upgrade MpsConfiguration-R2-85 Config 2020-01-02-b ------------- Delete devices from legacy link nodes that have either been moved to new ATCA link nodes to share with LCLS2 or are no longer needed due to changes in the beamline. Logic 2020-01-02-b ------------- Logic changes after deleting devices from legacy link nodes. MpsConfiguration-R2-84 Config 2020-01-02-a ------------- Add devices to config for new link nodes with correct PV names and correct inputs. Please ignore and do not use the previous version of MPS configuration, R2-83 Logic 2020-01-02-a ------------- No new logic. Support new configuration for new link nodes. MpsConfiguration-R2-83 Config 2019-12-02-a ------------- In this version, I add all the inputs to support the SXR beamlines, but I have not yet removed the un-needed inputs from the old link nodes. This is initially for testing and commissioning purposes. No logic has been added yet. Logic 2019-12-02-a ------------- In this version, I add all the inputs to support the SXR beamlines, but I have not yet removed the un-needed inputs from the old link nodes. This is initially for testing and commissioning purposes. No logic has been added yet. MpsConfiguration-R2-82 Logic 2019-11-12-a ------------- * New device LP_BKRCUS_FIRE Config 2019-11-12-a ------------- *New LP fault LP_BKRCUS_FIRE Logic 2019-04-17-a ------------- * New scripts version1-0-10: Add 1 Hz rate option to mpslogicpatch.py * New truth tables: MPS Beam Permit: Gun RF HXR MPS Beam Permit: Gun RF SXR MPS Beam Permit: BYKIKS Rate Request: Gun RF HXR 1 Hz Rate Request: Gun RF HXR 10 Hz Rate Request: Gun RF HXR 30 Hz Rate Request: Gun RF HXR 60 Hz Rate Request: Gun RF HXR Burst Rate Request: Gun RF HXR Single Shot Rate Request: Gun RF SXR 1 Hz Rate Request: Gun RF SXR 10 Hz Rate Request: Gun RF SXR 30 Hz Rate Request: Gun RF SXR 60 Hz Rate Request: Gun RF SXR Burst Rate Request: Gun RF SXR Single Shot Rate Request: BYKIKS 1 Hz Rate Request: BYKIKS 10 Hz Rate Request: BYKIKS 30 Hz Rate Request: BYKIKS 60 Hz Rate Request: BYKIKS Burst Rate Request: BYKIKS Single Shot Beam Destination: HXR Beam Destination: SXR Logic 2019-04-16-a ------------- * New LP internal faults (did not successfully add to logic in last version) ALLOWS_BEAM_BYKIKS ALLOWS_BEAM_GUN_HXR ALLOWS_BEAM_GUN_SXR MAX_RATE_BYKIKS_10_HZ MAX_RATE_BYKIKS_1_HZ MAX_RATE_BYKIKS_30_HZ MAX_RATE_BYKIKS_60_HZ MAX_RATE_BYKIKS_BURST MAX_RATE_BYKIKS_SINGLE_SHOT MAX_RATE_GUN_HXR_10_HZ MAX_RATE_GUN_HXR_1_HZ MAX_RATE_GUN_HXR_30_HZ MAX_RATE_GUN_HXR_60_HZ MAX_RATE_GUN_HXR_BURST MAX_RATE_GUN_HXR_SINGLE_SHOT MAX_RATE_GUN_SXR_10_HZ MAX_RATE_GUN_SXR_1_HZ MAX_RATE_GUN_SXR_30_HZ MAX_RATE_GUN_SXR_60_HZ MAX_RATE_GUN_SXR_BURST MAX_RATE_GUN_SXR_SINGLE_SHOT DESTINATION_HXR DESTINATION_SXR Config 2019-03-19-a ------------- * Use new version: scripts/version1-0-9 * New LP internal faults ALLOWS_BEAM_BYKIKS ALLOWS_BEAM_GUN_HXR ALLOWS_BEAM_GUN_SXR MAX_RATE_BYKIKS_10_HZ MAX_RATE_BYKIKS_1_HZ MAX_RATE_BYKIKS_30_HZ MAX_RATE_BYKIKS_60_HZ MAX_RATE_BYKIKS_BURST MAX_RATE_BYKIKS_SINGLE_SHOT MAX_RATE_GUN_HXR_10_HZ MAX_RATE_GUN_HXR_1_HZ MAX_RATE_GUN_HXR_30_HZ MAX_RATE_GUN_HXR_60_HZ MAX_RATE_GUN_HXR_BURST MAX_RATE_GUN_HXR_SINGLE_SHOT MAX_RATE_GUN_SXR_10_HZ MAX_RATE_GUN_SXR_1_HZ MAX_RATE_GUN_SXR_30_HZ MAX_RATE_GUN_SXR_60_HZ MAX_RATE_GUN_SXR_BURST MAX_RATE_GUN_SXR_SINGLE_SHOT DESTINATION_HXR DESTINATION_SXR Logic 2019-03-19-a ------------- * Use new version: scripts/version1-0-9 * New LP internal faults ALLOWS_BEAM_BYKIKS ALLOWS_BEAM_GUN_HXR ALLOWS_BEAM_GUN_SXR MAX_RATE_BYKIKS_10_HZ MAX_RATE_BYKIKS_1_HZ MAX_RATE_BYKIKS_30_HZ MAX_RATE_BYKIKS_60_HZ MAX_RATE_BYKIKS_BURST MAX_RATE_BYKIKS_SINGLE_SHOT MAX_RATE_GUN_HXR_10_HZ MAX_RATE_GUN_HXR_1_HZ MAX_RATE_GUN_HXR_30_HZ MAX_RATE_GUN_HXR_60_HZ MAX_RATE_GUN_HXR_BURST MAX_RATE_GUN_HXR_SINGLE_SHOT MAX_RATE_GUN_SXR_10_HZ MAX_RATE_GUN_SXR_1_HZ MAX_RATE_GUN_SXR_30_HZ MAX_RATE_GUN_SXR_60_HZ MAX_RATE_GUN_SXR_BURST MAX_RATE_GUN_SXR_SINGLE_SHOT DESTINATION_HXR DESTINATION_SXR Logic 2019-03-18-b ------------- * Use new version: scripts/version1-0-8 * Update mitigation device name: Pockels Cell to Gun Linac (PC to GUNL) *except* in places that affect LP code Config 2019-03-18-a ------------- * Use new version: scripts/version1-0-7 Logic 2019-03-18-a ------------- * Use new versions: mps-R1-1-1-branch-clts-R0-0 scripts/version1-0-7 algorithmCommon/version1-0-3 * Add new mitigation devices Gun HXR Gun SXR BYKIKS and add these for each macro state with rate of 'Ignore' MpsConfigurationMR-R2-81 MpsConfiguration-R2-80 Config 2018-09-25-a ------------- * New inputs for LTU Vertical Dechirper downstream mirror MIRR_LTU1_548_OUT_LIMSW MIRR_LTU1_548_IN_LIMSW Logic 2018-09-25-a ------------- * New truth table LTU Dechirper - MIRR LTU1 548 Position (MIRDVDHCP) MpsConfiguration-R2-79 Logic 2018-08-28-a ------------- * Remove XLEAP Wiggler - Downstream End Vertical Gap Too Small XLEAP Wiggler - Upstream End Vertical Gap Too Small * Remove ignore logic XCS Is Not In Main Line Affected truth tables: XCS SB1 VGC 01 Gate Valve Position XCS SB1 VGC 02 Gate Valve Position XCS SB2 VGC 01 Gate Valve Position XCS SB1 Diagnostic Stopper Position MpsConfiguration-R2-78 Logic 2018-03-21-a ------------- * Set OTR30 truth tables inactive: OTR30 LTU1 449 Position OTR30 LTU1 449 Position When TDUND Not In NOTE: Do not use MpsConfiguration-R2-77 MpsConfiguration-R2-77 MpsConfiguration-R2-76 Config 2018-03-02-a ------------- * Remove MFX_LENS_1_SAFE Logic 2018-03-02-a ------------- * Remove MFX Beam Focusing Interlock (Beryllium Lens) MpsConfiguration-R2-75 Config 2017-12-13-a ------------- * Change all PIC/BLM loss and test inputs to be non-autorecoverable (latching). Most already had this setting, but a small number had been misconfigured. * Delete all rate-based PIC/BLM loss inputs. These were intended for rate-recovery, whose prospects are currently unknown and these input state changes flood the log. Logic 2017-12-13-a ------------- * XLEAP MIRXL - MIRR LTU1 829 Position: Make 3 mm position allowed (change rate from 0 -> 120 Hz) MpsConfiguration-R2-74 Config 2017-10-17-a ------------- * Add A-line secondary target IN/OUT status Logic 2017-10-17-a ------------- * Set 'Main Manifold Gauge: LI30 Station 9' Inactive * Set 'XCS Gate Valve Summary - XRT Periscope Line' Inactive * Rename FEE camera 852 and 913 logic to be more accurate MpsConfiguration-R2-73 Config 2017-07-24-a ------------- * New input XCS:PBT:VGC_OUT_SUM Logic 2017-07-24-a ------------- * New truth table XCS Gate Valve Summary - XRT Persicope Line MpsConfiguration-R2-72 Config 2017-06-19-a ------------- * Swap XLEAP mirror 3mm and 5mm position inputs (they are currently reversed). Logic 2017-06-19-a ------------- * Swap XLEAP mirror 3mm and 5mm position inputs (they are currently reversed). MpsConfiguration-R2-71 Logic 2017-06-08-b ------------- * Rename M3H to XRT-M2 in logic truth table names and state names * XRT-M2 (aka M3H) no longer has valid in position; deactivated related logic * FEE camera 852 and 913 FEE PLC interlock logic now does photon transmission check; updated truth table names and state names accordingly * Updated truth table names for A-line kickers now that kickers have been re-named as part of BSY Reconfiguration. (LN inputs still need rename eventually.) Config 2017-06-08-a ------------- * New inputs for XLEAP wiggler gap and insertable devices Logic 2017-06-08-a ------------- * New logic for XLEAP wiggler gap and insertable devices Config 2017-05-24-a ------------- * Remove obsolete inputs: THZR_DMP1_350_OUT_LIMIT THZR_DMP1_350_IN_LIMIT Logic 2017-05-24-a ------------- * Remove obsolete truth tables: THz Radiator Beryllium Foil FEE Camera 1561 Position MpsConfiguration-R2-70 Config 2017-05-22-a ------------- * Add inputs for XLEAP LTU Beam Loss Fiber Logic 2017-05-22-a ------------- * Add logic for XLEAP LTU Beam Loss Fiber Logic 2017-05-18-h ------------- * Add D2 as ignore device for PIC Trigger Missed (LN31) Logic 2017-05-18-g ------------- * Add YAG01, YAG02, TD11 as ignore devices for Linac PIC truth tables Logic 2017-05-18-f ------------- * Add TD11 as ignore device for Linac truth tables downstream of TD11 Logic 2017-05-18-e ------------- * Reinstate TDUND as an ignore device for some end-of-LTU BLMs. (It was removed in 2017-05-18-a.) See changes.log for more details. Logic 2017-05-18-d ------------- * Add missing ignore devices for PIC Trigger Missed (LN25) BCS PIC RAW Charge Threshold DMP 997 BCS PIC RAW Charge Threshold DMP 998 Logic 2017-05-18-c ------------- * Add missing D2 ignore device to more LTU truth tables. Logic 2017-05-18-b ------------- * More ignore logic cleanup. Add D2 as ignore device for injector OTRs when 'TDUND Not In' Logic 2017-05-18-a ------------- * Fix: Remove TDUND as ignore condition for many LTU truth tables. Unclear why it was in the list originally. Logic 2017-05-17-a ------------- * Add D2 Stopper Summary In as ignore condition for many LTU, UND, DMP truth tables. * Add TD11 as ignore condition for VVMG LTU1 505 Position MpsConfiguration-R2-69 Logic 2017-05-16-a ------------- * Allow 120 Hz beam when D2 is IN MpsConfiguration-R2-68 Config 2017-05-13-a ------------- * Remove OTR22 inputs: OTRS_LI25_342_OUT_LMTSW OTRS_LI25_342_IN_LMTSW * For 2017 FEE reconfiguration, many changes. See changes.log and supporting files for details. Logic 2017-05-13-a ------------- * Remove OTR22 truth tables: OTR22 Position OTR22 Position When TDUND Not In * For 2017 FEE reconfiguration, many changes. See changes.log and supporting files for details. MpsConfiguration-R2-67 Config 2017-05-10-b ------------- * New A-line valve VVPG_BSYA_340_OPEN_LIMSW * Remove long-obsolete devices: DEV_52SL1 DEV_50B1 DEV_50PR3OUT HVPS_BSY0_54_POWER * Remove inputs not needed for BSY Reconfiguration: TRGT_BSYA_960_OUT_LIMSW TRGT_BSYA_960_IN_LIMSW TRGT_BSYA_960_FLOW_SW TRGT_BSYA_960_KLIXON COLL_BSYH_479_FLOW_SW COLL_BSYH_487_FLOW_SW COLL_BSYH_495_FLOW_SW COLL_BSYH_520_FLOW_SW Logic 2017-05-10-b ------------- * Logic for new A-line valve: VVPG BSYA 340 Position * Remove inactive obsolete logic DEV 50PR3 Position * Per K. Jobe, remove logic associated with A-line copper target: A-Line Secondary Target Position A-Line Secondary Target Flow Switch A-Line Secondary Target Klixon A-Line Secondary Target Is Out Logic 2017-05-10-a ------------- * Remove references to obsolete FEE Spoiler SP0 and Stoppers ST1/ST2: - Remove truth tables: Spoiler SP0 DMP1 765 Position Stopper: ST1/ST2 Position - Remove ignore logic: Spoiler SP0 Is In ST1/ST2 Are In MpsConfiguration-R2-66 Config 2017-04-28-a ------------- * Replace individual PCAPM flow switches with single switch for PCAPM1-4 * Changed PIC channel assignments for PCAPM1-4 PICs * Remove unused constantly cycling PIC inputs for new BSYH PICs. Note will need to be re-added to implement rate recovery! Logic 2017-04-28-a ------------- * Remove: PIC Raw Charge Thresholds: BSYH 520 PCBSYH/A Flowswitch: COLL BSYH 520 (PCBSYH/A) Flowswitch: COLL BSYH 479 (PCAPM1) Flowswitch: COLL BSYH 495 (PCAPM3) Flowswitch: COLL BSYH 487 (PCAPM2) * Add: Flowswitch: COLL BSYH 479, 487, 495, 503 (PCAPM1-4) MpsConfiguration-R2-65 Config 2017-04-17-a ------------- Many changes to support 2017 downtime BSY Reconfiguration of LCLS common-line, including some A-line related changes. See changes.log and the other supporting documents for details. Logic 2017-04-17-a ------------- Many changes to support 2017 downtime BSY Reconfiguration of LCLS common-line, including some A-line related changes. More details can be found in changes.log and the other supporting documents. * Change 'A-Line B1/B2 Is Not On AND A-Line Kicker Is Not Enabled' to 'A-Line Kicker Is Not Enabled' * Change 'BSY GLAST Target' to 'A-Line Secondary Target' (target now in A-line; no longer in common-line) * Add new truth tables: Flowswitch: COLL BSYH 479 (PCAPM1) Flowswitch: COLL BSYH 487 (PCAPM2) Flowswitch: COLL BSYH 495 (PCAPM3) Flowswitch: COLL BSYH 503 (PCAPM4) Flowswitch: COLL BSYH 520 (PCBSYH/A) PIC Raw Charge Thresholds: BSYH 479 (PCAPM1) PIC Raw Charge Thresholds: BSYH 487 (PCAPM2) PIC Raw Charge Thresholds: BSYH 495 (PCAPM3) PIC Raw Charge Thresholds: BSYH 503 (PCAPM4) PIC Raw Charge Thresholds: BSYH 520 PCBSYH/A PIC Raw Charge Thresholds: BSYH 762 PC90 PIC Raw Charge Thresholds: BSYH 836 PC119 Temperature RTD Summary: BSY Common Line VVFS CLTH 101 Position VVPG BSYH 470 Position VVPG BSYH 541 Position VVPG BSYH 837 Position VVPG CLTH 178 Position VVPG CLTH 375 Position * Remove obsolete truth tables PIC Raw Charge Thresholds: BSY0 16 PIC Raw Charge Thresholds: BSY0 33 PIC Raw Charge Thresholds: BSY0 45 PIC Raw Charge Thresholds: BSY0 59 PIC Raw Charge Thresholds: BSY0 78A PIC Raw Charge Thresholds: BSY0 78B DPS Temperature LI30 Fast Shutter FV2A LI30 Position Fast Shutter FV2 LI30 Position VVPG BSY0 IV2 Position VVPG BSY0 IV3 Position VVPG BSY0 IV4 Position Temperature RTD Summary: BSY Common Line Before D2 Temperature RTD Summary: BSY Common Line Past D2 Ion Chamber Gas Flowswitch BSY A Ion Chamber Gas Flowswitch BSY B Ion Chamber Gas Flowswitch BSY C Flowswitch: BSY PC320 Flowswitch: BSY PC90 Flowswitch: COLL BSY0 16 (50PC20) Flowswitch: COLL BSY0 33 (50PC30) Flowswitch: COLL BSY0 45 (50PC-45) Flowswitch: COLL BSY0 59 (PC0119) Flowswitch: COLL BSY0 65 (PC0145) Flowswitch: COLL BSY0 67 (PC0155) Flowswitch: COLL BSY0 69 (PC0165) Flowswitch: COLL BSY0 71 (PC0175) Flowswitch: COLL BSY0 73 (PC0185) Flowswitch: COLL BSY0 75 (PC0195) MpsConfiguration-R2-64 Logic 2016-11-09-a ------------- * Remove 'MFX Gate Valves Not All Open - PLC Summary Status' * Rename 'Toroid Comparator Dogleg (IM02 vs IM03)' to 'Toroid Comparator Dogleg 1 (IM02 vs IM03)' MpsConfiguration-R2-63 Logic 2016-11-03-a ------------- * Modify titles of toroid comparator truth table names for clarity Logic 2016-10-20-a ------------- * Add ignore condition 'BSY GLAST Target Is Out' * Modify 'BSY GLAST Target Klixon' and 'BSY GLAST Target Flow Switch' to use above ignore condition instead of using the target position in the actual truth table Config 2016-10-19-a ------------- * Delete obsolete device inputs: Dump B4C BSY PR45 BSY PR55 Logic 2016-10-19-a ------------- * Delete obsolete and inactive logic: Profile Monitor BSY0 55 MpsConfiguration-R2-62 Logic 2016-10-18-a ------------- * Remove truth tables: Profile Monitor BSY0 45 Position When D2 or TDUND Not In Profile Monitor BSY0 45 Position Logic 2016-10-17-a ------------- * New MFX interlocks * Add new analog link node inputs (not yet used in logic) Config 2016-10-17-a ------------- * Add new MFX inputs. See changes.log and *diff*.html files for details MpsConfiguration-R2-61 Logic 2016-08-25-a ------------- * Build against database 2016-08-25-a in order to test analog link node inputs. No logic changes. Config 2016-08-25-a ------------- * Add new Analog Link Node 44 and first set of inputs See changes.log for details MpsConfiguration-R2-60 Logic 2016-05-10-a ------------- * Again, minor change to state names for these truth tables: FEE Spectrometer Crystal - Beam Energy Too Low When Crystal Not Out FEE Spectrometer Crystal - Pulse Energy Too High When Crystal Not Out Gas Detector Problem When FEE Spectrometer Crystal Not Out Config 2016-05-02-a ------------- * Remove unused and obsolete device TIUKEYSW aka TIU:IN20:1:KEY_SWITCH_STATE Logic 2016-05-02-a ------------- * Remove unused and obsolete device TIUKEYSW aka TIU:IN20:1:KEY_SWITCH_STATE * Rename Spoiler: SP0 DMP1 765 Position to Spoiler SP0 DMP1 765 Position MpsConfiguration-R2-59 Logic 2016-04-29-a ------------- * Minor change to state names for these truth tables: FEE Spectrometer Crystal - Beam Energy Too Low When Crystal Not Out FEE Spectrometer Crystal - Pulse Energy Too High When Crystal Not Out Gas Detector Problem When FEE Spectrometer Crystal Not Out MpsConfiguration-R2-58 Config 2016-04-26-a ------------- * Delete obsolete dechirper devices DCHP_LTU1_545_WDOG_SUM DCHP_LTU1_545_BPM_INTOL * New devices for FEE spectrometer crystal protection XTAL_FEE1_441_PULSEENERGY, LN10, Card 4, Ch 3 GDET_FEE1_1_CAL_OK, LN10 Card 4, Ch 4 Logic 2016-04-26-a ------------- * New truth tables for FEE spectrometer crystal protection FEE Spectrometer Crystal - Pulse Energy Too High When Crystal Not Out Gas Detector Problem When FEE Spectrometer Crystal Not Out Logic 2016-04-24-a ------------- * No logic changes. Modify Makfile to use scripts/version1-0-6 Config 2016-04-24-a ------------- * No config changes. Modify Makfile.conf to use scripts/version1-0-6 MpsConfiguration-R2-57 Logic 2016-03-01-a ------------- * "FEE Solid Attenuators - Gas Pressure Interlock": allow SATTs 3 and 4 to be IN Logic 2016-02-26-a ------------- * Remove obsolete inputs and associated logic - should not affect algorithm Logic 2016-02-25-a ------------- * Remove obsolete inputs and associated logic - should not affect algorithm Logic 2016-02-24-a ------------- * Remove Dechirper BPM interlocks * Remove dangling unused database objects - should not affect algorithm MpsConfiguration-R2-56 Logic 2016-02-12-a ------------- * Update LTU Horizontal Dechirper Gap truth table now that we have 2 independent gap switches MpsConfiguration-R2-55 Logic 2016-01-22-b ------------- Remove LTU Dechirper - 10 Hz Rate Limit if Dechirper Not Out Logic 2016-01-22-a - BASED ON 2015-12-17-a ------------- Rename some inputs to match their PV names. See changes.log for details. Config 2016-01-22-a ------------- * Rename some input names to match their PV names. See changes.log for details. MpsConfiguration-R2-54 Config 2015-12-07-b ------------- * Removed unused PV attributes from database. For some External PV objects, fill in missing Device Details fields. See changes.log for details. Config 2015-12-07-a ------------- * Removed unused devicedetails and fault objects from database: Devicedetails: THZR LTU1 741 IN_LIMSW MIRR FEE1 1560 OUT_LIMIT1 (two of these) MIRR FEE1 1560 OUT_LIMIT2 (two of these) XTAL FEE1 441 OUT_LIMSW Faults: 'SPARE' '02B' '02A' 'Valve is open' 'A-line Kicker Pulser1': PULSER1_ON, PULSER1_OFF, PULSER1_TRIG_ENB, PULSER1_TRIG_LOCK 'A-line Kicker Pulser2': PULSER2_ON, PULSER2_OFF, PULSER2_TRIG_ENB, PULSER2_TRIG_LOCK 'SL10 CLOSED' 'ST22 OUT' 'THZ-2 Foil Out Switch' 'THZ-2 Foil In Switch' 'FEE spectrometer crystal OUT' Config 2015-12-01-a ------------- * Removed duplicate device instances: MIRR_FEE1_1560_OUT_LIMIT1 (2 duplicates) MIRR_FEE1_1560_OUT_LIMIT2 (2 duplicates) XTAL_FEE1_441_OUT_LIMSW (1 duplicate) Config 2015-11-30-a ------------- * Remove duplicate PvArea LTU1 from database. Changed all devices that used the deleted instance to use the other instance. See changes.log for list of affected devices. * Remove duplicate PvDeviceType BFW from database. Changed all devices that used the deleted instance to use the other instance. See changes.log for list of affected devices. Config 2015-11-23-a ------------- * Remove unused devices: FLOOD_SW_OK TARGET_EPV_FLOSW_2_OK AMO_HFP_MPA_02ASPARE MTLM_LOGIC_OK STOPPER_2_IN_OUT STOPPER_1_IN_OUT AMO_HFP_MPA_02BSPARE RAD_SHLD_FLOSW_9_OK * Remove unused LN channels LN 40 Card 1 Channel 10 LN 40 Card 1 Channel 11 LN 40 Card 2 Channel 9 LN 40 Card 2 Channel 10 LN 40 Card 2 Channel 11 LN 40 Card 3 Channel 11 LN 42 Card 2 Channel 4 LN 42 Card 2 Channel 6 LN 42 Card 3 Channel 8 Logic 2015-12-17-b ------------- Remove LTU Dechirper - 10 Hz Rate Limit if Dechirper Not Out Logic 2015-12-17-a - BASED ON 2015-11-09-a ------------- * Remove unused duplicate truth table * Fix XRT S5 state names (Moving and Broken were swapped) * Update LTU Vertical Dechirper Gap truth table now that we have 2 independent gap switches MpsConfiguration-R2-53 Config 2015-11-09-a ------------- * Add MEC_DV4_VGC_01_OPN_DI * Misc LN 39-41 rename and delete for photon-side inputs. Details in directory. Logic 2015-11-09-b ------------- Remove LTU Dechirper - 10 Hz Rate Limit if Dechirper Not Out Logic 2015-11-09-a - BASED ON 2015-10-10-a ------------- * Remove photon logic: HXX:HXM:VGC:01 Gate Valve Position HXX:HXM:VGC:02 Gate Valve Position HXX:HXM:VGC:03 Gate Valve Position XRT HXRAY MXT Isolation Valve HXX-MXT-VGC-01 NEH AMO Focusing Optics Entrance Gate Valve KBO-VGC-01 NEH AMO Focusing Optics Exit Gate Valve KBO-VGC-02 NEH AMO LAMP Gate Valve VGC 30 Position NEH AMO LAMP Gate Valve VGC 30 Is In Beam NEH AMO LAMP Gate Valve VGC 30 Is Out of Beam * Add photon logic: NEH AMO Valves Ok for Beam - Summary From PLC MEC BXL VGC 01 Gate Valve Position XRT HXRAY MXT Gate Valve HXX:MXT:VGC:01 XRT HXRAY MXT Gate Valve HXX:MXT:VGC:02 XRT HXRAY MXT Gate Valve HXX:MXT:VGC:03 XRT HXRAY MXT Gate Valve HXX:MXT:VGC:05 * Add ignore devices to TDUND Position * Remove B4C Position * Remove Temperature RTD Summary: North Arc MpsConfiguration-R2-52 Logic 2015-10-10-b ------------- Remove LTU Dechirper - 10 Hz Rate Limit if Dechirper Not Out Logic 2015-10-10-a ------------- Remove LTU Dechirper - Undulators Must Be Out If Dechirper Not Out Logic 2015-10-09-a - BASED ON 2015-09-08-a ------------- Add MEC DV4 VCG 01 Gate Valve Position Use database version 2015-10-09-a Config 2015-10-09-a ------------- * Add MEC_DV4_VGC_01_OPN_DI MpsConfiguration-R2-51 Logic 2015-09-08-z: NON-LINEAR LOGIC ------------- This is a version to be used ONLY for LTU Dechirper commissioning. It is based on 2015-09-04-a with these changes: * Add commissioning Dechirper logic: LTU Dechirper Commissioning - BPM 550 Watchdog LTU Dechirper Commissioning - BPM 550 X/Y Position LTU Dechirper Commissioning - TDUND Must Be In Logic 2015-09-08-a ------------- * Add production Dechirper logic: LTU Dechirper - Undulators Must Be Out If Dechirper In LTU Dechirper - 10 Hz Raw Limit if Jaws Not Out LTU Dechirper - BPM 550 Watchdog LTU Dechirper - BPM 550 X/Y Position LTU Dechirper - Horizontal Gap Too Small LTU Dechirper - Vertical Gap Too Small Ignore device: LTU Dechirper Is Out Logic 2015-09-04-a ------------- * Add truth table "MFX Gate Valves Not All Open - PLC Summary Status" Logic 2015-09-03-a ------------- * Add truth table "VVFV IN20 785 Position" * Add Dechirper BLF truth tables: "BLM Heartbeat: Dechirper LTU1 BLF545" "BLM Pedestal Thresholds: Dechirper LTU1 BLF545" "BLM Raw Charge Thresholds: Dechirper LTU1 BLF545" * Set "XPP CS-PAD 1 Detector Damage Fault" inactive Config 2015-09-03-a ------------- * Add Dechirper inputs: BLM:LTU1:BLF545:LOSS_60_L BLM:LTU1:BLF545:LOSS_60_H BLM:LTU1:BLF545:TEST_L BLM:LTU1:BLF545:TEST_H BLM:LTU1:BLF545:TEST_1_L BLM:LTU1:BLF545:TEST_1_H BLM:LTU1:BLF545:PED_L BLM:LTU1:BLF545:PED_H * Add new IN20 fast valve: VVFV:LI20:785:OPEN_LMTSW * Add new MFX hutch vacuum valve PLC summary: MFX_MPS_PLC_VAC_OK MpsConfiguration-R2-50 Logic 2015-07-13-b ------------- * Explicity add inputs for is-code logic (those that were missing) to support MPS GUI improvements * Update logic for CXI:SC3:VGC:01. See changelog for details. MpsConfiguration-R2-49 Logic 2015-07-13-a ------------- * Add new truth table for CXI gate valve: "CXI:SC3:VGC:01 Gate Valve Position" * Modify BC1 toroid comparator state names to reflect new threshold Config 2015-07-13-a ------------- * Add Dechirper inputs: DCHP_LTU1_545_BPM_INTOL_THRESHOLD DCHP_LTU1_545_GAP_LIMSW_NEGZ_POSITION DCHP_LTU1_545_GAP_LIMSW_POSZ_POSITION DCHP_LTU1_545_OUT_LIMSW_NEGY_POSITION DCHP_LTU1_545_OUT_LIMSW_POSY_POSITION DCHP_LTU1_545_WDOG_SUM_STATE DCHP_LTU1_555_GAP_LIMSW_NEGZ_POSITION DCHP_LTU1_555_GAP_LIMSW_POSZ_POSITION DCHP_LTU1_555_OUT_LIMSW_NEGX_POSITION DCHP_LTU1_555_OUT_LIMSW_POSX_POSITION USEG_UND1_1_ALL_OUT_STATE * Add new CXI gate valve open limit switch: CXI_SC3_VGC_01_OPN_DI_POSITION MpsConfiguration-R2-48 Logic 2015-05-18-a ------------- * Add new truth table FEE Solid Attenuators - Gas Pressure Interlock * Modify ignore device lists for: HXR - Beam Energy Too Low With M1S Out FEE Spectrometer Crystal - Beam Energy Too Low When Crystal Not Out Config 2015-05-18-a ------------- * Add FEE Gas attenuator pressure threshold interlock to LN38: VMPS:FEE1:E202:NOGAS MpsConfiguration-R2-47 Logic 2015-05-04-a ------------- * Add new devices: LN42 trigger; LTU dechirper BLF * Add truth table PIC Trigger Missed (LN42) * Remove duplicate truth table Mirror BL21 Position * Per CATER request, add MAD names to OTR/YAG truth tables. Then, to be consistent, add unit numbers to other OTR/YAG truth tables Config 2015-05-01-a ------------- * Add LTU Dechirper Beam Loss Fiber channel to LN30: BLM:LTU1:BLF545 Config 2015-04-22-a ------------- * Add PIC LN 42 trigger input status, fault: PICM_BSYA_2061_NO_TRIG_MISSED MpsConfiguration-R2-46 Logic 2015-03-04-a ------------- * Add TD11 Position truth table to fault moving/broken state Logic 2015-03-02-c ------------- * Remove BX01/BX02 and BXG from ignore device lists for truth tables also ignored by TD11 * Remove duplicate Flowswitch: COLL BSYA 1015 (PC10) * Rename BSY GLAST Target to BSY GLAST Target Position * Remove duplicate Linac slow and fast valves Logic 2015-03-02-b ------------- * Rename TIU, flow switch, IMPS Heartbeat, Pockels Cell truth tables for clarity and consistency Logic 2015-03-02-a ------------- * Remove duplicate truth tables: TIU: DPS Temperature TIU: Fast Shutter 2 Position: LI30 TIU: Fast Shutter 2A Position: LI30 YG BL241 Position YG BL351 Position * Change TIU:MCC Emergency Radiation Stopper to be always evaluated (never ignored) * Add D2 as ignore device for HXRSS logic MpsConfiguration-R2-45 Logic 2015-01-07-b ------------- * NOTE: this version is a pseudo-branch, containing just 2 changes from 2015-01-07-a. Last-minute release to support LCLS MD activities: - Ignore 30-9 slow valve if TD11 is IN MpsConfiguration-R2-44 Logic 2015-01-07-a ------------- * Add TDUND flow switch logic * Reorganize Profile Monitor BSY0 45 logic to take advantage of ignore devices instead of using stopper positions as inputs to logic. Set 'Profile Monitor BSY0 45' logic to Not Active Add 2 new truth tables: 'Profile Monitor BSY0 45 Position' and 'Profile Monitor BSY0 45 Position When D2 or TDUND Not In' * Fix typo in truth table name. Change 'FEE Spectrometer Crystal - Beam Energy Too Low With Crystal Out' to 'FEE Spectrometer Crystal - Beam Energy Too Low When Crystal Not Out' MpsConfiguration-R2-43 Logic 2014-12-05-a ------------- * Add logic to protect FEE spectrometer crystal from low energy beam Config 2014-12-05-a ------------- * Add fault XTAL_FEE1_441_ENERGY * Rename XTAL_FEE1_442_OUT_LIMSW to XTAL_FEE1_441_OUT_LIMSW MpsConfiguration-R2-42 Config 2014-11-25-a ------------- * Add faults KICK:LTU0:320:ABORTWIN KICK:LTU0:320:STANDBYWIN MpsConfiguration-R2-41 Logic 2014-10-24-a ------------ * Add truth tables XPP SB2 VGC 02 Gate Valve Position XPP SB2 VGC 03 Gate Valve Position Config 2014-10-24-a ------------ * Add inputs XPP_SB2_VGC_02_OPN_DI_POSITION XPP_SB2_VGC_03_OPN_DI_POSITION MpsConfiguration-R2-40 Logic 2014-10-16-a ------------ * BCS PIC RAW Charge Threshold DMP 997/998: add D2 to ignore list * OTR21/OTR22 Position: add TD11 To ignore list * OTR30/OTR33 Position: add TD11 and D2 to ignore list Config 2014-10-16-a ------------ * Add FEE Spectrometer Crystal OUT limit switch MpsConfiguration-R2-39 Logic 2014-10-10-a ------------ * Set 'Stopper: ST1/ST2 Position' to only be ignored if D2 IN MpsConfiguration-R2-38 Logic 2014-10-01-a ------------ * Add HXR Beam Energy with M1S Out truth table MpsConfiguration-R2-37 Logic 2014-09-24-a ------------ * Cleanup of photon logic ignore device lists See changes.log for more information MpsConfiguration-R2-36 Logic 2014-09-23-a ------------ * Add new ignore device SP0 spoiler, add it as ignore device to appropriate truth tables MpsConfiguration-R2-35 Modify for cram and static build Added to CVS modules as MpsConfiguration **Note new tag names use capital M, i.e. MpsConfiguration, not mpsConfiguration** mpsConfiguration-R2-34 Logic 2014-07-02-a ------------ * Modify D2 logic to rate-limit beam to 10 Hz (from 120) when D2 is IN * Update PIC HVPS input names to be consistent * Add truth tables for missing PIC HVPS inputs: LI20, LI24, BSY * Fix ignore devices for LI24 BLM/PIC watchdog Config 2014-07-02-a ------------ * Add missing BSY PIC HVPS inputs: 2-6 * Update input and state names for all PIC HVPS to be consistent mpsConfiguration-R2-33 Logic 2014-06-09-a ------------ * Added logic for DMP SP0 Spoiler Position Config 2014-06-09-a ------------ * Added IN and OUT limit switches for DMP SP0 spoiler mpsConfiguration-R2-32 Logic 2014-05-30-a ------------ * Remove photon mirror M3H from lists of ignore devices mpsConfiguration-R2-31 Logic 2014-05-13-a ------------ * Remove CXI Detector Damage truth tables * Set B4C Protection of ST1/ST2 inactive * Update B4C Position * BSY RTD truth table name cleanup * Fix incorrect LHS mitigation rate assignment for some non-LHS-related truth tables mpsConfiguration-R2-30 Logic 2014-03-31-a ------------ * Update CXI valve logic per A. Wallace mpsConfiguration-R2-29 Logic 2014-03-12-a ------------ * Update CXI Configurations 2 and 7 per A. Wallace mpsConfiguration-R2-28 Logic 2014-02-28-a ------------ * Changed names and removed channels for CXI. * Updated CXI configuration summary logic * Added D2 as Ignore Device for many CXI truth tables Config 2014-02-28-a ------------ * Changed names and removed devices for CXI mpsConfiguration-R2-27 Logic 2014-02-26-a ------------ * Update SXRSS Mode logic; remove temporary mode truth tables that were created for commissioniNG mpsConfiguration-R2-26 Logic 2014-02-21-a ------------ * Cleaned up FEE1 M1S Mirror Beam Energy Upper Limit truth table mpsConfiguration-R2-25 Logic 2014-02-06-a ------------ * No logic changes * Use database 2014-01-06-a to pick up databaseCommon/version1-0-4, which adds channel access security to MPS bypasses Config 2014-02-06-a ------------ * Use databaseCommon/version1-0-4 to add channel acces security to MPS bypasses mpsConfiguration-R2-24 Logic 2014-01-06-a ------------ * 50PC30, 50PC45, PC0119 - no longer ignore when A-Line B1/B2 Is Not On AND A-Line Kicker Is Not Enabled (never should have been the case) * SXRSS: Add individual truth tables for each insertable device; Modify mode logic to take advantage of these new tables mpsConfiguration-R2-23 Logic 2013-12-17-a ------------ * SXRSS Mode: Seeded Mode: Allow M3 to be either IN or OUT (previously required to be IN) mpsConfiguration-R2-22 Logic 2013-12-02-a ------------ * Modifications to HXR Beam Energy Lower Limit for future use and set inactive for now * Add FEE1 M1S Mirror State to check for inconsistencies * Add S5B to ignore list for HF4 LAM VGC 01 Gate Valve Position * Add D2 to ignore list for B4C Protection of ST1/ST2 mpsConfiguration-R2-21 Logic 2013-11-11-a ------------ * Enable production SXRSS Mode State; disable temporary SXRSS Mode State - Chicane, Slit, and M3 Active mpsConfiguration-R2-20 Logic 2013-10-28-a ------------ * A-line IV40: Ignore when 'SL10 Closed' or 'B1/B2 Off and A-line Kicker not enabled' mpsConfiguration-R2-19 Config 2013-10-15-a ------------ * Remove AMO_HFP_VGC_02A, AMO_HFP_VGC_02B * Add AMO_LMP_VGC_30_OPN_DI, AMO_LMP_VGC_30_CLS_DI Logic 2013-10-15-a ------------ * Changes for next AMO run: -Remove NEH AMO Diagnostics Chamber Gate Valve -Remove ANEH AMO HFP Beam Stop -Remove NEH AMO End Station Ready -Remove NEH AMO High Field Physics Chamber Gate Valve Summary -Add NEH AMO LAMP VGC 30 Position truth tables mpsConfiguration-R2-18 Config 2013-10-10-a ------------ * Remove OTRS LTU1 743 OUT/IN LIMITs (PSI profile monitor) * Add YAGS LTU1 743 OUT/IN LIMITs (PSI profile monitor) Logic 2013-10-10-a ------------ * Modify PSI Profile Monitor truth table to use YAGS:LTU1:743 inputs instead of OTRS:LTU1:743 inputs; changed truth table name to use YAG instead of OTR mpsConfiguration-R2-17 Config 2013-10-04-a ------------ * Add OTRS LTU1 743 OUT/IN LIMITs (PSI profile monitor) Logic 2013-10-04-a ------------ * Add logic for SXRSS with Chicane, Slit, and M3 Active (for M3 test) * Remove previous M3 standalone logic; not needed * Add LTU PSI profile monitor logic mpsConfiguration-R2-16 Logic 2013-09-24-a ------------ * Add logic for BSY GLAST Target Flow Switch * Add logic for SXRSS M3 (temporary for test of mirror only) * Modify logic for BSY collimator 65, 67, 69, 71, 73, 75) flow switches so that they are not masked by "A-Line B1/B2 Is Not On AND A-Line Kicker Is Not Enabled" * Revive Inactive BSY GLAST Target Klixon with new logic Config 2013-09-24-a ------------ * Add BSY GLAST Target Flow Switch mpsConfiguration-R2-15 Logic 2013-08-28-a ------------ * Modify Ignore Device A-Line B1/B2 Is Not ON and A-Line Kicker Is Not Enabled: - Replace power supply ON status with 2 new OFF status inputs from PPS * Per R. Iverson, modify BSY PR45 logic to require D2 or TDUND to be IN if PR45 IN * Per R. Iverson, M. Stanek remove SXR lower energy limit Config 2013-08-28-a ------------ * Add A-line B1/B2 OFF status Chains A and B from PPS mpsConfiguration-R2-14 Logic 2013-08-02-a ------------ * Add SXRSS logic and devices; remove obsolete e+ devices * Active SXRSS logic assumes only slit and chicane are installed * Inactive SXRSS logic added for potential future use: - All SXRSS devices installed - slit, chicane, M2, M3 installed Config 2013-08-02-a ------------ * Add SXRSS devices mpsConfiguration-R2-13 Logic 2013-07-19-a ------------ * Per CATER 109696, add fault if A-line IV26 NOT_OUT * Add missing state names for B4C protection mpsConfiguration-R2-12 Logic 2013-07-08-a ------------ * Per Cater 109199, add logic that requires B4C in ST0 to be OUT * Per J. Turner (see algorithm/2013-07-08-a/changes.log) require FEE M1S Mirror to be OUT OR Beam Energy is low enough Database 2013-07-08-a --------------- * To support M1S mirror protection (above), add 2 OUT limit switch inputs and 'energy OK' input (this repurposes an unused LN11 input 'BC1_CID') mpsConfiguration-R2-11 Logic 2013-06-15-a ------------ * Per Cater#108919 Regarding mitigating potential B4C damage while running low energy. In attendance were Rad Physics, Paul Miller, John Arthur, Roger, Jim Turner, and M. Stanek. The interim solution for allowing low energy running without a BAS 2 mJ limit was an agreement that we would not allow photons on the ST0 B4C piece at all. Sayed Rokni accepted that as an interim measure, we would use MPS to ensure this condition. What is need required: If ST1/ST2 = Not OUT, Zero rate fault the Gun. This fault should have an 'ignore condition' when TDUND is in, D2 is in, TD11 is in, BX01/02 is NOT ON, YAG BL211 is IN, BXG is ON. Existing B4C ST1_ST2 shall stay in place. mpsConfiguration-R2-10 Logic 2013-06-13-a ------------ * Change D2 Stopper State Strings. Bit 0 and 1 were reversed. Change does not affect logic only readback status string mpsConfiguration-R2-09 Database 2013-06-03-a ------------ * Add GLAST Limit Switches Logic 2013-06-03-a ------------ * Add Logic for GLAST Target Moving * Add Logic for VAC Valve BSYA 4005 (IV40) mpsConfiguration-R2-08 Database 2013-05-27-a * Add new STPR 60 System (D2, ST60,ST61, BTM60,BTM PPS SOLN CNTL). Signals coming from PPS Logic 2013-05-27-a ------------ * Add New STPR 60 System C-code logic, all must be IN or OUT. Change Ignore logic status to use new D2 IN bits and De-Activate D2 Logic from BCS * Add TDUND IN to Prof BSY 45 logic per R.Iverson * De-Activate A-Line LGPS/COR magnets from A-Line logic per R. Iverson and J. Nelson - lgps ab01 1010, 1090, 1950, 2050, 2750, 2850, and xcor 2890, 3212, and ycor 2911, 3313. * De-Activate A-Line GLAST Klixon per R. Iverson and J. Nelson mpsConfiguration-R2-07 Logic 2012-12-10-a --------------------- * Changed HXRSS Mode logic per Heinz-Dieter Nuhn: - HXRSS bend lints changed from 12.7