MpsConfiguration-FACET-R1-18 Config 2024-04-24-a ------------- * No changes to configuration Logic 2024-04-24-a ------------- * Add Laser Heater Attenuator Is In Ignore logic. * Change the way Laser Heater is handled for Injector OTRs to match LCLS behavior. Upon second thought though, I do not think this will actually help if they bypass the screen position to OUT like they did before. I think this will still allow beam. MpsConfiguration-FACET-R1-17 Config 2023-06-26-a ------------- * Remove FLTR:HT10:950:IN -> Kludge for missing LH attn. device * Add FLTR:HT10:430:IN / OUT to link node 10 -> LH attn. device Logic 2023-06-26-a ------------- * Change logic for laser heater with profile monitors to look at new LH attn. IN switch instead of kludge PV * Add logic for laser heater attn. so it closes LHS when ATTN is moving or broken MpsConfiguration-FACET-R1-16 Logic 2023-02-24-a ------------- * Add TD11 In ignore condition for VVPG:LI20:3172 MpsConfiguration-FACET-R1-15 Logic 2023-02-23-b ------------- No Changed - just needed a proper tag MpsConfiguration-FACET-R1-14 Config 2023-02-23-a ------------- * Add VVPG:LI20:3172:POSITION to LN34 Card 2 Channel 9 * Remove VVS:LI10:1:BREAKER Status from the configuration (cater 147150) Logic 2023-02-23-a ------------- * Add logic for VVPG:LI20:3172:POSITION to LN34 Card 2 Channel 9 * Remove VVS:LI10:1:BREAKER Status from the configuration (cater 147150) MpsConfiguration-FACET-R1-13 Logic 2022-11-17-a ------------- Temporarily remove logic for PR11375 and PR10971 - in switches don't work MpsConfiguration-FACET-R1-12 Config 2022-11-16-a ------------- Add PR10465 and laser heater shutter Logic 2022-11-16-a ------------- Add logic for profile monitors and laser heater shutter MpsConfiguration-FACET-R1-11 Logic 2021-05-19-c ------------- * Change OTRS 3158 IN = 0 Hz MpsConfiguration-FACET-R1-10 Config 2021-05-19-b ------------- * No config changes Logic 2021-05-19-b ------------- * Fix Insertable FC ignore logic truth table MpsConfiguration-FACET-R1-9 Config 2021-05-19-a ------------- * Change name of PR10465 to FC10241 Logic 2021-05-19-a ------------- * Add FC10241 as an ignore device for all downstream logic MpsConfiguration-FACET-R1-8 Logic 2021-05-14-d ------------- * Add "PR10241 Is In" Ignore device * Add "TD11390 Is In" Ignore Device * Add S20 logic per C. Clarke MpsConfiguration-FACET-R1-7 Config 2021-05-14-c ------------- * Fix device area and pv area for some hacked devices Logic 2021-05-14-c ------------- * No logic changes MpsConfiguration-FACET-R1-6 Config 2021-05-14-b ------------- * Fix channel mapping in LN11 for TD11390 Logic 2021-05-14-b ------------- * No new logic MpsConfiguration-FACET-R1-5 Config 2021-05-14-a ------------- * Add Profile Monitor inputs to sector 10 LN11 Logic 2021-05-14-a ------------- * Logic DB entries for S10 FACET profile monitors, but no machine logic yet MpsConfiguration-FACET-R1-4 Config 2021-05-06-a ------------- * Add Link Node 34 in Sector 20 (removed from B921) and all former 1553 inputs from CAMAC to this link node Logic 2021-05-06-a ------------- * No new truth tables, just logic to eventually support new inputs in LN34 MpsConfiguration-FACET-R1-3 Config 2021-02-10-a ------------- * Add dummy inputs needed by LP for LCLS into facet config. Bad software design, should get fixed at some point. Jereny's fault Logic 2021-02-10-a ------------- No logic added MpsConfiguration-FACET-R1-2 Logic 2018-05-30-a ------------- * MPS Mechanical Shutter Position: Fix mitigation: now only mitigate with Pockels Cell, not Mechanical Shutter. MpsConfiguration-FACET-R1-1 Config 2018-05-15-a ------------- * Add KLYS_LI10_21_PEAKPOWER Logic 2018-05-15-a ------------- * Add Gun RF Peak Power 10-2 MpsConfiguration-FACET-R1-00 Config 2018-05-11-a ------------- * Rename PLC_IN10_LN11_HEARTBEATSUM to PLC_IN10_MP01_HEARTBEATSUM * Set LN channel types to Deadman for: PLC_IN10_MP01_HEARTBEATSUM IOC_IN10_MP01_HEARTBEATSUM Logic 2018-05-11-a ------------- * Rename PLC-IN10-LN11 MPS Support PLC Heartbeat to PLC-IN10-MP01 MPS Support PLC Heartbeat * Fix mechanical shutter mitigation rate for MPS Beam Permit: Gun RF truth table * Removed PIC/VVS truth tables. Will need to be restored in future. Logic 2018-05-08-a ------------- * No changes to logic. Added unused EPICS External Fault Config 2018-05-08-a ------------- * Add unused 'External EPICS Fault' input to make LP and other software happy Logic 2018-03-21-a ------------- * Initial FACET-II injector MPS Not yet tested Config 2018-03-21-a ------------- * Initial FACET-II injector MPS Not yet tested