1. Set all remaining PIC/BLM 'LOSS' and 'TEST' faults to be non auto-recoverable. Most were, as designed, but a few were not: PICM_BSYH_836_LOSSH PICM_BSYH_762_LOSSL PICM_BSYH_762_LOSSH PICM_BSYH_479_LOSSL PICM_BSYH_479_LOSSH PICM_BSYH_487_LOSSL PICM_BSYH_487_LOSSH PICM_BSYH_495_LOSSL PICM_BSYH_495_LOSSH PICM_BSYH_503_LOSSL PICM_BSYH_503_LOSSH BLM_LTU1_BLF545_LOSS_H BLM_LTU1_BLF545_TEST_L BLM_LTU1_BLF545_TEST_H BLM_LTU1_BLF545_TEST_1_L BLM_LTU1_BLF545_TEST_1_H 2. Remove rate-based PIC and BLM LOSS and TEST inputs. These are intended for rate recovery, but it is unknown when that will happen and these fill the MPS log and input state changes history. Full list in these files (editor seems to not handle well reading in large list/file): BLM_PIC_Rate_Recovery_Related_Inputs_1.txt BLM_PIC_Rate_Recovery_Related_Inputs_2.txt BLM_PIC_Rate_Recovery_Related_Inputs_3.txt BLM_PIC_Rate_Recovery_Related_Inputs_4.txt BLM_PIC_Rate_Recovery_Related_Inputs_5.txt BLM_PIC_Rate_Recovery_Related_Inputs_6.txt 3. XLEAP MIRXL - MIRR LTU1 829 Position: For 3 mm position, change allowed rate from 0 Hz to 120 Hz See Email_A_Marinelli_XLEAP_3mm_Mirror.txt