1. New inputs for LTU Dechirper MPS. LN28 drawing number WD 384-402-25 LN10 drawing number WD 384-402-45 More details can be found here: https://slacspace.slac.stanford.edu/sites/controls/specialprojects/dechirper/Documents/Dechirper%20MPS/Dechirper_MPS.docx Date: Mon, 13 Jul 2015 16:57:23 +0000 From: "Iverson, Richard H." To: "Hoobler, Sonya" Subject: RE: Dechirper MPS question Hi Sonya, I agree we should just latch the BPM orbit fault and not latch any other for the Dechirper. Thanks, Rick -----Original Message----- From: Sonya Hoobler [mailto:sonya@slac.stanford.edu] Sent: Monday, July 13, 2015 9:54 AM To: Iverson, Richard H. Subject: Dechirper MPS question Hi Rick, I'm sorry if we've talked about this and I forgot, but I wanted to check in with you about latching Dechirper MPS faults. For each input, we can decide if the fault latches (requires an operator to reset after each fault) or automatically clears when the fault clears. We latch faults that are concerning enough that we want a person to acknowledge it; also it prevents the fault from just occurring, clearing, then recurring repeatedly. (In LCLS we latch the undulator 'big orbit' interlocks and beam loss monitors faults.) For Dechirper, we may want to latch the BPM orbit fault. I would not recommend latching any others. What would you like to do? Thanks, Sonya 2. New CXI gate valve: Date: Wed, 8 Jul 2015 03:14:52 +0000 From: "Wallace, Alex" To: "Hoobler, Sonya" Subject: MPS Addition for end of July Parts/Attachments: 1 Shown ~28 lines Text 2 OK ~47 lines Text ---------------------------------------- Hi Sonya, CXI is adding a new sample chamber to the their beamline. I was hoping to use LN40:01:16 for the gate valve position OK signal from the PLC. Do you know if the channel is occupied by anything not listed in the MPS screens? If not I'd like to claim it. CXI:SC3:VGC:01:OK The logic should be, beam on if the input is high. Please let me know if you need any other information or if the channel is occupied. Thanks! -Alex