New input to protect solid attenuators from condition in which gas attenuator pressure is high and beam is present: VMPS:FEE1:E202:NOGAS 0 = Gas pressure is too high to allow solid attenuator(s) to be in 1 = Gas pressure is low enough to allow solid attenuator(s) to be in Input signal comes from PLC in FEE. See algorithm/2015-05-18-a/SolidAttenuatorProtectionScheme_revision-2015-18-05.pdf for details.