Previous config/logic version 2016-04-24-a. 1. Delete obsolete dechirper devices: DCHP_LTU1_545_WDOG_SUM DCHP_LTU1_545_BPM_INTOL Changes to augment protection of FEE spectrometer crystal, per J Turner. (Existing energy low limit interlock for crystal remains intact.) 2a. New truth table: FEE Spectrometer Crystal - Pulse Energy Too High When Crystal Not Out Add interlock for pulse energy limit. If pulse energy is too high for the current beam energy and crystal is not out, cause fault. Dehong Zhang provided the lookup table to be used for this threshold. Energy and pulse energy comparisons are done in the MPS support ioc and it then provides a single digital input to LN10 New device XTAL_FEE1_441_PULSEENERGY, LN10, Card 4, Ch 3 2b. New truth table: Gas Detector Problem When FEE Spectrometer Crystal Not Out Add interlock for FEE gas detector 'OK'. The gas detector reading is what is used to measure pulse energy. This interlock verifies that the gas detector calibration is up-to-date and that its value is updating (not frozen or stale). If the value is not updating and the crystal is not out, cause fault. As for 2a, the details of this logic is performed in the MPS support ioc, which then provides a single digital input to LN10 New device GDET_FEE1_1_CAL_OK, LN10 Card 4, Ch 4 For more details, see algorithm/2016-04-26-a/logic_diff.txt patch.log Email_D_Zhang_FEE_Spectrometer_Protection_2016-03-09.txt database/2016-04-26-a/config_diff_abbreviated.html patch.log MpsSupport EPICS IOC application