Update Dechiper logic per R Iverson: LTU horizontal dechirper gap limit switch change. Previously both gap switches were AND-ed into single link node input. Now there are 2 new switches with independent status. Update logic accordingly. Note that switch status comes through motion control system and is not fail-safe if motion control panel loses power. Rick Iverson verbally approved this. See 2012-01-19-a/changes.log for more detail. [sonya@lcls-dev2 algorithm]$ sdiff -bs 2016-01-22-b/doc/MPSLogicDocumentation.txt 2016-02-12-a/doc/MPSLogicDocumentation.txt .. title:: MPS Logic 2016-01-22-b | .. title:: MPS Logic 2012-02-12-a ============= = ==================== ==================== === | ============================ = = ==================== ======= Name A Pockels Cell Mechanical Shutter | Name B A Pockels Cell Mechan ============= = ==================== ==================== === | ============================ = = ==================== ======= Gap too small F 0 Hz 0 Hz | Both ends gap too small F F 0 Hz Gap Ok T 120 Hz 120 Hz | Downstream end gap too small F T 0 Hz ============= = ==================== ==================== === | Upstream end gap too small T F 0 Hz > Gap ok T T 120 Hz > ============================ = = ==================== ======= > B = DCHP_LTU1_555_GAP_LIMSW_POSZ_POSITION