To support LCLS beam to TD11 during POMM work on 3/3/2015, per J Turner (via M Gibbs on phone), modify MPS logic as follows: Add TD11 to ignore device list of 30-9 slow valve (Turns out there are 2 truth tables for this valve, one a duplicate of the other. Add ignore device for both truth tables.) This is not technically a CVS branch, but because there are so many new algorithm versions that have not yet been tested/released, this 'branch' just includes this one change. [sonya@lcls-dev2 algorithm]$ sdiff -bs 2015-01-07-a/doc/MPSLogicDocumentation.txt 2015-01-07-br-a/doc/MPSLogicDocumentation.txt .. title:: MPS Logic 2015-01-07-a | .. title:: MPS Logic 2015-01-07-br-a > TIU: VVPG LI30-9 Position (Station 30-9) > ---------------------------------------- > ======== = ==================== ==================== ======== > Name A Pockels Cell Mechanical Shutter B > ======== = ==================== ==================== ======== > Not Open F 0 Hz 0 Hz > Open T 120 Hz 120 Hz > ======== = ==================== ==================== ======== > > Where:: > > A = SLOW_VLV_30_9_OK_OPEN_STATE > > > VVPG LI30-9 Position (Station 30-9) > ----------------------------------- > ======= = ==================== ==================== ========= > Name A Pockels Cell Mechanical Shutter BY > ======= = ==================== ==================== ========= > Not Out F 0 Hz 0 Hz > Out T 120 Hz 120 Hz > ======= = ==================== ==================== ========= > > Where:: > > A = SLOW_VLV_30_9_OK_OPEN_STATE > > TIU: VVPG LI30-9 Position (Station 30-9) < ---------------------------------------- < ======== = ==================== ==================== ======== < Name A Pockels Cell Mechanical Shutter B < ======== = ==================== ==================== ======== < Not Open F 0 Hz 0 Hz < Open T 120 Hz 120 Hz < ======== = ==================== ==================== ======== < < Where:: < < A = SLOW_VLV_30_9_OK_OPEN_STATE < < < VVPG LI30-9 Position (Station 30-9) < ----------------------------------- < ======= = ==================== ==================== ========= < Name A Pockels Cell Mechanical Shutter BY < ======= = ==================== ==================== ========= < Not Out F 0 Hz 0 Hz < Out T 120 Hz 120 Hz < ======= = ==================== ==================== ========= < < Where:: < < A = SLOW_VLV_30_9_OK_OPEN_STATE < < <