1. Add logic for new CXI gate valve, CXI_SC3_VGC_01. If valve is not out, cause 0 Hz fault. Ignore device list to match other CXI valves. 2. Modify BC1 toroid comparator logic state names to reflect new threshold: Upstream > Downstream 200 pC (previously 50 pC) Downstream > Upstream 50 pC (unchanged) Snapshot of checkout in file BC1_TC_Checkout_DgtU_50pC_UgtD_200pC.png [sonya@lcls-dev2 algorithm]$ sdiff -bs 2015-05-18-a/doc/MPSLogicDocumentation.txt 2015-07-13-a/doc/MPSLogicDocumentation.txt .. title:: MPS Logic 2015-05-18-a | .. title:: MPS Logic 2015-07-13-a > CXI:SC3:VGC:01 Gate Valve Position > ---------------------------------- > ======== = ==================== ==================== ======== > Name A Pockels Cell Mechanical Shutter B > ======== = ==================== ==================== ======== > Not Open F 0 Hz 0 Hz > Open T 120 Hz 120 Hz > ======== = ==================== ==================== ======== > > Where:: > > A = CXI_SC3_VGC_01_OPN_DI_POSITION > > ===================== = = ==================== ============== | ============================== = = ==================== ===== ===================== = = ==================== ============== | ============================== = = ==================== ===== Downstream > Upstream F T 0 Hz | Downstream - Upstream > 50 pC F T 0 Hz Upstream > Downstream T F 0 Hz | Upstream - Downstream > 200 pC T F 0 Hz ===================== = = ==================== ============== | ============================== = = ==================== =====