Refinement of MPS for BSY Reconfiguration: 1. PCAPM1-4 now have single water circuit and PCBSYA/H now BCS. Keep all signals in place until test inputs, then can be removed on next release. Meanwhile, rename inputs: COLL_BSYH_503_FLOW_SW to COLL_BSYH_479_PCAPM_FLOW_SW and rename logic: Flowswitch: COLL BSYH 503 (PCAPM4) to Flowswitch: COLL BSYH 479, 487, 495, 503 (PCAPM1-4) and remove logic: Flowswitch: COLL BSYH 520 (PCBSYH/A) Flowswitch: COLL BSYH 479 (PCAPM1) Flowswitch: COLL BSYH 495 (PCAPM3) Flowswitch: COLL BSYH 487 (PCAPM2) 2. PCBSYA/H PIC now BCS as well, so deleted these inputs and logic: PICM_BSYH_520_LOSS10H PICM_BSYH_520_LOSS10L PICM_BSYH_520_LOSS1H PICM_BSYH_520_LOSS1L PICM_BSYH_520_LOSS30H PICM_BSYH_520_LOSS30L PICM_BSYH_520_LOSS60H PICM_BSYH_520_LOSS60L PICM_BSYH_520_LOSSH PICM_BSYH_520_LOSSL PIC Raw Charge Thresholds: BSYH 520 PCBSYH/A 3. Due to bad LN PIC channels, changed channel mapping of PCAPM1-4 PICs. Name Before After PICM:BSYH:479 (PCAPM1) - PIC Card 1 Ch 6 - PIC Card 1 Ch 1 PICM:BSYH:487 (PCAPM2) - PIC Card 1 Ch 7 - PIC Card 1 Ch 2 PICM:BSYH:495 (PCAPM3) - PIC Card 1 Ch 8 - PIC Card 1 Ch 3 PICM:BSYH:503 (PCAPM4) - PIC Card 2 Ch 2 - PIC Card 1 Ch 5 (In patch.log, their associated logic will show as deleted, but were re-added using logic editor. Logic diff will correctly show this.) 4. Due to threshold changes of unused PIC inputs filling our logs, delete these inputs. They will need to be re-added when rate recovery implemented! Added note to special cases log (including how to re-add). PICM_BSYH_836_LOSS30L PICM_BSYH_836_LOSS30H PICM_BSYH_836_LOSS60H PICM_BSYH_836_LOSS60L PICM_BSYH_836_LOSS1L PICM_BSYH_836_LOSS10L PICM_BSYH_836_LOSS1H PICM_BSYH_836_LOSS10H PICM_BSYH_487_LOSS10L PICM_BSYH_487_LOSS10H PICM_BSYH_762_LOSS60L PICM_BSYH_479_LOSS60H PICM_BSYH_503_LOSS1L PICM_BSYH_487_LOSS30L PICM_BSYH_487_LOSS30H PICM_BSYH_762_LOSS30H PICM_BSYH_479_LOSS10L PICM_BSYH_762_LOSS30L PICM_BSYH_479_LOSS10H PICM_BSYH_503_LOSS60L PICM_BSYH_503_LOSS60H PICM_BSYH_762_LOSS1H PICM_BSYH_487_LOSS60H PICM_BSYH_487_LOSS60L PICM_BSYH_479_LOSS1L PICM_BSYH_479_LOSS1H PICM_BSYH_495_LOSS30L PICM_BSYH_495_LOSS30H PICM_BSYH_762_LOSS1L PICM_BSYH_479_LOSS30L PICM_BSYH_479_LOSS30H PICM_BSYH_495_LOSS1H PICM_BSYH_495_LOSS1L PICM_BSYH_495_LOSS60H PICM_BSYH_487_LOSS1L PICM_BSYH_503_LOSS1H PICM_BSYH_503_LOSS10H PICM_BSYH_495_LOSS60L PICM_BSYH_487_LOSS1H PICM_BSYH_503_LOSS10L PICM_BSYH_503_LOSS30H PICM_BSYH_762_LOSS10H PICM_BSYH_762_LOSS60H PICM_BSYH_503_LOSS30L PICM_BSYH_762_LOSS10L PICM_BSYH_495_LOSS10L PICM_BSYH_495_LOSS10H